BEC POWER PRIVATE LIMITED

DATA SHEET A1

400kV SWITCHYARD
SI. NO ITEM UNIT CLIENTS SPECIFICATION

400kV SWITCHYARD The 400kV Switchyard shall comply with the particulars indicated below. 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 i) ii) iii) iv) 1.12 1.13 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 400KV SWITCHYARD Nominal voltage Highest System voltage Frequency Short circuit current Making current Impulse withstand voltage One minute power frequency withstand voltage Switching impulse withstand Reference ambient temperature Creepage distance Minimum Clearances Phase to phase (min) Phase to earth (min) Sectional clearance Ground clearance Corona extinction voltage Radio interference voltage at 266kV (rms) CIRCUIT BREAKERS Application Quantity Type Execution of poles Type of system neutral earthing Rated current Short circuit breaking current Short circuit withstand current and Duration Making current Operating duty Auto Reclosing (1 pole / 3 pole) First pole clear factor Breaker opening time Breaker closing time Line charging breaking and making Current

kV kV Hz kA (rms) kA (Peak) kV (Peak) kV (rms) kV (Peak) oC mm

400 420 50 50kA for 1 sec. 125kA for 1 sec 1425 630 1050 50 25mm / kV based on highest system voltage 4200 3400 6500 8000 320 Not exceeding 1000 microvolts

Mm mm Mm mm kV (rms) Micro volts

Nos

A kA (rms) kA (rms) Sec kA (peak) m.sec. m.sec. A

As per project requirement 2 SF6 3 nos., single pole Solidly earthed 2500 50 50 1 125 O-0.3sec-CO-3min-CO Required 1.3 BIDDER to confirm BIDDER to confirm BIDDER to confirm

Page 1 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A1

400kV SWITCHYARD
SI. NO
2.16 2.17 2.18 2.19 2.20 2.21 2.22

ITEM
Capacitor breaking current Small inductive current breaking Out of phase switching Anti pumping Type of operating mechanism Operating mechanism to be suitable for Control voltage (AC / DC) a) Motor (AC / DC) b) Close/Trip coils/Circuit No. of trip coils per pole Phase to phase spacing No. of auxiliary contacts Environment (Normal / Polluted / Salty / Dusty / Corrosive) Gas evacuation and filling plant ISOLATORS Application Quantity a) With earth switch b) Without earth switch Type Execution of poles Rated current Short circuit withstand current and Duration Making current a) Breaking capacity of line charging current b) Breaking capacity of magnetising current Short circuit making current of earthing switch Material of main contact Whether contacts are to be silver faced Operating mechanism Main disconnector Earth switch Emergency operation Main disconnector Earth switch A A

UNIT

CLIENTS SPECIFICATION
Not required From 0.5A to 10A Required Required Spring charged 3 single pole operation 220V DC 220V DC 220V DC Two (2) 4200 15NO + 15 NC (min) Normal Required

2.23 2.24 2.25 2.26 2.27 3.0 3.1 3.2

V V V Nos. mm

Nos Nos

3.3 3.4 3.5 3.6 3.7 3.8

A kA (rms) Sec kA (Peak) A A kA (Peak)

As per project requirement As per project requirement As per project requirement Horizontal centre break 3 nos., single pole 2500 50 1 125 As per project requirement As per project requirement 125 Cu Yes Motor & Manual Motor & Manual Motor & Manual Motor & Manual Motor & Manual

3.9 3.10 3.11 3.12 3.12.2 3.12.3 3.13 3.13.1 3.13.2

Page 2 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A1

400kV SWITCHYARD
SI. NO
3.14 3.14.1 3.14.2 3.15 3.15.1 3.15.2 3.16 3.16.1

ITEM
Support insulators Type of insulator (Pedestal / Solid / Polycone etc.) Nominal creepage distance Minimum strength Torsoinal Minimum cantilever strength Miscellaneous No. of NO & NC aux. Contacts for purchaser's use (main and earth switch) Pole discrepancy circuit required Auxiliary supply Electrical

UNIT

CLIENTS SPECIFICATION
As required As required

Mm Nm Kgs Nos

As required As required As required As required

3.16.2 3.17 3.17.1

Yes / No

Yes 220V DC for control and interlock; 415V AC, 3 phase for motor drive Bolt interlock electrically operated. Normal

3.17.2 3.18 4.0 4.1 4.2 4.3 4.4

Type of interlock Environment : salty / dusty / normal/ corrosive / polluted CURRENT TRANSFORMER Type No. of cores Primary current ratio Accuracy class a) Tariff metering b) Metering c) Protection Secondary current Class of insulation Max. temp. rise of winding above ambient of 50C Radio interference voltage at 266kV (rms) CAPACITOR VOLTAGE TRANSFORMERS Quantity Type System neutral earthing Co-efficient of earthing No. of primary / secondary

SF6 filled As required As required 0.2s 0.5 5P20 1 SF6 filled Class-E 50 Not exceeding 500 microvolts

4.5 4.6 4.7 4.8 5.0 5.1 5.2 5.3 5.4 5.5

Micro volts

Nos

As required Outdoor, oil filled, hermetically sealed Solidly earthed 0.8 As per main one line

Page 3 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A1

400kV SWITCHYARD
SI. NO ITEM
windings Primary / secondary winding Voltage Class of insulation Maximum temp. rise of winding above ambient of 50C Application Accuracy class (Metering / Protection) Rated burden Rated power factor Rated voltage factor Rated capacitance

UNIT

CLIENTS SPECIFICATION
diagram As per main one line diagram Oil immersed Class A 50 Metering / Protection 3P / 0.2 As required 0.85 1.2 continuous and 1.5 for 30 seconds Bidder to furnish depending upon frequency selected for PLCC + 10% to 5% 40 500 Within 80% to 150% of rated capacitance Less than 40 ohm

5.6 5.7 5.8 5.9 5.10 5.11 5.12 5.13 5.14

pF

5.15 5.16 5.17

5.18

5.19 6.0 6.1

Tolerance High frequency range High frequency capacitance (i) For entire carrier frequency range (ii) Equivalent series resistance over the entire carrier frequency range Stray capacitance and conductance of low voltage terminal (i) Stray capacitance of low voltage terminal over entire carrier frequency range (ii) Stray conductance of the low voltage terminal over entire carrier frequency range Radio interference voltage at 266kV (rms) ELECTRO MAGNETIC VOLTAGE TRANSFORMERS (EMVTs) Type

kHz

pF

300 + 0.05 Cn, Where Cn is rated capacitance 50

Mho

Micro volts

Not exceeding 500 microvolts

6.2 6.3

System neutral earthing No. of primary / secondary Windings

Outdoor, oil filled, hermetically sealed / SF6 gas filled Solidly earthed As per main one line diagram

Page 4 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A1

400kV SWITCHYARD
SI. NO
6.4 6.5 6.6 6.7 6.8 6.9 7.0 7.1 7.2 7.3

ITEM
Primary / secondary winding Voltage Class of insulation Maximum temp. rise of winding above ambient of 50C Accuracy class Rated voltage factor Corona extinction voltage LIGHTNING ARRESTORS Quantity Installation System voltage Nominal Highest System Earthing Type of arrester Short circuit current at arrester Location Maximum duration of earth fault Co-efficient of earthing Rated values Rated arrester voltage / maximum continuous operating voltage Discharge class INSULATOR Bus post insulator Type Power frequency Puncture voltage Disc insulator Voltage class Type / No Creepage distance Minimum protected creepage distance Electromechanical strength Power frequency Puncture voltage POWER LINE CARRIER COMMUNICATION (PLCC) LINE TRAPS Installation C

UNIT

CLIENTS SPECIFICATION
As per main one line diagram Oil immersed Class A / SF6 filled Class-E 50 0.2 1.2 continuous and 1.5 for 30 seconds As required As required Outdoor

kV

kV kV

7.4 7.5 7.6 7.7 7.8 7.13 7.13.1 7.13.2 8.0 8.1 8.1.1 8.1.2 8.2 8.2.1 8.2.2 8.2.3 8.2.4 8.2.5 8.2.6 9.0 9.1 9.1.1

kA Sec

400 420 Solidly earthed Gapless 50 1 0.8 360 20 kA, Class-IV

kV

Solid core / post type / string 1.3 times corresponding to flash over voltage As required As required As required As required As required 1.3 times corresponding to flash over voltage.

Mm Mm

Outdoor

Page 5 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A1

400kV SWITCHYARD
SI. NO
9.1.2 9.1.3 9.1.4

ITEM
Type of earthing Rated current Minimum resistive component of impedance within carrier frequency blocking range Inductance of main coil Maximum tapping loss (Insertion loss with a line impedance of 400 Ohms) Blocking range Type of mounting Line trap arrester discharge current Band width Tuning device required Type of tuning Variation in 50 Hz impedance per degree centigrade variation in ambient temperature Variation in resonant frequency band per degree centigrade variation in ambient temperature Winding material Radio interference voltage at 266kV (rms)

UNIT

CLIENTS SPECIFICATION
Solidly earthed 2500 As required

A Ohm

9.1.5 9.1.6

mH dB

As required 2.6

9.1.7 9.1.8 9.1.9 9.1.10 9.1.11 9.1.12 9.1.13

kA kHz

90kHz to 500kHz Single point suspension mounting 20 40-500 Required Wide band As required

9.1.14

As required

9.1.15 9.1.16

Radio interference voltage at 266kV (rms) Micro volts dB dB W

AL. Alloy Not exceeding 500 microvolts

9.2 9.2.1 9.2.2 9.2.3 9.2.4 9.2.5 9.2.6 9.2.7 9.2.8 9.2.9

Coupling Devices Composite loss within pass band Return loss within pass band Nominal Peak power P.E.P. at 50/100 Hz. Inductance of the drain coil at 50Hz Continuous / Short time current of Drain coil Rated / Short time current of Earth Switch Rated voltage of surge arrestor Max. 100% impulse spark voltage (1.2/50 micro sec) of surge arrestor Rated discharge current (8/20

V V kA

Page 6 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A1

400kV SWITCHYARD
SI. NO ITEM
micro sec) of surge arrestor Type of construction of surge arrestor No. of H.F. terminals provided for carrier equipment connection Type of mounting / Degree of Protection HIGH FREQUENCY CABLE Type of cable Withstand test voltage (RMS) between conductor and sheath Earthing details of H.F. cable POWER LINE CARRIER TERMINAL Operating Mode Type of modulation Carrier frequency range Band width per channel Frequency separation between transmission(Tx) and reception (Rx) Frequency separation between adjacent channels HF power output Mode of transmission of guard signal Maximum number of noise impulses pps in presence of which the equipment shall satisfactorily perform its duty SCADA System Architecture Overall system availability Redundancy requirements Sequence of events recorder Weather proof box / IP 65

UNIT

CLIENTS SPECIFICATION

9.2.10 9.2.11

9.2.12

9.3 9.3.1 9.3.2

Armoured co-axial cable 4 kV (rms) for 1 Min.

9.3.3 9.4 9.4.1 9.4.2 9.4.3 9.4.4 9.4.5

Tinned copper braided screen to be earthed

kHz kHz kHz

Single side band mode with suppressed carrier Amplitude Modulation 40 to 500, Programmable 4 4

9.4.6

kHz

9.4.7 9.4.8 9.4.9

Watts Hz

80 Pilot frequency- 3780 200ms Noise burst / 1 sec pause

10.0 10.1 10.2 10.3 10.4

Distributed Processing 99.7% CPU, Power supply and communication Yes, with 1ms resolution

Page 7 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A1

400kV SWITCHYARD
SI. NO ITEM
Required System response time Updating of dynamic data on Display Key board command to field equipment execution time Key board command for display presentation execution Key board command to display presentation completion

UNIT

CLIENTS SPECIFICATION

10.5 10.5.1 10.5.2 10.5.3 10.5.4

Every 2 secs Less than 1 sec Less than 2 secs 3 secs

Page 8 of 8

BEC POWER PRIVATE LIMITED


DATA SHEET A2

400kV SWITCHYARD

Sl. No 1.

