You are on page 1of 172

Low Voltage

Prisma Plus G
Wall-mounted and floor standing enclosures for Electrical Distribution up to 630 A

Catalogue 2012

Table of contents
Index
Alphabetical index
> page 2

Catalogue number index


> page 4

Presentation

Overview
> page 10

IEC 61439 standard


> page 16

Examples of switchboard configurations


> page 20

Functional system
Functional units and distribution
> page 32 Circuit breakers > p. 32
Compact NSX 100/630 > p. 32 Easypact EZC 100/400 > p. 36

Switch-disconnect. > p. 38
Interpact INS-INV 250/630 > p. 38

Manuel srce. changeover system > p. 40


Circuit breaker Compact NSX 100/250 > p. 40 Switch-disconnect. Interpact INS-INV250 > p. 41

Accessories
> page 56

Front plates, rails, slotted mounting plates > p. 56

Fixing accessories > p. 58

Partitioning > p. 59

Cable running > p. 60

Distribution
> page 66

Panorama of the solution > p. 66

Non-Centralised distribution > p. 68


630 A Insulated busbars > p. 68 400 A Rear busbars > p. 70 630 A Multi-stage busbars in duct > p. 72

Prisma Plus G enclosures


IP30, IP31, IP43 enclosures
> page 91
Wall-mounted Floor standing enclosures > p. 94 Combinations > p. 96 Installation > p. 97 Gland plates > p. 98 Accessories > p. 99 Spare-parts > p. 101 Dimensions > p. 104

Pack enclosures Additional information

Pack wallmounted and flush-mounted enclosures > p. 124

Kilowatt-hour meters > p. 125 Accessories > p. 126

Insulated busbars > p. 128

Distribution blocks > p. 130

Electrical characteristics
> page 138

Practical Information
> page 145

Standards
> page 146

Prisma Plus G
Index
p. 2
Determining catalogue numbers
> page 25

Presentation

p. 10

Functional system
p. 29
Fusegear > p. 42
Fupact INF > p. 42 Fupact ISFT / ISFT-N > p. 44

Modular devices > p. 46


Switchboard incomer > p. 46 Outgoers > p. 47 TeSys, Altistart, Phaseo > p. 48

Other devices > p. 50


Kilowatt-hour meters > p. 50 Human-switchboard interface > p. 52

Functional units and distribution


> page 32

Switchboard lighting > p. 62

Finishing parts > p. 63

Management of the internal temperature > p. 64

Accessories
> page 56

Centralised distribution > p. 75


Insulated flexible bars > p. 74 Distribution blocks > p. 75 Comb busbars > p. 82 Earth / neutral blocks > p. 83 Earth bars > p. 84 Terminal blocks > p. 86 Terminal blocks layout > p. 87

Distribution
> page 66

Prisma Plus G enclosures


p. 89
IP55 enclosures
> page 107
IP55 enclosures > p. 110 Combinations > p. 111 Accessories > p. 112 Gland plates > p. 113 Partial door > p. 114 Side panels > p. 115 Door accessories > p. 116 Dimensions > p. 134 Spareparts > p. 117 Dimensions > p. 118

Comb busbars, Distribution blocks > p. 131

Accessories > p. 132

Pack enclosures
p. 121

Enclosure characteristics
> page 151

Thermal characteristics
> page 159

Practical Information
> page 167

Additional information
p. 137
1

Index

Alphabetical index

Designation

400 A rear busbars 630 A multi-stage busbars in duct A Additional block Adhesive labels for mimic diagrams After-sales service B Barrel locks Blanking plates Brackets C C120 Cable trunking for doors Cable-tie supports Canopy Central uprights Clip-nuts Comb busbars Combination Combination uprights Compact NSX 100/250 Compact NSX 400/630 Connections Connectors Covers D Devices 144 x 144 Devices 72 x 72 Devices 96 x 96 Distribloc Doors E Earth blocks Earthing braid Easypact EZC100/400 F Fan Filters Fixed lighting Flush-mounting kit Flush-mounting kit Front cover support uprights Front-plate Front-plate, Multiclip distribution bloc accessories Fupact INF Fupact ISFT and ISFT-N G Gasket Gland plates Grill with filter Grommets for wiring through front H Handles Heating elements Hexagonal spacers Hook-on rail system Human-switchboard interface I iC120 INS100/160 INS40/160 Inserts Insulated flexible bars Interpact INS-INV250/630 IP30 enclosures IP30 wall-mounted and floor standing enclosures IP55 enclosures J Joinable distribution block K Kilowatt-hour meters

70 72

Pages

69 63 101, 102, 103, 117 100, 116 127 97 46 61 61, 132 95, 110, 126 102 58 82, 131 96 127 32, 40 34 129 71 69, 129 54 53, 54 53 77, 130 110 84, 132 100, 132 36 64 64 62 97, 127 97 103 56, 103 103, 117 42 44 95, 126 98, 102, 113, 126 64 61 100, 116 65 58 97 52 46 46 46 100, 116 74 38 94 94 110 79 50, 125

Index

Alphabetical index

Designation

L Lamps Lifting accessories Lifting cross-members Locks M Metal plate with cut-outs Modular devices Modular front-plate Modular incoming fusegear Modular rails Mounting plates Mounting supports Mounting uprights Multiclip Multiclip distribution block Multiple combination Multi-stage distribution block N Neutral bars NG125 NG160 P Padlocking Partial doors Partitioning Plinth cover panel Plinth gusset Plinths Pole Polybloc Power Meter Power supply block Powerclip busbars Prefabricated connections Pushbuttons R Rails Recessed slotted mounting plate Regulating Reinforcement cross-members Resistors S Self-tapping screws Side panels with cut-outs Source changeover system Spare-parts Straps Switchboard portable lamp Symbol sheets T Tap-off block Terminal block Terminal block layout TeSys, Altistart, Phaseo Thermostat Trunking Trunking spreader Trunking supports Universal angle bracket V Ventilated front-plate Vigi C120 Vigi iC120 Vigi NG125 Vigi NG160 Vigilohm Vigilohm system Vigirex W Wall mounting

Pages
55 97 97 116 98, 113 46, 103, 117 133 46 133 114 112 111, 112 80 131 111 78, 130 84 46 46 100, 116 99, 114 59 112 112 102 112 75, 76, 130 53 69 68, 128 69 55 57 57, 133 65 112 65 58 115 40 101, 102, 103, 117 60 62 63 69, 129 86 86 48 65 60 98, 126 60 58 64 46 46 46 46 55 54 53, 55 127

Index

Catalogue number index

Cat. no. Designation


01005 01006 01007 01008 01009 01017 01018 01020 01025 01028 01029 01030 01032 01033 01034 01035 01036 01039 01040 01041 01042 01043 01044 01045 01046 01050 01051 01052 01053 01093 01094 01098 01201 01202 01210 01211 01220 01247 01248 01249 01250 01251 01252 01253 01254 01255 01256 01257 01258 01259 01260 01264 01265 03001 03002 03003 03004 03005 03008 03010 03011 03030 03031

Pages
63 63 63 63 63 102 101 102 117 102 102 102 101 95, 102 95, 102 95, 102 101 102 95, 102 95, 102 95, 102 95, 102 95, 102 95, 102 95, 102 102 102 102 102 56, 103, 117 103, 117 101 68, 103, 128 81, 103, 117 68, 103, 128 103 101 117 117 117 103 103 103 103 103 103 103 103 103 103 103, 117 103, 133 103, 133 46, 47, 48, 55, 57 46, 48, 55, 57, 75, 76, 86 49, 57, 133 48, 49, 57, 86, 133 57, 84, 86 133 46, 47, 48, 57 46, 48, 49, 57, 75, 76 32, 38

01000

03032

Cat. no. Designation

Diagram lines, 10 black mimic, W=900 mm Diagram outgoing arrows, 10 black mimic Diagram incoming arrows, 10 black mimic Diagram transformers, 5 black mimic Diagram earth symbols, 5 black mimic Plain IP30 gland plate System G IP30 accessory FL21 gland plate for Pack enclosures IP55 single struts (2), RAL 9001 Combination piece for IP30 33-module System G floor-standing enclosures Combination piece for IP30 30-module System G floor-standing enclosures Combination piece for IP30 27-module System G floor-standing enclosures Closing accessories for IP30 System G floorstanding enclosures Side for 33-module System G floor-standing enclo. Side for 30-module System G floor-standing enclo. Side for 27-module System G floor-standing enclo. IP30 System G struts (4) System G IP30 support plate for duct, W=300 mm Side for 6-module System G wall-mounted enclo. Side for 9-module System G wall-mounted enclo. Side for 12-module System G wall-mounted enclo. Side for 15-module System G wall-mounted enclo. Side for 18-module System G wall-mounted enclo. Side for 21-module System G wall-mounted enclo. Side for 24-module System G wall-mounted enclo. Accessories for plinth with holes Accessories for plinth Plinth front, 600 mm Plinth front, 300 mm Self adhesive front plate grips (20) Accessories quarter turn closing Washers for System G rear panel (4) IPxxB clipon covers for Powerclip (2) Terminal covers for 200 A Multiclip (4) Powerclip busbar accessories, 160 to 400 A Powerclip busbar accessories, 630 A System G retrofit handle Set of spare parts for IP55 wall-mounted enclo. Set of spare parts for IP55 wall-mounted enclo. IP55 closing system spare parts Plates uprights AFS G 6 m Plates uprights AFS G 9 m Plates uprights AFS G 12 m Plates uprights AFS G 15 m Plates uprights AFS G 18 m Plates uprights AFS G 21 m Plates uprights AFS G 24 m Plates uprights AFS G 27 m Plates uprights AFS G 30 m Plates uprights AFS G 33 m Pack modular device rail AFS Pack decentered plate 4 m AFS Pack decentered plate 4.5 m AFS Modular device rail Adjustable modular device rail Recessed modular device rail Rear modular device rail DIN rail support (45) Modular device rail for NG160 Pack Modular device rail, W=250 mm Adjustable modular device rail, W=250 mm

03033 03040 03041 03043 03050 03051 03070 03073 03074 03080 03081 03102 03104 03105 03113 03114 03120 03121 03122 03123 03124 03125 03126 03152 03154 03155 03156 03157 03158 03159 03160 03164 03165 03166 03170 03171 03172 03173 03175 03176 03177 03178 03180 03181 03182 03183 03185 03186 03187 03194 03195 03196 03197 03198 03199 03202 03203 03204 03205 03213 03214 03220 03221

03000

Mount. plate for horiz. NSX250 with motor mechanism/plug-in with toggle Mount. plate for horiz. fixed Vigi NSX250 with toggle Mount. plate for vert. fixed NSX250 with toggle Mount. plate for vert. fixed NSX250 with rotary handle Mount. plate for NSX-INS250 source changeover system with rotary handles Mount. plate for vert. fixed NSX-INS250 with toggle, W=250 mm Mount. plate for vert. fixed NSX-INS250 with rotary handle, W=250 mm Mount. plate for horiz fixed NSX630 with toggle Mount. plate for vert. fixed NSX-INS630 with toggle Mount. plate for vert. fixed NSX630 with rotary handle Mount. plate for vert. fixed NSX-INS630 with toggle, W=250 mm Mount. plate for vert. fixed NSX630 with rotary handle, W=250 mm Mounting plate for vertical EZC100, 1P Mounting plate for EZC250 /EZCV250 Mounting plate for EZC400 Mounting plate for INF32/40 Mounting plate for INF63-160 Mounting plate for vertical ISFT100 Mounting plate for ISFT160 Busbar assembly for mounting ISFT100N/160 Mount. plate for vertical ISFT160, W=250 mm Mounting plate for horizontal ISFT250 Mount. plate for vertical ISFT250, W=250 mm Mounting plate for ISFT100N Mounting plate for 2-meter service connection Front plate for 1 3-phase meter in duct Front plate for 3 1-phase meters Mounting plate for 1 3-phase meter in duct Mounting plate for 3 1-phase meters Front plate for 2 3-phase meters Front plate for Gould 3-phase fuses Mounting plate for 2 x 3PH meters 6 modules Clip-nuts for DIN rails, 20 M4 Clip-nuts for DIN rails, 20 M5 Clip-nuts for DIN rails, 20 M6 Slotted mounting plate, 4 modules, for wall-mounted or floor-standing enclosure Recessed slotted mounting plate, 4 modules, wall-mount. or fl.-standing encl. Recessed slotted mounting plate, 6 modules, wall-mount. or fl.-standing encl. Recessed slotted mounting plate, 9 modules, wall-mount. or fl.-standing encl. Slotted mounting plate, 4 modules, W=250 mm Recessed slotted mount. plate, 4 mod., W=250 mm Recessed slotted mount. plate, 6 mod., W=250 mm Recessed slotted mount. plate, 9 mod., W=250 mm Clip-nuts for slotted mounting plates, 20 M4 Clip-nuts for slotted mounting plates, 20 M5 Clip-nuts for slotted mounting plates, 20 M6 Self-tapping screws for functional unit mounting, 20 M5 Hexagonal spacers, H=9 mm, 4 M5 Hexagonal spacers, H=23 mm, 4 M5 Hexagonal spacers, H=55 mm, 4 M5 Captive nuts for M6 hexagonal spacers (20) Hexagonal spacers, H=9mm, 4 M6 Hexagonal spacers, H=23 mm, 4 M6 Hexagonal spacers, H=55 mm, 4 M6 Hexagonal spacers, H=25 mm, 4 M6 Hexagonal spacers, H=40+10mm, 4 M8 Modular front plate, 2 modules Modular front plate, 3 modules

32, 39

Pages

32 33, 39 33 40, 41 33, 39 33 34, 38 35, 39 35 35, 39 35 37 36, 37 36, 37 42, 43 42, 43 45 44, 45 45 45 44 45 45 50, 125 50, 125 50 51 50, 125 50 46 51 58 58 58 57 49, 57 49, 57, 125 57 49, 57 57 57 57 57, 58 57, 58 57, 58 58 58, 84 58, 84 58, 84 58 57, 58, 86 57, 58, 86 57, 58, 86 58 58 56 47, 48, 55, 56, 133 46, 47, 56 46, 48, 56, 133 47, 48, 56 46, 47, 56 46, 47, 48, 127 46, 47, 48, 127

Mount. plate for horizontal fixed NSX-INS250 with toggle Mount. plate for horizontal fixed NSX250 with rotary 32 handle

Modular front plate, 4 modules Modular front plate, 5 modules Modular front plate, 3 modules, W=250 mm Modular front plate, 4 modules, W=250 mm Blanking strip, W=1000 mm Divisible blanking plates (4), W=90 mm

Index

Catalogue number index

03223 03228 03229 03231 03232 03234 03235 03241 03243 03244 03245 03247 03248 03249 03251 03253 03271 03274 03275 03281 03283

Cat. no. Designation

03290 03292 03293 03296 03297 03298 03299 03303 03304 03305 03306 03307 03312 03313 03314 03315 03320 03321 03325 03326 03327 03328 03329 03342 03343 03344 03345 03352 03353 03354 03359 03581 03583 03801 03802

Modular front plate, 3 rows Vertical modular front plate 9 mod. Vertical modular front plate 12 mod. Front plate for horizontal INS250 Front plate for horizontal fixed NSX250 with toggles and rotary handle Front plate for horizontal fixed NSX250 with motor mechanism Front plate for INS250 source changeover system with rotary handles Front plate for 3-4 vertical Vigi NSX250 devices with toggles Front plate for 3-4 vertical NSX250 devices Front plate for 3-4 vertical Vigi NSX250 devices with rotary handles or motor mechanisms Front plate for vertical NSX250 source changeover system with rotary handles Front plate for INS250 complete source changeover assembly Front plate for vertical INS250 Blanking plate for vertical NSX-INS250 Front plate for vertical fixed INS250 with toggle, W=250 mm Front plate for vertical fixed NSX250 with rotary handle, W=250 mm Front plate for horizontal INS630 Front plate for vertical INS630 Front plate for vertical NSX630 with rotary handle or motor mechanism Front plate for vertical fixed INS630 with toggle, W=250 mm Front plate for vertical NSX630 with rotary handle or motor mechanism, W=250 mm Front plate for horizontal plug-in NSX250 with toggle Front plate for horiz.fixed manual Vigi NSX250 Front plate for vertical fixed manual Vigi NSX250, W=250 mm Front plate for horiz. fixed NSX630 with toggle Front plate for vertical Vigi NSX630 Front plate for vertical fixed manual NSX630, W=250 mm Front plate for vertical fixed manual Vigi NSX630, W=250 mm Front plate for vertical EZC100 Front plate for horizontal EZC250/EZCV250 Front plate for vertical EZC250/EZCV250 Front plate for horizontal EZC400 Front plate for vertical EZC400 Front plate for vertical INF32/40, 3P Front plate for INF32/40, 4P and horiz. 3P Front plate for INF63-160, 3P and vert. INV63, 3P Front plate for vert. INF63, 4P and vert. INF160 Front plate for vertical ISFT100 Front plate for vertical ISFT160 Front plate for vertical ISFT100N Front plate for horizontal ISFT160 Front plate for horizontal ISFT160, W=250 mm Front plate for horizontal ISFT250 Front plate for vertical ISFT250, W=250 mm Transparent front plate, 4 modules Transparent front plate, 6 modules Transparent front plate, 9 modules Transparent front plate, 12 modules Transparent front plate, 4 modules,W=250 mm Transparent front plate, 6 modules,W=250 mm Transparent front plate, 9 modules,W=250 mm Front plate for Gould 1-phase fuses Universal angle brackets (2) Universal angle brackets (6) Plain front plate, 1 module Plain front plate, 2 modules

47, 56 47 47 38 32 32 41 33 33 33 40 41 39 37 39 33 38 39 35 39 35 32 32 33 34 35 35 35

Pages

03803 03804 03805 03806 03807 03808 03811 03812 03813 03814 03815 03816 03817 03890 03891 03895 03900 03901 03902 03903 03904 03907 03908 03910 03911 03912 03913 03914 03928 03934

Cat. no. Designation

Plain front plate, 3 modules

Plain front plate, 4 modules Plain front plate, 5 modules Plain front plate, 6 modules Plain front plate, 9 modules Plain front plate, 12 modules Plain front plate, 1 module, W=250 mm Plain front plate, 2 modules, W=250 mm Plain front plate, 3 modules, W=250 mm Plain front plate, 4 modules, W=250 mm Plain front plate, 5 modules, W=250 mm Plain front plate, 6 modules, W=250 mm Plain front plate, 9 modules, W=250 mm Front plate for fan or grill IP30 ventilated front plate, 1 module IP30 ventilated front plate, 3 modules Plain mounting plate for 72 x 72 mm meter Plain mounting plate for 96 x 96 mm meter Mounting plate with cut-out for 72 x 72 mm meter Mounting plate with cut-out for 96 x 96 mm meter Front plate with cut-outs for meter mount. plates Blanking plate, 72 x 72 Blanking plate, 96 x 96 for meters Front plate with cut-outs for 72 x 72 mm meters Front plate with cut-outs for 96 x 96 mm meters Front plate with cut-outs for 144 x 144 mm + 4 72 x 72 mm meters Front plate 96 x 96 for 1 device Front plate with holes for 22 mm dia. pushbuttons and lamps Visor for human/switchboard interface (HSI) Front plate for Vigilohm TR22A + 6 72 x 72 mm meters Multiclip distribution block, 4P, 80 A Multiclip distribution block, 4P, 63A, 1/2 row Multiclip distribution block, 2P, 200A, 1 row Multiclip distribution block, 3P, 200A, 1 row Multiclip distribution block, 4P, 200A, 1 row Multiclip distribution block, 4P, 160A, 1/2 row Powerclip busbar connection for 200 A Multiclip distribution block Duct busbar connection for 200 A Multiclip distribution block Rear busbar connection for 200 A Multiclip distribution block Multiclip/NG160 connection, 200 A Polybloc distribution block, 1P, 160 A Polybloc distribution block, 3P, 250 A Polybloc distribution block, 4P, 250 A Spacers Cu for Polybloc 250A distribution block (4) Distribloc 63 (top connection) Distribloc 63 (bottom connection) Distribloc 125 Distribloc 160 + connections Connections (4) between NG-INS125 and Distribloc distribution block Multi-stage distribution block, 4P, 160 A Multi-stage distribution block, 4P, 250 A Multi-stage distribution block, 4P, 400 A Multi-stage distribution block, 4P, 630 A Power supply block for horizontal NSX250 Universal power supply block, 250 A Connection between vertical NSX-INS250 and universal power supply block Connection between vertical NSX-INS250 in duct and universal power supply block Connection between vertical NSX-INS250 in duct and busbars Incoming connection block for NSX-INS250 supplied via the top

34, 35, 38, 40, 48, 56 35, 49, 56 49, 56 39, 49, 50, 51, 56 50, 56 56 35, 46, 48, 49, 56 35, 39, 56 48, 56 49, 56 56 56 51, 56 56, 64 56, 64 56, 64 53 53 53 53 53 53, 54 53 53 53 54 53 55 53 54 80, 131 80, 131 81 81 81 81 69, 81 73, 81 71, 81 81 75, 130 76 76 76 77, 130 77, 130 77, 130 77, 130 77, 130 78 78 78 78 69 69 69 69 73 38

Pages

37 36 37 36 37 43 42, 43 42, 43 43 45 45 45 44 45 44 45 48, 49, 55, 56 50, 51, 55, 56 50, 55, 56 55, 56 48, 49, 56 56 51, 56 46 58 58 32, 33, 35, 38, 39, 44, 45, 48, 49, 56 32, 33, 35, 39, 40, 41, 42, 43, 44, 45, 56

04000 04008 04012 04013 04014 04018 04021 04024 04029 04030 04031 04033 04034 04037 04040 04041 04045 04046 04047 04052 04053 04054 04055 04060 04061 04062 04064 04065 04066

04000

Index

Catalogue number index

04067 04070 04071 04073 04074 04075 04076 04103 04104 04107 04108 04111 04112 04113 04114 04116 04117 04118 04119 04121 04122 04123 04124 04126 04127 04128 04129 04145 04146 04147 04148 04149 04150 04151 04152 04155 04156 04158 04161 04162 04163 04171 04172 04173 04174 04190 04191 04192 04194 04195

Cat. no. Designation

04197 04198 04200 04201 04202 04205 04206 04207 04208 04210 04214 04215 04220 04223 04224 04226

Incoming connection block for NSX-INS250 supplied via the bottom Power supply block for horizontal NSX400 Power supply block for horizontal NSX630 Connection between vertical NSX-INS400-630 in duct and universal power supply block Universal power supply block, 400-630 A Connection between vertical NSX-INS630 in duct and busbars In-duct incoming connection block for NSX630 Powerclip busbars, 125 A, 3P, W=450 mm Powerclip busbars, 125 A, 4P, W=450 mm Powerclip busbars, 125 A, 3P, W=750 mm Powerclip busbars, 125 A, 4P, W=750 mm Powerclip busbars, 160 A, 3P, W=1000 mm Powerclip busbars, 250 A, 3P, W=1000 mm Powerclip busbars, 400 A, 3P, W=1000 mm Powerclip busbars, 630 A, 3P, W=1000 mm Powerclip busbars, 160 A, 3P, W=1400 mm Powerclip busbars, 250 A, 3P, W=1400 mm Powerclip busbars, 400 A, 3P, W=1400 mm Powerclip busbars, 630 A, 3P, W=1400 mm Powerclip busbars, 160 A, 4P, W=1000 mm Powerclip busbars, 250 A, 4P, W=1000 mm Powerclip busbars, 400 A, 4P, W=1000 mm Powerclip busbars, 630 A, 4P, W=1000 mm Powerclip busbars, 160 A, 4P, W=1400 mm Powerclip busbars, 250 A, 4P, W=1400 mm Powerclip busbars, 400 A, 4P, W=1400 mm Powerclip busbars, 630 A, 4P, W=1400 mm Connections, 125 A (4) Connections 160 A (4) Busbar/modular device connection, 160 A Busbar/Vigi modular device connection, 160 A Modular device/Polybloc connection, 160 A Covers for Powerclip busbars, 8 IPxxB Powerclip tap-off blocks with 6 mm + 10 mm terminals (12) Powerclip tap-off blocks with 16mm terminals (12) Additional 35mm block, 3P Additional 35mm block, 4P Screws for Powerclip busbars (20) Bars with threaded holes (4), 160 A, W=1000 mm Bars with threaded holes (4), 250 A, W=1000 mm Bars with threaded holes (4), 400 A, W=1000 mm Bars with threaded holes (4), 160 A, W=1000 mm Bars with threaded holes (4), 250 A, W=1000 mm Bars with threaded holes (4), 400 A , W=1000 mm Bars with threaded holes (4), 630 A, W=1000 mm Copper angle brackets (4), 250A Rear busbar support Multi-stage bar support for duct Bolts for 5 mm bars, 20 M6 x 20mm Screws for bars with threaded holes, less than 630 A, 40 M6 x 16 mm Busbar power supply barrier, 630 A Rear busbar barrier Earth bar, 24 modules Earth bar for direct earth blocks, 12 x 3 mm Earth bars (2), 12 modules Supports for earth bar on DIN rail (2) Fixing brackets for vert. earth bar in wall-mount. or fl.-standing encl. H 15 mm Fixing brackets for vert. earth bar in wall-mount. or fl.-standing encl. H 45 mm Fixing brackets for vert. earth bar in wall-mount. or fl.-standing encl. H 80 mm Kit for neutral bar Earth blocks with 12x4mm spring terminals (4) Earth blocks with 3x16mm spring terminals (4) Mount. plate for terminal block and earth bar in duct Mount. plate with 4 vertical DIN rails for terminal blocks Raisers, 5 Practic Modular device rail, W=1600 mm

38 69 69 69 69 73

Pages

34 128 128 128 128 68, 128 68 68 68 68 68 68 68 68, 126 68 68 68 68 68 68 68 69, 71, 129 69, 71, 129 69, 129 69, 129 75, 130 69, 129 69, 129 69, 129 69 69 69, 129 70, 72 70, 72 70, 72 70, 72 70, 72 70, 72 72 71 70 72 71, 73 71, 73 72 70 84, 132 84, 132 84 84 57, 84, 85, 86, 132 57, 84, 85, 86 57, 84, 85, 86 84 84, 132 84, 132 85, 87 85, 87 56 47, 57

04227 04233 04234 04235 04239 04243 04255 04256 04257 04263 04264 04265 04267 04330 04331 04332 04333 04742 04743 04746 04751 04752 04753

Cat. no. Designation

Rail and raisers modular Trunking for door, W=2000 mm Grommets for wiring through front (10) Flexible trunking for wiring to door Horizontal cable straps (12) Covers for horizontal cable straps (4) Horizontal trunking supports (12) Adaptable support for horizontal trunking (10) Horiz. trunking sections (4), W=450 mm, + supports Covers for vertical cable straps (2), W=1000 mm Vertical cable straps, System G (12) Vertical trunking supports (12) Vertical trunking, W=2000 mm Vertical partition Horizontal partition for wall-mounted or floor-standing enclosure Horizontal partition for duct Horizontal partition for Pack enclosure Insulated flexible bar 20 x 2 mm, W=1800 mm Insulated flexible bar 20 x 3 mm, W=1800 mm Insulated flexible bar 24 x 5 mm, W=1800 mm Insulated flexible bar 32 x 5 mm, W=1800 mm Insulated flexible bar 32 x 6 mm, W=1800 mm Insulated flexible bar 32 x 8 mm, W=1800 mm Cable connectors (4), 160 A, 70 mm Cable connectors (4), 250 A, 185 mm Cable connectors (4), 400 A, 300 mm Surface-mount Pack enclosure, W=550 mm, 2 rows Surface-mount Pack enclosure, W=550 mm, 3 rows Surface-mount Pack enclosure, W=550 mm, 4 rows Surface-mount Pack enclosure, W=550 mm, 5 rows Surface-mount Pack enclosure, W=550 mm, 6 rows Pack extension enclosure, 2 rows Pack extension enclosure, 3 rows Plain door for Pack enclosure, W=550 mm, 2 rows Plain door for Pack enclosure, W=550 mm, 3 rows Plain door for Pack enclosure, W=550 mm, 4 rows Plain door for Pack enclosure, W=550 mm, 5 rows Plain door for Pack enclosure, W=550 mm, 6 rows Transparent door for Pack enclos., W=550 mm, 2 rows Transparent door for Pack enclos., W=550 mm, 3 rows Transparent door for Pack enclos., W=550 mm, 4 rows Transparent door for Pack enclos., W=550 mm, 5 rows Transparent door for Pack enclos., W=550 mm, 6 rows Wall-mounted enclosure, W=600 mm, 6 modules Wall-mounted enclosure, W=600 mm, 9 modules Wall-mounted enclosure, W=600 mm, 12 modules Wall-mounted enclosure, W=600 mm, 15 modules Wall-mounted enclosure, W=600 mm, 18 modules Wall-mounted enclosure, W=600 mm, 21 modules Wall-mounted enclosure, W=600 mm, 24 modules Wall-mounted enclosure, W=600 mm, 27 modules Plain door for wall-mounted enclosure, 6 modules Plain door for wall-mounted enclosure, 9 modules Plain door for wall-mounted enclosure, 12 modules Plain door for wall-mounted enclosure, 15 modules Plain door for wall-mounted enclosure, 18 modules Plain door for wall-mounted enclosure, 21 modules Plain door for wall-mounted enclosure, 24 modules Transp. door for wall-mounted enclos., 6 modules Transp. door for wall-mounted enclos., 9 modules Transp. door for wall-mounted enclos., 12 modules Transp. door for wall-mounted enclos., 15 modules Transp. door for wall-mounted enclos., 18 modules Transp. door for wall-mounted enclos., 21 modules Transp. door for wall-mounted enclos., 24 modules Duct for wall-mounted enclos., W=300 mm, 6 mod. Duct for wall-mounted enclos., W=300 mm, 9 mod. Duct for wall-mounted enclos., W=300 mm, 12 mod. Duct for wall-mounted enclos., W=300 mm, 15 mod. Duct for wall-mounted enclos., W=300 mm, 18 mod.

