Q.9.8. Compare the advantages Batteries.


ANS.
-,

and disadvantages

of Lead-Acid & Alkaline

LEAD-ACID

.ALKALINE i) Develops 1.2 volt per cell,so 20 cells are required for normal 24 volt supply. Costly bus has the longer life of 15 years compared to 5yrs of lead-acid. . Preferred for emergency power supply being ore suited to long periods of idle operation on stand-by. It is regarded as more reliable. Electrolyte is aqueous KOH solution, evolve gas. continuously during charging. Hydrogen and Oxygen gases are evolved during changing and vented through non-return values. Gases are highly explosive and . alkaline in nature. Evolution of gas causes water . loss during changing, which should be tapped up. Can be operated continuously at 45C, without loss of life. Sparking and naked film are prohibited in the battery room.

i)

Develops nominal 2 volt per cell, demanding. 12 cells battery for the normal 24 volt supply. Less expensive in initial cost and more efficient. . Preferred for regular recycling duty of essential power supplies operating on charge / discharge basis. Electrolyte IS dilute H2S04, evolves gas when nearing the top of the changing. Hydrogen & Oxygen evolved due to breakdown of water. rented to allow gases gases are chemical Cells are to escape.

ii)

ii)

iii)

iii)

iv)

iv)

v)

v)

vi)

Gases are highly explosive and acidic in nature. Evolution of gas causes water loss which should be topped up with distilled water. Life starts reducing considerably above 25C. Care must be taken not to cause sparks or produce naked flame, when inspecting batteries.

vi)

vii)

vii)

viii)

viii) ix)

ix)

201

Q.9.9. Give detailed report on Battery Checking, Maintenance What is Voltage Drop Test?
ANS.

And Safety.

1. Cell tops must be kept clean, dry, vents clear, and free of deposits. Terminal connections should be tight, free of corrosion and coated with petroleum jetty to prevent corrosion. 2. Electrolyte levels should be checked and topped up with distilled water to cover the plates, by about 1/8" higher than the top end of plates. 3. Checking of specific gravity or relative density by hydrometerFor a lead-acid battery, the relative density varies between 1.275-1.285 at 15C for a fully charged cell, to about 1.11 when fully discharged. The terminal voltage to be measured when supplying load. The terminal voltage of an idle cell is likely to be high giving false indication of a fully charged cell. The terminal voltage of a fully charged cell is about 2.0 volt on load falling to 1.75 V when fully discharged. For alkaline battery, the relative density does not change, however, as the cell ages, relative density gradually falls. A new cell will have a relative density of 1.190 at 15C, whereas when it falls to 1.145, it indicates chemical deterioration has occurred and electrolyte should be renewed or battery replaced. The terminal voltage of a fully charged alkaline cell is about 1.2 V falling to 1.09 V when fully discharged. 4. The relative density readings vary with temperature and correction must be made to arrive at a correct value. The figures specified above are for idea electrolyte at 15C. Actual readings should be corrected by adding 0.007 for each 10C rise above 15C and subtracting 0.007 for each 10C fall below 15C. . 5. The end charge is indicated when the terminal voltage of an alkaline cell levels out at 1.7 volt and for lead acid cell, it is about 2.6 volt. 6. Lead acid cells should be charged until gassing freely and charging should continue for a further period until the charging voltage per cell levels out at 2.6 V. Overcharging causes overheating, distortion of cell plates and consequent discharging of plate active materials. Lead acid cells suffer self- discharge due to spontaneous chemical reaction even when not in use, so they must be maintained on a trickle charge, a low rate of charging.
.. I

7. Alkaline cells should be charged at the recommended rate until gassing freely and the charging voltage per cell rises to about 1.7 V. Alkaline cells are able to retain their charge for a considerable period and do not suffer, self-discharge, except at high temp. Periodically, alkaline batteries should be given' a sort refresher charge by special arrangement or through shore facility. Lead acid cells best o~erating temp. range is 15 -:-25C and maximum recommended operating temp. is 45 C. If the temp. goes above, the battery condition deteriorates and battery life decreases for Alkaline cells, the operating range is 15 - 45C. At low temp., battery condition does not deteriorate but capacity decreases.

202
9. The battery capacity is rated in terms of its discharge current at the 10 hour rate. A 250 Amp-Hr battery can supply 25 Amp for 10 hours. Voltage drop test- The condition of a battery is checked by allowing it to discharge at the recommended rate for 10 hrs (i.e. for a 150 Amp-Hr battery, @15Amp for 10 Hrs.), the voltage drop should not exceed 12.5% of the nominal system voltage after the test The voltage variation should be within the limits of + 10% and -12.5% from fully charged to completion of full performance on load of the prescribed duty. Safety1. Wearing of protective clothing e.g. rubber apron, rubber gloves and eye goggles, while checking and topping up of batteries. 2. No naked light, flame should be taken into battery room because of hydrogen gas evolving from cells which can cause inflammable mixture. Insulated spanners and non-metallic water jugs should be used to prevent sparking and short circuiting of cells. 3. Ventilation fan should be kept on. 4. First aid treatment - H2S04 splashes should be washed off with fresh water and potassium hydroxide should be washed off with boracic powder or boracic acid solution. .

Q.9.10. a) State how short circuit may develop in a lead-acid battery and how this can be detected. b) State five causes of why the rated capacity of a lead-acid battery may fall off in service. Ans. a) Causes of short circuit i) If a metallic or conducting material falls across the positive & negative terminals of a cell.

ii) If the battery container or the electrolyte gets heated up above the maximum recommended temperature, then the electrolyte resistance (internal resistance of the battery) decreases as it has negative temp. coefficient of resistance, and the cell plates get shorted causing high current flow and further rise irr temperature. For every 10C rise in temp,the battery life reduced to half of its remaining life ..
'"

iii) If the separation plates deteriorates and the +ve and -ve plates comes in contact with each other. iv) If contaminated topping up. water of higher conductivity is added in place of distilled water

v) .Accumulation of sulphate at the bottom can also short the plates.

High current flow, heat generation and high temp. of battery container and buckling of plates are the indications of short circuit. b)i)Since the discharge action of the battery depends on the surface area of the plates dipped in electrolyte, the capacity reduces if the electrolyte level falls off and does not immerse the plates fully .. ii) A fall in relative density ofthe electrolyte reduces the rated capacity of the battery. iii) Corrosion or oxide formation at the battery terminals causes reduction in rated capacity. IV) Temperature below lSoC or in the minus range causes fall in rated capacity. v) Due to long use and ageing of the plates, the active material deteriorates or sometimes covered with sulphate deposition.

204 Q.9.11. Draw the Wiring Diagram For Two Sets of. Batteries On A ChargeDischarge Basis Br 4-Pole Change-Over Switch While One Is Being Charged The Other Is On Stand-By Duty.