INSTRUCTION MANUAL
FOR
MND11
NEUTRAL DISPLACEMENT
RELAY
2
CONTENTS
SECTION I Introduction 3
SECTION II Installation 3
2.1 Preliminary Check
2.2 Mounting & Wiring
2.3 Settings
2.4 Operation
SECTION III Maintenance 10
3.1 Handling Precautions
3.2 Control Card Removal Procedure
SECTION IV Specifications 11
Trip Time Characteristics
Mounting details
Wiring Diagram
Warranty ............... 16
3
SECTION I
Introduction
Neutral Displacement Relay Model MND11 is an electronic micro
controller based single-phase voltage relay. It is suitable Ior Earth
Fault Protection oI Generators earthed through a neutral earthing
transIormer and where immunity to operation on third harmonic
Irequency is essential, capacitor bank protection etc.
It`s micro controller based design oIIers a wide range oI Iield
selectable Trip-Time Characteristics. It incorporates a separate
instantaneous alarm relay and accepts very wide auxiliary supply
range.
MND11 is designed Ior Ilush mounting. It is very compact in size,
which results in saving oI panel space. Its Drawout construction
makes installation and maintenance very easy.
SECTION II
4
Installation
2.1 Preliminary Check
Relay packing consists oI
1. Relay
2. Mounting clamp
3. Instruction Manual
4. Test certiIicate
Check the relay Ior any obvious damage, iI Iound inIorm
nearest L & T oIIice or dealer. Check the Auxiliary Supply
Range (This is indicated on a label Iixed to one side oI the
relay which also shows external wiring details) Ior which the
unit has been conIigured. Ensure that this speciIication is as
per your order.
Remove the protective cover Irom the terminal block by
removing two screws. Connect suitable auxiliary supply
between terminals 2 and 3. Switch ON the supply, all LEDs
will blink once and then Power On` LED, Norm Inv 5.7s`
LED should glow, this indicates that Trip Time
Characteristics selected is Normal Inverse-5.7 Sec. which is a
deIault Iactory setting (or as per the order).
Now remove the transparent cover Irom the Iront panel.
Press Test` button Ior Iew seconds (1 sec.),Trip` LED will
glow Ior a short while and output relays will also operate.
Trip` LED will go OFF and output relay will release
automatically aIter a Iixed duration oI approximately 1sec,
even iI Test` button is kept pressed. Once Trip` LED goes
OFF, all LEDs will blink once, and then relay will return to
Normal mode i.e. only Power On`, 'Norm Inv 5.7s' LED
will glow. This completes the preliminary check. Disconnect
the auxiliary supply and Iix the protective covers back on
Iront panel and terminal block.
2.2 Mounting and Wiring:
5
MND11 is designed Ior Ilush mounting on the panel. ReIer
Fig. 6 Ior panel cutout dimensions and space required
behind the panel. Fix the mounting clamps supplied along
with, to the top and bottom side oI the relay. Insert the
relay through the panel cutout and hold it Iirmly against
the panel. Tighten the screws on the mounting bracket.
Wire the relay terminals as shown in the wiring diagram
(ReIer Fig. 7). Relay terminals are suitable Ior 2.5 mm.sq
lugs. Fix the protective cover back on the terminal block
with the help oI two screws aIter completing the wiring.
NOTE:
1. ENSURE PROPER EARTH CONNECTION TO
THE RELAY
2. IT IS RECOMMENDED TO REMOVE THE
RELAY FROM THE PANEL DURING
TRANSPORTATION.
2.3 Settings
User has to set Iour diIIerent parameters while installing
the Relay, they are:
Selection oI Trip Time Characteristics
Selection oI Fault voltage level Ior Trip Relay
Selection oI Alarm level Ior Alarm Relay
Selection oI Trip Time using Time Multiplier setting
(TMS)
2.3.1 Selection of Trip Time Characteristics
6
MND11 oIIers Iollowing Trip Time Characteristics
Normal Inverse
DeIinite Time - Three Ranges: 1sec, 10sec, 100sec.
MND11 is dispatched with deIault Iactory setting oI
Normal Inverse 5.7sec` (or as per your order). II diIIerent
characteristic is required, Iollow the steps given below to
change the setting.
Remove the control card Irom the relay. (ReIer Section
3.2.1 Ior detailed procedure)
Set the DIP Switch on the control card to give required
characteristic. Table 1 shows DIP Switch positions Ior
diIIerent Trip Time Characteristics.
Fix the control card back in the relay enclosure. (ReIer
section 3.2.2 Ior detailed procedure).
Table 1: Showing the DIP Switch position for various
Trip time characteristic curves.