46, 57, 133 61 61 61 60, 132 60, 132 60, 132 60, 132 60, 132 60 60 60 60 59 46, 50, 51, 59 51, 59 125 71, 73, 74 71, 73, 74 71, 73, 74 71, 73, 74 71, 73, 74 71, 73, 74 71 71 71 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94, 95 94, 95 94, 95 94, 95 94, 95

Pages

07051 07052 07053

07000

08002 08003 08004 08005 08006 08012 08013 08082 08083 08084 08085 08086 08092 08093 08094 08095 08096 08102 08103 08104 08105 08106 08107 08108 08109 08122 08123 08124 08125 08126 08127 08128 08132 08133 08134 08135 08136 08137 08138 08172 08173 08174 08175 08176

08000

Index

Catalogue number index

08177 08178 08179 08182 08183 08184 08185 08186 08187 08188 08197 08198 08202 08203 08204 08212 08213 08214 08222 08223 08224 08232 08233 08234 08272 08273 08274 08282 08283 08284 08292 08293 08294 08302 08303 08304 08305 08306 08307 08309 08312 08313 08314 08315 08316 08317 08319 08322 08323 08324 08325 08326 08327 08329 08332 08333 08334 08335 08336 08337 08339 08342 08343 08344 08345 08346 08347 08349 08352 08353

Cat. no. Designation

Duct for wall-mounted enclos., W=300 mm, 21 mod. Duct for wall-mounted enclos., W=300 mm, 24 mod. Duct for wall-mounted enclos., W=300 mm, 27 mod. Door for wall-mounted enclosure duct, 6 modules Door for wall-mounted enclosure duct, 9 modules Door for wall-mounted enclosure duct, 12 modules Door for wall-mounted enclosure duct, 15 modules Door for wall-mounted enclosure duct, 18 modules Door for wall-mounted enclosure duct, 21 modules Door for wall-mounted enclosure duct, 24 modules Transp. door for wall-mounted enclos. duct, 21 mod. Transp. door for wall-mounted enclos. duct, 24 mod. Floor-standing enclosure, W=600 mm, 27 modules Floor-standing enclosure, W=600 mm, 30 modules Floor-standing enclosure, W=600 mm, 33 modules Floor-standing enclos. extension, W=600 mm, 27 mod. Floor-standing enclos. extension, W=600 mm, 30 mod. Floor-standing enclos. extension, W=600 mm, 33 mod. Plain door for wall-mounted and floor-standing enclosure, 27 modules Plain door for floor-standing enclosure, 30 modules Plain door for floor-standing enclosure, 33 modules Transparent door for wall-mounted and floorstanding enclosure, 27 modules Transp. door for floor-standing enclos., 30 modules Transp. door for floor-standing enclos., 33 modules Duct for floor-standing enclos., W=300 mm, 27 mod. Duct for floor-standing enclos., W=300 mm, 30 mod. Duct for floor-standing enclos., W=300 mm, 33 mod. Door for wall-mounted and floor-standing enclosure duct, 27 modules Door for floor-standing enclosure duct, 30 modules Door for floor-standing enclosure duct, 33 modules Transparent door for wall-mounted and floor-standing enclosure duct, 27 modules Transp. door for floor-standing enclos. duct, 30 mod. Transp. door for floor-standing enclos. duct, 33 mod. IP55 enclosure, 7 modules IP55 enclosure, 11 modules IP55 enclosure, 15 modules IP55 enclosure, 19 modules IP55 enclosure, 23 modules IP55 enclosure, 27 modules IP55 enclosure, W=850 mm, 33 modules IP55 enclosure extension, 7 modules IP55 enclosure extension, 11 modules IP55 enclosure extension, 15 modules IP55 enclosure extension, 19 modules IP55 enclosure extension, 23 modules IP55 enclosure extension, 27 modules IP55 enclosure extension, 33 modules IP55 plain door, 7 modules IP55 plain door, 11 modules IP55 plain door, 15 modules IP55 plain door, 19 modules IP55 plain door, 23 modules IP55 plain door, 27 modules IP55 plain door, 33 modules IP55 transparent door, 7 modules IP55 transparent door, 11 modules IP55 transparent door, 15 modules IP55 transparent door, 19 modules IP55 transparent door, 23 modules IP55 transparent door, 27 modules IP55 transparent door, 33 modules IP55 duct, W=300 mm, 7 modules IP55 duct, W=300 mm, 11 modules IP55 duct, W=300 mm, 15 modules IP55 duct, W=300 mm, 19 modules IP55 duct, W=300 mm, 23 modules IP55 duct, W=300 mm, 27 modules IP55 duct, W=300 mm, 33 modules IP55 side panels, 7 modules IP55 side panels, 11 modules

94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94 94 94 94 94 94 94 94 94 94

Pages

08354 08355 08356 08357 08359 08362 08363 08364 08365 08366 08367 08369 08371 08372 08374 08375 08376 08377 08381 08382 08383 08384 08386 08387 08391 08392 08393 08394 08395 08396 08585 08783 08801 08803 08804 08805 08807 08811 08812 08813 08814

Cat. no. Designation

94 94 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110

08815 08816 08817 08818 08819 08820 08821 08822 08823 08824 08826 08827 08830 08831 08832 08833 08841 08850

IP55 side panels, 15 modules IP55 side panels, 19 modules IP55 side panels, 23 modules IP55 side panels, 27 modules IP55 side panels, 33 modules IP55 side panels with cut-outs, 7 modules IP55 side panels with cut-outs, 11 modules IP55 side panels with cut-outs, 15 modules IP55 side panels with cut-outs, 19 modules IP55 side panels with cut-outs, 23 modules IP55 side panels with cut-outs, 27 modules IP55 side panels with cut-outs, 33 modules Top and bottom plates, W=600 mm Top and bottom plates, W=300 mm IP55 4-module partial plain door for 11-27 module enclosures IP55 6-module partial plain door for 33-module enclosures IP55 4-module partial door with cut-outs for 11-27 module enclosures IP55 6-module partial door with cut-outs for 33-module enclosures IP55 horizontal/vertical combination kit IP55 L combination kit IP55 square combination kit IP55 vertical partition Canopy for IP55 wall-mounted or floor-standing enclosure, W = 600 mm Canopy for IP55 duct, W = 300 mm IP55 mounting upright IP55 plinth gusset IP55 plinth cover panels, W=600 mm IP55 plinth cover panels, W=300 mm Pole-mount kit for enclosures IP55 lifting rings 52 Front plate hinge kit (set of 2 hinges) Form C cable-tie support W=1600 Lifting rings (2) External wall-mounted brackets (4) for Pack enclos. External wall-mounted brackets (4) Plinth raiser for floor-standing enclosures, 100 mm Plinth raiser for ducts, 100 mm Lifting/reinforcement cross-members (2) for 2 wall-mounted or floor-standing enclosures Lifting/reinforcement cross-members (2) for single wall-mounted or floor-standing enclosure and duct Lifting-reinf. cross-members (2) for wall-mount. or fl.-standing encl. + ducts Lifting/reinforcement cross-members (2) for duct + enclos. + duct + enclos. or duct + enclos. + enclos. + duct IP30 combination kit for floor-standing enclosures Combination kit Combination uprights (2) Multiple combination kit Flush-mounting kit, 6 to 18 modules Flush-mounting kit, 21 to 27 modules Trunking spreader for Pack enclosure Pack flush-mount kit Pack IP31 canopy Trunking spreader for wall-mounted or floor-standing enclosure Lifting/reinforcement cross-members (2) for duct + enclosure + duct + enclosure + duct Canopy for duct + single wall-mounted or floor-standing enclosure + duct, IP31 IP31 canopy for 2 wall-mounted or 2 floor-standing enclosures Canopy for 2 wall-mounted or 2 floor-standing associated enclosures, IP31 Canopy for floor-standing enclosure, IP31 Canopy for enclosure + duct + enclosure, IP31 IP43 door gasket kit, 6-33 modules Partial door for wall-mounted or floor-standing enclosure, 6-module

110 110 110 110 110 115 115 115 115 115 115 115 110 110 114 114 114 114 111 111 111 59 110

Pages

110 111, 112 112 112 112 112 111 56 61 97 127 97 97 97 96, 97 96, 97 96, 97 96, 97 96 96 96, 127 96 97 97 126 127 126 98 96 95 95 95 95 95 95, 126 99

Index

Catalogue number index

08851 08861 08862 08863 08864 08866 08867 08868 08870 08871 08872 08874 08875 08876 08878 08879 08880

Cat. no. Designation

08881 08882 08884 08887 08888 08891 08892 08895 08896 08897 08898 08899 08900 08903 08904 08905 08906 08910 08911 08913 08914 08915 08916 08917 08918 08931 08932 08933 08934 08935 08936 08938 08939 08940 08941 08942 08943 08944 08945 08946 08947 08948 08949 08950 08951 08952 08953 08955 08956

Partial door with cut-out for human/switchboard interface (HSI) for wall-mounted or floorstanding enclosure, 6-module Plain mounting plate, 210 x 150 mm Mounting plate with eight 22 mm diameter holes Mounting plate with two 65 x 85 mm holes for industrial sockets IP55 mounting plate with 65 x 85 mm and 90 x 100 mm holes for industrial sockets Cable tie support adapter Cable tie supports for wall-mounted or floor-standing enclosure (2) Cable tie supports for ducts (4) Plain metal gland plate for wall-mounted or floor-standing enclosure Interface for gland plate for wall-mounted or floor-standing enclosure Membrane-type gland plate, 25 entries Plain metal gland plate for duct Interface for gland plate for duct IP55 gland plate interface Plastic gland plate and interface for Pack enclosures Plain metal gland plate for Pack enclosures Plastic gland plate and interface for wall-mounted or floor-standing enclosure Plain gland plate Plain plate for wall-mounted and floor-standing enclos. Plastic gland plate and interface for ducts Gland plate for floor-standing enclosure plinth Gland plate for duct plinth Knockout gland plate with 4xM12/20 + 4xM16/25 Knockout gland plate with 2xM20/32 + 2xM25/40 Gland plate with 13 knockouts Membrane-type gland plate, 35 entries Membrane-type gland plate, 2 entries Gland plate 39 incoming 7/26 IP55 Gland plate 2 incoming 33/72 IP55 Switchboard identification plate Adhesive label holders (12), H=24 mm, W=432 mm Adhesive label holders (12), H=36 mm, W=432 mm Adhesive label holders (12), H=24 mm, W=180 mm Adhesive label holders (12), H=36 mm, W=180 mm Earthing braid, 6 mm Earthing wire, 6 mm Clip-on labels (12), 18 x 35 mm Engraving plates (12), 18 x 35 mm Clip-on labels (12), 18 x 72 mm Engraving plates (12), 18 x 72 mm Clip-on labels (12), 25 x 85 mm Engraving plates (12), 25 x 85mm Standard handle, Ral 7016 EURO handle without insert Handle without insert, ASSA-ABLOY Handle for cylinder, EURO, IP55 Handle, IP55, L = 155 mm IP55 door latch with lock and 2 no. 405 keys Handle padlocking kit IP55 handle padlocking kit Barrel lock no. 405 Barrel lock no. 455 Barrel lock no. 1242E Barrel lock no. 3113A Barrel lock no. 2433A DIN double bar insert Screwdriver slot insert Triangle insert, 6.5 mm male Triangle insert, 7 mm male Triangle insert, 8 mm male Triangle insert, 9 mm male Square insert, 6 mm male Square insert, 7 mm male Square insert, 8 mm male Square insert, 6 mm female Barrel lock no. 2432E

99

Pages

114 114 114 114 61 32, 61, 132 61 98, 113 98 98, 113 98 98 113 126 126 98 98, 113 96 98 97, 98, 113 98 98, 113 113 98, 113 98, 113 98, 113 113 113 63 63 63 63 63 51, 100, 132 125 63 63 63 63 63 63 100 100 100 116 116 116 100 116 100, 116 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

08961 08963 08964 08965 08987 08988 08989 08990 08992 08993 08994 08998 09931 09932 09933 09934 09937 09939 09942 09943 09945 09946 09947 09948 09949 09981 09982 09983 09984 09985 09986 09987 09988 09989 13142 13143 13144

Cat. no. Designation

Touch-up paint brush Adhesive drawing holder Switchboard lighting Switchboard portable lamp Fan Grill with filter Filters, 5 standard Filters, 5 fine Resistor, 55 W Resistor, 90 W Resistor, 250 W Thermostat

63 63 62 62 64 64 64 64 65 65 65 65

Pages

09000

Slot handle insert IP55 for screwdriver Double bar handle insert IP55, 3 mm IP55 barrel + 2 no. 2433 A keys IP55 8 mm male triangle insert for handle (CNOMO) IP55 7 mm male triangle insert for handle IP55 9 mm male triangle insert for handle IP55 barrel + 2 no. 1242E keys IP55 barrel + 2 no. 3113A keys IP55 barrel + 2 no. 455 keys IP55 6 mm female square insert for handle IP55 7 mm male square insert for handle IP55 8 mm male square insert for handle IP55 6 mm male square insert for handle IP55 screwdriver slot insert for door IP55 3 mm double bar insert for door IP55 7 mm male triangle insert for door IP55 8 mm male triangle insert for door (CNOMO) IP55 9 mm male triangle insert for door IP55 6 mm male square insert for door IP55 7 mm male square insert for door IP55 8 mm male square insert for door IP55 6 mm female square insert for door Installation accessory for Kaedra enclosure: 103 x 225 mm plate - 2 openings Installation accessory for Kaedra enclosure: 103 x 225 mm plate - for 65 x 65 or 75 x 75 mm outlet Installation accessory for Kaedra enclosure: 103 x 225 mm plate - for 100 x 107 mm outlet Two-pole multi-stage distrib. block, 100 A (2 x 7 holes) Two-pole multi-stage distrib. block, 125 A (2 x 13 holes) Four-pole multi-stage distrib. block, 40 A (4 x 13 holes) Four-pole multi-stage distrib. block, 100 A (4 x 7 holes) Four-pole multi-stage distrib. block, 125 A (4 x 13 holes) Four-pole multi-stage distrib. block, 125 A (4 x 17 holes) Additional neutral bar for cat. no. 13508 Additional neutral bar for cat. no. 13510 Additional neutral bar for cat. no. 13512 Additional neutral bar for cat. no. 13514 Self-adhesive label sheets for common symbols (10) Self-adhesive label sheets for special symbols (10) Comb busbar (W=430 mm, 16 poles) 1P Comb busbar (W=430 mm, 16 poles) 2P Comb busbar (W=430 mm, 16 poles) 3P Comb busbar (W=430 mm, 16 poles) 4P Tooth caps (set of 20) Comb busbar, 24-module (9 mm modules) 1P Comb busbar, 24-module (9 mm modules) 2P Comb busbar, 24-module (9 mm modules) 3P Comb busbar, 24-module (9 mm modules) 4P Insulated connectors for 25 mm cables (4) End-caps 1P/2P/1P + N, for comb busbars (40) End-caps 3P/4P/3P + N, for comb busbars (40) Tooth-caps for comb busbar teeth (40) Comb busbars, 2 48-module (9 mm modules) 1P Comb busbars, 2 48-module (9 mm modules) 2P Comb busbars, 2 48-module (9 mm modules) 3P Comb busbars, 2 48-module (9 mm modules) 4P

116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 115 115 115 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 63 63 82 82 82 82 82 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82 82, 131 82, 131 82, 131 82, 131 82, 131

13000

13506 13507 13508 13510 13512 13514 13515 13516 13517 13518 13735 13736 14811 14812 14813 14814 14818 14881 14882 14883 14884 14885 14886 14887 14888 14891 14892 14893 14894

14000

Index

Catalogue number index

14936 14937 14938 14939 21086 21088 21089 21090 21092 21093 21094 21095 21096 21098 28947 28948

Cat. no.

80A joinable distribution block 1P - 25 and 16 mm 80A joinable distribution block 2P - 25 and 16 mm 80A joinable distribution block 1P - 35 and 25 mm 80A joinable distribution block 2P - 35 and 25 mm comb busbar for DPN - 2P - 24 mod (9mm) comb busbar for DPN - 2P - 48 mod (9mm) comb busbar for DPN - 2P - 96 mod (9mm) comb busbar for DPN - 3P - 24 mod (9mm) comb busbar for DPN - 3P - 48 mod (9mm) comb busbar for DPN - 3P - 96 mod (9mm) lateral tooth-caps - 2P lateral tooth-caps - 3P Tooth-caps (12) Insulated connectors (4) lateral tooth-caps - 2P lateral tooth-caps - 3P Tooth-caps (12) Long terminal shield INS-INV 250 Coupling accessory NSX 100/250-3P Coupling accessory NSX 100/250-4P Raiser Mechanical interlocking Source changeover assembly-100A-3P Source changeover assembly-100A-4P Source changeover assembly-200A-3P Source changeover assembly-200A-4P Source changeover assembly-160A-3P Source changeover assembly-160A-4P Source changeover assembly-250A-3P Source changeover assembly-250A-4P Long terminal shield INS-INV 320/630 Long terminal shield Fupact INF40/60 Long terminal shield Fupact INF100/160 Long terminal shield Fupact ISFT160-3P Long terminal shield Fupact ISFT250-3P Stop plate for markers 2-pole commoning link for 35 mm screw term.block 2-pole commoning link for 70 mm screw term.block 2-pole commoning link for 150 mm screw term.block Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 6 mm pitch Markers - 8 mm pitch Markers - 6 mm pitch

Designation

79 79 79 79

Pages

21000

82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 69, 129 69, 129 38, 39, 41 40, 41 40, 41 41 41 41 41 41 41 41 41 41 41 38, 39 42, 43 42, 43 44, 45 44, 45 87 86 86 86 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87

28000 29000

29324 29358 29359 31064 31073 31140 31141 31142 31143 31144 31145 31146 31147 32565 49658 49659 49869 49872

31000

32000 49000

AB1 AB8P35 AB1 ALN352 AB1 ALN702 AB1 ALN1502 AB1 B6L1 AB1 B6L2 AB1 B6L3 AB1 B610 AB1 B620 AB1 B630 AB1 B640 AB1 B650 AB1 B660 AB1 B680 AB1 B690 AB1 B810 AB1 B820 AB1 B830 AB1 B840 AB1 B850 AB1 B860 AB1 B870 AB1 B880 AB1 B890 AB1 B6100 AB1 B670 AB1 B8100 AB1 BV6

AB1

AB1 BV6BM AB1 BV6RP AB1 BV8 AB1 RRAL42 AB1 RRAL102 AB1 RRAL162 AB1 RRN435U2BL AB1 RRN435U2GR AB1 RRN435U3BL AB1 RRN435U3GR AB1 RRN635U2BL AB1 RRN635U2GR AB1 RRN1035U2BL AB1 RRN1035U2GR AB1 RRN1635U2BL AB1 RRN1635U2GR AB1 RRNAC442BL AB1 RRNAC442GR AB1 RRNAC443BL AB1 RRNAC443GR AB1 RRNAC643BL AB1 RRNAC643GR AB1 RRNAC1042BL AB1 RRNAC1042GR AB1 RRNAC1642BL AB1 RRNAC1642GR AB1 RRNAL62 AB1 RRNTP435U2 AB1 RRNTP435U3 AB1 RRNTP635U2 AB1 RRNTP1035U2 AB1 RRNTP1635U2 AB1 RRNTPAC442 AB1 RRNTPAC443 AB1 RRNTPAC642 AB1 RRNTPAC1042 AB1 RRNTPAC1642 AB1 S1 AB1 VVN3535U AB1 VVN3535UBL AB1 VVN7035U AB1 VVN7035UBL AB1 VVN15035U AB1 VVN15035UBL EZ4TSHD3P EZ4TSHD4P EZATSHD3P EZATSHD4P EZETSHD3P EZETSHD3PN EZETSHD4P EZETSHD4PN LV429285 LV429306 LV429307 LV429369 LV429515 LV429516 LV429517 LV429518 LV432593 LV432594 PRA90045 PRA90046 PRA90047 PRA90048 PRA90049 PRA90050 PRA90051

Cat. no.

Markers - 6 mm pitch Markers - 6 mm pitch Markers - 8 mm pitch 2-pole insulated commoning link - 4 mm 2-pole insulated commoning link - 10 mm 2-pole insulated commoning link - 16 mm Terminal block 1in/1out-blue-4 mm Terminal block 1in/1out-grey-4 mm Terminal block 1in/2out-blue-4 mm Terminal block 1in/3out-grey-4 mm Terminal block 1in/1out-blue-6 mm Terminal block 1in/1out-grey-6 mm Terminal block 1in/1out-blue-10 mm Terminal block 1in/1out-grey-10 mm Terminal block 1in/1out-blue-16 mm Terminal block 1in/1out-grey-16 mm Blue end plate - 4 mm Grey end plate - 4 mm Blue end plate - 4 mm Grey end plate - 4 mm Blue end plate - 6 mm Grey end plate - 6 mm Blue end plate - 10 mm Grey end plate - 10 mm Blue end plate - 16 mm Grey end plate - 16 mm 2-pole insulated commoning link - 6 mm Terminal block 1in/1out-green/yellow-4 mm Terminal block 1in/2out-green/yellow-4 mm Terminal block 1in/1out-green/yellow-6 mm Terminal block 1in/1out-green/yellow-10 mm Terminal block 1in/1out-green/yellow-16 mm Separation partition - 4 mm Separation partition - 4 mm Separation partition - 6 mm Separation partition - 10 mm Separation partition - 16 mm Label for markers Screw terminal block grey 35 mm Screw terminal block blue 35 mm Screw terminal block grey 70 mm Screw terminal block blue 70 mm Screw terminal block grey 150 mm Screw terminal block blue 150 mm Long terminal shield EZC/EZCV250 3P Long terminal shield EZC/EZCV250 4P Long terminal shield EZC100-3P Long terminal shield EZC100-4P Long terminal shield EZC250-3P Long terminal shield EZC250-3P Long terminal shield EZC250-4P Long terminal shield EZC250-4P Sas Vigi NSX 100/250 400/630 Adaptator NSX 100/250 3P Adaptator NSX 100/250 4P Mechanical interlocking for NSX 100/250 changeover system Short terminal shield NSX400/630 3P Short terminal shield NSX400/630 4P Long terminal shield NSX100/250 3P Long terminal shield NSX100/250 4P Long terminal shield NSX400/630 3P Long terminal shield NSX400/630 4P 50 mm terminal block kit 25 mm terminal block kit 4 x 6 mm terminal block kit Splitter block kit Splitter block kit Splitter block kit Terminal block support kit

Designation

87 87 87 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86

Pages

EZ

36, 37 36, 37 37 37 36 37 36 37 32, 33, 35 32 32 40 32, 33, 35 32, 33, 35 32, 33, 40 32, 33, 40 35 35 83 83 83 83 83 83 83

LV

PRA

Presentation

Overview

To respond to increasing building requirements

Improve the continuity of service

Ensure the safety of life and property

Control deadlines and costs

10

Prisma Plus:

the optimised, tested and IEC compliant solution, for low voltage electrical distribution and control switchboards.

Prisma Plus,

a comprehensive range of enclosures and cubicles


> A solution based on more than 25 years of experience in low voltage switchboards. > Integrating Schneider Electric switchgear offerings and ensuring electrical, mechanical and communication functions complete consistency. > Quality production, certified ISO 9001.

11

Presentation

Overview

G System

> Small companies > Buildings > Offices

160 A

> Residential > Laboratories > Healthcare centres > Shopping centres > Supermarkets > Malls, etc.

> Schools > Hotels, etc.

Pack

12

P System

3200 A

> Hospitals > Bottling factories > Packaging factories

630 A

> Automobile factories > Food industry > Deary > Internet data centres > Logistics centres, etc.

Prisma Plus P

Prisma Plus G

13

Presentation

Overview

Simple, functional systems for safe, up to 630 A


Switchboards that are safe
With Prisma Plus G you can be sure to build 100 % Schneider Electric switchboards that are safe, optimised: > All components (switchgear, distribution blocks, prefabricated connections, etc.) are perfectly rated and coordinated to work together; > All switchboard configurations, even the most demanding ones, have been tested. You can prove that your switchboard meets the current standards, at any time. You can be sure to build a reliable electrical installation and give your customers full satisfaction in terms of dependability and safety for people and the installation.

aesthetics
Prisma Plus G with its discreet design, blends harmoniously into all tertiary and industrial buildings, including in entrance halls and passageways.

Available power Safety of people and property Controlled costs and delivery times Upgradeability

14

upgradeable LV switchboards
optimised and upgradeable
With Prisma Plus G you can build just the right switchboard for your customer, sized precisely to fit costs and needs. With this complete, prefabricated and tested system, it's easy to upgrade your installation and still maintain the performance levels. > The wall-mounted and floor-standing enclosures combine easily with switchboards already in service. > Devices can be replaced or added at any time.

Simple moves for cabling in the workshop

Efficient installation and connection work on site

Easy maintenance throughout the switchboard

All connection points are fully accessible and easy to check.

Easy connection on site, whatever the cable cross-section or installation location.

Easy and direct access to devices, in a switchboard in service.

15

Presentation

IEC 61439 standard

The switchboard, central to the electrical installation


Both the point of arrival of energy and a device for distribution to the site applications, the LV switchboard is the intelligence of the system, central to the electrical installation.
It plays an essential role in the availability of electric power, while meeting the needs of personal and property safety. Its definition, design and installation are based on precise rules; there is no place for improvisation. The IEC 61439 standard aims to better define "low-voltage switchgear and controlgear assemblies", ensuring that the specified performances are reached. It specifies in particular: > the responsibilities of each player, distinguishing those of the original equipment manufacturer; the organization that performed the original design and associated verification of an assembly in accordance with the standard, and of the assembly manufacturer - the organization taking responsibility for the finished assembly; > the design and verification rules, constituting a benchmark for product certification. All the component parts of the electrical switchboard are concerned by the IEC 61439 standard. Equipment produced in accordance with the requirements of this switchboard standard ensures the safety and reliability of the installation. A switchboard must comply with the equirements of standard IEC 61439-1 and 2 to guarantee the safety and reliability of the installation. Managers of installations, fully aware of the professional and legal liabilities weighing on their company and on themselves, demand a high level of safety for the electrical installation. What is more, the serious economic consequences of prolonged halts in production mean that the electrical switchboard must provide excellent continuity of service, whatever the operating conditions.

Prisma Plus tested switchboards


The conformity of the switchboard has been tested and proven. A Prisma Plus switchboard is: > made up of Schneider Electric low-voltage devices and components that all comply with the applicable standards; > based on configurations in our catalogue; > made up of Prisma Plus mechanical and electrical components that have been subjected to the verification of original equipment manufacturer; > mounted and wired by a panelbuilder in compliance with professional standards; > subjected to the individual verification. Schneider Electric makes available to the panelbuilder everything required to create tested Prisma Plus switchboards, including the basic configurations in the low voltage distribution catalogue, all the documentation for switchboard design and mounting, calculation and design software, etc. Panelbuilders can demonstrate conformity with standard IEC 61439-1 and 2 by presenting the declarations or certificates of conformity for type tests carried out by independent laboratories (ASEFA, ASTA, KEMA, etc.) and supplied by Schneider Electric. The panelbuilder is responsible for the individual routine verification and delivers the corresponding declarations of conformity.

The Schneider Electric solution


> Specify switchboards that comply with standard IEC 61439-1 and 2. > guarantee a level of safety that has been 100% tested, from the day the switchboard is installed and throughout its service life. > ensure a lasting investment through easy upgrading of the installation in compliance with the standard. > guarantee that the switchboard complies with the technical specifications.

16

Original Manufacturer and Assembly Manufacturer:

Both involved in tested assemblies

Standard IEC 61439 clearly defines the type of verifications that must be conducted by both organisations involved in final conformity of the solution: the Original Manufacturer, guaranteeing assembly system design and the Assembly Manufacturer, responsible for the final conformity of the switchboard.

Specifier
> Specifies the needs and constraints for design, installation, operation and upgrading of the complete system. > Checks that its requirements have been fully integrated by the Assembly Manufacturer. Depending on the application, the specifier could be the end-user or a design office.

sse

ly mb

Sy

m ste

Tes t

Assembly Manufacturer (Panel builder)


The organisation (whether or not the same as the OM) responsible for the completed assembly.
He is responsible for "Routine verifications" on each panel produced, according to the standard. If he derivates from the instructions of the original manufacturer he has to carry out again design verifications.

ed

As

Proje

ct spe

sem

Original Manufacturer
The organisation that has carried out the original design and the associated verification of an assembly system.
He is responsible for the "Design verifications" listed by IEC 61439-2 including many electrical tests.

cifica

tion*

bly

End-User
Should ask for a certified LV switchboard. By systematically requesting routine verifications, he ensures that the assembly system used is compliant.

* Schneider Electric has developed a specification guide.

17

Presentation

IEC 61439 standard

The main 10 functions of standard IEC 61439

For each of the following 10 functions, the standard IEC 61439 requires design verifications from the system manufacturer - mainly through type-tests - and routine verifications on each panel from the Panel Builder to achieve 3 basic goals: safety, continuity of service and compliance with end-user requirements. Safety
Voltage stresses withstand capability Current-carrying capability
To withstand long term voltages, and transient and temporary overvoltages according to the insulation coordination principles and requirements. To protect against burns and to withstand temperature rise: > when any circuit is continuously loaded, alone, to the specified current > when the assembly is loaded to the specified current according to the specified load pattern (between circuits and/or as a function of the time).

Short-circuit withstand capability Protection against electric shock

To withstand the stresses resulting from the prospective short-circuit current and from the associated data (High forces between conductors, temp. rise in a very short time, air ionization, overpressure). > Hazardous-live-parts not to be accessible (basic protection) > Accessible conductive parts not to become hazardous-live (fault protection).

Protection against risk of fire or explosion

> Resistance to internal glowing elements > Note: Protection of persons, and optional protection of the assembly, against arcing due to internal fault can be specified through a "special test" according to IEC 61641.

Continuity of service
Maintenance and modification capability
Capability to preserve continuity of supply without impairing safety during assembly maintenance or modification > Electrical condition of the assembly or various circuits > Speed of exchange of the functional units > Test facilities

Electro-Magnetic compatibility

To properly function (immunity) and not to generate EM disturbances (emission) in specified environmental conditions: > Industrial networks or locations (Environment A) > Domestic, commercial, and light industrial locations (Environment B).

Compliance with end-user requirements


Capability to operate the electrical installation
To properly function, according to: > The electrical diagram of the overall system and related information (voltages, coordination) > The specified operating facilities (e.g. free or restricted access to Man Machine Interfaces, isolation of the outgoing circuits).

Capability to be installed on site

> To withstand handling, transport, storage and installation constraints > Capability to be erected and connected (type of enclosure, type, material and cross sectional areas of external conductors).

Protection of the assembly against mechanical and atmospheric environmental conditions


> Presence of water or solid foreign bodies (IP according to IEC 60529) > External mechanical impacts (optional IK according to IEC 62262) > Indoor or outdoor installation (humidity, UV). 18

IEC 61 439-1 paragraph 11.4

Protection against electric shocks and integrity of protection circuits


The following should be checked visually: > Presence of protective shields against direct and indirect contacts on live parts; > Presence of the PE conductor. The continuity of protection circuits is ensured by compliance with the assembly instructions delivered with each product.
IEC 61 439-1 paragraph 11.5

Standard individual check sheet


in accordance with the IEC 61439-1 and 2 standard from the assembly manufacturer (panelbuilder)

Integration of incorporated components


The assembly manufacturer must comply with the instructions of the original equipment manufacturer for installation and wiring of the components used.
IEC 61 439-1 paragraph 11.6

Job No.: ................................................................................................. Switchboard No.: ................................................................................... Drawing No./Rev. No.: ............................................................................

Chapter
Degrees of protection provided by enclosures Insulation clearances and creepage distances Protection against electric shocks and integrity of protection circuits Integration of incorporated components Internal electric circuits and connections Terminals for external conductors Mechanical operation Dielectric properties Wiring, operating performance and function 11.2 11.3 11.4 11.5 11.6 11.7 11.8 11.9 11.10

Verified

Internal electric circuits and connections


Schneider Electric recommends marking the nut with a tinted acrylic lacquer, indelible and temperature-resistant. This allows: > not only self-checking to check effective tightening to torque; > but also identification of any loosening.
IEC 61 439-1 paragraphe 11.9

Dielectric properties
The main circuits, and the auxiliary and control circuits connected to the main circuit, shall be subjected to the test voltage in accordance.
IEC 61 439-1 paragraph 11.10

Date of verification: ............ / ............ /.............

Wiring, operating performance and function


Verification of wiring and marking conformity with the drawings, parts list and diagram.

Verifications performed by: ..........................................................................

19

Presentation

Examples of switchboard configurations


PD390891_SE PD390287_SE

Incomer
Compact NSX250 4P Fixed, front connection Toggle Incoming cables via bottom to incoming connection block

Distribution
Polybloc distribution block

Outgoing devices
Multi 9 or Acti 9 devices Supply 80 A Multiclip Comb busbars Cable running Straps + cover Connection Terminal block at top of switchboard Motor circuit breakers Supply Comb busbars Cable running Straps + cover Connection Terminal block at top of switchboard

IP30 enclosure
Wall-mounted enclosure, W = 595 mm, H = 930 mm Plain door Partial plain door

20

Presentation

Examples of switchboard configurations


PD390446R_SE PD395007_SE

Incomer
Interpact INS160 4P Incoming cables via top

Distribution
160 A Powerclip busbars

Outgoing devices
Multi 9 or Acti 9 devices Supply 80 A Multiclip Comb busbars Cable running Straps + cover Connection Terminal block in duct, W = 300 mm Motor circuit breaker + contactor combinations Supply Cable wiring Cable running Straps + cover Connection Terminal block in duct, W = 300 mm

IP30 enclosure
Wall-mounted enclosure, W = 595 mm, H = 1230 mm Transparent door Duct, W = 305 mm, H = 1230 mm Plain door

21

Presentation

Examples of switchboard configurations


PD390288_SE PD390289_SE

Incomer
Compact NSX250 Fixed, front connection Toggle Incoming cables via top to incoming connection block

Distribution
Powerclip busbars

Outgoing devices
Multi 9 or Acti 9 devices Supply 80/200 A Multiclip Comb busbars Cable running Straps + cover Trunking Connection Terminal block in duct, W = 300 mm Motor circuit breakers Supply Cable wiring Cable running Trunking Connection Terminal block in duct, W = 300 mm

IP30 enclosure
Wall-mounted enclosure, Transparent door W = 595 mm, H = 1230 mm Duct, W = 305 mm, Plain door H = 1230 mm

22

Presentation

Examples of switchboard configurations


PD390450R_SE PB110003

Incomer
Interpact INS160 Lateral handle Incoming cables via bottom, directly to device

Distribution
Distribloc distribution block

Outgoing devices
Multi 9 or Acti 9 devices Supply Comb busbars Cable running Cable running Straps + cover Connection Terminal block at bottom of enclosure Motor control and protection devices Supply Comb busbars Cable running Trunking Connection Terminal block at bottom of enclosure

IP55 enclosure
Wall-mounted enclosure, Transparent door W = 595 mm, H = 1250 mm

23

Presentation

Examples of switchboard configurations


PD395034_SE PD390893_SE

Incomer
Compact NSX400 Fixed, front connection Toggle Incoming cables via bottom in duct (W = 300 mm) to incoming connection block

Distribution
Powerclip busbars

Outgoing devices
Compact NSX250 Fixed, front connection Toggle Supply

Powerclip busbars with power supply block

Multi 9 or Acti 9 devices Supply Comb busbars 200 A Multiclip Cable running Trunking Connection Vertical terminal block at bottom of floor-standing enclosure Appareils protection et commande moteur Supply Multiclip 200 A Cable running Trunking Connection Vertical terminal block at bottom of floor-standing enclosure

Enveloppe IP30
Floor-standing enclosure, Transparent door W = 595 mm, H = 1830 mm Duct, W = 305 mm, Plain door H = 1830 mm

24

Presentation

Determining catalogue numbers


Rapsody software

Easy design with Rapsody software


A time-saver in the design and quotation phases. More flexibility since modifications and upgrades are possible throughout the project.

easy steps to design a switchboard


Define the switchboard's electrical and environmental characteristics, in a few clicks.

Choose and configure the devices to be installed, with no risk of error.

Customise, and easily modify the single-line diagram. Move or duplicate devices. Generate current distribution and connection systems.

Choose the switchboard and let the software set up the enclosure. A list of mounting and connection accessories is proposed to make mounting work easier. Automatically export the information required to make a clear, comprehensive and professional quotation.

25

Presentation

Determining catalogue numbers

Starting with the electrical diagram: IP30 switchboard

DD384078

NSX250 C60 ou IC60 C60 ou IC60 C60 ou IC60

1
DD383850

Installation/connection

> see page 32


DD381888

DD383960

Install the incomer


bb order the mounting plates and the front plates bb the incoming connection block bb the power supply block for the Powerclip busbars.

NSX100/250

NSX

03232

2
DD381878

Distribution using Powerclip busbars

DD383961

NSX100/250

NSX

NSX

DD383521

Order the mounting plates and front plates taking into account: bb supply to the rows bb cable running.

1
DD383518

Multi 9 or Acti 9
> see page 47

DD384084 DD384085 DD381978 DD381979

Install the modular devices

All Multi 9 or Acti 9 devices Multi 9 or Acti 9 devices y 40 A

DD383519

All Multi 9 or Acti 9 devices Multi 9 or Acti 9 devices y 40 A

2
DD381880

TeSys "U"

> see page 49

bb Multiclip distribution block > see page 80 bb cable running > see page 60

Determine the size of the switchboard


bb count the number of occupied modules bb determine the corresponding wall-mount enclosure bb order the additional plain front plate.

19 modules 21 modules
Plain front plate

> see page 56

26

Presentation

Determining catalogue numbers

Powerclip busbars
> see page 68
DD381882

DD383522

DD383520

> see page 84


DD383523

> see page 89


DD381892

DD381884

IP wall-mount enclosure

DD381982 DD381985 DD381983

Select the enclosures

DD384356

Select the terminal blocks and the earth bar

DD384355

Plan the distribution system

Wall-mount enclosure (IP30)

DD381885

Duct, W = 300 mm

3 4

Cable tie supports Accessories for lifting, handling, wall mounting, finishing parts, etc.