2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16 17.

Applicable standards Specification for wrought aluminium and aluminium alloy bars, rods, tubes and selections for electrical purposes Circuit breakers
Insulators

IS 5082

BS

_ IEC

IS 13118

BS

IEC 62271100 IEC 273

IS 2544

BS

Large hollow porcelains

IS 5621

BS

IEC 233

Electrical Power Connectors Hot dip galvanizing

IS 5561

BS

IEC

IS 2629 IS 2633 IS 9135

BS

IEC

Guide for testing of circuit breakers for out-of-phase switching SF6 gas

BS

IEC

IS

BS

IEC 376

Isolators

IS 9921

BS

IEC 129 IEC 694 IEC 60146 IEC IEC 137 IEC 358 IEC 186 IEC

Semiconductor converters Current transformers Bushings Coupling capacitors and capacitor dividers Capacitor voltage transformer Electrical relays for power system Protection Specification for static protective Relays Lightning arrester

IS IS 2705 IS 2099 IS 9348 IS 3156, Part IV IS 3231

BS BS BS BS BS BS

IS 8686

BS

IEC

IS 3070

BS

IEC 99

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A2

400kV SWITCHYARD

18. 19. 20.


21. 22

Suspension Insulators Insulator fittings High voltage fuse Low voltage fuse Boards blanks for sley bottom, race, cap and box back of cotton looms

IS 731 IS 2486 IS 9385 IS 9224 IS 9794

BS BS BS BS BS

IEC IEC IEC 602822 IEC IEC

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO ITEM UNIT TO BE FILLED BY BIDDER

DATA TO BE FURNISHED ALONG WITH THE BID.


1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 i) ii) iii) iv) 1.12 1.13 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 400KV SWITCHYARD Nominal voltage Highest System voltage Frequency Short circuit current Making current Impulse withstand voltage One minute power frequency withstand voltage Switching impulse withstand Reference ambient temperature Creepage distance Minimum Clearances Phase to phase (min) Phase to earth (min) Sectional clearance Ground clearance Corona extinction voltage Radio interference voltage at 266kV (rms) CIRCUIT BREAKERS Application Quantity Type Execution of poles Type of system neutral earthing Rated current Short circuit breaking current Short circuit withstand current and Duration Making current Operating duty Auto Reclosing (1 pole / 3 pole) First pole clear factor Breaker opening time Breaker closing time Line charging breaking and making Current Capacitor breaking current

kV kV Hz kA (rms) kA (Peak) kV (Peak) kV (rms) kV (Peak) oC mm mm mm mm mm kV (rms) Micro volts

Nos

A kA (rms) kA (rms) Sec kA (peak)

m.sec. m.sec. A A

Page 1 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO
2.17 2.18 2.19 2.20 2.21 2.22

ITEM
Small inductive current breaking Out of phase switching Anti-pumping Type of operating mechanism Operating mechanism to be suitable for Control voltage (AC / DC) a) Motor (AC / DC) b) Close/Trip coils/Circuit Bushing CT required No. of trip coils per pole Phase to phase spacing No. of auxiliary contacts Purchaser's earthing conductor (material and size) Whether mounting structure included in vendor's scope of supply Clamps and connectors a) By purchaser / vendor b) Take-off (Horiz /Vert / Other) c) Conductor material and size Height of connection/bus above ground level Environment (Normal/Polluted) (Salty/Dusty/Corrosive) Wind pressure Seismic coefficient Altitude above msl Gas evacuation and filling plant List of type tests to be carried out Cantilever strength ISOLATORS Application Quantity a) With earth switch b) Without earth switch Type Execution of poles Rated current Short circuit withstand current and Duration Making current A

UNIT

TO BE FILLED BY BIDDER

V V V Nos. mm mm x mm

2.23 2.24 2.25 2.26 2.27 2.28 2.29

2.30 2.31 2.32 2.33 2.34 2.35 2.36 2.37 3.0 3.1 3.2

mm

Kg/sq.m Mtr

kgs

Nos Nos

3.3 3.4 3.5 3.6 3.7

A kA (rms) Sec kA (Peak)

Page 2 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO
3.8

ITEM
a) Breaking capacity of line charging current b) Breaking capacity of magnetising current Short circuit making current of earthing switch Material of main contact Whether contacts are to be silver faced Operating mechanism Operating device (motor / manual) Main disconnector Earth switch Emergency operation Main disconnector Earth switch Support insulators Type of insulator (Pedestal / Solid / Polycone etc.) Nominal creepage distance Minimum strength Torsoinal Minimum cantilever strength Miscellaneous No. of NO & NC aux. Contacts for purchaser's use (main and earth switch) Pole discrepancy circuit required Purchaser's earthing conductor (material & size) Mounting structure included in vendor's scope of supply Phase to phase spacing of poles Height of connection/bus above ground level Clamps and connectors By purchaser/vendor Take off (Horz, Vert, etc) Conductor size and material Type of interlock Environment : salty / dusty / normal/ corrosive / polluted A A

UNIT

TO BE FILLED BY BIDDER

3.9 3.10 3.11 3.12 3.12.1 3.12.2 3.12.3 3.13 3.13.1 3.13.2 3.14 3.14.1 3.14.2 3.15 3.15.1 3.15.2 3.16 3.16.1

kA (Peak)

mm Nm kgs Nos

3.16.2 3.16.3 3.16.4 3.16.5 3.16.6 3.17 3.17.1 3.17.2 3.17.3 3.18.2 3.19

Yes / No mm x mm Yes / No mm mm

Page 3 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO
3.20 3.21 3.22 3.23 3.24 3.24.1 3.24.2 3.24.3 3.24.4 3.24.5 3.24.6 4.0 4.1 4.2 4.3 4.4

ITEM
Wind pressure Coefficient of seismic acceleration Altitude above M.S.L. List of type tests to be carried out Spares Support insulator column Operating rod insulator Drive motor Motor contactor of each type Fuses of each rating Spring CURRENT TRANSFORMER Type No. of cores Primary current ratio Accuracy class a) Tariff metering b) Metering c) Protection Secondary current Class of insulation Max. temp. rise of winding above ambient of 50C Cantilever strength of CT at the Terminal Radio interference voltage at 266kV (rms) CAPACITOR VOLTAGE TRANSFORMERS Quantity Type System neutral earthing Co-efficient of earthing No. of primary / secondary windings Primary / secondary winding voltage Class of insulation Maximum temp. rise of winding above ambient of 50C Application Accuracy class Rated burden

UNIT
Kg / Sq.m Mtr

TO BE FILLED BY BIDDER

Drive motor

4.5 4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 5.11

A
0

kgs Micro volts

Nos

Page 4 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO
5.12 5.13 5.14 5.15 5.16 5.17

ITEM
Rated power factor Rated voltage factor Rated capacitance Tolerance High frequency range High frequency capacitance (i) For entire carrier frequency range (ii) Equivalent series resistance over the entire carrier frequency range Stray capacitance and conductance of low voltage terminal (i) Stray capacitance of low voltage terminal over entire carrier frequency range (ii) Stray conductance of the low voltage terminal over entire carrier frequency range Radio interference voltage at 266kV (rms) Cantilever strength of CVT at the Terminal ELECTRO MAGNETIC VOLTAGE TRANSFORMERS (EMVTs) Type System neutral earthing No. of primary / secondary windings Primary / secondary winding voltage Class of insulation Maximum temp. rise of winding above ambient of 50C Accuracy class Cantilever strength of CVT at the Terminal Rated voltage factor Corona extinction voltage LIGHTNING ARRESTORS Quantity Installation System voltage Nominal Highest

UNIT

TO BE FILLED BY BIDDER

pF kHz

5.18

pF

mho

5.19 5.20 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 7.0 7.1 7.2 7.3

Micro volts kgs

kgs

kV

kV kV

Page 5 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO
7.4 7.5 7.6 7.7 7.8 7.9 7.10 7.11 7.12 7.13 7.13.1 7.13.2 7.13.3 7.13.4 7.13.5

ITEM
System Earthing Type of arrester Short circuit current at arrester Location Maximum duration of earth fault Co-efficient of earthing Temperature limits Seismic requirement Wind velocity Variation in frequency Rated values Rated arrester voltage / maximum continuous operating voltage Discharge class Maximum residual voltage at nominal discharge current Pressure relief class (short circuit capability) Long duration current Impulse withstand a) Discharge class b) Peak current & virtual duration of peak c) High current impulse Gapless arrester Continuous operating voltage Residual voltage corresponding to a) Steep current impulse b) Switching current impulse Arrestor Housing Material of housing Withstand Test Voltages a) One minute power frequency dry & wet (rms) b) 1.2 / 50 micro second Impulse withstand voltage(Peak) Minimum total creepage distance of whole insulator mm Suitable for live washing Level of pollution Additional requirements Minimum cantilever strength of

UNIT

TO BE FILLED BY BIDDER

kA Sec

kV

A/s kA (Peak) kV kV (Peak) kV (Peak)

7.14 7.14.1 7.14.2

7.15 7.15.1 7.15.2

7.15.3 7.15.4 715.5 7.16 7.16.1

mm Yes/ No

kgs

Page 6 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO ITEM
arrestor assembly Maximum radio interference voltage Type of mounting Whether insulating base required Accessories required a) Discharge counter b) Grading ring c) Clamps and connectors d) Leakage current meter e) Earth lead disconnector Purchaser conductor size a) Line side b) Earth side Visual discharge voltage Pressure relief valve INSULATOR Bus post insulator Type Cantilever strength Power frequency Puncture voltage Disc insulator Voltage class Type / No Creepage distance Minimum protected creepage Distance Electromechanical strength Power frequency Puncture voltage POWER LINE CARRIER COMMUNICATION (PLCC) LINE TRAPS Installation Type of earthing Rated current Minimum resistive component of impedance within carrier frequency blocking range Inductance of main coil Maximum tapping loss (Insertion loss with a line impedance of 400 Ohms) Blocking range Type of mounting Line trap arrester discharge current Band width

UNIT

TO BE FILLED BY BIDDER

7.16.2 7.16.3 7.16.4 7.16.5

7.16.6

7.16.7 8.0 8.1 8.1.1 8.1.2 8.1.3 8.2 8.2.1 8.2.2 8.2.3 8.2.4 8.2.5 8.2.6 9.0 9.1 9.1.1 9.1.2 9.1.3 9.1.4

Yes / No

kgs

mm mm

9.1.5 9.1.6 9.1.7 9.1.8 9.1.9 9.1.10

mH dB

kA kHz

Page 7 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO
9.1.11 9.1.12 9.1.13

ITEM
Tuning device required Type of tuning Variation in 50 Hz impedance per degree centigrade variation in ambient temperature Variation in resonant frequency band per degree centigrade variation in ambient temperature Winding material Radio interference voltage at 266kV (rms) Coupling Devices Composite loss within passband Return loss within passband Nominal Peak power P.E.P. at 50/100 Hz. Inductance of the drain coil at 50Hz Continuous / Short time current of Drain coil Rated / Short time current of Earth switch Rated voltage of surge arrestor Max. 100% impulse spark voltage (1.2/50 micro sec) of surge arrestor Rated discharge current (8/20 micro sec) of surge arrestor Type of construction of surge arrestor No. of H.F. terminals provided for carrier equipment connection Type of mounting / Degree of protection HIGH FREQUENCY CABLE Type of cable Withstand test voltage (RMS) between conductor and sheath Earthing details of H.F. cable POWER LINE CARRIER TERMINAL Operating Mode Type of modulation Carrier frequency range Band width per channel