TRIP TIME
CHARACTERISTICS
S/W
1
S/W
2
S/W
3
S/W
4
Normal Inverse (5.7sec) OFF OFF OFF OFF
DeIinite Time (1sec) OFF OFF ON OFF
DeIinite Time (10sec) OFF ON OFF OFF
DeIinite Time (100sec) OFF ON ON OFF
O N
7
Fig. 1.Shows the DIP Switch setting Ior
DeIinite Time (1 sec) characteristic.
1 2 3 4
O F F
NOTE:
1. HANDLE THE CONTROL CARD CAREFULLY
TAKING ANTISTATIC PRECAUTIONS. REFER
SECTION III FOR HANDLING PRECAUTIONS.
2. OPERATE THE SWITCH WITH A SMALL
POINTED OB1ECT SUCH AS SMALL SCREW
DRIVER. DO NOT APPLY EXCESSIVE FORCE TO
OPERATE THE SWITCH.
3. DO NOT TOUCH OTHER COMPONENTS ON
THE CARD.
2.3.2 Setting the Fault Voltage Level
Fault Voltage level Vs is expressed as percentage oI PT
rating Vn (Vn110V). MND11 oIIers Voltage setting oI 2
to 32 oI Vn in steps oI 2. i.e. it can be set to
2,4,...,32 oI Vn. This setting is done using Iirst block
oI 4 DIP switches Irom top on the Iront panel (ReIer Fig.
2). Desired Iault level can be set by switching ON one or
more oI these switches, each one having its deIinite weight
a. The Iault level is then the sum oI a Iixed base plus the
addition oI all the terms a, corresponding to the switches
in ON position, multiplied by PT rating Vn. This is
8
indicated by the Iollowing Iormula on the Iront panel,
Vs 0.02 ( 1 + a ) Vn
Where,
Vs Set Voltage Level (Fault Voltage Level) in Volts.
Vn Rated PT Voltage (110 Volts).
a Weight oI switch in ON position .
(ReIer Table 2 Ior switch position details)
II required Fault Level
setting is 12 oI Vn.
(i.e. Vs Vn x 0.12).
Then to achieve this, put
switch no. 4 and 2 with a
1 and 4 respectively in
ON position. This will
make a in above
Iormula as 5 and Vs
0.12 Vn. i.e. 12, the absolute Iault level becomes 13.2 volts (110
x 0.12). Whenever voltage crosses this Iault level relay picks up
and trips according to selected trip time characteristics.
The trip time oI the Trip Relay (R1) will depend upon Trip Time
Characteristic selected and magnitude oI Iault in case oI Normal
Inverse Trip Time Characteristics or DeIinite Time in case oI
DeIinite Time Characteristics.
1 8
2 O 4
3 N 2 a
4 1
Fig. 2: shows DIP
switch to Set Vs
9
Table 2: DIP switch setting for various fault voltages
Vs ( of Vn)
SETTING
RANGE
S/W 1 S/W 2 S/W 3 S/W 4
2 OFF OFF OFF OFF
4 OFF OFF OFF ON
6 OFF OFF ON OFF
8 OFF OFF ON ON
10 OFF ON OFF OFF
12 OFF ON OFF ON
14 OFF ON ON OFF
16 OFF ON ON ON
18 ON OFF OFF OFF
20 ON OFF OFF ON
22 ON OFF ON OFF
24 ON OFF ON ON
26 ON ON OFF OFF
28 ON ON OFF ON
30 ON ON ON OFF
32 ON ON ON ON
10
2.3.3 Setting Alarm Level for Alarm Relay
MND11 has one
additional Alarm
Voltage setting. It can
be set Irom 2 to 32 oI
Vn in steps oI 2.
Alarm
level is set using the middle block oI
Iour DIP Switches on the Iront panel
as shown in Fig. 3. The method oI
setting is same as that Ior setting
Normal Fault Level` explained above.
Alarm level Vis is given by Iormula,
Vis 0.02 x ( 1 + b ) Vn
Where,
Vis Alarm level (Alarm Voltage Level) in Volts.
Vn Rated PT Voltage (110 Volts).
b Weight oI switches in ON position.
For e.g. Alarm is required iI Iault voltage is more than
20 oI the rated voltage. Then to achieve this, put switch
no. 4 and 1 with b 1 and 8 respectively in ON position.
This makes b in above Iormula as 9 and Vis 0.20Vn
i.e. 20. Alarm will occur when Iault voltage reaches a
level oI 20 oI Vn i.e. when absolute voltage
becomes 22 volts.
NOTE: Alarm Relay is R2 Relay, which cannot
be used Ior Tripping.
Trip Relay is R1 Relay.
