Installation and commissioning handbook

AutroSense 200

116-P-AS200/DE, Rev. A, 2009-08-20

COPYRIGHT This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidiaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security. The information in this publication may be updated without notice. Product names mentioned in this publication may be trademarks. They are used only for identification.

Table of Contents

Table of Contents
1. Introduction.......................................................................5
1.1 1.2 About the Handbook ......................................................................... 5 CE identification ................................................................................ 6

2. Types of detectors ............................................................7


2.1 2.2 2.3 2.4 2.5 Standard detector.............................................................................. 7 Command Module/ Command Module detector ............................... 7 Standard detector interior view ......................................................... 8 Stand alone command module interior view ..................................... 9 Command module detector interior view .......................................... 10

3. Controls and indicators....................................................11


3.1 Types of display ................................................................................ 12

4. Programming the unit.......................................................13


4.1 4.2 4.3 4.4 Engineering Access code.................................................................. 13 Main menu......................................................................................... 14 Navigating through the menus .......................................................... 14 AutroSense 200 functions ................................................................. 15 4.4.1 Time and date (Numeric - Address 000-127) ......................... 15 4.4.2 Alarm levels (Numeric - Address 001-127)............................. 16 4.4.3 Alarm delays (Numeric - Address 001-127) ........................... 16 4.4.4 ClassiFire override (Numeric - Address 001-127) ............... 16 4.4.5 ClassiFire alarm factor (Numeric - Address 001-127) .......... 17 4.4.6 Hour start of day and night operation (Numeric - Address 001-127).................................................................................. 18 4.4.7 LDD Enable (Yes/No - Address 001-127)........................... 18 4.4.8 Start / Stop FastLearn (Yes/No - Address 001-127)............... 18 4.4.9 Auto FastLearn enable / disable (Yes/No - Address 001127) ......................................................................................... 19 4.4.10 Time Delay Override (Numeric - Address 001-127) ............... 19 4.4.11 Cascading alarms (Yes/No - Address 001-127) ..................... 19 4.4.12 Latching alarms (Yes/No - Address 000-127) ........................ 19 4.4.13 Latching faults (Yes/No - Address 000-127)........................... 19 4.4.14 Remote day/night (Yes/No - Address 001-127)...................... 19 4.4.15 Remote reset enable (Yes/No - Address 000-127) ................ 20 4.4.16 Remote Isolate Enable (Yes/No - Address 000-127) ............. 20 4.4.17 Programmed Isolate (Yes/No - Address 000-127) ................. 20 4.4.18 Detector address / Number of detectors (Display Address 000-127) ................................................................... 20 4.4.19 Device Text (Alpha - Address 000-127).................................. 21 4.4.20 Reference device (Numeric - Address 001-127) .................... 21 4.4.21 Reference enable (Yes/No - Address 001-127) ..................... 21 4.4.22 Reference level (Numeric - Address 001-127) ....................... 21 4.4.23 Back-off (Numeric - Address 001-127) ................................... 21 4.4.24 Reset, Test & Isolate button enable/disable (Yes/No Detectors 000-127) ................................................................. 21
Page 1

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS

Table of Contents

4.5

4.4.25 Power save enable (Yes/No - Addresses 001-127) ............... 22 4.4.26 Battery check enable (Yes/No - Address 000-127) ................ 22 4.4.27 Mains check enable (Yes/No - Address 000-127) .................. 22 4.4.28 Aspirator speed (Numeric - Address 001-127) ....................... 22 4.4.29 Flow set-up (Yes/No - Address 001-127) ............................... 23 4.4.30 Airflow monitoring (Display / Numeric - Address 001-127)..... 23 4.4.31 Chart log recording rate (Numeric - Address 000-127) .......... 24 4.4.32 User defined access code (Numeric - Address 000-127)....... 24 4.4.33 BMS protocol (Numeric - CM only) ......................................... 24 4.4.34 Factory default (Yes/No - Address 000 - 127) ........................ 25 4.4.35 Scan devices (Yes/No - CM only)........................................... 25 4.4.36 Looped bus (Yes/No - CM only) ............................................. 25 4.4.37 Poll timeout (Numeric - CM only) ............................................ 25 4.4.38 Call centre (Numeric - CM only) ............................................. 26 4.4.39 Password (Alpha - CM only) ................................................... 26 4.4.40 Pager (Numeric - CM only) ..................................................... 26 4.4.41 Page on fault (Yes/No - CM only) ........................................... 26 4.4.42 Page on alarm (Yes/No - CM only)......................................... 26 4.4.43 View event log (Display - Address 000-127) .......................... 26 4.4.44 Diagnostics (Test - Address 001-127) .................................... 26 4.4.45 Detector read (Display - Address 001-127) ............................ 27 4.4.46 Loop errors (Display) .............................................................. 27 4.4.47 Dust separator condition (Display - Address 001-127) Diagnostic menu ..................................................................... 27 4.4.48 Relay tests (Test - Detector 000-127)..................................... 27 4.4.49 Watchdog trip count (Display)................................................. 27 Menu Map ......................................................................................... 28

5. Sampling Pipe System .....................................................29


5.1 5.2 Pipework............................................................................................ 30 EN 54-20 compliance........................................................................ 30

6. Installation.........................................................................32
6.1 6.2 6.3 6.4 General.............................................................................................. 32 Mechanical installation ...................................................................... 33 Removal and replacement of the detector front cover...................... 34 Electrical installation.......................................................................... 35 6.4.1 Detector terminal block connections....................................... 35 6.4.2 Command Module terminal block connections....................... 36 Power Supply Connections ............................................................... 37 6.5.1 Detector power supply connections........................................ 37 Command Module power supply connections .................................. 37 Command Module internal power supply.......................................... 38 Backup batteries................................................................................ 39 Demonstration Mode ......................................................................... 40

6.5 6.6 6.7 6.8 6.9

7. External Communications................................................41
7.1 BMS protocols on the AutroSense 200 Command Module .............. 41 7.1.1 Text output support (protocol 1).............................................. 41 7.1.2 BACnet support (protocol 2) ................................................... 42 7.1.3 Paging from the Command Module ........................................ 42 7.1.4 Configuring the software ......................................................... 43

8. Event log............................................................................44
Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 2

Table of Contents

9. Interfacing .........................................................................45
9.1 9.2 Setting the detector address ............................................................. 45 9.1.1 Address table .......................................................................... 46 Connecting a detector network to a command module .................... 47 9.2.1 Fault tolerant detector loop configuration ............................... 47 9.2.2 Non-fault tolerant serial configuration ..................................... 48 Connecting AutroSense 200 to an AutroSafe panel ......................... 48 9.3.1 Terminal connections overview - AutroSense 200 ................ 48 9.3.2 Terminal connections I/O unit with SelfVerify BN-320......... 49 9.3.3 Connection between AutroSense 200 and AutroSafe detection loop.......................................................................... 49 9.3.4 Connecting to a PC................................................................. 50

9.3

10. Commissioning .................................................................51


10.1 Commissioning checklist................................................................... 51

11. Maintenance ......................................................................52 12. Troubleshooting................................................................53


12.1 12.2 12.3 12.4 12.5 12.6 Pressing RESET or ISOL. button has no effect ................................ 53 Nuisance alarms occur too often ...................................................... 53 Elevated smoke levels do not generate alarms ................................ 53 Low mean output............................................................................... 53 Detector sensitivity varies over time.................................................. 54 Flow fault errors................................................................................. 54 12.6.1 "Low flow" error messages. .................................................... 54 12.6.2 "High flow" error messages..................................................... 54 12.7 Cannot refit the front cover................................................................ 55 12.8 No display.......................................................................................... 55

13. Error messages.................................................................56 14. Dos and Donts .................................................................57


14.1 Do ................................................................................................ 57 14.2 Dont ................................................................................................ 57

15. AutroSense 200 Specification .........................................58 16. Readers Comments .........................................................59

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 3

Table of Contents

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 4

Introduction

1. Introduction
1.1 About the Handbook
AutroSense 200 is a highly sophisticated next generation of High Sensitivity Aspirating Smoke Detection product that has been designed to ensure that installation and commissioning is as simple as possible, while optimizing performance. AutroSense incorporates a patented artificial intelligence known as ClassiFire , which allows the detector to configure itself to optimum sensitivity, alarm thresholds and minimum nuisance alarms for any environment. ClassiFire intelligence also monitors the detector chamber and dust separator for contamination, continually adjusting the appropriate operating parameters to counteract the negative effects of such contamination. AutroSense is unique in being able to provide a consistent level of protection in a very wide range of environments by continuously making minor adjustments to sensitivity. AutroSense has proven its worth many times by detecting difficult-to-detect slow growth electrical overload incipient fires in difficult environments. This handbook gives information likely to be needed for most installations, but for more detailed information on subjects such as Fresh Air Referencing, please refer to the complete Technical Manual or System Design Guide. This equipment is Class 111 as defined in EN60950 (i.e., this equipment is designed to operate from Safety Extra Low Voltages and does not generate any hazardous voltages). As this equipment is part of a fire detection system, it should be supplied from an approved power supply conforming to EN 54-4. This symbol appears on the main board of the unit and indicates that the board contains static sensitive components. Suitable anti-static precautions must be taken when handling the board, eg. for fuse replacement. This symbol indicates the Safety Earth studs (see sections 2.3 and 2.4). These are for grounding cable screens etc. and should not be connected to 0V or signal earth. This label is located on the laser chamber at the bottom right of the open detector and signifies that the unit is a Class 1 Laser product as specified in IEC 60825-1. The unit incorporates a Class 3B embedded laser, which must not be removed from the detector as retinal damage may result if the laser beam enters the eye.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 5

Introduction

1.2 CE identification

0832 Autronica Fire and Security AS

7483 Trondheim Norway 09 0832-CPD-1190

EN 54-20:2006 Aspirating smoke detectors for fire detection and fire alarm systems for buildings Class A, B and C Technical data: see INF48027 held by the manufacturer

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 6

Types of detectors

2. Types of detectors
2.1 Standard detector
The standard detector is usually used in smaller installations or when central control of multiple detectors is not needed. The standard detector may be fitted with a two-line LCD display for programming the unit. If this display is not fitted then the detector must be programmed via a PC using the remote software or via the RS485 connections using Autronica Fire and Security ASs SenseNET command, control and display software.

