Introduction Theoretical background Determination of impedances Determination of capacitances Calculation of line impedances Measurement of line impedances Transformer characteristics
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 1
01.2008
Th. Connor
PTD SE PTI
Characteristics of network elements are necessary for: Network planning Network calculation (e.g. load flow, short circuit) Design of equipment Protection setting (especially distance protection) Analysis of disturbances
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 2
01.2008
Th. Connor
PTD SE PTI
Line characteristics
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 3
01.2008
Th. Connor
PTD SE PTI
Conductor
Resistance
Reactance
Capacitance
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 4
01.2008
Th. Connor
PTD SE PTI
Resistance
Conductor
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 5
01.2008
Th. Connor
PTD SE PTI
Reactance of a loop
Conductors
Current
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 6
01.2008
Th. Connor
PTD SE PTI
Capacitance
Conductor
Diameter of conductor
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 7
01.2008
Th. Connor
PTD SE PTI
Conductor Current
Current
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 8
01.2008
Th. Connor
PTD SE PTI
Conductor Current
Current
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 9
01.2008
Th. Connor
PTD SE PTI
X ext = 0 f ln
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 10
01.2008
Th. Connor
PTD SE PTI
Input data
2rt dab s
DE
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 11
01.2008
Th. Connor
PTD SE PTI
Data
Internal Inductance
1 0 r Li = 8
0 = 1,26 10-3 H/km r = 1 Li = 0,05 mH/km Equivalent depth of return path of earth current E = 100 m f = 50 Hz D E = 930 m
D E = 660
E f
r =
s rt n 180 2 sin n
n 1
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 12
01.2008
Th. Connor
PTD SE PTI
Z M = R M + j XM
1 RM = 0 8
XM = 0 f ln
DE dab
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 13
01.2008
Th. Connor
PTD SE PTI
U R = I R Z S R + I S Z M RS + I T Z M RT U S = I R Z M RS + I S Z S S + I T Z M ST U T = I R Z M RT + I S Z M ST + I T Z S T
ZS = ZM
M
= I
+ (I
+ I T ) Z
1 Z S R + Z ST + Z ST 3 1 = Z M RS + Z M ST + Z M TR 3
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 14
01.2008
Th. Connor
PTD SE PTI
= I
I S + IT = I R U R = I R (Z S Z M )
U R = I R Z1
Z1 = Z S Z M
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 15
01.2008
Th. Connor
PTD SE PTI
Z1 = Z S Z M Z1 = R1 + j X1
R1 = Rint + R ext RM R1 = 1 1 + 0 0 q 8 8 X1 = Xint + X ext XM X1 = L i 1 De De + 0 f ln 0 f ln n r dm
dm = 3 dR,S dS,T dT,R
X1 = 2 f 1 0 r 1 d + 0 f ln m 8 n r
R1 =
Page 16
q
01.2008
dm r + ln X1 = f 0 r 4 n
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Th. Connor
PTD SE PTI
Page 17
01.2008
Th. Connor
PTD SE PTI
29 mm 2 R1 = 150mm 2 km
R 1 = 0 . 19 km
X1 =
X 1 = 0 . 42
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 18
01.2008
Th. Connor
PTD SE PTI
Page 19
01.2008
Th. Connor
PTD SE PTI
29 mm 2 R1 = 70mm 2 km
R 1 = 0 . 41 km
X1 =
X 1 = 0 . 38
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 20
01.2008
Th. Connor
PTD SE PTI
U R = I R Z S R + I S Z M RS + I T Z M RT U S = I R Z M RS + I S Z S S + I T Z M ST U T = I R Z M RT + I S Z M ST + I T Z S T
ZS = ZM
= I
+ (I
+ I T ) Z
1 Z S R + Z ST + Z ST 3 1 = Z M RS + Z M ST + Z M TR 3
M
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 21
01.2008
Th. Connor
PTD SE PTI
= I
+ (I
+ I T ) Z
IR = IS = IT
U R = I R (Z S + 2 Z M )
= I
Z0
Z 0 = Z S + 2 ZM
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 22