UNIT

TO BE FILLED BY BIDDER

9.1.14

9.1.15 9.1.16 9.2 9.2.1 9.2.2 9.2.3 9.2.4 9.2.5 9.2.6 9.2.7 9.2.8 9.2.9 9.2.10 9.2.11 9.2.12 9.3 9.3.1 9.3.2 9.3.3 9.4 9.4.1 9.4.2 9.4.3 9.4.4

Micro volts

dB dB W

V V kA

kHz kHz

Page 8 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO
9.4.5 9.4.6 9.4.7 9.4.8 9.4.9

ITEM
Frequency separation between transmission(Tx) and reception (Rx) Frequency separation between adjacent channels HF power output Mode of transmission of guard Signal Maximum number of noise impulses pps in presence of which the equipment shall satisfactorily perform its duty SCADA System Architecture Overall system availability Redundancy requirements Sequence of events recorder required System response time Updating of dynamic data on display Key board command to field equipment execution time Key board command for display presentation execution Key board command to display presentation completion

UNIT
kHz kHz Watts Hz

TO BE FILLED BY BIDDER

10.0 10.1 10.2 10.3 10.4 10.5 10.5.1 10.5.2 10.5.3 10.5.4

Page 9 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

400kV SWITCHYARD
SI. NO ITEM UNIT TO BE FILLED BY BIDDER

Page 10 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET A1
AC UPS SYSTEM

SI. NO
1.1 Application

ITEM

CLIENTS SPECIFICATION
Instrumentation & controls, DCS, PLC, Servers/ PCs and system loads etc. As required

1.2

Power rating at load PF 0.8 lagging Quantity (nos.) Method of energy storage Type

1.3 1.4 1.5

As required Battery back -up Parallel Redundant with static by pass to regulated supply. Continuous Indoor, Natural ventilated / Forced cooling For 4 ms (fuse clearing) : App. 300% For 10 seconds : 150% For 10 Minutes : 125%

1.5 1.6 1.6

Duty Installation Over load capability

1.7

Over all efficiency including the Isolation Transformer and filters.

More 90 % at 50% Load. More 91 % at 100% Load

1.8 1.9 2.0 2.1

Ambient Temperature (0C) Relative Humidity ENCLOSURE Sheet steel thickness

500C Up to 95% Non-condensing

2mm, CRCA for doors and 1.6mm CRCA for side covers IP-54

2.2

Degree of protection as per IS13947 Painting

2.3

Page 1 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1
AC UPS SYSTEM

SI. NO
- Exterior

ITEM

CLIENTS SPECIFICATION
To match with adjacent panels

- Interior

Glossy white

2.4

Cable Entry

Bottom

2.5

Acoustic Noise level

60 65 dBA max up to 40 kVA 60 70 dBA max above 40 kVA Required.

2.6

Space heater, 240V, 1 Ph

3.0

UPS SYSTEM

3.1

Input

3.1.1

Supply voltage

415 V, 3 PH, 3 W, 50 Hz AC effectively earthed.

3.1.2

Supply Variation

(a) (b) (c)

Voltage Frequency Combined voltage + frequency

+ 10% -5% to +5% 10%

3.1.3 3.1.4 3.1.5 3.1.6 3.1.7

Power factor Input current THD Start up current limiting Start up Walk in Steady state current limiting

Minimum 0.8 at rated load 10% (Max) at all loading condition. Maximum 25% of full load current. 15 to 30 seconds to full load. a) For grid power 125% rated load

Page 2 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1
AC UPS SYSTEM

SI. NO

ITEM

CLIENTS SPECIFICATION
b) For emergency fed from engine generator 100% rated load plus 5 kVA

3.2 3.2.1 3.2.2 3.2.3 3.2.4

Output Output voltage Regulation ( With the specified input supply variation) Line drop compensation Transient response

3.2.5 3.2.6 3.2.7 3.2.8 3.2.9 3.2.10 3.2.11 3.2.12 3.2.13 3.2.14 3.3 3.3.1

Transient recovery Voltage wave from Range of adjustment of AC output voltage AC Harmonic content (THDVoltage) Phase displacement for three phase output Nominal frequency Frequency regulation (Without static by-pass source) Frequency regulation (With static by-pass source) Line sync. range Slew rate AC Standby supply Servo controlled voltage stabilizer (SCVS) (a) Rating (b) (c) Overload capacity Input voltage phase & frequency Percentage voltage regulation Spike busters / surge suppressors and input filters

230 V, Single phase AC, 2 Wire 2% for balanced load. 3% for 20% unbalanced load 10% for bypass or return from bypass 0 to 5% adjustable + 5% for loss or return of AC input power + 8% for 50% load step + 10% for bypass or return from bypass Return to steady state condition within 50 ms after disturbance. Sinusoidal. + 5% at rated load. 5% THD & 3% ( Individual harmonic ) 120010 for balanced load. 120030 for 20% unbalanced load. 50 Hz 0.1 % 2 Hz 0.5 Hz to 1 Hz, adjustable. Maximum 1Hz / Sec Required To match UPS continuous rating. 10 times rated current for 100 mS 415V + 10% ,3 ph 3 wire 50 HZ

(d)

+ 2%

(e)

Required.

Page 3 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1
AC UPS SYSTEM

SI. NO
3.3.2

ITEM
Isolation transformer (a) (b) Rating Input voltage phase & frequency

CLIENTS SPECIFICATION

To be decided by BIDDER 415V, 3ph, wire 50 Hz

3.4 4.0 4.1 4.2 4.3 4.5 4.6 5.0 5.1 5.2 5.3 6.0 6.1

Maintenance by pass switch BATTERY No. of 100% capacity batteries Type of battery cell DC link voltage Battery backup time Mounting Arrangement RECTIFIER Rectifier unit Parallel Operation Recharge time on battery boost charge. INVERTER Overload Capacity

Required.

2 Nos. (for each UPS system) Lead acid Plante type with Transparent SAN container / Nickel cadmium To be chosen by Bidder 60 Minutes Multi Tier

Three phase 12 Pulse. Required. 8 hrs

125% for 10 Min. 150% for 1 Min. 500% for 5 Milli seconds

6.2

Synchronising - Between inverters - Between inverters and standby supply Required. Required.

Page 4 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1
AC UPS SYSTEM

SI. NO
6.3 6.4 7.0 7.1 7.2 8.0 8.1 9.0 9.1 9.2 9.3 9.4 9.5 9.6

ITEM
Parallel Operation Synchronising Range STATIC SWITCH Maximum transfer time Short time current rating CIRCUIT BREAKER Type AC DISTRIBUTION BOARD Type Construction Busbars Incoming Outgoing Cable entry facility MCCB Required.

CLIENTS SPECIFICATION

50 2 Hz (adjustable)

5ms (1/4 cycle) 750% for 1.0 secs.

Draw out type for incomers & bus coupler and fixed for outgoing feeders. Modular, single/double front Aluminium. MCCB/ACB MCCB To be decided by BIDDER

Page 5 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1
AC UPS SYSTEM

SI. NO

ITEM

CLIENTS SPECIFICATION

Page 6 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A2
AC UPS SYSTEM

APPLICABLE STANDARDS 1. Basic climatic & mechanical IS 9000 BS IEC

durability tests for components for electronic and electrical equipment 2. Environmental tests for IS 9000 BS IEC

electronic & electrical equipment 3. Transformer and inductors (Power IS 6297 BS IEC

, Audio, Pulse & switching) for electronic equipment 4. 5. Printed wiring boards Environmental requirements for semiconductor devices and integrated circuits 6. Terminals for electronic IS 4007 BS IEC IS 7405 IS 6553 BS BS IEC IEC

equipment 7. HRC Catridge fuses IS 9224 BS 88 IEC60269-1

8. 9.

Indicating Instruments Degree of protection

IS 1248 IS 13947

BS 89 BS

IEC 51 IEC60947-1

10.

Semiconductor converters

IS

BS

IEC60146

11.

Semiconductor rectifier equipment code

IS 6619

BS

IEC

12. 13.

Tyristor converters Emergency std by power systems

IS 5082 IEEE 446

BS BS

IEC IEC

14.

Sealed lead acid cells

IEC60896-2

15.

Vented type Ni-Cd batteries

BS : 10918

IEC60623

16. (a)

Stationary cells of batteries lead Tabular plate BS : 1651 IEC60896-1

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A2
AC UPS SYSTEM

(b)

Plante plate

BS : 1652

IEC60896-1

17. IEEE recommended practice for sizing Ni-Cd batteries for stationary application. 18. 19. 1100V cables Surge withstand capability test in accordance with 20. Harmonic levels

IEEE 1115

IS 1554 IEC 60255-5 ANSI C-37-90-1

IEEE-519

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET B

AC UPS SYSTEM
SI. NO
1.0 1.1 1.2 1.3 1.4 1.5 1.6

ITEM
GENERAL PARTICULARS Name / Manufacturer Quantity Offered Type of UPS Output Rating at 0C Ambient Mains Input at load PF 0.8 Mains Tolerance Range Voltage Frequency Combined

UNIT

TO BE FILLED BY BIDDER

Nos.

kVA kVA

% % %

1.7 1.7.1

Environment Design Ambient Temperature Range For Operation For Storage


0 0

C C

1.7.2 1.7.3

Relative Humidity Installation Altitude range without derating Overall Efficiency ( Including Filter and Isolation Transformer) 25 % Load 50% Load 100% Load ENCLOSURE Sheet Thickness / Material Degree of protection as per IS 13947 Mode of Cooling Earth Bus material & size Cable Entry From Top / Bottom

% M

1.7.4

2.0 2.1 2.2 2.3 2.4 2.5

mm

2.6

Dimensions of Rectifier/ Inverter Panel Bypass Transformer Panel

LxDxH (mm)

Page 1 of 4

BEC POWER PRIVATE LIMITED


DATA SHEET B

AC UPS SYSTEM
SI. NO ITEM
Automatic Voltage stabiliser Panel Battery CB Panel System Output Assembly Panel AC Distribution Board 2.7 Mimic Diagram a) Graphic LCD display b) Mimic diagram with event indication LED dBA

UNIT

TO BE FILLED BY BIDDER

2.8 2.9

Accoustic Noise Level Colour of Paint Exterior Interior

2.10 3.0 3.1 3.2

Weight of each Panel RECTIFIER Ripple Harmonics at the point of connection to source at 50 % and 100% load. a) THD (Voltage) b) THD ( Current) Whether Soft Start Feature Incorporated Type of Rectifier Bridge Circuit Rectifier Efficiency (a) At Half Rated Load of the System At Full Rated Load of the System

kg

% rms

3.3 3.4 3.5

Yes / No

(b)

3.6 4.0 4.1 4.2 4.3 4.4

Input Power factor range INVERTER SYSTEM PWM / any other Type of Power Switching Devices Output Rating at 0.8 Pf Lag at 0C Input Nominal DC Voltage and Range kVA V DC

Page 2 of 4

BEC POWER PRIVATE LIMITED


DATA SHEET B

AC UPS SYSTEM
SI. NO
4.5 4.5.1 4.5.2 4.5.3 Output Voltage Voltage adjustment range Steady state output voltage regulation from no-load to full load for input line variations (a) (b) For balanced loads For 20% unbalanced loads in 3PH system +% V +% +%

ITEM

UNIT

TO BE FILLED BY BIDDER

4.5.4

Transient voltage regulation for 100% load application Transient recovery time to regulating band Frequency Nominal frequency Frequency deviation range Synchronising adjustable range Slew rate of synchronising adjustable range Overload Capability - for 10 min. - for 10 secs.