2.2 Command Module/ Command Module detector


When multiple detectors are networked together, a Command Module may be used to tie all the detectors together and to provide a central point for programming, running diagnostics and PC and fire panel connection. The Command Module can be mounted either inside a detector as shown or as a standalone unit in its own housing without an aspirator or smoke detection circuitry. If detectors attached to the Command Module are mounted in different fire zones then the Command Module must be mounted in its own housing with separate power supply to comply with BS5839 and EN 54. When a Command Module is mounted inside a detector, the standard detector display is replaced with a dedicated Command Module display. The programming buttons and display on the front of the detector belong to the Command Module. Programming of the Command Module is very similar to programming a detector, the main difference being that the Command Module has extra functions to control all the AutroSense detectors connected to the detector loop.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 7

Types of detectors

2.3 Standard detector interior view

1.Terminal block connections (see section 6.4.1) 2.RS-485 terminal connections (see section 6.4) 3.24VDC power supply connections (see section 6.5) 4.1A 5 x 20 mm T-type protection fuse 5.Detector address DIP switch (see section 9.1) 6.Front-panel display-connector 7.Filter-removal tab (see section 11) 8.RS-232 serial port (see section 9.5) 9.Safety earth studs (see section 6.5)

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 8

Types of detectors

2.4 Stand alone command module interior view

1.Terminal block connections (see section 6.4.2) 2.24VDC power supply connections (see section 6.6) 3.500mA 5 x 20 mm T-type protection fuse 4.Internal power supply (see section 6.7) 5.Standby batteries (see section 6.8) 6.RS-232 serial port 7.Safety earth studs (see section 6.5) 8.Front panel display connectors

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 9

Types of detectors

2.5 Command module detector interior view

1.Detector CPU board (see section ) 2.Command module CPU board (see section) 3.Command module display connection 4.Detectio display connection

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 10

Controls and indicators

3. Controls and indicators


Standard detector

Command module detector

1. Aux, Pre-Alarm, Fire 1 and Fire 2 indicators illuminate when the appropriate alarm level has been reached and the appropriate time delays have expired. On a stand-alone Command Module, the indicators signify an alarm condition from any detector on the communications loop. 2.+ 3. Smoke density indicators. This display is in two sections. The first part, labelled 1 to 10, is the relatively scaled ClassiFire bar graph and changes in steps of half a segment. The second part displays absolutely scaled smoke levels above 1% obscuration per metre (% obs/m) to a maximum of 25% obs/m. The Fire 2 activation level is programmed normally somewhere in this range. These indicators have no function on the standalone Command Module. 4. Status display (if fitted). This display shows all events as they happen in real time and is also used to configure the unit. See Section 4, Programming the unit for more information. 5. RESET. When enabled, pressing <RESET> will clear any latched alarms or faults and set the status display back to its normal operation display. To comply with national standards, detectors are supplied with the RESET function disabled as default. 6. TEST. When enabled, pressing <TEST> will start a lamp test and then the detector will show its nominal operating sensitivity as calculated by the ClassiFire Artificial Intelligence System. 7.ISOL. Pressing <ISOL> will toggle the units isolation state. When isolated, the unit cannot generate any alarms and will signal a fault condition and the text display will show Panel Isolate . To comply with national standards, detectors are supplied with the ISOL button disabled as default. Note: these three buttons can be individually enabled or disabled. The factory default state of the detector is for only the <TEST> button to be enabled and for <RESET> and <ISOL> to be disabled.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 11

Controls and indicators

, , or . These buttons, also referred to in the text as 8. menu buttons are used when programming the unit, which is passcode protected. See section 4, Programming the unit for more information.; Pressing or when not in programming mode (the access code has NOT been entered) will scroll through the detectors event log. See section 8 Event log for more information. 9. Fault. Illuminates when the unit has a fault and a fault signal is being sent to the fire alarm panel. On the Command Module, this also indicates a fault in a detector on the communications loop, or in the loop itself. 10. OK. Illuminates to show normal operation when there are no faults. On the Command Module this means that the Command Module and all detectors on the loop are operating normally.

3.1 Types of display


The standard detector display is a two-line LCD that allows basic programming of the detector. Latching faults Enter Yes/No: Yes The Command Modules display contains more information than that for the standard detector and prompts the user with the action expected by the use of graphic symbols. Latching faults Enter Yes/No:Yes

Press to Change

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 12

Programming the unit

4. Programming the unit


The AutroSense 200 programmer means that programming and configuration of the unit can be performed without opening the detector case. To enter programming mode, press any of the program menu keys.

4.1 Engineering Access code


The Engineering Access code is required to allow the detector parameters to be programmed. The access code is only valid whilst the user is in programming mode. It will need to be entered again if programming mode is exited, if the detector is powered down or if <RESET> is pressed. To enter programming mode, press or . The unit responds by displaying the prompt Access code:0000 asking for the engineering access code. The factory default access code is 0102. To enter the default access code, follow the sequence shown. Note: Pressing has no effect until is pressed to place the cursor under the first digit.

This correctly sets the access code. If an incorrect access code is entered or <RESET> is pressed, the display will show Bad access code. Pressing a menu key will prompt the user again for the correct access code. All of the programmable functions work in a similar manner. The keys move the cursor position through the user-settable digits and step through the available values for the currently selected digit (e.g. 1 - 99, Yes / No etc) pressing enters the displayed figure. Note that it is not possible to save an illegal value, e.g. for the Fire 1 level the maximum valid input is 10 and it would be possible to enter 99, but the programmer will display Bad value to inform you that the entry is invalid and prompt for the value to be re-entered. All programmable parameters have the valid input values range in brackets below the parameter legend on the display. Having edited the value as required, press to select the amended setting.

Pressing when the cursor is on the right most digits has the same effect. If no programming activity is detected for 5 minutes, the detector will display the legend Access timeout and exit-programming mode.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 13

Programming the unit

4.2 Main menu


When the correct access code is entered, the display will show the main menu. The current selection is always shown with an arrow after it. Press to activate the selection. The choices available in the main menu are, in order: Set-up menu: contains all the user-programmable functions Log menu: Allows the user to view historical information such as the event log (time and date of various events such as alarm or fault conditions) Diagnostic menu: Contains a number of detector self-tests Reset: Clears any latched fault readings or exits from a menu item to its parent menu. This has the same effect as pressing the <RESET> button. Isolate: Isolates the detector. This has the same effect as isolating with the <ISOL> button The main menu wraps around so that pressing brings up Exit etc when in Set-up menu

4.3 Navigating through the menus


To navigate through the main menu options, press to navigate through the available choices. The display shows two adjacent items, e.g.

i.e.

selects items lower in the list by effectively scrolling the screen UP,

. and vice versa for The currently selected item is the upper item of the two and is identified by a trailing arrow as shown (for a menu) or a trailing dot (for a menu item or single choice such as Exit). When you have the menu you require, press . This then gives you a choice of the items within the selected menu, e.g. as follows to set the main fire alarm level.

Having entered the Fire 1 level , the selected item indicator steps along to the item below it in the Alarm levels submenu. Either this can be edited as above, or can be used to move to the next choice. Once the last

entry in the sub-menu is reached pressing will move you back up to the Set-up menu . Pressing <RESET> at any time exits programming mode, assuming the <RESET> button is enabled.
Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 14

Programming the unit

Section 4.5 shows the full menu map for the AutroSense 200 , showing the choices available within each menu and submenu. Move the menu pointer progressively towards the left or right of the map as appropriate, and step up/down the choices in the currently selected menu or submenu. Items within sub-menus are sequentially accessed with the button followed by the . button. Values are edited with followed by

4.4 AutroSense 200 functions


A list of all programmable functions follows with an explanation of their usage and the menu and submenu in which they can be found. The location of each sub-menu and function within the main menu is shown in the menu map (section 4.5), which can be folded out to aid visibility. The menu map also shows the valid input range for programming parameters. Each function listed below gives the following information:

Function name and description Type of function. There are five types of function: Yes/No, Numeric, Alpha, (alphanumeric), Display and Test. In the case of Display and Test functions the user cannot amend the parameters shown. The menu and submenu within which the function can be found. Applicability. The legend "CM only" means that the function applies only to the Command Module and is not present in the standard detectors list. The legend "Address 000-127" means that the function may apply to the Command Module and the standard detector (allowable addresses from 000 to 127). Time and date and Relay test are examples of these. All other functions are present in both the standard detector and Command Module function lists and are used to program the detectors. They can either be remotely set on the Command Module, or locally on the detector front panel. These are annotated "Address 001-127" since they do not apply to the Command Module itself.
Where a programmable function on the Command Module applies to a standard detector, the Command module will scan the loop and, if more than one detector is present, will prompt the user for the address of the detector to be programmed. If the function applies to the Command Module, the address "000" should be entered. For other detectors on the loop (including the detector element of a Command Module detector), the value is the same as the address set on the detectors internal DIP switch. If a user enters an address that does not appear on the loop, the error message Bad detector will appear. This message will also appear if the Command module address "000" is entered into a function which only applies to detectors, i.e. anything except "CM only" and "Address 000-127" functions.