01.2008
Th. Connor
PTD SE PTI
Z0 = R 0 + j X 0
R 0 = Rint + R ext + 2 RM R0 = 1 2 + 0 + 0 q 8 8 X0 = Xint + X ext + 2 XM X0 = L i 1 De De + 0 f ln + 2 0 f ln n r dm
dm = 3 dR,S dS,T dT,R
X0 = f 0 r De 3 + 0 f ln 2 4 n r dm
3 R 0 = + 0 q 8
Page 23 01.2008 Th. Connor
r De3 X0 = f 0 4 n + ln r d2 m
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
PTD SE PTI
Page 24
01.2008
Th. Connor
PTD SE PTI
29 mm 2 3 0.00126 s 50 2 + R0 = km s 150mm 2 km 8
R 0 = 0 . 34 km
De = 660
E = 930m f
X0
r De 3 = f 0 4 n + ln r d 2 m
km
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
PTD SE PTI
Page 26
01.2008
Th. Connor
PTD SE PTI
R0 =
29 mm 2 3 0 .00126 s 50 2 R0 = + 70 mm 2 km 8 km s
R 0 = 0 . 56 km
De = 660
E = 930m f
X0
X0
r De 3 = f 0 4 n + ln r d 2 m
50 0.00126 s = s km
1 930 3 + ln 4 0 . 00525 1 . 76 2
X 0 = 1 . 57
km
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 27
01.2008
Th. Connor
PTD SE PTI
Further influences
Earthed conductors (overhead line earth wire; cable shield) Height above ground; line sag Length of conductor twist Skin effect Proximity effect Conductor temperature
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 28
01.2008
Th. Connor
PTD SE PTI
Z0M
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 29
01.2008
Th. Connor
PTD SE PTI
Z=
1pol
1 (Z 0 + Z 0 M ) 2
Z = Z0
X X 1pol
Z = 2 (Z 0 Z 0 M )
1pol
Z = Z 0G
1pol
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 30
01.2008
Th. Connor
PTD SE PTI
Capacitance of lines
2r
Q = C U
h
C = 2 0 r
1 2h ln r
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 31
01.2008
Th. Connor
PTD SE PTI
CM =
CS =
QR = UR CS + (UR US ) CM + (UR UT ) CM
Q R = UR (C S + 2 C M ) (U S + U T ) C M
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 32
01.2008
Th. Connor
PTD SE PTI
U R = U S U T QR = UR (CS + 3 CM ) QR = C S + 3 CM UR
C1 = CS + 3 CM
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 33
01.2008
Th. Connor
PTD SE PTI
CM =
CS =
QR = UR CS + (UR US ) CM + (UR UT ) CM
UR = US = UT
QR = UR CS QR = CS UR
Page 34 01.2008 Th. Connor
C0 = CS
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
PTD SE PTI
C1 =
dTR
2 r 0 d ln r
hS hR hT
C0 =
2 r 0 2h 3 ln 3 r d2
r 0 d h s r
Page 35
relative dielectric constant (in air: r = 1) dielectric constant (8.854 nF/km) conductor distance conductor height line sag radius of conductor
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
01.2008
Th. Connor
PTD SE PTI
Positive and Zero Sequence Capacitance Example Overhead line Given Data
Conductor: Diameter: Frequency: Max. line sag: 70 mm Al d = 10.5 mm f = 50 Hz s=4m
Page 36
01.2008
Th. Connor
PTD SE PTI
1 . 4 m 1 . 4 m 2 . 8 m = 1 . 76 m
2 r 0 2 1 8 . 854 nF / km = 1 . 76 m d ln ln r 0 . 00525 m
C 1 = 9 . 57
nF km
h=
3
h R h S h T 0 .7 s
h = 12 m 0 . 7 4 m = 9 . 2 m
C0 =
C 0 = 4 . 33
nF km
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 37
01.2008
Th. Connor
PTD SE PTI
R1 X1 Ohm/km Ohm/km 400 kV overhead line 110 kV overhead line cable 20 kV overhead line cable 0,03 0,07 0,04 0,31 0,20 0,25 0,41 0,11 0,4 0,13
C1 R0 X0 nF/km Ohm/km Ohm/km 14 10 400 10 300 0,33 0,35 0,5 0,40 0,50 1,44 1,65 0,28 1,50 0,30
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 38
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 39
01.2008
Th. Connor
PTD SE PTI
Calculation of Overhead Line Constants Calculation of electrical parameters of overhead lines with With several three phase systems different voltage levels any number of earth wires (or counterpoise electrodes) The three phase systems to be calculated may also run on different parallel overhead lines.
