PIPING SYMBOLS AND ABBREVIATIONS

NOTE: SYMBOLS AND ABBREVIATIONS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACT DOCUMENTS.

FIELD MOUNTED CONTROLS PIPE FITTINGS


FLANGE UNION ANCHOR PIPE GUIDE PIPE SLEEVE ECCENTRIC REDUCER CONCENTRIC REDUCER ELBOW DOWN ELBOW UP TEE DOWN TEE UP PIPE CAP SOIL, STORM, OR WASTE PLUG NP DI ROS ROR PW PIPE VALVES AND SPECIALTIES GAS SHUT OFF VALVE GATE VALVE DIAPHRAGM VALVE FLOW SENSING DEVICE BALL VALVE BUTTERFLY VALVE BALANCING VALVE CHECK VALVE PRESSURE OR VACUUM SWITCH LHR TF WGE LA HEAT TRACE TERMINATION POINT MA CA HEAT TRACE POWER CONNECTION POINT THERMOMETER S SOLENOID VALVE PRESSURE GAUGE (WITH VALVE) LVAC MV XLHR XTF XWGE XLA XMA XCA XLVAC XMV PIPE FLEXIBLE CONNECTION PCW PHW PHR LCW LHW XNP XDI XROS XROR XPW XPCW XPHW XPHR XLCW XLHW NEW DCW DHW DHR CS HT EXISTING XDCW XDHW XDHR XCS XHT

PIPING SYSTEM LABELS


NEW DOMESTIC COLD WATER DOMESTIC HOT WATER DOMESTIC HOT WATER RETURN COLD SOFT WATER HEAT TRACE HOT WATER NON-POTABLE WATER DEIONIZED WATER REVERSE OSMOSIS WATER SUPPLY REVERSE OSMOSIS WATER RETURN PURE WATER PROCESS COLD WATER PROCESS HOT WATER PROCESS HOT WATER RETURN LAB COLD WATER LAB HOT WATER LAB HOT WATER RETURN TRAP FILLER LINE WASTE GAS EVACUATION LAB COMPRESSED AIR MEDICAL COMPRESSED AIR PROCESS COMPRESSED AIR LAB VACUUM MEDICAL VACUUM V CWV CRV PV LV VC H2 O2 N2 NG XV XCWV XCRV XPV XLV XVC XH2 XO2 XN2 XNG SAN SD S OD FM CWW IW CRW PW EXISTING XSAN XSD XS XOD XFM XCWW XIW XCRW XPW WASTE OR SOIL LINE SUBSOIL DRAIN LINE STORM OVERFLOW DRAIN LINE FORCE MAIN CLEARWATER WASTE INDIRECT WASTE CORROSION RESISTANT WASTE PROCESS WASTE UNDERFLOOR FOR WASTE OR SOIL, SUBSOIL, STORM & FORCE MAIN VENT CLEARWATER VENT CORROSION RESISTANT VENT PROCESS VENT LAB VENT VACUUM CLEANING HYDROGEN OXYGEN NITROGEN NATURAL GAS A AAP ACC ACFM ADB ADJ AFF ALT AMPS AP APPROX ARCH ASME ASSY BHP BLDG BOP BOT BT BTU BTUH BTWN CA CFCI CFM CLG CMU CO CO2 CONN CONTR CORR CS CTR CU CRVTR CWW D DCW DET DFU DHR DHW DIA DIM DISCH DN DS DWG EA EEW EFF EJ ELEC ELEV EQUIP ET ETR ES EWC EWT EXP EXT -

ABBREVIATIONS
AIR AREA ALARM PANEL ACCESS ACTUAL CUBIC FEET PER MINUTE ACID DILUTION BASIN ADJUSTABLE ABOVE FINISHED FLOOR ALTERNATE AMPERES ACCESS PANEL APPROXIMATE ARCHITECTURAL AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASSEMBLY BRAKE HORSEPOWER BUILDING BOTTOM OF PIPE ELEVATION BOTTOM BATHTUB BRITISH THERMAL UNIT BRITISH THERMAL UNITS PER HOUR BETWEEN COMPRESSED AIR CONTRACTOR FURNISHED CONTRACTOR INSTALLED CUBIC FEET PER MINUTE CEILING CONCRETE MASONRY UNIT CLEANOUT CARBON DIOXIDE CONNECTION/CONNECT CONTRACTOR CORRIDOR CLINICAL SINK/COLD SOFT WATER CENTER COPPER CORROSIVE VENT THROUGH ROOF CLEARWATER WASTE DEPTH/DRAIN LINE DOMESTIC COLD WATER DETAIL DRAINAGE FIXTURE UNIT DOMESTIC HOT WATER RETURN DOMESTIC HOT WATER DIAMETER DIMENSION DISCHARGE DOWN DOWNSPOUT DRAWING EACH EMERGENCY EYEWASH EFFICENCY EXPANSION JOINT ELECTRICAL ELEVATION EQUIPMENT EXPANSION TANK EXISTING TO REMAIN EMERGENCY SHOWER ELECTRIC WATER COOLER ENTERING WATER TEMPERATURE EXPANSION EXTERIOR FAHRENHEIT FLOOR CLEANOUT FLOOR DRAIN FULL LOAD AMPERES FLOOR FORCE MAIN FIREPROOF FEET PER MINUTE FEET FEET HEAD FOOTING GAS GAUGE GALLON GALVANIZED GALLONS PER HOUR GALLONS PER MINUTE HOSE BIBB HUB DRAIN HORSEPOWER HOSE REEL HEAT TRACE HOT WATER HEATER HEATING VENTILATING & AIR CONDITIONING HERTZ INSIDE DIAMETER INVERT ELEVATION INCHES INCHES WATER COLUMN INDIRECT WASTE KILOWATT LENGTH LABORATORY AIR LAVATORY POUNDS LIGHTING LABORATORY VACUUM LEAVING WATER TEMPERATURE MAP MAX MB MBH MEZZ MFR MH MIN MISC MTD MTG NC NIC NO NOM NPSH NPT NTS OC OD OFCI OFOI P PH PIV PLBG PRESS PRV PSF PSI PSIG PW R RAD RD REC RECPT REF REQD RI RPM RV S SA SAN SCH SCFM SD SF SH SHT SPEC SQ SR S/S STD STM STRU SUCT TD TDH TEMP TMV TOB TOD TOJ TOS TF TP TYP UR V VAC VEL VFD VIB VOL VTR W W/ W/O WAGD WC WCO WGE WH WSFU X YCO ZVB KW L LA LAV LBS LTG LV LWT MASTER ALARM PANEL MAXIMUM MOP BASIN ONE THOUSAND BTUH MEZZANINE MANUFACTURER MANHOLE MINIMUM/MINUTE MISCELLANEOUS MOUNTED MOUNTING NORMALLY CLOSED NOT IN CONTRACT NUMBER NOMINAL NET POSITIVE SUCTION HEAD NATIONAL PIPE THREAD NOT TO SCALE ON CENTER OUTSIDE DIAMETER/OVERFLOW DRAIN OWNER FURNISHED CONTRACTOR INSTALLED OWNER FURNISHED OWNER INSTALLED PUMP PHASE POST INDICATOR VALVE PLUMBING PRESSURE PRESSURE REDUCING VALVE POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH GAUGE PURE WATER RADIUS REFRIGERATED AIR DRYER ROOF DRAIN RECESSED RECEPTACLE REFERENCE REQUIRED ROUGH-IN REVOLUTIONS PER MINUTE RELIEF VALVE STORM MECHANICAL SHOCK ARRESTOR SANITARY SCHEDULE STANDARD CUBIC FEET PER MINUTE SUBSOIL DRAIN SQUARE FEET SHOWER SHEET SPECIFICATION SQUARE SERVICE RECEPTOR STAINLESS STEEL STANDARD STORM STRUCTURAL/STRUCTURE SUCTION TRENCH DRAIN TOTAL DYNAMIC HEAD TEMPERATURE THERMOSTATIC MIXING VALVE TOP OF BEAM TOP OF DECK TOP OF JOIST TOP OF SLAB/TOP OF STEEL TRAP FILLER TRAP PRIMER TYPICAL URINAL VENT / VACUUM / VOLTS VACUUM VELOCITY VARIABLE FREQUENCY DRIVE VALVE-IN-BOX VOLUME VENT THRU ROOF WASTE/WATER WITH WITHOUT WASTE ANESTHETIC GAS DISPOSAL WATER CLOSET WALL CLEANOUT WASTE GAS EXHAUST WALL HYDRANT WATER SUPPLY FIXTURE UNIT EXISTING YARD CLEANOUT ZONE VALVE BOX
REVISIONS

Architect and Engineer Name and LOGO

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

MEP ENGINEERS

STRUCTURAL ENGINEER

EXPANSION JOINT

MARK

DATE

DESCRIPTION

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

WALL HYDRANT

THERMOSTATIC MIXING VALVE

HOSE BIBB

A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET CITY BUILDING STATE/ZIP

TEMPERATURE BLENDING VALVE

SLIDE-OXYGEN OR VACUUM BOTTLE GAS OUTLET

BACKWATER VALVE GAS TERMINAL REDUCED PRESSURE BACKFLOW PREVENTER FILTER DOUBLE CHECK BACKFLOW PREVENTER DIRECTION OF PITCH PIPELINE STRAINER M MECHANICAL SHOCKSTOP ZVB ZONE VALVE BOX LABEL IS SHOWN ON FRONT OF VALVE BOX TO INDICATE ORIENTATION DEMOLITION OF PIPING, DEVICE, ETC. WATER METER

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR PROJECT LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

AAP OR MAP AREA OR MASTER ALARM PANEL LABEL IS SHOWN ON FRONT OF PANEL TO INDICATE ORIENTATION

REFERENCE SYMBOLS
REFER SHT # GENERAL REFERENCE DESIGNATES SHEET NUMBER NAME # EQUIPMENT NAME AND NUMBER

DETAIL NUMBER FLOOR DRAIN/FLOOR SINK ROOF DRAIN HUB DRAIN FIXTURE WASTE TRAP X CLEANOUT FLOOR CLEANOUT X X DRAWING NUMBER WHERE DETAIL IS DRAWN SHEET NUMBER WHERE DETAIL IS TAKEN