1 8
2 O 4
3 N 2
4 1
Fig. 3: shows DIP
switch to Set Vis
11
2.3.4 Time Multiplier Setting (TMS)
This Ieature oIIers various
options oI Trip Time Ior a
selected Trip Time
Characteristic. The Time
Multiplication Factor can be
set Irom 0.1 to 1.6 in steps oI
0.1 using the last block oI Iour
DIP switches shown in Fig. 4.
This means in case oI Inverse
Trip Time Characteristics,
MND11 oIIers 16 parallel
curves corresponding to each
Time Multiplier Setting and in
case oI DeIinite Trip Time
mode, the trip time can be set Irom 100msec to 160secs. The
method oI setting this switch is similar to one explained above.
Trip time T is given by Iormula,
T k ( 0.1 + t )
Where,
T Trip time in seconds.
K Constant depending on Trip Time Characteristic
selected. Value oI k Ior diIIerent characteristics are as indicated
below.
Normal Inverse when Iault is 10Vn ....... 5.7
DeIinite Time ( 1.0sec ) ....... 1.0
DeIinite Time ( 10 sec ) ....... 10.0
DeIinite Time ( 100sec) ........ 100.0
t Weight oI switch in ON position
1 0.80
2 O 0.40
3 N 0.20
4 0.10
Fig. 4: shows DIP
switch to Set TMS
12
For e.g. Time Multiplier required is 1, then to achieve this
put switch no. 1 and 4 to ON position. This will make t
0.9 to give Time Multiplying Factor 1. In case oI Inverse
Trip Time Characteristics, trip time k` corresponds to trip
time obtained Irom the curve. In the same example iI
DeIinite Time 1sec range is selected then relay will trip
aIter 1sec as soon as voltage exceeds Iault level.
2.4 OPERATION
During normal operation the Power On LED, and one oI
the Iour yellow LEDs indicating the selected Trip Time
Characteristic will glow. Whenever voltage exceeds set
value Vs, Trip LED will start blinking at a Irequency oI
1sec and will continue till Trip Relay operates. It will stop
blinking and will remain permanently ON as soon as relay
trips. Whenever voltage exceeds set value Vis, and
remains Ior 5 sec. Alarm Relay operates. The output relay
contacts are selI reset` type (i.e. they will reset as soon as
Iault gets cleared) whereas Trip LED has to be reset
manually. Press Reset` button to reset the trip LED
indication (it is not possible to reset Trip indication unless
Iault is cleared). Reset button is used only Ior resetting the
trip indication, it does not aIIect the Iault detection
Iunction oI Relay (i.e. even iI operator Iorgets to reset the
Trip indication, MND11 will still detect the Iault iI occurs
and trips, only thing is in such case, Trip LED will not
blink when it senses the Iault).
NOTE: Alarm Indication is by blinking the Trip LED
at slower rate compared to the normal blinking during
Fault.
13
SECTION III -
MAINTENANCE
MND11 does not need any routine maintenance during its
working liIe. It does not contain any user serviceable /
replaceable parts. In case oI Iailure oI the relay inIorm nearest
L & T oIIice.
3.1 Handling Precautions
MND11 has draw out construction hence in case oI Iailure
control card alone can be removed and replaced without
removing the complete relay Irom the panel. The control card
contains electronic components sensitive to static electrical
charge, hence should be handled very careIully taking
precautions such that human body is at Ground` potential
beIore removing the control card Irom the relay, packing the
card using Anti Static` material and not touching any
components on the card. It is advisable to handle the control
card by holding the Iront panel. This will reduce the chances oI
electronic components getting damaged during handling.
3.2 Control Card Removal Procedure
3.2.1 To remove the control card, follow the
instructions given below
Remove the transparent cover Irom the Iront panel by removing
two screws.
Turn the two screws located at top right and bottom leIt corner
oI the panel through 90(clockwise / anti-clockwise).
Pull the panel out using the handle provided on the Iront panel.
14
Take care the position oI polarizing strip Iixed at backside oI 64
pin Connector (This polarizing strip will prevent, control card oI
diIIerent models oI relays going into wrong box)
3.2.2 To install the control card, follow the
instructions given below
Observe that locking pin on two screws at top and bottom
corners oI the panel is in horizontal direction. (This pin is
on the back side oI the panel)
Engage the card careIully between two card guides
mounted in the relay enclosure.
Push the card in Iully till Iront panel locks in with click
sound. Turn the two screws at top and bottom corners oI
the Iront panel through 90 (clockwise / anti-clockwise)
Pull the handle to ensure that card has locked in properly.
Fix the transparent cover back with two screws.
Whenever control card is removed and installed back,
Iollow the test procedure given in section 2.1 beIore
commissioning it.
