Professional Documents
Culture Documents
Standard Features
Time Delay Normal to Emergency
(0-1800 sec) (Default 5 sec)
Help
Pressing the Help pushbutton in any function mode will bring up display messages, explanations and prompts to assist the operator.
Engine Test
Pressing the Engine Test pushbutton twice initiates the engine test cycle.
Lamp Test
Pressing the Lamp Test pushbutton lights all LEDs and then displays ATC-300 controller information.
Bypass TDNE/TDEN
Pressing Step and Help/Lamp Test pushbuttons simultaneously reduces programmed time delays to zero to simplify test procedures.
LCD-Based Display
The LCD based display is a backlit, 2-line, 16 character display. Displayed information includes: Source Voltages and frequency Time/date stamp Historical data Programming and set point information
Password entry
PASSWORD 0300
Operation
Diesel controllers monitor the fire sprinkler system pressure by means of a pressure transducer or pressure switch. Upon detecting a drop in system pressure, a start signal is sent to the engine, initiating its crank cycle.
Starting
The starting process can be initiated by causes other than a pressure drop, such as a signal from a Deluge Valve opening or a Remote Start pushbutton being activated.
Each engine shall be provided with two storage battery units. At 4.5 degrees C (45 deg. F) - each battery unit shall have twice the capacity sufficient to maintain the cranking speed recommended by the engine manufacturer.
Crank Cycle
The attempt to start cycle shall be of a 3 minute duration - consisting of 15 seconds of cranking followed by 15 seconds of rest, in six consecutive cycles.
Stopping
Manual Electric Shutdown Manual shutdown shall be accomplished by either of the following:
Operation of the main switch inside the controller. Operation of a stop button on the outside of the controller enclosure. (The stop button shall cause the engine to shutdown through the automatic circuits only if all starting causes have been returned to normal - ie: pressure rises above the start point.) The controller then returns to the full automatic position.
Stopping
There are several conditions that must be met for this method to be used. All starting causes must have returned to normal for a minimum of 30 minutes.
Stopping
The engine cannot shut down automatically on high water temp. or low oil pressure when any starting cause exists. If no other starting cause exists during engine test, shutdown is permitted.
Battery Chargers
There are several stringent requirements that Battery Chargers must meet under this section of the NFPA Code. This is an extensive section of the code - without properly charged batteries, there is no way to start the engine - hence . NO FIRE PROTECTION
Battery Chargers
Chargers shall be specifically listed for fire pump service. The rectifier shall be a semiconductor type.
Battery Chargers
When the battery (lead-acid type) reaches a fully charged condition, the charger must reduce the charging rate to less than 500mA. The charger must charge the battery without damaging it - and must restore the battery to 100% of reserve capacity within 24 hours.
Overpressure Requirements
Due to the introduction of pressure limiting drivers there is a requirement for the controller to monitor overpressure. For engines equipped with pressure limiting controls, the controllers are required to provide visual and audible indication when system overpressure reaches 115 % of total rated head pressure.
Due to the introduction of electronic engines into the market, a visible indicator and audible alarm must be provided for the conditions ECM Selector Switch in Alternate and Fuel Injection Malfunction. In order to meet the requirements, two pilot lights and relay contacts are added to the controller.
Controller terminal strips have two additional terminals for connecting to the engine control panel. They are as follows:
Terminal Number: 301 - ECM Selector Switch in Alternate Terminal Number: 302 - Fuel Injection Malfunction
Advanced diagnostics and troubleshooting Communication Memory for storage of alarm conditions On site changes performed easily Digital accuracy of parameters
FD100 Diesel
Microprocessor Based 12VDC or 24VDC Battery Voltage NEMA 2 Enclosure Dual 10 Amp Battery Chargers Pressure Transducer (0-600 psi) Weekly Test Timer Run Period Timer
Manual Stop Printer Recorder AC Power Failure Start Sequential Start Timer Relay Energized Indicator Remote Start Deluge Valve Start
To ensure dependable operation of the diesel engine, NFPA 20 code requires automatic weekly starting and running of the engine. The weekly test period is for at least 30 minutes.
