CS51 INTELLIGENT DIGITAL INDICATOR INSTRUCTION

220V AC power supply

ZIBO FEIYAN XIANXING CONTROL TECHNOLOGY CO., LTD

Table of Contents

1. FUNCTION CHARACTERISTIC AND TECHNOLOGY PARAMETER......................................1 2. INSTALLATION CONNECTION .......................................................................................................2 3. SHOW AND OPERATION INSTRUCTION ......................................................................................3

1. FUNCTION CHARACTERISTIC AND TECHNOLOGY PARAMETER 1.1 Function Characteristic 1.1.1. The indicator adopts the technology of Single Chip Micyoco and integrate the technology of automatic steady zero and non-linear management to insure the veracity of the whole metrical scope. 1.1.2. The indicator convenient for use and maintenance by user, hereby adopt 220V.50Hz AC power supply, character man-machine operation interface, set up of protect for drop electricity, set up of password purview, and instruction of input failure(Break off for the input signal show brok; Exceed the upper limit show H.FUL; Exceed the lower show dALo) along with input configuration. 1.1.3. The product is cover with the System of Quality Guarantee ISO9002, so the quality of the product is insured.

1.2 Technology Parameter


1.2.1. Using condition: environment temperature :0-50, relative humidity: 90% 1.2.2. Power supply voltage: AC90V~265V, Power supply frequency: 50~60Hz 1.2.3. Basic error: 0.5%.FS1 bit 1.2.4. Power waste3W Differentiate rate: 0.0010.010.11

1.3 Familiar trouble and Quality Guarantee


1.3.1. Management of familiar trouble 1.3.2. Management of severe disturb When the spot disturb is severe and the management of table 3.1 is invalid, please buy a power purity low pass and connect the indicator of the power entry and the exit of relay down-lead. Table 3.1
Trouble phenomena Trouble reason Spark influence of back-degree contact machine Power disturb The power wire is wrong Quality of the wire is bad Spark influence of back-degree contact machine Management AC circuit connect resistance capacitance spark receiver The wire of indicator power and drive power are detached and away from controllable drive equipment such as silicon, transducer, ect. Check the power wire Connect power wire, add a pure power AC circuit connect resistance capacitance spark receiver, DC circuit connect reverse diode

Show change suddenly

Power board burnout Wrong operation of Relay

Trouble phenomena

Electrified indicator is not bright

Trouble reason The power is not connected or connection is bad The indicator is damaged in the transportation. Input signal is too strong Non pressure input Non connect outside equipment (4 20ma output) Show modified setup is wrong Dont modify to zero before use Wrong choice for scope of indicator Parameter setup is locked The password is lost

Management Connect the indicator power rightly(re. installation and connection) survey the input voltage carefully Contact with supplier Check if pressure exceed the scope Check if the channel is pluged up or pressure is too low. Output connect outside equipment or short connect Set up the value of leave factory (re. measure scope transfer value) Please verify zero again Contact with the supplier Input password according prompt Contact with supplier

LED show brok

The survey value is wrong

Cannot enter corresponding menu Cannot open the lock

1.3.3. Quality Guarantee 1.3.3.1 Under natural condition, the indicator dont need special maintenance, please pay attention to dampproof, dustproof. 1.3.3.2 If the product quality cause the trouble, the indicator will be repaired for free in 12 months from leave factory. 1.3.3.3 One reference manual 1.3.3.4 One production inspection eligible certificate(Guarantee Repair Card)

2. INSTALLATION CONNECTION 2.1 Attentive proceeding 2.1.1 The indicator wire shouldnt go with drive cable side by side. 2.1.2 The indicator power shouldnt derivate from drive power, should use independent power, and pure power is the best. 2.2 Wiring diagram refer to diagram 1 Connection instruction: The power supply is 220VDC.There are 4 alarm input at best, and the quantity is according to the customer need. Every output alarm can be set up to high alarm or low alarm, you can connect wire according the diagram if you use it.