LAB EQUIPMENT NUMBER

SHEET KEYNOTE NUMBER

# # X0.0 SECTION REFERENCE TOP DESIGNATES SECTION NUMBER BOTTOM DESIGNATES SHEET NUMBER

REVISION NUMBER

CONSTRUCTION BULLETIN NUMBER

G GA GAL GALV GPH GPM HB HD HP HR HT HTR HVAC HZ ID IE IN IN WC IW

FIXTURE INSTALLATION
FIXTURE WATER CLOSET URINAL LAVATORY DRINKING FOUNTAIN SHOWER VALVE SHOWER HEAD BARRIER FREE DESIGN FLOOR TO RIM 17" FLOOR TO RIM 17" MIN. ONE PER ROOM FLOOR TO RIM 34" MAX. FLOOR TO UNDER APRON 29" FLOOR TO SPOUT 36" MAX. FLOOR TO UNDER APRON 27" FLOOR TO VALVE 42" FLOOR TO HEAD 60" ON HOSE ADJ. 48" NON-BARRIER FREE FLOOR TO RIM 15" FLOOR TO RIM 24" FLOOR TO RIM 31" FLOOR TO RIM 40" FLOOR TO VALVE 48" FLOOR TO HEAD 78" VARIES

ELEVATION SYMBOL

END OF DEMOLITION

NEW CONNECTION TO EXISTING

SEAL

DESIGNED BY DRAWN BY CHECKED BY DATE FILE NAME DRAWING NO. DRAWING

WS WS CTC 11/16/12

P0.01
OF SHEET NUMBER

C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt

11/21/2012 9:56:03 AM

DRAWING TITLE

PROJECT TITLE

PLUMBING SYMBOLS AND ABBREVIATIONS

###

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

DRAINS AND CLEANOUTS

F FCO FD FLA FLR FM FP FPM FT FTHD FTG

TRUE NORTH

PROJECT NORTH

10

11

12

13
1.

GENERAL NOTES:
A
2. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO DEMOLITION WORK. DURING DEMOLITION PHASE, IF ANY EXISTING NONRELATED PIPING IN THE AREAS OF THE SCOPE OF WORK ARE DETERIORATED, LEAKING OR FAILING, CONTRACTOR SHALL NOTIFY THE A/E FIRM IN ORDER TO ASSESS IF THIS PIPING IS ALSO TO BE REPLACED DURING THE NEW CONSTRUCTION EFFORT, TO ENSURE THAT ANY EXISTING FAILING PIPING DOES NOT DAMAGE NEW CONSTRUCTION AREAS. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. ALL EXISTING PENETRATIONS FROM PIPING BEING REMOVED, WHICH ARE NOT BEING REUSED FOR NEW PIPING INSTALLATION, SHALL BE PATCHED AND SEALED TO MATCH SURROUNDING FINISHES AND FIRE RATINGS.

PLAN NOTES:
1
REMOVE EXISTING 1-1/4" DCW, 4" SAN, & 4" V AS INDICATED AND PREPARE FOR FUTURE CONNECTION REMOVE EXISTING SINK FIXTURE AND PREPARE EXISTING PLUMBING ROUGH-IN FOR FUTURE SINK.

3.

C
4.

SEE ENLARGED PLAN ON THIS SHEET

Architect and Engineer Name and LOGO

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

MEP ENGINEERS

D E

5.

STRUCTURAL ENGINEER

G A
MARK DATE DESCRIPTION

2
REVISIONS

X - 4"SAN X - 4"V X - 1 1/4"DCW

H
1

I
CONTRACTORS

A/E CON. NO. A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET BUILDING

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

CITY STATE/ZIP

PROJ. CODE # PIMS # WORK ORDER #

J
PROJECT

UVA PROJ. MGR LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

TRUE NORTH

PROJECT NORTH

P0.20

1/4" = 1'-0"

BARRINGER BARRINGER ANNEX

DN UP

UP

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

4'

2'

0'

4'

8'

M
DAVIS

MCINTIRE

SEAL

1 P0.20

2ND FLOOR PLUMBING DEMOLITION PLAN


1/8" = 1'-0"

DESIGNED BY DRAWN BY

16'

8'

0'

16'

32'

CHECKED BY DATE FILE NAME DRAWING NO. DRAWING

WS WS CTC 11/16/12

P0.20
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:06 AM

DRAWING TITLE

PROJECT TITLE

2ND FLOOR PLUMBING OVERALL DEMOLITION PLAN

SPIN LAB PLUMBING DEMOLITION PLAN

1 P0.31

10

11

12

13
1.

GENERAL NOTES:
A
DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO DEMOLITION WORK. DURING DEMOLITION PHASE, IF ANY EXISTING NON-RELATED PIPING IN THE AREAS OF THE SCOPE OF WORK ARE DETERIORATED, LEAKING OR FAILING, CONTRACTOR SHALL NOTIFY THE A/E FIRM IN ORDER TO ASSESS IF THIS PIPING IS ALSO TO BE REPLACED DURING THE NEW CONSTRUCTION EFFORT, TO ENSURE THAT ANY EXISTING FAILING PIPING DOES NOT DAMAGE NEW CONSTRUCTION AREAS. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. ALL EXISTING PENETRATIONS FROM PIPING BEING REMOVED, WHICH ARE NOT BEING REUSED FOR NEW PIPING INSTALLATION, SHALL BE PATCHED AND SEALED TO MATCH SURROUNDING FINISHES AND FIRE RATINGS. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
Architect and Engineer Name and LOGO ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

A
3385B 3381 3385 3391 3389A 3379A 3393 3385A

WAITING CRU EXAM 1


3401

3445G 3442 3445F

NSGY EXAM 5 TEAM ROOM 3407 3405

3419

2.

CORRIDOR DIRTY UTIL PREP


3409 3467 3441 3445D 3445E

3.

B
3389

3397B

C
CORRIDOR
3379 3397B

3403

C.1
CORRIDOR
3435 3468

3445C

4.

SCALE STG
3397C 3413 3377

C.5
TOILET
3420

MEP ENGINEERS

D E

CART STG
3410

ELEV
3464 3445
5.

STRUCTURAL ENGINEER

NSGY EXAM 4
3376

NSGY EXAM 2 NSGY EXAM 3


3412 3414

ELEC
3394 3374

3402 3406

3408

NSGY EXAM 1
3418

3468A

STAIR #5
3465 3445B 3445A

6.

3372

3451

F
3371 3370

G
3361B 3365 3366 3452 3453

MARK

DATE

DESCRIPTION

3397A

1 P0.32

OPEN TO GRADE BELOW

3361

2 P0.33

3364 3362 3397 3469

H I

3361A

REVISIONS A/E CON. NO.

3459 3458

CONTRACTORS

A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

3335 3360A

3338
1 P0.33

ROOF AREA #1 (2ND FLOOR ROOF): SEE MEP DWGS FOR DEMO THIS AREA
BUILDING

BUILDING NO. NAME STREET CITY STATE/ZIP

3453

PROJ. CODE # PIMS # WORK ORDER #

J
3475B 3475

J
PROJECT

UVA PROJ. MGR LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

3361A 3361A

CORRIDOR
3360

ELEV
3354

3472A

3472 3475A

K
CORRIDOR STAIR #4
3355

K
CORRIDOR
3359A 3504A

TRUE NORTH

PROJECT NORTH

3359

3489A 3489 3488A

ELEV
3502

STAIR #6
3503
BARRINGER ANNEX

BARRINGER

3499A

A B
DN UP

2.1

2.9
3488

D
1 P0.34

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

ROOF AREA #2 BELOW (1ST FLOOR ROOF)


3492

3491 3488C 3499

DAVIS

MCINTIRE

3493

3488D

SEAL

1 P0.30

3RD FLOOR PLUMBING OVERALL DEMOLITION PLAN


1/8" = 1'-0"

DESIGNED BY

8'

4'

0'

8'

16'

3497

3498

DRAWN BY CHECKED BY DATE FILE NAME DRAWING

WS WS CTC 11/16/12

3495

DRAWING NO.

P0.30
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:10 AM

DRAWING TITLE

PROJECT TITLE

3RD FLOOR PLUMBING OVERALL DEMOLITION PLAN

CORRIDOR

GENERAL NOTES:
1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO DEMOLITION WORK. DURING DEMOLITION PHASE, IF ANY EXISTING NON-RELATED PIPING IN THE AREAS OF THE SCOPE OF WORK ARE DETERIORATED, LEAKING OR FAILING, CONTRACTOR SHALL NOTIFY THE A/E FIRM IN ORDER TO ASSESS IF THIS PIPING IS ALSO TO BE REPLACED DURING THE NEW CONSTRUCTION EFFORT, TO ENSURE THAT ANY EXISTING FAILING PIPING DOES NOT DAMAGE NEW CONSTRUCTION AREAS. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. ALL EXISTING PENETRATIONS FROM PIPING BEING REMOVED, WHICH ARE NOT BEING REUSED FOR NEW PIPING INSTALLATION, SHALL BE PATCHED AND SEALED TO MATCH SURROUNDING FINISHES AND FIRE RATINGS. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
Architect and Engineer Name and LOGO ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

2.

3.

4.

MEP ENGINEERS

5.

STRUCTURAL ENGINEER

6.

