PAC-E Series Numerical Protection Relays

TECHNICAL SPECIFICATIONS (V2.00)

PAC-E100/E110 (Over Current & Earth Fault Relay)

P&C Technologies Co., Ltd.


VER 1.0

PAC-E100 (Over Current & Earth Fault Relay)

REVISIONS
REV 1.00 2.00 Date 2005-08-11 2006-03-20 Description/Reason 1.Initial specification 1.E110 functions are added. 2.Frequency Tracking function is deleted. 3.THD measurement function are deleted.

2/24

PAC-E100 (Over Current & Earth Fault Relay)

1. General Data 1.1 Power Supply


Input Voltage 110~220 VAC20 %, 50/60 Hz 80~300 VDC 19~28 VDC less then 30 VA

Power Consumption

1.2 Current Input


Nominal Frequency Phase CT Secondary Ground CT Secondary Input Range Burden Current Withstand 50/60 Hz 5 A or 1A 5 A or 1A 0.1~250 A(5 A rated), 0.01~50 A(1 A rated) less then 0.5 VA per phase 1 sec at 100 times rated , 2 sec at 20 times rated , continuous at 3 times rated

1.3 Contact Input


Number Voltage Range On/Off Voltage Level 4, configurable 250 VDC maximum Control Voltage On Level Off Level Recognition Time less then 10 msec 24/48 VDC 19 V 14 V 110~220 VDC 80 V 60 V

1.4 Contact Output


Number Make and Carry Breaking Capacity 2 NO, 2 NC, configurable 16 A continuous, 250 VAC 30 A, 0.5 sec, 125 VDC, resistive load 0.5 A, L/R of 25 msec, 125 VDC

1.5 Communication Interface


Front Panel Rear Panel RS-232C, 19200 bps (fixed), Modbus protocol RS-232C, physically identical port to front panel RS-232C Galvanic isolated RS-485, 300~38400 bps Protocol : Modbus, DNP3.0, IEC60870-5-103

1.6 Type Test


Insulation Oscillatory Transient Surge Immunity Fast Transient Electrostatic Discharge RFI Susceptibility Vibration Shock IEC 60255-5, ANSI/IEEE C37.90.0 IEC 60255-22-1, ANSI/IEEE C37.90.1 IEC 60255-22-5 class IEC 60255-22-4 class , ANSI/IEEE C37.90.1 IEC 60255-22-2 class IEC 60255-22-3 class , ANSI/IEEE C37.90.2 IEC 60255-21-1 class IEC 60255-21-2 class

3/24

PAC-E100 (Over Current & Earth Fault Relay)

Seismic Humidity(non-condensing)

IEC 60255-21-3 class I, IEC60068-3-3 56days, 95 %, +40 C, IEC60068-2-78

1.7 Environmental
Carrying and Storage Operating Temperatures Altitude -25 C~+70 C -25 C~+70 C up to 2000 m

2. Protection 2.1 Definite Time Overcurrent(50_1,50_2,50N_1,50N_2)


Setting Pickup Current Operating Delay Accuracy Pickup Current Operating Time Dropout Level Dropout Time Information Pickup 0.50~100.00 A, 0.05 step*) 0.00~60.00 sec, 0.01 step

2 % of setting value or 70 mA 3 % or 35 msec of setting value, @ 2xpickup current 96~98 % of pickup current less than 40 msec

Operation

50_1_PKP_A, 50_1_PKP_B, 50_1_PKP_C, 50_1_PKP_OR 50_2_PKP_A, 50_2_PKP_B, 50_2_PKP_C, 50_2_PKP_OR 50N_1_PKP, 50N_2_PKP 50_1_OP_A, 50_1_OP_B, 50_1_OP_C, 50_1_OP_OR 50_2_OP_A, 50_2_OP_B, 50_2_OP_C, 50_2_OP_OR 50N_1_OP, 50N_2_OP

