Gas & Vapor Sizing

Required Sizing Data Fluid Properties


Fluid State Molecular Weight Specific Gravity Liquid (referred to water) Gas (referred to air) Ratio of specific heats (k) Compressibility factor, Z O2 gas 32.00

1.39 1 kPag C

Operating Conditions
Operating Pressure (max) Operating Temperature (max) Max. Allowable Working Press

Relieving Conditions
Required Relieviing Capacity Gas or Vapor (kg/hr), W Gas or Vapor (Sm3/min) Liquid (Liter/min) Set Pressure Allowable Overpressure % Superimposed Backpressure (specify constant or variable) Built-Up Back Pressure Relieving Temperature 45.79 kg/hr

70 kPag 10% kPag kPag 30 C

Calculation
10% Overpressure (kg/hr) Tag A= A= C K Kb M 0.0466 sq inch 30.06 mm2 355.37 0.975 1 31.999 1190-PSV-060

P1 T W Z

178 kPa 303 Kelvin 45.787 Kg/hr 1

Min Eff Discharge Area Coeff from ratio of spec heats. effective coeff of discharge. 0,975 Capacity correction due to back pressure Mol weight Relieving pressure = Set Pressure + overpressure + atm pressure. temp of fluid at valve inlet Required relieving capacity, kg/hr Compressibility factor

Critical Temperature Critical Pressure

154.94 K 5042.7 kPaa

Reduced Temp Reduced Press

2.0 0.0

=to 315 if unknow

With superimposed constant back press exceding critical, Table T7-1. for bellows or Series BP with superimposed or variable back pressure, f Table T7-7 or =to 315 if unknow

fig F7-1. Use 1 if unknown

Gas & Vapor Sizing


Required Sizing Data Fluid Properties
Fluid State Molecular Weight Specific Gravity Liquid (referred to water) Gas (referred to air) Ratio of specific heats (k) Compressibility factor, Z Helium gas 4

1.6703 1 kPag C

Operating Conditions
Operating Pressure (max) Operating Temperature (max) Max. Allowable Working Press

Relieving Conditions
Required Relieviing Capacity Gas or Vapor (kg/hr), W Gas or Vapor (Sm3/min) Liquid (Liter/min) Set Pressure kPag Allowable Overpressure % Superimposed Backpressure (specify constant or variable) Built-Up Back Pressure (kPag) Relieving Temperature C 17.63

70 kPag 10% kPag kPag 30 C

Calculation
10% Overpressure (kg/hr) Tag A= A= C K Kb M 0.0477 sq inch 30.79 mm2 377.89 0.975 1 4 1190-PSV-082

P1 T W Z

178 kPa 303 Kelvin 17.63 Kg/hr 1

Min Eff Discharge Area Coeff from ratio of spec heats. effective coeff of discharge. 0,975 Capacity correction due to back pressure Mol weight Relieving pressure = Set Pressure + overpressure + atm pressure. temp of fluid at valve inlet Required relieving capacity, kg/hr Compressibility factor

Critical Temperature Critical Pressure

5.2 K 228.99 kPaa

Reduced Temp Reduced Press

58.3 0.8

=to 315 if unknow

With superimposed constant back press exceding critical, Table T7-1. for bellows or Series BP with superimposed or variable back pressure, f Table T7-7 or =to 315 if unknow

fig F7-1. Use 1 if unknown

Gas & Vapor Sizing


Required Sizing Data Fluid Properties
Fluid State Specific Gravity Liquid (referred to water) Gas (referred to air) Ratio of specific heats (k) Compressibility factor, Z

Operating Conditions
Operating Pressure (Kpag maximum) Operating Temperature (C maximum) Max. Allowable Working Pressure

Relieving Conditions
Required Relieveing Capacity Gas or Vapor (kg/hr), W Gas or Vapor (Sm3/min) Liquid (Liter/min) Set Pressure kPag Allowable Overpressure % Superimposed Backpressure (kPag) (specify constant or variable) Built-Up Back Pressure (kPag) Relieving Temperature C

Calculation
10% Overpressure (kg/hr)