MARK

DATE

DESCRIPTION

PLAN NOTES:
A
1
REVISIONS A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME

REMOVE EXISTING SINK AND ALL ASSOCIATED PIPING AND CAP AS FAR BACKTO THE ACTIVE PLUMBING SYSTEM AS POSSIBLE

WAITING
3419 3442

CRU EXAM 1
3401

NSGY EXAM 5
3405

TEAM ROOM
3407

X-4" SAN UP & DN X-3" V UP & DN

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

B
PREP
BUILDING

STREET CITY STATE/ZIP

DIRTY UTIL
3403

3409

PROJ. CODE #

C.1
MATCHLINE - SEE 1 / P0.32

PIMS # WORK ORDER # UVA PROJ. MGR PROJECT LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

CORRIDOR
3435

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

SCALE STG
3413

C.5

TRUE NORTH

PROJECT NORTH

TOILET CART STG


3410 3420

ELEV

D
1
BARRINGER BARRINGER ANNEX

E
3402

NSGY EXAM 4
3408

NSGY EXAM 2
3414

A
DN UP

NSGY EXAM 3
3406 3412

NSGY EXAM 1
3418

STAIR #5
3465

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

3464

MATCHLINE - SEE 2 / P0.33

DAVIS

MCINTIRE

SEAL

DESIGNED BY DRAWN BY CHECKED BY DATE

WS WS CTC 11/16/12

1 P0.30 P0.31

DRAWING

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA A


1/4" = 1'-0"

FILE NAME DRAWING NO.

4'

2'

0'

4'

8'

P0.31
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:12 AM

DRAWING TITLE

PROJECT TITLE

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA A

4
1.

GENERAL NOTES:
DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO DEMOLITION WORK. DURING DEMOLITION PHASE, IF ANY EXISTING NON-RELATED PIPING IN THE AREAS OF THE SCOPE OF WORK ARE DETERIORATED, LEAKING OR FAILING, CONTRACTOR SHALL NOTIFY THE A/E FIRM IN ORDER TO ASSESS IF THIS PIPING IS ALSO TO BE REPLACED DURING THE NEW CONSTRUCTION EFFORT, TO ENSURE THAT ANY EXISTING FAILING PIPING DOES NOT DAMAGE NEW CONSTRUCTION AREAS. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. ALL EXISTING PENETRATIONS FROM PIPING BEING REMOVED, WHICH ARE NOT BEING REUSED FOR NEW PIPING INSTALLATION, SHALL BE PATCHED AND SEALED TO MATCH SURROUNDING FINISHES AND FIRE RATINGS. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
Architect and Engineer Name and LOGO ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

3" XSD 3" XV 1 4" XSAN 1-/4" XDHW 1-1/4" XDCW

2.

3385B

3385A 3381

3.

3 3
3385

3391 3389A
4.

3379A 3393

MEP ENGINEERS

B
5.

STRUCTURAL ENGINEER

3389

3397B

C
6.

3379

CORRIDOR
3397B

REMOVE EXISTING SINK AND ALL ASSOCIATED PIPING AND CAP AS FAR BACK TO THE ACTIVE PLUMBING SYSTEM AS POSSIBLE REMOVE EXISTING WATER CLOSET AND ALL ASSOCIATED PIPING AND CAP AS FAR BACK TO THE ACTIVE PLUMBING SYSTEM AS POSSIBLE. REMOVE VERTICAL RISERS 6" BELOW 4TH FLOOR SLAB DOWN TO 6" BELOW 3RD FLOOR SLAB AND PREPARE PIPING FOR FUTURE CONNECTION. REMOVE EXISTING 2" V & 3" SAN AS INDICATED AND CAP.

D E

3376

REVISIONS

3" XV UP & DN 4" XSAN UP & DN

3377

2-1/2" XDHW (MAIN RISER) 3" XSD 3" XV 2" XVV 4" XV 3397C 4" XSAN 1-1/2" XDCW 1-1/4" XDHW

MATCHLINE - SEE 1 / P0.31

MARK

DATE

DESCRIPTION

PLAN NOTES:
1

A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET CITY BUILDING STATE/ZIP

ELEC

4 5

3
3374
3/4" XDCW UP & DN 2" XSAN UP & DN 2" XV UP & DN 3/4" XDHW UP & DN

3394
REMOVE EXISTING ABANDONED IN PLACE AS INDICATED.

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

3372
1 1/2"V

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR PROJECT

F
3371 3370

LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

2"V

G
3361B
3/4" XDCW UP & DN 2" XSAN UP & DN 2" XV UP & DN 3/4" XDHW UP & DN 3"SAN

TRUE NORTH

PROJECT NORTH

BARRINGER BARRINGER ANNEX

3397A

DN UP

1 3
3361
1-1/4" XDCW UP & DN 4" XSAN UP & DN 3" XV UP & DN

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

3365

3366

3364

3361A 3397
4"SAN

3362 4" XSAN UP TO WC


MCINTIRE

DAVIS

I
MATCHLINE - SEE 1 / P0.33

SEAL

DESIGNED BY DRAWN BY CHECKED BY

1 P0.30 P0.32

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA B


1/4" = 1'-0"
DRAWING

DATE FILE NAME

WS WS CTC 11/16/12

4'

2'

0'

4'

8'

DRAWING NO.

P0.32
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:14 AM

DRAWING TITLE

PROJECT TITLE

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA B

GENERAL NOTES:
1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO DEMOLITION WORK. DURING DEMOLITION PHASE, IF ANY EXISTING NON-RELATED PIPING IN THE AREAS OF THE SCOPE OF WORK ARE DETERIORATED, LEAKING OR FAILING, CONTRACTOR SHALL NOTIFY THE A/E FIRM IN ORDER TO ASSESS IF THIS PIPING IS ALSO TO BE REPLACED DURING THE NEW CONSTRUCTION EFFORT, TO ENSURE THAT ANY EXISTING FAILING PIPING DOES NOT DAMAGE NEW CONSTRUCTION AREAS. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. ALL EXISTING PENETRATIONS FROM PIPING BEING REMOVED, WHICH ARE NOT BEING REUSED FOR NEW PIPING INSTALLATION, SHALL BE PATCHED AND SEALED TO MATCH SURROUNDING FINISHES AND FIRE RATINGS. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
Architect and Engineer Name and LOGO ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

2.

3.

9
4.

MATCHLINE - SEE 1 / P0.31

MEP ENGINEERS

5.

STRUCTURAL ENGINEER

6.

4"SAN
MARK DATE DESCRIPTION

H
MATCHLINE - SEE 1 / P0.32
3452

PLAN NOTES:
REMOVE EXISTING SINK AND ALL ASSOCIATED PIPING AND CAP AS FAR BACK TO THE ACTIVE PLUMBING SYSTEM AS POSSIBLE REMOVE EXISTING PLUMBING FIXTURES AND ALL ASSOCIATED PIPING AND CAP AS FAR BACK TO THE ACTIVE PLUMBING SYSTEM AS POSSIBLE. REMOVE EXISTING 3" SAN AS INDICATED AND CAP.
A/E CON. NO. CONTRACTORS REVISIONS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E

I
1

3 4

NO PLUMBING DEMOLITION WORK IN THESE AREAS.

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

3335 3360A

3338

BUILDING NO. NAME STREET CITY BUILDING STATE/ZIP

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR

3"SAN
PROJECT

LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

3458

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

3 2
3"SAN
TRUE NORTH PROJECT NORTH

3361A 3361A

ELEV CORRIDOR
3360
BARRINGER ANNEX

3354

3453
BARRINGER

K J

DN UP

D
2.1 2.9

1 P0.30 P0.33

1/4" = 1'-0"

P0.30 P0.33

1/4" = 1'-0"

DAVIS

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA C


4' 2' 0' 4' 8'

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA D


4' 2' 0' 4' 8'

MCINTIRE

SEAL

DESIGNED BY DRAWN BY CHECKED BY DATE FILE NAME DRAWING NO. DRAWING

WS WS CTC 11/16/12

P0.33
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:17 AM

DRAWING TITLE

PROJECT TITLE

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA C AND D

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

GENERAL NOTES:
1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO DEMOLITION WORK. DURING DEMOLITION PHASE, IF ANY EXISTING NON-RELATED PIPING IN THE AREAS OF THE SCOPE OF WORK ARE DETERIORATED, LEAKING OR FAILING, CONTRACTOR SHALL NOTIFY THE A/E FIRM IN ORDER TO ASSESS IF THIS PIPING IS ALSO TO BE REPLACED DURING THE NEW CONSTRUCTION EFFORT, TO ENSURE THAT ANY EXISTING FAILING PIPING DOES NOT DAMAGE NEW CONSTRUCTION AREAS. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. ALL EXISTING PENETRATIONS FROM PIPING BEING REMOVED, WHICH ARE NOT BEING REUSED FOR NEW PIPING INSTALLATION, SHALL BE PATCHED AND SEALED TO MATCH SURROUNDING FINISHES AND FIRE RATINGS. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
Architect and Engineer Name and LOGO ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

2.

3.

10

12

4.

MEP ENGINEERS

5.

STRUCTURAL ENGINEER

L
6.

3489A

ELEV
3502 3489 3488A

STAIR #6
3503

3499A
X - 4"S

MARK

DATE

DESCRIPTION

PLAN NOTES:
7 9
1"XMA 1"XN2 1"XCO2 1"XO2 1"XMV REMOVE EXISTING SINK AND ALL ASSOCIATED PIPING AND CAP AS FAR BACK TO THE ACTIVE PLUMBING SYSTEM AS POSSIBLE. REMOVE EXISTING WATER CLOSET AND ALL ASSOCIATED PIPING AND CAP AS FAR BACK TO THE ACTIVE PLUMBING SYSTEM AS POSSIBLE. REMOVE EXISTING 4" SAN DOWN TO 12" BELOW 3RD FLOOR SLAB AND PREPARE PIPING FOR FUTURE CONNECTION.
A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. REVISIONS

1 6 2

X - 3"SAN

X - 4"S

8
3488

4" XS DN 4" XSAN DN 4"SAN

3491

3/4"XMV 1/2"XO2 1/2"XCO2 1/2"XN2 1/2"XMA

3
3488C 3499
3/4"DHW 1/2"DHR 3/4"DCW

REMOVE EXISTING 3" SAN DOWN TO 12" BELOW 3RD FLOOR SLAB AND PREPARE PIPING FOR FUTURE CONNECTION. REMOVE EXISTING 3/4" DHW, 1/2" DHR & 3/4" DCW AS INDICATED. PREPARE AND CAP FOR FUTURE CONNECTION.