*)

for 1A rated, all value divided by 5

2.2 Inverse Time Overcurrent(51,51N)


Setting Pickup Current Time Multiplier Trip Characteristic Curve IEC 60255-3, ANSI/IEEE, KEPCO 0.50~100.00 A, 0.05 step*) 0.01~10.00, 0.01 step

K + C T = TM (sec ) L G 1 GS
T K,C,L,M G GS TM : Trip time in second : Constants : Current input : Pickup current setting : Time multiplier Curve K

4/24

PAC-E100 (Over Current & Earth Fault Relay)

IEC Normal Inverse 0.14 0.02 IEC Very Inverse 13.50 1.00 IEC Extremely Inverse 80.00 2.00 IEC Long Inverse 120.00 1.00 ANSI Inverse 8.9341 2.0938 ANSI Short Inverse 0.2663 1.2969 ANSI Long Inverse 5.6143 1 ANSI Moderately Inverse 0.0103 0.02 ANSI Very Inverse 3.922 2 ANSI Extremely Inverse 5.64 2 ANSI Definite Inverse 0.4797 1.5625 KEPCO Normal Inverse 0.11 0.02 KEPCO Very Inverse 39.85 1.95 Trip time for G/Gs 20 are identical to those for G/Gs = 20. Accuracy Pickup Current Operating Time Dropout Level Dropout Time Information Pickup Operation
*)

0.00 0.00 0.00 0.00 0.17966 0.03393 2.18592 0.0228 0.0982 0.02434 0.21359 0.42 1.08

2 % of setting value or 70 mA 3 % or 35 msec of setting value 96~98 % of pickup current less than 40 msec for instantaneously reset setting

51_PKP_A, 51_PKP_B, 51_PKP_C, 51_PKP_OR, 51N_PKP 51_OP_A, 51_OP_B, 51_OP_C, 51_OP_OR, 51N_OP

for 1A rated, all value divided by 5

2.3 Negative Phase Sequence Overcurrent (46)


Setting Pickup Current Operating Delay Accuracy Pickup Current Accuracy Operating Time Accuracy Dropout Level Dropout Time Information Pickup Operation
*)

0.50~100.00 A, 0.05 step*) 0.00~180.00 sec, 0.01 step

2 % of setting value or 70 mA 3 % or 35 msec of setting value, @ 2xpickup current 96~98 % of pickup current less than 40 msec

46_PKP 46_OP

for 1A rated, all value divided by 5

2.4 Undercurrent (37)


Setting Pickup Current Operating Delay Accuracy Pickup Current Accuracy Operating Time Accuracy Dropout Level 0.10~5.00 A, 0.05 step*) 0.00~180.00 sec, 0.01step

2 % of setting value or 70 mA 3 % or 35 msec of setting value, @ 0xpickup current 102~104 % of pickup current

5/24

PAC-E100 (Over Current & Earth Fault Relay)

Dropout Time Information Pickup Operation


*)

less than 40 msec

37_PKP_A, 37_PKP_B, 37_PKP_C, 37_PKP_OR 37_OP_A, 37_OP_B, 37_OP_C, 37_OP_OR

for 1A rated, all value divided by 5

2.5 Thermal Overload (49)


Setting K-Factor for IEC 60255-8 Time Constant( ) Thermal Alarm 0.10~4.00, 0.01 step 1.0~999.9 min, 0.1 step 50~100 %, 1 step

Trip Characteristic Curve(for I/k IN <= 8) - With pre-load

-Without pre-load

I I P kI k I N N t = ln 2 I kI 1 N
2

[min]

I 2 k IN t = ln [min] 2 I 1 kI N

: : I : : IP k : IN : Thermal State Calculation

Trip time Temperature rise time constant Load current Pre-load current Setting factor Nominal current

m+1

I = kI N

[1 exp(t / )] + m exp(t / )

being calculated every 100ms I means True RMS

Accuracy Pickup Current Accuracy Operating Time Accuracy Dropout Level Information Alarm Trip

2 % of setting value or 70 mA 10 % or 2 sec of setting value 98~100 % of thermal trip setting