4.4.1 Time and date (Numeric - Address 000-127)


Set-up menu > Time and Date It is important that the time and date be set up correctly on the controllers internal calendar/clock because it uses this information to store events in the event log. See section 8, "Event log" for more details. Unless specially ordered, units are supplied with the correct setting for UK time. This is backed up with a rechargeable battery. Later adjustments to the clock setting should not exceed 70 minutes unless a FastLearn is initiated.
Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 15

Programming the unit

4.4.2 Alarm levels (Numeric - Address 001-127)


Set-up menu > Alarm levels The value set in the Pre Alarm level, Fire 1 level and Aux level functions in the Alarm levels submenu is the relatively scaled bar graph level at which the appropriate alarm is initiated on the detector. The Fire 2 level function assigns an absolutely scaled alarm level in % obs/m to the Fire 2 alarm. The Aux level is set by factory default at level 10 which means that this alarm will occur after the Fire 1 alarm. NB: When used with BS systems, the AUX level must be set below the prealarm level to ensure correct pre-alarm function on the panel.

4.4.3 Alarm delays (Numeric - Address 001-127)


Set-up menu > Alarm levels The alarm delay is the number of seconds that an alarm level has to be continuously sensed before the alarm is initiated. Each alarm level has a programmable delay of between 0 and 90 seconds.

4.4.4 ClassiFire override (Numeric - Address 001-127)


Set-up menu > Alarm levels When this function is set to a value other than zero, the shorting together of one of the "Input 3" contacts on the detectors main circuit board by means of volt free contacts will desensitise the detector by moving the alarm levels out by the specified percentage.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 16

Programming the unit

4.4.5 ClassiFire alarm factor (Numeric - Address 001-127)


Set-up menu > Alarm levels The detector sensitivity is set with this entry, which will also affect the probability of nuisance alarms. 0 = high sensitivity, higher probability, 8 = low sensitivity, lower probability. Note: The highest sensitivity setting is suitable for clean, environmentally controlled environments, e.g. semiconductor manufacturing clean rooms where airborne pollutants are kept to an absolute minimum and the least contamination is cause for alarm. Use of this setting in a busy machine shop would lead to relatively frequent nuisance alarms due to the normal variation of atmospheric contamination and a lower sensitivity setting is recommended. It is therefore important that the alarm factor chosen is suitable for the area to be protected. When the appropriate alarm factor for the protected area has been set, nuisance alarms will be reduced to an absolute minimum. The following table gives suggested settings of ClassiFire alarm setting for different locations
Alarm factor 0 1 2 3 4 5 6 7 8 Medium Medium Medium Low Low Sensitivity Extremely High Probability of Nuisance Alarm Once per year Once per 5 years Once per 10 years Once per 50 years Once per 1000 years Once per 5,000 years Once per 10,000 years Once per 20,000 years Suggested Protected Area Semiconductor manufacturing clean room Computer room Non-smoking office Clean factory Warehouse Warehouse with diesel trucks operating Warehouse with diesel trucks operating Warehouse with diesel trucks operating

Once per 100,000 years Warehouse with diesel trucks operating

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 17

Programming the unit

4.4.6 Hour start of day and night operation (Numeric - Address 001-127)
Set-up menu > Alarm levels These values are the times to the nearest hour at which the day/night switching is desired to take place on the detector. Entries are made in 24-hour format, e.g. 19:00 for 7pm. If no day/ night switching is required, then both entries should be set to 00:00. Day and night switching is intended so that the detector may automatically select a different sensitivity when the protected area is unoccupied and fewer contaminants are being produced. ClassiFire automatically detects the change in smoke level after the protected area is left, and if the time at which this happens is within +/ 70 minutes of the programmed switchover time it selects the night-time histogram. Note that if the environment actually becomes more contaminated during the night period for any reason then ClassiFire will adapt to that too, reducing the night-time sensitivity.

4.4.7 LDD Enable (Yes/No - Address 001-127)


Set-up menu > Alarm levels When this function is set to Yes , Laser Dust Discrimination (LDD) increases the response time of the detector slightly, whilst greatly reducing the likelihood of nuisance alarms due to dust ingress. LDD may be disabled in very clean rooms for a slightly faster response to smoke by setting this function to No . Disabling LDD is not recommended for areas other than manufacturing clean rooms, due to the increased probability of nuisance alarms in most other operating environments.

4.4.8 Start / Stop FastLearn (Yes/No - Address 001-127)


Set-up menu > Alarm levels If the detector is in FastLearn mode, setting this function to No will stop the FastLearn process. Using the function in this way is neither recommended nor supported by Autronica Fire and Security AS. Setting this function to Yes will start a FastLearn at any time. The bar graph display on the front of the detector will show a rolling segment display on the front panel for the fifteen minutes that it takes to complete. The text display will initially display the legend FastLearn 15 and will then count down each minute until the FastLearn is complete. It will take a further 24 hours after the FastLearn for full sensitivity to be reached, unless Demonstration Mode has been initiated. It is essential for proper functioning that the detector is not left in Demonstration mode, and that it is allowed to complete the 24-hour learning period. To cancel demo mode, set this function to Yes or power down and restart the detector to initiate FastLearn mode.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 18

Programming the unit

4.4.9 Auto FastLearn enable / disable (Yes/No - Address 001-127)


Set-up menu > Alarm levels As default, this function is set to Yes . This ensures that if the detector is powered down for any reason (e.g. for maintenance or to be moved to a new area), a FastLearn is commenced automatically on power-up. There may be occasions when it is desirable to power down the detector for short periods of time, and it is highly likely that ambient contaminant levels will be the same on power-up. Under these circumstances it may not be desirable that the detector should to go through the whole learning process again. To this end, this function can be set to No before power-down, whereupon it will return to the original settings on power-up.

4.4.10 Time Delay Override (Numeric - Address 001-127)


Set-up menu > Alarm actions If this function is set to Yes , then the detector will ignore any pre-set time delays in the event of an unacceptably rapid increase in smoke density, thereby minimising response time to 'rapid growth' fires. This function would normally only be used where there were long time delays programmed on the alarm levels.

4.4.11 Cascading alarms (Yes/No - Address 001-127)


Set-up menu > Alarm actions Setting this function to Yes means that only when the detectors controller has gone into Pre-Alarm does the controller start counting down the main Fire delay i.e. the time delays on Pre-Alarm and Fire 1 are cumulative. The Aux alarm is not included in the cumulative delay since it may be set to a higher level than either the Pre-Alarm or Fire 1 levels.

4.4.12 Latching alarms (Yes/No - Address 000-127)


Set-up menu > Alarm actions When this function is set to Yes it requires a reset on the front panel or a remote reset to clear an alarm condition. It may be applied to the Command Module or a standard detector.

4.4.13 Latching faults (Yes/No - Address 000-127)


Set-up menu > Alarm actions When this function is set to Yes it requires a reset from the front panel or a remote reset to clear fault indications. This is the factory default setting. It may be applied to the Command Module or a standard detector.

4.4.14 Remote day/night (Yes/No - Address 001-127)


Set-up menu > Alarm actions Setting this function to Yes allows the detector to be manually switched between day and night modes using a remote input.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 19

Programming the unit

4.4.15 Remote reset enable (Yes/No - Address 000-127)


Set-up menu > Alarm actions If remote resetting of the detector or Command Module is required from the host Fire Alarm controller or other external source, this option must be set to Yes .

4.4.16 Remote Isolate Enable (Yes/No - Address 000-127)


Set-up menu > Alarm actions When this function is set to Yes a remote switch may be used to isolate the detector or Command Module.

4.4.17 Programmed Isolate (Yes/No - Address 000-127)


Set-up menu > Alarm actions When set to Yes the controller will not generate alarms and will not indicate a fault condition on any fire panel which is connected, e.g. for use during detector maintenance. The Fault light will be illuminated on the detector or Command Module front panel. The isolated condition will be disabled automatically after 7 days if not manually disabled.

4.4.18 Detector address / Number of detectors (Display - Address 000127)


Set-up menu > Detector In the case of the standard detector, this function displays the current address of the detector as set by the internal DIP switch. On the Command Module, it shows the number of detectors found on the communications loop. This function appears immediately on entering the Detector submenu. The Command Module is always at address 000. When the Command Module unit is fitted in a detector, the detector must have a separate address.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 20

Programming the unit

4.4.19 Device Text (Alpha - Address 000-127)


Set-up menu > Detector This is the default text string displayed on the standard detector or Command Modules LCD display. If desired, this can be altered to any 16 character alphanumeric identification. Thus, for example, the name of the area being protected, or the name of the person responsible for fire safety could be entered. The default device text is AutroSense 200 and the firmware revision level for the standard detector, and Command Module and the firmware revision level for the Command Module.

4.4.20 Reference device (Numeric - Address 001-127)


Set-up menu > Reference Any detector on the loop may use another detector as a fresh air reference. When entering the Reference submenu the user is prompted to first select the address of the detector that will be using the reference, and is then forwarded to this option. To set a detector as a reference detector, enter its address as set by its internal DIP switch into this function.