3. SHOW AND OPERATION INSTRUCTION 3.1 Panel show instruction 3.1.1 Indicator exterior chart

3.1.2 Panel show information instruction 3.1.2.1 Panel key-press: Devalue key-press is used to modify setup parameter; increment key-press is used to modify setup parameter; Function key-press (SET) is used to confirm setup parameter. 3.1.2.2 Panel character: AL1AL2AL3AL4 represent Alarm1, Alarm2, Alarm3, Alarm4 respectively. Project unit such as mA, MPa, can be changed into other project unit according to the need. 3.1.2.3 Panel screen: Under natural condition, it show input project measure or trouble state of input signal; parameter setup state show parameter information.

3.2 Parameter setup Setup means: Under work state, press set to enter into setup menu, then press to change different menu setup option. When enter into setup menu, it returns into work state automatically after stopping operation for 40 seconds. If according menu dont appear, it is locked, so you must open the lock before entering setup menu. 3.2.1 Open lock and lock setup 3.2.1.1Open lock MENU SHOW
LOCK SET

OPERATION Enter into open lock menu, press SET to confirm

PARAMETER INSTRUCTION

0 UNL C

Press to input Password :2002 password, press SET to confirm Opening lock is successful

AL..AR SET

3.2.1.2 Lock MENU SHOW


LOCK SET

OPERATION Enter into lock menu, press SET to confirm

PARAMETER INSTRUCTION

YES/NO LOCK

Press to change YES denote lock, NO whether to lock, change denote not lock YES, press SET to confirm

Finish the setup, press SET to return work state


END SET

3.2.2 Measure scope setup MENU SHOW

OPERATION Enter into measure scope setup menu, press SET to confirm

PARAMETER INSTRUCTION

TANg SET

0-10/4-20 STP

Press to choose 0-10 voltage output graduated mark, press SET 4-20 current output to confirm Press to choose decimal place, press SET to confirm Pressto set up zero Set up zero value value, press SET to confirm Press to set up full Set up full degree value, degree value, press SET to confirm Finish the setup, press SET confirm to return work state.

0.000 POIN

xxxx Rg.00

xxxx Rg.FS

EDN SET

3.2.3 Communication setup MENU SHOW


CONU SET xxx C.ADR

OPERATION Enter into Communication setup menu, press SET to confirm Pressto set up communication address code, press SET to confirm Press to set up communication baud rate, press SET to confirm Finish the setup, press SET confirm to return work state.

PARAMETER INSTRUCTION

xxxx C.BPS EDN SET

3.2.4Verify zero operation MENU SHOW OPERATION Enter into Verify zero menu, press SET to confirm Press to choose YES whether Verify zero , press NO SET to confirm press SET to Verify zero Verify zero Not Verify zero PARAMETER INSTRUCTION

IN.00 SET

YES/NO IN.00

xxxx IN.00

EDN SET

Finish Verify zero, press SET confirm to return work state.

3.2.5 Verify operation MENU SHOW OPERATION Enter into verify menu, press SET to confirm PARAMETER INSTRUCTION

CAL SET

YES/NO CAL

Press to choose YES whether Verify, press SET NO to confirm

Verify Not Verify

xxxx CAL.0

Press SET or verify, Verify zero press cancel verify

xxxx CAL.F

Press SET or verify, Verify full degree press cancel verify

EDN SET

Finish Verify, press SET confirm to return work state.

3.2.6 High or low alarm setup MENU SHOW OPERATION Enter into alarm point menu of upper and lower limit, press SET to confirm Press set up the first alarm point value, press SET to confirm Press to set up the LOAL low alarm point high and low alarm point, HIAL high alarm point press SET to confirm Press set up the second alarm point value, press SET to confirm Press to set up the LOAL low alarm point high and low alarm point, HIAL high alarm point press SET to confirm Press set up the third alarm point value, press SET to confirm Press to set up the LOAL low alarm point high and low alarm point, HIAL high alarm point press SET to confirm Pressset up the fourth alarm point value, press SET to confirm Press to set up the LOAL low alarm point high and low alarm point, HIAL high alarm point press SET to confirm Pressto set up dispersion, press SET to confirm Press SET confirm return work state. to PARAMETER INSTRUCTION

AL.AR SET

xxxx ALR.1

LOAL/HIAL

ALT.1

xxxx ALR.2

LOAL/HIAL

ALT.2

xxxx ALR.3

LOAL/HIAL

ALT.3

xxxx ALR.4

LOAL/HIAL

ALT.4

xxxx HYST

END SET