49_ARM 49_TRIP

2.6 Auto-Reclosing(79)
Setting Shot Number Prepare Condition Cycle Start Condition 1~4, 1 step EasyLogic Operand EasyLogic Operand

6/24

PAC-E100 (Over Current & Earth Fault Relay)

Prepare Time Discriminating Time Reclaim Time 1st ~ 4th Shot Delay

0.05~200.00 sec, 0.01 step 0.01~5.00 sec, 0.01 step 0.01~350.00 sec, 0.01 step 0.01~300.00sec, 0.01 step

Command CB Close Command CB Final Trip Command Information Auto-Reclosing Ready Auto-Reclosing In Progressing Auto-Reclosing Fail(Final Trip) Reclosing Cycle 1st Delay Reclosing Cycle 2nd Delay Reclosing Cycle 3rd Delay Reclosing Cycle 4th Delay

79_CLS_CMD 79_OPN_CMD

79_READY 79_IN_PROG 79_FAIL 79_DELAY_1 79_DELAY_2 79_DELAY_3 79_DELAY_4

2.7 Circuit Breaker Failure(50BF)


Setting Trip Relay Pickup Current(CB Closed) Operating Delay(Trip Timer) Accuracy Pickup Current Operating Time Dropout Time Information Operation
*)

TS1, TS2, TS3, TS4 0.50~5.00 A, 0.05 step*) 0.00~60.00 sec, 0.01 step

3 % of setting value 20 msec of setting value less than 40 msec, after trip relay reset

50BF_OP

for 1A rated, all value divided by 5

2.8 Cold Load Pick-up(COLD_LD)


Setting Current Detection Level OP Delay Reset Delay Accuracy Pickup Current Information Pickup Operation
*)

0.50~2.50 A, 0.05 step*) 0~1000 sec, 1 step 0~1000 sec, 1 step

3 % of setting value

COLD_LD_PKP COLD_LD_OP

for 1A rated, all value divided by 5

2.9 Inrush Detection(I2/I1)


Setting 2nd Harmonic of I2/I1 10~100 % , 1 step

7/24

PAC-E100 (Over Current & Earth Fault Relay)

Operating Delay Minimum Current(at least one phase)

0.00~60.00 sec, 0.01step 0.50~2.50 A, 0.05 step*)

2nd Harmonic Measuring Time Accuracy Pickup Current Operating Time Dropout Time Information Operation
*)

1/2 cycle

3 % of setting value 20 msec of setting value less than 40 msec

I2/I_OP

for 1A rated, all value divided by 5

3.Control 3.1 Circuit Breaker Control


Setting Trip Pulse Time Close Pulse Time 0.1~5.0 sec, 0.1 step 0.1~5.0 sec, 0.1 step

3.2 EasyLogic
Contact Output, LED Logic OR8(8 input OR) , HALF-OR8(Non inverting 4 input & inverting 4 input OR) , AND8(8 input AND) , HALF-AND8(Non inverting 4 input & inverting 4 input AND) Reference PAC-E100 Logic Input Diagram Self(latched until delay timer is expired) , Manual(latched until annunciator reset is issued) 0.00~60.00sec(0.01sec step) Last fault only is annuciated.

Input Reset Type Self Reset Delay Conditional automatic reset for LED Contact Input Function

Not Connected , CB Open , CB Close , Remote Annunciator Reset , Protection Block , General Input , TCS Input

8/24

PAC-E100 (Over Current & Earth Fault Relay)

Logic Design (Contact Output & LED)

Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8 Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8 Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8 Input#1 Input#2 Input#3 Input#4 Input#5 Input#6 Input#7 Input#8