5
3492

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

NAME

3" XSAN DN

BUILDING

REMOVE EXISTING MEDICAL GASES AND VACUUM PIPING AND ALL ASSOCIATED SUPPLY TANKS AND SERVICE PANELS. REMOVE EXISTING 4" STORM DOWN TO 12" BELOW 3RD FLOOR SLAB AND PREPARE PIPING FOR FUTURE CONNECTION. REMOVE EXISTING DRINKING FOUNTAIN AND CAP ALL ASSOCIATED PLUMBING PIPING IN WALL.

STREET CITY STATE/ZIP

M
3/4" XDHW DN 1/2" XDHR DN 3/4" XDCW DN X - 3"SAN 3"SAN

PROJ. CODE # PIMS #

8 9

WORK ORDER # UVA PROJ. MGR PROJECT LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

REMOVE EXISTING GAS CYLINDERS AND ASSOCIATED EQUIPMENT FROM CLOSET. REMOVE EXISTING CAPPED IN CEILING WATER SUPPLY PIPING.

10
X - 3"SAN 3/4"XMV 1/2"XO2 1/2"XCO2 1/2"XN2 1/2"XMA

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

3493 3488D
4" XSAN UP 3" XSAN UP

TRUE NORTH

PROJECT NORTH

3498
4" XSAN UP 4"SAN

3" XSAN UP

3497

10
BARRINGER BARRINGER ANNEX

1"XMA 1"XN2

1"XCO2 1"XO2 1"XMV

1/2"XN2 1/2"XMA

3495

4" XSAN DN

DN UP

4"SAN

4" XSAN UP

2" XSAN UP

DAVIS

MCINTIRE

SEAL

DESIGNED BY DRAWN BY

1 P0.30 P0.34

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA E


1/4" = 1'-0"

CHECKED BY DATE FILE NAME

WS WS CTC 11/16/12

4'

2'

0'

4'

8'
DRAWING

DRAWING NO.

P0.34
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:19 AM

DRAWING TITLE

PROJECT TITLE

ENLARGED 3RD FLOOR PLUMBING DEMOLITION PLAN - AREA E

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

3/4"XMV 1/2"XO2 1/2"XCO2

1 A

3" UP TO FD-1

2
1-1/2" V UP

10

11

12

13 A
1.

GENERAL NOTES:
DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. SLOPES AND PITCHES OF PIPING INSTALLED ARE TO COMPLY WITH THE RELEVANT SPECIFICATIONS SECTIONS INCLUDED WITH THIS PROJECT. SLOPING PIPING SHALL BE GIVEN THE RIGHT OF WAY DURING COORDINATION DRAWINGS EFFORTS IN CONSTRUCTION. HOLD SLOPING PIPING AS HIGH AS POSSIBLE AGAINST STRUCTURE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES. IF CONDITIONS PROHIBIT ROUTING OF PIPING AS INDICATED ON THIS PLAN, NOTIFY THE A/E IMMEDIATELY PRIOR TO ANY REROUTING OR INSTALLATION, TO VERIFY DESIGN INTENT OF THIS PROJECT & FUTURE PROJECTS IN THIS BUILDING. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. CONTRACTOR IS TO MAKE ALL FINAL CONNECTIONS TO FIXTURES AND EQUIPMENT NOT SHOWN ON THE DRAWINGS. UNLESS OTHERWISE NOTED, BALANCING VALVES SHOWN ARE TO BE SET AT 0.5 GPM. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.

PLAN NOTES:
1
CONNECT NEW 4" SAN & STORM TO EXISTING 4" SAN & STORM CONNECT NEW 3/4" DHW, 2" SAN, 2" V & 3/4" DCW TO EXISTING 3/4" DHW, 2" SAN, 2" V & 3/4" DCW

3/4" DHW UP 2" V UP 2" SAN UP 3/4" DCW UP 2" UP TO S-1 4" V UP 4" SAN UP

2. 4" SAN UP TO S-4 4"SAN

3"SAN

B
3/4" DHW UP 3/4" DCW UP 3/4" DHW UP 2" V UP 2" SAN UP 3/4" DCW UP 4"SAN

CO

3.

CONNECT NEW 1-1/2" DCW TO EXISTING 1-1/2" DCW CONNECT NEW 3/4" DHW & 3/4" DCW TO EXISTING 3/4" DHW & 3/4" DCW CONNECT NEW SINK TO EXISTING SUPPLY AND WASTE PIPING IN THIS WALL. 1-1/2" WASTE FROM PANTRY SINK ABOVE TO CONNECT TO EXISTING JANITOR'S SINK WASTE ON THIS FLOOR. CONNECT NEW 3" SAN TO EXISTING 3" SAN.
ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

2" UP TO S-2 4" UP TO WC 2" V UP SEE ENLARGED PLAN ON THIS SHEET HX 1 1-1/2" V UP 8 P5.00

8
4.

C.1

5 6

2"SAN

C.5

5.

2" UP TO L-1 4" UP TO WC 2" V UP 2"SAN

Architect and Engineer Name and LOGO

MEP ENGINEERS

2" UP TO SH-1 RCP 1

CONNECT NEW 4" SAN TO EXISTING 4" SAN.

E
4"SAN 2" UP TO S-1 4"SAN

STRUCTURAL ENGINEER

1 1/4"DHW 1 1/4"DHW 1 1/2"V 1 1/2"SAN

6.

CONNECT NEW 1-1/4" DCW,4" V & 4" SAN TO EXISTING 1-1/4" DCW, 4" V & 4" SAN.

3
2" UP TO L-1 4" UP TO WC X-3/4" DCW X-2" SAN X-2"V X-3/4" DHW UP & DN

3"SAN CO 2" V UP

6
3/4" DHR UP 1-1/4" DHW UP 1-1/4" DHW UP 1-1/2" V UP 1-1/2" UP TO S-1 2" UP TO SH-1 1-1/2" V UP

7. 8.

4"SAN

2" V UP

2" UP TO S-1 4"SAN 4"SAN 3"SAN

1-1/2" V UP

G
3" UP TO MS-1 2" V UP 4" UP TO WC-1

GRADE BELOW (GRASS)

1-1/2" V UP PIPING IN MILLWORK BELOW

MARK

DATE

DESCRIPTION

3"SAN 2" UP TO S-1 CO

4"SAN

3" UP TO FD-1 4" UP TO WC-1 2" V UP

8
2" UP TO L-1 2" UP TO S-1

2"SAN 2" UP TO L-1

2
1"DCW

3" UP TO FD-1

GRADE BELOW (CONC)


1/2"DCW 1 1/2"V 1/2"DHW

S-3

5
S-2

2"SAN 2"V 1"DHW

I
4"SAN 2"SAN 2"SAN 2"SAN 2" SAN UP 2" V UP 4" UP TO WC
CONTRACTORS

3/4" DHW DN 2" V DN 2" SAN DN 3/4" DCW DN

REVISIONS A/E CON. NO. A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO.

2"SAN

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

B
4"SAN

1-1/4" DCW DN 4" V DN 4" SAN DN


BUILDING

NAME STREET CITY STATE/ZIP

PROJ. CODE #

C
PROJECT

PIMS # WORK ORDER # UVA PROJ. MGR LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

K
TRUE NORTH PROJECT NORTH

P1.20

1/4" = 1'-0"

BARRINGER BARRINGER ANNEX 4" S UP 4"SAN 4"S CO CO 4" SAN UP

DN UP

UP

2.1

2.9

CO

CO

3"SAN

M
7
DAVIS 3" SAN UP

MCINTIRE

X-3/4" DHW X-1/2" DHR X-3/4" DCW

1 P1.20

2ND FLOOR PLUMBING OVERALL NEW WORK PLAN


1/8" = 1'-0"

1/2" TF UP 4" UP TO FD-1 CO


DESIGNED BY

SEAL

2" V UP

DRAWN BY CHECKED BY DATE FILE NAME

16'

8'

0'

16'

32'

WS WS CTC 11/16/12

8
CO

DRAWING

4"SAN

DRAWING NO.

P1.20
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:23 AM

DRAWING TITLE

PROJECT TITLE

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

4'

2'

0'

4'

8'

2ND FLOOR PLUMBING OVERALL NEW WORK PLAN

2ND FLR ENLARGED NEW WORK PLAN

NSGY EXAM 5
3405

1 P1.31

10

11

12

13

GENERAL NOTES:
A
1.

CLEAN UTILITY SPIN LAB


3372 3375

EXIST

CRU EXAM 1
3401

CLINIC TEAM ROOM


3407

WAITING
3419

3445G 3442 3445F


2.

DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. SLOPES AND PITCHES OF PIPING INSTALLED ARE TO COMPLY WITH THE RELEVANT SPECIFICATIONS SECTIONS INCLUDED WITH THIS PROJECT. SLOPING PIPING SHALL BE GIVEN THE RIGHT OF WAY DURING COORDINATION DRAWINGS EFFORTS IN CONSTRUCTION. HOLD SLOPING PIPING AS HIGH AS POSSIBLE AGAINST STRUCTURE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES. IF CONDITIONS PROHIBIT ROUTING OF PIPING AS INDICATED ON THIS PLAN, NOTIFY THE A/E IMMEDIATELY PRIOR TO ANY REROUTING OR INSTALLATION, TO VERIFY DESIGN INTENT OF THIS PROJECT & FUTURE PROJECTS IN THIS BUILDING. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. CONTRACTOR IS TO MAKE ALL FINAL CONNECTIONS TO FIXTURES AND EQUIPMENT NOT SHOWN ON THE DRAWINGS. UNLESS OTHERWISE NOTED, BALANCING VALVES SHOWN ARE TO BE SET AT 0.5 GPM. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
MARK DATE DESCRIPTION

CORRIDOR
3467 3441 3445E C.1
4. 3.

B C

PREP
3409

NURSES STATION
3371

CORRIDOR
3397B

CORRIDOR
3435

CORRIDOR
3468 3445C C.5

NSGY CLEAN UTILITY


D E 3404

TOILET
3420

5.