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 40
01.2008
Th. Connor
PTD SE PTI
Calculation of Line Constants of Cables Calculation of electrical parameters of cables with with concentric screens or metal sheaths or armouring additional common sheaths around a threephase system any number of parallel earthing conductors Several three phase systems have to be considered in one calculation.
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 41
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 42
01.2008
Th. Connor
PTD SE PTI
Presentation of Results
PTD SE NC1-ue1118 24.09.01
Example Example 110 kV overhead line 110 kV overhead line KENNWERTE IN SYMMETRISCHEN KOMPONENTEN KENNWERTE IN SYMMETRISCHEN KOMPONENTEN ====================================== ======================================
E1
E1
Selbstimpedanzen Selbstimpedanzen
2S 1S 2T 2R 1T 1R
C(nF/km) C(nF/km) System 1 System 13,537891 1 13,537891 System 2 System 13,537891 2 13,537891 Koppelimpedanzen Koppelimpedanzen
1S
2S
1T
2R
2T
0,002292 0,002292
0,000552 0,000552
1S 1R
m m m m
2S 2T
Report Report
Page 43 01.2008 Th. Connor
Bild 1
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
PTD SE PTI
Z M = R M + j XM
Calculation with series expression acc. to Carson for earth return consideration
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 44
01.2008
Th. Connor
PTD SE PTI
Aluminium clad steel conductor (only for earth wires) (ACS, St-Al-um, A20SA)
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 45
01.2008
Th. Connor
PTD SE PTI
R_ = v
R_ = v
1 A A rf + rf
R_ v A A
- DC Resistance - Twist factor - resistivity of conductor material - Cross-section of conductor - resistivity of reinforcement material - Cross-section of reinforcement
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 46
01.2008
Th. Connor
PTD SE PTI
Increase of DC-resistance acc. to EN 50182: 7wires 19 wires 37 wires 61 wires 127 wires 1 layer 2 layers 3 layers 4 layers 6 layers 1.11 % 1.68 % 2.03 % 2.36 % 2.75 %
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 47
01.2008
Th. Connor
PTD SE PTI
PTD SE PTI
Calculation:
R =
Page 49
X =
1 f 0 r 4
Th. Connor
R~ > R
X~ < X
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
01.2008
Exact calculation: Series expression by Carson to consider earth current distribution and conductor height above ground
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 50
01.2008
Th. Connor
PTD SE PTI
Matrix Inversion
UE = 0
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 51
01.2008
Th. Connor
PTD SE PTI
Symmetrical components
U1L1
Positive sequence U1 =
U1L2 UL1 U2 L1
1 (U + a UL2+ a UL3) 3 L1
Zero sequence
U0 L1
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 52
01.2008
Th. Connor
PTD SE PTI
Elimination of conductors earthed at both sides (overhead line earth wires, Cable sheaths)
Z 00 Z 01 Z 02
Page 53 01.2008 Th. Connor
Z 20 Z 21 Z 22
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
PTD SE PTI
Partial capacitances