4.4.21 Reference enable (Yes/No - Address 001-127)


Set-up menu > Reference Setting this function to Yes enables the reference for the detector, if one has previously been allocated in Reference device (1-127)

4.4.22 Reference level (Numeric - Address 001-127)


Set-up menu > Reference The value set with this function is the percentage reference signal subtracted from the detectors signal, if a reference device has been allocated.

4.4.23 Back-off (Numeric - Address 001-127)


Set-up menu > Reference This value is the delay time between a build up of pollution being seen by the reference (if used) and the pollution being seen by the detector.

4.4.24 Reset, Test & Isolate button enable/disable (Yes/No - Detectors 000-127)
Set-up menu > Front panel The front panel buttons may be enabled or disabled individually for the Command Module or standard detectors by setting these functions to Yes or No.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 21

Programming the unit

4.4.25 Power save enable (Yes/No - Addresses 001-127)


Set-up menu > Power checks This function allows the detector to minimise electrical power consumption when operating from stand-by batteries. If enabled, upon mains supply failure the aspirator will reduce speed to minimum, regardless of the user-defined value. This function may be disabled if the minimum aspirator speed increases transport time unacceptably. (See Section 4.4.28, "Aspirator speed"). When in this condition, any smoke reading above 3 bar graph segments on the detector will automatically remove this condition. This function has no effect on the Command Module.

4.4.26 Battery check enable (Yes/No - Address 000-127)


Set-up menu > Power checks If no battery back-up is required, this function should be set to No to avoid Battery fault being displayed on the front panel. If a back-up battery is used, it is recommended that the battery check be enabled. When this is done the user will be prompted for an input terminal to use. The battery fault will be displayed when this contact is open. The default setting is battery fault enabled on "I/P 1". Section 6.4.1 "Detector terminal block connections" and Section 6.4.2 "Command Module terminal block connections" show the input terminal connections for the standard detector and Command Module respectively.

4.4.27 Mains check enable (Yes/No - Address 000-127)


Set-up menu > Power checks The AutroSense 200 detector and Command Module are capable of signalling power supply faults from the power supply where this is equipped with a fault relay (the power supply fitted by default has this feature). The mains check is disabled by default. If the user sets this function to Yes , the user will be prompted with an unassigned input terminal to use (this will normally be "I/P 2" if battery check is already enabled on "I/P 1" - see section 4.4.26, Battery check enable). The mains fault will be displayed when this contact is open.

4.4.28 Aspirator speed (Numeric - Address 001-127)


Set-up menu > Air flow The value entered sets the aspirator in the detector to one of a range of predetermined speeds. The lower the number entered, the lower the airflow rate and the lower the power consumption.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 22

Programming the unit

4.4.29 Flow set-up (Yes/No - Address 001-127)


Set-up menu > Air flow Setting this function to Yes puts the detector into automatic flow limit set-up mode. This takes a few minutes to set the flow fault thresholds based on the current flow rates.

4.4.30 Airflow monitoring (Display / Numeric - Address 001-127)


Set-up menu > Air flow There are separate Sensor pipe , Flow low , Flow high and Flow pipe parameters for each pipe 1 to 4 on the detector. For example, Flow pipe 1 indicates the current airflow rate for pipe 1. Sensor pipe 1 to Sensor pipe 4 are used to enable or disable flow sensing on the specified pipe inlet of the detector. If any pipe inlets are unused, set the relevant flow sensor function for the pipe inlet to No to avoid unwanted flow faults. Flow low is the level below which airflow needs to be reduced to trigger a fault reading (which may indicate a blocked pipe) and Flow high is the level above which airflow needs to increase to trigger a fault indication (which may indicate a loose or damaged inlet pipe). Flow low and Flow high parameters are automatically set up on initial powerup or when Flow set-up is selected (see section 4.4.29). The airflow rates Flow pipe 1 to Flow pipe 4 are for display purposes only and cannot be changed.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 23

Programming the unit

4.4.31 Chart log recording rate (Numeric - Address 000-127)


Set-up menu > Miscellaneous This function controls how frequently the detector and alarm level or flow rates are stored in the standard detector or Command Modules internal chart recorder log. The chart log recording rates are as follows. setting type storage interval time per division on chart log
Setting 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Type Detector output Detector output Detector output Detector output Detector output Detector output Detector output Detector output Detector output Detector output flow recording flow recording flow recording flow recording flow recording flow recording flow recording flow recording flow recording flow recording Storage Interval 1 second 5 seconds 12 seconds 30 seconds 1 minute 2 minutes 5 minutes 10 minutes 20 minutes 50 minutes 1 seconds 5 seconds 12 seconds 30 seconds 1 minutes 2 minutes 5 minutes 10 minutes 20 minutes 50 minutes Time pr. division on the chart log 10 seconds 50 seconds 2 minutes 5 minutes 10 minutes 20 minutes 50 minutes 100 minutes 200 minutes 500 minutes 10 seconds 50 seconds 2 minutes 5 minutes 10 minutes 20 minutes 50 minutes 100 minutes 200 minutes 500 minutes

In the above table the greyed section indicates flow rate recording while the white section indicates detector and alarm level recording. The factory default setting is 8. At the slowest recording rate, one month of data can be recorded. A PC must be connected via the RS-232 port with appropriate software to view the chart recorder log. See section 9.5, "Connecting to a PC"

4.4.32 User defined access code (Numeric - Address 000-127)


Set-up menu > Miscellaneous This function sets the access code that the user has to input in order to modify any of the function values. The default setting is "0102" but for added security it can be changed to any four-digit number desired by the user.

4.4.33 BMS protocol (Numeric - CM only)


Set-up menu > Miscellaneous This function sets the communications protocol for connection to a Building Management System (BMS). Refer to Section 7, "External Communications" for details of these protocols.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 24

Programming the unit

4.4.34 Factory default (Yes/No - Address 000 - 127)


Set-up menu > Miscellaneous On the standard detector, this function has two purposes. If the user has changed any of the detectors functions, this function will display No, indicating that the detector is not at factory default. Setting the function to Yes will restore the detector to the factory default settings. On the Command Module, this setting returns all detectors on the communications loop to their default settings. To default an individual detector in the loop, it is necessary to use the detectors own front panel.

4.4.35 Scan devices (Yes/No - CM only)


Set-up menu > Bus setup Setting this function to Yes causes the Command Module to scan the RS485 data bus for connected detectors. While scanning, the display will show Scanning loop and display a progress bar. When finished, the display will show the number of devices found and the detector addresses in the form. 001 loop 1 Y 002 loop 1 Y 003 loop 1 N Press to change The list "wraps around", so that pressing <<up arrow>> when viewing Address 001 brings up detector number 127. Pressing <<right arrow>> allows the user to remove a detector address from the loop (e.g. during by changing "Y" to "N", or to re-instate a previously removed detector. This is different from the Isolate function in that a fault is still generated on the Command Module. However, this may need to be done if replacing a detector on the loop so that the detectors address becomes available to the replacement. After replacing the detector, the address may be re-enabled.

4.4.36 Looped bus (Yes/No - CM only)


Set-up menu > Bus setup This function is set to Yes to signify that the detectors are connected to the Command Module in a fault tolerant loop configuration (see section 9.2.1 for details). Failing to set this value to Yes for a loop configuration will mean that the fault monitoring advantages of the detector loop are lost. Setting the value to Yes for a non-fault tolerant configuration will generate detector loop errors, so it is important that the appropriate configuration is identified.

4.4.37 Poll timeout (Numeric - CM only)


Set-up menu > Bus setup This is the time, specified in milliseconds, which a device has to respond to a poll from the command module. If no response is received for this time then a Comms fault message is shown for this device on the Command Module display.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 25

Programming the unit

4.4.38 Call centre (Numeric - CM only)


Set-up menu > Pager This is the phone number the modem dials up to send a message. For further details on this and the other functions in the "Pager" submenu, see section 7.1.3, "Paging from the Command Module".

4.4.39 Password (Alpha - CM only)


Set-up menu > Pager This is an optional password used to access the system.

4.4.40 Pager (Numeric - CM only)


Set-up menu > Pager This is the number of the actual pager.

4.4.41 Page on fault (Yes/No - CM only)


Set-up menu > Pager Where a pager has been allocated as above, this function determines whether the pager holder is to be paged when a fault condition is generated by the Command Module.

4.4.42 Page on alarm (Yes/No - CM only)


Set-up menu > Pager Where a pager has been allocated as above, this function determines whether the pager holder is to be paged when a fire alarm condition is generated by the Command Module.

4.4.43 View event log (Display - Address 000-127)


Log menu This function shows the start and stop time and date of events such as FastLearn, alarm condition and error messages. The event log can also be downloaded to a PC via the RS232 serial port. See section 8, "Event log" and section 9.5, "Connecting to a PC" for further details.

4.4.44 Diagnostics (Test - Address 001-127)


Diagnostic menu This function puts the detector into self-test mode. On a Command Module, it tests all detectors on the loop.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 26

Programming the unit

4.4.45 Detector read (Display - Address 001-127)


Diagnostic menu This function displays five values as shown: 009.47%

086 091 087 091


The top value is the detectors current smoke level reading as a percentage of the full-scale value, and the bottom four readings are the current flow rates on each pipe as a percentage of the maximum possible flow rate.

4.4.46 Loop errors (Display)


Diagnostic menu This displays the percentage of loop errors in messages addressed to the detector or Command Module from the detector loop, along with a count of the number of received messages since the last message was received on port 1 and port 2 of the RS485 bus.