Architect and Engineer Name and LOGO

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

MEP ENGINEERS

ELEV
3464 3445

STRUCTURAL ENGINEER

NIC
3445G

INFUSION ROOM
3402
EXIST EXIST EXIST

OVERNIGHT 1
3367 F

NSGY EXAM EXIST 1


3418

6.

STAIR #5
3465 3445A
7.

CORRIDOR CRU EXAM 2


3366

3451

8.

NSGY EXAM 4
3408

NSGY EXAM 3
3412

NSGY EXAM 2
3414

3469

MONITORING-2
3363-2

3453

OVERNIGHT 2
3361 H

CLAMP / 2-BED OVERNIGHT


3362

1 P1.32

2 P1.33

CONF ROOM
I 3452 3459
CONTRACTORS A/E CON. NO. A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME

CRU EXAM 3
3341

REVISIONS

OPEN TO BELOW

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

OFFICE
3335A J

CORRIDOR
3360A

1 P1.33

BUILDING

NURSE'S CUBICLES
3338

STREET CITY STATE/ZIP

PROJ. CODE # PIMS #

J
PROJECT

WORK ORDER # UVA PROJ. MGR LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

3475B

3475

ADMIN STAFF
3335

ELEV
3354

3472A

3472 3475A

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

K
TRUE NORTH PROJECT NORTH

CORRIDOR STAIR #4
3355

CORRIDOR
3504A L 3RD FLOOR PLUMBING OVERALL NEW WORK PLAN
OF SHEET NUMBER DRAWING TITLE

CORRIDOR
3360

3359A

ELEV TEAM RM 1
3481 3502

STAIR #6
3503
BARRINGER ANNEX BARRINGER

STOR
2.1 2.9 3482

A B
DN UP

D
TEAM RM 2
3485

TEAM RM 3
3484

1 P1.34

TEAM RM 4
3488

3487

3480C

CORRIDOR
3480D
BFP

SEAL

FACULTY 1

CORRIDOR

DAVIS

MCINTIRE

PROJECT TITLE DESIGNED BY DRAWN BY CHECKED BY DATE FILE NAME DRAWING NO. DRAWING

1 P1.30

3RD FLOOR PLUMBING OVERALL NEW WORK PLAN


1/8" = 1'-0"

FACULTY 4 FACULTY 3
3491 O 3492

8'

4'

0'

8'

16'

MECH FACULTY 2
3489 3490

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:28 AM

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS


WS WS CTC 11/16/12

P1.30

GENERAL NOTES:
1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. SLOPES AND PITCHES OF PIPING INSTALLED ARE TO COMPLY WITH THE RELEVANT SPECIFICATIONS SECTIONS INCLUDED WITH THIS PROJECT. SLOPING PIPING SHALL BE GIVEN THE RIGHT OF WAY DURING COORDINATION DRAWINGS EFFORTS IN CONSTRUCTION. HOLD SLOPING PIPING AS HIGH AS POSSIBLE AGAINST STRUCTURE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES. IF CONDITIONS PROHIBIT ROUTING OF PIPING AS INDICATED ON THIS PLAN, NOTIFY THE A/E IMMEDIATELY PRIOR TO ANY REROUTING OR INSTALLATION, TO VERIFY DESIGN INTENT OF THIS PROJECT & FUTURE PROJECTS IN THIS BUILDING. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. CONTRACTOR IS TO MAKE ALL FINAL CONNECTIONS TO FIXTURES AND EQUIPMENT NOT SHOWN ON THE DRAWINGS. UNLESS OTHERWISE NOTED, BALANCING VALVES SHOWN ARE TO BE SET AT 0.5 GPM. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
MARK DATE DESCRIPTION

2.

3.

4.

5.

Architect and Engineer Name and LOGO

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

MEP ENGINEERS

STRUCTURAL ENGINEER

6.

9
7. 8.

EXIST

CRU EXAM 1
3401

NSGY EXAM 5
3405

CLINIC TEAM ROOM


3407

WAITING
3419 3442

PLAN NOTES:
CONNECT NEW EXAM SINK AND MOP SINK WATER, WASTE & VENT TO EXISTING ADJACENT SINK PIPING.
REVISIONS A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET BUILDING

1
3/4"DCW

S-1

(X)SINK

2"V 3/4"DHW

PREP
3409
S-4

C
1 1/4"DHW

C.1
MATCHLINE - SEE 1 / P1.32

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

CORRIDOR
3/4"DHR

CITY STATE/ZIP

3435

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR PROJECT

1 1/4"DHW

LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

C.5

NSGY CLEAN UTILITY


1 1/4"DHW

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

3404

TOILET
3420

ELEV
3464
TRUE NORTH PROJECT NORTH

1 1/4"DHW

D E

3402
S-1 1-1/4" DHW DN 1-1/4" DHW DN 1 1/2"V 3/4" DHR DN

EXIST

EXIST

EXIST

EXIST

STAIR #5
3465
BARRINGER ANNEX BARRINGER

NSGY EXAM 4
3408

NSGY EXAM 3
3412

NSGY EXAM 2
3414

NSGY EXAM 1
3418

A
DN UP

2" WASTE DN 1-1/2" V DN

MATCHLINE - SEE 1 / P1.33

S-3

S-2

DAVIS

MCINTIRE

SEAL

1 P1.30 P1.31

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA A


1/4" = 1'-0"

DESIGNED BY DRAWN BY CHECKED BY

4'

2'

0'

4'

8'

DATE FILE NAME DRAWING NO. DRAWING

WS WS CTC 11/16/12

P1.31
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:31 AM

DRAWING TITLE

PROJECT TITLE

1/2" DCW TO REFRIGERATOR WITH ICE MAKER

2"SAN 1 1/2"V 1/2"DCW

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

1/2"DCW 2"V

INFUSION ROOM

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA A

GENERAL NOTES:
1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. SLOPES AND PITCHES OF PIPING INSTALLED ARE TO COMPLY WITH THE RELEVANT SPECIFICATIONS SECTIONS INCLUDED WITH THIS PROJECT. SLOPING PIPING SHALL BE GIVEN THE RIGHT OF WAY DURING COORDINATION DRAWINGS EFFORTS IN CONSTRUCTION. HOLD SLOPING PIPING AS HIGH AS POSSIBLE AGAINST STRUCTURE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES. IF CONDITIONS PROHIBIT ROUTING OF PIPING AS INDICATED ON THIS PLAN, NOTIFY THE A/E IMMEDIATELY PRIOR TO ANY REROUTING OR INSTALLATION, TO VERIFY DESIGN INTENT OF THIS PROJECT & FUTURE PROJECTS IN THIS BUILDING. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. CONTRACTOR IS TO MAKE ALL FINAL CONNECTIONS TO FIXTURES AND EQUIPMENT NOT SHOWN ON THE DRAWINGS. UNLESS OTHERWISE NOTED, BALANCING VALVES SHOWN ARE TO BE SET AT 0.5 GPM. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
MARK DATE DESCRIPTION

A
FD-1 1-1/2" V DN 3/4" DHW DN 2" V DN 2" SAN DN 3/4" DCW DN

1 1/2"V S-2

X-3" SD X-3" V X-4" SAN X-1-/4" DHW X-1-1/4" DCW

CLEAN UTILITY
3375

2.

3.

SPIN LAB
3/4"DHW 3372 2"V 2"SAN 1/2"DCW 3/4"DCW 2"V 1-1/2" SAN DN 4" V DN 4" SAN DN 3/4"DCW

2
3/4"DCW 3/4"DCW

4.

3
4"SAN 4"V 3/4" DCW DN 1 1/4"DHW 2" SAN DN 2" V DN 6. 1"DCW 2"V 5.

Architect and Engineer Name and LOGO

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

WC-1

L-1

MEP ENGINEERS

STRUCTURAL ENGINEER

C
MATCHLINE - SEE 1 / P1.31

NURSES STATION
3371
3/4"DHW 2"V 2"SAN 3/4"DCW 1 1/4"DHW

1 1/4"DHW

CORRIDOR
3397B
X-2-1/2" DHW (MAIN RISER) X-3" SD X-3" V X-2" VV X-4" V X-4" SAN X-1-1/2" DCW X-1-1/4" DHW

7. 8.

S-1

3/4" DCW DN 3/4" DHW DN 3/4"DHW 3/4"DCW

SHARED TOILET / SHOWER


3/4" DHW DN 2" V DN 2" SAN DN 3/4" DCW DN 1 1/4"DHW

1 1/4"DHW

3368

L-1 1/2"DCW 1/2"DHW 3/4"DHW 3/4"DCW

PLAN NOTES:
1 1/4"DHW 1 1/4"DHW CONNECT NEW 2" V, 3/4" DHW & 1" DCW TO EXISTING 4" V, 11/4" DHW & 1-1/2" DCW. CONNECT NEW 3/4" DHW, 2" V, 2" SAN & 3/4" DCW TO EXISTING 3/4" DHW, 2" V, 2" SAN & 3/4" DCW. CONNECT NEW 1-1/4" DCW, 4" V & 4" SAN TO EXISTING 1-1/4" DCW, 4" V & 4" SAN. CONNECT NEW 3/4" DCW & DHW TO EXISTING 3/4" DCW & DHW.
CONTRACTORS REVISIONS A/E CON. NO. A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO.

3/4"DCW 3/4"DHW

1 2
SH-2 FD-1 3/4"DCW 2"V

D E

2" V DN 2"V S-1

2"V WC-1

4
1-1/2" V DN X-4" SAN X-3" V

3 4

NIC
2" WASTE DN S-1 1 1/4"DCW 1"DCW 1 1/4"DCW 1-1/4" DCW DN 2"V 2"V 3/4"DCW 2" V DN 1 1/2"V WC-1

3445G

5 6

CONNECT NEW 1-1/4" DCW TO EXISTING 1-1/4" DCW .