Voltmeter for each Battery Ammeter for each Battery Current System Pressure
Standard Alarms
Can be connected now, or in the future, without the addition of any auxiliary components Off Mode Pump Room Trouble Crank Battery #1 & #2 Drain Valve Solenoid
Pressure Start & Stop Points Weekly Test Timer Run Period Timer Sequential Start Timer Pressure Deviation (paperless chart recorder) Low Suction Alarm and/or Shutdown
Stop Mode
Manual or Automatic Input = Output High Engine Temp. Low Fuel Engine Overspeed Low Oil Pressure Battery Charger Fail
Language
Print Routine
FD100 Options
NEMA 12/3R/4/4X
FD100 Options
Electronic Control Module (ECM)
The FD100 diesel engine fire pump controllers are compatible with NFPA20 - Section 12.4.1.3 for engines with ECM controls.
FD100 Options
Electronic Control Module (ECM)
When the ECM option is requested, two pilot lights and relay contacts are added to the controller in order to meet the requirements.
FD100 Options
Electronic Control Module (ECM)
As well, the terminal strip now has two additional
terminals for connecting to the engine control panel. They are as follows: Terminal Number: 301 - ECM Selector Switch in Alternate Terminal Number: 302 - Fuel Injection
FD100 Options
System Over Pressure
In order to meet the requirements of NFPA 20; when the PLD option is requested, a visible alarm light and an additional pressure switch are added to the controller.
Upgraded firmware will perform System Overpressure function by utilizing pressure transducer input eliminates the need for a second input from a pressure switch. New battery chargers with enhanced features.
Voltage Input: 90 - 130VAC / 180 - 240VAC Auto detect Voltage Output: 12-24VDC DIP switch selectable Hertz: Operates on 50 / 60 Hz Temperature Monitoring Dead Battery Cell Alarm Battery Temperature Probe
Purpose
Plumbing systems can encounter leaks for various reasons. Leaks = drop in pressure - (usually minor - only a few psi) The pressure must be kept at a level that will enable the system to react correctly in case of a call to start.
Purpose
Since the pressure drop is minor - the fire pump should not be called upon to keep the pressure at a minimum level. A smaller Jockey Pump is used to keep the system pressure at the desired constant. A separate Jockey Pump Controller is used to control the jockey pump.
Internal Components
NEMA 2 Rated Enclosure 120V Control Transformer Circuit Breaker Disconnect Pressure Switch 15-260 psi
Operation
The Jockey Pump controller is essentially an Across-The-Line combination starter with a pressure switch. The pressure switch is set to operate at a specific set-point - set on site.
Operation
Typically the jockey pump starting set point is 10psi above the set point of the fire pump controller. This allows the jockey pump to cycle on and off, as needed, to keep the pressure at the desired psi - without excessively cycling the fire pump.
Typically two styles of jockey pump controllers can be found in the market. For turning power on and off to the controller either a fusible disconnect or a breaker with a mechanical operating handle are utilized.
One of the most common reasons breakers are used over fuses, are on-site disappearances of fuses. However, breaker style controllers may be more expensive depending on which manufacturer chosen.
Circuit Transformers
The control voltage in the jockey pump controller is typically line voltage or 120V, 3 phase. The controllers can have a transformer in the circuit which operates on full line voltage and steps down the voltage to 120V.
Overload Protection
Thermal overload protection is allowed by code. Overloads are sized according to the namplate Full Load Amps (FLA) on the motor. Most jockey pump manufacturers size the controller for the appropriate Hp and supply the proper size overload.
Options
Enclosure Type - NEMA 12/3R/4/4X Single Phase Service (120V or 220V) Low Suction Shutdown c/w Pressure Switch Space Heater / Thermostat / Humidistat Power On Light Extra Contacts
A Run Period Timer can be added - as an option - to a standard jockey pump controller. The purpose is to ensure that the jockey pump runs for a minimum period of time, when there is a call to start due to low pressure.
http://www.chfire.com