4.4.47 Dust separator condition (Display - Address 001-127) Diagnostic menu


The value given at this function is the efficiency rating of the dust separator element in the detector. A new element will give the reading Separator 100.0% in this function. When the efficiency has decreased to 80%, the Fault indicator LED will illuminate and the text display will show Separator renew. If the separator is missing or improperly fitted the display will read Separator change . Fitting a new element will reset this figure to 100%. See section 11, "Maintenance" for further details.

4.4.48 Relay tests (Test - Detector 000-127)


Diagnostic menu This tests the connection of the Command Module or detector to an alarm panel by operating the alarm or fault relay currently selected. Assuming proper connection, this should give appropriate indications on the fire panel. The test runs through the sequence Aux > Pre-Alarm + Fault > Fire 1 + Fault > Fire 2 + Fault > Fault, stepping to the next test on the list when <<ENTER>> is pressed. Although the relevant relays are activated at each stage, the associated lights on the front panel are not illuminated or recorded in the event log.

4.4.49 Watchdog trip count (Display)


Diagnostic menu The watchdog is a circuit built into the controller that restarts the controller in the event of a failure to function properly. This could be as a result of electrical spikes. This count shows the number of interruptions found. The details of each problem can be found in the event log. See 4.4.43, "Event log" and section 8 for further details.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 27

Programming the unit

4.5 Menu Map


4.4.1

4.4.2

4.4.3

4.4.4 4.4.5 4.4.6 4.4.7 4.4.8 4.4.9 4.4.10 4.4.11 4.4.12 4.4.13 4.4.14 4.4.15 4.4.16 4.4.17 4.4.18 4.4.19 4.4.20 4.4.21 4.4.22 4.4.23 4.4.24

4.4.25 4.4.26 4.4.27 4.4.28 4.4.29 4.4.30

4.4.31 4.4.32 4.4.33 4.4.34 4.4.35 4.4.36 4.4.37 4.4.38 4.4.39 4.4.40 4.4.41 4.4.42 4.4.43 4.4.44 4.4.45 4.4.46 4.4.47

4.4.48

4.4.9 3.2 3.2 3.2

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 28

Sampling Pipe System

5. Sampling Pipe System


Aspirating system design is inherently simple. It is often possible to achieve good system performance with very simple installations. There are however a few rules which must be adhered to, and these rules are equally applicable to all aspirating systems which operate on similar principles to AutroSense 200. The information contained in this Handbook is intended as an overview only. For further information please see the complete System Design Guide. 1. Do not expect one detector to achieve good performance if sampling from areas of different air pressure (typically: underfloor air plenums and room spaces or different rooms in air-conditioned areas). This is because the air pressure differences may cause reverse or poor airflow along the sampling pipes. If it is not possible to locate the detector within the protected area it may be necessary to lead an exhaust pipe from the detector exhaust port returning air to the protected area.

2. Always locate the sampling points in a position to which smoke may reasonably be expected to travel. This may sound obvious, but, for example, do not expect ceiling mounted sampling points to operate satisfactorily if air flow prevents the cool smoke from an incipient fire from reaching ceiling level. In this instance it is usually better to locate the sampling pipes directly in the airflow (for example in an air conditioning unit air intake). There is no substitute for carrying out smoke tests prior to installation of pipes to indicate suitable sampling point location. 3. To assist in design and to verify system performance, it is advisable to use the PipeCAD sampling pipe modelling software.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 29

Sampling Pipe System

5.1 Pipework
Sampling pipes should be made from a non-hazardous material and should be clearly identified. a. The ideal internal diameter of sampling pipes is 22mm. Other sizes will often work but will provide different response times. b. Ideally, if the total length of sampling pipe is greater than 50 metres, then multiple pipes should be used. When using multiple sampling pipes, care should be taken to achieve a reasonable degree of balance (say within 10% of airflow) to ensure even suction from the pipes. c. Maximum recommended total sampling pipe length is 200 metres. This is 4 lengths of 50 metres, or 2 lengths of 100 metres. In order for the installation to conform to EN 54-20, pipes must conform at least to EN61386-1 Class 1131. d. Sampling pipes must have capped ends. The end cap should be drilled with a sampling hole normally between 4 or 5mm diameter and free from burrs. Sampling holes should normally be 3-4mm diameter or as calculated by PipeCAD and free from burrs. Each pipe run should not have more than 25 holes. Pipe transit time must not exceed 120 seconds and an approved type of pipe must be used for installations conforming to LPCB requirements. When drilling holes in the sample pipes, or cutting off lengths of pipe, ensure that all swarf and debris is removed from the pipe. This guide holds true for average sampling pipe lengths, but if using long pipes (typically more than 60 metres total), performance may be improved by making the sampling holes near the ends slightly larger than those nearer the detector. Although by no means essential, it must be recommended that if in doubt, PipeCAD be used to ensure that transit times, balance of suction and individual sampling point sensitivity are within desired limits.

5.2 EN 54-20 compliance


The installation must be designed using PipeCAD software, which is provided free on the CD shipped with each detector. After designing the installation including pipes, endcaps and sampling holes, enter the detector type in the Type drop-down list in Options Calculation options. Select Options Calculate or click on the calculator icon. The software will prompt you to choose from Use set hole sizes Best flow balance and Max. permissible transit time. Select the appropriate option and click OK. The results for each pipe (View Results) show calculations for each sampling hole on the pipe with the nearest to the detector at the top of the screen, and the endcap hole at the bottom. Transit time shows the smoke transit time to the detector from each sampling hole. For EN 54-20, this must be below 120 seconds from every hole. The column headed Hole sensitivity % obs/m shows the predicted sensitivity for each hole. For the installation to comply with EN 54-20, depending on the class of installation, each sampling hole must be no less sensitive than the following: Class A: 0.62% obs/m Class B: 1.95% obs/m Class C: 4.65% obs/m

The calculation can be further refined by leaving a working detector in the protected area for at least 24hrs at the intended alarm factor for the installation (this could be done before or after installation). The detector sensitivity can be read from the Sensitivity figure on the histogram screen of the Remote software supplied with each detector. Enter this figure into the PipeCAD calculation under Options Calculation options. Detector sensitivity. Clicking on OK will update the hole sensitivities to the figure expected for the actual layout.
Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 30

Sampling Pipe System

Commissioning and periodic system tests must involve smoke tests to verify that the system performs as expected and enters Fire 1 alarm within 120 seconds from the farthest hole. The detector sensitivity must also be inspected to ensure it has not radically fallen from the installed figure. If it has changed for any reason. the new figure must be re-entered into PipeCAD and the recalculated hole sensitivities must be confirmed to be within the class limits shown above. The settings of a compliant system should be recorded, as it is possible by changing certain programmable functions to make the system non-compliant. If functions are changed, it is recommended that the system is retested if continuing compliance is in any doubt. IMPORTANT NOTE! For EN 54-20 compliant installations the detector requires that the flow thresholds be set manually to 6% of the nominal value, after the FastLearn phase is completed. For example, if the flow rate is 64% after the completion of the FastLearn period, the user must manually set the low flow threshold to 58% and the high flow threshold to 70%.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 31

Installation

6. Installation
6.1 General
Before installing the detector the local standards for installation of aspirating detection systems must be consulted as these standards differ throughout the world. Specific advice for one country may not be applicable to another. The following is a brief set of guidelines on installing detectors. The detector will normally be mounted at a level where there is easy access to the unit for configuration and programming. Unused sampling pipe inlets must be closed. For advice on pipe layout design consult the System Manual and contact Autronica Fire and Security AS Ltd in case of difficulty. The exhaust air from the unit must not be impeded in any way. If the unit is mounted in a different air pressure from where the air is being sampled (for example an air duct), then a pipe must be taken from the exhaust port back to the same air pressure zone as the sampling holes. All signal cables must be screened and must be of a suitable type. The specific type of cable will normally depend upon the local fire regulations. The unit must not be placed in areas where either the temperature or humidity is outside the specified operating range. The unit should not be placed in close proximity to any equipment expected to generate high Radio Frequency levels (such as radio alarms) or units generating high levels of electrical energy (such as large electric motors or generators). Ensure that when the detector is fitted to the wall there is enough space on the right hand side to allow removal and replacement of the filter element (see section 11, Maintenance).