4.5.5

ms

4.6 4.6.1 4.6.2 4.6.3 4.6.4 4.7

Hz +% + Hz Hz/Se c. % full load % full load

5.0 5.1 5.2 5.3 5.4 5.5 6.0 6.1

BATTERY No. of 100% capacity batteries Battery backup time Type of battery cells No. of battery cells Battery cell / Rack dimensions STATIC SWITCH Rating of basic SCR used A Nos. LXWX H Nos. Min.

Page 3 of 4

BEC POWER PRIVATE LIMITED


DATA SHEET B

AC UPS SYSTEM
SI. NO
6.2 Load Transfer

ITEM

UNIT

TO BE FILLED BY BIDDER
Bidder to furnish a detailed write up on load transfer /. Switching arrangement

7.0 7.1 7.1.1 7.1.2 7.1.3

STAND-BY REGULATED SUPPLY Servo controlled Voltage Stabiliser with isolation transformer provided Input volts with percentage variation allowed Output volts Voltage regulation for line variation of + 10% and 0 to 100% load variation and PF 0.8 to 1.0 range Output voltage setting range Stabiliser continuous rating Isolation transformer on output side provided DISTRIBUTION BOARD Single front or double front Modular construction Type of outgoing feeder protection Total dimension of each complete switchgear L x W x D Yes / No V+% V +%

7.1.4 7.1.5 7.1.6 8.0 8.1 8.2 8.3 8.4

+% kVA Yes / No

SF / DF Yes / No

Page 4 of 4

BEC POWER PRIVATE LIMITED


DATA SHEET C
AC UPS SYSTEM

DATA TO BE FURNISHED BY BIDDER AFTER AWARD OF CONTRACT 1.0 1.1 1.2. 1.3 Drawings / Documents for Approval: Detailed schematic diagram of the UPS system showing all components Bill of Material indicating rating & type designation of components. General Arrangement drawing showing overall dimensions, foundation fixing details, location

of various devices, mimic diagram, list of protections, annunciation and meters, cable openings, etc. 1.4 2.0 2.1 2.2 Quality assurance plan. Drawings / Documents for information Type test reports on components chosen. Instruction manuals.

Page 1 of 1

BEC POWER PRIVATE LIMITED


DATA SHEET A2

CABLES & ITS ACCESSORIES

APPLICABLE CODES & STANDARDS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. IS 8130 Conductors for insulated electric cables and flexible cords. IS 5831 PVC insulation and sheath for electric cables. IS 6474 Polyethylene insulation and sheath for electric cables. ASTM D 2863.
IEC-60754 For testing of Fire survival cables.

NES 715. IS-10810 Part 53/61/62 Fire conditions. IEC 754-1 Acid Gas generation test. DIN 53387 UV Test. IS 1554 Part 2 PVC insulated heavy duty electric cables - for working voltages up to IS 1554 Part 1 PVC insulated heavy duty electric cables for working voltages up to and IS 7098 Part 2 Cross Linked Polyethylene Insulated PVC Sheathed Cables. IS 7098 Part 1 Cross Linked Polyethylene Insulated PVC sheathed cables. IEC 189 1 Low frequency cables and wires with PVC insulation and sheath General Tests IEC 189 2 Low frequency cables and wires with PVC insulation and sheath Cables in pairs, IS 694 PVC insulated cables for working voltages up to and including 1100V.

and including 11 kV. 11.

including 1100 V. 12.

For working voltages from 3.3kV up to and including 33kV. 13.

For working voltages up to and including 1100 V. 14.

and measuring methods. 15.

triples, quadruples and quintuples. 16.

Page 1 of 1

BEC POWER PRIVATE LIMITED


DATA SHEET B

CABLES & ITS ACCESSORIES


SI. NO
1.0 1.1

ITEM
Name of manufacturer Conductor No. core x Size Form- circular/segmented Effective cross sectional area sq. mm

UNIT

TO BE FILLED BY BIDDER

1.2

Whether cores identification numbers for cables with 5 cores and above to be provided Whether incremental running lengths are marked on cable Finished cable a) Diameter under armour in mm b) Diameter over armour in mm c) Overall diameter in mm Cable drums a) Whether cable drums confirm to IS : 10417 b) Length of cables in drum & tolerance c) Weight of cable drum without cables d) Weight of cable drum with cables e) Type of end sealing FRLS cables a) Critical oxygen index value at 250 deg C when tested for temperature index test as per ASTMD-2763 b) Total acid gas generation by weight when tested as per IEC 7541 in % c) Percentage of light transmission under fire for assessment of smoke generation when tested as per ASTM D 2743 d) Will the cables offered against this specification pass the flammability tests as per 1) Class F3 Swedish standard S5-

1.3

1.4

1.5

1.6

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET B

CABLES & ITS ACCESSORIES


SI. NO
424- 1475 2) IEC 332 1 3) IEC 331 - 1 1.7 maximum dielectric loss of cable per KM at normal voltage and frequency Short circuit capability for 1 Sec (HT & LT Power Cable) Maximum dielectric stress at core screen Max. overall diameter of cables Watt/km

ITEM

UNIT

TO BE FILLED BY BIDDER

1.8

kA rms

1.9

KV/cm

1.10

mm

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET C

CABLES & ITS ACCESSORIES

DATA TO BE FURNISHED BY THE BIDDER AFTER THE AWARD OF CONTRACT Following additional data for Information shall be furnished by the BIDDER for all cables. 1.0 (a) Continuous current rating of all cables In ground at soil temperature 30oC and soil thermal resistivity of 150oC cm/watt and depth of burial A A A, Hr

about a metre (b) (c) (d) (i) (ii) (iii) 2.0 2.1 In air at 40oC Overload capacity and duration De-rating Factors for: Soil temperature and thermal resistivity Ambient temperature Single core cables laid in trefoil circuits General Technical Data (Power cables) Equivalent star impedance per km of 3 Ph, circuit at power

frequency at maximum conductor temperature 2.2 2.3 voltage 2.4 2.5 Loss tangent at normal frequency and rated voltage Maximum dielectric loss of cable per km at normal Voltage Maximum electrostatic capacitance per core per km of cable Maximum charging current per conductor per km at nominal

Ohm F

and frequency 2.6 2.7 2.8 2.9 3.0 Short circuit capacity for 1 Sec. Short Circuit current capacity of armour Maximum dielectric stress at core screen Maximum overall dia. of cable

Watts/km KA (rms) kA for 1 sec kV/cm mm

Construction details including type of material used and thickness of each material for each

type of cable in a tabular form. 4.0 4.1 Instruction Manuals Two (2) number of copies of instruction manuals, descriptive bulletins etc. shall be furnished prior

to despatch of cables. The manual shall include amongst others, the following particulars. 4.1.1 4.1.2 4.1.3 General information. Principal technical data. Description of insulation, sheathing and screening. This should include data on resistance to

attack by chemicals, fungus, termites, rodents, water and ultra- violent radiation.

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET C

CABLES & ITS ACCESSORIES

4.1.4 5.0 5.1

Installation and termination instructions. Test Certificates Type/Routine test certificates for all types of cables included in the order and special tests on

FRLS/FS cables. 6.0 Any other information specifically called for by PURCHASER or ENGINEER

subsequent to order. 7.0 7.1 7.2 7.3 7.4 DATA FOR APPROVAL Technical particulars of all cables. Cross section of all cables. QAP for all cables All engineering drawings.

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A1

DC SYSTEM
SI. NO
A. 1 2 3 BATTERY Application Type of Battery Number required of battery banks Indoor (Power Plant) Lead Acid Plante / Ni-Cad To be finalised during detailed engineering To be finalised during detailed engineering 50 deg C High / Medium / Low Discharge Transparent SAN 220V / 48V 10%

ITEM

UNIT

CLIENTS SPECIFICATION

Number of cells in each bank in series (Approximate) Ambient conditions Type of Ni-cad battery Cell container (Ni-cad) D. C. System voltage Design margin to be considered Ampere hour capacity of battery at 27 Deg.C. 10 hours rate to give final cell voltage of 1.85 volts / cell for sealed lead acid battery. 10 hours rate to give final cell voltage of 1.14 volts / cell for Nickel cadmium battery. Momentary load / duration / limits of Voltages Emergency load / duration / limits of Voltages Continuous load / duration / limits of Voltages Minimum ambient for which load cycle is applicable AH

5 6 7 8 9 10

BIDDER to decide detailed engineering BIDDER to decide detailed engineering

during

AH

during

11

12

13

Amp Min Volts Amp Hrs Volts Amp Hrs Volts

During detailed engineering

During detailed engineering

During detailed engineering

14

As per project information

Page 1 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

DC SYSTEM
SI. NO
15

ITEM
Sketch No. (If any) showing Duty / Load Cycle on battery (load cycle diagram) Tentative size of cables to connect battery to external circuit Available area in battery room (LXB ) Layout drawing No. (If any)

UNIT

CLIENTS SPECIFICATION
During detailed engineering

16

Type Size mm x mm

During detailed engineering

17

During detailed engineering

18

19

Mounting Arrangement

Multi-tier

20

High discharge test required

Yes / No

If yes,

Amps :

Time :

End cell voltage :

21

Charging method proposed

Float / Trickle

B.

BATTERY CHARGER

1.0

General

1.1

Number required

To be finalised by BIDDER.

1.2

Type

Float cum Boost charger

1.3

DC System Voltage (Nominal)

220V & 48V

Page 2 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

DC SYSTEM
SI. NO
1.4

ITEM
DC System Earthing

UNIT

CLIENTS SPECIFICATION
Unearthed for 220V DC and positive earthed for 48V DC system 50 deg.

1.5

Ambient Design Temperature

Deg.C

2.0

DC BUS LOAD

2.1

Total continuous DC load

During detailed engineering

2.2

Short time loads (Additional to continuous loads) a) Testing of DC lights / Facia lamps b) Starting / Running current of Largest connected DC Motor A sec A/A sec

During detailed engineering

During detailed engineering

During detailed engineering

3.0

Ac system data

3.1

Supply

Volts

415V

Phase

3 Phase

Hz

Hz

50 Hz

3.2

a) Variation in supply Voltage

10%

b) Variation frequency 3.3

in

supply

-5% to +3%

Short Circuit level

kA

50kA (rms) for 1 Sec.

Page 3 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

DC SYSTEM
SI. NO
3.4 Type of earthing

ITEM

UNIT

CLIENTS SPECIFICATION
Solidly earthed

4.0

Performance

4.1

DC voltage setting adjustment for float charger Voltage stabilisation constant voltage regulator for

10% of nominal voltage

4.2

1% of set D.C voltage, with AC input variation as in 3.2 1%

4.3

Maximum permissible variation in DC voltage (no load to full load) D.C. voltage setting adjustment for boost charging D.C. current adjustment boost charging for

4.4

70% to 100% of max. Boost charging voltage. 30% to 100% of max. boost charging current 2%

4.5

4.6

4.7

Current stabilisation for constant current regulator for boost charger Minimum permissible power factor at rated continuous load Permissible ripple content at rated continuous load Hz

0.85

4.8

1% (maximum)

Hz

50 Hz

3.2

a) Variation in supply Voltage

10%

b) Variation frequency 3.3

in

supply

-5% to +3%

Short Circuit level

kA

50kA (rms) for 1 Sec.