CONNECT NEW 3/4" DCW, 2" V & 3/4" DHW TO EXISTING 3/4" DCW, 2" V & 3/4" DHW. CONNECT NEW 2" V, 3/4" DHW & 1" DCW TO EXISTING 3" V, 11/4" DHW & 1-1/2" DCW.
BUILDING

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

OVERNIGHT 1
3367
1"DCW L-1 1 1/2"V

L-1

7 8

NAME STREET CITY

1 1/2"V 1/2"DCW 1 1/4"DHW

1/2"DCW 1/2"DHW S-1

1 1/2"DCW

CONNECT NEW 2" V, 1-1/4" DHW & 1-1/2" DCW TO EXISTING 4" V, 1-1/4" DHW & 1-1/2" DCW.

STATE/ZIP

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR PROJECT LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

F
2"V X-3/4" DCW X-2" SAN X-2" V X-3/4" DHW

WC-1

1 1/4"DHW

1 1/4"DCW

CRU EXAM 2
3366
1-1/2" V DN 1 1/4"DCW 3/4"DCW SH-1

2" V DN

3/4"DHW

2"V

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

TRUE NORTH

PROJECT NORTH

MONITORING-2
3363-2
X-1-1/2" DCW X-1-1/4" DHW X-4" SAN X-3" V 2" V DN 1/2"DHW 1/2"DCW 1/2"DHW 1/2"DCW 2"V 2"V S-1 1 1/4"DHW 1"DCW WC-1 1 1/4"DHW

WC-1

FD-2

2"V L-1 BARRINGER BARRINGER ANNEX

OVERNIGHT 2
3361

2"V

2"V 1"DCW L-1 1/2"DHW

3/4"DCW 1/2"DCW

DN UP

CLAMP / 2-BED OVERNIGHT


2

1 1/2"V 1 1/2"V 3/4"DCW S-1 2" WASTE DN

X-1-1/2" DCW X-4" SAN X-3" V 1/2"DHW

1"DHW 2"V 2"SAN 1"DCW MCINTIRE 1" DHW DN 2" V DN 2" SAN DN 1" DCW DN

DAVIS

H
3/4"DHW 1/2"DHW 2"V

MATCHLINE - SEE 1 / P1.33

SEAL

DESIGNED BY DRAWN BY CHECKED BY

1 P1.30 P1.32

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA B


1/4" = 1'-0"
DRAWING

DATE FILE NAME DRAWING NO.

WS WS CTC 11/16/12

4'

2'

0'

4'

8'

P1.32
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:35 AM

DRAWING TITLE

PROJECT TITLE

3362

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA B

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

GENERAL NOTES:
1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. SLOPES AND PITCHES OF PIPING INSTALLED ARE TO COMPLY WITH THE RELEVANT SPECIFICATIONS SECTIONS INCLUDED WITH THIS PROJECT. SLOPING PIPING SHALL BE GIVEN THE RIGHT OF WAY DURING COORDINATION DRAWINGS EFFORTS IN CONSTRUCTION. HOLD SLOPING PIPING AS HIGH AS POSSIBLE AGAINST STRUCTURE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES. IF CONDITIONS PROHIBIT ROUTING OF PIPING AS INDICATED ON THIS PLAN, NOTIFY THE A/E IMMEDIATELY PRIOR TO ANY REROUTING OR INSTALLATION, TO VERIFY DESIGN INTENT OF THIS PROJECT & FUTURE PROJECTS IN THIS BUILDING. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. CONTRACTOR IS TO MAKE ALL FINAL CONNECTIONS TO FIXTURES AND EQUIPMENT NOT SHOWN ON THE DRAWINGS. UNLESS OTHERWISE NOTED, BALANCING VALVES SHOWN ARE TO BE SET AT 0.5 GPM. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
MARK DATE DESCRIPTION

2.

3.

4.

5.

Architect and Engineer Name and LOGO

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

MEP ENGINEERS

MATCHLINE - SEE 1 / P1.31

STRUCTURAL ENGINEER

1/2" DCW TO REFRIGERATOR WITH ICE MAKER 2" SAN ABOVE FL.

2"SAN 1 1/2"V S-3 1/2"DCW EWH 2 S-2

6.

7. 8.

S-1 2" WASTE DN

PLAN NOTES:
MATCHLINE - SEE 1 / P1.32
3/4"DHW 2"V
REVISIONS A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET CITY BUILDING STATE/ZIP

H
1
CONNECT NEW 3/4" DHW, 2" V, 2" SAN & 1-1/4" DCW TO EXISTING 3/4" DHW, 2" V, 2" SAN & 1-1/2" DCW. ROUTE 1-1/2" FIXTURE DRAIN LINES FROM SINKS ABOVE FLOOR AND CONNECT TO 1-1/2" FIXTURE BRANCH AT THIS LOCATION.

I
1/2"DHW

L-1 S-1 3/4"DHW

1
3/4"DHW 1/2"DHW 1"DCW WC-1 1-1/2" V DN 1"DCW 2"V

1 1/2"V 1/2"DCW

CRU EXAM 3
3341

MS-1

1 1/2"V 3/4"DCW

HSKPG
3/4"DCW

3339
1 1/2"V

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

COPY/FAX OFFICE
3335A 3337

CORRIDOR
3360A

NURSE'S CUBICLES
3338
PROJECT

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

CONF ROOM
3452
TRUE NORTH PROJECT NORTH

ADMIN STAFF
3335

ELEV CORRIDOR
3360
3/4"DCW

3354
BARRINGER ANNEX

BARRINGER

DN UP

K J

D C

2.1

2.9
MCINTIRE

1 P1.30 P1.33

1/4" = 1'-0"

P1.30 P1.33

1/4" = 1'-0"

4'

2'

0'

4'

8'

4'

2'

0'

4'

8'

SEAL

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA C

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA D

DAVIS

DESIGNED BY DRAWN BY CHECKED BY DATE FILE NAME DRAWING NO. DRAWING

WS WS CTC 11/16/12

P1.33
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:39 AM

DRAWING TITLE

PROJECT TITLE

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA C AND D

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

1 1/2"V

GENERAL NOTES:
1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, DETAILS AND RISER DIAGRAMS INCLUDED IN THIS PACKAGE. SLOPES AND PITCHES OF PIPING INSTALLED ARE TO COMPLY WITH THE RELEVANT SPECIFICATIONS SECTIONS INCLUDED WITH THIS PROJECT. SLOPING PIPING SHALL BE GIVEN THE RIGHT OF WAY DURING COORDINATION DRAWINGS EFFORTS IN CONSTRUCTION. HOLD SLOPING PIPING AS HIGH AS POSSIBLE AGAINST STRUCTURE. FIELD VERIFY ALL EXISTING CONDITIONS IN THE CEILING OF THIS SPACE TO CONFIRM EXACT ROUTING AND POTENTIAL CONFLICTS WITH OTHER TRADES. IF CONDITIONS PROHIBIT ROUTING OF PIPING AS INDICATED ON THIS PLAN, NOTIFY THE A/E IMMEDIATELY PRIOR TO ANY REROUTING OR INSTALLATION, TO VERIFY DESIGN INTENT OF THIS PROJECT & FUTURE PROJECTS IN THIS BUILDING. CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT FOR SHUT-DOWNS AND DISTURBANCES NECESSARY TO PERFORM DEMOLITION AND NEW WORK IN THIS AREA. NO SHUT-DOWN OR DISTURBANCES TO EXISTING SERVICES SHALL BE ALLOWED WITHOUT PRIOR APPROVAL. CONTRACTOR IS TO MAKE ALL FINAL CONNECTIONS TO FIXTURES AND EQUIPMENT NOT SHOWN ON THE DRAWINGS. UNLESS OTHERWISE NOTED, BALANCING VALVES SHOWN ARE TO BE SET AT 0.5 GPM. DURING CONSTRUCTION, CONTRACTOR SHALL NOTE THAT THERE MAY BE ASBESTOS INSULATION ABOVE THE EXISTING PLASTER CEILINGS THAT HAS NOT YET BEEN REMOVED BY UVA, AND SHOULD CONSULT WITH UVA UPON DISCOVERY OF ANY ASBESTOS PRIOR TO PROCEEDING WITH CONSTRUCTION IN ORDER TO HAVE ANY DISCOVERED ASBESTOS SAFELY REMOVED BY APPROPRIATE ABATEMENT PERSONNEL.
MARK DATE DESCRIPTION

2.

10

12

3.

4.

5.

Architect and Engineer Name and LOGO

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

MEP ENGINEERS

STRUCTURAL ENGINEER

L
4

6.

7.

ELEV TEAM RM 1
3481
2"V

8.

3502

STAIR #6
3503

5
X - 4"S

X-2" SAN UP 2"V

STOR
3482
1

PLAN NOTES:
CONNECT NEW 4" SAN TO EXISTING 4" SAN.
REVISIONS A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO.

4"S

2
X - 3"SAN 4"SAN 4" S DN 4" SAN DN

CONNECT NEW 3" SAN TO EXISTING 3" SAN.

3/4"DCW

3 4 5

CONNECT NEW 3/4" DCW TO EXISTING 3/4" DCW. VALVE AND CAP WITH RETURN BY-PASS FOR PHASING OF CONSTRUCTION. CONNECT NEW 4" STORM TO EXISTING 4" STORM.

X - 4"SAN

TEAM RM 3
3484

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

TEAM RM 2
BUILDING

NAME STREET

3485

3" SAN DN

CITY STATE/ZIP

PROJ. CODE #

M
3"SAN X - 3"SAN 3/4"DCW X-3/4" DHW DN X-1/2" DHR DN X-3/4" DCW DN

PIMS # WORK ORDER # UVA PROJ. MGR PROJECT LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

FACULTY 1
3487

2"V X - 3"SAN

TEAM RM 4
3488

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

CORRIDOR
3480C

X-4" SAN UP

TRUE NORTH

PROJECT NORTH

CORRIDOR
X - 4"SAN 3/4"DCW

X-4" SAN UP

EE-1 BARRINGER TP-1 BARRINGER ANNEX X-3" SAN UP


BFP

FACULTY 4
3492

MECH
3490
X-3" SAN UP 3/4"DCW

FD-1 2" V DN

FACULTY 3
3491

DN UP

SEE MECH. DWG FOR CONTINUATION X - 4"SAN X - 2"SAN X-2" SAN UP

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

EHW 1

3480D

O
X-4" SAN UP X-4" SAN DN DAVIS MCINTIRE

SEAL

DESIGNED BY

1 P1.30 P1.34

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA E


1/4" = 1'-0"

DRAWN BY CHECKED BY DATE

WS WS CTC 11/16/12

4'

2'

0'

4'

8'
DRAWING

FILE NAME DRAWING NO.