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 32

Installation

6.2 Mechanical installation


The detector body is fitted to a wall-mounting bracket, which is attached to the wall via the mounting holes E as shown below. The detector is then fitted over the mounting stud D and secured inside the detector body with the nut provided for the purpose. For a more discreet layout, it is possible to allow the sampling pipes and cables to enter the detector from the rear (see illustrations below), with the sample pipes and connection cables channelled into the wall. In order to achieve this, sampling holes A and B need to be opened up to a diameter of 30mm to take the sampling pipes (A) and the exhaust pipe (B). The holes C need to be opened up to 25mm diameter in order to take a suitable threaded metal cable gland to provide adequate RF screening for the connection cables. These modifications are shown in dotted lines below. The wall will also need to be suitably prepared to allow the mounting plate to sit flush against the wall. The sampling and exhaust pipes must also extend out of the wall sufficiently to tightly engage in the pipe entries on the rear of the detector as shown. A good starting point would be 25 mm of pipe extending past the back plate. If the detector then sits proud of the bracket, the pipe excess can be trimmed back in small increments until the correct fit is achieved.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 33

Installation

6.3 Removal and replacement of the detector front cover


To remove the front cover, unlock it using the key provided (turn anticlockwise). The bottom of the front cover may then be lifted away from the detector chassis until the top of the cover disengages from the retaining rails at the top of the chassis. The cover may then be lifted away from the detector body to allow internal access. If for any reason the cover has to be completely removed, disengage the ribbon connectors connecting the cover. The ribbon connections are as follows: For the standard detector, a single ribbon cable connected to the detectors "Front Panel" display connector (see section 2.3) For the Command Module detector, a twin ribbon cable, one ribbon connected to the detectors "Front Panel" display connector and marked "DET", and one connected to the Command Module boards "Commander Display" connector and marked "COM" (see sections 2.3 and 2.4). For the standalone Command Module, a twin ribbon cable, one ribbon connected to the "Detector display" connector and marked "DET", and one connected to the "Commander Display" connector and marked "COM" (see section 2.5). When completely removing the front cover it is recommended that the ribbon connectors be removed from the main detector or command module board rather than from the display board. When removing these connectors, ensure that suitable antistatic precautions are taken, e.g. use of antistatic wrist straps, to prevent possible static damage to the units electronics. To refit the front cover, first reconnect the display connectors as described above, and hook the recessed lip at the top of the front cover behind the two retaining guard rails at the top of the chassis like so:

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 34

Installation

6.4 Electrical installation


All electrical (power and signal) connections should be made to the green terminal block inside the detector. Approved screened 4-core cable (e.g. Pirelli FP200 or Pyrotenax MICC type CCM4L1.5 4-core) should be used, and this should enter the detector via metal cable glands. Terminal block connections are as described below.

6.4.1 Detector terminal block connections

* These connections can be used as the input terminals for mains supply and battery fault sensing. When this is the case, the contacts will signal a fault when the contacts are open rather than closed, as fault relays operate in the opposite sense to other relays, i.e. they are open for normal operation. The factory default setting is for supply monitoring on I/P 1.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 35

Installation

6.4.2 Command Module terminal block connections


All electrical (power and signal) connections should be made to the green terminal block inside the detector. Approved screened cable should be used, and this should enter the detector via metal cable glands (provided). Terminal block connections are as described below.

* These connections can be used as the input terminals for mains supply and battery fault sensing. When this is the case, the contacts will signal a fault when the contacts are open rather than closed, as fault relays operate in the opposite sense to other relays, i.e. they are open for normal operation. The factory default setting is for supply monitoring on I/P 1.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 36

Installation

6.5 Power Supply Connections


The detector may be powered by any monitored 24DC power supply of sufficient capacity.

6.5.1 Detector power supply connections

6.6 Command Module power supply connections

*Note: the safety earth connection must be separate and not connected to the GND (0V) connection.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 37

Installation

6.7 Command Module internal power supply


The Command Module may be fitted with an integral power supply and battery charger. The relevant connections are shown below, although these will normally be made when the unit is manufactured. This diagram applies only to Command Modules fitted with an integral supply, although connections to alternative external power supplies will be similar.

1. BAT + and : battery recharge terminals. Bat + (red wire) goes to the positive terminal of the first battery and Bat (black wire) to the negative terminal of the second battery. The negative terminal of the first battery is connected to the positive terminal of the second battery with the yellow cable supplied (see section 6.8, "Backup batteries"). 2. + and : 24V DC supply connecting to the 24VDC and 0V terminals on the Command Module terminal block respectively (see section 6.4.2, "Command module power supply connections"). 3. NC and C : Volt-free fault relay contacts to connect to the "I/P 1" or "I/P 2" terminals on the Command Module terminal block (see section 6.6, "Command module terminal block connections"). Polarity of the wires on these terminals is not important. See section 4.4.27, "Mains check enable" 4. 24V supply fuse: 5 x 20mm 500mA type. 5. Mains supply terminals: This unit should only be powered by mains cable with an earth conductor. Connections are as follows: Neutral (N): Blue wire (White in U.S) Earth ( ): Green and Yellow wire Live (L): Brown wire (Black in U.S) 6. Mains fuse: For 230V operation, a standard 3A, 5 x 20mm mains fuse.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 38

Installation

6.8 Backup batteries


The AutroSense 200 Command Module can be fitted with 2 x 12V, 7 Ah backup batteries to give up to 24 hours operation in the event of mains power failure. The integral battery charger can recharge the batteries to a minimum of 80% capacity within 24 hours of mains reconnection to comply with BS5839 and EN 54 part 4. These fit under the covers immediately beneath the power supply, which are secured with four screws each. The batteries are fitted with the supply terminals to the left hand side as viewed from above, with the cutout on the cover on the same side. To avoid current surge it is recommended that the batteries be fitted with the unit powered up. Batteries are fitted as follows:

Remove the battery covers. The positive terminal on the battery nearest the power supply is connected to the red wire from the power supply "BAT +" terminal (see section 6.5, "Power supply connections"). The negative terminal on the first battery is connected to the positive terminal on the second battery with the yellow battery interconnect wire supplied with the unit. The negative terminal on the second battery is connected to the black wire from the power supply "BAT " terminal. Replace the battery covers after fitting the batteries.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 39

Installation

6.9 Demonstration Mode


In normal use, the detector remains in a reduced sensitivity mode for 24 hours whilst it gathers information about its environment. For purposes of demonstration, e.g. to verify a new installation, this may be disabled by putting the detector into "Demonstration Mode". This special operating mode bypasses the 24-hour learning process and allows the detector to operate at a high sensitivity. To enter Demonstration Mode, the detector must be in FastLearn mode. Whilst FastLearn is running, hold down the front panel <<RESET>> button and whilst holding this, simultaneously press the <<TEST>> and <<ISOL>> buttons. The <<RESET>> and <<ISOL>> buttons do not need to be enabled for this function. When entering Demonstration Mode, the detector front panel LCD display will show the legend Demo mode and the time and date on which this was invoked. Demonstration Mode should only be used for demonstrations. It should not be used as a substitute for normal operation as the alarm settings in this mode are based solely on the sparse data gained during the 15-minute FastLearn period. Over time, this would lead to nuisance alarms due to normal variation in the detectors environment. To cancel Demonstration Mode, invoke a new FastLearn (see section 4.4.9).

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 40

External Communications

7. External Communications

7.1 BMS protocols on the AutroSense 200 Command Module


The Command Module of the AutroSense 200 has a second RS232 port that can be used to send messages to a pager or compatible GSM phone using a modem or to enable connection to a Building Management System (BMS). This comprises the terminals "RS 232 Tx" (transmit), "RS 232 Rx" (receive) and "GND" on the green terminal block inside the unit (see section 6.4.2, Command Module terminal block connections"). Set-up of the Command Module is done using three functions; BMS protocol , Page on fault and Page on alarm (see sections 4.4.33, 4.4.41 and 4.4.42 respectively). When either Page on fault or Page on alarm is enabled the second serial port is reserved exclusively for paging purposes by setting BMS protocol to 0 (TAP paging). Programmable function BMS protocol sets the communications format that is used by the second serial port to communicate with the BMS. Setting BMS protocol to anything other than 0 (Tap paging) will disable functions Page on fault and Page on alarm if they are enabled. BMS Protocol numbers are as follows: Protocol number 0 1 Protocol TAP paging (default) Output only. Events are sent in the same Ascii text format as the internal event log display. This may be used to drive a serial printer if required. BACnet ANSI/ASHRAE standard 135-1995

7.1.1 Text output support (protocol 1)


Text is output at 9600 baud, 8 bits with no parity. When an event occurs the event is printed in the following format: Device ' Command Module' or 'Detector n' Event 'Fire 1' Timedate 10:32 21/03/2001

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 41

External Communications

7.1.2 BACnet support (protocol 2)


The Command Module models the attached detectors as analogue value object types instances 2 to 128. The Command Module status is stored as analogue value instance 1. The Present_Value property of the analogue objects can have one of the following values; 0 = Disabled; 2 = Fault; 32 = Normal; 48 = PreAlarm; 64 = Fire 1; 128 = Fire 2. The device object supports the following Properties: Object_Identifier Object_Name Object_Type System_Status Vendor_Name Vendor_Identifier Model_name Firmware_Revision Application_Software_Version Protocol_Version Protocol_Conformance_Class Protocol_Services_Supported Protocol_Object_Types_Supported Max_APDU_Length_Accepted Segmentation_Supported APDU_Timeout Number_Of_APDU_Retries The following Properties are supported by the analogue value objects: Object_Identifier Object_Name Object_Type Present_Value Status_Flags Event_State Out_Of_Service Units

For further information on BACnet implementation consult the AutroSense 200 Technical Manual.

