Bid Specification, Permanent Power Quality Analyzer

Technical specification requirement IEC 61000-4-30 Class A Permanent Power Quality Analyzer Technical specification Voltage Channel:

1(3)

Must have at least 4 Differential Input Voltage Channel in order to be able to measure line neutral as well as line-to-line voltages. The voltage channels will be connected directly to the measure point or via existing PTs. Measure range is from 0-275 Vrms. 0-275 Vrms 14 bits (84 db) or better 128 sample points per cycle (6.4 kHz) simultaneously on all eight channels without time-gaps. Up to 7.7 khz (60 Hz system) At least 2 Mohm 3 khz for calculated parameters. In accordance with IEC 61000-4-30 Class A 0.1% according to IEC 61000-4-30 Class A >= 1 us duration (1 Mhz) +/- 1000V peak 14 bits (84 dB) or better 3 MHz.

Channel Input level: Resolution: Sampling rate:

Input Impedance: Bandwidth: Anti-aliasing filter: Accuracy: Transient Detection: Transient Capture Input: Transient Resolution: TransientBandwidth:

Current Channel: Channel input level: Resolution: Sampling rate: Input Impedance: Bandwidth: Accuracy: Anti-aliasing filter: Storage Interval:

At least 4 Differential, isolated inputs 0-6 A rms or similar 14 bits (84 dB) or better 128 sample points per cycle (6.4 kHz) simultaneously on all channels 10 mohm maximum 3 khz for calculated parameters 0.1% according to IEC 61000-4-30 Class A In accordance with IEC 61000-4-30 Class A The storage intervals of all measured parameters shall be able to set independently (programmable) with different time intervals Minimum of 10 days of storage in accordance with IEC 61000-2-12

Storage Capacity:

Bid Specification, Permanent Power Quality Analyzer


Communication:

2(3)

Built in RS-232, RS-485, Internal Modem and Ethernet communication shall be available. 0 Centigrade to 50 deg Centigrade IEC 61 010-1

Operating Temperature: Personal Safety Standard: Electro-Magnetic Compatibility: Power Supply:

IEC 61000-6-2 and IEC 61000-6-4 110-240 Vac (50 or 60 Hz) or 100 375 Vdc

Measurement Modules Voltage: RMS values every cycle according to IEC 61000-4-30 Class A. Minimum, Maximum and Average value each storage interval. RMS values every cycle according to IEC 61000-4-30 Class A. Minimum, Maximum and Average value each storage interval. 45 65 Hz Voltage & Current Harmonics up to 50th including interharmonics. According to IEC 61000-4-30 Class A and IEC 61000-4-7Ed2 Class I. THD related to fundamental

Current:

Frequency: Harmonics:

THD-F ( Fundamental ):

THD-R ( Relative, RMS ): THD related to the total rms value. THD-I ( Inter harmonics ): Total Inter Harmonic Distortion related to the fundamental . TDD: THD-2650: K factor: Power Harmonics (PFFT): Harmonic Phase Angle: Flicker: Voltage Unbalance & Current Unbalance: Sags & Swells: Total Demand Distortion related to nominal value Total Upperband Harmonic Distortion ( 26th to 50th ) related to the fundamental. Transformer derating K factor Power Harmonics up to the 11th with sign indicating direction of disturbance Capable of harmonic phase angle measurement IFL (real time flicker), PST & PLT calculated according to IEC61000-4-30 Class A Positive, Negative and zero phase sequence voltage / current plus unbalance (%) according to Standard IEC 61000-4-30 Class A. Selectable trigger condition. Sag management data. Event depth and duration according to IEC 61000-4-30 Class A. RMS Trend Recording. Programmable in percentage of nominal value according to IEC 6100-4-30 Class A Must have a sliding reference function according to IEC 61000-4-30 Class A for all medium and high voltage measurements.

Sag & Swell Hysteresis: Sliding Reference:

Bid Specification, Permanent Power Quality Analyzer


Power Measurements All power quantities must be calculated for single phase or Wye or Delta three phase configuration. Power: Power Factor: Energy: Active Power (kW), Reactive Power (kVAR), Apparent Power (kVA) Power factor (Fundamental), Displacement Power Factor (Fundamental plus harmonics) Active Energy (kWh), Reactive Energy (kVArh), Apparent Energy (kVAh)

3(3)

Data Storage Measured Values must be stored in a non- volatile flash memory. The PQ Analyzer must not contain moving parts like hard disk drives, fans, etc. in order to ensure highest long-time reliability. Instruments with moving parts mentioned earlier will not be considered acceptable.

Real-time Capabilities When in real-time mode the PQ Analyzer must be able to perform real-time analysis of voltage and current waveforms, phase displacement, real-time values of all parameters, harmonics spectrum, trends and others. This must be done with no stopgap measurement, meaning real-time analysis must be performed without stopping the measurement and data updates.

Software Packages Power Quality Evaluation Software. Automatic Report Writer based on International Reference Standards (IEC 61000-2-12). Data transfer and interface capabilities to an open database program (like Microsoft SQL) for performing network power analysis. Requisites Proponents must present demo unit of the actual model of the equipment offered, hardware and software and conducts actual sample measurement of data to verify performance. Certificates: 1. Calibration Certificate with Traceability 2. Warranty Certificate 3. The Harmonics and Flicker accuracy must be 3rd party certified