27

Functional system

28

Functional system

Contents

Presentation..................................................................................30

Functional units and distribution............................32


Circuit breakers .............................................................................32
Compact NSX 100/250 horizontal mounting........................................................ 32 Compact NSX 100/250 vertical mounting............................................................ 33 Compact NSX 400/630 horizontal mounting........................................................ 34 Compact NSX 400/630 vertical mounting............................................................ 35 Easypact EZC100/400 horizontal mounting......................................................... 36 Easypact EZC100/400 vertical mounting............................................................. 37 Interpact INS-INV250/630 horizontal mounting.................................................... 38 Interpact INS-INV250/630 vertical mounting........................................................ 39

Switch-disconnectors ....................................................................38 Manual source changeover system ..............................................40


Compact NSX 100/250 changeover system........................................................ 40 Interpact INS-INV250 changeover system........................................................... 41

Fusegear ......................................................................................42
Fupact INF horizontal mounting........................................................................... 42 Fupact INF vertical mounting............................................................................... 43 Fupact ISFT and ISFT-N horizontal mounting...................................................... 44 Fupact ISFT and ISFT-N vertical mounting.......................................................... 45

Modular devices............................................................................46 Industrial control devices ..............................................................48


TeSys, Altistart, Phaseo....................................................................................... 48

Modular devices 80/160 A switchboard incomer.................................................. 46 Modular devices outgoers y 63 A.......................................................................... 47

Other devices................................................................................50
Kilowatt-hour meters Classe II............................................................................. 50 Kilowatt-hour meters............................................................................................ 51 Human-switchboard interface.............................................................................. 52

Accessories.................................................................. 56
Front plates, rails, slotted mounting plates........................................................... 56 Fixing accessories............................................................................................... 58 Partitioning........................................................................................................... 59 Cable running...................................................................................................... 60 Switchboard lighting............................................................................................. 62 Finishing parts..................................................................................................... 63 Management of the internal temperature............................................................. 64

Distribution.................................................................. 66
Panorama of the solution..................................................................................... 66

Non-Centralised distribution..........................................................68
630 A insulated busbar......................................................................................... 68 400 A rear busbars............................................................................................... 70 630 A multi-stage busbars in duct......................................................................... 72 Insulated flexible bars.......................................................................................... 74

Centralised distribution..................................................................75

Distribution block ................................................................................................. 75 Comb busbars..................................................................................................... 82 Earth block / neutral block.................................................................................... 83 Earth bars............................................................................................................ 84 Terminal blocks.................................................................................................... 86 Terminal blocks layout.......................................................................................... 87

29

Functional system

Presentation

Readily available close by


The kit concept makes handling and transport easier and you get to benefit from Schneider Electrics efficient international logistics. Your distributor, hand-picked by Schneider Electric, can give you the very best advice. For determining catalogue numbers, > see page 25.

Straightforward organisation to make your job easier


> Clearly identified functions.
Compact NSX 160 Mounting plate The switchboard is set up in different functional units, organised naturally.

Terminal block

Busbar power connection

Front plate
Example: "Incomer" functional unit.

> A switchboard with a high degree of legibility.

The easy-to-read switchboard circuit diagram makes on-site cabling and connection operations simple.

30

Functional system

Presentation

The Prisma Plus functional system


The Prisma Plus functional system can be used for all types of low-voltage distribution switchboards up to 630 A, in commercial and industrial environments. Switchboard design is very simple. A functional structure for devices made up of wall-mounted and floor-standing enclosures that can be used alone or combined. A distribution system made up of Centralised distribution blocks and vertical busbars installed on the side or in the rear of the switchboard. Complete functional units Each device is part of a functional unit comprising: bb a dedicated mounting plate for device installation bb a front plate to block direct access to live parts bb prefabricated busbar connections bb systems for on-site connections and running of auxiliary wires. The functional units are modular and are arranged rationally, one on top of another, within the enclosure. The system includes everything required for functional unit mounting, supply and onsiteconnection. The components of the Prisma Plus system and those of the functional units in particular have been designed and tested taking into account device characteristics. This design approach ensures a high degree of reliability in system operation and optimum safety for personnel.

Electrical characteristics
Prisma Plus components comply with standard IEC 61439-1 et 2 and have the following electrical characteristics: bb rated insulation level of main busbars at rear of enclosure: 1000 V bb rated operational current Ie (40 C): 630 A bb rated peak withstand current Ipk: 53 k bb rated short-time withstand current Icw: 25 kA rms / 1 second bb frequency: 50/60 Hz.

31

Functional system

Functional units and distribution


Circuit breakers

Compact NSX 100/250 horizontal mounting

Mounting
600 300

Horizontal fixed (1)


DD383856 DD380594

Devices

Toggle

Direct rotary handle

Motor mechanism module 1 8 03031 03292 [4] + LV429285 (sas) 03802 [2] 03802 [2] 3P: LV429517 4P: LV429518

Number of devices per row No. of vertical modules Mounting plates Front plates with cut-out [No. of vertical upstream modules] downstream Incoming connection block Long terminal shields + cable tying

1 5 03030 03232 [4] 03801 [1] cables via top: 04066 cables via bottom: 04067 -

NSX100/250

1 6 03033 03292 [4] 03802 [2] -

Vigi NSX100/250

1 8 03031 03232 [4] 03802 [2] 03802 [2] -

NSX100/250

Vigi NSX100/250

1 8 03032 03234 [4] 03802 [2] 03802 [2] -

NSX100/250

3P: LV429517 4P: LV429518 08867

3P: LV429517 4P: LV429518 -

3P: LV429517 4P: LV429518

(1) Maximum size of connection cables: 70 mm. For cable cross-sections greater than 70 mm, use of a cable duct is recommended.

Mounting
600 300

Horizontal fixed
DD383855 DD380589

Horizontal plug-in
DD383855

Devices

Toggle

Direct rotary handle

Motor mechanism module

Toggle

NSX100/250 NSX100/250
with ammeter module or Vigi

NSX100/250 Vigi NSX100/250 NSX100/250


1 6 03031 03232 [4] 03802 [2] 1 6 03031 03292 [4] +LV429285 (sas) 03802 [2] 1 6 03032 03234 [4] 03802 [2]

NSX100/250
1 4 03032 03290 [4] 3P: LV429517 4P: LV429518 3P: LV429306 4P: LV429307

Number of devices per row No. of vertical modules Mounting plates Front plates with cut-out [No. of vertical modules] downstream Long terminal shields + adaptator

1 4 03030 03232 [4] 3P: LV429517 4P: LV429518 -

1 4 03033 03292 [4] -

Distribution

Polybloc distribution block


DD380587

Powerclip busbars
DD380522

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices Busbars / distribution blocks Power supply block Short terminal shield

All type

Toggle NSX NSX with ammeter module or VigiNSX

Direct rotary handle or All type motor mechanism module


> see page 70

All type

3P: 04033 > see page 75 > see page 68 4P: 04034 04060 (2) 04060 (2) 3P: LV429515 4P: LV429516

> see page 72

04061 (3) -

(2) Supplied with connections - (3) Connection must be made.

32

Functional system

Functional units and distribution


Circuit breakers

Compact NSX 100/250 vertical mounting

Mounting
600 300

Vertical fixed
DD383871 DD380666

Devices Number of devices per row No. of vertical modules (1) Mounting plates Front plates with cut-out [No. of vertical modules] upstream downstream Incoming connection block Divisible 85 x 147 mm blanking plates 107 x 147 mm

Toggle 4 x 3P or 3 x 4P 7 9 03040 03040 03243 [5] 03243 [5]

Direct rotary handle

NSX100/160 NSX250

Vigi NSX100/160
8 03040 03241 [7]

Vigi NSX250 NSX100/160 NSX250


11 03040 03241 [7]

03802 [2] 03802 [2] 03802 [2] 03802 [2] 03801 [1] 03802 [2] 3P: LV429517 4P: LV429518 03249 (to add modular devices to a row with Compact NSX 3P or 4P without electronic trip unit) 03222 (to add modular devices to a row with Compact NSX 3P or 4P with electronic trip unit)

4 x 3P or 3 x 4P 7 9 8 03041 03041 03041 03243 [5] 03243 [5] 03244 [7] + LV429285 (sas) 03802 [2] 03802 [2] 03802 [2] 03801 [1]

Vigi NSX100/160 Vigi NSX250


11 03041 03244 [7] + LV429285 (sas) 03802 [2] 03802 [2]

(1) With or without spreaders, whatever the distribution solution.

Distribution

Polybloc distribution block Powerclip busbars


DD380780 DD380593

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices Distribution block / busbars Adjustable rail Power supply block Connection block Short terminal shield

All type 3P: 04033 4P: 04034 03002 -

> see page 75

> see page 68

NSX

VigiNSX

> see page 70

All type

> see page 72

All type

04061 04062 3P: LV429515 4P: LV429516

must be made

Mounting
300 600

Vertical fixed
DD383858

Distribution Polybloc distribution block in duct


DD380745

Busbars Powerclip (3)

Multi-stage busbars Rear busbars ormulti-stage distribution block in duct


DD382305 DD380777

Devices

Toggle

Direct rotary handle

Number of devices per row No. of vertical modules (2) Mounting plates Cut-out front plates Incoming connection block

NSX 100/250

Vigi NSX NSX 100/250 100/250


1 9 03051 03253

11

Type of connected devices Distribution block / busbars Adjustable rail Power supply block Connection block Short terminal shield

All type 3P: 04033 4P: 04034

NSX

DD382567

VigiNSX

All type
> see page72

All type
> see page70

> see page68

> see page75

03011 -

04061 04062 must be made 3P: LV429515 4P: LV429516

04065 -

03050 03050 03253 03293 3P: LV429517 4P: LV429518

(2) With or without spreaders.

(3)  Space available at the top of the enclosure after mounting the universal power supply block: - NSX 100/250 = 7 modules - Vigi NSX 100/250 = 9 modules. Space required by power supply block on Powerclip busbars = 5 modules.

33

Functional system

Functional units and distribution


Circuit breakers

Compact NSX 400/630 horizontal mounting

Mounting
600 300

Horizontal fixed
DD383852 DD383851

Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] Incoming connection block

Toggle 1 9 03070 03296 [6] 03803 [3] 04076

NSX400/630

1 6 03070 03296 [6] 04076

Distribution

Powerclip busbars
DD380783

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices Busbars Power supply block

NSX400 04070

> see page 68

NSX630 04071

> see page 70

All type -

> see page 72

All type -

34

Functional system

Functional units and distribution


Circuit breakers

Compact NSX 400/630 vertical mounting

Mounting
600 300

Vertical fixed
DD383853 DD383854

Devices Number of devices per row No. of vertical modules (1) Mounting plates Front plates cut-out [No. of vertical modules] upstream downstream Long terminal shield (1) With or without spreaders.

Toggle 1 11 03073 03275 [9]

Direct rotary handle 1 12 03073 03275 [9]

NSX400

NSX630

1 13 03073 03297 [11] 03802 [2] -

Vigi NSX400

1 14 03073 03297 [11] 03802 [2] 03801 [1]

Vigi NSX630

1 14 03074 03275 [9]

NSX400/630

03802 [2] 3P: LV432593 4P: LV432594

03802 [2] 03801 [1]

03802 [2] 03803 [3]

1 17 03074 03297 [11] + LV429285 (sas) 03802 [2] 03804 [4]

Vigi NSX400/630

Distribution

Powerclip busbars
DD383825

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices Busbars Power supply block Short terminal shield (2) Connection must be made

All type

> see page 68

> see page 70

All type

> see page 72

All type

04074 (2) 3P: LV429515 4P: LV429516

Mounting
300 600

Vertical fixed
DD383857 DD383858

Busbars

Powerclip (4) Multi-space in duct


Dd382567 Dd382305

Rear
DD380777

Devices

Toggle

Direct rotary handle

Number of devices per row No. of vertical modules (3) Mounting plates Front cut-out plates [No. of upstream vertical downstream modules] Long terminal shield

NSX400 NSX630 Vigi NSX400/630 NSX 400/630


1 1 1 12 03080 03298 [8] 03812 [2] 03812 [2] 14 03080 03299 [10] 03812 [2] 03812 [2]

Type of connected devices Busbars Power supply block Connection block Short terminal shield Barrier

All type
> see page 68

All type
> see page 70

All type
> see page 72

04074 04073

04075

04198

3P: LV432591 4P: LV432592 included 04197

11 03080 03298 [8] 03812 [2] 03811 [1]

03081 03283 [12] -

(4) Space available at the top of the enclosure after mounting the universal power supply block: - NSX 100/250 = 7 modules - Vigi NSX 100/250 = 9 modules Space required by power supply block on Powerclip busbars = 5 modules.

3P: LV432593 4P: LV432594

(3) With or without spreaders

35

Functional system

Functional units and distribution


Circuit breakers

Easypact EZC100/400 horizontal mounting

Mounting
600 300

Horizontal fixed
DD383994

Devices

Toggle 3P 1 4 03104 03304 EZETSHD3P

EZC250 / EZCV250

Number of devices per row No. of vertical modules Mounting plates Cut-out front plates Long terminal shield (set of 2)

4P 1 4 03104 03304 EZETSHD4P

3P 1 5 03105 03306 EZ4TSHD3P

EZC400

4P 1 5 03105 03306 EZ4TSHD4P

Distribution

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices Busbars / distribution block

All type

> see page 70

> see page 72

All type

36

Functional system

Functional units and distribution


Circuit breakers

Easypact EZC100/400 vertical mounting

Mounting
600 300

Vertical fixed
DD38110 DD383044 DD383993

Devices

Toggle 1P 15 5 03102 03303 03249

EZC100

Number of devices per row No. of vertical modules Mounting plates Cut-out front plates Long terminal shield (set of 2) Divisible blanking plate H=85 mm, L=147 mm

3P 5 5 03102 03303 EZATSHD3P

4P 3 5 03102 03303 EZATSHD4P

3P 4 7 03104 03305 EZETSHD3PN -

EZC250 / EZCV250

4P 3 7 03104 03305 EZETSHD4PN

3P 1 10 03105 03307 EZ4TSHD3P

EZC400

4P 1 10 03105 03307 EZ4TSHD4P

Distribution

Polybloc distribution block Rear busbars


DD383493 DD380777

Busbars in duct
DD380761

Type of connected devices Busbars / distribution block Fixed rail

EZC100 04031 (x no. of pole) 03001

> see page 70

All type

All type

> see page 72

37

Functional system

Functional units and distribution

Interpact INS-INV250/630 horizontal mounting

Switch-disconnectors

Mounting
600 300

Horizontal fixed with connection block


DD380669

Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] Incoming cables via top connection cables via top block

Direct front handle 1 5 03030 03231 [4] 03801 [1] 04066 04067

INS-INV250

Mounting
600 300

Horizontal fixed, direct connection


DD380670

Devices

Direct front handle

INS-INV250

INS-INV320/630 INS-INV320/630

Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] Long terminal shield (set of 2)

1 4 03030 03231 [4] 29324

1 9 03070 03271 [6] 03803 [3] 32565

1 6 03070 03271 [6] 32565

Distribution

Polybloc distribution block Powerclip busbars


Dd381346 Dd381349

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices Distribution block / busbars Power supply block (1) (1) Supplied with connection

INS-INV250 3P 04033 4P 04034

INS-INV 250 04060

INS-INV 320/400 04070

INS-INV 500/630 04071

All type
> see page 70

All type
> see page 72

> see page 68

38

Functional system

Functional units and distribution

Interpact INS-INV250/630 vertical mounting

Switch-disconnectors

Mounting
600 300

Vertical fixed with or without spreaders


Dd380761

Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] downstream Long terminal shield (set of 2)

Direct front handle 1 8 03040 03248 [5] 03801 [1] 03802 [2] 29324

Lateral handle 1 10 03073 03274 [10] 32565

INS/INV250

INS/INV320/400

1 12 03073 03274 [10] 03802 [2] 32565

INS/INV500/630

1 8 03032 03806 [6] 03802 [2] 29324

INS/INV250

Distribution

Polybloc distribution block


Dd381347

Powerclip busbars
Dd381348

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices

INS-NV250 Front handle 3P 4P 04033 04034 03002 03002

Distribution block / busbars Adjustable modular device rail Power supply block Connection block Short terminal shield (1) Copper spacer.

Lateral handle 3P 4P > see page 68 04033 04034 + 04037 (1) + 04037 (1) 03003 03003 04060 04062 29322

INS-INV 250

INS-INV 320/630

All type

All type

> see page 70

> see page 72

04074 must be made 32563

Mounting

Vertical fixed with or without spreaders


DD80773

Distribution

Polybloc distribution block


DD382569

Powerclip busbars (2)


DD382570

Multi-stage busbars in a duct


DD382571

Rear busbars

300

600

Type of connected devices Distribution blocks / Busbars Adjustable modular device rail Power supply block Connection block Short terminal shield Barrier

INS-INV 250 3P 04033 03011 4P 04034

INS-INV INS-INV INS-INV INS-INV All type 250 320/630 250 320/630
> see page 68 > see page 70 > see page 72

Devices

Front direct rotary handle

04061 04064 29322 included 04074 04073 32563

04065 29322 04197 04075 32563

04198

No. of vertical modules Mounting plates Front plates cut-out [No. of downstream vertical modules] Long terminal shield (set of 2)

Number of devices per row

INS-INV INS-INV INS-INV 250 320/400 500/630


1 1 10 03080 03281 [10] 32565 12 03080 03281 [10] 03812 [2] 32565

9 03050 03251 [9] 29324

(2) Space available at the top of the enclosure after mounting the universal power supply block: 7modules. Encombrement du bloc dalimentation sur Powerclip: 5modules

DD380777

39

Functional system

Functional units and distribution

Manual source changeover system

Compact NSX 100/250 circuit breaker changeover system


Mounting
300

(changeover with mechanical interlocking)


DD380535

Fixed

600

ON I

reset

O OFF

Devices

Front connection, direct rotary handle 3P 10 03043 03245 [5] 03802 [2] 03803 [3] LV429369 LV429517 29358

NSX100/250

No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] downstream Mechanical interlocking Long terminal shield Coupling accessory

4P 10 03043 03245 [5] 03802 [2] 03803 [3] LV429369 LV429518 29359

40

Functional system

Functional units and distribution

Manual source changeover system

Interpact INS-INV250 switch-disconnector changeover system


Fixed
DD380537

Mounting
300

(changeover with mechanical interlocking)


DD380536

Fixed

(Complete source changeover assembly)

600

I ON

I ON

OFF O

Devices

Front, direct rotary handle 3P 9 03043 + 2 x 31064 (raiser) 03235 [5] 03802 [2] 03802 [2] 31073 -

Front, direct rotary handle 4P 9 03043 + 2 x 31064 (raiser) 03235 [5] 03802 [2] 03802 [2] 31073 3P 9 03043 03247 [5] 03802 [2] 03802 [2] 100 A: 31140 160 A: 31144 200 A: 31142 250 A: 31146 29324 29358

INS-INV250

INS250

No. of vertical modules Mounting plates cut-out Front plates [No. of vertical upstream modules] downstream Mechanical interlocking Complete source changeover assembly Long terminal shield Coupling accessory

29324 29358

29324 29359

4P 9 03043 03247 [5] 03802 [2] 03802 [2] 100 A: 31141 160 A: 31145 200 A: 31143 250 A: 31147 29324 29359

41

Functional system

Functional units and distribution


Fusegear

Fupact INF horizontal mounting

Mounting
600 300

Horizontal
DD382474 Dd382475

Devices

Extended rotary handle 3P or 4P 1 3 03113 03313 -

INF32

Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical downstream modules] Long terminal shield

3P 1 5 03114 03314 -

INF40/60

4P 1 5 03114 03314 49658 x 2

3P 1 7 03114 03314 [5]

INF100/160

4P 1 7 03114 03314 [5] 03802 [2] (1) 49659 x 8

03802 [2] (1) 49659 x 6

49658

(1) Not needed if direct distribution.

Distribution

Multi-stage busbars in a duct


DD383846

Powerclip busbars (2)


DD381380

Rear busbars
DD380777

Type of connected devices Distribution blocks / busbars Additional 35 mm2 block Connection block

All type
> see page 70

INF100/160 3P

> see page 68

4P 04156

All type
> see page 72

must be made

04155 must be made

(2) T  he mounting plate for INF Fupact does not leave a passage for the busbar; it can only be installed below the plate. The distribution system is installed under the functional unit.

42

Functional system

Functional units and distribution


Fusegear

Fupact INF vertical mounting

Mounting
600 300

Vertical
DD382477 DD382478

Devices

Extended rotary handle 3P 4 3 03113 03312 -

INF32/40

Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical downstream modules] Long terminal shield

4P 3 3 03113 03313 -

3P 3 5 03114 03314 -

INF63

4P 2 5 03114 03315 49658 x 2

3P 2 7 03114 03315 [5]

INF100/160

4P 2 7 03114 03315 [5] 03802 [2] (1) 49659 x 8

03802 [2] (1) 49659 x 6

49658

(1) Not needed if direct distribution.

Distribution

Polybloc distribution block Powerclip busbars (2)


DD383658 DD381380

Rear busbars
DD380777

Busbars in duct
DD380761

Type of connected devices Distribution blocks / busbars Adjustable modular device rail Universal power supply block Connection block

INF100/160 3P 04031 x 3 03002 must be made

4P 04031 x 4 03002 must be made

INF100/160
> see page 70

All type
> see page 68

All type
> see page 72

04061 must be made

(2) T  he mounting plate for INF Fupact does not leave a passage for the busbar; it can only be installed below the plate. The distribution system is installed under the functional unit.

43

Functional system

Functional units and distribution


Fusegear

Fupact ISFT and ISFT-N, 3P horizontal mounting

Mounting
600 300

Horizontal
DD342480

Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] downstream Long terminal shield

On mounting plate 1 6 03121 03326 [3] 03801 [1] 03802 [2] (1) 49869 x 2

ISFT160

1 6 03124 03328 [5] 03801 [1] 49872 x 2

ISFT250

(1) Not needed if direct distribution.

Busbars

Powerclip busbars
Dd382481

Rear busbars
Dd380777

Busbars in duct
Dd380761

Type of connected devi ces Distribution blocks / busbars Universal power supply block Connection block

All type

> see page 68

All type

> see page 70

> see page 72

All type

04061 must be made

44

Functional system

Functional units and distribution


Fusegear

Fupact ISFT and ISFT-N, 3P vertical mounting

Mounting
600 300

Vertical
Dd382482 Dd382483

Distribution
Devices Number of devices per row No. of vertical modules Mounting plates Front cut-out plates upstream [No. of downstream vertical modules] Long terminal shield On mounting plate 5 On busbars 4 6

Comb busbar
DD382484

ISFT100 ISFT100N ISFT160


8 8 03126 03325 [8] 8 03121 03321 [6] 03802 [2] (1) 49869 x 2

ISFT100N

ISFT160
Connected devices Comb busbar Type Number

7 03120 03320 [6] 03801 [1] -

8 03122 03325 [8] -

8 03122 03321 [6] 03802 [2] (1) 49869 x 2

Coupler to connect 2 busbars Tooth cover Set of 3 connectors 25 to 95 mm2

ISFT100 2 3 4 5 49861 49862 49863 49861 + 49862 49890 49864 49865

(1) Not needed if direct distribution.

Distribution

Connectors (2)

Polybloc distribution block Powerclip busbars Rear busbars


DD383659 DD382847 DD380777

Busbars in duct
DD380761

Type of connected devices Connectors / distribution block / busbars Adjustable modular device rail Universal power supply block Connection block

ISFT100 49860 must be made

All type 04031 x 3 03002 must be made

All type

> see page 68

> see page 70

All type

> see page 72

All type

04061 must be made

(2) Set of 3 connectors 3 x10mm2

Mounting
300 600

Vertical fixed
Dd382488

Devices Number of devices per row No. of vertical modules Mounting plates Cut-out front plates Long terminal shield

On mounting plate 1 6 03123 03327 49869 x 2

ISFT160

1 9 03125 03329 49872 x 2

ISFT250

Distribution

Polybloc distribution block Powerclip busbars


Dd382843

Multi-stage busbars in a duct Rear busbars


Dd382490 DD380777

Type of connected devices Distribution block / busbars Adjustable modular device rail Universal power supply block Connection block

ISFT160 04031 x 3 03011 must be made

All type

> see page 68

All type

> see page 70

All type

> see page 72

04061 must be made

must be made

45

Functional system

Functional units and distribution


Modular devices

Modular devices 80/160 A switchboard incomer

Mounting
600 300

Circuit breaker
Dd383268

Switch-disconnector
Dd383995

Devices No. of vertical modules Rail (48 modules of 9 mm) Modular front plates Blanking plate strip > see page 127 divisible

NG160, Vigi NG160 5 03002 (adjustable) (1) 03205 03220 03221

NG125, Vigi NG125, C120, Vigi C120, iC120, Vigi iC120 5 03001 03205

INS40/160 4 03001 03204 03220 03221

INS100/160 with long terminal shields 5 03001 03205

(1) Can be completed by a rail + raiser (ctn.no 04227) to instal modular devices on.

Mounting
300 600

Circuit breaker
Dd383626

Switch-disconnector
Dd383496

Devices No. of vertical modules Rail (20 modules of 9 mm) Front plates modular [No. of vertical modules] downstream Blanking plate strip > see page 127 divisible

NG160 5 03011 (adjustable) (2) 03214 [4] 03811 [1] 03220 03221

INS40/160 4 03010 03214 [4] 03220 03221

INS100/160 with long terminal shields 5 03010 03214 [4] 03811 [1] 03220 03221

(2) Can be completed by a rail + raiser (ctn.no 04227) to instal modular devices on.

Distribution

Powerclip busbars
Dd383270

Rear busbars

Busbars in duct

Polybloc distribution block 160 A


DD383300

Distribloc distribution block


DD383301

Multi-stage distribution
DD382813

DD380777

Type of connected devices Distribution block / busbars Connection block

All type

> see page 68 > see page 68

All type

> see page 70

All type

DD380761

> see page 72

All type

must be made

must be made

> see page 75 > see page 75

All type

> see page 77 > see page 77

All type

> see page 78

must be made


Mounting
600 300
Dd383530

Service connection
Modular incoming fusegear
Dd383531

Devices Number of devices per row No. of vertical modules Rail (48 modules of 9 mm) Cut-out front plates Horizontal partitioning (3)

Modular incoming fusegear 1 Ph 8 4 03001 03359 04331

Modular incoming fusegear 3 Ph 3 4 03001 03159 04331

(3) Order twice the catalogue number in case of other installation than at top enclosure

46

Functional system

Functional units and distribution


Modular devices

Modular devices outgoers 63 A

Mounting
300

Horizontal distances between centres: 200 mm


Dd383264

Horizontal distances between centres: 150 mm


Dd383265 Dd383266

Vertical
Dd383121

600

Devices Rail length (modules of 9 mm) No. of vertical modules Rail (48 modules of 9 mm) Modular front plates Blanking plate strip > see page 127 divisible

All modular devices 48 4 (1) 03001 03204 03220 03221

Modular devices 40 A 48 3 03001 03203 03220 03221 48 8 03001 x 3 03223 03220 03221

All modular devices 48 64 9 12 04226 04226 03228 03229 03220 03221

(1) Note: For a modular row with a 160A (half row) and 200 A Multiclip distribution block positioned directly below a non-modular mounting-plate (Compact, Interpact, etc...), or at the top of a switchboard, add one additional module (i.e. 4+1) and a plain upstream front plate(03801)

Distances between rows


300 600

Horizontal distances between centres: 200 mm


Dd383490

Horizontal distances between centres: 150 mm


Dd383489

Devices Rail length (modules of 9 mm) No. of vertical modules Rail (20 modules of 9 mm) Modular front plates Blanking plate strip > see page 127 divisible

All modular devices 20 4 03010 03214 03220 03221

Modular devices 40 A 20 3 03010 03213 03220 03221

Distribution

Comb busbar
Dd382484

Multiclip distribution block


DD384088

Type of connected devices Comb busbars / distribution blocks

According devices
> see page 82

All type

> see page 80

47

Functional system

Functional units and distribution

TeSys, Altistart, Phaseo

Industrial control devices TeSys D, TeSys K contactors


Mounting
300

For 600 mm wide wall-mounted For 300 mm wide duct and floor standing enclosures
DD381613 DD380708

600

Devices Useful length for rail No. of vertical modules Rail Plain front plates

LC1Dp or LC1Kp ( 40 A) 432 mm 3 03004 (in rear) 03803

LC1Dp or LC1Kp ( 40 A) 180 mm 3 03011 (adjustable) 03813

TeSys GV2/GV3 circuit breakers


Mounting
300

For 600 mm wide wall-mounted For 300 mm wide duct and floor standing enclosures
DD383494 DD383492

600

Devices Useful length for rail No. of vertical modules Rail Front plates cut-out [No. of vertical upstream modules] downstream Blanking plate strip > see page 127 divisible

TeSys GV2 432 mm 3 03001 03203 [3] 03220 03221

TeSys GV3 432 mm 5 03002 03205 [5] 03220 03221

TeSys GV2 180 mm 3 03010 03213 [3] 03220 03221

TeSys GV3 180 mm 5 03011 (adjustable) 03213 [3] 03811 [1] 03811 [1] 03220 03221

Combined TeSys GV2 circuit breaker + contactor


Mounting
300

For 600 mm wide wall-mounted and floor standing enclosures


DD381318

For 300 mm wide duct


DD381189

600

Devices Useful length for rail No. of vertical modules Rail Front plates transparent [No. of vertical plain modules] downstream

GV2 + LC1Dp or LC1Kp ( 40 A) 432 mm 5 03004 (in rear) 03342 [4] 03801 [1]

GV2 + LC1Dp or LC1Kp ( 40 A) 180 mm 5 03011 (adjustable) 03352 [4] 03811 [1]

48

Functional system

Functional units and distribution

TeSys, Altistart, Phaseo

Industrial control devices Tesys U starter-controler


Mounting
300

For 600 mm wide wall-mounted and floor standing enclosures


DD381319

For 300 mm wide duct


DD381190

600

Devices Useful length for rail No. of vertical modules Rail Front plates transparent [No. of vertical plain modules]

TeSys U 432 mm 5 03004 (in rear) 03342 [4] (2) 03801 [1]

TeSys U (1) 432 mm 4 03004 (in rear) 03342 [4] (3) -

TeSys U 180 mm 5 03011 (adjustable) 03352 [4] (2) 03811 [1]

TeSys U (1) 180 mm 4 03011 (adjustable) 03352 [4] (3) -

(1) TeSys U without communication module, neither auxiliary contact, neither inverter module. (2)  If the communication module is installed, the transparent front plate is mandatory. If not, the 2 front plates can be replaced by one plain front plate (cat.no 03805 in wall-mounted or floor-standing enclosure, 03815 in duct). (3) Or plain front plate (cat.no 03804 in wall-mounted or floor-standing enclosure, 03814 in duct).

Soft starters Altistart 01


Mounting
300

On rail in the enclosure (L = 600 mm)


DD382603

On recessed slotted On rail in duct mounting plate (L = 600 mm) (L = 300 mm)
DD382604 DD381191

600

Devices

Number of devices per row Useful length No. of vertical modules Rail Slotted plates Plain front plates

ATS01N103FT ATS01N109FT ATS01N222 ATS01N106FT ATS01N112FT to 232 ATS01N206 to212 19 9 9 432 mm 432 mm 432 mm 4 5 6 03004 03003 03003 (in rear) 03804 03805 03806

ATS01N230LY ATS01N272LY, ATS01N285LY ATS01N244LY ATS01N272Q, ATS01N285Q ATS01N244Q 2 432 mm 5 03003 03805 2 420 mm 6 03172 03806

ATS01N103FT ATS01N106FT 19 180 mm 4 03011 (adjustable) 03814

Supply and LV/LV Phaseo transformer


Mounting
300

On recessed slotted mounting plate (L = 600 mm)


DD382816

On a slotted plate (L = 300 mm)


DD380709

600

Devices Useful length for mounting plate No. of vertical modules Slotted plates Plain front plates

ABL6TS/TD, ABL6-RF 420 mm 4 03171 03804

ABL6TS/TD, ABL6-RF 172 mm 4 03175 03814

49

Functional system

Functional units and distribution


Other devices

Kilowatt-hour meters Classe II

Mounting
600 300

Accessible (1)
DD382948 DD382949

Devices Number of devices per row No. of vertical modules Mounting plates Metering front plates Horizontal partitioning Insulating plate Accessories

Single-phase (Ph + N) 3 6 03157 03155 04331 03154 M5 spacers for mounting plate > see page 58

3-phase (3 Ph + N) 2 9 03152 03158 04331 03154

Mounting
600 300

Behind front plate (1)


DD382950 DD382951

Devices Number of devices per row No. of vertical modules Mounting plates Front plate at transparent your choice plain Horizontal partitioning Insulating plates Accessories

Single-phase (Ph + N) 3 6 03157 03343 03806 04331 03154 M5 spacers for mounting plate > see page 58

3-phase (3 Ph + N) 2 9 03152 03344 03807 04331 03154

(1) Order one additional horizontal partition in case of installation other than at the top of enclosure. Note: Meters can be installed directly on mounting plate equipped with 6 mm earthing braid (cat.no 08910) and combined with partitioning or front plates.

50

Functional system

Functional units and distribution


Other devices

Kilowatt-hour meters

Mounting
600 300

Behind front plate (1)


DD383045 DD383046 DD383047

Devices Number of devices per row No. of vertical modules Mounting plates Front plates at transparent your choice plain Horizontal partitioning Earthing braid (2) Accessories

3-phase kilowatt-hour meters Connection blocks (3 Ph + N) 2 2 6 6 03160 03160 03343 03343 03806 03806 04331 04331 08910 08910 M5 spacers for mounting plate > see page 58

3-phase kilowatt-hour meters (3 Ph + N) + connection block 1+1 6 03160 03343 03806 04331 08910

Mounting
300 600

Behind front plate (1)


DD382956

Devices Number of devices per row No. of vertical modules Mounting plates Front plates at transparent your choice plain Horizontal partitioning Earthing braid (2) Accessories

3-phase (3 Ph + N) 1 9 03156 03354 03817 04332 08910 M5 spacers for mounting plate > see page 58

(1) O  rder one additional horizontal partition in case of installation other than at the top of enclosure. (2) M  eters can be installed directly on mounting plate equipped with 6 mm earthing braid (cat.no 08910) and combined with partitioning or front plates.