7.1.3 Paging from the Command Module


The AutroSense 200 Command Module has the facility to send text messages to alphanumeric pagers or SMS messages to some mobile phones. In order to send messages to a pager or similar device a modem must be plugged into the serial port of the Command Module using a suitable cable. The call centres of the pager or SMS-capable phone must support the TAP protocol. In the UK Cellnet phones and BT pagers have this facility, amongst others. Please contact your pager provider to check whether they provide access with the TAP protocol.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 42

External Communications

7.1.4 Configuring the software


No manual configuration of the modem is required as the command module configures the modem automatically on dialling. The command module has three entries used to send messages. They are described below with an example for a BT pager. The functions may be found in Set-up menu. Pager. Call centre This is the phone number the modem dials up to send a message. For the BT EasyReach service this number is 09011130000. Password This is an optional password used to access the system. BT EasyReach does not use the password so leave this entry blank. Pager This is the number of the actual pager. This number will be detailed in the pager or SMS phone documentation.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 43

Event log

8. Event log
An event is defined as operation of any of the front panel controls (when enabled), a signal received from a remote source (e.g. the master controller or PC), a detector level exceeding the Aux., Pre-Alarm, Fire 1 or Fire 2 thresholds or certain commands sent from the remote software or SenseNET. The event log will also store items such as day and night start times, demonstration mode, power fault, detector fault etc. The detector keeps a log of the last 200 events for reference purposes. The event log can be downloaded using a PC that has the remote software installed and is connected to the AutroSense 200s RS 232 port using a serial cable. See section 9.5, Connecting to a PC The event log can also be viewed in the Log menu, which prints out the event log in reverse order i.e. the last recorded event, is printed out first. When the buffer that stores events is full (200 events are stored) and a new event occurs, the oldest event in the buffer is discarded.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 44

Interfacing

9. Interfacing
Because of the flexible nature of the AutroSense 200 detector and the many possible configurations, there are many options for interfacing the detectors to the Fire Panel.

9.1 Setting the detector address


In order to identify itself to the Command Module or fire panel, each detector needs to have a unique address ranging from 1 to 127. The detector address is simply set on the red DIP switch SW1 at the bottom left of the opened detector on the main circuit board. The switch settings are up for 1 and down for 0, and the detector address is set as a 7-bit binary code (switch 8 equates to a value of 128 and so is outside the usable address range). An example is shown below.

The address equates to 01100011 in binary, or (1 x 1) + (1 x 2) + (0 x 4) + (0 x 8) + (0 x 16) + (1 x 32) + (1 x 64) + (0 x 128) = 99 The full range of available addresses and their relevant switch settings are in section 9.1.1 for reference.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 45

Interfacing

9.1.1 Address table


Addresses chosen for detectors do not have to be consecutive or in a given order so long as they are all different.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 46

Interfacing

9.2 Connecting a detector network to a command module


120 ohm screened twisted pair such as Belden 9729 24 AWG should be used for all loop connections. The total length of interconnecting cable between adjacent detectors in the loop should not exceed 1.2 kilometres. The detectors are connected using the RS485 connections on the terminal block (see sections 6.4.1/6.4.2) RS485 1A and 1B are the signal connections for bus 1 and RS485 2A and 2B are the signal connections for bus 2. SCREEN 1 and 2 are the screen connections for buses 1 and 2 respectively. For the command module, the RS485 1A and 1B connections may be thought of as the "Send" lines, and 2A and 2B the "Return" lines. For each detector on the loop, the 1A and 1B connections may be thought of as the lines from the previous detector on the loop and the 2A and 2B connections the lines to the next detector in the loop.

9.2.1 Fault tolerant detector loop configuration

It should be pointed out that loop connections such as above are only needed for a fully fault-tolerant network where full isolation is required between detectors. If all detectors are operating within the same zone a series connection can be used where the output from the command module is taken from the Bus 2 terminals and the last detector in the loop does not require to be connected back to the command module as shown below. In this example, the Command Module will not be able to monitor the network for communications problems but less wiring is required.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 47

Interfacing

9.2.2 Non-fault tolerant serial configuration

9.3 Connecting AutroSense 200 to an AutroSafe panel

9.3.1 Terminal connections overview - AutroSense 200


Remote input 1, 2 and 3 can be used to monitor the power supply, the mains power and the battery. Fire 2, N/O contact, alarm 2 Fire 1, N/O contact, alarm 1 Pre, N/O contact, prealarm Aux, N/O contact, Early Warning (AutroSafe) Fault, N/C contact, fault warning.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 48

Interfacing

9.3.2 Terminal connections I/O unit with SelfVerify BN-320


The BN-320 unit is connected to the detector loop to monitor the AutroSense 200. Terminal connections, BNA-320

1. Pos (+) in 2. Pos (+) out Loop 3. Neg (-) in 4. Neg (-) out 5. (+) input A 6. (-) input A 7. (+) input B 8. (-) input B 9. Normally open 10. Normally closed Relay contact 11. Common

11 10

9.3.3 Connection between AutroSense 200 and AutroSafe detection loop


2k Fault contact Aux. contact N.C. N.O. 910 910 Alarm-contact N.O. 2k

Prealarm contact N.O.

Input B

Input A

AutroSense 200 terminals (see 9.3.1)

NC NO

11 10

BN-320 (see 9.3.2)


1 2 + + 3 4 -

Main loop in

+ _
AutroSafe detection loop

+ _

Main loop out

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 49

Interfacing

9.3.4 Connecting to a PC
To connect a single standalone detector to a PC, connect the PCs serial port directly to the detectors 9-way RS232 port. Connections for this cable are shown below.

When multiple detectors are networked together and a Command Module is being used, the PC connects to the Command Modules 9-way RS232 port. The cable connections are the same as the standard detector cable connections.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 50

Commissioning

10. Commissioning
Before commissioning the detector the local standards of aspirating detection systems must be consulted. These standards differ widely throughout the world and specific advice for the market in one country may not be applicable to another. Commissioning strategy will initially depend upon the environment in which the detector is installed. For instance, the test for a computer room (which should be a relatively clean environment) would be very different from, say, a flourmill, which would probably have a high level of airborne particulate content. A widely accepted standard for computer rooms/EDP areas is British Standard BS6266, equipment overheating at a stage well before combustion. To perform the test electrically overload a 1 metre length of PVC insulated wire of 10/0.1mm gauge for one minute using an appropriate power supply. The detector has two minutes from the end of the wire burn to give an alarm indication. For areas with higher levels of background particulate matter testing methodology would be similar to that of standard point detectors.

10.1 Commissioning checklist


The following brief checklist allows quick set-up of the detector. This procedure will be adequate for most standard installations. Before powering up the detector, visually check all cabling to ensure correct connection. If wire identification is not immediately clear (e.g. by use of different coloured wires or wire identification sleeves) an electrical check should be made. Note: any damage caused by misconnection of the detector is not covered by warranty. Power up the unit and enter the engineering access code. The factory default setting for this is 0102 . See section 4.1 Engineering access code for further details. Enter the Set-up menu and verify that the time and date are correct. (see section 4.4.1) Set an appropriate alarm factor for the protected environment. The detector will perform a FastLearn for the new alarm factor. (see section 4.4.5) Whilst the detector is still in FastLearn mode exit the program mode on the display by pressing <RESET> and set the detector into demonstration mode (see section 6.9). To do this, press and hold down the <RESET> button and simultaneously depress the <TEST> and <ISOL> buttons. The text display will then display Demo mode and the time and date. Wait for the FastLearn to finish (when the legend FastLearn end will appear on the display and the rolling LED indications will finish) and perform any necessary smoke tests, ensuring that the detector reacts appropriately, and let the smoke fully dissipate. Perform another FastLearn, this time not putting the detector into demonstration mode. The detector will generate no alarms during the 15 minute FastLearn period, and after this the detector will operate at a reduced sensitivity for 24 hours whilst ClassiFire acclimatises to the protected environment and sets up appropriate day and night sensitivity settings.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 51

Maintenance

11. Maintenance
AutroSense 200 is a very low maintenance detection system. If required, external cleaning of the unit should be performed using a damp (not wet) cloth. Do not use solvents as these may mar the display bezel. The only part that may require field replacement during servicing is the dust separator assembly. The dust separator condition can be checked using the Dust Separator test in the Diagnostics menu , which gives a percentage reading of dust separator efficiency. When this level drops to 80% the detector will signal a Separator renew fault and the dust separator will need replacing. See section 4.4.38 As dust contained in the dust separators may expose maintenance personnel to a Nuisance Dust hazard as defined by the Control of Substances Hazardous to Health (COSHH), it is strongly recommended that suitable masks and protective clothing be worn when changing filters. Used separators are not intended for re-use and should be disposed of. The following illustration shows how the dust separator is replaced. Make sure to push the separator fully home, or the detector will fail to register its presence, and will continue to indicate Separator change . Open the front cover using the key provided, and locate the dust separator tab at the bottom right of the detector as shown. Remove the black end piece with the removal tab from the filter element and dispose of the element. Fit the new element into the plastic end piece and slide into the detector, the filter should be fitted with the legend IN towards the front of the detector. If the filter is inserted the wrong way up, the detector will not register its presence and the Separator change legend will stay on the display.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 52

Troubleshooting

12. Troubleshooting
12.1 Pressing RESET or ISOL. button has no effect
Check that the controls have been enabled. These functions are disabled by default. See section 4.4.24

12.2 Nuisance alarms occur too often


Check that the ClassiFire alarm factor setting is appropriate for the normal working environment of the protected area. See section 4.4.5 Check that the detector is not in Demonstration mode. This can be

ascertained by viewing the event log (see sections 4.4.43 and 8) and checking that the entry Demo mode has a higher log entry number than the most recent FastLearn start and FastLearn
end entries. Remember that the log entries are in reverse order, with the most recent entries appearing first. If the log shows that Demonstration mode was invoked during the last FastLearn period, start a new FastLearn and allow it to complete its 24-hour cycle. (See section 4.4.8) From the event log (see sections 4.4.43 and 8), check that 24 hours have elapsed since the last FastLearn end entry. Check that day-night switchover times are appropriately set to reflect active and non-active periods (see section 4.4.6).

12.3 Elevated smoke levels do not generate alarms


Check that detector is not Isolated or in FastLearn (if Isolated, the Fault light will be lit) Check that the detector sampling points are in the smoke stream Check that unused sampling pipe ports are closed and that sampling pipes are firmly and cleanly seated in their ports and
undamaged

Check that the correct ClassiFire alarm setting has been set (see section 4.4.5) Check that the detector has either had a 24-hour learning period or that it has been placed in demonstration mode.