3.4

Type of earthing

Solidly earthed

Page 4 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

DC SYSTEM
SI. NO
4.0 Performance

ITEM

UNIT

CLIENTS SPECIFICATION

4.1

DC voltage setting adjustment for float charger Voltage stabilisation constant voltage regulator for

10% of nominal voltage

4.2

1% of set D.C voltage, with AC input variation as in 3.2 1%

4.3

Maximum permissible variation in DC voltage (no load to full load) D.C. voltage setting adjustment for boost charging D.C. current adjustment boost charging for

4.4

70% to 100% of max. Boost charging voltage. 30% to 100% of max. boost charging current 2%

4.5

4.6

4.7

Current stabilisation for constant current regulator for boost charger Minimum permissible power factor at rated continuous load Permissible ripple content at rated continuous load Reference ambient temperature Maximum temperature of bus bars droppers and contacts at continuous current rating under site reference ambient temperature

0.85

4.8

1% (maximum)

1.4 1.5

50 degree 90C FOR NON SILVER PLATED JOINTS 105C FOR SILVER PLATED JOINTS

1.6

Short circuit current withstand for bus bars and droppers a) short time (1sec) at 220V DC kA 20kA (min)

b) Dynamic rating

kA (Peak)

Page 5 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

DC SYSTEM
SI. NO
1.7 2.0

ITEM
STANDARD APPLICABLE Switchgear requirements THICKNESS OF SHEET STEEL (in mm) constructional

UNIT

CLIENTS SPECIFICATION
As per data sheet D18.2

2.1

COLD ROLLED

FRAME 2.5

DOORS 1.6

COVERS 1.6

HOT ROLLED

FRAME -

DOORS 2.0

DOORS 2.0

2.2 2.3

Degree of protection Colour finish shade as per IS:5 INTERIOR EXTERIOR

IP 52 GLOSSY WHITE To match with other nearby Panels. GS 65X10mm

2.4

Earthing bus

MATERIAL SIZE.

Page 6 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A2

DC SYSTEM

APPLICABLE STANDARDS A. 1. 2. 3. 4. SEALED LEAD ACID BATTERY Sealed Lead Acid Cells Water for Storage Battery Sulphuric Acid Synthetic separator for Lead Acid IS:1069 IS: 266 IS: 6071 BS:4974 BS:3031 IEC:60896-2

Batteries 5. 6. Ni-Cad 7. 8. B. 1. Vented type Ni-Cad batteries IEEE recommended practice for sizing batteries for stationary applications UL: 924 UL: 1778 IS:10918 IEC:60623 IEEE: 1115

Containers & Vent Plugs Battery Enclosures BATTERY CHARGER Basic climatic and mechanical

IS 9000

BS

IEC

durability tests for Components for electronic and electrical equipment. 2. Environmental tests for Electronic and IS 9000 BS IEC

electrical equipment. 3. Metal clad base material for printed IS 5921 BS IEC 60249 circuits for

use in electronic and telecommunication equipment. 4. audio, 5. 6. Transformers and inductors (power, pulse and switching) IS 6297 BS IEC

for electronic equipment. IS 7405 For IS 6553 BS BS IEC 60326 IEC

Printed wiring boards Environmental requirements

semiconductor devices and integrated circuits. 7. 8. Terminals for electronic equipment. Factory built assemblies of switchgear IS 4007 IS 8623 BS BS 5486 IEC IEC 60439 and control

gear For voltages up to and including 1000V A.C. and 1200 V D.C. 9. 10. 11. Air break switches Miniature circuit breakers HRC cartridge fuses IS 13947 IS 8828 IS 13703 BS EN BS 3871 BS 88 IEC 60947-3 IEC 60898 IEC 60269

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A2

DC SYSTEM

12. 13. 14. 15. 16.

Contactors Control switches / push buttons Indicating instruments Degree of protection Climate proofing of electrical

IS 13947 IS 6875 IS 1248 IS 2147 IS

BS 775 BS BS 89 BS BS

IEC 60947 IEC IEC 60051 IEC 60947 IEC

equipment 17. Code of practice for phosphating iron IS 6005 BS 3189 IEC

and steel 18. 19. Semi-conductors converters Semiconductors rectifier equipment IS IS 6619 BS BS IEC 60146 IEC

safety code 20. IS 3715 C. 1. 2. 3. 60898 4. Marking and identification of IS:11353 BS:159 conductors and apparatus DC SWITCHGEAR Switchgear general requirements Indicating instruments Miniature circuit breakers IS:13947 IS:1248 IS:8828 BS:5486 BS:89 BS: IEC: 60947 IEC: 60051 Thyristor converters IS3700 BS IEC 60747

terminals 5. Starters IS: 13947 BS: EN IEC: 60947-

4-1 TOP 4. 6. 4-1 7. 1to 4. 8. 9. 10. 11. NOTES Equipment, accessories, component IS: BS IEC: Air break switches Degree of protection Circuit breakers Control switches / push buttons IS:13947 IS: 13947 IS:13947 IS:6875 BS: BS: BS:EN BS: IEC:60947-3 IEC: 60529 IEC:60947-2 IEC: HRC cartridge fuse links up to 650v IS: 9224 BS: 88 IEC-60269Contactors IS:13947 BS:EN IEC: 60947-

parts, raw materials and tests shall be in general conform to

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
A.

ITEM
LEAD ACID PLANTE / Ni-cad BATTERY a) Manufacturers Name b) Type of battery

UNIT

TO BE FILLED BY BIDDER

1.0

2.0

Standards to which battery is manufactured Rated Capacity At 27 Deg.C Capacity at minimum ambient temp. and the formula used (enclose temperature de-rating curves / data) Capacity at high discharge rate at 27 Deg. C, at different end cell voltages (enclose capacity rating factor curves / data). 5 minutes 30 minutes 45 minutes 1 hour 2 hour 3 hour 4 hour 5 hour 6 hour 7 hour Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah At 10 hour rate

3.0 3.1 3.2

3.3

3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.3.9 3.3.10

Page 1 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
3.3.11 3.3.12 3.3.13 3.4 3.5 4.0 4.1 4.2 4.3 8 hour 9 hour 10 hour Maximum Momentary current 1 minute Expected life of battery Recommended charging rate Float charging Voltage / Current Trickle charging Voltage / Current Rapid Boost charging Voltage / Current duration Normal Boost charging voltage/Current /duration Equalising charge a) Voltage / current b) Duration c) Interval between successive equalising charges d) Criteria to initiate the same 5.0 6.0 6.1 7.1 7.2 8.1 Expected fault level at bus due to battery Internal resistance of each cell (fully charged) Total resistance of battery including resistance of inter-cell connectors AH efficiency at rated load Watt hour efficiency Type of positive plate V/A V/A V / A /Hr V / A /Hr

ITEM
Ah Ah Ah

UNIT

TO BE FILLED BY BIDDER

Amps Years

4.4

V/A Hrs Days

kVA Ohms Ohms % %

Page 2 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
8.2 8.3

ITEM
No. of positive plates / cell No. of cells per battery, with recommended float voltage and dc system voltage tolerances as specified Whether the battery can meet the duty cycle requirements with ageing factor etc., as specified (enclose battery sizing calculations) INTER CELL / INTER ROW CONNECTORS a) Type (lead, lead plated copper) b) Thickness of lead plating (shall be not less than 0.025 mm as measured in accordance with IS: 6848). Whether acid level indicators, included (applicable for opaque containers) Type of containers Type of cell Overall dimensions Each cell L x W x H Whether battery room size adequate Weight Each cell Complete Whether explosion vents are offered Ventilation requirements Cubic content of battery room Exhaust fans m3 kg kg mm

UNIT

TO BE FILLED BY BIDDER

8.4

8.5

8.6 8.7 8.8 9.0 9.1 9.2 10.0 10.1 10.2 11.0 12.0 12.1 12.2

Yes / No

Yes / No.

Page 3 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
a) Number b) Rating of each 13.0 Whether there would be any harmful effect on the life of battery if discharged as per load cycle specified above, after being maintained in float charging condition. List of spares / accessories enclosed List of deviations enclosed BATTERY CHARGER Manufacturers Name Type Ratings Input voltage Output voltage a) Nominal b) Setting range 3.3 3.4 4.0 4.1 Rated output Capability of starting the DC motor with other connected load Type of AVR / controller Voltage regulation with AVR, when supply voltage fluctuation is 10%, frequency fluctuation is -5% to +3% and load variation is 0% to 100% Voltage regulation with manual controller. Indicate the protective devices provided. kW kW V AC Phase V DC FLOAT CH. BOOST CH. kW Yes / No

ITEM

UNIT

TO BE FILLED BY BIDDER

14.0 15.0 B. 1.0 2.0 3.0 3.1 3.2

Yes / No Yes / No

4.2 4.3

Page 4 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
5.0 6.0

ITEM
Type of voltage/current control and adjustment provided for boost charger. Type of range of tap changing gear (off load/ on load) if provided on main transformer. Guaranteed efficiency. At 50% load At rated load Power factor. At 50% load At rated load Maximum permissible temperature rise over ambient. Rectifier transformer Rectifier cells. Smoothing reactor. Class of insulation. Rectifier transformer. Smoothing reactor. Type of rectifier cell. Method of cooling. Rectifier cells. Transformer. Whether rectifier and transformer are mounted in the same cubicle or in different cubicles. Ripple content at rated load. % %

UNIT

TO BE FILLED BY BIDDER

7.0 7.1 7.2 8.0 8.1 8.2 9.0 9.1 9.2 9.3 10.0 10.1 10.2 11.0 12.0 12.1 12.2 13.0

C C C

14.0

Page 5 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
14.1 14.2 15.0 15.1 15.2 15.3 16.0 16.1 16.2 16.3 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 C. 1.0 1.1 With battery. Without battery. Rectifier and Blocking Diodes Make and Type. RMS current rating. Peak inverse voltage continuous. Silicon controlled Rectifiers (SCR) Make and Type. RMS current rating. Peak inverse voltage continuous. Fault indicating lamps and necessary circuit provided as required. Potential free contacts for each fault provided. Common alarm contact provided. Overall dimensions of charger (L x W x H) Degree of Protection. Weight. List of spares / accessories enclosed. List of deviations brought out separately. DC SWITCHGEAR GENERAL PARTICULARS Switchgear designation A V YES/NO YES/NO YES/NO mm V

ITEM
% %

UNIT

TO BE FILLED BY BIDDER

kg. YES/NO YES/NO

Page 6 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
1.2 1.3 1.4 1.5 1.6 1.7

ITEM
Single front or double front. Modular construction. Fully draw-out /semi-draw-out /fixed Dimension of the switchgear LxWxD Width of each vertical section. Sheet metal thickness Frames Door Rear Covers Side and top covers Panel partitions. mm mm mm mm mm

UNIT
SF/DF Yes/No FD/SD/F mm LWD mm

TO BE FILLED BY BIDDER

1.8 1.9 1.10 1.11

Has the sheet metal been treated in accordance with the specification Bus bar continuous rating. Short time rating (1-sec.) Clearance in air i) Between poles. ii) Between pole and earth for unearthed system. Degree of protection provided by the enclosure (as per IS:13947 or equivalent) Earth bus bar size. CIRCUIT BREAKER/MCCB/MCB Make

Yes/No A-DC kA-DC

mm

1.12

1.13 2.0 2.1

mm2

Page 7 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 Type designation Circuit breaker type (Air break and/or MCCB) Service Voltage. No. of poles and breaks per pole. Rated operating duty Rated current. De-rating factor for operation under site conditions Rating breaking current at V DC A

ITEM

UNIT

TO BE FILLED BY BIDDER

V-DC

kA DC

For L/R = _

ms.