Reset Type = Self

Contact Out #1 ~ #4

0.00 ~ 60.00 LED#1~#4 Reset Type = Manual S Q R


Annunciator

Logic

<PAC-E100 Logic Input>


Input Group Logic Input L_OFF L_ON CB_OPEN_CTL CB_CLOSE_CTL 79_OPEN_CMD 79_CLOSE_CMD CONT_IN #1 CONT_IN #4 SYS_ERR PROT_PKP_OR PROT_OP_OR 50_1_PKP_OR 50_1_PKP_A 50_1_PKP_B 50_1_PKP_C 50_1_OP_OR 50_1_OP_A 50_1_OP_B 50_1_OP_C 50_2_PKP_OR 50_2_PKP_A Description Logic 0 Logic 1 CB Open Control(Local or Remote) CB Close Control(Local or Remote) Auro-Reclosing CB open command Auto-Reclosing CB close command Contact input#1 status Contact input#4 status Self-diagnosis error is occurred Any protection element is picked up Any protection element is operated At least 1 phase of 50_1 is picked up Phase A of 50_1 is picked up Phase B of 50_1 is picked up Phase C of 50_1 is picked up At least phase of 50_1 is operated Phase A of 50_1 is operated Phase B of 50_1 is operated Phase C of 50_1 is operated At least 1 phase of 50_2 is picked up Phase A of 50_2 is picked up

CB control

Contact inputs System Protection elements

9/24

PAC-E100 (Over Current & Earth Fault Relay)

50_2_PKP_B 50_2_PKP_C 50_2_OP_OR 50_2_OP_A 50_2_OP_B 50_2_OP_C 51_PKP_OR 51_PKP_A 51_PKP_B 51_PKP_C 51_OP_OR 51_OP_A 51_OP_B 51_OP_C 50N_1_PKP 50N_1_OP 50N_2_PKP 50N_2_OP 51N_PKP 51N_OP 37_PKP_OR 37_PKP_A 37_PKP_B 37_PKP_C 37_OP_OR 37_OP_A 37_OP_B 37_OP_C 49_ALARM 49_OP 46_PKP 46_OP 79_READY 79_IN_PROG 79_FAIL 50BF_OP COLD_LD_PKP COLD_LD_OP I2/I_OP

Phase B of 50_2 is picked up Phase C of 50_2 is picked up At least phase of 50_2 is operated Phase A of 50_2 is operated Phase B of 50_2 is operated Phase C of 50_2 is operated At least 1 phase of 51 is picked up Phase A of 51 is picked up Phase B of 51 is picked up Phase C of 51 is picked up At least phase of 51 is operated Phase A of 51 is operated Phase B of 51 is operated Phase C of 51 is operated 50N_1 is picked up 50N_1 is operated 50N_2 is picked up 50N_2 is operated 51N is picked up 51N is operated At least 1 phase of 37 is picked up Phase A of 37 is picked up Phase B of 37 is picked up Phase C of 37 is picked up At least phase of 37 is operated Phase A of 37 is operated Phase B of 37 is operated Phase C of 37 is operated 49 is alarmed 49 is operated 46 is picked up 46 is operated 79 ready 79 is in progressing 79 is failed 50BF is operated Cold load pickup is picked up Cold load pickup is operated 2nd harmonic Inrush condition is operated

10/24

PAC-E100 (Over Current & Earth Fault Relay)

4. Monitoring 4.1 Self-Diagnosis


Memory Setting After power-on reset, RAM pattern test error When power-on reset or setting is changed, Non-volatile memory setting is checked. Setting value is out of boundary Total check-sum Error A/D running counter stop , A/D reference input is out of boundary Each analog input calibration factor is out of boundary , Ttotal check-sum error Only One DI is used for TSC. If contact input function setting set to TCS input, then trip circuit supervision function is enabled. TCS DI Input is checked every 600 msec. If consecutive 100 is failed, TCS fail annunciation is reported. After TSC fail is cleared, the failure annunciation is reset automatically.

A/D Converter Auto-Calibration

Trip Circuit Supervision

5. Measurement
Current
Phase, Ground Current RMS Input Range Accuracy 0.5~250 A*) 2 %(0.5~1 A), 0.5 %(1~6 A) *)

Sequence Current
Positive/Negative/Zero Sequence Current RMS

Frequency
Range Accuracy
*)

40 Hz~70 Hz, Phase A Current 0.03 Hz at Nominal current input

for 1A rated, all value divided by 5

6. Record 6.1 Events(Include Fault Information)


Storage Capacity Data Max. 128 events with 1 msec time resolution System reset , Annuciator reset , Setting changed , Clear event record , Clear waveform recording , Protection pickup/operate/release etc. Analog input information(current rms) are recorded when a protection element triggered.