51

Functional system

Functional units and distribution


Other devices

Human-switchboard interface

2 types of device mounting 72x72 and 96x96

3 mounting types in Prisma Plus System G

1
Dd381685

1
> In the device zone of wall-mounted and floor-standing enclosures

> On an interface with plastic mounting plates clipped onto the metal front plate with cut-outs
Dd381705

40 10 0

60 10 0

40

60 10 0

40

60

A
60

40 10 0

bb The interface is made up of a metal front plate and plastic mounting plates that clip onto the front plate. bb The devices are attached in the cut-outs of the plastic mounting plates and insulated from the front plate.
Dd381687

2
> On a partial door with cut-outs in wallmounted and floor-standing enclosures
Dd382574 Dd381643

bb A system at the rear of the mounting plates guides the wires.


Dd381688

0 0 0

bb Each mounting plate can receive an adhesive label. bb Plain mounting plates are available to blank off any unused locations.

bb With flexible trunking to protect and guide wiring to door (04235).

2
> Directly on a metal front plate with cut-outs
Dd381689 Dd382636

3
> On a partial door with cut-outs, on an inclined visor by 30

bb Devices are attached directly to the metal front plate. bb Blanking plates are available to blank off any unused locations.

bb With cut-out plastic mounting plate directly clipped on the visor. bb Supplied with a drilling diagram for mounting on a plain door.

Note: - to maintain the IP55 degree of protection, the measurement devices must be installed behind a transparent door. - if they are installed on a plain door, use the corresponding mounting plates. ( > see page 53).

52

Functional system

Functional units and distribution


Other devices

Human-switchboard interface

Vigirex and other devices 72 x 72


Measurement, inspection, indication

Mounting
300

On an interface with plastic mounting plates


DD381705

Directly on a metal front plate On an inclined visor by 30 with cut-outs with plastic mounting plates
DD381689 DD382636

600

Devices Number of devices per row No. of vertical modules Visor Metal front plates with cut-outs Plastic mounting plates with cut-outs Blanking plate or device support

Vigirex (1) and other devices 72 x 72 5 3 03904 03902 03900 To blank-off or install: - from 1 to 4 buttons, 16 or 22 mm - 1 device 45 x 45
DD382575

Other devices 72 x 72 6 3 03910 03907 To blank-off or install: - 1 or 2 buttons, 22 mm - 1 device 45 x 45


DD383637

Vigirex and other devices 72 x 72 5 03928 03902 03900 To blank-off or install: - from 1 to 4 buttons 16 or 22 mm - 1 device 45 x 45
DD382575

(1) RHU, RH10P, RH21P, RH99 relay, RM12T Multiplexer, for 72 x 72 mm version.

Power Meter and other devices 96 x 96


Measurement, inspection, indication

Mounting

On an interface with plastic mounting plates


Dd382632

Directly on a metal front plate with cut-outs


Dd381711 DD383662

On an inclined visor by 30 with plastic mounting plates


Dd382636

600

300

Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs Visor Plastic mounting plates with cut-outs Blanking plate or device support

Other devices 96x96 4 3 03904 03903 03901 To blank-off or install: - from 1 to 4 buttons 16 or 22mm - 1 device 45 x 45 - 1 device 72 x 72
DD382633

Power Meter (2) and other devices 96 x 96 4 1 3 3 03911 03913 03908 To blank-off or install: - 1 or 2 buttons 22 mm - 1 device 45 x 45 - 1 device 72 x 72
DD383634

Power Meter (2) and other devices 96 x 96 4 03928 03903 03901 To blank-off or install: - from 1 to 4 buttons 16 or 22 mm - 1 device 45 x 45 - 1 device 72 x 72
DD382633

(2) Power Meter PM200 / PM700 / PM800, FDM121.

53

Functional system

Functional units and distribution


Other devices

Human-switchboard interface

Device 144 x 144 + 4 devices 72 x 72


Measurement, inspection, indication

Mounting
600 300

On a metal front plate with cut-outs


Dd381712

Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs Blanking plate or device support

Device 144 x 144 + devices 72 x 72 1+4 4 03912 03907 To blank-off the unused locations 72 x 72 or install: - 1 or 2 buttons 22mm - 1 device 45 x 45
Dd382637

Vigilohm system
Mounting
600 300

On a metal front plate with cut-outs


Dd381699
40 10 0 60

Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs Blanking plate or device support

Vigilohm system (1) + devices 72 x 72 1+6 4 03934 03907 To blank-off the unused locations 72 x 72 or install: - 1 or 2 buttons 22mm - 1 device 45 x 45
Dd382637

(1) Vigilohm TR22A/AH insulation monitor.

54

Functional system

Functional units and distribution


Other devices

Human-switchboard interface

Pushbuttons and lamps


Pushbuttons and lamps 22 mm
600 300
DD381690

Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs (1) Harmony Style 4, 5 and 7

Metal front plate with knock-outs 22 mm (1) 12 2 03914

Other modular devices


Vigirex, Vigilohm and other modular devices
DD383479

600

300

DD383480

2 3 4 5

Devices No. of vertical modules Rail (48 modules of 9 mm) Cut-out front plates

Vigirex (1), Vigilohm (2) 3 03001 03203

(ammeter, voltmeter, lamp, pushbuttons, etc.)

Other modular devices

2 03001 03002 (3)

(1) RH10, RH21, RH99, RMH relay and RM12T Multiplexer. (2) EM9, TR5A, SM21, IMD-IM9. (3)  For installation at the top or bottom of the enclosure, use a 3-module modular front plate (03203).

Other devices behind transparent front plates


Other devices behind transparent front plates
600 300
DD383481

Transparent front plates

4 mod. (H = 200 mm) 6 mod. (H = 300 mm) 9 mod. (H = 450 mm) 12 mod. (H = 600 mm)

03342 03343 03344 03345

55

Functional system

Accessories

Front plates, rails, slotted mounting plates


Plain and transparent front plates

Used for

Enclosure L600
DD381583 DD381582

Duct L300
DD381584 DD381585

Nb. of vertical modules 1 2 3 4 5 6 9 12

Height 50 mm 100 mm 150 mm 200 mm 250 mm 300 mm 450 mm 600 mm

Plain 03801 03802 03803 03804 03805 03806 03807 03808

Transparent 03342 03343 03344 03345

Plain 03811 03812 03813 03814 03815 03816 03817 -

Transparent 03352 03353 03354 -

Other front plates


Used for Enclosure L600
DB124225 DB124224 DD381676 DD60759

Duct L300
DB124226

Nb. of vertical modules 1 2 3 4 5 7 8 9 12

Height 50 mm 100 mm 150 mm 200 mm 250 mm 350 mm 400 mm 450 mm 600 mm

1 row of modular devices 03202 03203 03204 03205 -

3 rows of modular devices 03223 -

Ventilated 03891 03895 -

With cut-out for fan or filter > see page 64 03890 -

1 row of modular devices 03213 03214 -

Accessories for rails and slotted mounting plates


Pratic raiser
DD381314

Accessories for front plates


Used for Front plate hinge kit
DD383950

Self adhesive front plate grips

DD381576

Catalogue number Characteristics

04224 Set of 5 Heigth 10 mm, length 27 mm Colour: RAL 9001, insulating material

Catalogue numbers Characteristics

08585 Set of 2 hinges

01093 Set of 20 white RAL9001

56

Functional system

Accessories

Front plates, rails, slotted mounting plates


Rails

Used for

Enclosure L600
DD381351

Duct L300
DD381370

DD383497

DD381371

DD381353

DD381352

DD383497

Catalogue numbers Useful length 9mm modules number Useful depth behind front plate

Fixed 03001 432 mm 48 50 mm

Adjustable 03002 432 mm 48 de 47 114mm

Rear 03004 432 mm 48 128 mm

Recessed 03003 432 mm 48 158 mm

Fixed 03010 180 mm 20 50 mm

Installation accessories
Used for 45 supports
DD383504

Brackets
DD383505

Hexagonal spacers
DD383506

Catalogue numbers Characteristics

03005 Set of 2

04206 H = 15 mm

04207 H = 45 mm

04208 H = 80 mm

03195 H = 9 mm

03196 H = 23 mm

DD381371

Adjustable 03011 180 mm 20 de 47 114mm

03197 H = 55 mm

Adjustable rails
Rail to be cut
DD381310 DD383292

Catalogue numbers Characteristics

04226

04227

Set of 2 rails, useful length: 1600 mm Rail and 4 modular raisers with 4 holes, dia. 6.4 mm, 450 mm Useful length: 432 mm between centres

Slotted mounting plate


Used for Enclosure L600
DD381369 DD381375

Duct L300
DD381369 DD381375

Catalogue numbers Nb. of vertical modules Height Useful length Useful depth behind front plate

Flat 03170 4 200 mm 440 mm 140 mm

Recessed 03171 4 200 mm 420 mm 160 mm

03172 6 300 mm

03173 9 450 mm

Flat 03175 4 200 mm 172 mm 140 mm

Recessed 03176 4 200 mm 152 mm 160 mm

03177 6 300 mm

03178 9 450 mm

Clip-nuts
For slotted mounting plates
DD381312

M4 M5 M6 Characteristics

03180 03181 03182 Set of 20. Can also be mounted on cable-tie support cat. no. 08876. Offers installation of various devices

57

Functional system

Accessories

Fixing accessories

Clip-nuts
Clip-nuts
DD381312 DD381313 DD381612 DD381637 DD384035

M4 M5 M6 Mounting on Characteristics

03180 03181 03182 Slotted mounting plate and also on cable-tie support (08876) Set of 20 Mounting of various devices

03164 03165 03166 Rail Set of 20

03194 Functional uprights of IP30 / 55 enclosures Set of 20

Self-tapping screws
Self-tapping screws

M5 Characteristics

03183 Set of 20 Mounting on functionnal uprights

Hexagonal spacers
Hexagonal spacers
Dd380828 Dd380828 Dd380828 Dd380828 Dd380828

M5 M6 M8 Characteristics

03185 03195 Height: 9 mm Set of 4

03186 03196 Height: 23 mm Set of 4

03198 Height: 25 mm Set of 4

03187 03197 Height: 55 mm Set of 4

03199 Height: 40 + 10 mm Set of 4

Universal angle bracket


Universal angle bracket
Dd381577 Dd383078

Catalogue numbers Characteristics

03581 Set of 2

03583 Set of 6

58

Functional system

Accessories

Partitioning

Horizontal partitioning

The metal partitions are used to: bb separate the functional units from one to another bb create a physical separation between devices and a terminal block, for example.

Used for

IP30 and IP55 enclosures


DD381418

IP30 and IP55 ducts


DD381419

Catalogue numbers Characteristics

04331 04332 Metal. It is mounted directly on the functional uprights. Lateral and rear cut-outs are available for cable running or the installation of busbars at the rear of the switchboard.

Vertical partitioning

The metal partition creates a physical separation between the device compartment and a wide duct. It is used to: bb separate the devices from busbars or a distribution block installed in the duct, bb set up a special zone for terminal blocks in the duct.

Used for

Wall-mounted, floor-standing enclosures and IP30 duct


DD383509

Wall-mounted enclosures and IP55 duct


DD383119

Cat. no. Description

04330 Can be used for partitioning up to 33-modules. It can be cut to length every 150 mm.

08384 Metal. There are cut -outs for cable running. Quantity to order according to height. Nb. of vertical modules 7 11 of 50 mm Height (mm) 450 650 Quantity 1

15 850 2

19 1050

23 1250 3

27 1450

33 1750

59

Functional system

Accessories

Cable running

Straps and covers


Type Vertical cable straps
Dd383485

Covers for vertical cable straps

Horizontal cable straps


Dd383484

Covers for horizontal cable straps

Dd381628

Dd381618

Catalogue numbers Characteristics

04264 Set of 12

Dd381633

04263 Set of 2 x1 m

04239 Set of 12 Have the same capacity as 60 x 30 mm trunking

04243 Set of 4 covers of430 mm

Trunking supports
Type Vertical trunking supports
Dd383476

Horizontal trunking supports


Dd383477

Adaptable support for horizontal trunking


Dd383486

Dd381623

Catalogue numbers Characteristics

04265 Set of 12

Dd381626

04255 Set of 12

Trunkings
Type Vertical trunkings 80 x 60 mm
Dd381640

Dd382922

04256 Set of 10 Aligns the cover of a horizontal trunking section (H=60 or 80mm) with that of a vertical trunking section (H=80mm) Note: not designed for use with Pack enclosures.

Horizontal trunkings 60x30mm


Dd381639

Catalogue numbers Characteristics

04267 Set of 18 L = 2000 mm

04257 Set of 4 L = 450 mm Supplied with supports

60

Dd381621

Functional system

Accessories

Cable running

Cable trunkings for doors


Type Flexible trunkings for wiring to door
DD381643 DD380863

Cable trunkings
DD381641

Catalogue numbers Characteristics

04235 L = 500 mm, inner diameter = 19 mm

04233 Set of 30 adhesive trunkings 30 x 30 mm, L = 2000 mm

Grommets for wiring through front


Grommets
DD380864 DD380865

Catalogue number Characteristics

04234 Set of 10. For wiring through front.

Cable-tie supports
Used for Cable-tie supports for wall-mounted or floor-standing enclosures
DD381820

Cable-tie supports in a duct

C-shaped cable-tie supports for wallmounted or floor standing enclosures and ducts
DD383424

Cable-tie support adapters

Catalogue numbers Characteristics

08867 bb Set of 2 bb Supplied with hardware for mounting on the functional uprights of the enclosure.

08868 bb Set of 4 bb Supplied with hardware for mounting on the functional uprights of the duct.

DD383423

08783 bb L = 1600 mm, can be cut to length as needed. bb Cables secured by ties or cable clamps. bb Supplied with hardware for mounting on the functional uprights of the enclosure or duct.

08866 bb Set of 2 bb Makes it possible to tie down the cables next to the gland plate and gain one module in height.

DD381171

61

Functional system

Accessories

Switchboard lighting

Fixed lighting
Fixed lighting
600 300
DD381719

Catalogue number Presentation

08964 This system is generally used to illuminate the front of a switchboard. bb The kit is made up of: vv a base, vv a neon tube, vv a front plate with cut-out (1 module), vv a door contact. bb Supply voltage: 220/240 V bb Power rating: 8 W bb Height: 1 vertical module (50 mm)

Characteristics

Switchboard portable lamp


Switchboard portable lamp
DD381675

Catalogue number Presentation

Characteristics

08965 bb Lamp with a magnetic base for installation behind a door or directly on the cubicle framework. bb Supplied without a power cord. bb It does not take up any useful space in the switchboard. bb Supply voltage: 220/240 V bb Power rating: 11 W

62

Functional system

Accessories

Finishing parts

Identification labels
Clip-on labels
DD381714

Engraving plates
DD381757

IERE LUM

IERE LUM

Catalogue numbers Dimensions (mm) Characteristics

08913 08915 08917 18 x 35 18 x 72 25 x 85 bb Set of 12 bb The clip-on support is supplied with a paper label and a transparent cover. bb It clips onto the front plate horizontally or vertically and can be screwed to any support (plain door, plain front plate, etc.).

08914 08916 08918 18 x 35 18 x 72 25 x 85 bb Set of 12 bb These plates simply replace the paper labels.

Adhesive labels
DD381715

Symbol sheets
DD381751 DD381753 DD381752

Catalogue numbers Dimensions (mm) Characteristics

08905 08906 08903 08904 24 x 180 36 x 180 24 x 432 36 x 432 bb Set of 12 bb The adhesive label holders are supplied with a paper label and a transparent cover.

13735 bb Set of 10 adhesive symbol sheets bb Standard symbols: vv loads: sockets, lights, heating units, etc. vv rooms: bedroom, bathroom, etc.

13736 bb Set of 10 adhesive symbol sheets bb Special symbols: vv loads: lightning arrestor, gate, swimming pool, etc. vv rooms: technical room, computer room, etc.

Adhesive labels for mimic diagrams


Catalogue numbers Characteristics 01005 Set of 10

Lines, 900mm long (7mm thick)

Outgoing arrows Incoming arrows Transformers


01006 01007 01008

Earth symbols
01009

Accessories
Switchboard identification plate
DD381721

Adhesive drawing holder


DD381208

Touch-up paint brush


DD381008

Catalogue numbers Characteristics

08900 Colour: RAL 9001

08963 Colour: RAL 9001

08961 Colour: RAL 9001

63

Functional system

Accessories

Management of the internal temperature


Ventilation

In most cases and notably for IP30 switchboards, convection takes place naturally and does not require fans. However, when the switchboard is installed in temperate environments or when the degree of protection is high (IP55), ventilation accessories are indispensable.
For more in-depth information on selecting air-conditioning accessories and the thermal management of switchboards. > see page 158 to page 167.

Fan
DD381703

Grill with filter


DD381704

Catalogue numbers Installation Characteristics

08987 08988 Generally installed at the bottom of floor-standing enclosures: bb by cutting out a side panel; bb or by using the front plate with cut-out for fan, directly clipped on (03890). The set comprises the fan with a grill and a filter. bb Power rating: 70 W. bb Input voltage: 230 V. bb Noise level: 69 db. bb Degree of protection: IP54. bb Weight: 3 kg. bb Unimpeded throughput: 460 m3/h. bb Throughput with counterpressure (grill + standard filter, cat. no. 08988): 350 m3/h.
DD381723

Supplied with standard filter. bb Maximum throughput 350 m3/h. bb Degree of protection: IP54.

Front plate for fan or grill


Front plate for fan or grill
DD60759

Filters
Catalogue numbers Characteristics 08989 Set of 5 (for replacement)

DD381724

Dimensions

Standard filters

08990 Set of 5 (for replacement)

Fine filters

Ventilated front plate


Ventilated front plate
Catalogue number Characteristics 03890 Front plate with cut-out for fan or filter. bb Degree of protection: IP30. bb Height: 7 modules.
Dd381676

03891 03895 1 vertical module, 3 vertical modules, H = 50 mm H = 150 mm 250 cm2 Surface area of the openings 80 cm2 Characteristics Degree of protection: IP30. Located at the top and bottom of the switchboard, IP30 ventilated front plates facilitate natural convection in the switchboard. Catalogue numbers Height

64

Functional system

Accessories

Management of the internal temperature


Heating elements

The resistors prevent condensation, corrosion and superficial leakage currents. They maintain a positive temperature in the enclosures when external temperatures drop very low.

Heating resistor
DD381574 DD381573

Catalogue numbers Power rating Characteristics

08992

08993

08994

55 W 90 W 250 W bb Horizontal or vertical mounting. bb Aluminium case with fins. bb Temperature: vv turns off at 60 C, vv turns on at 25-30 C (temperature of the resistor itself). bb Equipped with a symetrical rail for rapid mounting (clips on). bb Input voltage: 230 V.

Regulating
Thermostat
DD381575

Used to control the temperature inside electrical switchboards in conjunction with heating resistors and fans.

Catalogue number Characteristics

08998 bb Setting range: +5 C to +60 C. bb Input voltage: 230 V. bb Fixing: clips onto a modular rail.

65

Functional system

Distribution

Panorama of the solution

Distribution blocks
> For incoming devices
160 to 250 A Polybloc

Prisma Plus G System


> For rows of modular devices
125 to 160 A Distribloc - Spring terminals for electrical connections that stay tight - Front designed to integrate perfectly with modular devices

63/200 A Multiclip

- Reliable spring-terminal connections for outgoing circuits, requiring no maintenance - Horizontal or vertical installation in minimum space

- Reliable spring-terminal connections requiring no maintenance - Fast installation - Easy upgrades through replacement or addition of devices - Easy balancing of phases

160 to 630 A multi-stage distribution block

80 to 125 A comb busbars

- Fast and direct connections, adaptable to all needs - Fast, economical connections

63/160 A adaptable earthing terminal blocks

- Traditional, highly polyvalent solution - Many installation possibilities

- Innovative solution

66

Functional system

Distribution

Panorama of the solution

Customised organisation of your switchboard


> Busbars up to 630 A for all switchboard architectures
Powerclip busbars: compact for fast upgrades. Flat busbars: for traditional distribution.

Prefabricated connections, optimised and fully insulated.

Rear busbars.

Lateral busbars. The bars are staggered for easy access to connection points.

> Row distribution blocks for modular devices


Comb busbars: a simple, cost-effective solution. Multiclip: a fast, flexible and reliable solution.

> Wiring routing components


Cable straps: a fast and efficient solution. Trunkings: for a neat finish.

 omb busbars are fully C insulated. Device can de connected in a single operation.

80 A Multiclip.

200 A Multiclip.

The Multiclip distribution block snaps easily onto the back of the rails. All types of modular devices can be mixed in the same row and phase balancing is simple. It's easy to change or add devices.

Snapped onto the back of rails, cable straps are a solution for clear and well-organised cabling.

They can be used for all configurations, whatever the number of cables and cable cross-sections. A cover protects the wiring and provides a neat finish. Horizontal and vertical, with different cross-sections, they are interconnected by adjustable trunking supports.

> Centralised distribution blocks for switchboard incomers

160 A Distribloc: practical and aesthetic.


Rpartiteur monobloc modulaire connexion rapide.

160 A Polybloc: " la carte" distribution block.


Modular combinable components for fast connections.

160 A multistage distribution block: a traditional solution.


Installation on modular rail on mounting-plate. Screw-terminal connections.

Polybloc 250 A: modular and compact.


Installed directly downstream of Compact circuit breakers and Interpact switches without taking up any extra vertical modules. Fast connections in spring-loaded terminals.

67

Functional system

Distribution

630 A insulated busbar

Non-Centralised distribution

Powerclip busbars 160 / 630 A


PD390545

Compact busbars, IPxxB, ready for installation in the switchboard (supplied with supports and extremity obturators) Tap-off blocks for 6 mm and 10 mm cable ETP H12 channelled copper bars with threaded M6 holes every 25 mm, can be cut every 200 mm Bars mounted on insulated bases that screw to the functional upwrights Wide choice of prefabricated and tested connections Clip-on covers to protect against direct contacts from the front (IPxxB). They can be easily cut for the connections to the devices The ends are protected by extremity obturators 200 A connection for Multiclip distribution block

PD390546

Clip-on covers that block off the connected cable lugs


PD391009

Powerclip busbars

Additional accessories*

Spare parts* * For more information > see page 103

W = 1000 mm W = 1400 mm 4P W= 1000 mm W = 1400 mm 2 Powerclip supports + 2 extremity obturators + mounting hardware 2 IPxxB clip-on covers, L= 200 mm

3P

04111 04116 04121 04126 01210 01201

160 A

04112 04117 04122 04127 01210 01201

250 A

PD390337

04113 04118 04123 04128 01210 01201

400 A

04114 04119 04124 04129 01211 01201

630 A

Electrical characteristics
Rated level
Insulation Ui 750 750 750 1000 Impulse withstand voltage Uimp 8 8 8 8

Rating
160 A 250 A 400 A 630 A

Rated withstand current max.


Short-time withstand current Icw Withstand peak Ipk 10 13 20 25

(kA rms / 1 s)

30 30 52,5 52,5

(k)

(V)

(kV)

Choice of connections depending on devices


Compact NSX

Device to connect

NSX400 horizontal NSX630 horizontal NSX400/630 vertical with or without Vigi NSX100/250 horizontal with or without Vigi NSX100/250 vertical without Vigi

Interpact INS-INV

Fupact INS NG

NSA160 C120, iC120 Multiclip 63/80/160 A 200 A Modular devices

NSX100/250 vertical with Vigi INS-INV250 horizontal INS-INV320/400 horizontal INS-INV500/630 horizontal INS-INV250 vertical INS-INV320/630 vertical INF100/160 horizontal INF100/160 vertical ISFT 100/250 vertical or horizontal INS40/125 3P 4P INS160 NG125 NG160 Vigi NG160

04070 04071 04074 + connection must be made (in enclosure) or 04074 + 04073 (in duct) 04060 04061 + 04062 (in enclosure) or 04061 + connection must be made (with rotary handle in enclosure) or 04061 +04064 (in duct) 04061 + connection must be made (in enclosure)04061 + 04064 (in duct) 04060 04070 04071 04061 + 04062 (in enclosure) or 04061 + 04064 (in duct) 04074 + connection must be made (in enclosure) or 04074 + 04073 (in duct) 04155 + connection must be made (3P) or 04156 + connection must be made (4P) 04061 + connection must be made 04061 + connection must be made 04145 +28947 04145 +28948 04147 or 04148 or 04146 04145 or 04147 or 04148 or 04146 04147 or 04148 or 04146 04148 04147 or 04148 or 04146 04147 or 04148 04151 or04152 04021 04151 or04152

Catalogue numbers (see details on next page)

68

Functional system

Distribution

630 A insulated busbar

Non-Centralised distribution

Busbar connection
DD380522

Power supply block with connection

Description

Compact NSX100/250 horizontal with or without Vigi Interpact INS-INV250 horizontal Compact NSX400 horizontal Interpact INS-INV320/400 horizontal Compact NSX630 horizontal Interpact INS-INV500/630 horizontal Compact NSX100/250 toggle in enclosure Interpact INS-INV250 vertical in enclosure Compact NSX100/250 with or without Vigi in duct Interpact INS-INV250 vertical in duct Compact NSX400/630 with or without Vigi in duct Interpact INS-INV320/630 in duct Compact NSX100/250 rotary handle in enclosure Fupact INF100/160 vertical Fupact ISFT Compact NSX400/630 with or without Vigi in enclosure Interpact INS-INV320/630 in enclosure NSX, Multiclip 200 A, Fupact

Allows connection of

04060 04070 04071

Cat. no.

DD380593

Universal power supply block +prefabricated connections

Universal power supply block +connections must be made (possibility to use insulated flexible bars)
> see page 74

04061 + 04062 04061 + 04064 04074 + 04073 04061 04074


> see page 74

DD381659

Universal power supply block +insulated flexible bars Set of 4 125 A connections, L= 230 mm 35 mm ferrule + 45 angle lug ( insulated covers IPxxB, cat. No 04150) Set of 4 160 A connections, L= 230 mm 45 mm ferrule + 45 angle lug ( insulated covers IPxxB, cat. No 04150) One-piece connection 3/4P - 160 A, L = 150mm bb Fast connection to busbars bb Equipped with male fittings one end for tunnel terminals bb Respects the degree of protection IPxxB bb Neutral is clearly indicated (blue)
DD383274

NG125, NSA equipped with tunnel terminals or comb, INS with tunnel terminals Catalogue numbers 28947 or 28948 NSA160, INS160, NG125, NG160 NSA160, NG160 (located on left-hand side), NG125, INS160, C120, iC120

DD381379

04145 04146 04147

DD383294

One-piece connection 3/4P - 160 A, L = 440mm bb Fast connection to busbars bb Equipped with male fittings one end for tunnel terminals bb Respects the degree of protection IPxxB bb Neutral is clearly indicated (blue)
DD383276

NSA160, NG160 (located on left-hand side), Vigi NG160 (located in the middle), NG125, INS160, C120, iC120

DD383295

04148

DD381405

Additional 35 mm block + connection must be made

Fupact INF100/160 3P horizontal Fupact INF100/160 4P horizontal

04155 04156 04151 04152

12 tap-off blocks for 6 mm and 10 mm cable Respects the degree of protection IPxxB 12 tap-off blocks for 16 mm Respects the degree of protection IPxxB Set of 4 200 A connections Supplied with mouting hardware + Insulating cover

DD383498

All type of device, equipped with tunnel terminals, 160/200 A Multiclip All type of device, equipped with tunnel terminals, 160/200 A Multiclip Multiclip 200A

DD383472

04021 + 04150

Accessories
Connection cover
DD381385

bb Clip-on covers that block off the connected 04150 cable lugs and can be cut as needed. bb They maintain IPxxB with 90 angle lugs and/ or cable sizes from 10 to 25 mm. bb 8 IPxxB covers for Powerclip busbars 04158

Cat. no.

Set of 20 CHC M6 x 12 mm screws for Powerclip busbars

8.8 class mounting hardware

Cat. no.

69

Functional system

Distribution

400 A rear busbars

Non-Centralised distribution

Flat, copper bars with threaded M6 holes every 25 mm for connection along the entire length of the busbars. bb Connection by: vv 16 mm to 50 mm flexible cables, with crimped lugs vv insulated flexible bars
> see page 74

Dd381388

Dd381192

Presentation The rear busbars are mounted directly on the uprights of the framework. There are three and four-pole versions with ratings from 160 to 400 A. Available in two lengths, 1000 and 1400 mm, they can be cut as needed. The connection with a Compact or Interpact incoming device occupies two vertical modules (50 mm each).

Rear busbars 160 / 400 A


PD390532

Barrier protect against direct contact with connections.

Bars supports in insulating material direct installation on the functional uprights.

Bars (Set of 4)

Rating

Insulating support (1) (2) Accessories

Cross-sectional areas of conductors Length 1000 mm 1400 mm Catalogue numbers Barrier, H = 100 mm, supplied with mounting hardware

15 x 5 mm 04161 04171 04191 04198

160 A

20 x 5 mm 04162 04172 04191 04198

250 A

Dd381389

32 x 5 mm 04163 04173 04191 04198

400 A

(1) The insulating supports can receive a fifth bar, 15 x 5 mm or 20 x 5 mm to create an earth bar. (2) Rating (A) 160 250 400 Size of bars Distance between support centres (mm) (3) (mm) Icw (kA rms / 1 s) y 10 y 13 y 15 y 20 y 25 15 x 5 20 x 5 450 300 225 32 x 5

(3) Multiclip 200 A distribution blocks equipped with connections (04029) can be used as intermediate supports (200 mm max.distance between centres) in addition to the top and bottom supports (04191).

Electrical characteristics
Rating Icw (kA)
Short-time withstand current Icw 160 A 250 A 400 A 10 13 15, 20, 25

Ui (V)
Rated peak withstand current Rated insulation level

(kA rms / 1 s)

30 40 55

(k)

1000 1000 1000

(V)

70

Functional system

Distribution

400 A rear busbars

Non-Centralised distribution

Connection between busbar


Set of 4 rear busbar connection - 125 A, L= 230mm A 35 mm ferrule for connection to tunnel terminals + A 45 ring lug Set of 4 rear busbar connection - 160 A, L = 250 mm A 45 mm ferrule for connection to tunnel terminals + A 45 ring lug
DD383511

Designation

bb A comb busbar bb NG125, NSA and INS equipped with tunnel terminals

For the connection of

DD383510

04145

Catalogue numbers

NSA160

04146

Set of 4 rear busbar connection - 200 A Note: Multiclip 200 A distribution blocks equipped with connections (04029) can be used as intermediate supports (200 mm max. distance between centres) in addition to the top and bottom supports.

Multiclip 200 A

04029

DD381458

Set of 4 copper angle brackets - 250 A

Electrical connections between two sets of rear busbars.

04190

DD381659

Insulated flexible bars


> see page 74

NSX100 NSX160/250 NSX400 NSX630 INS125/160 INS250 INS400 INS630 200 A multiclip Fupact 250 Fupact 400 Fupact 630

04742 04743 04751 04753 04742 04743 04751 04752 04743 04746 04751 04753

Accessories
8.8 class mounting hardware
20 bolts M6x20 + 20 nuts + 40 contact washers 40 screws M6x16 + 40 contact washers
DD381398

Catalogue numbers
04194 04195

Set of 4 connectors for copper or aluminium cables Catalogue numbers


E13771

180 A for rigid cables 70 mm


E56852

07051

250 A for rigid cables 185 mm


E56851

07052

400 A for rigid cables 300 mm


E56850

07053

71

Functional system

Distribution

Non-Centralised distribution

630 A Multi-stage busbars in duct


Busbar 160 / 630 A
Dd381396 PD390533

Presentation The multi-stage busbars are installed in a 300 mm wide duct. They are particularly useful for distribution to two enclosures on each side of the duct. All connection points are easily accessible from the front. The inclination of the bars facilitates connections and improves cable running. There are three and four-pole versions with ratings from 160 to 630 A. Available in two lengths, 1000 and 1400 mm, they can be cut as needed.

Front barrier protect against direct contact with connections (in option).

Dd381388

Flat, copper bars with threaded M6 holes every 25 mm for connection along the entire length of the busbars. bb Connection: vv 16 mm to 50 mm flexible cables, with crimped lugs vv insulated flexible bars
> see page 74

Bars (Set of 4)

Rating

Insulating support (1) (2) Accessories (1) Rating (A) 160 250 400 630 Size of bars (mm) 15 x 5 20 x 5 32 x 5 32 x 8

Cross-sectional areas of conductors Length 1000 mm 1400 mm Catalogue numbers Barrier, H = 1500 mm

15 x 5 mm 04161 04171 04192 04197

160 A

20 x 5 mm 04162 04172 04192 04197

250 A

32 x 5 mm 04163 04173 04192 04197

400 A

Dd381395

Bars supports in insulating material direct installation on the functional uprights of the duct.

32 x 8 mm must be made 04174 04192 04197

630 A

Distance between support centres (mm) Icw (kA rms / 1 s) y 10 y 13 y 15 y 20 y 25 450 300 300 (3)

(2) Supplied with mounting hardware for barrier, cat.no. 04197. (3) With Icw 25 kA rms / 0,6 s.: distance between supports 300 mm (Rating 400 A with bars 32 x 5 mm only).

Electrical characteristics
Rating Icw (kA)
Short-time withstand current Icw 160 A 250 A 400 A 630 A 10 13 15, 20 25

Ui (V)
Rated peak withstand current Rated insulation level

(kA rms / 1 s)

30 40 55 55

(k)

750 750 750 750

(V)

72

Functional system

Distribution

Non-Centralised distribution

630 A Multi-stage busbars in duct


Connection between busbar

Dd382305

Set of 4 rear busbar connection - 250 A

Description

bb Compact NSX 100/250 vertical in duct bb Interpact INS-INV 250 vertical in duct

For the connection of

04065

Catalogue numbers

Set of 4 rear busbar connection - 630 A

bb Compact NSX 400/630 vertical in duct bb Interpact INS-INV 320/630 vertical in duct

04075

Dd383499

Set of 4 rear busbar connection - 200 A

Multiclip 200A

04024

DD381659

Insulated flexible bars


> see page 74

NSX100 NSX160/250 NSX400 NSX630 INS125/160 INS250 INS400 INS630 200 A multiclip Fupact 250 Fupact 400 Fupact 630

04742 04743 04751 04753 04742 04743 04751 04752 04743 04746 04751 04753

Accessories
Dd381398

8.8 class mounting hardware


20 bolts M6 x 20 + 20 nuts + 40 contact washers 40 screws M6x16 + 40 contact washers

Catalogue numbers
04194 04195

73

Functional system

Distribution

Insulated flexible bars

Non-Centralised distribution

The insulated flexible bars are tested in a type-tested switchboard environment. Their design takes into account the switchboard architecture where they are often in close proximity to a protection device (circuit breaker or fuse) with significant heat losses. The sizes for the flexible bars indicated below take into account the heat losses of Schneider Electric devices in a Prisma Plus switchboard.