15
SECTION IV
SPECIFICATIONS
Ratings
Voltage Vn 110 VAC
Frequency 50 Hz 2.5 Hz
Aux. Power
Supply
24V to 110V AC / DC 15
OR
95V to 240V AC / DC 15
Settings
Fault Voltage Vs 2 to 32 oI Vn in steps oI 2
Alarm voltage
Vis
2 to 32 oI Vn in steps oI 2
TimeMultiplier
TMS
0.1 to 1.6 in steps oI 0.1
Operating
Characteristics
Trip Characteristic Normal Inverse
DeIinite Time
Trip Time Normal Inverse
( T 5.7 sec 10 times Vs and
TMS1 )
DeIinite Time
(1, 10, 100secs).
Alarm 5 secs (Iixed)
Reset Time Less than 50 msecs
Pickup voltage Same as set voltage, Vs
Reset Voltage 90 to 95 oI Pickup voltage
Accuracy As per Error Class 5, IS:3231:1987
(Timing accuracy : 5 or 20msecs
whichever is more)
16
Third Harmonic
Rejection
26 dB
Overload Capacity PT 300Volts
Burden
On Potential TransIormer Less than 0.25VA
On Aux. Power Supply Less than 7VA
Operation Indicators Trip time characteristic selected
Power ON status
Trip status
Contacts
ConIiguration 2 independent relays (selI reset type)
One Relay with single C/O contacts
One Relay with single N/O contact
Contact Rating
Rated Voltage 250VAC / 30VDC
Rated Current 5Amps
Rated Breaking Capacity 2000VA / 240W (Resistive)
Insulation
As per IS 3231:1987 / IEC 60255-5
2kV AC RMS, 50Hz Ior 1 min.
across independent circuits.
1kV AC RMS, 50Hz Ior 1 min.
across open contacts.
High Freq. Disturbance
As per IS 8686:1977 / IEC 60255-22-
1, Class III
1MHz, 1kV peak across input circuits
and 1MHz, 2.5kV peak between
independent circuits
17
Impulse Withstand As per IEC 60255-5,5 kV (CM), 2KV
(DM),1.2/50 secs
Electrical
Fast Transient
As per IEC 61000-4-4, Level III
2kV, 5kHz
Ring Wave As per IEC 61000-4-12, Level 4
4kV (CM), 2kV (DM)
Surge Immunity As per IEC 61000-4-5, Level 4
4kV (CM), 2kV (DM)
Voltage Dips &
interrupts
As per IEC 61000-4-11, 200 msecs
Electrostatic Discharge As per IEC 61000-4-2, Level 3
Air Discharge 8kV
Vibration & Shock As per IEC 255-21- 1/2 Class 1
Dry Heat As per IEC 600 68-2-2, 70 C, 96 hrs.
Damp Heat As per IEC 600 68-2-3, 93
40 C, 56 days.
Temperature
Operating 0C to 60C
Storage -10C to 70C
Case Draw Out
Weight Approx. 1kg
Dimension (L x B x H )
in mm.
224 x 71 x 158
18
Fig. 5: Time Voltage Characteristics (At TMS1)
For Trip time at TMS other than 1
Trip time (Trip time at TMS1) x TMS
19
Fig. 6: Overall Size & Panel Cutout Details
Fig. 7 : Wiring Diagram
20
WARRANTY
LARSEN & TOUBRO LIMITED (L&T) warrants that the
Protective Relay Model MND11 will meet L&T`s published
speciIications and will be Iree Irom deIects in workmanship and
materials Ior a period oI 12 months Irom the date oI shipment.
L&T`s obligation under this warranty shall be limited to servicing
or replacing deIective parts provided that notice oI such deIects
and satisIactory prooI thereoI is given to L&T by its customer
within the warranty period.
This warranty does not cover any deIect in the product caused by
accident, misuse, neglect, alteration, modiIication or substitution
oI any oI the components or parts, or any attempt at internal
adjustments by unauthorized service personnel.
Under no circumstances shall L&T be liable Ior any consequential
or resulting injury or Ior loss, damage or expense, directly or
indirectly, arising Irom the use oI this product.
The Ioregoing warranty is in lieu oI all other warranties, express
or implied and is the sole and exclusive remedy Ior any claim
arising Irom the deIect in the product.
21
Manufactured by
LARSEN & TOUBRO LIMITED,
KIADB INDUSTRIAL AREA,
HEBBAL, HOOTAGALLY,
MYSORE - 570 018.
INDIA.
Visit us @ www.Intmps.com
www.Intebg.com
www.Iarsentoubro.com
Reach us @ mpsinfo@myw.Itindia.com
Part No. 4D060084 Rev. 1