6.2 Waveform
Storage Capacity Record Type(block*cycle) Trigger Position Max. 20 10 * 6(300 msec, 50Hz) or 20 * 3 , for 16 sample per cycle 10 * 12, 20 *6, for 8 sample per cycle 0 ~ 99%

11/24

PAC-E100 (Over Current & Earth Fault Relay)

Trigger Source Data

Protection trip , Change of contact input status Current sample(IA, IB, IC, IN) , Contact input/Output status , Enabled protection status

6.3 CB Trip Counter


Trip counter is accumulated in non-volatile memory after only protection trip is issued. Trip Counter range are 0 to 65535, free running(roll-over). This counter can be edit by local front key operation.

7.Communication 7.1 RS-232


Front Panel Rear Panel 19200 bps (fixed), Modbus protocol Physically identical port to front panel RS-232C

7.2 RS-485
Galvanic isolated BPS Protocol 300~38400 bps Modbus, DNP3.0, IEC60870-5-103

8.PC Software
Relay setting upload and download. Event upload from relay and save to file. Waveform upload from relay and analysis in PC supported.

12/24

PAC-E100 (Over Current & Earth Fault Relay)

9. Mounting and Dimensions


Panel Mounting, Draw-out type

5 8 4 S R 6 1 7 1 8 1 9 1 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2

2 3 2 S R 1 2 3 4 5 6 7 8 9 0 1 1 1 2 1 3 1 4 1 5 1

13/24

PAC-E100 (Over Current & Earth Fault Relay)

Rear Terminal Block


PAC-E110
No 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Description IA+ IB+ IC+ IN+ TS1_COM TS2_COM TS3_COM TS4_COM TS4_NC DI1_COM DI2_COM PWR+ PWRFG No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Description IAIBICINTS1_NO TS2_NO TS3_NO TS3_NC TS4_NO DI1_P DI2_P DI3_P DI4_P DI3_4_COM

14/24

PAC-E100 (Over Current & Earth Fault Relay)

10. External Connection Diagram


C B A
Aux Power AC/DC 110~220V

PAC-E110
28 29 30

PWR+ PWR-

DI1_P DI1_COM DI2-P DI2_COM DI3 P DI4 P DI3_4_COM

11 26 12 27 13 14 15 IA IB IC IN 16 1 17 2 18 3 19 4

TS1_NO TS1_COM

6 21

TS2_NO TS2_COM

7 22

TS3_NC TS3_COM TS3_NO TS4_NC TS4_COM TS4_NO

9 23 8 25 24 10

DB-9

DB-9

RS232 (front) RS485 (Rear)

<External Connection Diagram of PAC-E110>

15/24

PAC-E100 (Over Current & Earth Fault Relay)

11.Ordering Information
Power Supply CT Rated Secondary Language 125 VDC/110 VAC or 250 VDC/220 VAC 24/48 VDC 1 A or 5 A English, Turkish

16/24

PAC-E100 (Over Current & Earth Fault Relay)

12. LCD Menu Configuration


- DISPLAY DISPLAY (ENT)

STATUS

CONTAC INPUT CONTACT OUTPUT SELF DIAGNOSIS

CONT IN#1~#4 CONT OUT#1~#4 MEMORY SETTING AD CONVERTER CALIBRATION IOC1(50_1) IOC2(50_2) TOC(51) IOCG1(50N_1) IOCG2(50N_2) TOCG(51N) THERMAL(49) UC(37) NSOC(46) AREL(79)

OFF / ON DEENERGIZED / ENERGIZED FAIL / OK FAIL / OK FAIL / OK FAIL / OK FAIL / OK Pickup, Operation Pickup, Operation Pickup, Operation Pickup, Operation Pickup, Operation Pickup, Operation Alarm, Operation Pickup, Operation Pickup, Operation Ready, In Progress, Fail Operation Pickup, Operation
17/24

TRIP CIRCUIT

PROTECTION

CBFAIL(50BF) COLD LD(COLD_LD)

PAC-E100 (Over Current & Earth Fault Relay)

INRUSH(I2/I)

Operation

MEASURE

CURR(IA) CURR(IB) CURR(IC) CURR(IN) SEQ(I0) SEQ(I1) SEQ(I2)


SYSTEM INFO.

