DIgSILENT Pacific User Conference 2007

DETAILED MODELLING OF HV SINGLE CORE CABLE SYSTEMS USING POWERFACTORY ..to determine armour and screen
current magnitudes under varying conditions of installation Peter Willis, DIgSILENT Pacific
Perth Office
DIgSILENT Pacific PowerFactory Training

SYSTEM MODELLING

Cable Systems Frequency domain model Traditionally represented by equivalent PI representation for Z1 and Z0 impedances. Impedance data is typically taken from manufacturers catalogues

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING Multi-Core Cables

For multi-core cables, manufacturer data is used. Here we see a non-SWA OLEX cable.

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING Multi-Core Cables

..and here we see the same OLEX cable with SWA.

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING Single-Core Cables


For single core cables systems, the overall impedance is based on assumptions on the installation and connection of screens.

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING Single-Core Cables

For single core cables systems, the overall impedance must be calculated from the geometric arrangement of the conductors, as is the requirement for overhead lines. These complexity of these calculations are also compounded by the multiple insulation and conducting layers of single core cable profiles, however the new PowerFactory cable system tools encapsulates this.

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING Single-Core Cables

Unlike multi-core cables, the individual phase screens are not in electrical contact along the cable length, so there can be substantial induced currents flowing when screens are bonded together and earthed at the cable terminations. If the screens are not bonded at both ends, induced currents do not flow however screen voltages become elevated. All this requires engineering assessment, hence new tools were developed (first supported in Version 13.1) to model single phase cable systems.

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING New PowerFactory Objects

There are three new PowerFactory objects in the model: TypCab Single Phase cable profile TypCabsys Geometric arrangement of cables making up the circuits in a cable system ElmCabsys The link between cable system type and the line elements in the active network Overhead line equivalents: TypCon Arial Conductor Type TypTow Tower geometry Type ElmTow Tower Element

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING TypCab

DIgSILENT Pacific PowerFactory Training

CABLE SYSTEM MODELLING TypCabsys

DIgSILENT Pacific PowerFactory Training

10

CABLE SYSTEM MODELLING ElmCabsys

DIgSILENT Pacific PowerFactory Training

11

CABLE SYSTEM MODELLING ElmCabsys (EMT Tab)

DIgSILENT Pacific PowerFactory Training

12

GRAPHICS

DIgSILENT Pacific PowerFactory Training

13

GRAPHICS

DIgSILENT Pacific PowerFactory Training

14

WHY DO IT ???

Why do we need this tool? Customers asked for this Screen and armour currents need to be quantified so connections & equipment can be correctly dimensioned. Where screens or armours are lifted, the standing voltage can be determined under load and fault conditions. Screen-cross bonding distances can be examined Effect of cascading failures can be examined
DIgSILENT Pacific PowerFactory Training

15

CASE STUDY Real Failure

Example of how the Cabsys model was used to quantify screen currents following screen joint failure in 6.6kV generator incomer and how the geometric orientation of cable grouping in the field affects current imbalance across all conducting layers.

DIgSILENT Pacific PowerFactory Training

16

CASE STUDY

Oil & Gas Installation - VESDA System detected fault but damage was already done - Generator outage - Very significant $AUD in production losses

DIgSILENT Pacific PowerFactory Training

17

SINGLE CORE CABLE SYSTEMS

3 Main Areas of Concern - Orientation & configuration


multiple cable runs, rotating phases within trefoil groups..

- Circulating currents
armour and screen bonding and earthing, termination kits..

- Eddy Currents
steel pipes, transit boxes, gland plates..

DIgSILENT Pacific PowerFactory Training

18

SCREEN CURRENTS Cable Damage due to Hot Joints

DIgSILENT Pacific PowerFactory Training

19

SCREEN CURRENTS Cable Damage due to Hot Joints (cont)

DIgSILENT Pacific PowerFactory Training

20

10

Cable Profile

DIgSILENT Pacific PowerFactory Training

21

Joint Instructions

DIgSILENT Pacific PowerFactory Training

22

11

Constant Force Springs

DIgSILENT Pacific PowerFactory Training

23

Final outer layer of joint

DIgSILENT Pacific PowerFactory Training

24

12

What should have been done

DIgSILENT Pacific PowerFactory Training

25

Thermography Effect of screen connection

Screens Connected

Screens Lifted on end

DIgSILENT Pacific PowerFactory Training

26

13

Thermography Effect of screen connection

PowerFactory Study cases: Effect of parallel circuits Lack of transposition Phase positions in trefoil groups Effect of high resistance joints leading to cascading failure Lifting screens and isolating armour-clamping glands

Screens Connected

DIgSILENT Pacific PowerFactory Training

27

Repaired Joints

DIgSILENT Pacific PowerFactory Training

28

14

SUMMARY

Modelling Cable Systems A tool that has a time and a place Can also be used to offline to valid Z1/Z0 in conventional models. Has associated line objects for each conducting path (sheath, armour, conductor) of each circuit. Going forward.. Easier to visualise with composite branch line graphic (V14 feature) Has some application for EPR calculation, whereby ground impedance is modelled from external tool (CDEGS). Feedback welcomealways

DIgSILENT Pacific PowerFactory Training

29

15