Dd381659

Dd382008

Characteristics
Length Rated insulation level (Ui) 1800 mm 1000V

Connection between device busbar

The flexible bars are determined taking into account the connected device, whatever the internal temperature of the switchboard. The bar sizes indicated below take into account the derating curves of devices.
NSX100 NSX160/250 NSX400 NSX630 INS125/160 INS250 INS400 INS630 200 A multiclip Fupact 250 Fupact 400 Fupact 630

Device

20 x 2 20 x 3 (1) 32 x 5 32 x 8 20 x 2 20 x 3 32 x 5 32 x 6 20 x 3 24 x 5 32 x 5 32 x 8

Size (mm)

04742 04743 04751 04753 04742 04743 04751 04752 04743 04746 04751 04753

Catalogue numbers

(1)  To connect a Compact NSX250 to Powerclip busbars, use a 24 x 5 mm flexible bar (04746).

Connection between busbars

Flexible bars are designed for connections between busbars taking into account the following characteristics: bb a maximum temperature of 60 C inside the switchboard. This corresponds to the average temperature inside a switchboard for an ambient temperature of 35 C bb the maximum withstand temperature for the insulating material is 125 C.
200 A 250 A 400 A 520 A 580 A 660 A

Ie* Max.

20 x 2 20 x 3 24 x 5 32 x 5 32 x 6 32 x 8

Size (mm)

04742 04743 04746 04751 04752 04753

Catalogue numbers

* Rated operational current.

74

Functional system

Distribution

Distribution block

Centralised distribution

DD381399

The 160 A Polybloc is made up of individual elements that can be used alone or with others to make two-pole, three-pole or four-pole distribution blocks. Mounting is very fast. It clips onto a modular rail and is supplied by cables via a tunnel terminal. The connection spring terminals are slanted to facilitate cable entry and bending of the flexible and rigid cables. It is supplied with a cover that also guides the cables.

160 A Polybloc

160 A Polybloc
Dd382981 Dd383300 Dd383658

Catalogue number Total connection capacity Installation Space required

Dd381392

04031 bb Supply direct to a tunnel terminal, for cables up to 70 mm. bb Distribution via cables, up to 6x16 mm cables. Clip onto a modular rail.
Dd384321

70

95

36

Rated insulation level (Ui) Impulse withstand voltage (Uimp) Short-circuit withstand current

750 V 8 kV The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations were tested.The electrical characteristics are perfectly compatible with the connected devices. Neither the temperature derating curves nor the performance levels of the circuit breakers and switch-disconnectors are altered.

Choice of accessories depending on devices


Fupact

Device to connect

INF100/160 vertical ISFT vertical INS40/125/160 NG160

INS NG C120, iC120

Connection must be made + rail 03002 Connection must be made + rail 03002 or 03011 04149 04149 04149

Catalogue numbers

Distribution block connection


Four 160 A connections for modular INS40/125/160 devices, W = 380 mm NG160 Two 45 mm end fittings for C120, iC120 tunnel terminals

Description

For the connection of

04149

Cat. no.

Accessories
Adjustable modular rails
Dd381371

For wall-mounted or floor-standing enclosure For a duct

03002 03011

Cat. no.

75

Functional system

Distribution

Distribution block

Centralised distribution

DD381399

250 A Polybloc

Applications The Polybloc distribution block is designed for installation directly downstream of Compact circuit breakers and Interpact switch-disconnectors devices up to 250 A. It can be rapidly mounted in the horizontal position. Electrical connections are made directly to the device terminals. It has the same width as the devices and does not take up any additional space in the switchboard. The connection terminals are slanted to facilitate cable entry and not exceed the bending radius of the flexible and rigid cables.

3P
PD390549R DD380780 Dd381346

4P
DD380745

Catalogue numbers Total connection capacity Installations

Rated insulation level (Ui) Impulse withstand voltage (Uimp) Short-circuit withstand current

DD381406

Space required

H L P

04033 04034 Supply directly to the terminals of the Compact NSX and Interpact INS devices up to 250 A. Directly on the mounting plates of horizontally mounted Compact NSX100/250 and Interpact INS250 devices in the enclosures. It can also be mounted downstream of vertically mounted Compact NSX100/250 and Interpact INS250 devices in the enclosures. In this case, the Polybloc is mounted on a depth-adjustable modular rail 105 140 138 138 63 63

750 V 8 kV The reinforced breaking capacity due to cascading in circuit-breaker combinations is maintained. The worst-case situations have been tested.

Choice of accessories depending on devices


Compact Interpact

Device to connect

NSX100/250 with or without Vigi horizontal NSX100/250 with or without Vigi vertical INS-INV250 horizontal INS-INV250 vertical INS-INV250 Lateral handle vertical

04033 (3P) 04034 (4P) 04033 (3P) 04034 (4P) + rail 03002 or 03011 04033 (3P) 04034 (4P) 04033 (3P) 04034 (4P) + rail 03002 or 03011 04033 (3P) 04034 (4P) + rail 03002 or 03011 + spacer 04037

Catalogue numbers

Accessories
Adjustable modular rails
Dd381371

For wall-mounted or floor-standing enclosure For a duct

03002 03011

Catalogue numbers

Copper spacer

04037

Catalogue number

35 mm additional blocks
Designation
DD381403

These blocks with screw terminals can be mounted on the 250 A Polybloc for connection of two 35 mm cables per phase.
35 mm, 3P additional blocks (3 blocks) 35 mm, 4P additional blocks (4 blocks) 04155 04156

Catalogue numbers

76

Functional system

Distribution

Distribution block

Centralised distribution

Distribloc 125 et 160 A


Rated operational current (Ie) 40 C
Dd383474

125 A
PG123021 054947

160 A
PD390657

Supply Catalogue numbers Total connection capacity ( for flexible cables)

Distribution block 4P Connections block

Connections characteristics Installation Dimensions

From the top or from bottom From the top or from bottom 04045 04046 04047 Supplied bb Incoming connection in a terminal for 10 to 35 mm cable per phase bb Distribution spring terminals: vv 7 outgoers from 1.5 to 4 mm2 vv 3 outgoers from 2.5 to 6 mm2 vv 2 outgoers from 4 to 10 mm2 bb Distribution in tunnel terminal: vv 1 outgoer from 4 to 16 mm2 For INS100/160 or NSA160, For NG125 andINS125 Installed on the right or left. Set of four flexible Set of 4 flexible connections 35mm2, L= 210mm connections supplied with the distribution block bb Clipped onto a modular rail: 12 modules (9 mm each) bb Screwed to plain or slotted backplate. Distances between centres = 100 x 75 mm.
Dd381608 Dd381609

Rated insulation level (Ui) Impulse withstand voltage (Uimp) Short-circuit withstand current Degree of protection Accessories supplied

750 V 8 kV The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested. IPxxB An identification label Adhesive labels for phase identification

Distribloc 63 A
Rated operational current (Ie) 40 C 63 A
PB104500 PB104499

Incoming Catalogue numbers Total connection capacity ( for flexible cables) Installation Dimensions

Distribution block 4P

From the top From bottom 04040 04041 bb Incoming connection in a tunnel terminal for 25 mm cable per phase bb Distribution spring terminals: vv 4 outgoers from 6 mm2 for each phase vv 12 outgoers from 6 mm2 for the neutral bb Clipped onto a modular rail: 8 modules (9 mm each)
Dd122616

Rated insulation level (Ui) Rated operational voltage (Ue) Impulse withstand voltage (Uimp) Short-circuit withstand current Degree of protection

500 V CA 440 V CA 6 kV Up to the breaking capacity of Schneider Electric circuit breakers, even in cascading configuration IP20

77

Functional system

Distribution

Distribution block

Centralised distribution

Multi-stage distribution block 160 / 630 A


Rated operational current (Ie) for 40 C
PD390659

160 A
DD381342

250 A
Dd381343

400 A

630 A

Catalogue numbers Total connection capacity Installation

Composition

Rated insulation level (Ui) Impulse withstand voltage (Uimp) Rated short-time withstand current (Icw) Rated peak withstand current (Ipk)

750 V 8 kV 10 kA rms /1 s 30 k

DD381344

Busbar size Space required

04052 04053 04054 04055 bb 13 threaded M6 holes for outgoers bb Four 12.2 mm diameter holes to supply the distribution block. bb Screwed horizontally onto the functional uprights of wall-mounted and floor standing enclosures. bb Screwed vertically onto the functional uprights of the 300 mm wide duct. bb Screwed to plain or slotted backplate. bb Two staggered supports made of an insulating material bb Four slanted copper bars with holes every 25 mm bb M6 hardware bb One IPxxB insulating barrier for the front. 15 x 5 mm 20 x 5 mm 32 x 5 mm 32 x 8 mm

13 kA rms /1 s 30 k

20 kA rms /1 s 40 k

25 kA rms /1 s 40 k

78

Functional system

Distribution

Distribution block

Centralised distribution

Multi-stage distribution block 40 / 125 A


Distribution block 2P
058923d

4P
058930d

Catalogue numbers Additional neutral bar Rated operational current (Ie) Pole number Supply (screw terminal) per phasis Distribution (screw terminal) per phasis Dimensions (H x W x P) Electrical characteristics

13506 100 A 2P 1 term 16mm2 3 term 6 mm2 3 term 10 mm2

13507 125 A 2P 1 term 25mm2

13508 13516 40 A 4P 2 term 10mm2

13510 13515 100 A 4P 1 term 16mm2

13512 13517 125 A 4P 1 term 25mm2

13514 13518 4P 1 term 25mm2 7 term 6 mm2 7 term 10 mm2 2 term 16 mm2 15 modules (9 mm) 81 x 134 x 50 mm

Installation

5 term 6mm2 11 term 6mm2 3 term 6 mm2 5 term 6 mm2 5 term 10 mm2 3 term 10 mm2 5 term 10 mm2 2 term 16 mm2 2 term 16 mm2 7 modules (9 mm) 12 modules (9 mm) 10 modules (9 mm) 7 modules (9 mm) 12 modules (9 mm) 40 x 62 x 50 mm 40 x 107 x 50 mm 81 x 89 x 50 mm 81 x 62 x 50 mm 81 x 107 x 50 mm bb Rated insulation level (Ui): 500 V CA bb Short-circuit withstand current: compatible with all Schneider Electric circuit-breakers. bb With other device, it is advised to check the energy limiting curve of the upstream device bb Rated short-time withstand current (Icw): 3.5 kA rms /1 s bb Rated peak withstand current Ipk = 20 k Designed to be clipped onto rail

Joinable distribution blocks 80 A


Distribution block 1P
030925d 030925d

2P
030925d

Catalogue numbers Pole number Supply per phasis Distribution per phasis Electrical characteristics Installation Dimensions

14936 14938 1P 1P 2 1 screw terminal 35 mm2 1 screw terminal 25 mm 4 screw terminal 16 mm2 4 screw terminal 25 mm2 bb Rated operational current (Ie): 80 A bb Rated insulation level (Ui): 500 V CA Designed to be clipped onto rail 2.5 modules 18 mm

14937 2P 2 x 2 screw terminal 25 mm2 2 x 4 screw terminal 16 mm2

14939 2P 2 x 2 screw terminal 35 mm2 2 x 4 screw terminal 25 mm2

5 modules 18 mm

79

Functional system

Distribution

Distribution block

Centralised distribution

Multiclip 63 / 80 A
Multiclip 63 / 80 A 63 A
DD383403

80 A
PD104505

PD381661

Catalogue numbers Characteristics

Supply Distribution

Installation

04008 b Rating: 63 A b 4P b 24 modules (9 mm), 12 modules (18 mm) Tunnel terminals up to 25 mm2 b Spring terminals: v 4 for each phase (2 x 4 mm2 + 2 x 6 mm2) v 8 for the neutral (4 x 4 mm2 + 4 x 6 mm2) By clipping at the rear of a modular rail, or by screwing.
DB404608

04000 b Rating: 80 A b 4P b 48 modules (9 mm) 24 modules (18 mm) Tunnel terminals up to 25 mm2 b Spring terminals: v 6 for each phase (6 mm2) v 18 for the neutral (6 mm2) By clipping at the rear of a modular rail, or by screwing.
DB124195

Accessories supplied

100 mm long bared copper connections 10 of 4 mm2 + 6 of 6 mm2

6 mm2 bared copper connections (12 blue + 12 black)

80

DB124196

PD384088

Functional system

Distribution

Distribution block

Centralised distribution

Multiclip 160 / 200 A


Multiclip 160 / 200 A 200 A
PD390661R DD381672 DD381670 DD381671

160 A
DD381673

Catalogue numbers Characteristics

Supply

Distribution

Installation Accessories supplied

04012 04013 04014 04018 bb 3P bb 4P bb 4P bb 2P bb Rating: 200 A bb Rating: 200 A bb Rating: 200 A bb Rating: 160 A bb 48 modules (9 mm), bb 48 modules (9 mm), bb 48 modules (9 mm), bb 24 modules (9 mm), 24 modules (18 mm) 24 modules (18 mm) 24 modules (18 mm) 12 modules (18 mm) 1/2 row bb Rated insulation level (Ui): 750 V bb Impulse withstand voltage (Uimp): 8 kV bb Short-circuit withstand current: the reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested. vv 10 mm cable outgoer: Imax = 50 A vv two 10 mm cables: Imax = 63 A. bb From Powerclip insulated busbars in a wall-mounted or floor-standing enclosure (04021) bb From lateral, channelled busbars in a cubicle (connection must be made) bb From busbars in the duct of a wall-mounted or floor-standing enclosure (04024) bb From busbars in the rear of a wall-mounted or floor-standing enclosure (04029) bb 12 connection points for bb 12 connection points for each phase bb 6 connection points phase and neutral bb 18 connection points for the neutral for each phase bb 9 connection points for the neutral bb Clipped onto the rear of modular rail bb Screwed to plain or slotted backplate. bb 100 mm long, bared 10 mm copper connections bb 2 sets of 12 connections bb Protection covers for the supply terminals (IPxxB) 100 mm long, bared 10 mm bb The hardware required for the supply terminals copper connections bb Protection covers for the supply terminals (IPxxB) bb The hardware required for the supply terminals

Connections to the block


Description
Dd383472

Connection 4P 200 A (supplied with mounting hardware)

Powerclip busbars

Supplied with

04021

Catalogue numbers

Connection 4P 200 A (supplied with mounting hardware)

Dd383617

Busbars in duct

04024

Connection 4P 200 A (supplied with mounting hardware) Connection 4P 160 A for Multiclip 1/2 row

A rear busbars Device

04029 04030

Spare parts
Description
DD384505

4 terminal covers for 200 A Multiclip

01202

Catalogue number

81

Functional system

Distribution

Comb busbars

Centralised distribution

Comb busbars for DPN


Comb busbar
DD382981

Lateral tooth-caps

Tooth-caps

Insulated connectors

Catalogue numbers Characteristics

2-pole 3-pole

21086

21088

21089

21094

21096 21096 6 modules (9 mm) 3 modules (18 mm) Set of 12 -

21098 21098 Set of 4 For 25mm2 cable -

Supplied accessories

21090 21092 24 modules (9 mm) 48 modules (9 mm) 12 modules (18 mm) 24 modules (18 mm) Rating: 80 A Quantity per catalogue numbers: 1 4 lateral tooth-caps 1 tooth-caps 2 tooth-caps

21093 21095 96 modules (9 mm) 48 modules (18 mm) Set of 40 0 0 -

Comb busbars for C60 and iC60


Comb busbar
DB123466

Lateral tooth-caps

Tooth-caps

Insulated connectors

Catalogue numbers

Characteristics

1-pole 2-pole 3-pole 4-pole

Supplied accessories

14881 14891 14882 14892 14883 14893 14884 14894 bb 24 modules (9 mm) bb 48 modules (9 mm) bb 12 modules (18 mm) bb 24 modules (18 mm) bb 1 piece bb Set of 2 Rating: 80 A with 1 supply point 100 A with 2 supply points 2 lateral tooth-caps

14886 14886 14887 14887 Set of 40

14888 14888 14888 14888 Set of 40

14885 14885 14885 14885 Set of 4 For 25mm2 cable

Comb busbars for C120 and NG125


Comb busbar
054948d

Lateral tooth-caps + tooth-caps

Catalogue numbers

Characteristics

1-pole 2-pole 3-pole 4-pole

Supplied accessories

14814 bb 45 modules (9 mm) bb 48 modules (9 mm) bb 22.5 modules (18 mm) bb 24 modules (18 mm) bb 1 piece bb Set of 1 Rating: 125 A 63 A maxi by outgoers Tooth-caps (8 for 1 and 2-pole, 4 for 1 and 2-pole) 2 lateral tooth-caps

14813

14811 14812

14818 14818 14818 14818 4 lateral tooth-caps +20 tooth-caps

82

Functional system

Distribution

Earth blocks / neutral blocks

Centralised distribution

Earth blocks / neutral blocks


50mm terminal block kit
2
PB101638_68

25 mm terminal block kit


2

4x6mm2 terminal block kit


PB101639_32

Terminal block support kit

Splitter block kit

DB107883

DB107884

DB107885

DB107888

DB107891

DB107887

Catalogue numbers Characteristics

PRA90045 bb Set of 2 bb W = 2 blocks

PRA90046 bb Set of 5 bb W = 1 blocks

PRA90047

PRA90051

PRA90048

PRA90050

PRA90049

bb Set of 10 bb Set of 1 bb W = 1 blocks bb W = 34 blocks max. bb Mounting on the functional uprights 63 A to 40C -

Permissible current

160 A to 40C

90 A to 40C

bb Set of 4 bb Set of 1 bb Set of 10 bb W = 1 blocks bb W = 8blocks bb W = 2blocks bb Designed to be clipped onto modular rail bb Ui: 400 V - Uimp: 6 kV 90 A with 1 jonction 160 A with 2 jonctions in parallel

Examples of composition
Single-phase terminal block
E101369d E101370d

Single-phase distribution block


E101371d E101372d

3-phase distribution block


E101373d

Used Catalogue numbers

90 A 1 x PRA90051 1 x PRA90045 2 x PRA90046 1 x PRA90050

160 A 1 x PRA90051 1 x PRA90045 2 x PRA90046 2 x PRA90050

80 A 2 x PRA90048 1 x PRA90045 2 x PRA90046 1 x PRA90050

125 A 2 x PRA90048 1 x PRA90045 2 x PRA90046 2 x PRA90050

160 A 3 x PRA90048 4 x PRA90045 3 x PRA90046 4 x PRA90050

DB107886

83

Functional system

Distribution

Earth bars

Centralised distribution

Earth bars
They are installed: bb In a duct, which may be a dedicated zone, totally separate from the devices bb In the device compartment, at the top or bottom.
Dd383501

Earth blocks with spring terminals


Bare earth bar Earth blocks with spring terminals to clip-on
Dd381560 Dd381560

Dd381560

Catalogue numbers Characteristics

04201 bb Size: 12 x 3 mm bb W = 330 mm bb Equipped with a 35 mm tunnel terminal (for earth blocks with spring terminals)

04214 bb 12 x 4 mm2 bb Set of 4 bb W = 75 mm

04215 bb 3 x 16 mm2 bb Set of 4 bb W = 37 mm

Earth bar with clamps


Earth bar with clamps
DD381516

Catalogue numbers Characteristics

04200 bb Earth bar with 40 clamps + one 35 mm terminal bb W = 450 mm

04202 bb 2 earth bars with 20 clamps + one 35 mm terminal bb W = 200 mm

Dd383513

Neutral bars
Kit for neutral bar
DD382529

Catalogue number Description

04210 Insulating spacers to insert under an earth bar

Accessories for top or bottom installation


Fixing mode On rear of modular rail
DD383512

On 45 supports
DD383514

On fixing brackets
DD383515

On hexagonal spacers
DD383516

Catalogue numbers Characteristics Used earth bars

04205 Set of 2 supports

03005 Set of 2 supports

04206

04207

04208 H= 80 mm

03185

03186

03187

In enclosure: earth bars W = 450 mm with clamps or spring terminals In duct: earth bar with clamps W = 200 mm

H= H= 15 mm 45 mm Set of 2 brackets

H= H= H= 9 mm 23 mm 55 mm Set of four M5 hexagonal spacers

84

Functional system

Distribution

Earth bars

Centralised distribution

Accessories for installation on the side


Fixing mode

This solution saves considerable space in the device zone and avoids the need for the 300 mm wide duct.

2 fixing brackets for the earth bar on the functional uprights


Dd383517

Catalogue numbers Characteristics Used earth bars

04206 04207 04208 H = 15 mm H = 45 mm H = 80 mm Set of 2 brackets Earth bar with clamps or spring terminals.

Accessories for installation in duct


Fixing mode On mounting plate for terminal block and earth bar
Dd383495

Catalogue number Characteristics

Used earth bars

04220 bb A mounting plate (04220), made up of two supports, is equipped with: vv a 1600 mm modular rail (04226) for terminal blocks vv an earth bar The supports have cut-outs that can be used to easily tie down the connection wires. Earth bar with clamps or spring terminals.

Accessories for installation on a dedicated mounting plate, in device compartment


Fixing mode On mounting plate
DD383488

Catalogue number Characteristics Used earth bars

04223 The mounting plate for terminal blocks (04223) can be equipped with two earth bars with clamps 200 mm earth bar with clamps.

85

Functional system

Distribution

Terminal blocks

Centralised distribution

Terminal block layout

They can be installed: bb In a duct, which may be a dedicated zone, totally separate from the devices bb In the device compartment, at the top or bottom.


Size of the conductor 4 mm
DD383818

Fast-connection terminal blocks


2

4 mm2
DD383819

6 mm2
DD383820

10 mm2
DD383821

16 mm2
DD383821

Number of points Catalogue 1 Terminal Grey numbers blocks and Blue quantity Green / Yellow 2 Separation partition 3 End Grey plate Blue 4 2-pole insulated commoning link

1 incomer, 1 outgoer AB1 RRN435U2GR 100 AB1 RRN435U2BL 100 AB1 RRNTP435U2 100 AB1 RRNTPAC442 10 AB1 RRNAC442GR 10 AB1 RRNAC442BL 10 AB1 RRAL42 10

1 incomer, 2 outgoers AB1 RRN435U3GR 100 AB1 RRN435U3BL 100 AB1 RRNTP435U3 100 AB1 RRNTPAC443 10 AB1 RRNAC443GR 10 AB1 RRNAC443BL 10 AB1 RRAL42 10

1 incomer, 1 outgoer AB1 RRN635U2GR 50 AB1 RRN635U2BL 50 AB1 RRNTP635U2 50 AB1 RRNTPAC642 10 AB1 RRNAC643GR 10 AB1 RRNAC643BL 10 AB1 RRNAL62 10

1 incomer, 1 outgoer AB1 RRN1035U2GR 50 AB1 RRN1035U2BL 50 AB1 RRNTP1035U2 50 AB1 RRNTPAC1042 10 AB1 RRNAC1042GR 10 AB1 RRNAC1042BL 10 AB1 RRAL102 10

1 incomer, 1 outgoer AB1 RRN1635U2GR 50 AB1 RRN1635U2BL 50 AB1 RRNTP1635U2 50 AB1 RRNTPAC1642 10 AB1 RRNAC1642GR 10 AB1 RRNAC1642BL 10 AB1 RRAL162 10

Width

6 mm

6 mm

8 mm

10 mm

12 mm


Size of the conductor 35 mm2
501685_1R

Terminal blocks screw technology


70 mm2
501686_1R

150 mm2
501687_1R

Number of points Catalogue 1 Terminal Grey numbers blocks and Blue quantity 2 2-pole insulated commoning link

1 incomer, 1 outgoer AB1 VVN3535U 20 AB1 VVN3535UBL 20 AB1 ALN352 10 (insulated)

1 incomer, 1 outgoer AB1 VVN7035U 20 AB1 VVN7035UBL 20 AB1 ALN702 10 (non-insulated)

1 incomer, 1 outgoer AB1 VVN15035U 10 AB1 VVN15035UBL 10 AB1 ALN1502 10 (non-insulated)

Width

16 mm

24 mm

28 mm


Fixing mode Directly on the functional uprights
DD383503 DD383504

Accessories for top or bottom installation


On 45 supports On fixing brackets
DD383505

On hexagonal spacers
DD383506

Catalogue numbers Characteristics

03002 bb Depthadjustable modular rail bb W = 432 mm

03004

03005

04206

04207

04208

03195 H = 9mm

03196

03197

bb Rear modular bb Set of 2 supports rail bb Rail catalogue numbers 03004 bb W = 432 mm ordered separately

H= H= H= 15mm 45mm 80mm bb Set of 2 brackets bb Rail catalogue numbers 03004 ordered separately

H= H= 23mm 55mm bb Set of four M6 hexagonal spacers bb Rail catalogue numbers 03004 ordered separately

86

Functional system

Distribution

Terminal blocks layout

Centralised distribution

Dd383500

Accessories for installation in the duct


Mounting In a duct
DD383502

Catalogue number Characteristics

04220 bb A mounting plate, made up of two supports can be equipped with: vv a modular rail for the terminal blocks, that is 1600 mm long, can be cut to length and has 6.4 mm holes every 450 mm vv an earth bar. bb The supports have cut-outs that can be used to easily tie down the connection wires.

Accessories for installation on a dedicated mounting assembly

This mounting assembly is used to easily install and connect a large number of terminal blocks in a minimum amount of space. It is particularly useful when a duct is not warranted or cannot be installed.

Mounting

In device compartment
DD383507

Catalogue number Characteristics

04223 bb Mounting brackets, fixed to the functional uprights at the top or bottom of the enclosure, is equipped with four 200 mm symetrical rails. They are installed vertically to facilitate cable running. bb To facilitate mixing of different size terminal blocks and ensure convenient connections from the front or the side, the distance between rails and the depth of each rail can be adjusted. bb The assembly has cut-outs that can be used to easily tie down the connection wires. bb Earth bars, supplied separately, can be installed between the rows of terminal blocks to form different configurations, e.g.: vv four sets of terminal blocks vv 3 sets of terminal blocks + one or two earth bars (W = 290mm). bb The mounting assembly occupies a height of 250 mm, i.e. five 50mm vertical modules.

Accessories
Markers
Catalogue numbers
DG113069

Label
AB1 S1

Stop plate
AB1 AB8P35

Characteristics

Marking Blank 1 to 10 11 to 20 21 to 30 31 to 40 41 to 50 51 to 60 61 to 70 71 to 80 81 to 90 91 to 100 L1 L2 L3 + red blue Clip-on Set of 25

6 mm pitch AB1 BV6 AB1 B610 AB1 B620 AB1 B630 AB1 B640 AB1 B650 AB1 B660 AB1 B670 AB1 B680 AB1 B690 AB1 B6100 AB1 B6L1 AB1 B6L2 AB1 B6L3 AB1 BV6RP AB1 BV6BM

8 mm pitch AB1 BV8 AB1 B810 AB1 B820 AB1 B830 AB1 B840 AB1 B850 AB1 B860 AB1 B870 AB1 B880 AB1 B890 AB1 B8100 -

Clip-on 4.5 x 8.3 mm Set of 500

Screwable Set of 100

87

Prisma Plus G enclosures

Prisma Plus G enclosures

Contents

IP30, IP31, IP43 enclosures.......................................91


Presentation..................................................................................91 Wall-mounted and floor standing enclosures.................................94 Combinations................................................................................96 Installation / lifting accessories......................................................97 Gland plates..................................................................................98 Accessories...................................................................................99 Door accessories.........................................................................100 Spare-parts..................................................................................101 Dimensions..................................................................................104

IP55 enclosures......................................................... 107


Presentation................................................................................107 IP55 enclosures...........................................................................110 Multiple combinations.................................................................. 111 Installation accessories...............................................................112 Wall-mounted enclosures IP55 gland plates................................113 Partial doors and functional units.................................................114 Side panels with cut-outs.............................................................115 Door accessories.........................................................................116 Spare-parts..................................................................................117 Dimensions..................................................................................118

89

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Presentation

For safe and upgradeable electrical switchboards

> Safety of people and property > Continuity of service > Optimization and upgradeability > Ergonomics and complete accessibility > Controlled costs (installation, maintenance) and delivery times

100% reliable and in compliance with existing standards  All the components (switchgear, splitter blocks, prefabricated connections, etc.) have been designed to work together. All switchboard configurations have been tested. Optimized, upgradeable installation With Prisma Plus G, you can build the right switchboard for your customer, sized precisely to fit costs and needs. Thanks to the organization around functional units, the installation evolves simply while preserving its original performance. Ease of setup The complete accessibility of all mounting and connection points facilitates assembly and cabling in the workshop. The functional units are clearly identified: operations are intuitive and reliable, and connection and checking are performed naturally.

91

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Presentation

Surface mounting enclosures

Commercial buildings: hotels, offices, shops, etc. Industry: technical room, etc.

Enclosure delivered flat: total accessibility Designed for electrical continuity

bb160 A bbIP30 bbIK07/08

Gland plate

PD390300

bb Dismountable and cuttable

Quick fastening on hook-on rail

bb Easy wall mounting

Safety

bb Powerclip busbars, IPxxB, pre-fitted

Ergonomic handle Quick-connect terminal blocks

Fast operation and easy maintenance


bb Straightforward organization in functional units

Ergonomics and safety


bb Easy front plate handling thanks to the ergonomic gripper bb Legible "Open/closed" positions of front plate bb Integrated front plate sealing function

Continuity of service

bb Direct accessibility of functional unit thanks to the front plate hinges kit bb Total accessibility of switchgear thanks to the installation of hinges on all front plate (allows the front panel to be made swivelling)

PD390240

Main characteristics

Steel sheet metal with electrophoresis treatment + hot-polymerised polyester epoxy powder. Enclosure: bb width: 600 mm, with duct: 300 mm bb height: 330 to 1380 mm, bb depth: 205 mm without door / 250 mm with door.

Designation
G IP30 - IP31 - IP43 enclosure
Rated operational current Color Standards conformity Degree of protection Degree of protection against mechanical impacts Isolation Doors 630 A - Icc = 50 kA White colour RAL 9001 EN 62208, IEC 61439-2 IP30 with or without door, IP31 with canopy + door, IP43 with canopy + door + gasket IK08 with door, IK07 without door Class 1 bb Plain or transparent, opening to right or left bb By design, electrical continuity of moving parts (hinges) bb Supplied with a handle and keylock (key 405) Distance behind door = 58mm (possibility of push-buttons, lamps installation). Surface mounting, floor standing, flush mounting via a kit

Easy design with

Rapsody software
> see page 25

Mounting

> see page 97

93

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Wall-mounted and floor standing enclosures


IP30 630 A enclosures

Reversible doors (opening to left or right), equipped with a handle and keylock (key 405).

Wall-mounted enclosures, width 600 mm


DD380618

Ducts, width 300 mm


DD382927

DD380622

DD380623

DD380624

DD382928

DD380626

No. of vertical modules of 50mm 6 9 12 15 18 21 24 27

Height inmm 330 480 630 780 930 1080 1230 1380

Enclosure

Plain door

Transparent door

No. of vertical Height modules of inmm 50mm 6 9 12 15 18 21 24 27 330 480 630 780 930 1080 1230 1380

Rear + top and bottom plates (1) 08172 08173 08174 08175 08176 08177 08178 08179

Plain door

08102 08103 08104 08105 08106 08107 08108 08109

08122 08123 08124 08125 08126 08127 08128 08222

08132 08133 08134 08135 08136 08137 08138 08232

08182 08183 08184 08185 08186 08187 08188 08282

(1) Supplied with a combination kit for enclosure + duct association.

Floor standing enclosures IP30

Reversible doors (opening to left or right), equipped with a handle and keylock (key 405). bb two basic floor standing enclosures cannot be combined; bb to create a switchboard comprising a number of enclosures, use a basic floor standing enclosure and one or more floor-standing enclosure extensions; bb floor standing enclosure extensions are supplied with a combination kit for the basic floor standing enclosure; bb cables can be run on the sides of the plinth (diameter y 140 mm).

Floor standing enclosures, width 600 mm


Dd380631 Dd381354

Enclosure extensions, Ducts, width 300 mm width 600 mm

Dd380634

Dd380636

Dd380636

Dd380635

Dd380636

Dd380637

Dd380638

Dd380639

DD380627

Transparent door 08197 08198 08292

No. of vertical modules of 50mm 27 30 33

Height Basic Plain inmm enclosure door 1530 1680 1830 08202 08203 08204 08222 08223 08224

Transparent door 08232 08233 08234

No. of vertical modules of 50mm 27 30 33

Height inmm 1530 1680 1830

Rear

Plain door

Transparent door 08232 08233 08234

Rear + top and bottom plates 08272 08273 08274

Plain door

08212 08222 08213 08223 08214 08224

08282 08292 08283 08293 08284 08294

Partitionning

> see page 59

> see page 101

Spare parts (rear accessories, door accessories, sides, uprights, etc. )

94

Dd380640

Transparent door

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Wall-mounted and floor standing enclosures


Accessories to increase the degree of protection IP

Canopy to increase the IP value from IP30 to IP31


Dd381257

Gasket for the door to increase the IP value from IP31 to IP43
Dd381268

Used with

1 wallmounted enclosure

1 wallmounted enclosure + 1 duct (1)

2 wallmounted enclosures

2 wallmounted enclosures + 1 duct (1)

1 wallmounted enclosure + 2 ducts (2)

Enclosures or a duct from 6 to 33modules

Catalogue numbers Designation

08830

08832

08831

08833

08827

08841

The addition of a canopy over a wall-mounted or floor standing enclosure equipped with When the switchboard is equipped with a canopy, a door ensures compliance with the degree of protection IP31. a gasket for the doors ensures compliance with the degree of protection IP43. L = 5.3 m

(1) Whatever the duct position. (2) Ducts on the sides.