FREQUENCY TRIP COUNTER

Version Display

- SETTING/SYSTEM SETTING (ENT) Function Range (Step) 50/60 Hz 1A : 1 ~ 6000 : 1 (1) 5A : 1 ~ 6000 : 5 (1) 1A : 1 ~ 6000 : 1 (1) 5A : 1 ~ 6000 : 5 (1) 0.1 ~ 5.0s (0.1) 0.1 ~ 5.0s (0.1) DISALBE / ENABLE

SYSTEM

POWER SYSTEM

FREQUENCY PHS CT RATIO GND CT RATIO TRIP PULSE CLOSE PULSE FUNCTION

CB CONTROL

COM

18/24

PAC-E100 (Over Current & Earth Fault Relay)


DNP3.0

SLAVE ADDR BPS PROTOCOL TX DELAY LINK CONFIRM LINK RETRY LINK TIMEOUT SBO TIMEOUT WR TIME INT COLD RESTART CONT IN#1~#4

1 ~ 65534 (1) 300 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 DNP3.0 / MODBUS / IEC870 0 ~ 65000 (1) NEVER / ALWAYS / SOMETIMES 0 ~ 5 (1) 1 ~ 65000 (1) 1 ~ 65000 (1) 0 ~ 65000 (1) DISABLE / ENABLE NOT_CONNECTED / CB_OPENED / CB_CLOSED / ANNUN_RESET / PROT_BLOCK / GENERAL_INPUT OR8 / HALF_OR8 / AND8 / HALF_AND8 Reference Reference Reference Reference Reference Reference Reference Reference

CONTACT INPUT

CONTACT OUTPUT

LOGIC INPUT#1 INPUT#2 INPUT#3 INPUT#4 INPUT#5 INPUT#6 INPUT#7 INPUT#8

/ CONT OUT#1~#4

19/24

PAC-E100 (Over Current & Earth Fault Relay)

LED

RESET TYPE RESET DELAY LOGIC INPUT#1 INPUT#2 INPUT#3 INPUT#4 INPUT#5 INPUT#6 INPUT#7 INPUT#8 RESET TYPE

SELF / MANUAL 0.00 ~ 60.00s (0.01) OR8 / HALF_OR8 / AND8 / HALF_AND8 Reference Reference Reference Reference Reference Reference Reference Reference SELF / MANUAL 0.00 ~ 60.00s (0.01) 0~9, 0~9, 0~9, 0~9

/ LED#1~#4

PASSWORD

RESET DELAY NEW PASSWORD : ****

- SETTING/PROTECTION SETTING (ENT) Function Range/Step DISABLE / ENABLE 1A : 0.10~20.00A (0.01) 5A : 0.50~100.00A (0.05) 0.00 ~ 60.00s (0.01) NO / YES DISABLE / ENABLE

PROTECTION

IOC1(50_1)

FUNCTION PICKUP DELAY BLOCK FUNCTION

IOC2(50_2)

20/24

PAC-E100 (Over Current & Earth Fault Relay)