2.10 2.11 2.12 2.13

Rated short time current for (1 sec.) Rated making current Operating mechanism Limits of voltage for satisfactory operation of the following devices as a % normal voltage. i) Operating mechanism. ii) Closing coil. iii) Trip oil. Power required for closing at i) Normal voltage. ii) 80% normal voltage. Power required for tripping at i) Normal voltage. ii) 50% of normal voltage Spring charging motors details : i) Rating. ii) Rated voltage. Number of opening the circuit is capable of performing without inspection, replacement of contacts or other parts at 110% rated breaking current.

kA DC kA DC

% % %

2.14

WW

2.15

WW

2.16

kW V

2.17

Page 8 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
2.18 2.19 2.20 2.21 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8

ITEM
Overload release settings. Short circuit release settings and time delay features provided. Under voltage release settings. Electrical and mechanical anti-pumping features been provided or not. BUS BARS Material of bus bars Size Type of insulation. Whether bus bars have been taped. Maximum continuous current rating. Temperature rise over the specified ambient when carrying rated current. Spacing between bus bars. Clearance in air i) between poles. ii) between poles and earth. Maximum fault withstand current rating (peak) Maximum fault withstand current momentary rating (peak) Dielectric strength. One min. power frequency withstand voltage. AIR BRAEAK SWITHCHES Make Type

UNIT

TO BE FILLED BY BIDDER

Yes/No

Yes/No

mm2

Yes/No A DC C mm

3.9 3.10 3.11 3.12 4.0 4.1 4.2

mm mm kA DC kA DC Volts AD RMS kV RMS

Page 9 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
4.3 4.4 5.0 5.1 5.2 5.3 5.4 Rated Current. De-rating factor for use under site ambient conditions. D.C. CONTACTORS Make Rated duty Rated utilisation category Limits of operation. i) Supply voltage variation. ii) Dropout voltage No. of aux. contacts. i) Normally open. ii) Normally closed. FUSES Make Type Rated current Whether fuse is mounted in an insulated carrier. Category of duty as per IS:9224 Rupturing capacity (prospective current) Maximum let through current for 1 sec. INSTANTANEOUS OVER CURRENT RELAY Application Make Type designation. A Yes/No % %

ITEM
A

UNIT

TO BE FILLED BY BIDDER

5.5

6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 7.0 7.1 7.2 7.3

kA kA

Page 10 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
7.4 7.5 8.0 8.1 8.2 8.3 8.4 8.5 8.6 9.0 9.1 9.2 9.3 9.4 10.0 10.1 10.2 10.3 10.4 10.5 10.6

ITEM
Current coil burden. Setting range. INVERSE TIME OVER CURRENT RELAY. Application Make Type Current coil burden Current setting range. Time setting range. UNDER VOLTAGE RELAY Make Type Burden Setting range AUXILIARY RELAYS Make Type. Coil burden Operating time. Time delay range (for timer). Resetting features VA VA V VA A VA A

UNIT

TO BE FILLED BY BIDDER

Sec.

Sec. Sec.

Page 11 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
10.7

ITEM
No. of contacts i) Normally open ii) Normally closed. Contact rating. Whether operation indicator is provided. CONTROL/SELECTOR SWITCH Make Type designation. Spring return or stay put. Type of handle. VOLTMETER Make Type Accuracy class. AMMETER Make Type Accuracy class. WATT METER Make Type Accuracy class INDICATING LAMPS

UNIT

TO BE FILLED BY BIDDER

10.8 10.9 11.0 11.1 11.2 11.3 11.4 12.0 12.1 12.2 12.3 13.0 13.1 13.2 13.3 14.0 14.1 14.2 14.3 15.0

A Yes/No

Page 12 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET B

DC SYSTEM
SI. NO
15.1 15.2 16.0 16.1 16.2 17.0 17.1 17.2 18.0 18.1 Make Type PUSH BUTTONS Make Type SPACE HEATER Make Type WIRING & THERMAL BLOCKS Minimum size of conductor for i) Power wiring. ii) Control wiring. mm2 mm2

ITEM

UNIT

TO BE FILLED BY BIDDER

Page 13 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET C

DC SYSTEM

INFORMATION TO BE FURNISHED BY BIDDER AFTER AWARD OF CONTRACT A. 1.0 1.1 BATTERY FOR REVIEW/APPROVAL Layout drawing showing the battery room dimensions, no. of rows, overall dimensions of

each row, cable termination location with dimension, no. of air changes recommended, cross sectional view etc. 1.2 2.0 2.1 2.2 (a) Copies of Test Reports FOR INFORMATION Drawing showing constructional details of cell. Battery characteristics : Curve showing cell volts Vs. time of different discharge rates. (b) AH capacity Vs. years of service. Curve showing cell volts Vs.

time at different charging currents. (c) 2.3 B. 1.0 1.1

Copies of instruction manuals to cover installation, commissioning, operation and maintenance. BATTERY CHARGER FOR REVIEW/APPROVAL Detailed schematic diagram of charger scheme including voltage / current regulator

electronic controller, under voltage / overvoltage / overload / earth fault relays, annunciation scheme, etc. 1.2 1.3 Bill of materials. General arrangement drawing showing main dimensions, type of mounting, location of

various devices, weight, mounting arrangement and floor opening,etc. 1.4 2.0 2.1 2.2 C. 1.0 1.1 Test reports. FOR INFORMATION Instruction manuals. Drawing showing constructional details DC SWITCHGEAR FOR REVIEW/APPROVAL Complete assembly drawings of the switchgear showing plan, elevation, typical sectional views of

equipment mounted in each module and location of terminal blocks for wiring connections, cable entry slots, etc. 1.3 General arrangement drawing of each switchgear showing the equipment mounted on

each module. 1.4 Complete wiring diagrams including terminal wiring designations of each module including all

spare terminals and inter-modular and inter panel wiring.

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET C

DC SYSTEM

1.5

Schematic control diagrams for breaker control, interlocks, relays, instruments and space

heaters etc. 1.6 Circuit breaker release characteristics for each release. Protective relay characteristics

for each type of relay including thermal overload relay. 1.7 1.8 1.9 Fuse characteristic curves for each type and rating of fuse. Contact development diagram of electrical switches. Itemised bill of material for each module, listing all devices mounted indicating

MANUFACTURERs type, rating quantity, etc. 1.10 Test certificates in respect of major component equipment and complete switchgear

assemblies. 2.0 2.1 2.2 FOR INFORMATION Operation and maintenance manual for individual equipment and for complete switchgear. Reproducible tracing films (RTFs) of all finally approved general arrangement drawings,

schematics and wiring diagrams.

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A2

ELECTRICAL EQUIPMENT INSTALLATION WORK


APPLICABLE CODES & STANDARDS 1.0 CABLING SYSTEM IS:1646 IS:5216 electrical work IS:3837 IS:2667 IS:3419 IS:4649 IS:800

Code of practice for fire safety of bldgs. Guide for safety procedures and practices in Accessories for rigid steel conduits Fittings for rigid steel conduits Fittings for rigid non-metallic conduits Adaptors for flexible steel conduits Code of practice for structural steel 2.0 EARTHING & LIGHTNING PROTECTION

Code of practice for earthing Protection of building and allied structures against lighting Code of practice for electrical installations Hot dip galvanising on iron and steel Codes for welding Galvanised round steel wire Copper conductors Methods Of Testing Uniformity Of Coating Of Zinc Coated Articles 3.0 EQUIPMENT INSTALLATION

IS:3043, IEEE:80 IS:2309, BS:6651

IS:732 IS:2629, IS:816 IS:3975 IS:12444, BS:6360 IS:2633 BS:729

Installation and maintenance of transformers Code of practice for maintenance and supervision of, mineral insulating oil in equipment Installation and maintenance of switchgear Installation and maintenance of induction motors Guide for safety procedures and practices in electrical work Hot dip galvanising Codes for welding Electrical wiring installations voltages >650v Fire safety of buildings (general) -

IS:10028 IS:1866, BS:5730 IEC:422

IS:10118 IS:900 IS:5216

IS:2629 IS:816 IS:732

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A2

ELECTRICAL EQUIPMENT INSTALLATION WORK


electrical installations Danger plates New insulating oils IS:1646 IS:2551 IS:335

Indian electricity act 1910, (as amended) Electricity supply act 1948, (as amended) Indian electricity rules 1956 (as amended)

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET B

ELECTRICAL EQUIPMENT INSTALLATION WORK


SI. NO ITEM TO BE FILLED BY BIDDER

DATA TO BE SUBMITTED AFTER THE AWARD OF CONTARCT.

Lightning Protection( BIDDER to furnish following data for every structure and building) Whether lightning conductors have been envisaged for the lightning protection. Angle of protection. Indicate nearby buildings protected.. Number of electrodes provided. Earthing resistance value Size of down conductors Standard followed Deviations if any on technical specification

1 2 3 4 5 6 7 8

II 1 2 3 4 5 6 7

Earthing Material and size of earth strip for various places Gap between earth mat conductorslengthwise, breadth wise Size of main outer strip Galvanising content on GI strips Value of earthing resistance (proposed to be achieved) Standard to be followed for galvanising a)Type of electrodes b)Size of material

8 9

Construction of earthing pit as per IS Riser Connections Material

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET B

ELECTRICAL EQUIPMENT INSTALLATION WORK


SI. NO ITEM TO BE FILLED BY BIDDER

DATA TO BE SUBMITTED AFTER THE AWARD OF CONTARCT.


2) Size 10 Treated earth pit 1)Material 2)Size 3)Length of each electrode 4)Total no. of pits Deviations if any on technical specification

11

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET C

ELECTRICAL EQUIPMENT INSTALLATION WORK


DATA TO BE SUBMITTED AFTER THE AWARD OF CONTARCT. 1. 2. 3. 4. 5. 6. 7. Earthing & lightning protection calculation. Earthing & lightning protection layout. Cable tray Layouts. LPB layouts. Electrical Equipment layouts (Switchgear room layouts). Transformer yard layout. General arrangement drawings and data sheet of each equipment covered under this

specification. 8. 9. 10. 11. Lighting schematics and Lighting Layout drawings along with calculations. Cable tray loading details. Cable schedules and its interconnection schedules. Type test reports of the Electrical items supplied under this specification.

Page 1 of 1

BEC POWER PRIVATE LIMITED


DATA SHEET A1

ELEVATOR
SI. NO
1.0 Lift category

ITEM

UNIT

CLIENTS SPECIFICATION
Passenger elevator for Service building. Passenger cum goods elevator for Boiler and TG Building.

1.1

Quantity a) Service Building b) TG Building c) Boiler Rated load

Nos 1 1 1 Kg 2,000

1.2

1.3

Rated Speed

m/sec

0.75

1.4

Total rise

As required ( Indicated during detail engineering )

1.5

Number of floors served

All floors and platforms

1.6

Lift well dimension

mm x mm

As per IS

1.7

Levelling zone Levelling device

By BIDDER Two way maintaining.

automatic

1.8

No of door in car

One, Centre opening sliding

1.9

Type of control

By BIDDER

1.10

Operation

Automatic without attendant.

Page 1 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A1

ELEVATOR
SI. NO
1.11

ITEM
Automatic operation type

UNIT

CLIENTS SPECIFICATION
Selective Collective

1.12

Operating devices

As listed in write up

1.13 1.14 1.15

Indicating devices Material of the list rope Miscellaneous devices a) Car lighting b) Car ventilation fan with manual and automatic switch through selector c) Decor inside the car d) Enclosure for electrical equipment located outside the M/C room e) Emergency exit f) Provision for opening the landing door in case of emergency g) Emergency device 220V DC operated. h) Provision to prohibit accidental closing of door on person/object at the lift entrance Car accessories

As listed in write up Steel

a) b)

Yes Yes

c) d) e) f) g) h)

Yes Dust & (IP 55) Yes Yes Yes Yes

water

tight

1.16

Following accessories to be provided in addition to those mentioned in the write up a) Hand rail b) PVC flooring c) Emergency DC light

1.17

Special requirements and notes a) Inching control b) Stop blocked in floors c) Fire extinguisher d) Facia plates

a) Yes b) Yes c) Yes d) Yes

Page 2 of 2

BEC POWER PRIVATE LIMITED


DATA SHEET A2

ELEVATOR

SL. NO. 1

APPLICABLE STANDARDS CODE OF PRACTICE FOR INSTALLATION, OPERATION AND MAINTENANCE OF ELECTRIC PASSENGER AND GOODS LIFTS IS 1860 IS 14665 (Part 2) : 2000 BS IEC

OUTLINE DIMENSIONS ELECTRIC LIFTS.