P1.34
OF SHEET NUMBER

WEST COMPLEX KEY PLAN


C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt 11/21/2012 9:56:42 AM

DRAWING TITLE

PROJECT TITLE

ENLARGED 3RD FLOOR PLUMBING PLAN - AREA E

X-4" V 1-1/2" V (E)2" V 4" V 2" V 1-1/2" V S-1 FD-1 2" SAN 3" SAN 2" V S-2 1-1/2" V 2" SAN WC-1 L-1 2" SAN 4" SAN 4" SAN X-4" SAN FOR CONTINUATION SEE PLANS 4" SAN FOR CONTINUATION SEE FLOOR PLANS 4" SAN 2" SAN 4" SAN 2" SAN 4" SAN FOR CONTINUATION SEE PLANS WC-1 2" V 2" V

FOR CONTINUATION SEE FLOOR PLANS 1-1/2" V L-1

2" V

Architect and Engineer Name and LOGO

X-4" SAN X-3" V

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

MEP ENGINEERS

WC-1

STRUCTURAL ENGINEER

CO

7 P4.01

PLUMBING SANITARY RISER TOILET ROOM 3373

4 P4.01

PLUMBING SANITARY RISER TOILET ROOM 3367A

1 P4.01

PLUMBING SANITARY RISER TOILET ROOM 3340


MARK DATE DESCRIPTION

1-1/2" V

1-1/2" V

2" V
REVISIONS

2" V 2" V 1-1/2" V 1-1/2" V 2" V FD-1 3" SAN S-1 4" SAN 4" SAN 2" SAN 1-1/2" V X-3" V 2" V X-4" SAN

A/E CON. NO. CONTRACTORS A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET CITY BUILDING STATE/ZIP

L-1 WC-1

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

WC-1 2" SAN 3" SAN S-1

2" SAN

PROJ. CODE #

2" SAN 4" SAN


PROJECT

PIMS # WORK ORDER # UVA PROJ. MGR LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

5 P4.01

PLUMBING SANITARY RISER TOILET ROOM 3368

2 P4.01

PLUMBING SANITARY RISER TOILET ROOM 3361A

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

TRUE NORTH

PROJECT NORTH

(E)4" SAN 1-1/2" V

(E)3" V

1-1/2" V

2" V 2" V 1-1/2" V 2" V 2" V 1-1/2" V

2" V

SH-1 2" SAN S-1 1-1/2" V 2" SAN WC-1 1-1/2" V S-1 2" SAN 4" SAN 3" SAN 2" SAN 2" SAN 4" SAN S-1
SEAL

FD-1 S-1 WC-1

S-1 4" SAN

2" SAN

DESIGNED BY DRAWN BY

6 P4.01

PLUMBING SANITARY RISER TOILET ROOM 3369

3 P4.01

PLUMBING SANITARY RISER TOILET ROOM 3362A


DRAWING

CHECKED BY DATE FILE NAME DRAWING NO.

Designer Author Checker 11/16/12

P4.01
OF SHEET NUMBER

C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt

11/21/2012 9:56:46 AM

DRAWING TITLE

PROJECT TITLE

PLUMBING SANITARY RISER DIAGRAMS

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

3/4" DCW 1/2" DCW (E)3/4" DCW 3/4" DCW 1/2" DCW 12" DCW 1/2" DHW 1" DCW 3/4" DHW 1/2"DCW (E)3/4" DHW 1" DCW 1/2" DHW 1-1/4" DHW

1-1/4" DHW 3/4" DHW

1" DCW

1-1/4" DHW

3/4" DCW 1/2" DHW 1" DCW X-3/4" DCW


Architect and Engineer Name and LOGO ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

L-1

S-4 WC-1 1/2" DHW L-1 1/2" DHW 1/2" DCW 1" DCW 1/2" DCW WC-1

MEP ENGINEERS

STRUCTURAL ENGINEER

7 P4.02

PLUMBING WATER RISER TOILET ROOM 3373

4 P4.02

PLUMBING WATER RISER TOILET ROOM 3367A


1 P4.02

PLUMBING WATER RISER TOILET ROOM 3340

1-1/4" DHW 3/4" DCW


MARK DATE DESCRIPTION

1-1/4" DCW 1/2" DCW 1" DCW 1/2" DHW 1" DCW 1" DHW 1/2" DCW 1/2" DHW L-1 1/2" DCW 1/2" DHW S-1 WC-1 X-2-1/2" DHW X-1-1/2" DHW X-1-1/2" DCW X-1-1/2" DCW X-1-1/4" DHW L-1 WC-1 3/4" DCW 3/4" DCW
CONTRACTORS REVISIONS

1" DCW

1/2" DCW

1/2" DHW
A/E CON. NO. A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET CITY BUILDING STATE/ZIP

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

PROJ. CODE #

5 P4.02

PLUMBING WATER RISER TOILET ROOM 3368

2 P4.02

PLUMBING WATER RISER TOILET ROOM 3361A


PROJECT

PIMS # WORK ORDER # UVA PROJ. MGR LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

TRUE NORTH

PROJECT NORTH

1/2" DHW 3/4" DCW 3/4" DHW 1/2" DCW 3/4" DCW 1-1/4" DCW 1-1/4" DCW 1/2" DHW

1/2" DCW

1/2" DHW 1/2" DCW

1-1/4" DHW 3/4" DHW SH-2 L-1 1" DCW L-1 WC-1 WC-1

1/2" DCW 1/2" DHW 1" DCW 1-1/4" DCW S-1

1-1/4" DHW

6 P4.02

PLUMBING WATER RISER TOILET ROOM 3369

3 P4.02

PLUMBING WATER RISER TOILET ROOM 3362A

SEAL

DESIGNED BY DRAWN BY CHECKED BY DATE FILE NAME DRAWING NO. DRAWING

Designer Author Checker 11/16/12

P4.02
OF SHEET NUMBER

C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt

11/21/2012 9:56:49 AM

DRAWING TITLE

PROJECT TITLE

3/4" DCW

PLUMBING WATER RISER DIAGRAMS

3/4" DCW

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

System No. C-AJ-5091


C
R

US

Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115

F Rating 2 Hr T Ratings 0 and 1 Hr (See Items 2 and 4) L Rating At Ambient 4 CFM/Sq Ft L Rating At 400 F Less Than 1 CFM/Sq Ft

PIPE

1 GROUT SLOPE TO DRAIN INLET

2D D (DIAMETER)

Architect and Engineer Name and LOGO

5B

PIPE INSULATION

STRUCTURAL CONCRETE FLOOR

ARCHITECT:

LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

1
STRAINER EXTENSION BACKING MATERIAL AS REQUIRED DRAIN INLET STRAINER CORED HOLE 1 2

MEP ENGINEERS

STRUCTURAL ENGINEER

SEALANT

5A

A
9 P5.00

WITH PIPE INSULATION 3

RATED ASSEMBLY UL PENETRATION_


1/4" = 1'-0"

4 3
SECTION A-A
PIPE RISER CLAMP WHERE APPLICABLE DRAIN BODY MUST BE STYLE WITH SEEPAGE COLLAR LEGEND SEALANT BACKING MATERIAL AS REQUIRED 1 DRAINLINE 2

System No. C-AJ-1421


C
R

US

Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115

F Rating - 2 and 3 Hr (See Item 4B) T Rating = 0 Hr

4B A

4B

A 3 SECTION A-A

4A

7 P5.00

NON-INSULATED FLOOR UL PENETRATION


1" = 1'-0"
SEQUENCE OF OPERATION: 1. 2-POSITION CONTROL VALVE SHALL BE CONNECTED TO THE BAS AND CONTROLLED BY THE TEMPERATURE TRANSMITTER AT THE HEAT EXCHANGER. 2. WHEN TEMPERATURE TRANSMITTER SENSES WATER TEMPERATURE GREATER THAN 57F, CONTROL VALVE OPENS. 3. WHEN TEMPERATURE TRANSMITTER SENSES WATER TEMPERATURE BELOW 53 F, CONTROL VALVE CLOSES.
(BY MECH.CONTRACTOR) HWS

DCW BRANCH PIPING WITH PIPE INSULATION POLYESTER OR VINYLESTER 1-1/2" X 1-1/2" X 6" LONG CHANNEL FRAMING WITH CONCRETE INSERTS

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 6 in. (152 mm). See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Metallic Sleeve - (Optional) Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces. 3. Through-Penetrant - One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe, tube or conduit and periphery of opening shall be min 0 in. (0 mm) (point contact) to max 5-3/8 in. (137 mm). Pipe or conduit to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or conduits may be used: A. Steel Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing. E. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel conduit. F. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT). 4. Firestop System - The firestop system shall consist of the following: A. Packing Material - Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. For 3 Hr rated assemblies, a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the concrete/pipe interface at the point contact location on the top surface of floor and on both surfaces of wall.