Wall-mounted enclosures, width 300 mm


Dd383028

Dd382928

Dd383030

Dd380626

No. of vertical modules of 50mm 6 9 12 15 18 21 24 27

Height inmm

Rear + top and bottom plates 08172 08173 08174 08175 08176 08177 08178 08179

Side panels

Plain door

330 480 630 780 930 1080 1230 1380

2 x 01040 2 x 01041 2 x 01042 2 x 01043 2 x 01044 2 x 01045 2 x 01046 2 x 01035

08182 08183 08184 08185 08186 08187 08188 08282

Floor standing enclosures, width 300 mm


Dd380631

Dd380631

Dd383030

Dd380639

No. of vertical modules of 50mm 27 30 33

Height inmm 1530 1680 1830

Rear + top and bottom plates 08272 08273 08274

Side panels

Plain door

2 x 01035 2 x 01034 2 x 01033

08282 08283 08284

Spare parts (rear accessories, door accessories, sides, uprights, plinths, etc.)
> see page 101

Dd380640

Transparent door 08292 08293 08294

Dd380627

Transparent door 08197 08198 08292

95

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Combinations

Multiple combinations
Combination kits Horizontal

To make the combination more rigid, particularly during transport, it is mandatory to use a set of cross-members secured to the rear of the switchboard.

Vertical

1 wall-mounted enclosure + 1 duct Set of two lifting/reinforcement 08812 cross-members or vertical uprights + combination kit (2) DD384000

For wall-mounted enclosure

1 wall-mounted enclosure + 2 ducts 08811 -

2 wall-mounted enclosures 08811 08816

2 wall-mounted enclosures + 1 duct 08813 08816

2 wall-mounted enclosures +2 ducts 08814 08816

2 wall-mounted enclosures +3 ducts 08826 08816

2 wall-mounted enclosures 08817 (1) 08816

For floor standing enclosure

1 floor standing enclosure + 1 duct

1 floor standing enclosure + 2 ducts 08811 -

1 floor standing enclosure + 1 enclosure extension 08811 -

DD384000

Set of two lifting/reinforcement 08812 cross-members or vertical uprights + combination kit (2) -

1 floor standing enclosure + 1 duct +1enclosure extension 08813 -

1 floor standing enclosure +2 ducts +1enclosure extension 08814 -

1 wall-mounted enclosure +3 ducts +1enclosure extension 08826 -

1 floor standing enclosure + 1 wall-mounted enclosure 08817 (1) 08816

+ plain plate

08882

Combination kits

Multiple

DD384000

2 wall-mounted enclosures + 2 ducts Set of two lifting/reinforcement 08812 cross-members Set of two vertical uprights (1) 08817 + combination kit (2) 08816

For wall-mounted enclosures

4 wall-mounted enclosures 08811 08817 08816

4 wall-mounted enclosures + 2 ducts 08813 08817 08816

4 wall-mounted enclosures +4 ducts 08814 08817 08816

4 wall-mounted enclosures +6 ducts 08826 08817 08816

2 additional ducts must be made 2 supplied with the ducts

2 additional wall-mounted enclosures must be made 2 supplied with the enclosure extensions

+ multiple combination kit


DB124228

08818

08818

2 x 08818

3 x 08818

4 x 08818

08818

08818

For floor standing enclosure

1 floor standing enclosure + 1 wall-mounted enclosure + 2 ducts

1 floor standing enclosure + 1 enclosure extension + 2 wall-mounted enclosures 08811 08817 08815

Set of two lifting/reinforcement 08812 cross-members Set of two vertical uprights 08817 + combination kit (2) 08815
DD384000

1 floor standing enclosure + 1 enclosure extension + 2 ducts + 2 wall-mounted enclosures 08813 08817 -

1 floor standing enclosure + 1 enclosure extension +4 ducts + 2 wall-mounted enclosures 08814 08817 -

1 floor standing 2 more ducts enclosure + 1 enclosure extension +6 ducts + 2 wall-mounted enclosures 08826 must be made 08817 -

2 floor standing enclosures + 2 additional wall-mounted enclosures must be made -

+ multiple combination kit + plain plate

08818 08882

08818 2 x 08882

2 x 08818 2 x 08882

3 x 08818 2 x 08882

4 x 08818 2 x 08882

08818 -

08818 08882

(1) Note: for more than 33 combined modules, these vertical uprights are mandatory. (2) A combination kit is supplied with each duct or enclosure extension. It can be necessary to use one kit more than those already supplied.

96

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Installation / lifting accessories


Lifting accessories

The lifting rings are used to move a single wall-mounted or floor standing enclosure. For combined enclosures, use the lifting/reinforcement cross-members (see below).

2 lifting rings for single wall-mounted or floor standing enclosures


DD384010

Lifting/reinforcement cross-members for combined enclosures


DD381653

Catalogue numbers Characteristics

08801

08812

08811

08811

08813

08814

08826

Set of two lifting rings

Have 2 types of holes: for lifting and for mounting on a wall

Installation possibilities

Switchboards can be mounted on a wall in three manners: with the hook-on rail system, via the inside of the enclosure or using external wall-mounted brackets. Combined enclosures can be mounted using the lifting/reinforcement crossmembers set of two lifting/reinforcement cross-members.

Hook-on rail system


DD384036

Mounting via the inside


DD384038

Mounting using the external wall-mounted brackets


DD384037

Catalogue numbers Characteristics

Delivered with the enclosure The enclosure comes with 2 cross-members secured to the back of the enclosure (top and bottom) and a support rail (with levelling adjustment) for screwmounting on the wall. The enclosure is easily mounted on the hook-on rail system.

08804 The enclosure can be mounted through 4 external wall-mounted brackets. the spacers in the 4 holes provided on the enclosure using using 8 mm diameter screws (2 knockouts can be removed if necessary to provide 2 other holes).

Plinth raiser
For floor standing enclosure
Dd380633

Catalogue numbers Characteristics

08805 For basic floor standing enclosure or extension

08807 For a duct

Flush-mounting kit
For wall-mounted enclosure
Dd381256

Catalogue numbers Characteristics

08819 6 to 18 modules

08820 21 to 27 modules

97

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Gland plates

G gland plates

Enclosures (wall-mounted, floor standing, ducts) are supplied with a plastic gland plate installed on the top or bottom for wall-mounted enclosures and the top for floor standing enclosures. For some connections needs, the existing plastic gland plate can be replaced by this metal gland plate.

Plain metal gland plates


Dd382817

Metal plates with cut-outs + plastic gland plates


Dd380861

Used with Cat. no.

At the top or bottom of a wall-mounted enclos. or duct, at the top of a floor standing enclos. Wall-mounted or floor standing enclos. Duct 08870 08874

Used with Catalogue numbers

Using at the top or bottom of a wall-mounted enclosure (+ duct) at he top of a floor standing enclosure (+ duct) Wall-mounted or floor standing enclosure. Duct 08880 08884

FL21 cut-out metal plates


Metal plate with cut-outs

Trunking spreader
Trunking spreader
Dd381636

This plastic gland plate can be replaced by an interface plate with cut-outs for special cable entry systems made of an insulating material (plain, with knockouts or membrane-type).

Metal plate with cut-outs


Dd382933

Cat. no. 08824 Characteristics For a professional-looking connection between the trunking and the enclosure. Can be installed at the top or bottom. The spreader is marked for cut-outs for standard trunking sizes. The maximum capacity is two 250 x 80 mm trunking sections.

Used with Catalogue numbers

Wall-mounted or floor standing enclosure 08871

Duct 08875

Metal gland plates for plinth


DB124234 DB124235

Used with Catalogue numbers

Between the plinth and the bottom of a floor standing enclosure or duct, for ensuring IP20 Floor standing enclosure Duct 08887 08888

FL21 gland plates, plain with knockouts or membrane-type

The gland plates are easy to install using the mounting kit (supplied with each gland plate) that positions and holds the nuts during installation. This makes it possible to mount the gland plates using a single tool.

Gland plates

Plain
Dd382934

With knockouts
Dd382935 Dd382935 Dd382935

Membrane-type
Dd382936 Dd382936 Dd382936

Catalogue numbers M12 M12 or M20 M16 or M25 M20 M20 or M32 M25 or M40

08881 -

08891 4 4 4 -

08892 2 2

08895 5 8 -

Number of entries

12

13

From 5 to 7 mm dia. From 6 to 10 mm dia. From 7 to 12 mm dia. From 8 to 12 mm dia. From 10 to 14 mm dia. From 12 to 18 mm dia. From 14 to 20 mm dia. From 17 to 32 mm dia. From 20 to 26 mm dia. From 28 to 60 mm dia.

08872 4 4 12 4 1 25

08896 2 6 8 16 2 1 35

08897 2 2

98

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Accessories

Partial doors
Type Plain door Partial door with cut-outs
Dd381636

(for 72 x 72 or 96 x 96 mm devices)

Catalogue numbers Characteristics

Partitionning > see page 59 Canopy - Gasket > see page 95

Dd381636

08850 08851 Height: 6 modules. Useful height behind a partial door: 5modules. Installation on a wall-mounted enclosure at least 12 modules high (H u 630 mm). Reversible (opening to left or right), equipped with a handle and keylock (key 405). Note: each wall-mounted enclosure and basic floor standing enclosure or extension can be equipped with only one partial door. The front must be completed with another door.

99

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Door accessories

Door handles and padlocking


EURO handle
DD383881

ASSA/ABLOY handle
DD383882

Standard handle
DD383883

Padlocking
DD383885

Catalogue numbers Characteristics

08932 Supplied without barrel

08933 Supplied without barrel

08931 Supplied with barrel lock (key no. 405) RAL 7016

08938 The kit can be installed on the door handles equipped with any of the barrel locks and inserts above

Barrel locks, inserts


Barrel locks
DD383884 DD381203

The barrel locks and inserts below can be mounted on handle 08931 and on all the door handles of the Prisma Plus G IP30.

Catalogue numbers Characteristics

08940 1 key no. 405

08941 2 keys no. 455

08942 2 keys no. 1242E

08943 2 keys no. 3113A

08944 2 keys no. 2433A

08956 2 keys no.2432E

Inserts
DD383884 DD383884 DD383884 DD383884

Catalogue numbers Characteristics

08945 08946 DIN double bar insert Screwdriver slot insert

08947 08948 08949 Male triangle insert 6.5 mm 7 mm 8 mm

08950 9 mm

08951 08952 08953 Male square insert 6 mm 7 mm 8 mm

Earthing braid
Earthing braid, 6 mm
DD384005

The earthing braid is used to earth a door or partial door with devices.
2

Earthing wire, 6 mm2


DD384005

Catalogue numbers Characteristics

08910 Equipped with a 4 mm diameter lug at one end and a 6 mm diameter lug on the other
DD381338

08911 Equipped with a 5 mm diameter lug at one end and a 6 mm diameter lug on the other
DD384052

Finishing parts > see page 63

100

DD383884

08955 Female square insert 6 mm

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Spare-parts

Accessories (IP30)
Duct accessories
DD384483

01036

4 kit pillars + pillar heads 1 earthing braid plug 4 washers 2 combination uprights 2 short combination crossbars 2 base blanking plugs 2 association fasteners 4 spacers 2 screws with flange 1 self threading screw 2 A-angle parts 2 B-angle parts 7 nuts HX grooved Wall-mounted and floor standing enclosure accessories 01018

DD384484

4 kit pillars + pillar head 2 A-angle parts 2 B-angle parts 8 self threading screws 1 earthing braid plug 4 base blanking plugs 4 spacers 4 nuts HX grooved
DD384485

4 spacers

01098

Door accessories (IP30)


Accessory for closing, wall-mounted and floor standing enclosure
DD384486

01032

1 earthing braid plug 2 door stops 3 self threading screws M5 x 10 1 handle staple 1 handle 1 square rod 3 fixed hinges 3 hinge pins 3 stop bolt 4 self threading screws M5 x 17 Retrofit handle 01220

DD384487

1 handle 1 key no.405 1 handle staple 1 Pack kit pin 1 assembled rod angle 1 peg and angle assembly for G cubicle 1 pozidriv screw for handle staple 1 self threading screw for Pack enclosure 1 pozidriv screw for wall-mounted and floor standinbg enclosures

101

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Spare-parts

Gland plates (IP30)


DD384488

Plain bottom gland plate

01017

DD384490

Duct bottom plate

01039

Side (IP30)
DD384491

Wall-mounted enclosures Side for 6-module wall-mounted enclosures Side for 9-module wall-mounted enclosures Side for 12-module wall-mounted enclosures Side for 15-module wall-mounted enclosures Side for 18-module wall-mounted enclosures Side for 21-module wall-mounted enclosures Side for 24-module wall-mounted enclosures Floor standing enclosures Side for 27-module floor standing enclosures Side for 30-module floor standing enclosures Side for 33-module floor standing enclosures

01040 01041 01042 01043 01044 01045 01046

01035 01034 01033

Central uprights (IP30)


DD384492

Floor standing enclosures Side for 27-module floor standing enclosures Side for 30-module floor standing enclosures Side for 33-module floor standing enclosures

01030 01029 01028

Plinths (IP30)
DD384493

Floor standing enclosures Left drilled base bracket + Right drilled base bracket 4 self threading screws Accessories for plinth Left base bracket + Right base bracket 4 self threading screws Plinth front, 600 mm Base cover + plinth 2 self threading screws

01050

DD384494

01051

DD384495

01052

Plinth front, 300 mm


DD384496

01053

Base cover + plinth 2 self threading screws

102

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Spare-parts

Front cover support uprights (IP30)


DD384500

2 front cover support uprights - 6 modules 2 front cover support uprights - 9 modules 2 front cover support uprights - 12 modules 2 front cover support uprights - 15 modules 2 front cover support uprights - 18 modules 2 front cover support uprights - 21 modules 2 front cover support uprights - 24 modules 2 front cover support uprights - 27 modules 2 front cover support uprights - 30 modules 2 front cover support uprights - 33 modules

01250 01251 01252 01253 01254 01255 01256 01257 01258 01259 01093

Front-plate accessories
DD384501

20 front-plate locking handles with sticker

DD384502

10 sets of front-plate locking handles

01094

Powerclip busbar accessories (IP30)


DD384503

Accessories Powerclip 160/400 A 2 extremity obturators 2 brackets 2 screws Accessories Powerclip 630 A 2 extremity obturators 2 metallic supports 2 brackets for support 2 hexagonal spacers 8 self threading screws

01210

01211

DD384504

2 IPxxB clipon cover Powerclip

01201

103

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Dimensions

Wall-mounted enclosures
DD384039 Dd381897 DD384044

Floor standing enclosures


DD381914 DD383826 DD384040

No. of vertical modules


Wall-mounted enclosures 6 9 12 15 18 21 24 27 27 30 33

H
330 480 630 780 930 1080 1230 1380 1530 1680 1830

H1
1380 1530 1680

Floor standing enclosures

Ducts
DD384041 DD384045

DD383052

DD383049

DD383050

147

104

Prisma Plus G enclosures

IP30, IP31, IP43 enclosures

Dimensions

Cable entry
DD383841

Trunking spreader
157
DD383841

496

206

Wall-mounted installation
Wall-mounted and floor standing enclosures
DD384318 DD384317

Ducts
545 483
DD384043

255 193

No. of vertical modules


Wall-mounted enclosures 6 9 12 15 18 21 24 27 27 30 33

H1
246 396 546 696 846 996 1146 1296 1488 1638 1788

H2
430 580 730 880 1030 1180 1330 1480 1580 1730 1880

Floor standing enclosures

Floor standing plinth fixation


DD383062

Depth behind front plate


Dd383055 Dd383056 Dd383057 Dd383061 Dd383061

Functional uprights

Modular rail

Slotted mounting plate

Fixed rail Cat. no. 03001 or 03010

Adjustable rail Cat. no. 03002 or 03011

Recessed mounting plate Cat. no. 03171, 03172, 03173, 03176, 03177 or 03178

Dd383058

Dd383059

Recessed rail Cat. no. 03003

Rear rail Cat. no. 03004

Flat plate Cat. no. 03170 or 03175

105

Prisma Plus G enclosures

IP55 enclosures

Prisma Plus G enclosures

IP55 enclosures

Presentation

Great capability for meeting the requirements of your installation

> Safety of people and property > Continuity of service > Robustness > Ergonomics and complete accessibility > Optimization and upgradeability

100% reliable and in compliance with existing standards  All the components (switchgear, splitter blocks, prefabricated connections, etc.) have been designed to work together. All switchboard configurations have been tested. Even the most demanding.  ptimized, upgradeable installation O Prisma Plus G IP55 is the only switchboard in this category designed as a "kit". All configurations and combinations are possible, with full access. Thanks to the organization around functional units, the installation evolves simply while preserving its original performance. Ease of setup  The complete accessibility of all mounting and connection points facilitates assembly and cabling in the workshop. The functional units are clearly identified: operations are intuitive and reliable, and connection and checking are performed naturally.

107

Prisma Plus G enclosures

IP55 enclosures

Presentation

Weatherproof enclosures

Metallic indoor enclosures to compose Severe environments: industrial and agricultural buildings, basements, kitchens, etc.

Enclosure delivered flat: total accessibility Designed for electrical continuity

bb630 A bbIP55 bbIK10

Practical

bb Functionalized installation of push buttons, power sockets, etc. bb Installation of power sockets on the side

PE60330

Ergonomics and safety


bb Easy panel handling thanks to the ergonomic gripper bb Legible "Open/closed" positions of front plate, bb Integrated front plate sealing function

Continuity of service

bb Direct accessibility of functional unit if front plates are equiped with hinges

Wide range of combination possibilities

bb Vertical, horizontal with duct, etc.

Numerous installation possibilities

bb Direct installation on: self-supporting structure, pole-mounted, wall mounted

Weaterproofing

bb Broad choice of IP55 gland plates

PE60331

Main characteristics

Steel sheet metal with electrophoresis treatment + hot-polymerised polyester epoxy powder. Enclosure: bb width: 575 mm, with duct: 325 mm bb height: 450 to 1750 mm, bb depth: 260 mm with door. Delivered with earthing braid (with door).

Description
Rated operational current Color Standards conformity Degree of protection Degree of protection against mechanical impacts Isolation Doors

IP55 enclosure

630 A - Icc = 50 kA White colour RAL 9001 EN 62208, IEC 61439-2 IP55 with door IK10 Class 1 bb Plain or transparent, opening to right or left bb By design, electrical continuity of moving parts (hinges) bb Supplied with a handle and keylock (key 405) Distance behind plain door = 78 mm, Distance behind transparent door = 73 mm Earthing braid delivered with enclosure
> see page 111

Easy design with

Rapsody software
> see page 25

Earthing Combination

109

Prisma Plus G enclosures

IP55 enclosures

IP55 enclosures

Enclosures and doors


Type Basic enclosure, width 600 mm
Dd381521 Dd381522 Dd381523

Reversible doors (opening to left or right), equipped with a handle and keylock (key 405).

Extension enclosures, width 600 mm


Dd381524 Dd381525 Dd381526 Dd381522 Dd381523

No. of vertical modules of50mm

Height inmm

Basic enclosure

Frame + plain Frame Rear door + transparent door 08322 08323 08324 08325 08326 08327 08329 08332 08333 08334 08335 08336 08337 08339 08312 08313 08314 08315 08316 08317 08319

7 11 15 19 23 27 33

450 650 850 1050 1250 1450 1750

08302 08303 08304 08305 08306 08307 08309

Top and bottom plates for side-by-side combination 08371 08371 08371 08371 08371 08371 08371

Side panels for vertical combination 08352 08353 08354 08355 08356 08357 08359

Frame + plain door

Frame + transparent door 08332 08333 08334 08335 08336 08337 08339

08322 08323 08324 08325 08326 08327 08329

Type

Ducts, width 300 mm


Dd381527 Dd381528

Wall-mounted enclosures, width 300 mm


Dd381527 Dd381528 Dd383032

No. of vertical modules of50mm 7 11 15 19 23 27 33

Height inmm 450 650 850 1050 1250 1450 1750

Rear + plain door 08342 08343 08344 08345 08346 08347 08349

Top and bottom plates 08372 08372 08372 08372 08372 08372 08372

Rear + plain door 08342 08343 08344 08345 08346 08347 08349

Top and bottom plates 08372 08372 08372 08372 08372 08372 08372

Side panels 08352 08353 08354 08355 08356 08357 08359

2 struts 2 x 01025 2 x 01025 2 x 01025 2 x 01025 2 x 01025 2 x 01025 2 x 01025

Spare parts > see page 117 Dimensions > see page 118

Canopy
Using For enclosure
DB404577

For duct

Catalogue numbers Characteristics

08386 08387 bb Installed on the mounting uprights or directly on the wall, canopies improve switchboard protection against vertically falling water and objects. bb Colour: RAL 7016. bb Supplied with: vv the hardware required for mounting on the uprights vv the components required for combination with another canopy.

Dimensions > see page 118

Partitioning > see page 59

110

Prisma Plus G enclosures

IP55 enclosures

Multiple combinations

Combination kits
Catalogue numbers
Horizontal/vertical combination kit 08381 2 double pillars "L" combination kit 08382 1 triple pillar + 1 single pillar Square combination kit 08383 1 quadruple pillar Single pillar Supplied with basic enclosures Mounting upright 08391 L = 1950 mm

Catalogue numbers Characteristics

Mounting example
Simple In L In square

Dd381434

DB404572

Wall-mounted enclosures

1 Basic enclosure 2 Rear plate for enclosure extension 3 Rear plate for enclosure extension

1 1 basic enclosure 2 1 rear + door for duct 3 1 set of two top and bottom plates for duct 4 1 rear plate for enclosure extension 5 1 set of two side panels

Combination kits

4  1 horizontal/vertical combination kit 08381

6  1 "L" combination kit 08382 7  1 horizontal/vertical combination kit 08381

Mounting uprights

Note: for combinations of more than two enclosures, the switchboard must be reinforced using mounting uprights (08391).

Lifting
Lifting rings
Dd381455

Catalogue number Characteristics

08396 Set of two. Supplied with mounting hardware. The lifting rings are secured directly to the switchboard or to the mounting uprights.

Dd381436

1 1 basic enclosure 2  3 rear plates for enclosure extensions 3  1 set of two top and bottom plates for enclosure extensions 4 1 set of two side panels 5  1 square combination kit 08383 6  2 horizontal/vertical combination kits 2 x 08381 7  3 mounting uprights W = 1950 mm (to reinforce the switchboard) 3 x 08391

111

Prisma Plus G enclosures

IP55 enclosures

Installation accessories

Mounting supports
Catalogue numbers
Mounting uprights Catalogue numbers Characteristics 08391 bb W = 1950 mm bb Colour: RAL 7016 bb Supplied with: vv two adjustable fixing brackets, vv one joint for combination with a plinth or another upright. Leave space behind the switchboard for cable running and to improve ventilation. For one enclosure, order two uprights. For each enclosure extension or duct, order one additional upright. Plinth gusset 08392 bb H=150mm bb Colour: RAL 7016 Plinth cover panel (for enclosure) 08393 bb L = 600 mm bb Colour: RAL 7016 Plinth cover panel (forduct) 08394 bb L = 300 mm bb Colour: RAL 7016

Quantity to order

For the basic enclosure, order two gussets and one 600 mm wide plinth cover panel. For each enclosure extension or duct, order one additional gusset and the corresponding cover panel.

Mounting example
On uprights
DB404573

On plinth
DB404574

On wall structure
DB404575

Free-standing structure
DB404576

Catalogue numbers Designation

Remarks

4 x 08391 + 4 x 08392 + 2 x 08393 3 mounting uprights 4 uprights + 4 gussets + 2 plinth cover panels for enclosure The uprights are used to The plinth, installed in the factory The switchboard can be mounted The free-standing structure is mount on a wall one or or on-site, raises the switchboard on the structure in the factory or on simply two wall structures more enclosures combined to protect it and facilitate spreading site. combined back-to-back. horizontally or vertically. of cables arriving from a trough. Two wall-fixing brackets supplied The switchboard can be The wall-fixing brackets supplied with the basic enclosure ensure positioned anywhere. with the plinth ensure that the that the switchboard cannot topple It can be fixed to the floor and switchboard cannot topple over. over. moved easily using the lifting rings (08396). It can be equipped with one or more enclosures with Schneider sockets.

08391

3 x 08391 + 3 x 08392 + 08393 + 08394 3 gussets 3 uprights + 3 gussets + 1 plinth cover panel for enclosure + 1 plinth cover panel for enclosure + 1 plinth cover panel for duct + 1 plinth cover panel for duct

3 x 08392 + 08393 + 08394

Mounting on a pole
2 reinforcement cross-members to support the enclosure
DD381450

Catalogue number Characteristics

08395 The kit is used to mount an enclosure or an enclosure + duct combination, without drilling, to an I-beam or concrete pole that can be rectangular or cylindrical. The maximum circumference of the pole is 580 mm. Supplied with mounting hardware.

112

Prisma Plus G enclosures

IP55 enclosures

Wall-mounted enclosures IP55 gland plates


Gland plates

Enclosures are supplied with metal gland plates installed on the top or bottom panel of the enclosures (2 plates) or 300 mm wide ducts (1 plate). These plates can be replaced by metal plates with cut-outs for special cable entry systems made of an insulating material (plain, with knockouts or membrane-type). They are designed for entry of cables of different cross-sectional areas via the bottom of a switchboard while maintaining the IP55 degree of protection. The gland plates are easy to install using the mounting kit (supplied with each gland plate) that positions and holds the nuts during installation. This makes it possible to mount the gland plates using a single tool.

Metal plate with cut-outs


DD383827

Catalogue number

08876

FL21 plain gland plates and gland plates with knockouts


DD383828 DD383829 DD383829 DD383829

Other gland plates


DB124229 DB124230

Catalogue numbers M12 M12 or M20 M16 or M25 M20 M20 or M32 M25 or M40 Number of entries

08881 -

08891 4 4 4 12

08892 2 2 4

08895 5 8 13

08898 39 x 7 to 26 mm diameter entries

08899 2 x 33 to 72 mm diameter entries

39

FL21 membrane-type gland plates


DD383830 DD383830 DD383830

Catalogue numbers From 5 to 7 mm cable diameters From 6 to 10 mm cable diameters From 7 to 12 mm cable diameters From 8 to 12 mm cable diameters From 10 to 14 mm cable diameters From 12 to 18 mm cable diameters From 14 to 20 mm cable diameters From 17 to 32 mm cable diameters From 20 to 26 mm cable diameters From 28 to 60 mm cable diameters Number of entries

08872 4 4 12 4 1 25

08896 2 6 8 16 2 1 35

08897 2 2

Spare parts (FL21 gland plate for Pack enclosures) > see page 117 Dimensions > see page 119

113

Prisma Plus G enclosures

IP55 enclosures

Partial doors and functional units for partial door


Partial doors

Type

Plain
DD382674

With cut-outs
DD381438

4 modules (H = 200 mm) for enclosure from 11 to 27 modules 6 modules (H = 300 mm) for enclosure at least 33 modules high Installation Characteristics

08374 08375

08376 08377

bb On a wall-mounted enclosure at least 11 modules high (H = 650 mm). bb The front must be completed with another door (plain or transparent). bb Each enclosure or extension can be equipped with only one partial door. bb Designed for two mounting plates with 22 mm diameter devices or Schneider Electric industrial sockets. bb They are supplied with an insulating plain mounting plate that can be used to: vv blank off a reserve hole, vv install all types of devices (sockets, EPO devices, measurement devices). bb The dimensions of the two holes are 200 mm x 112 mm. bb Hinges that open 170 bb Equipped with a 8 mm male triangle insert (key not supplied).

They can be installed: bb horizontally on the partial doors with cut-outs bb horizontally vertically at any point on a door or side panel.

Functional units for partial doors

Type

Plain
DB404552

For 22 mm diameter devices


Dd381442

For industrial sockets


DB404553

Catalogue numbers Characteristics

08861 bb Can be used to: vv blank off partial doors with cut-outs vv mount any type of device (EPO devices, measurement devices, sockets)

08862 bb For installation of eight 22 mm diameter devices (lights, switches, pushbuttons, etc.) bb Supplied with 4 blanking plug

08863 bb With two 65 x 85 mm holes bb Intended for the installation of: vv 10/16 A residential sockets vv flush-mount 16 A LV sockets, inclined or straight, IP44/IP67

08864 bb Intended for the installation of: vv residential sockets (< 10 /16 A) in the 65 x 85 mm hole (1a) vv flush-mount inclined or straight 16 A LV sockets, IP44/ IP67, IK08, in the 65 x 85 mm hole (1b) vv inclined 16 and 32 A IP44 and IP67 sockets in the 90 x 100 mm hole (1)
DD381444

114

DD381443

Prisma Plus G enclosures

IP55 enclosures

Side panels with cut-outs

Side panels with cut-outs


Side panels with cut-out
DB404578

These panels are designed to replace the standard side panel. They can be mounted on the left or right-hand side.

No. of vertical modules of50mm 7 11 15 19 23 27 33

Height inmm 450 650 850 1050 1250 1450 1750

No. of 103 x 255 mm holes 1 2 2 2 2 2 2

Catalogue numbers 08362 08363 08364 08365 08366 08367 08369

The cut-outs are designed for the installation of Pratika PK industrial sockets up to 63 A either directly or on 103 x 225 mm adaptation plates of the Kaedra enclosure range. Installation is direct (in 103 x 225 mm cut-outs) for: bb 16/32 A interlocked LV sockets, IP44/IP65, IK08 bb 16 A VLV sockets with safety transformers, IP44/IP65, IK08.

Industrial sockets and functional units 103 x 225 mm


DD382840 DD382842 DD382839 DD382841 DD382841

Industrial sockets and functional units Size for industrial sockets Functional units catalogue numbers

bb 16/32 A interlocked LV sockets bb 16 A VLV sockets with safety transformers 103 x 225 mm Direct installation

bb 16 A and 32 A LV bb VLV sockets bb RJ45 sockets 65 x 85 mm + 90 x 100 mm 13142

bb 63 A LV sockets 100 x 107 mm 13144

bb 16 or 32 A VLV sockets (after uncapping of the opening) 65 x 65 mm 13143

bb blanking plate 13143

115

Prisma Plus G enclosures

IP55 enclosures

Door accessories

Locks

bb The small plain and transparent doors (7 to 23 modules) are supplied with a small handle comprising a barrel lock no. 405. bb The large plain and transparent doors (27 to 33 modules) are supplied with a large handle comprising a barrel lock no. 405. bb The partial doors are supplied with an 8 mm male triangle insert. bb All doors can receive as optional equipment: vv a large or small handle with a barrel lock no. 405. The latter can be replaced by other barrel locks or special inserts vv a large EURO handle, supplied without a barrel lock vv door inserts (squares, triangles, double bars, screwdriver slots).

Handles for replacement


Handles
Dd380704 Dd380704

Catalogue numbers 08936 Designation Door latch with lock and 2 no.405 keys

08935 08934 Handle (W = 155mm) EURO handle without with lock and a barrel lock (1) 2 no.405 keys

(1) Do not suit to barrels with an automatic return stroke of the key.

Padlocking
Padlocking
Dd380706

Catalogue number Designation

08939 The kit can be installed on all IP55 doors, except those equipped with an EURO lock. Kit designed for three padlocks.

Handle barrel locks and inserts


Handle barrel locks (1)
Dd380706 Dd380706 Dd380706 Dd380706

These components may equip handles after removing the standard barrel lock no.405.
Dd380706 Dd380706

Supplied with Catalogue numbers

2 keys 2 keys 2 keys 2 keys Screwdriver Double Male triangle insert Male square insert no.2433A no.455 no.1242E no.3113A slot insert bar insert 7 mm 8 mm 9 mm 6 mm 7 mm 8 mm 3mm (CNOMO) 09933 09945 09942 09943 09931 09932 09937 09934 09939 09949 09947 09948

(1) Others A and E combinations are available from Ronis, please contact us.

Door insert

Type

Dd380705

Dd380705

Dd380705

Dd380705

Screwdriver slot insert 09981

Catalogue numbers

3 mm double Male triangle insert bar insert 7 mm 8 mm (CNOMO) 09982 09983 09984

9 mm 09985

Male square insert 6 mm 7 mm 09986 09987

8 mm 09988

Finishing parts > see page 63

116

Dd380705

Partial door inserts

These inserts simply replace the standard male triangle insert (8 mm).

Female square insert 6mm 09946

6 mm female square insert 09989

Prisma Plus G enclosures

IP55 enclosures

Spare-parts

Accessories (IP55)
Dd384507

2 pillars

01025

Set of spare parts for wall-mounted enclosure


Dd384508

01247

24 screws M6 x 12 + stubs contact 4 simple fixing brackets 4 screws pillar/seating 12 nylon washers 12 self threading screws 4 conical washers 4 screws M8 x 16 Set of spare parts for door 01248

Dd384508

1 screw M6 x 12 + stub washers 2 keys no.405 1 spring nut 4 screws frame/pillar 3 hinge pins 8 o-ring joints 3 stop rings Spare parts for closing system 01249

Dd384510

1 stop washer 1 screw body 1 screw cap 1 o-ring 1 screw nut 1 composite seal 1 captive screw 1 special washer 1 cam 1 washer

Front-plate accessories
DD384501

20 front-plate locking handles with sticker

01093

DD384502

10 sets of front-plate locking handles

01094

117

Prisma Plus G enclosures

IP55 enclosures

Dimensions

Wall-mounted enclosures
Dd381726 Dd381729

Ducts
No. of vertical modules H1
425 625 825 1025 1225 1425 1725

Doors
A
375 575 775 975 1175 1375 1675

B
525 725 925 1125 1325 1525 1825

7 11 15 19 23 27 33
Dd381727 Dd381730

Dd381728

Dd381735

Dd381734

Surface utile
Dd381731

(1) Multifix rail. (2) Recessed slotted mounting plate. (3) Transparent door. (4) Plain door. (5) Front plate. (6) Door.

7 11 15 19 23 27 33

No. of vertical modules

C
420 620 820 1020 1220 1420 1720

E
284 484 684 884 1084 1284 1584

H
450 650 850 1050 1250 1450 1750

Dd381732

Enclosure combinations
Dd381738 Dd381742

Canopy

118

Dd381742

Dd381737

Prisma Plus G enclosures

IP55 enclosures

Dimensions

Gland plates
Dd381733

Side panels with cut-outs


Dd381744 Dd381745

Partial door with cut-outs


Dd381743

7 modules

(1) Cat. no. 08376 for wall-mounted enclosures from 11 to 27 modules (2) Cat. no. 08377 for wall-mounted enclosures at least 33 modules

From 11 to 33 modules

Functional mounting plates


Dd381748 Dd381746 Dd381749 Dd381750

Cat. no 08863

Cat. no 08864

Cat. no 08862

Cat. no 08861

Wall structure
Dd381741 Dd381740 Dd381739

119

Pack enclosures

Pack enclosures

Contents

Presentation................................................................................123 Pack wall-mounted and flush-mounted enclosures......................124 Kilowatt hour meters....................................................................125 Accessories.................................................................................126 Distribution Insulated busbars........................................................................128
Power supply of rows from the incoming device Power supply of rows from the incoming device Power supply of a modular devices row

Distribution blocks.......................................................................130 Comb busbars, distribution blocks...............................................131 Accessories.................................................................................132 Spare-parts..................................................................................133 Dimensions..................................................................................134

121

Pack enclosures

Pack enclosures

Presentation

Metallic indoor enclosures, supplied mounted, can be ordered with a single catalogue number. An enclosure + modular rails + front plates + blanking plates + a plastic gland plate + an earth bar + a template for drilling wall-mounted holes.