US CRS
UR
CTR
Basic formulae:
Q = UC
QS = (US UR ) CSR + US
QR = UR
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 54
01.2008
Capacitance Coefficients
Partial Capacitances C (Equation)
QS = (US UR ) CSR + US
QR = UR
CRS
(CTR
CRT
QR Q S = Q T
Page 55 01.2008
K RR K SR K TR
Th. Connor
K RS K SS K TS
K RT K ST K TT
UR U S UT
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
QR K RR K RS K RT UR QS = K SR K SS K ST US Q T K TR K TS K TT UT
Potential Coefficients P
Matrix Inversion
UR ZRR U = Z S SR UT Z TR
Page 56 01.2008
ZRS Z SS Z TS
ZRT IR Z ST IS Z TT IT
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Th. Connor
PTD SE PTI
Pii =
2 hi 1 ln 2 ri
P ik =
1 D ln ik 2 d ik
Page 57
01.2008
Th. Connor
PTD SE PTI
Capacitive Coefficients
Inverting
K RR K SR K TR K RS K SS K TS K RT K ST K TT K RE K SE K TE K ER K ES K ET K EE
Partial Capacitances
CRR C RS CRT CRE CSR CSS CST CSE CTR CTS CTT CTE CER CES CET CEE
Inverting
Balancing
Z 00 Z 01 Z 02 Z 20 Z 21 Z 22 K 00 K 10 K 20 K 01 K 11 K 21 K 02 K 12 K 22 C00 C10 C20 C 01 C11 C21 C02 C12 C22
Inverting
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 58
01.2008
Th. Connor
PTD SE PTI
ZW =
R1 + j X1 j C1
ZW R1 X1 C1 Snat
Surge impedance (complex) Resistance in the positive phase-sequence system Reactance in the positive phase-sequence system Angular frequency (2f) Capacitance in the positive phase-sequence system Natural load
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 59
01.2008
Th. Connor
PTD SE PTI
2 Q C = UN C 1
QC UN C1
Page 60
Charging power Rated voltage Angular frequency (2f) Capacitance in the positive phase-sequence system
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
01.2008
Th. Connor
PTD SE PTI
Reduction factor Earth current (current flowing through earth) Zero sequence current during a single phase fault Coupling impedance between phase conductors and earthed conductors Self impedance of earthed conductors
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 61
01.2008
Th. Connor
PTD SE PTI
3I0 = IK1
IK1
IK1 rE
RG
IG
A low reduction factor results in low earth, touch and step voltages low inductive interference in case of earth faults low magnetic fields in case of earth faults
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 62
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 63
01.2008
Th. Connor
PTD SE PTI
IMeas
power cable
W
IMeas
ISheath
IEarth
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 64
01.2008
Th. Connor
PTD SE PTI
earth wire
overhead line
current source
P
W V
I
A
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 65
01.2008
Th. Connor
PTD SE PTI
Volt-Meter Volt-Meter
Page 66
01.2008
Th. Connor
PTD SE PTI
1. Be aware of trapped charges 2. Be aware of induced or influenced voltages 3. Have a clear predefined switching procedure 4. Have a back up switch off strategy 5. Stop work in case of confusion 6. Stop work in case of thunder storm (which may be at the remote end!)