PICKUP DELAY BLOCK FUNCTION CURVE

1A : 0.10~20.00A (0.01) 5A : 0.50~100.00A (0.05) 0.00 ~ 60.00s (0.01) NO / YES DISABLE / ENABLE IEC_NI / IEC_VI / IEC_EI / IEC_LI / ANSI_I / ANSI_SI / ANSI_LI / ANSI_MI / ANSI_VI / ANSI_EI / ANSI_DI / KNI / KVI 1A : 0.10~20.00A (0.01) 5A : 0.50~100.00A (0.05) 0.01 ~ 10.00 (0.01) INST / TIMED NO / YES DISABLE / ENABLE 1A : 0.10~20.00A (0.01) 5A : 0.50~100.00A (0.05) 0.00 ~ 60.00s (0.01) NO / YES DISABLE / ENABLE 1A : 0.10~20.00A (0.01) 5A : 0.50~100.00A (0.05) 0.00 ~ 60.00s (0.01) NO / YES DISABLE / ENABLE IEC_NI / IEC_VI / IEC_EI / IEC_LI / ANSI_I / ANSI_SI / ANSI_LI / ANSI_MI / ANSI_VI / ANSI_EI / ANSI_DI / KNI / KVI

TOC(51)

PICKUP MULTIPLIER RESET TYPE BLOCK FUNCTION PICKUP DELAY BLOCK FUNCTION PICKUP DELAY BLOCK FUNCTION CURVE

IOCG1(50N_1)

IOCG2(50N_2)

TOCG(51N)

21/24

PAC-E100 (Over Current & Earth Fault Relay)

PICKUP MULTIPLIER RESET TYPE BLOCK FUNCTION K-FACTOR TIME CONST ALARM BLOCK FUNCTION PICKUP DELAY BLOCK FUNCTION PICKUP DELAY BLOCK MULTIPLIER BLOCK FUNCTION SHOT NUM PRE CON START CON

1A : 0.10~20.00A (0.01) 5A : 0.50~100.00A (0.05) 0.01 ~ 10.00 (0.01) INST / TIMED NO / YES DISABLE / ENABLE 0.10 ~ 4.00 (0.01) 1.0 ~ 999.9min (0.1) 50 ~ 100% (1) NO / YES DISABLE / ENABLE 1A : 0.02~1.00A (0.01) 5A : 0.10~5.00A (0.05) 0.00 ~ 180.00s (0.01) NO / YES DISABLE / ENABLE 1A : 0.10~20.00A (0.01) 5A : 0.50~100.00A (0.05) 0.00 ~ 180.00s (0.01) NO / YES 0.01 ~ 10.00 (0.01) NO / YES DISABLE / ENABLE 1~4 (1) Reference Reference

THERMAL(49)

UC(37)

NSOC(46)

AREL(79)

22/24

PAC-E100 (Over Current & Earth Fault Relay)

CB FAIL(50BF)

PREPARE TIME DISCRIM TIME RECLAIM TIME 1st DLY TIME 2nd DLY TIME 3rd DLY TIME 4th DLY TIME BLOCK FUNCTION TRIP RELAY PICKUP DELAY BLOCK FUNCTION PICKUP OP DELAY RST DELAY BLOCK FUNCTION I2/I1 MIN I1 OP DELAY BLOCK

0.05~200.00s (0.01) 0.01~5.00s (0.01) 0.01~350.00s (0.01) 0.01~300.00s (0.01) 0.01~300.00s (0.01) 0.01~300.00s (0.01) 0.01~300.00s (0.01) NO / YES DISABLE / ENABLE TS1, TS2, TS3, TS4 1A : 0.10~1.00A (0.01) 5A : 0.50~5.00A (0.05) 0.00 ~ 60.00s (0.01) NO / YES DISABLE / ENABLE 1A : 0.10~0.50A (0.01) 5A : 0.50~2.50A (0.05) 0~1000 s (1) 0~1000 s (1) NO / YES DISABLE / ENABLE 10~100% (1) 1A : 0.10~0.50A (0.01) 5A : 0.50~2.50A (0.05) 0.00~60.00s (1) NO / YES

COLD LD(COLD_LD)

INRUSH(I2/I1)

23/24

PAC-E100 (Over Current & Earth Fault Relay)

- COMMAND COMMAND (ENT)

CONT OUT TEST

CONT OUT#1~#4

DEENERGIZED / ENERGIZED

EVENT CLEAR WAVE CLEAR TRIP CNT EDIT

PANEL TEST

24/24