1 product reference = a complete modular enclosure ready to be equipped

bb160 A bbIP30 bbIK07/08

PD391279

Gland plate

bb Removable, easy-toinstall and easy-to-cut

Accessibility

bb Side panels dismountable for full access

Double rail Installation


bb Door easy to install without any tool bb Plain or transparent reversible door

bb Double rail supplied premounted in the 4-, 5- and 6-row enclosures allowing mixing of devices of different depths

PD390161

Main characteristics

Steel sheet metal with electrophoresis treatment + hot-polymerised polyester epoxy powder. Enclosure: bb width: 555 mm, bb height: 480 to 1080 mm, bb depth: 157 mm without door / 186 mm with door.

Description
Pack enclosures
Rated operational current Colour Standards conformity Degree of protection Degree of protection against mechanical impacts Isolation Doors 160 A - Icc = 50 kA White colour RAL 9001 EN 62208, IEC 61439-2, NFC 61-910 IP30 with or without door IK08 with door IK07 without door Class 1 bb Plain or transparent, opening to right or left bb By design, electrical continuity of moving parts (hinges) bb Supplied with a handle and keylock (key 405) bb No possibility to install push buttons (distance behind door = 42 mm) The Pack enclosures can be built-in easily using its flush mounting kit

Mounting

The design of Pack enclosures ensures easy device access and mounting. Optimised depth and an extra-thin door ensure perfect integration in all environments. Models with 4, 5 and 6 rows are particularly well-suited for the incomer function: bb more space available for wiring of the incoming device bb optimised number of front plates. 123

Pack enclosures

Pack wall-mounted and flush-mounted enclosures


Wall-mounted enclosures for modular devices
Enclosures include: bb 1 modular rail per row (L= 24 modules of 18mm). The recessed rail at the top of 4, 5, 6-row enclosures is for NG160 installation and supplied with another rail + 4 raisers for modular devices. bb earth bar, bb 1 front plate with cut-out per row (height depending on model), bb 1 plastic gland plate, bb divisible blanking plates (number depending on model). Doors are: bb reversible, opening to left or right, bb supplied with a handle and barrel with keylock (key 405), bb barrel locks and inserts > see page 100

DD383298

DD383985

Nb. of Nb. of vertical Dimensions in mm rows modules

Height of front plates (mm)

Nb. of divisible Enclosure Door blanking plates


DD383299 DD381801 DD381802

2 3 4 5 6

9 12 15 18 21

Height Width Depth 480 555 157 without door 630 175 with 780 door + 11 930 for handle 1080

Top Intermediate Bottom 225 150 225 3 250 200 6

08002 08003 08004 08005 08006

Plain 08082 08083 08084 08085 08086

Transparent 08092 08093 08094 08095 08096

Flush-mounting kit > see page 127

DD383982

Enclosure extension

Meters can be installed at different levels on the functional uprights of enclosures. Class 1: Depending on preferences and needs, meters can be installed directly on mounting plates equipped with earthing braids and combined with partitioning or front plates. The mounting plates can be raised using M5 spacers. Doors are: bb reversible, opening to left or right, bb supplied with a handle and barrel with keylock (key 405), bb barrel locks and inserts > see page 100

Nb. of vertical modules (50 mm)

Dimensions (mm)

Enclosure
DD382404

Door
DD382405 DD382406

9 12

Height 480 630

Width 555

Depth 157 without door 175 with door + 11 for handle

08012 08013

Plain 08082 08083

Transparent 08092 08093

124

Pack enclosures

Kilowatt-hour meters

Class 1: Depending on preferences and needs, meters can be installed directly on mounting plates (without insulating plate) equipped with earthing braids of 6mm2 (08910) and combined with partitioning or front plates. The mounting plates can be raised using M5 spacers > see page 58

Kilowatt-hour meters, Class 2

Installation

In Pack wall-mounted enclosures


DD382947 DD382945

In an enclosure extension
DD383982 DD383981

Device Nb. of devices per row Nb. of vertical modules Mounting plate Insulating plate Horizontal partitioning (1) Front plate transparent plain Enclosure Door Earthing wire 6 mm2 Combination uprights (set of 2)

Single-phase meters 3 6 03157 03154 04333 03343 or 03806 Pack enclosure Depending on enclosure 08911 -

3-phase meters 2 9 03152 03154 04333 03344 or 03807 Pack enclosure Depending on enclosure 08911 -

Single-phase meters 3 6 03157 03154 03343 or 03806 08012 08092 (transparent) or 08082 (plain) 08911 08817 (2)

3-phase meters 2 9 03152 03154 03344 or 03807 08013 08093 (transparent) or 08083 (plain) 08911 08817 (2)

(1) If not installed at the top of a Pack enclosure, order an addition horizontal partition (04333). (2) To make the combination more rigid, particularly during transport, it is mandatory to use a set of combination uprights secured to the rear of the switchboard.

125

Pack enclosures

Accessories

Gland plates
Gland plates
DD383989 DD383990

Catalogue numbers Characteristics

Top or bottom plate with plastic gland plate 08878 -

Metal gland plate 08879 Plain metal gland plate

Trunking spreader
Trunking spreader
DD383991

Catalogue number

08821

Canopy
Canopy for IP31
DD383933

Catalogue number Characteristics

08823 The canopy cannot be mounted on the existing top plate. It therefore comes with a special top plate that must be mounted in place of the existing top plate. The existing top plate is remounted at the bottom of the enclosure to allow cable entry and exit via the bottom. The addition of a canopy over a wall-mounted or floor-standing enclosure equipped with a door ensures compliance with the degree of protection IP31.

Gasket
Gasket for IP43
DD381268

Catalogue number Characteristics

08841 When the switchboard is equipped with a canopy, a gasket for the doors ensures compliance with the degree of protection IP43. L = 5.3 m

126

Pack enclosures

Accessories

Combination uprights
Combination uprights
DD383984

Catalogue number Characteristics

08817 Set of 2 uprights. Particularly during transport, it is mandatory to use a set of combination uprights secured to the rear of the switchboard, to make the combination more rigid.

Wall mounting
Wall mounting
DD384071

Catalogue number Characteristics

08803 4 external wall-mounted brackets 08803

Flush-mounting kit
Flush-mount kit
DD381256

Catalogue number

08822

Blanking plates
Blanking plates
DD384029

Catalogue numbers Characteristics

03220 bb Blanking strip bb H = 46 mm, L = 1 m

03221 bb Divisible bb Set of 4 bb H = 46 mm, L = 90 mm

Finishing parts > see page 63

127

Pack enclosures

Distribution

Insulated busbars

power supply of rows from the incoming device


PD390546_SE

PD390545_SE

Powerclip busbars 125 to 160 A

Powerclip tap-off blocks with 6 mm + 10 mm terminals

Clip-on covers to block off the connected cable lugs.

bb Compact busbars, fully insulated(IPxxB), ready for installation (supplied with supports and clip-on covers) bb Copper bars: vv channelled ETPH12, vv threaded M6 holes every 25 mm, vv can be cut every 150 mm (125 A) or 200 mm (160 A). bb Mounted on insulated bases. bb Delivered with supports that screw to the functional upwrights of enclosures. bb Large choice of prefabricated and tested connections. bb Clip-on covers protect against direct contact. Can be easily cut for the connections to the devices. bb Ends are protected by shutters.

125 A
DD382673

160 A
DD381380

Powerclip busbars

3P

4P

Spare parts*

2 busbars supports + 2 end plugs + 2 screws 2 IPxxB clip-on cobers, L. 200 mm

L = 450 mm L = 750 mm L = 1000 mm L = 450 mm L = 750 mm L = 1000 mm

04103 04107 04104 04108 -

04111 04121 01210 01201

* For more information, > see page 103

Electrical characteristics
Rating
125 A 160 A

8,5 10

Rated short-time withstand current Icw (kA rms / 1 s)

Rated peak withstand current Ipk (k)


20 30

Rated insulation voltage Ui (V)


500 750

Impulse withstand voltage Uimp (kV)


8 8

Choice of connection / device


Device to connect
INS NG NSA 160 C120, iC120 Multiclip Modular devices INS40/125 3P 4P INS160 NG125 NG160 Vigi NG160 04145 +28947 04145 +28948 04147 or 04148 04145 or 04147 or 04148 or 04146 04147 or 04148 or 04146 04148 04147 or 04148 or 04146 04147 or 04148 04151 or04152 04021 04151 or04152

Catalogue numbers (see details on next page)

160 A 200 A

128

Pack enclosures

Distribution

Insulated busbars

power supply of rows from the incoming device


Busbar connections
Description
Set of four 125 A connections, W = 230 mm 35 mm ferrule + 45 ring lug (IPxxB covers 04150) Set of four 160 A connections, W = 250 mm 45 mm ferrule + 45 ring lug (IPxxB covers 04150) One piece connection, 3/4P, 160 A, W = 150 mm Fast connection to busbars Equipped with male fittings one end for tunnel terminals Respects the degree of protection IPxxB Neutral is clearly indicated (blue)
DD383274

For the connection of


NG125, NSA equipped with tunnel terminals or combbusbar INS with tunnel terminals: cat.no. 28947 or 28948 NSA160, INS160, NG160, NG125 NSA160, INS160, NG160 (located on left-hand side), NG125, C120, iC120

Catalogue numbers
04145

DD381379

04146 04147

DD383294

One piece connection, 3/4P, 160 A, W = 150 mm Fast connection to busbars Equipped with male fittings one end for tunnel terminals Respects the degree of protection IPxxB Neutral is clearly indicated (blue)
DD383276

NSA160, INS160, 04148 NG160 (located on left-hand side), Vigi NG160 (located in the middle), NG125, C120, iC120

DD383295

12 tap-off blocks with 6 mm and 10 mm terminals Respects the degree of protection IPxxB 12 tap-off blocks with 16 mm terminals Respects the degree of protection IPxxB

All device equipped with tunnel terminals Multiclip 160 A All device equipped with tunnel terminals Multiclip 160 A

DD383498

04151 04152

Accessories
Description
8 IPxxB covers Set of 8 clip-on covers that can be cut as needed Maintain IPxxB with 90 angle lugs and/or cable sizes from 10 to 25 mm Set of 20 CHC M6 x 12 mm
DD381385

Catalogue numbers
04150

8.8 class mounting hardware

04158

129

Pack enclosures

Distribution

Distribution blocks

power supply of rows from the incoming device


Polybloc 160 A
Polybloc distribution block 160 A Set of four 160 A connections, W380mm

DD381200

DD382981

Catalogue numbers Characteristics

04031 Installation on a raised modular rail Other characteristics > see page 75

04149 Two 45 mm end fittings for tunnel terminals For the connection of: INS40/160, NG125, NG160, C120, iC120 with or without Vigi

Distribloc 63, 125 and 160 A


Types Distribloc 63 A (top connection)
PB104500

Distribloc 63 A Distribloc 125 A (bottom connection) (top connection / bottom connection)


PB104499 PG123021 054947

Distribloc 160 A (top connection / bottom connection)


PD390657

DD383301

Catalogue numbers Characteristics

Distribution block 4P Connections

04040

04041

04045 04047 bb Installation on a modular rail bb Width: 6 modules of 18 mm bb Connections L = 210 mm for NG125, INS40/125, C120, iC120

04046 Supplied bb Installation on a modular rail bb Width: 6 modules of 18 mm bb Connection for NG160, INS100/160 with or without Vigi

Supplied Supplied bb Installation on a raised modular rail bb Width: 4 modules de 18 mm Other characteristics > see page 77

Multi-stage distribution blocks 40, 100 and 125 A


Types
DD382813

Distribution blocks 2P Distribution blocks 4P


058923 058930d

Rating Catalogue numbers Characteristics

Distribution block Additional neutral bar

100 A 125 A 40 A 13506 13507 13508 13516 2 x 7 holes 2 x 13 holes 4 x 13 holes Other characteristics > see page 78

100 A 13510 13515 4 x 7 holes

125 A 13512 13517 4 x 13 holes

125 A 13514 13518 4 x 17 holes

130

Pack enclosures

Distribution

Comb busbars, distribution blocks


Comb busbars for DPN

power supply of a modular devices row

Comb busbars
DD382981

Lateral bracket

Tooth-caps

Insulated connectors

Catalogue numbers Characteristics

Two-pole Four-pole

Supplied accessories

21086 21090 24 modules of 9 mm 12 modules of 18 mm Rating: 80 A Set of 1 4 lateral bracket 1 tooth-caps

21088 21092 48 modules of 9 mm 24 modules of 18 mm

21089 21093 96 modules of 9 mm 48 modules of 18 mm 0

21094 21095 Set of 40

21096 21096 Set of 12 6 modules of 9 mm 3 modules of 18 mm -

21098 21098 Set of 4 For 25 mm2 cables -

2 tooth-caps

Comb busbars for C60 and iC60


Comb busbars
DB123466

Lateral bracket

Tooth-caps

Insulated connectors

Catalogue numbers

Characteristics

One-pole Two-pole Three-pole Four-pole

Supplied accessories

14881 14882 14883 14884 b Set of 1 b 24 modules of 9 mm b 12 modules of 18 mm Rating: 80 A with 1 feeding point 100 A with 2 feeding points 2 lateral bracket

14891 14892 14893 14894 b Set of 2 b 48 modules of 9 mm b 24 modules of 18 mm

14886 14886 14887 14887 Set of 40

14888 14888 14888 14888 Set of 40

14885 14885 14885 14885 Set of 4 For 25 mm2 cables

Multiclip distribution blocks


Distribution blocks Multiclip
DB404608 DD383403 DB123466

Rating Catalogue numbers Characteristics

Supplied accessories

63 A 04008 b 4P b 24 x 9 mm modules, 12 x 18 mm modules b Upstream connection: tunnel terminals for cables up to 25 mm b Downstream connection spring terminals: v 4 for each phase (2 x 4 mm2 + 2 x 6 mm2) v 8 for the neutral (4 x 4 mm2 + 4 x 6 mm2) Clipped onto the rear of modular rail or screwed. Bared copper connections (L=100 mm) 10 of 4 mm2 + 6 of 6 mm2

80 A 04000 b 4P b 48 x 9 mm modules, 24 x 18 mm modules b Upstream connection: tunnel terminals for cables up to 25 mm b Downstream connection spring terminals: v 6 for each phase (6 mm2) v 18 for the neutral (6 mm2)

Bared copper connections 6 mm2 (12 blue + 12 black)

131

Pack enclosures

Accessories

Cable running
DD381819

Cable-tie supports
Cable-tie supports
DD381820

12 horizontal cable straps 4 covers for horizontal cable straps, W = 430 mm 4 horizontal sections, 60 x 30 mm, W = 450 mm + supports 12 horizontal trunking supports 2 fixing brackets, H = 15 mm (for vertical trunking)

Cable straps

04239 04243

Cat. no.
Catalogue number Characteristics 08867 Set of 2 Supplied with hardware for mounting on the functional uprights of the enclosure

Trunking

04257 04255 04206

Cat. no.

Earth and neutral bars


Blocks with spring terminals
DD381860 DD381560 DD381560

Bare earth bar Catalogue numbers Characteristics 04201 bb Size: 12 x 3 mm bb Connection space: 330 mm Equipped with a 35 mm tunnel terminal bb Can receive earth blocks with spring terminals

Earth blocks with spring terminals to clip 04214 04215 bb 12 x 4 mm2 bb Set of 4 bb Length: 75 mm bb 3 x 16 mm2 bb Set of 4 bb Length: 37 mm

Earth bar with clamps


DD381516

Catalogue number Characteristics

04200 40 clamps and 1 x 35 mm terminal Length: 450 mm

Catalogue number Characteristics Fixing mode Earth bar used

Accessories installed on the side

04206 H = 15 mm Set of 2 brackets Vertically on two fixing brackets secured to a functional upright. Earth bar with clamps or spring terminals

Earthing braid
Earthing braid, 6 mm
DD384005

The earthing braid is used to earth a door or wicket door with devices.
2

Earthing wire, 6 mm2


DD384005

Catalogue numbers Characteristics

08910 The braid is equipped with a 4 mm diameter lug at one end and a 6 mm diameter lug on the other
DD381338

08911 Equipped with a 5 mm diameter lug at one end and a 6 mm diameter lug on the other
DD384052

132

Pack enclosures

Spare-parts

Front-plate (IP30)
DD384498

4 modules Pack decentered plate 1 front-plate 2 front-plate locking mechanisms

01264

DD384499

4.5 modules Pack decentered plate 1 front-plate 2 front-plate locking mechanisms

01265

Modular rail
DD384506

Pack modular device rail 1 DIN rail 432 mm lenght 2 fixing brackets 2 self threading screws M5 x 10

01260

Gland plate (IP30)


DD384489

FL21 cut-out gland plate for Pack enclosure

01020

Front-plate accessories
DD384501

20 front-plate locking handles with sticker

01093

DD384502

10 sets of front-plate locking handles

01094

133

Pack enclosures

Dimensions

Wall-mounted enclosures of 2 and 3 rows


DD383987 DD381951

2 3

Nb. of rows

480 630

Wall-mounted enclosures of 4, 5 and 6 rows


DD383303 DB124231

4 5 6

Nb. of rows

780 930 1080

Door
DD383988 DD381953 DD381956

134

Pack enclosures

Dimensions

Gland plates
DD381954

Trunking spreader
DD382916

Wall-mounted
DD381955 DD380509

2 3 4 5 6

Nb. of rows

H1

396 546 696 846 996

H2

546 696 846 996 1146

Useful depth behind front plate


DD381957 DD383305 DD383307 DD383306 DD383308

Supplied modular rail

Upper rail in wall-mounted enclosures of 4, 5 and 6 rows

Rail ref. 03004

Rail ref. 03003

135

Additional information

Additional information

Contents

Electrical characteristics.........................................138
Designing Prisma Plus power circuits..........................................138
Presentation and approach................................................................................ 138

Designing connections y 630 A....................................................139


Device connections............................................................................................ 139 Compact circuit breakers NSX100 to NSX630................................................... 140 Incoming connection block and power supply block on Powerclip busbars......................................................................................... 141

Designing connections with cables..............................................142


Tubular lugs....................................................................................................... 143

Designing the PEN conductor......................................................144


Power circuit...................................................................................................... 144

Practical information................................................145
Connection of power cables.........................................................145

Standards................................................................... 146 Enclosure characteristics....................................... 151


Selection of enclosures according to the premises......................151 Properties of metal enclosures....................................................158

Thermal characteristics..........................................159
Thermal management of switchboards........................................159
General.............................................................................................................. 159 Comparative method......................................................................................... 161 Example............................................................................................................. 163 Charts................................................................................................................ 164 Ventilation.......................................................................................................... 165 Heating.............................................................................................................. 166

Practical information................................................167
Tools required for mounting and connection................................167

137

Additional information

Electrical characteristics

Designing Prisma Plus power circuits


Presentation and approach
In the following pages you will find a number of examples, validated for Prisma Plus switchboards, intended to assist in determining the busbars as well as the upstream and downstream connections for the installation. The examples assume that the devices have already been selected. A complete process involves a number of steps before making final choices (transformer, conductors, protection, etc.). Schneider Electric offers a number of tools to assist in designing a complete installation (technical guides, software).

The Prisma Plus system takes into account the installation and connection conditions of Schneider Electric devices. The entire installation complies with standard IEC61439-1 and 2. The result is a type tested switchboard.
PD390311

Busbar sizing

The factors that must be taken into account in determining the size of busbars include: bb the diversity factor. Not all the loads supplied by a set of busbars are used at full rated load or at the same time. The diversity factor is the means to determine the maximum load current used to size the busbars. Standard IEC 61439-1 and 2 4.7 specifies the table below: Number of circuits
2 and 3 4 and 5 6 and 9 10 and more

Rated diversity factor (RDF)


0.9 0.8 0.7 0.6

bb the degree of protection IP. bb the ambient temperature around the switchboard.

Flexible copper bars with an insulating cover. To determine the required sizes for flexible bars, see the tables starting on > see page139 which indicate the correct size for each type of connected device. bb an insulated flexible bar (not connected) must meet standards IEC 60243-1, (dielectric, > see page139), NFC 32201 (insulation) and IEC 60332-1 (fire) bb a flexible bar connected to a device in an enclosure must comply with standard IEC61439-1 and 2. Cables To determine the cables required, see the tables. on > see page142. They can be used to determine: bb the size of cables as a function of: vv the circuit breaker rating vv the current vv the ambient temperature around the switchboard bb the permissible current for individually tied cables or touching cables as a function of: vv the size of the cables vv the degree of protection for the switchboard.

Supply of devices for outgoers y 630 A

Easy design with

Rapsody software
> see page 25

138

Additional information

Electrical characteristics

Designing connections y 630 A


Device connections
Flexible copper bars with an insulating sheath
Switchboards that comply with standard IEC 61439-1 and 2
It is imperative to use the values indicated below that have been validated for the installation of devices in Prisma Plus switchboards. The parameters determining the size of flexible bars are: bb the environment in which the devices are installed: vv position in the enclosure vv dimensions of other conductors in the circuit vv ambient temperature around the switchboard bb the characteristics of the connected devices: vv device heat losses vv the type of installation (horizontal or vertical) vv the type of device (fixed or withdrawable). Only the equipment manufacturer with in-depth knowledge on: bb the characteristics of the installed devices bb the configuration of the installation in the enclosure can provide the correct sizes of flexible bars for a given permissible current. Insulated, flexible bars make for easy, fast and flexible implementation up to 630 A, but higher ratings require sizes that cancel these advantages. For high Isc values, it is advised to use rigid bars which require fewer supports.

Insulated flexible bars are better than cables, they offer:

bb better insulation temperature withstand (125 C for bars, 105 C for cables) and a larger exchange surface for an equivalent size, i.e. a smaller size for a given current bb greater rigidity offering better electrodynamic characteristics for short-circuit currents bb no intermediate parts (lugs) for a direct connection between the device and the busbars therefore less temperature rise and less risk of error bb fast implementation of prefabricated connections already cut to length, formed and drilled.

Technical characteristics bb thickness of the insulation: variable depending on the bar size, 2 mm on average bb rated insulation level Ui = 1000 V bb impulse withstand voltage Uimp = 12 kV bb maximum withstand temperature of insulating material = 125 C.

Connection

In all enclosures with IP y 55 bb the switchboard internal temperature is 60 C bb the withstand temperature of the insulating material is 125 C. If the withstand temperature of the insulation is only 105 C, use the next largest flexible bar. The bar sizes (S) indicated below take into account the derating curves of devices.

Connection of devices and distribution blocks to busbars


Device S (mm) Device S (mm) INS125 INS160 INS250 20 x 2 20 x 2 20 x 3 NSX250 (1) NSX400 (1) NSX630 20 x 3 32 x 5 32 x 8 INS320 INS400 32 x 5 INF250 ISFT250 24 x 5 INS500 INS630 32 x 6 INF400 ISFT400 32 x 5 NSX100 (1) NSX160 (1) 20 x 2 INF630 ISFT630 32 x 8 20 x 3

(1) The values for circuit breakers apply to contactors with the same ratings.

To connect a Compact NSX250 to Powerclip busbars, use a 24 x 5 mm flexible bar (04746).


Device S (mm) Multiclip distribution Polypact distribution Polypact distribution block (200 A) block (3P) block (4P) 20 x 3 32 x 6 32 x 5

Disconnectors, terminal blocks, connections, busbars to busbars


I max. (60 C) S (mm) 200 A 20 x 2 250 A 20 x 3 400 A 24 x 5 400 A 24 x 5 480 A 24 x 6 520 A 32 x 5 580 A 32 x 6 660 A 32 x 8

Note: the values indicated above have been validated for Prisma Plus switchboards.

139

Additional information

Electrical characteristics

Designing connections y 630 A


Compact NSX100 to NSX250
Insulated flexible copper bars

Compact circuit breakers NSX100 to 630

Devices IP y 55
NSX100 TMD-TMG NSX125 TMD-TMG NSX160 (1) TMD-TMG NSX250 (1) TMD-TMG NSX100 STR NSX160 STR NSX250 (2) STR Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A)

Rated current of a circuit Inc (A) Ambient temperature around the switchboard
25 C 30 C 35 C

40 C 20 x 2 92.5 20 x 2 116 20 x 3 147 20 x 3 231 20 x 2 100 20 x 3 160 20 x 3 237.5

45 C 20 x 2 90 20 x 2 113 20 x 3 144 20 x 3 225 20 x 2 100 20 x 3 160 20 x 3 225

50 C 20 x 2 85 20 x 2 100 20 x 3 140 20 x 3 198 20 x 2 100 20 x 3 160 20 x 3 225

20 x 2 100 20 x 2 125 20 x 3 160 20 x 3 250 20 x 2 100 20 x 3 160 20 x 3 250

20 x 2 97.5 20 x 2 122 20 x 3 156 20 x 3 244 20 x 2 100 20 x 3 160 20 x 3 250

20 x 2 95 20 x 2 119 20 x 3 152 20 x 3 238 20 x 2 100 20 x 3 160 20 x 3 237.5

(1) For a withdrawable NSX160 or NSX250 equipped with a Vigi or an insulation-monitoring module, multiply the In values by 0.9. (2) For a withdrawable NS250 equipped with a Vigi or an insulation-monitoring module, multiply the In values by 0.86.

Compact NSX400 to NSX630


Insulated flexible copper bars
Devices IP y 55
NSX400B/F/N/H/S/L fixed NSX400B/F/N/H/S/L with Vigi NSX400B/F/N/H/S/L withdrawable NSX630B/F/N/H/S/L fixed NSX630B/F/N/H/S/L with Vigi or withdrawable Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) 32 x 5 400 32 x 5 400 32 x 5 400 32 x 6 630 32 x 8 570 32 x 5 400 32 x 5 390 32 x 5 390 32 x 6 615 32 x 8 550 32 x 5 400 32 x 5 380 32 x 5 380 32 x 6 600 32 x 8 535 32 x 5 390 32 x 5 370 32 x 5 370 32 x 6 585 32 x 8 520 32 x 5 380 32 x 5 360 32 x 5 360 32 x 6 570 32 x 8 505 32 x 5 370 32 x 5 350 32 x 5 350 32 x 6 550 32 x 8 490 Ambient temperature around the switchboard 25 C 30 C 35 C

Rated current of a circuit Inc (A)

40 C

45 C

50 C

Note: the values indicated above have been validated for Prisma Plus switchboards.

140

Additional information

Electrical characteristics

Designing connections y 630 A


Compact NSX100 to NSX630
Horizontal mounting

Incoming connection block and power supply block on Powerclip busbars

Determining the permissible current of NSX100 to NSX630 connection and power supply blocks as a function of the ambient temperature around the switchboard and their IP degree of protection. Device Rated current of a circuit Inc (A)

Ambient temperature around the switchboard 25 C 30 C 35 C 40 C 45 C 50 C IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 95 100 92 100 90 97 87 95 85 92 bb

NSX100 TMD-TMG NSX100STR

Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block

via the top via the bottom via the top via the bottom via the top via the bottom via the top via the bottom via the top via the bottom via the top via the bottom

04066 100 04067 04060 04066 100 04067 04060 04066 160 04067 04060 04066 160 04067 04060 04066 238 04067 04060 04066 250 04067 04060 04076 400 04070 04076 570 04071

100

100

97

100

95

100

92

100

90

97

bb

NSX160 TMD-TMG NSX160STR

152

160

147

160

144

156

140

152

136

147

bb

160

160

156

160

152

160

147

160

144

156

bb

NSX250 TMD-TMG NSX250STR

213

231

207

225

200

219

193

213

185

207

bb

219

245

213

238

207

225

200

219

193

213

bb

NSX400B/F/ N/H/S/L fixed NSX630B/F/ N/H/S/L fixed

360

390

350

380

340

370

330

360

320

350

bb

520

555

505

540

490

525

470

510

450

495

bb

b connection not possible.

The indicated performance characteristics are valid for: bb Compact NSX100/160/250/400 circuit breakers used as incoming or outgoing devices bb Compact NSX630 circuit breakers used as incoming device.

Note: the values indicated above have been validated for Prisma Plus switchboards.

141

Additional information

Electrical characteristics

Designing connections with cables


Cables
Practical guidelines
Schneider Electric provides cabling recommendations according to the rating of the circuit breaker. The size of cables must be selected according to: bb the level of current bb the ambient temperature around the conductors bb the degree of protection for the switchboard. The tables below take into account the installation conditions for each type of device (permissible temperature at connection terminals, etc.). They follow the temperature derating values for installed devices in all enclosures with cover panels rated IP y 55. bb switchboard internal temperature 60 C bb connections using copper cables. For System G, the volumes, ratings and connection lengths are low. Select the values in the Cables tied together column, according to the IP.

Connection of circuit breakers


Size of cables (mm)
1.5 2.5 4 6 10 16 25 35 50 70 95

Permissible current (A) Cables tied individually IP y 31 IP > 31


16 25 32 40 63 90 110 135 180 230 275 14 25 29 39 55 77 100 125 150 190 230

Cable tied together IP y 31 IP > 31


14 22 28 36 55 80 100 125 12 20 24 33 50 70 93 120

Connection of other devices


Size of cables (mm)
1.5 2.5 4 6 10 16 25 35 50 70 95

Permissible current (A) Cables tied individually IP y 31 IP > 31


13 23 28 36 55 80 100 120 165 210 250 12 21 26 35 50 70 90 115 135 176 210

Cable tied together IP y 31 IP > 31


12 20 25 32 50 72 90 110 10 19 22 30 46 63 84 103

Connection of NSX100 to 630 A


Device Size (mm)
> see page 139

NSX100
25

NSX160
50

NSX250
95

Note: Schneider Electric recommends connecting NSX400/630 circuit breakers with insulated flexible bars or rigid bars.

Note: the values indicated above have been validated for Prisma Plus switchboards.

142

Additional information

Electrical characteristics

Designing connections with cables


Tubular lugs
Tubular lugs for incoming connection blocks
Standard Cu lugs Narrow Cu lugs

Maximum size of lugs for connection to the different incoming connection blocks.
Narrow bimetal lugs

Incoming connection block for NSX-INS250 supplied via the top or bottom, cat. no. 04066 and 04067 In-duct incoming connection block for NSX630, cat. no. 04076

150 mm 240 mm

240 mm 300 mm

185 mm 300 mm

Narrow bimetal lugs


DD382788

Catalogue numbers selection


Catalogue numbers Cable size (mm) 150 150 185 185 240 240 300 300 Quantity 3 4 3 4 3 4 3 4

Lugs for aluminium cable(1)


29504 29505 29506 29507 32504 32505 32506 32507 (1) Supplied with 2 or 3 interphase barriers.

143

Additional information

Electrical characteristics

Designing the PEN conductor


Power circuit

Size of PEN protective conductor


Practical guidelines
The size of the PEN is determined in the same manner as a neutral conductor, i.e.: bb for copper single-phase circuits or sized y 16mm, it must be the same size as the phase conductors bb for copper three-phase circuits sized > 16 mm, it can be: vv the same size as the phase conductors vv smaller on the condition that: -- the current likely to flow in the neutral during normal operation is less than the permissible current for the conductor -- the power rating of single-phase loads does not exceed 10% of the total rating. The conductor must be accessible to enable connections both in the factory and on site, as well as checks on the tightness of connections.

Implementing the PEN protective conductor


Practical guidelines
According to standard IEC 61439-1 and 2, the practical guidelines for implementing the PEN are the following: bb at the entry to the assembly, the PEN connection must be next to the phase connections bb within the assembly, the PEN does not need to be insulated from the exposed conductive parts (except on sites where there is a risk of fire or explosion) bb the size of the conductor must be at least equal to that of the neutral bb the size must remain constant throughout the main busbars bb the change from a TNC to a TNS system must take place at a single point in the switchboard, via a marked neutral-disconnection bar that is accessible and can be dismantled to facilitate the impedance measurement of the fault loop bb after the TNS creation point, it is forbidden to recreate a TNC system. The PE and the neutral must meet their specific requirements.

144

Additional information

Practical information

Connection of power cables

bb To ensure protection of persons, first connect the switchboard protective conductor to the earth electrode. bb Tie the cables as close as possible to the connections to avoid any mechanical stresses on the device terminals. When not using cable glands, also attach the cables near to the cubicle entry point. bb Cables must never be in contact with or passed between live conductors. bb Sharp edges of the framework must be protected where cables pass to avoid damaging the conductors. bb Comply with a minimum radius of curvature of 6 to 8 times the cable outside diameter. bb All power connections must be made with class 8.8 mounting hardware and elastic contact washers, tightened to the torque indicated in the table below. bb When connecting aluminium cables to copper terminals, use bimetal lugs or interfaces. bb Separate the different types of circuits into separate cable bundles (power, control, 48 V, 24 V, DC, AC, etc).

Cable bundles
Cable cross-sectional area (mm ) CSA y 10 16 < CSA y 50 CSA u 50 Max. number of cables per bundle 8 4 Tie individually

Tying the cable bundles


Type of tie Width: 4.5 mm Load: 22 kg Width: 9 mm Load: 80 kg Maximum Icw (kA/rms 1s) 10 15 20 20 25 35 45 Distance between ties (mm) 200 100 50 350 200 100 70

For cable sizes of 50 mm or more, use 9 mm wide fixing ties. Recommended tightening torque for mechanical and electrical connections with 8.8 class screws.
Diameter of screw M3 M4 M5 M6 M8 M10 M12 Tightening torque (Nm) (with nut + contact washer) 1.5 3.5 7 13 28 50 75

145

Additional information

Standards

Standards

What is a standard?
A common reference
"A standard helps to define a common language between economic stakeholders (producers, users and consumers), to clarify and harmonize practices and to define the levels of quality, safety, compatibility, and least environmental impact of products, services and practices. Standards facilitate trade, both national and international, and help to better structure the economy and facilitate the everyday life of everyone."
Afnor definition

IEC international standards

The IEC (International Electrotechnical Commission) is a worldwide organisation for standardisation comprising all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote international cooperation on all questions concerning standardisation in the electrical and electronic fields. To that end, the IEC publishes International Standards. Their preparation is entrusted to technical committees and any IEC National Committee interested in the subject dealt with may participate in the preparatory work.