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 67
01.2008
Th. Connor
PTD SE PTI
earth wire
P
W V
I
A
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 68
01.2008
Th. Connor
PTD SE PTI
earth wire
I
A W
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 69
01.2008
Th. Connor
PTD SE PTI
earth wire
P
W V
I
A
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 70
01.2008
Th. Connor
PTD SE PTI
P
W V
I
A
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 71
01.2008
Th. Connor
PTD SE PTI
Short circuiting of test line for Short circuiting of test line for zero sequence measurement zero sequence measurement
Page 72
01.2008
Th. Connor
PTD SE PTI
Zero Sequence Impedance of 220 kV Double Circuit Comparison of Measured and Calculated Values
E1 E1
2T
1T 1S 2S
2S
1S 1R 2R 2R 1R
1T 2T
1T 1R 1S
measured calculated measured calculated __________________________________ __________________________________ R0 0.23 /km 0.20 /km R0 0.23 /km 0.20 /km X0 1.01 /km 1.02 /km X0 1.01 /km 1.02 /km R0M 0.16 /km 0.15 /km R0M 0.16 /km 0.15 /km X0M 0.48 /km 0.49 /km X0M 0.48 /km 0.49 /km
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 73
01.2008
Th. Connor
m m m m
PTD SE PTI
length:
measured calculated measured calculated __________________________________ __________________________________ R1 1.57 1.46 R1 1.57 1.46 X1 7.66 7.80 X1 7.66 7.80 R0 3.63 3.42 R0 3.63 3.42 X0 23.4 22.0 X 23.4 22.0
0
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 74
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 75
01.2008
Th. Connor
PTD SE PTI
current source
IMeas
power cable
W
IMeas
ISheath
IEarth
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 76
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 77
01.2008
Th. Connor
PTD SE PTI
3,0
2,5
measured R0 measured X0
2,0
1,5
1,0
0,5
Cross-section in mm
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 78
01.2008
Th. Connor
PTD SE PTI
1,8 1,6
measured X0
Impedance in
1,4 1,2 1,0 0,8 0,6 0,4 0,2 0,0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
Measuring current in A
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 79
01.2008
Th. Connor
PTD SE PTI
B = 0 H
I H= 2 r
B = r 0 H
XLE
Page 80 01.2008
= B dr I r =0
Th. Connor
De
H
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
PTD SE PTI
Calculation examples
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 81
01.2008
Th. Connor
PTD SE PTI
Conductors: phase wire: max line sag: spec. soil resistivity: frequency: Al 70 4m 50 m 50 Hz
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 82
01.2008
Th. Connor
PTD SE PTI
Influence on Positive Sequence Impedance ?? Zero Sequence Impedance ?? Positive Sequence Capacitance ?? Zero Sequence Capacitance ??
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 83
01.2008
Th. Connor
PTD SE PTI
_______________________________________________________________________ positive sequence resistance positive sequence reactance zero sequence resistance zero sequence reactance R1 X1 R0 X0 0.414 /km 0.381 /km 0.559 /km 1.566 /km 9.640 nF/km 4.332 nF/km 0.414 /km 0.381 /km 0.631 /km 1.419 /km 9.641 nF/km 4.999 nF/km
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 84
01.2008
Th. Connor
PTD SE PTI
Conductors: phase wire: Al/St 230/30 2er bundle earth wire: Al/St 95/55 max. sag: 15 m spec. soil resistivity: frequency : 50 m 50 Hz
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 85
01.2008
Th. Connor
PTD SE PTI
Z11(I,I)
= Z11(II,II) = 0.063 /km + j 0.266 /km = Z22(II,II) = 0.063 /km + j 0.266 /km = Z00(II,II) = 0.223 /km + j 0.970 /km = 0.165 /km + j 0.537 /km 0.020 /km + j 0.020 /km
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
negative sequence impedance Z22(I,I) zero sequence impedance zero sequence coupling imp. all other impedances
Page 86 01.2008
Z00(I,I)
<
PTD SE PTI
Example 2: 110 kV Double Circuit Influence of zero sequence coupling on s.c. results (I) Calculation of single phase short circuit currents Without consideration of zero sequence coupling impedance
0.00 kA 4.18 kA
0.00 kA 21.68 kA
4.18 kA 8.36 kA
wrong
0.00 kA 21.68 kA
3.42 kA 6.83 kA
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 87
01.2008
Th. Connor
PTD SE PTI