1. Floor or Wall Assembly Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 29 in. (737 mm). See Concrete Blocks (CAZT) category in the Fire Resistance directory for names of manufacturers. 2. Metallic Sleeve (Optional) Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. (76 mm) above floor or beyond both surfaces of wall. If the steel sleeve extends beyond the top surface of the floor or both surfaces of the wall, the T Rating of the firestop system is 0 hr. 2A. Sheet Metal Sleeve (Optional) - Max 6 in. (152 mm) diam, min 26 ga galv steel provided with a 26 ga galv steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor. 2B. Sheet Metal Sleeve (Optional) - Max 12 in. (305 mm) diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor. 3. Through Penetrants One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or tubing may be used: A. Steel Pipe Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. 4. Pipe Covering Min 1/2 in. (13 mm) to max 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m) glass fiber units jacketed on the outside with an all-service jacket. Longitudinal joints sealed with metal fasteners or factory-applied, self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated pipe and the edge of the periphery of the opening shall be min 1/2 in. (13 mm) to max 12 in. (305 mm). When thickness of pipe covering is less than 2 in. (51 mm), the T Rating for the firestop system is 0 hr. See Pipe Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4A. Pipe Covering (Not Shown) As an alternate to Item 4, max 2 in. (51 mm) thick cylindrical calcium silicate (min 14 pcf or 224 kg/m) units sized to the outside diam of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 18 AWG stainless steel wire spaced max 12 in. (305 mm) OC. The annular space shall be min 1/2 in. (13 mm) to max 12 in. (305 mm). 5. Firestop System The firestop system shall consist of the following: A. Packing Material Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* Sealant Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall.

MARK

DATE

DESCRIPTION

APPROVED NON-SHRINK CONCRETEEPOXY GROUT IN ANNULAR CORE SPACE & SURFACE SLOPE. SHEET METAL CLOSURE ANCHORED TO CONCRETE FLOOR. SAFING MATERIAL 1-1/2 x DRAIN DIAMETERS (8) MINIMUM STUD PIN SUPPORTS.

WITHOUT PIPE INSULATION 3

CONTRACTORS

NOTE: WHERE FLOOR IS FIRE RATED, COMBINATION OF SEALANT, BACKING MATERIAL AND INSULATION SHALL MEET THIS RATING. REFER TO SPECIFICATION SECTION (200573) FOR FIRE STOPPING SYSTEM MANUFACTURERS.

REVISIONS A/E CON. NO. A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E

1-1/2"x3"x12" ANGLE STEEL SUPPORT EACH SIDE WITH MINIMUM (4) STUD PIN FASTENERS.

PIPE THROUGH FLOOR

CORE DRILLED FLOOR DRAIN


BUILDING

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

BUILDING NO. NAME STREET CITY STATE/ZIP

P5.00 SCALE: NONE

P5.00 SCALE: NONE

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR PROJECT LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

SEALANT PIPE INSULATION STRUCTURAL CONCRETE FLOOR SLAB


TRUE NORTH PROJECT NORTH

5 P5.00

INSULATED FLOOR UL PENETRATION


1" = 1'-0"
BACKING MATERIAL AS REQUIRED PIPE

A
1/2"

FRP THREADED ROD

NOTES: (1) TEST VALVE WITH 6" NIPPLE ANDCAP. TEST VALVE TO BE 1/4" SIZE, LOCATE TEST VALVE AT SIDE OF PIPE. (2) ANCHOR DRAIN PIPE TO THE FLOOR (3) BALANCE SHELL SIDE TO 7 GPM
XV 1-1/4" BAS

TRAP PRIMER

SEALANT

2-POSITION CONTROL VALVE BAS TT CONCENTRIC INCREASER AS REQ'D DHW TO FLOOR DRAIN (2) AIR VENT

SINGLE TO MULTI-UNIT: ONE DISTRIBUTION LINE TO EACH FLOOR DRAIN

BACKING MATERIAL AS REQUIRED PRIMER DISTRIBUTION UNIT

PIPE

1/2" COPPER

WITHOUT PIPE INSULATION FIBERGLASS CLEVIS HANGER

DHW

(1) (BY MECH.CONTRACTOR) HWR 1-1/4"

(3)

NOTE: WHERE WALL IS FIRE RATED, COMBINATION OF SEALANT, BACKING MATERIAL AND INSULATION SHALL MEET THIS RATING. REFER TO SPECIFICATION SECTION (200573) FOR FIRE STOPPING SYSTEM MANUFACTURERS. TO FLOOR DRAINS

SEAL

DESIGNED BY DRAWN BY CHECKED BY DATE FILE NAME DRAWING

WS WS CTC 11/16/12

WATER TO WATER HEAT EXCHANGER

TRAP PRIMER

PIPE THROUGH INTERIOR WALL

PIPE HANGER

DRAWING NO.

P5.00 SCALE: NONE

P5.00 SCALE: NONE

P5.00 SCALE: NONE

P5.00 SCALE: NONE

P5.00
OF SHEET NUMBER

C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt

11/21/2012 9:56:52 AM

DRAWING TITLE

PROJECT TITLE

PLUMBING DETAILS

FIXTURE AND EQUIPMENT PIPING


NUMBER FIXTURE WASTE (IN)
WC-1 WATER CLOSET 4

VENT (IN)
2

TRAP (IN)
-

COLD WATER (IN)


1

HOT WATER (IN)


-

TEMPERED WATER (IN)


-

GPF/GPM

REMARKS

1.28

FLOOR MOUNTED, FLUSH VALVE, ACCESSIBLE

L-1

LAVATORY

1-1/2

1-1/2

1-1/4

1/2

1/2

0.5

WALL HUNG

S-1 S-2 S-3 S-4 CS-1

EXAM SINK SPIN LAB WORK SINK HAND SINK PANTRY SINK CLINICAL SERVICE SINK

1-1/2 1-1/2 1-1/2 1-1/2 4

1-1/2 1-1/2 1-1/2 1-1/2 2

1-1/4 1-1/4 1-1/4 1-1/4 -

1/2 1/2 1/2 1/2 3/4

1/2 1/2 1/2 1/2 -

1.0 1.0 1.0 1.0 1.6

SINGLE COMPARTMENT, INTEGRATED WITH COUNTER TOP S.S., SINGLE COMPARTMENT, COUNTER MOUNTED, CUSTOM S.S. WORKTABLE S.S., SINGLE COMPARTMENT, COUNTER MOUNTED S.S., SINGLE COMPARTMENT, COUNTER MOUNTED VITREOUS CHINA, FLOOR MOUNT, FLUSH VALVE
Architect and Engineer Name and LOGO ARCHITECT: LOUVIERE, STRATTON & YOKEL, LLC 8484 GEORGIA AVE, SUITE 650 SILVER SPRING, MD 20910 (301) 588-1500 AFFILIATED ENGINEERS 401 N. WASHINGTON ST, SUITE 400 ROCKVILLE, MD 20850 (301)468-7766 DUNBAR MILBY WILLIAMS PITTMAN 110 3rd ST CHARLOTTESVILLE, VA 22902 (434)293-5171

SH-1 SH-2

SHOWER VALVE SHOWER VALVE

2 2

1-1/2 1-1/2

2 2

1/2 1/2

1/2 1/2

1.5 1.5

SHOWER STALL BY OTHERS ACCESSIBLE, SHOWER STALL BY OTHERS

MEP ENGINEERS

STRUCTURAL ENGINEER

MS-1

JANITOR'S SINK

1-1/2

3/4

3/4

FLOOR MOUNTED, TERRAZO, 24x24x10

EE-1 FD-1 TP-1

EMERGENCY EYEWASH FLOOR DRAIN - GENERAL TRAP PRIMER

3 -

1-1/2 -

1/2

1/2 -

0.5 -

WALL MOUNTED CAST-IRON BODY, NICKLE BRONZE GRATE, TRAP PRIMER CONNECTION WALL MOUNTED

PLUMBING EQUIPMENT SCHEDULE


EQUIPMENT TAG
EWH 1

MARK

DATE

DESCRIPTION

DESCRIPTION

DETAIL

CAPACITY

HP

VOLTAGE

WEIGHT LB

REMARKS

EMERGENCY POWER

NOTES

EWH 2

TANKLESS ELECTRIC WATER HEATER DOMESTIC HOT WATER HEAT EXCHANGER RECIRCULATION PUMP

0.5 GPM @ 48 F RISE

2.4 KW

120

HOT WATER RETURN LINE RE-HEATER FOR LAB HWR BASIS OF DESIGN: EEMAX SINGLE POINT MODEL SP3512 DOMESTIC HOT WATER LINE HEATING FROM 85 F TO 105 F 7 GPM SHELL SIDE CAPACITY @ 140 F IN-LINE CARTRIDGE TYPE, AQUASTAT CONTROLLED

HX 1

5 GPM @ 20 F RISE 50 MBH TOTAL 5 GPM @ 22 FT/HD

120

1,2

RCP 1

120/1

1
CONTRACTORS

REVISIONS A/E CON. NO. A/E TASK NO. CONS. CONTR. CONS. WORK PRIME A/E SUB A/E BUILDING NO. NAME STREET CITY BUILDING STATE/ZIP

TANKLESS ELECTRIC WATER HEATER

0.5 GPM @ 33 F RISE

2.4 KW

120

HOT WATER RETURN LINE RE-HEATER FOR LAB HWR BASIS OF DESIGN: EEMAX SINGLE POINT MODEL SP2412

NOTES: 1. REQUIRES ELECTRICAL CONNECTIONS. COORDINATE WITH DIVISION 16. 2. PROVIDE 36" STAND FOR HEAT EXCHANGERS FOR ADEQUATE CLEARANCES OF STEAM TRAPS AND DRAINS.

LSY ARCHITECTS AEI 1174


MED CTR WEST COMPLEX 1300 JEFFERSON PARK AVE CHARLOTTESVILLE VIRGINIA 22903 209-B1119-000

PROJ. CODE # PIMS # WORK ORDER # UVA PROJ. MGR PROJECT LSY PROJ. NO. LSY PROJ. MGR SUBMISSION SUB. DATE

P02804 1242906 KRISTINE VEY 11016 ROBERT WORTHING FINAL DOCUMENTS 11-16-12

TRUE NORTH

PROJECT NORTH

WEST COMPLEX - CRU AND NEUROSURGERY CLINICS

SEAL

DESIGNED BY DRAWN BY CHECKED BY DATE FILE NAME DRAWING NO. DRAWING

WS WS CTC 11/16/12

P6.00
OF SHEET NUMBER

C:\AEI\Revit Projects\2012\11679-00 UVA\11697-00 UVA-CRC_gsimmons.rvt

11/21/2012 9:56:54 AM

DRAWING TITLE

PROJECT TITLE

PLUMBING SCHEDULES