National standards
In Europe The IEC documents are first studied by CENELEC, which establishes: bb either a European standard (EN), often identical to the IEC standard, which then becomes the applicable national standard in all the member countries bb or, in the event of differences, a harmonisation document (HD). Other IEC member countries Each country is autonomous and can accept the IEC standard as the national standard, with or without modifications. Even though they are IEC members, countries such as Japan and the United States continue to develop their own standardisation systems. Countries without a standardisation system It is possible to refer to an IEC standard in the framework of a project.
DD383972

Worldwide

Other IEC member countries

Countries
CEI / IEC Commission Electrotechnique Internationale CENELEC Comit Europen de Normalisation ELECtrotechnique UTE Union Technique de llectricit VDE Verband der Elektrotechnik, Elektronik und Informationstechnik e.v. (German electrotechnical, electronics and computer technology standardisation organisation) BSI British Standards Institution

146

Additional information

Standards

Standards

The different types of standards


There are different types of standards, including: bb management standards bb installation standards bb product standards.
DD381775 DD381776

Management standards

ISO 9004: Quality-management systems - guidelines for performance improvements. Used in setting up a quality-management system. ISO 9001: Quality management systems - requirements. Used for certification audits.

Design and manufacture.

Switchgear and controlgear assemblies.


DD381778

ISO 14004: Environmental-management systems. General guidelines on the principles, systems and supporting techniques. ISO 14001: Environmental-management systems. Specification with guidance for use. The majority of Schneider Electric development centres and factories are certified ISO 9001 and ISO 14001.

DD381777

Low voltage installation standards


Switchgear and controlgear. Installation.

The set of IEC 60364 standards defines the main principles and rules for the design and the mounting of the electrical installation: bb determining general characteristics of installations bb protection bb selection and installation of equipment bb verification and maintenance of installations.

Switchgears standards

They apply to devices or assemblies and are aimed at ensuring correct operation and safety of the concerned products: bb standards on low-voltage switchgear and controlgear: vv IEC 60947-1: general rules vv IEC 60947-2: circuit breakers vv IEC 60947-3: switches and disconnectors vv IEC 60947-4: contactors vv IEC 62208: empty enclosures. bb The IEC 61439 switchboard standard The IEC 61439 standard: vv characterizes the electrical switchboard and specifies the design, construction and verification rules vv describes in detail all low-voltage switchgear and controlgear: definitions, technical characteristics, conditions of use, and construction and verification requirements vv applies to power switchgear and controlgear assemblies (PSC assemblies) whose rated voltage does not exceed 1000 V in alternating current or 1500 V in direct current. Regulations in a given country may make certain standards legally binding and may also create additional safety requirements. In addition to providing proof of the conformity of its quality-management system, a product manufacturer can demonstrate the quality of products by providing proof that the design and manufacture comply with the requirements in the applicable standard. Proof of conformity may be a declaration by the manufacturer or a certificate supplied by an independent organisation.

147

Additional information

Standards

Standards

Enclosure standards

Standard IEC 62208 lay down definitions, classifications, characteristics and test requirements for enclosures used for switchgear and controlgear assemblies. They apply to empty enclosures before installation of the devices by the panelbuilder, as supplied by the manufacturer. They apply to one-piece enclosures and to enclosures supplied in kit form.

Type tests of standard IEC 62208


1 - Static load 2 - Hoisting 3 - Axial loads of metal inserts 4 - IK code 5 - IP code 6 - Thermal stability 7 - Resistance to heat 8 - Resistance to abnormal heat and to fire 9 - Dielectric strength 10 - Protective-circuit continuity 11 - Weather resistance 12 - Corrosion resistance 13 - Marking

e marking

e marking is a regulatory symbol attributed under the sole responsibility of the manufacturer and intended for the verification authorities of the European countries that enforce the European regulations. It allows free circulation of a product in the European Union and certifies that it complies with the basic requirements in all the applicable European directives. e marking is not a quality symbol and does not indicate conformity with a standard The e declaration is intended exclusively for the authorities in charge of verifying compliance with the applicable regulations and it is drafted, signed and held for presentation to the authorities by the manufacturer. For the Prisma Plus range, the declaration is the responsibility of the Schneider Electric unit that has designed and developed the product. For LV switchboards, the declaration is the responsibility of the panelbuilder. The following products receive e marking: bb all products that are liable to endanger the safety of persons, animals and property (LV directive) bb all products likely to emit electromagnetic disturbances above a standardised threshold or to be disturbed during operation (EMC directive). Consequences: bb the Prisma Plus range falls under the LV directive only bb LV switchboards are covered by the LV directive and may also fall under the EMC directive, depending on the type of devices incorporated. For the Prisma Plus range, e marking is applied: bb on the packing of "mechanical" components bb on the product itself for "electrical" components. For the LV assemblies created by the panelbuilder, e marking is applied: bb on the packing bb on the rating plate (if applicable) bb on one of the documents accompanying the switchboard when it is shipped.

e
148

Additional information

Standards

Standards

Degree of protection

Standard IEC 60364-5-51 lists and codifies a large number of external influences to which electrical installations can be subjected, including the presence of water, solid objects, shocks, vibrations, corrosive substances, etc.

IP code

Standard IEC 60529 (IP code, February 2001) indicates the degrees of protection provided by an enclosure for electrical devices against access to hazardous parts, against penetration of solid foreign objects and against penetration of water. These standards do not apply for the protection against the risks of explosion or conditions such a humidity, corrosive vapour, fungus or vermin. The IP code is made up of two characteristic numerals and can include an additional letter when the actual protection for persons against access to the hazardous parts is better than that indicated by the first numeral. The first numeral characterises the protection provided against the ingress of solid foreign objects and the protection of persons. The second numeral characterises the protection provided against the ingress of water with harmful effects.

1st numeral Protection of persons


DD381959

DD381959

DD381960

DD381963

DD381961

DD381961

DD381962

DD381962

DD381962

DD381964

DD381962

DD381965

DD381973

Protected against the effects of continuous immersion in water

DD381972

Protected against the effects of temporary immersion in water

DD381971

Protected against access with a wire

Dust tight

Protected against powerful water jets from all directions

DD381970

Protected against access with a wire

Protected against dust (dust protected)

Protected against water jets from all directions

DD381969

4 Protected against access with a wire

Protection against solid foreign objects larger than 1 mm

Protected against splashing water from all directions

DD381968

Protected against access with a tool

Protection against solid foreign objects larger than 2.5 mm

Protected against spraying water up to 60 from vertical

DD381967

2 Protected against access with a finger

Protection against solid foreign objects larger than 12.5 mm

Protected against dripping water up to 15 from vertical

DD381966

Protected against access with back of hand

Protection against solid foreign objects larger than 50 mm

Protection against ingress of solid objects

2nd numeral Protection against ingress of water

Protected against vertically dripping water (condensation)

149

Additional information

Standards

Standards

Additional letter

The additional letter is used only if the actual protection of persons is higher than that indicated by the first characteristic numeral of the IP code. Additional letter
A B C D

Protection
A Protected against access with back of hand B Protected against access with a 12 mm diameter finger C Protected against access with a 2.5 mm diameter tool D Protected against access with a 1 mm diameter wire

If only the protection of persons is of interest, the two characteristic numerals are replaced by the letter "X", e.g. IPXXB.

Illustration of the above explanations:


Protection against solid foreign objects larger than 2.5 mm

IP30D

No protection Protected against access with a 1 mm diameter wire

Remarks bb The degree of protection IP must always be read and understood numeral by numeral and not as a whole. For example, an IP31 wall-mount enclosure is suitable for an environment that requires a minimum degree of protection IP21. However an IP30 wall-mount enclosure is not suitable. bb the degrees of protection indicated in this catalogue are valid for the enclosures as presented. However, the indicated degree of protection is guaranteed only when installation and device mounting are carried out in accordance with professional standards that conserve the initial degree of protection.

IK code
IK code
01 02 03 04 05 06 07 08 09 10

Standard IEC 62262 defines an IK code characterising the capacity of products to resist mechanical impacts from all sides. Impact energy (joules)
0.14 0.2 0.35 0.5 0.7 1 2 5 10 20

IK codes can be selected according to the risks of impacts on a given site. Site
No risk of major impact Significant risk of impact that can damage devices Maximum risk of impact that can damage the switchboard Technical premises Hallways Workshops

Recommended IK
07 08 (switchboard with door) 10

150

Additional information

Enclosure characteristics

Selection of enclosures according to the premises


The IP and IK degrees of protection provided by an enclosure must be specified as a function of the various external influences defined by standard IEC 30364-5-51, in particular: bb presence of foreign solid bodies (code AE) bb presence of water (code AD) bb mechanical stress (code not specified) bb capability of persons (code BA) bb ... Prisma Plus switchboards are designed for indoor installation. Unless the rules, standards and regulations of a specific country stipulate otherwise, Schneider Electric recommends the following IP and IK values based on French guide UTE C 15-103 (March 2004).

Using the table

1 Opposite the relevant premises, read the recommended IP and IK values. 2  The b symbol indicates the enclosure or cubicle satisfying the criteria of the UTE guide. Any enclosure or cubicle with a higher degree of protection can also be used. 3  If several degrees of protection are possible (refer to the standard for more details) and the v and b symbols are indicated (e.g. 24v/25b), enclosures that correspond to the higher degree of protection (b) are suitable for the lower degree of protection (v). Example: Selection of an enclosure for a laundry room. Minimum degree of protection: IP21/IK02 A wall-mounted enclosure with a door (plain or transparent), a canopy and a gasket offer IP43/IK08 degrees of protection and are therefore suitable for this application. Type of premises Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK Domestic or comparable premises or locations 24 07 Porch Bathrooms (see washrooms) Bicycles, motorcycles, tricycles, etc. (premises for) Water, sewer and heating connections Laundries Cellars, garages, furnace rooms Bedrooms Trash rooms Halls in cellars Courtyards Kitchens Shower rooms (see washrooms) Indoor stairways and alleys Outdoor stairways and outdoor alleys without roofs Outdoor alleys with roofs Attics (roof space) Garden shelters Latrines Dustbin rooms Ironing room Access ramps to garages N/A 20 24 21 20 24/25 20 25 20 25 02/07 07 02 02 02/07 02 02/07 02 07 bb bb bb bb bb bb bb bb 20 23 21 20 20 25 20 24/25 20 07 02 02 02/07 02 07 07 02/07 02 bb bb bb bb bb bb bb bb without door with door with door + canopy with door + canopy + gasket with door + canopy+ gasket IP43/IK08 IP55

without door IP30/IK07

with door IP30/IK08

with door + canopy IP31/IK08

IP55/IK10

bb

151

Additional information

Enclosure characteristics

Selection of enclosures according to the premises

Type of premises

Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK 27 02 24 23 21 20 21 21 20 20 23 02 02 02 02 02 02 02 02 07 08 07 07 07 07 02 08 07 02 02 02 07 07 02/07 07 07 07 07 02 08 08 07 07 07 02 02 02 08 07 02 07 bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb b bb bb bb bb bb bb bb bb bb bb bb bb bb bb without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55

without door IP30/IK07

with door IP30/IK08

with door + canopy IP31/IK08

IP55/IK10

Washrooms, rooms containing a bathtub or shower

volume 0 volume 1 volume 2 volume 3

bb

Lounges, living rooms, etc Drying rooms Covered terraces WCs Verandas Crawl spaces

Commercial premises and adjoining areas Gunsmiths (storage area, workshop) 30 Laundries (wash room) Butchers shop cold room: y -10 C Bakers, cake shops (kitchens) Coffee roasters Coal, wood, oil Delicatessen (production) Sweets (production) Shoe repair shops Dairies Hardware stores (storage areas for chemicals and paint) Wood workers Art galleries Florists Furriers Fruit and vegetable merchants Grain shops Bookshops, stationers Motorcycle and bicycle repairs and accessories Messenger services Furniture shops (antiques, secondhand) Glass and mirror merchants (workshop) Wallpaper shop (storage area) Cosmetics shop (storage area) Chemists (storage area) Photographers (dark room) Plumbers (storage area) Fishmongers Dry cleaners Hardware stores (without paint, chemicals, etc.) Locksmiths Vintners, spirits Interior decorator (carding) Tailors, clothing retailers (storage area) Pet care N/A 24 24 23 50 21 20 24 20 20 24 33 50 20 24 20 24 50 20 20 20 20 20 20 20 20 23 20 25 23 20 20 20 50 20 35

07v/08b vv 07 07 02 07 bb

152

Additional information

Enclosure characteristics

Selection of enclosures according to the premises

Type of premises

Enclosures
Wall-mounted enclosure without door with door with door + canopy with door + canopy + IP55 gasket with door + canopy + gasket IP43/IK08 IP55/IK10

Floor-standing enclosure without door Min. IP/IK required IP IK Buildings open to the general public Shared premises of storage rooms buildings open to the packing rooms general public archive rooms film and magnetic media storage linen rooms laundry rooms misc. shops kitchens (large) J L Reception old and handicapped people Lecture halls, halls meeting rooms, stage areas auditoriums, scenery storage halls used for several purposes rooms costume rooms Retail premises, sales premises shopping malls areas for storage and handling of packing Restaurants and cafes Hotels and boarding houses Dance halls and gaming parlours Teaching classrooms establishments, dormitories holiday camps Libraries and documentation centres Exhibitions halls and rooms areas for reception of equipment and merchandise U Healthcare establishments bedrooms incineration operating rooms centralised sterilisation 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 21 20 24 02 02/07 08 08 07 08 08 08 02 07 02 08 02 02 07 02 07/08 07 02/07 bb bb bb bb bb bb bb bb bb bb bb 20 20 20 20 20 24 21 08 08 02 02 02 07 07/08 bb bb bb IP30/IK07

with door IP30/IK08

with door + canopy IP31/IK08

bb bb

bb bb

bb bb

bb bb bb

N O P R S T

bb

bb bb vv bb bb bb bb bb vv bb bb bb vv bb bb

pharmacies and labs 21v/23b 02v/07b with more than 10 l of inflammable liquids V W X Places of worship Administrative premises, banks Indoor sports facilities Museums Covered open air facilities halls 20 20 20 02 02 08 02 08 08 08v/10b

07v/08b vv

premises containing 21 refrigeration facilities 20 44 44 21

Y PA

23v/25b 08v/10b

CTS Marquees and tents SG Inflatable structures PS Covered parking lots

153

Additional information

Enclosure characteristics

Selection of enclosures according to the premises

Type of premises

Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55

without door IP30/IK07

with door IP30/IK08

with door + canopy IP31/IK08

IP55/IK10

Technical premises Battery rooms Lifts (machine rooms and pulley rooms) Electrical rooms Control rooms Workshops Laboratories Air conditioning washers Garages (used exclusively for parking vehicles) of an area not exceeding 100 m2 Machine rooms Water pressurisers Boiler rooms coal fuel other fuel electrical Fuel storage areas Cinder tips Pump rooms Pressure reduction rooms (gas) Steam or hot water facilities Expansion vessel rooms Parking lots Carwash areas (inside premises) Petrol stations Lubrication areas Battery recharging areas Workshops Offices Libraries Archives Computer rooms Design offices Rooms containing reprographic machines Sorting rooms Refectories in restaurants or canteens Large kitchens Sports rooms Barracks Meeting rooms Waiting rooms, lounges, halls Medical consulting rooms, not fitted with specific equipment inside outside coal oil liquefied gas

23 20 20 20

02/07 07v/08b vv 07 02 bb bb vv vv bb bb bb

bb

21v/23b 07v/08b 21v/23b 02v/07b 24 21 31 23 07 07 07/08 07/08

bb bb bb

bb vv bb bb vv bb bb bb vv bb vv bb vv bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb

Boiler houses and adjoining premises (power in excess of 70 kW) 51v/61b 07v/08b 21 21 20 20 50 20 21 21 25 21 23 23 21 20 20 20 20 20 20 20 21 07/08 07/08 07v/08b vv 07v/08b vv 08 07v/08b vv 02 07v/10b 07 07 08 07 08 02 02 02 02 02 02 07 07

50v/60b 08

21v/23b 07v/08b 21v/23b 07v/08b

Garages and car parks of an area exceeding 100 m2

Public building (other than for the general public)

20 20 20 20 20

07v/08b vv 07 02 02 02 02/07 bb bb bb bb bb

bb

Demonstration and exhibition rooms 20 N/A

154

Additional information

Enclosure characteristics

Selection of enclosures according to the premises

Type of premises

Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK without door with door with door + canopy with door + canopy + IP55 gasket with door + canopy + gasket IP43/IK08 IP55/IK10

without door IP30/IK07

with door IP30/IK08

with door + canopy IP31/IK08

Farm premises or locations Alcohol (storage) Closed cattle sheds Laundries Wood storage rooms Threshing floors Distilling cellars Vat rooms (wine) Courtyards Poultry barns Stables Fertiliser (storage) Stables Manure heaps Haylofts Haystacks, forage (storage) Granaries, barns Straw (storage) Greenhouses Grain silos Milking rooms Pig sties Chicken houses Miscellaneous installations Fair facilities Water treatment facilities

23 35 24 30 50 23 23 35 35 35 50 35 24 50 50 50 50 23 50 35 35 35 33 24/25

07 07 07 10 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 08 07/08

bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb

Thermodynamic installations, air-conditioned rooms and cold rooms 25 07 Height above from 0 to 1.10 m ground 24 07 from 1.10 to 2 m above 2 m under evaporator or water drain pipe ceiling and up to 10cm underneath Temperature y -10 C Compressor room 21 23 23 21 07 07 07 08 08

34 integral unit located outside or on a terrace

N/A

155

Additional information

Enclosure characteristics

Selection of enclosures according to the premises

Type of premises

Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55

without door IP30/IK07

with door IP30/IK08

with door + canopy IP31/IK08

IP55/IK10

Industrial facilities Slaughter houses Batteries (manufacture) Acid (manufacture and storage) Alcohol (manufacture and storage) Aluminium (manufacture and storage) Livestock (raising, fattening and sale) Asphalt and bitumen storage Wool beating and carding Industrial laundry Wood (processing) Meat packers Bakeries Breweries Brickworks Rubber (production and processing) Carbide (manufacture and storage) Ammunition factories Carton board (production) Quarries Celluloid (manufacture of objects) Cellulose (manufacture) Coal (depots) Pork products Boiler-making works Lime kilns Rag (storage) Chlorine (manufacture and storage) Chrome-plating Cement works Coking plant Adhesives (production) Bottling lines Liquid fuels (storage) Fats (processing) Leather (tanning and storage) Copper (ore processing) Paint stripping Detergents (manufacture) Distilleries Electrolysis Ink manufacturing Fertilisers (manufacture and storage) Explosives (manufacture and storage) Iron (production and processing) Spinning mills Furriers (beating process) Cheese factories Gas (production and storage) Tar (processing) Seed production Metal engraving Oils (extraction) Petroleum products (manufacture) Printworks

55 33 33 33 51 45 53 50 24/25 50 24/25 50 24 53 54 51 53 33 55 30 34 53 24/25 30 50 30 33 33 50 53 33 35 31v/33b 51 31 31 54 53 33 33 31 53 55 51 50 50 25 31 33 50 33 31 33v/34b 20

08 07 07 07 08 07 07 08 07 08 07 07 07 08 07 07 08 07 08 08 08 08 07 08 08 07 07 07 08 08 07 08 08 07 08 08 08 07 07 08 07 07 08 08 07 07 07 08 05 07 07 07 08 08

bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb vv bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb vv bb

156

Additional information

Enclosure characteristics

Selection of enclosures according to the premises

Type of premises

Enclosures
Wall-mounted enclosure Floor-standing enclosure without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55

without door IP30/IK07

with door IP30/IK08

with door + canopy IP31/IK08

Min. IP/IK required IP IK Industrial establishments (continued) Dairies 25 07 Public wash-houses Liqueurs (production) Halogenated liquids (use) Inflammable products (storage and workshops where they are used) 25 21 21 21 07 07 08 08 08 08 08 08

IP55/IK10

bb bb bb bb bb bb bb bb bb vv bb bb bb bb vv bb bb bb bb bb bb vv bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb

Magnesium (production, storage and 31 use) Machine rooms Plastics (production) Cabinet makers Metals (processing) Combustion engines (testing of) Ammunition storage Nickel (ore processing) Household waste (processing) Paper (production) Paper (storage) Perfume (production and storage) Pulp mill Paint (production and storage) Plaster (processing and storage) Gunpowder factory Chemicals (production) Oil refineries Salt preserve factories Soap (production) Saw mills Metalwork shops Grain or sugar silos Silk and artificial hair factories Sodium carbonate (processing and storage) Sulphur (processing) Spirits (storage) Sugar mills Tanners Dye works Textile and fabric (production) Varnish (production and application) Glass works Zinc works 20 51 50 30 33 33 54 31 31 34/35 33 50 55 34/35 33 31 50 30 50 50 33 51 33 55 35 35 51 33 33 31

31v/33b 08 08 08 08 07 07 07 07 08 07 08 07 07 07 08 08 07 08 07 07 07 07 07 07 08 08 08 08

33v/34b 07

30v/50b 08

157

Additional information

Enclosure characteristics

Properties of metal enclosures

Schneider Electric enclosures comply with standard IEC 62208 for empty enclosures. The sheet metal used for Schneider Electric enclosures receives an anti-corrosion epoxy electrophoresis treatment and a coating of a thermosetting, polyester-resinmodified epoxy powder for colour and appearance. This two-coat system provides excellent finish and corrosion protection. The characteristics of this coating are much better than those of traditional epoxy powders: bb improved colour stability bb wider operating temperature range.

Mechanical properties of enclosures


Static load on doors, wall-mounted and floor-standing enclosures and cubicles
Floor-standing enclosure Wall-mounted enclosure Floor-standing enclosure door Wall-mounted enclosure door 64 kg 48 kg 4 kg 4 kg

Mechanical properties of powder coated surfaces


Test conditions Test piece made of 1 mm thick steel sheet, degreased, iron phosphated, final rinsing with 100000 W cm DI water, 15 microns of anti-corrosion electrophoresis treatment and 35 microns of powder paint.
class 0 required > 1 kg/50 cm < 10 mm 300 s (ISO 2409) (ISO 6272) (ISO 6860) (ISO 1522)

Adhesion (cross-hatch and pull-off) Impact strength (1) Mandrel bending test (2) Persoz hardness

(1) No cracking of the paint film after dropping a weight of one kilogram on the test piece from a height of 50 centimetres. (2) Film cracks over a length of 10 millimetres maximum.

Test conditions: two tests carried out on the same 1 mm thick steel sheet test piece. bb cyclical damp-heat test: vv as per standard IEC 68-2-30 -- six 24-hour cycles at temperatures higher than 40 C bb continuous resistance to neutral salt mist: vv the tests were carried out over a period of 400 hours, far more than the 48 hours required by the standard for indoor installations vv as per standard IEC 68-2-11 and ISO 7253 -- 400 hours without blistering for normal surface on test piece -- 250 hours for a scratched surface. Evaluation of corrosion as per ISO 4628: bb adhesion: class y 1 bb blistering: degree 1 dim.1 bb rusting: Ri 1 bb cracking: class 1 bb flaking imp. 1 dim. 1 bb propagation of corrosion under scratch with respect to the scratch axis: 3 mm max.

Artificial ageing test on powder coating

Chemical properties of powder coating


Tests carried out at ambient temperature on phosphated test pieces coated with a 150 to 200 micron film.
Acids

Test duration (months)


Acetic Sulphuric Nitric Phosphoric Hydrochloric Lactic Citric Soda Ammonia Distilled water Seawater Tap water Diluted bleach Petrol High alcohols Aliphatics Aromatics Ketones, esters Tri-perchlorethylene Film intact.

Bases Water

Concentration 20 % 30 % 30 % 30 % 30 % 10 % 10 % 10 % 10 %

10

12

Solvents

Film damaged (blisters, yellowing, loss of shine).

158

Additional information

Thermal characteristics

Thermal management of switchboards


General
A switchboard is designed for operation under normal ambient conditions. Most devices do not operation correctly outside a temperature range of -10 and +70C. It is therefore important to maintain the switchboard internal temperature within this temperature range by: bb correctly sizing the switchboard during design bb correcting the temperature using suitable means.

Management of the internal temperature


Cooling There are a number of way to dissipate heat from the switchboard. The drawings below present the various means. Convection
DD383633 DD383634 DD383635

Forced-air ventilation

IP > 31 IP y 31 Ensured naturally in Prisma Plus enclosures.

IP y 54 Using fans, it significantly increases the thermal capacity of an enclosure.

Forced-air ventilation with air-air exchanger


DD383637 DD383638

Forced convection and cooling

?
IP > 31 On special request. IP > 31

bb For these extreme cases, many installers prefer to set up the switchboards with other electrotechnical and electronic devices in air-conditioned electrical rooms. Heating The means employed to raise the internal temperature in a switchboard is a resistorbased heater, used to: bb avoid condensation by limiting variations in temperature bb ensure that the switchboard does not freeze.

159

Additional information

Thermal characteristics

Thermal management of switchboards


General
Calculation of the internal temperature

DD381401

Calculation of the temperature is the means to check that the enclosure can evacuate the dissipated power of the installed devices. Important note Correct thermal management of the switchboard depends on compliance with the installation requirements for the distribution system (power circuits). Incorrect installation will have major consequences on the connected device, but almost none on the internal temperature of the enclosure. Once the circuit has been correctly sized, it is necessary to check whether the assembly (devices + distribution system + cables) have a level of dissipated power P(W) y the P(W) that the enclosure can handle. Method defined by IEC 890 technical report This IEC guide for switchboards proposes a calculation method to determine three levels of internal temperature, depending on the dissipated power of the devices and distribution blocks installed in the switchboard. Users can consult this document when it is necessary to determine precisely the internal temperature in view of optimising the switchboard. On request, Schneider Electric can carry out a thermal study to check that the installed assembly and the thermal capacity of the enclosure are compatible. Comparative method A number of qualified and tested configurations serve as the basis for indicating the thermal capacity of Prisma Plus enclosures. This is en empirical means to check whether the dissipated power of the desired configuration is close to that of a tested configuration. Method using charts taking into account enclosure characteristics To speed up calculations, Schneider Electric produces charts based on the companys experience and a number of assumptions on the installation. They can be used sufficiently precisely to determine the variations in temperature and the dissipated-power levels for the different types of wall-mount enclosures, floor-standing enclosures and cubicles.

DD382422

DD383636

160

Additional information

Thermal characteristics

Thermal management of switchboards


Comparative method
Comparative method

You will have no problems with your switchboard if: bb the volume of the enclosure is greater than that of the tested enclosure with a similar assembly bb the P(W) of the installed assembly is less than the P(W) of the tested configuration in the same size enclosure. Pack enclosure, 3 rows, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 95 W

DD384080

C60N or IC60N 40 A

C60N or IC60N 32 A

C60N or IC60N 20 A

C60N or IC60N 25 A

C60N or IC60N 40 A

C60N or IC60N 25 A

Wall-mounted enclosure, 23 modules, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 170 W

DD384081

NSX250N

C60N or IC60N 63 A

C60N or IC60N 50 A

C60N or IC60N 20 A

C60N or IC60N 50 A

C60N or IC60N 40 A

C60N or IC60N 32 A

C60N or IC60N 20 A

C60N or IC60N 20 A

C60N or IC60N 40 A

C60N or IC60N 32 A

C60N or IC60N 20 A

C60N or IC60N 25 A

161

Additional information

Thermal characteristics

Thermal management of switchboards


Comparative method
Comparative method

You will have no problems with your switchboard if: bb the volume of the enclosure is greater than that of the tested enclosure with a similar assembly bb the P(W) of the installed assembly is less than the P(W) of the tested configuration in the same size enclosure. Wall-mounted enclosure, 23 modules, plain door, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 200 W

DD383955

NSX400

NSX125N

NSX100N

Floor-standing enclosure, 33 modules, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 270 W

DD384082

NSX630N

NSX250N NSX250N

C60a or IC60a 10 A

C60a or IC60a 10 A

C60a or IC60a 10 A

C60a or IC60a 10 A

C60a or IC60a 10 A

162

Additional information

Thermal characteristics

Thermal management of switchboards


Example
Once the dissipated power of the devices has been determined and the enclosure with its IP selected, transfer the results (sum of the dissipated power and width of the device zone) to the chart corresponding to the enclosure IP.
DD382423

Draw a line parallel to the others on the chart and read the corresponding difference in temperature. For the given example, the heat rise is 22 C at mid-height in the enclosure. The internal temperature = external temperature + heat rise = 35 C + 22 C = 57 C 57 C < 60 C stipulated by the standard, i.e. the result is acceptable for an IP3 cubicle. This gives roughly: Internal temperature = 60 C at mid-height in the enclosure for a low IP value. = 70 C at mid-height in the enclosure for a high IP value.

163

Additional information

Thermal characteristics

Thermal management of switchboards


Charts
Quick calculation charts for internal temperatures
The indicated internal heat rise is that measured at mid-height in the enclosure.

IP3X wall-mounted enclosure


DD382432 DD382433

IP43 wall-mounted enclosure

Test conditions: 600 mm wide enclosure mounted directly on wall without fixing lugs. IP3X floor-standing enclosure
DD382434 DD382435

Test conditions: 600 mm wide enclosure mounted directly on wall without fixing lugs. IP43 floor-standing enclosure

Test conditions: 600 mm wide enclosure on floor against a wall.

Test conditions: Mounted on wall with fixing lugs or on mounting uprights. IP55 wall-mounted and floor-standing enclosures
DD382436

Test conditions: 600 mm wide enclosure mounted directly on wall without fixing lugs or mounting uprights.

164

Additional information

Thermal characteristics

Thermal management of switchboards


Ventilation
Switchboard ventilation

The air enters the lower section via the fans and exits the upper section: bb through a ventilated roof bb or through a ventilation opening. The air throughput of the fans is determined by the equation:
P D = 31 -- KS DT

The chart below can be used to determine the necessary throughput, based on the dissipated power, the difference in temperature (internal - external) and the exposed surface area of the enclosure. Example Consider an IP3X cubicle, 650 mm wide and 400 mm deep, containing components (devices, connections, busbars, etc.) dissipating 1000 W. The ambient temperature around the cubicle is 50 C. Given that the average temperature at mid-height should not exceed 60 C, the difference in temperature DT is equal to 60 - 50 = 10 C. The exposed surface of the cubicle (non adjacent to a wall or other cubicle) is 4.46m. (back = 1.3 m, front = 1.3 m, roof = 0.26 m, side panels = 1.6 m). What is the necessary throughput of the ventilation system? The throughput can be calculated as:
1000 D = 31 ----- 5 5 10 46

D=234m3/h. In the range of Prisma Plus accessories, select a system with a throughput of 300m3/h.
DD381391

Calculation data P : power dissipated by the devices, connections and busbars (in Watts) Pr : power of the heating resistor (in Watts) Tm : maximum internal temperature in the device zone (in C) Ti : average internal temperature (in C) Te : average external temperature (in C) DTm =Tm Te DT=Ti Te S : total free surface area of the enclosure (expressed in m2) K : thermal-conduction coefficient of the material (W/m2 C) K = 5.5 W/m2 C for painted sheet metal D : ventilation throughput (in m3/h)

Note: The dissipated power of each device is provided by the manufacturer. Add approximately 30% to account for the connections and the busbars.

165

Additional information

Thermal characteristics

Thermal management of switchboards


Heating
Switchboard heating

The heating resistor, placed in the bottom of the switchboard, maintains the internal temperature 10 C higher than the external temperature. When the switchboard is not in operation, the heater compensates the dissipated power normally emitted by the switchboard. The power of the heating resistor is calculated: bb using the equation: Pr = (DT x S x K) - P bb or using the charts below, based on the exposed surface area of the enclosure and the desired difference in temperature. Chart to determine the heating resistor for small wall-mounted enclosures (exposed surfaces y 1 m2)
DD381788

Chart to determine the heating resistor for all types of enclosures


DD381789

Calculation data P : power dissipated by the devices, connections and busbars (in Watts) Pr : power of the heating resistor (in Watts) Tm : maximum internal temperature in the device zone (in C) Ti : average internal temperature (in C) Te : average external temperature (in C) DTm =Tm Te DT=Ti Te S : total free surface area of the enclosure (expressed in m2) K : thermal-conduction coefficient of the material (W/m2 C) K = 5.5 W/m2 C for painted sheet metal D: ventilation throughput (in m3/h)

Note: The dissipated power of each device is provided by the manufacturer. Add approximately 30 % to account for the connections and the busbars.

166

Additional information

Practical information

Tools required for mounting and connection


bb Vacuum cleaner to clean the switchboards bb Ratchet wrench with sockets bb Torque wrench with sockets and ring bits to tighten the electrical connections to the correct torque (max. torque 50 Nm) bb Open-ended spanners (15 to 27 mm) bb Electrician's knife bb 7, 8, 10, 13, 16, 17 and 19 mm sockets bb Bit holder socket bb 4, 5, 6, 8 and 10 mm hexagonal-head bits bb Pozidriv no. 1, 2 and 3 bits bb Rubber mallet bb Level bb Measurement and inspection tools and instruments bb Drill bb Semi-circuit nosed pliers bb Cable-tie pliers bb Wire stripper bb Crimping tool bb Diagonal cutter bb Wire cutters bb Flat-nosed pliers bb Bit holder for screwdriver bb Extension bb Electric saw bb Jig saw bb Clamp for cubicle alignment bb Buzzer or tester bb 3, 5, 4, 5.5 and 8 mm flat screwdrivers bb Posidriv no. 2 crosshead screwdriver (to mount handle) bb Hydraulic jacks that can be operated in horizontal position to lift cubicles and move them sideways if necessary bb Coloured, indelible and temperature resistant acrylic varnish bb Electric screwdriver

DD383904

167

Notes

168

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F- 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com DESW015EN

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
This document has been printed on ecological paper.

Publication: Schneider Electric Industries SAS Design/Layout: Emmanuel Froger / SEDOC Printed: Altavia Connexion - Made in France 10-2011

2011 - Schneider Electric - All rights reserved.