Example 2: 110 kV Double Circuit Influence of zero sequence coupling on s.c. results (II) Calculation of single phase short circuit currents Without consideration of zero sequence coupling impedance
2.94 kA
wrong
0.00 kA
0.00 kA 21.68 kA
5.18 kA 5.18 kA
0.00 kA 21.68 kA
5.18 kA 5.18 kA
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 88
01.2008
Th. Connor
PTD SE PTI
Metallic sheath: Cross-Section: Material: Inner Diameter: Arrangement: trefoil spec. Soil Resistivity: 50 m Frequency: 50 Hz
Page 89 01.2008 Th. Connor
50 mm Copper 69 mm 73 mm 84 mm
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Arrangement
0.039
0.120
0.368
0.134
0.196
0.070
0.175
0.365
0.138
0.212
0.031
0.190
0.179
1.673
1.000
0.035
0.183
0.192
0.349
0.189
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 90
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 91
01.2008
Th. Connor
PTD SE PTI
500 mm
secondary cable: Cross-Section: Material: spec. Soil Resistivity: 50 m Frequency: 50 Hz Cable Diameter: 2.5 mm Copper 10 mm
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 92
01.2008
Th. Connor
PTD SE PTI
Example 4: Secondary Cable parallel to 110 kV Cable Induced Voltage in Case of Single Phase Fault Current
Eind = Z C r110 rsec Ik1 l
Eind Zc = induced longitudinal voltage coupling impedance between 110 kV and secondary cable (before elimination of earthed conductors) reduction factor of 110 kV cable sheath reduction factor of secondary cable sheath (no metallic sheath) single phase fault current length of parallel section
0.475 / km
= = = =
Eind =
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 93
01.2008
Th. Connor
PTD SE PTI
Example 4: Secondary Cable parallel to 110 kV Cable Induced Voltage in Case of Single Phase Fault Current
Eind = Z 'C Ik1 l
Eind Zc = induced longitudinal voltage coupling impedance between 110 kV and secondary cable (after elimination of earthed conductors) single phase fault current length of parallel section
0.094 / km
Ik1 l
= =
10 kA 1300 m 1225 V
Eind =
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 94
01.2008
Th. Connor
PTD SE PTI
Example 4: Secondary Cable parallel to 110 kV Cable Induced Voltage in Case of Zero Sequence Current
Eind = Z 00 3 I0 l
Eind Z00 = induced longitudinal voltage coupling impedance between zero-sequence system of 110 kV cable and zero-sequence system of secondary cable single phase fault current length of parallel section
0.092 / km
3 I0 = l = Eind =
10 kA 1300 m 1196 V
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 95
01.2008
Th. Connor
PTD SE PTI
Example 4: Secondary Cable parallel to 110 kV Cable Induced Voltage in Case of Load Current
Eind = 3 Z10 ILoad l
Eind Z10 = 0.0038 / km induced longitudinal voltage coupling impedance between positive-sequence system of 110 kV cable and zero-sequence system of secondary cable ILoad = l = 600 A 1300 m 9V maximum load current length of parallel section
Eind =
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 96
01.2008
Th. Connor
PTD SE PTI
Transformer characteristics
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 97
01.2008
Th. Connor
PTD SE PTI
Transformer types
Two winding Two winding with delta winding Three winding Autotransformer
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 98
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 99
01.2008
Th. Connor
PTD SE PTI
YNy, Yyn Five-limb core: No capability Three-limb core: Neutral rating: 25 % of rated current for1.5 hours Neutral rating: 20 % of rated current for 3 hours YNy(d), Yyn(d) (Delta-winding of 1/3 of rated capacity) Neutral rating: 100 % of rated current Dyn, YNd Neutral rating: 100 % of rated current
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 100
01.2008
Th. Connor
PTD SE PTI
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 101
01.2008
Th. Connor
PTD SE PTI
Small zero sequence system voltage at secondary side during earth fault at high voltage site possible
Zero sequence system voltage at secondary side during earth fault at high voltage site not recommended (detailed investigation required) Negligible zero sequence system voltage at secondary side during earth fault at high voltage site possible without restrictions
For internal use only. / Copyright Siemens AG 2008. All rights reserved.
Page 102
01.2008
Th. Connor
PTD SE PTI