12.4 Low mean output


Check that the filter does not require changing (see section 4.4.37) and that the air plenum chamber is clean. The chamber may become clogged when, for example, heavy building activity has occurred near the sampling pipes. If so, the chamber may require cleaning. The detector is not designed to handle large quantities of coarse debris and dust.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 53

Troubleshooting

12.5 Detector sensitivity varies over time


There are many reasons why particle densities may vary, and the ClassiFire system automatically compensates for this in order to replace the likelihood of nuisance alarms due to normal variations in background smoke density. Within limits set by the ClassiFire alarm factor, this is a normal part of the detectors working.

12.6 Flow fault errors


These occur when the airflow rate into the detector exceeds the pre-programmed parameters. As the detector learns the flow setup from the initial installation, this usually means that there has been some change in conditions. A Flow high fault may indicate that a sampling pipe is damaged, and a Flow low fault may indicate that the pipe has been blocked, e.g. by nearby building operations. If the detector input is sampled from one area and the exhaust is in another area with different pressure (e.g. the detector is in a roof space and sampling from an enclosed room), this may lead to flow
faults. In this case it would be necessary to lead a pipe from the exhaust to the protected area to ensure nominal flow.

12.6.1 "Low flow" error messages.


Check that the pipe giving the error is not blocked Check that, if the pipe is unused, the flow sensor for this pipe has been disabled (see section 4.4.30) Check that the low flow fault threshold is not set too high (see section 4.4.30) Consider increasing the aspirator (fan) speed (see section 4.4.28)

12.6.2 "High flow" error messages


Check that the pipe is pushed home into the inlet and is not broken or cracked Check that installed pipework is fitted with an endcap. Autronica Fire and Security AS Ltds PipeCAD pipe modelling software prompts the use of appropriate endcaps. Open bore pipes are not recommended. Check that the high flow fault threshold is not set too low (see section 4.4.30) Consider reducing the aspirator (fan) speed (see section 4.4.28).

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 54

Troubleshooting

12.7 Cannot refit the front cover


Check that the recessed top edge of the cover is securely located behind the locating guardrails on the chassis (see section 6.2). Check that the display ribbon cable is not trapped between the cover and the chassis Check that the key is turned to the unlocked position (anticlockwise)

12.8 No display
Check that the display ribbon cable is securely connected to the detector/ command module main board as appropriate (see section 6.2) and to the display board on the front cover

Check that the display ribbon cable has not been damaged.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 55

Error messages

13. Error messages


The AutroSense 200 text display can provide a wide range of information about the detector. A list of error messages follows with a brief explanation of their meanings. Separator renew : The dust separator requires replacement. See section 11, Maintenance Separator change : The dust separator is missing or improperly fitted. See section 11,Maintenance Bad value , Bad time , Bad date : A value has been input into a function, which is out-side the parameter range for that value. Take note of the range of values allowed (in brackets) and try again. Bad detector : A detector address has been entered which is either outside the allowed range or which is not present on the loop. This may also happen if the user has entered address 000 (command module) for a function which it does not support (e.g. alarm factor) No response : The Command Module has unsuccessfully attempted to read a function value from a connected unit. Check that the unit connected supports this function. 001 x 002 Loop break: There is a break in the communications loop between the detector addresses specified. Check the wiring. Comms fault : The detector has polled a detector and no response has been received after the specified poll timeout value. Bad access code : An incorrect access code has been entered. Enter the correct code. Battery fault : This indicates either that the standby battery has discharged to a predetermined level or that no standby battery is fitted. In the former case, the battery should be replaced and recharged. In the latter case, the battery check should be disabled (see section 4.4.26). It is important that the battery fault be acted upon as soon as noticed, as excessive discharge may cause damage to the battery. The battery fault condition comes on before the battery reaches this portion of the discharge curve. Watchdog reset : This indicates that there has been a power supply fault. If there are frequent power outages it may be advisable to power the unit from a UPS. Detector fault : This indicates that there is a problem with the detector head. This may be due to a number of causes. Refer to the chart readout if this can be downloaded to a PC and note the detector signal level at the time of the fault. When as much information as possible has been determined about the conditions at the time of the error, please contact Autronica Fire and Security AS Ltd.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 56

Dos and Donts

14. Dos and Donts

14.1 Do
Ensure that the ClassiFire alarm factor is appropriately set. Ensure that reference detectors are correctly connected before powering up by use of cable identifiers or electrical continuity checks. Incorrect connection could damage the detector. Ensure that cable of an appropriate approved type is used for interconnection. Place sampling points so that the detector will be able to detect smoke at the earliest opportunity. Ensure that the detector exhaust is in an area with the same atmospheric pressure as the sampling pipes, either by placing the detector physically in the protected area or by leading a pipe from the detector exhaust to the protected area. Ensure that the environment of the protected area is within the environmental operating parameters of the detector (temperature -10 to +60C, (humidity 0-90%, non-condensing). Close unused pipe inlet ports on the detector to ensure optimal operation.

14.2 Dont
Forget to set the appropriate ClassiFire alarm factor for the area to be detected. Forget to set the Detector Address Switches correctly when used in a network. Site detectors in damp or exposed areas. Remove or connect boards when the detector is powered up. Connect internal 0 volt terminals to local earth. Attempt to re-use dust separator cartridges once removed. Attempt to adjust or alter detector settings other than via the userprogrammable functions. In particular, the setting up of the laser is a precision task, and once set up the potentiometers should be left alone. If it is suspected that the laser focus has shifted (e.g. after dropping the detector), it should be returned to Autronica Fire and Security AS for recalibration. Place the detector near high power RF sources. Place the detector so close to other equipment that there is insufficient room to access and change the dust separator. See section 11. Maintenance.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 57

15. AutroSense 200 Specification


SELV rating (EN 60950) Supply Voltage Class III 21.6V 26.4V DC PSU Type: conforming to EN 54-4 Electrical safety complies with BS EN610190-1 427W x 372H x 95D 5.2kg (Detector) 5.3kg (Command Module Detector) 6.2kg (Stand alone Command Module) 10.1kg (Stand alone Command Module + batteries) 10 to +60C 0 -90% Non Condensing BS EN 61010-1 Pollution degree 1 BS EN 61010-1 Installation Cat. II Min = 25% Max = 0.03% FSD 0.0015 %Obs/m Laser light scattering mass detection 0.0003m to 10m 400mA (Detector) 450mA (Stand alone Command Module) 850mA (Command Module Detector) 500mA @ 30V 200 metres total 4 15-25mm 4 (Fire 2, Fire 1, PreAlarm and Aux) 0.0015 - 25% obs/m 26 Greater than 8 years (depending on environment) Greater than 5 years (depending on environment) Greater than 1000 years Front panel or PC via RS232/RS485 RS485 data cable 1.2 km IN, 1.2km OUT IP50 Czech, Dutch, English, Estonian, Finnish, French, German, Hungarian, Italian, Norwegian, Spanish and Swedish

Size (mm) Weight

Operating temperature range Operating humidity range

Sensitivity range (%Obs/m) Maximum sensitivity resolution Detection principle Particle sensitivity range Current consumption

Relay contact rating Maximum sampling pipe length Sampling pipe inlets Sampling pipe internal diameter Alarm levels Bargraph sensitivity range Bargraph segments Chamber service intervals Dust separator replacement intervals Laser lifetime (MTTF) Programming Data bus cable Data bus length IP rating Supported languages on internal programmer

NB! This equipment is only to be used in accordance with this specification. Failure to operate the equipment as specified may cause damage to the unit.

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS Page 58

Readers Comments

16. Readers Comments


Please help us to improve the quality of our documentation by returning your comments on this manual:

Title: Installation and Commissioning Handbook, AutroSense 200 Ref. No.: 116-P-AS200/DE, Rev. A, 2009-08-20 Your information on any inaccuracies or omissions (with page reference):

Please turn the page

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS

Readers Comments

Suggestions for improvements

Thank you! We will investigate your comments promptly. Would you like a written reply? Name: Title: Company: Address: Yes No

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Telephone: Fax: Date:

----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Please send this form to:

Autronica Fire and Security AS N-7483 Trondheim Norway Tel: + 47 73 58 25 00 Fax: + 47 73 58 25 01 www.autronicafire.com

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS

Readers Comments

Installation and commissioning handbook, AutroSense 200 116-P-AS200/DE, Rev. A, 2009-08-20, Autronica Fire and Security AS

Autronica Fire and Security AS is an international company, based in Trondheim, Norway and has a worldwide sales and service network. For more than 40 years Autronicas monitoring systems have been saving lives and preventing catastrophes on land and at sea. Autronica Fire and Securitys most important business area is fire detection & security. Autronica Fire and Security stands for protecting life, environment and property.

Quality Assurance Stringent control throughout Autronica Fire and Security assures the excellence of our products and services. Our quality system conforms to the Quality System Standard NS-EN ISO 9001, and is valid for the following product and service ranges: marketing, sales, design, development, manufacturing, installation and servicing of:

fire alarm and security systems petrochemical, oil and gas instrumentation systems for monitoring and control

In the interest of product improvement, Autronica Fire and Security reserves the right to alter specifications according to current rules and regulations.

Autronica Fire and Security AS Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01. Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99. Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77. Visit Autronica Fire and Security's Web site: www.autronicafire.com