A= C K Kb M

255.16 344 0.975 1 19

P1 T W Z

1696 323 2675 1

Natural Gas

2675

1450 kPag 10%

50 C

Min Eff Discharge Area Coeff from ratio of spec heats. effective coeff of discharge. 0,975 Capacity correction due to back pressure Mol weight Relieving pressure = Set Pressure + overpressure + atm pressure. temp of fluid at valve inlet Required relieving capacity, kg/hr Compressibility factor

mm2 Table T7-7 or =to 315 if unknow

With superimposed constant back press exceding critical, Table T7-1. for bell Table T7-7 or =to 315 if unknow

kPa Kelvin Kg/hr fig F7-1. Use 1 if unknown

onstant back press exceding critical, Table T7-1. for bellows or Series BP with superimposed or variable back pressure, fig F7-2. For pilot, page 7--4

able back pressure, fig F7-2. For pilot, page 7--4

Gas & Vapor Sizing


Required Sizing Data Fluid Properties
Fluid State Molecular Weight Specific Gravity Liquid (referred to water) Gas (referred to air) Ratio of specific heats (k) Compressibility factor, Z O2 gas 32.00

1.40 1 kPag C

Operating Conditions
Operating Pressure (max) Operating Temperature (max) Max. Allowable Working Press

Relieving Conditions
Required Relieviing Capacity Gas or Vapor (kg/hr), W Gas or Vapor (Sm3/min) Liquid (Liter/min) Set Pressure Allowable Overpressure % Superimposed Backpressure (specify constant or variable) Built-Up Back Pressure Relieving Temperature 45.67 kg/hr

70 kPag 10% kPag kPag 30 C

Calculation
10% Overpressure (kg/hr) Tag A= A= C K Kb M 0.0612 sq inch 39.49 mm2 356.06 0.739 1 31.999 1190-PSV-060

P1 T W Z

178 kPa 303 Kelvin 45.669 Kg/hr 1

Min Eff Discharge Area Coeff from ratio of spec heats. effective coeff of discharge. 0,975 Capacity correction due to back pressure Mol weight Relieving pressure = Set Pressure + overpressure + atm pressure. temp of fluid at valve inlet Required relieving capacity, kg/hr Compressibility factor

Critical Temperature Critical Pressure

154.94 K 5042.7 kPaa

Reduced Temp Reduced Press

2.0 0.0

=to 315 if unknow

With superimposed constant back press exceding critical, Table T7-1. for bellows or Series BP with superimposed or variable back pressure, f Table T7-7 or =to 315 if unknow

fig F7-1. Use 1 if unknown

Gas & Vapor Sizing


Required Sizing Data Fluid Properties
Fluid State Molecular Weight Specific Gravity Liquid (referred to water) Gas (referred to air) Ratio of specific heats (k) Compressibility factor, Z Helium gas 4

1.63 1 kPag C

Operating Conditions
Operating Pressure (max) Operating Temperature (max) Max. Allowable Working Press

Relieving Conditions
Required Relieviing Capacity Gas or Vapor (kg/hr), W Gas or Vapor (Sm3/min) Liquid (Liter/min) Set Pressure kPag Allowable Overpressure % Superimposed Backpressure (specify constant or variable) Built-Up Back Pressure (kPag) Relieving Temperature C 17.63

70 kPag 10% kPag kPag 30 C

Calculation
10% Overpressure (kg/hr) Tag A= A= C K Kb M 0.0481 sq inch 31.04 mm2 374.85 0.975 1 4 1190-PSV-082

P1 T W Z

178 kPa 303 Kelvin 17.63 Kg/hr 1

Min Eff Discharge Area Coeff from ratio of spec heats. effective coeff of discharge. 0,975 Capacity correction due to back pressure Mol weight Relieving pressure = Set Pressure + overpressure + atm pressure. temp of fluid at valve inlet Required relieving capacity, kg/hr Compressibility factor

Critical Temperature Critical Pressure

5.2 K 228.99 kPaa

Reduced Temp Reduced Press

58.3 0.8

=to 315 if unknow

With superimposed constant back press exceding critical, Table T7-1. for bellows or Series BP with superimposed or variable back pressure, f Table T7-7 or =to 315 if unknow

fig F7-1. Use 1 if unknown