FOR

IS 3534

BS 2655

IEC

SPECIFICATION FOR ELECTRIC PASSENGER AND GOODS LIFTS LIFT CABLES SPECIFICATION FOR LIFT DOOR LOCKING DEVICES AND CONTACTS SPECIFICATION FOR BUFFERS FOR ELECTRICAL LIFTS BRAKES FOR ELECTRICAL PASSENGER AND GOODS LIFTS

IS 4666

IEC

4 5

IS 4289 IS 7759

BS 6977

IEC IEC

IS-9803

IEC

IS 10913

IEC

Page 1 of 1

BEC POWER PRIVATE LIMITED


DATA SHEET B

ELEVATOR
SI. NO
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Make Type - Standards Capacity Rated speed Contract speed Car dimensions (L X B X H) Overall weight Total Rise No. of Landings & Locations Lift control type Operation Levelling device Type of car and landing doors Size of doors Door Operator Vision panel in doors Operating devices in car Operating devices in landings Indicating devices in car Indicating devices in landings Details of car lighting mm x mm Kg M/sec. M/sec mm Kg. M

ITEM

UNIT

TO BE FILLED BY BIDDER

Page 1 of 3

BEC POWER PRIVATE LIMITED


DATA SHEET B

ELEVATOR
SI. NO
22 23 24 25 26 27 27.1 27.2 27.3 27.4 27.5 27.6 27.7 28.0 28.1 28.2 28.3 28.4 28.5 28.6 29

ITEM
Details of car ventilation Details of Painting Pit height from bottom landing Clearance between top landing and Machine Room Machine Room Dimensions (L X B X H) Machine Type Enclosure & Ventilation Rated voltage Winding insulation class Output Torque/speed characteristics enclosed Temperature rise at full load Rope Material No. & diameter of strands Cross sectional area Outside diameter Ultimate strength Working stress Enclosure equipment for electrical V mm mm mm

UNIT

TO BE FILLED BY BIDDER

Yes/No. C

mm2 mm Kg Kg/cm2

Page 2 of 3

BEC POWER PRIVATE LIMITED


DATA SHEET B

ELEVATOR
SI. NO
30 30.1 30.2 31 32 33 34 35 36.0 36.1 36.2 36.3 36.4 36.5

ITEM
Sheaves and Pulleys Material for construction Dia and grooves Type of brake Hand cranking device Safety type Governor type Counterweight Cables Standard Size Cores No. of cables No. of cable groups Kg.

UNIT

TO BE FILLED BY BIDDER

mm2

Page 3 of 3

BEC POWER PRIVATE LIMITED


DATA SHEET c

ELEVATOR

DATA TO BE FURNISHED BY BIDDER AFTER AWARD OF CONTRACT 1. 1.1 2. Final dimensions of the lift car & machine room. Any modification required. Largest Package for Transport and storage at site. : The schedule of submission of

Dimensions : Weight 3.

DRAWINGS : BIDDER shall furnish the following drawings.

drawings shall be furnished: 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Dimensioned Drawings of Lift and accessories. Layout of machine room. General arrangement drawing of control panels. Wiring diagram and schematic diagrams of control panels. Braking load on guides. Fixing detail of side guides. Reaction of buffers or lift pit.

Page 1 of 1

BEC POWER PRIVATE LIMITED


DATA SHEET A1

GENERATOR CIRCUIT BREAKER


SI. NO
1.0 1.1 1.2 1.3 1.4

GENERAL INFORMATION
GENERAL INFORMATION QUANTITY LOCATION INSULATION AND BREAKING MEDIUM COOLING METHOD. IF FORCE COOLED, REDUNDANT EQPT. IS TO BE PROVIDED.

CLIENTS SPECIFICATION

1 Nos. INDOOR SF6 BY BIDDER

1.5

DEGREE OF PROTN. OF GCB ENCLOSURE

IP65

1.6

DEGREE OF PROTN. OF LOCAL CONTROL PANEL

IP65

1.7 1.8 1.8.1

AUXILIARY VOLTAGE POWER CONNECTION TYPE

220V DC, 415V 3PH AC 50Hz

ISOLATED PHASE BUSDUCT (IPBD) ENCLOSURE THROUGH FLANGES AND BUSBAR THROUGH FLEXIBLE CONNECTIONS 50C 105C 80C AS PER RELEVANT IEEE /IEC STANDARDS AS PER RELEVANT IEEE STANDARDS

1.8.2

INTERFACE WITH IPBD

1.9 1.10 1.11 1.12 1.13 2.0

MAX. AMBIENT TEMP. MAX. TEMP. OF BUSBAR CONNECTIONS CONSIDERING SILVER PLATED JOINTS MAX. TEMP. OF ENCLOSURE CONNECTIONS NOISE LEVEL EMC GENERATOR CIRCUIT BREAKER

Page 1 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

GENERATOR CIRCUIT BREAKER


SI. NO
2.1

GENERAL INFORMATION
RATED VOLATGE

CLIENTS SPECIFICATION
21kV ( Shall be decided based on the generator rated voltage during detailed engineering ) 24kV 50 Hz 24000A ( Shall be decided based on the generator rated voltage during detailed engineering )

2.2 2.3 2.4

RATED MAXIMUM VOLTAGE RATED FREQUENCY RATED CONTINUOUS CURRENT

2.5 2.5.1

RATED INSULATION LEVEL ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE TO EARTH & ACROSS CIRCUIT BREAKER/SWITCH CONTACTS LIGHTNING IMPULSE WITHSTAND VOLTAGE TO EARTH & ACROSS CIRCUIT BREAKER/SWITCH CONTACTS ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE FOR AUXILIARY AND CONTROL CIRCUITS NUMBER OF STORED CLOSE/OPEN OPERATIONS SHORT CIRCUIT CAPABILITY RATED PEAK WITHSTAND CURRENT (kA PEAK) RATED SHORT TIME WITHSTAND CURRENT (kA RMS, FOR 3 SEC) OUT-OF-PHASE CURRENT SWITCHING CAPABILITY INTERRUPTING TIME (TRIPPING COMMAND TILL ARC EXTINCTION) AT MINIMUM OPERATING PRESSURE OF THE MECHANISM OPENING TIME (TRIPPING COMMAND TILL CONTACT SEPARATION) CLOSING TIME (CLOSING COMMAND TILL CONTACT TOUCH) SIMULTANEITY OF POLES (CLOSING OR OPENING) TRANSIENT RECOVERY VOLTAGE (FOR GENERATOR SOURCE FAULTS) BY BIDDER BY BIDDER BY BIDDER NOT MORE THAN 60 ms 40 ms (BIDDER TO INDICATE TOLERANCE) BY BIDDER <5 m sec 2.2 kV/micro sec 80 kV (RMS)

2.5.2

150 kV (PEAK)

2.5.3

2 kV (RMS)

2.6 2.7 2.7.4 2.7.5 2.7.6 2.8

NOT LESS THAN 2

2.9 2.10 2.11 2.12

Page 2 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

GENERATOR CIRCUIT BREAKER


SI. NO
2.13 2.14 2.15 2.15.1 2.15.2 2.16 2.17 3.0 3.1 3.2 3.3 3.4 3.5 3.5.1

GENERAL INFORMATION
TRANSIENT RECOVERY VOLTAGE (FOR SYSTEM SOURCE FAULTS) RATED DUTY CYCLE SF6 GAS NORMAL PRESSURE LEAKAGE RATE OPERATING MECHANISM OPENING & CLOSING COIL VOLTAGE DISCONNECTING SWITCH DATA RATED VOLTAGE RATED MAXIMUM VOLTAGE RATED FREQUENCY RATED CONTINUOUS CURRENT RATED INSULATION LEVEL ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE ACROSS ISOLATING DISTANCE OF DISCONNECTOR LIGHTNING IMPLUSE WITHSTAND VOLTAGE ACROSS ISOLATING DISTANCE OF DISCONNECTOR RATED SHORT TIME WITHSTAND CURRENT (kA FOR 3 SEC) RATED PEAK WITHSTAND CURRENT (kA PEAK) OPERATING TIME (SEC) OPERATING MECHANISM 21kV 24kV 50Hz

CLIENTS SPECIFICATION
5.5 kV/micro sec CO-30 MIN-CO

BY BIDDER BY BIDDER SPRING OPERATED 220V DC

24000A

BY BIDDER

3.5.2

BY BIDDER

3.6 3.7 3.8 3.9

BY BIDDER BY BIDDER BY BIDDER ELECTRICAL MOTOR OPERATED

Page 3 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

GENERATOR CIRCUIT BREAKER


SI. NO
4.0 4.1 4.2 4.3 4.4 4.4.1 4.4.2 4.5 4.6 4.7 4.8 5.0 5.1 5.2 5.3 5.4 5.5 5.5.1 5.5.2

GENERAL INFORMATION
EARTHING SWITCH RATED VOLTAGE RATED MAXIMUM VOLTAGE RATED FREQUENCY RATED INSULATION LEVEL POWER FREQUENCY WITHSTAND VOLTAGE TO EARTH & ACROSS SWITCH CONTACTS LIGHTNING IMPLUSE WITHSTAND VOLTAGE TO EARTH & ACROSS SWITCH CONTACTS RATED SHORT TIME WITHSTAND CURRENT (kA FOR 3 SEC) RATED PEAK WITHSTAND CURRENT (kA PEAK) OPERATING MECHANISM OPERATING TIME (SEC) SHORT CIRCUIT LINK DATA RATED VOLTAGE RATED MAXIMUM VOLTAGE RATED FREQUENCY RATED CONTINUOUS CURRENT RATED INSULATION LEVEL POWER FREQUENCY WITHSTAND VOLTAGE ACROSS ISOLATING CONTACTS LIGHTNING IMPLUSE WITHSTAND VOLTAGE ACROSS ISOLATING CONTACTS 21kV 24kV 50 HZ 21kV 24kV 50 HZ

CLIENTS SPECIFICATION

BY BIDDER BY BIDDER BY BIDDER BY BIDDER ELECTRICAL MOTOR OPERATED BY BIDDER

BY BIDDER BY BIDDER BY BIDDER BY BIDDER

Page 4 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

GENERATOR CIRCUIT BREAKER


SI. NO
5.6 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 7.0 7.1 7.2 7.3 7.4 7.5 7.6 8.0 8.1 8.2

GENERAL INFORMATION
INSULATION LEVEL TO ENCLOSURE VOLTAGE TARNSFORMERS QUANTITY LOCATION RATED VOLTAGE RATIO ACCURACY RATED BURDEN SECONDARY PROTECTION INSULATION TYPE CURRENT TRANSFORMERS QUANTITY LOCATION CT RATIO CT PARAMETERS RATING INSULATION TYPE SURGE CAPACITORS LOCATION RATING

CLIENTS SPECIFICATION
BY BIDDER

REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM.

REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. REFER MAIN ONE LINE DIAGRAM. BY BIDDER CAST RESIN

REFER MAIN ONE LINE DIAGARAM. BY BIDDER

Page 5 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A1

GENERATOR CIRCUIT BREAKER


SI. NO
9.0 9.1 9.2 9.3 9.4

GENERAL INFORMATION
SURGE ARRESTORS LOCATION VOLTAGE CLASS TYPE RATING

CLIENTS SPECIFICATION

REFER MAIN ONE LINE DIAGARAM. BY BIDDER METAL OXIDE GAPLESS BY BIDDER

Page 6 of 6

BEC POWER PRIVATE LIMITED


DATA SHEET A2

GENERATOR CIRCUIT BREAKER

APPLICABLE STANDARDS

1.0

A.C. HIGH VOLTAGE GENERATOR CIRCUIT BREAKER

IS:

BS:

IEC:

IEEE Std. C37.013

2.0

HIGH VOLTAGE SWITCHGEAR AND CONTROLGEAR SURGE ARRESTERS

IS:

BS:

IEC:60694

3.0

IS:

BS:

IEC:60099-4

4.0

HIGH VOLTAGE SWITCHGEAR & CONTROLGEAR : AC DISCONNECTORS & EARTHING SWITCHES INSTRUMENT TRANSFORMERS

IS:

BS:

IEC:62271-102

5.0

IS:

BS:

IEC:60044-2

6.0

DEGREE OF PROTECTION PROVIDED BY ENCLOSURES COUPLING CAPACITORS & CAPACITOR DIVIDERS HIGH VOLTAGE AC CIRCUIT BREAKERS : GUIDE FOR SEISMIC QUALIFICATION HOT DIP GALVANIZING

IS:

BS:

IEC:60529

7.0

IS:

BS:

IEC:60358

8.0

IS:

BS:

IEC:61166

9.0

IS:4759, IS:2633

NOTES :

EQUIPMENT ACCESSORIES COMPONENTS/PARTS RAW MATERIALS AND TESTS SHALL IN GENERAL CONFORM TO IS: IEC: IEEE:

Page 1 of 1

BEC POWER PRIVATE LIMITED


DATA SHEET B

GENERATOR CIRCUIT BREAKER


SI. NO
2.0 2.1 2.2 2.3 2.4 2.5 2.5.1

ITEM
GENERATOR CIRCUIT BREAKER RATED VOLATGE RATED MAXIMUM VOLTAGE RATED FREQUENCY RATED CONTINUOUS CURRENT RATED INSULATION LEVEL ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE TO EARTH & ACROSS CIRCUIT BREAKER/SWITCH CONTACTS LIGHTNING IMPULSE WITHSTAND VOLTAGE TO EARTH & ACROSS CIRCUIT BREAKER/SWITCH CONTACTS ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE FOR AUXILIARY AND CONTROL CIRCUITS NUMBER OF STORED CLOSE/OPEN OPERATIONS SHORT CIRCUIT CAPABILITY SYMMETRICAL INTERRUPTING CAPABILITY DC COMPONENT OF FAULT CURRENT SHORT CIRCUIT MAKING CURRENT RATED PEAK WITHSTAND CURRENT (kA PEAK) RATED SHORT TIME WITHSTAND CURRENT (kA RMS, FOR 3 SEC)

TO BE FILLED BY BIDDER

2.5.2

2.5.3

2.6

2.7 2.7.1

2.7.2 2.7.3 2.7.4 2.7.5

Page 1 of 5

BEC POWER PRIVATE LIMITED


DATA SHEET B

GENERATOR CIRCUIT BREAKER


SI. NO
2.7.6 2.18

ITEM
OUT-OF-PHASE CURRENT SWITCHING CAPABILITY INTERRUPTING TIME (TRIPPING COMMAND TILL ARC EXTINCTION) AT MINIMUM OPERATING PRESSURE OF THE MECHANISM OPENING TIME (TRIPPING COMMAND TILL CONTACT SEPARATION) CLOSING TIME (CLOSING COMMAND TILL CONTACT TOUCH) SIMULTANEITY OF POLES (CLOSING OR OPENING) TRANSIENT RECOVERY VOLTAGE (FOR GENERATOR SOURCE FAULTS) TRANSIENT RECOVERY VOLTAGE (FOR SYSTEM SOURCE FAULTS) RATED DUTY CYCLE SF6 GAS NORMAL PRESSURE LEAKAGE RATE OPERATING MECHANISM OPENING & CLOSING COIL VOLTAGE DISCONNECTING SWITCH DATA RATED VOLTAGE RATED MAXIMUM VOLTAGE RATED FREQUENCY RATED CONTINUOUS CURRENT RATED INSULATION LEVEL ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE ACROSS

TO BE FILLED BY BIDDER

2.19

2.20 2.21 2.22

2.23 2.24 2.25 2.25.1 2.25.2 2.26 2.27 3.0 3.10 3.11 3.12 3.13 3.14 3.5.3

Page 2 of 5

BEC POWER PRIVATE LIMITED


DATA SHEET B

GENERATOR CIRCUIT BREAKER


SI. NO ITEM
ISOLATING DISTANCE OF DISCONNECTOR LIGHTNING IMPLUSE WITHSTAND VOLTAGE ACROSS ISOLATING DISTANCE OF DISCONNECTOR RATED SHORT TIME WITHSTAND CURRENT (kA FOR 3 SEC) RATED PEAK WITHSTAND CURRENT (kA PEAK) OPERATING TIME (SEC) OPERATING MECHANISM EARTHING SWITCH RATED VOLTAGE RATED MAXIMUM VOLTAGE RATED FREQUENCY RATED INSULATION LEVEL POWER FREQUENCY WITHSTAND VOLTAGE TO EARTH & ACROSS SWITCH CONTACTS LIGHTNING IMPLUSE WITHSTAND VOLTAGE TO EARTH & ACROSS SWITCH CONTACTS RATED SHORT TIME WITHSTAND CURRENT (kA FOR 3 SEC) RATED PEAK WITHSTAND CURRENT (kA PEAK) OPERATING MECHANISM OPERATING TIME (SEC) SHORT CIRCUIT LINK DATA RATED VOLTAGE RATED MAXIMUM VOLTAGE

TO BE FILLED BY BIDDER

3.5.4

3.15 3.16 3.17 3.18 4.0 4.9 4.10 4.11 4.12 4.4.3

4.4.4

4.13 4.14 4.15 4.16 5.0 5.6 5.7

Page 3 of 5

BEC POWER PRIVATE LIMITED


DATA SHEET B

GENERATOR CIRCUIT BREAKER


SI. NO
5.8 5.9 5.10 5.5.3

ITEM
RATED FREQUENCY RATED CONTINUOUS CURRENT RATED INSULATION LEVEL POWER FREQUENCY WITHSTAND VOLTAGE ACROSS ISOLATING CONTACTS LIGHTNING IMPLUSE WITHSTAND VOLTAGE ACROSS ISOLATING CONTACTS INSULATION LEVEL TO ENCLOSURE VOLTAGE TARNSFORMERS QUANTITY LOCATION RATED VOLTAGE RATIO ACCURACY RATED BURDEN SECONDARY PROTECTION INSULATION TYPE CURRENT TRANSFORMERS QUANTITY LOCATION CT RATIO CT PARAMETERS RATING INSULATION TYPE

TO BE FILLED BY BIDDER

5.5.4

5.6 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 7.0 7.1 7.2 7.3 7.4 7.5 7.6

Page 4 of 5

BEC POWER PRIVATE LIMITED


DATA SHEET B

GENERATOR CIRCUIT BREAKER


SI. NO
8.0 8.1 8.2 9.0 9.1 9.2 9.3 9.5

ITEM
SURGE CAPACITORS LOCATION RATING SURGE ARRESTORS LOCATION VOLTAGE CLASS TYPE RATING

TO BE FILLED BY BIDDER

Page 5 of 5

BEC POWER PRIVATE LIMITED


DATA SHEET C

GENERATOR & ACCESSORIES

DATA TO BE FURNISHED ALONG WITH THE BID 1.0 Duly filled Technical particulars for the GCB and calculations as indicated in the Data sheet - B. 1.1 etc. 1.2 Descriptive literature, pamphlets, write-up on the GCB and its construction details, features

Type test report for the GCB of similar or identical current rating and parameters.

DATA TO BE FURNISHED BY THE BIDDER AFTER AWARD OF CONTRACT 1.0 The BIDDER shall furnish the following drawings/documents for the GCB and accessories within 2 months from the date of award of Contract 1.1 Engineering Schedule indicating list of drawings, documents, data, performance curves, test certificates, manuals, etc. to be submitted by the BIDDER together with dates of submissions and category of approval i.e. for approval or for reference. 1.2 General Arrangement drawings for approval- a) Overall GA of GCB b) Local Control Panels Including all dimensional details, layout and maintenance requirements, details of supports required for piping and other accessories, cable entry details, earthing requirements, etc. 1.3 Foundation drawings for all equipment/accessories indicating the grouting details, static and dynamic loading data and any insert details for supporting structures and other equipment being supplied by the BIDDER. 1.4 Bill of materials including make, technical specification, etc. for all equipment/accessories.

1.5 Detailed cross-sectional drawings showing all relevant internal details of all equipment / accessories. 1.6 1.7 1.8 1.9 Detailed schematic drawings for all equipment/accessories. Manufacturing Plan. Detailed quality assurance plan. Final test procedures (at shop as well as at site).and Test Set-Up

1.10 Design calculations (wherever necessary) to prove the adequacy of the equipment offered. 1.11 2.0 Any other drawings/documents considered necessary. Following drawings shall be for reference and will not be approved

2.1 Interconnection schedules (ICS) with terminal numbers indicating the details of cable connections to be made between all equipment being supplied under this CONTRACT and also for interconnections

Page 1 of 3

BEC POWER PRIVATE LIMITED


DATA SHEET C

GENERATOR & ACCESSORIES

between equipment supplied under this CONTRACT and equipment covered by other CONTRACTS. The format of the ICS shall be subject to PURCHASERS/CONSULTANTS approval. 3.0 Data to be submitted Progressively but within 3 months

3.1 All final technical details, parameters, characteristic and performance curves as specified and any other data required. 3.2 CT characteristic curves with excitation current Vs. secondary voltage for each core as measured in the case of protection CTs. 3.3 CT secondary resistance values in ohms.

3.4 Maximum dimensions and weights of various packages for shipment under this CONTRACT. 3.5 Details of pedestals to be provided outside the TG building for the purpose of bus duct support, SF6/Air bushings, piping supports, etc. 4.0 4.1 TEST CERTIFICATES Type test certificates for all equipment/plants/accessories being supplied under this CONTRACT.

4.2 Routine test certificates for all equipment/plants/accessories being supplied under this CONTRACT. 4.3 4.4 5.0 Specified number of copies of the compiled and approved test certificates. Records of radiography tests and NDT as specified. INSTRUCTION MANUALS

The BIDDER shall furnish two nos. copies of the instruction manual which contains detailed instructions for all erection, testing, operation and maintenance requirements. The manual shall be furnished at the time of despatch of the equipment and shall include the following aspects BEFORE START OF COMMISSIONING. 5.1 Outline dimension drawings showing relevant cross sectional views, earthing details and constructional features. 5.2 Catalogue numbers of all the components which need to be replaced during the life of the equipment. 5.3 5.4 5.5 5.6 Instructions for unpacking and handling at site. Storage for prolonged duration. Erection drawings with written assembly instructions that would enable to carry out erection. Detailed instructions for the installation, operation and maintenance of GCB and accessories.

Page 2 of 3

BEC POWER PRIVATE LIMITED


DATA SHEET C

GENERATOR & ACCESSORIES

5.7 5.8

Pre-commissioning tests. Maintenance procedures including precautions to be taken during operation and maintenance work. All detailed catalogues and literature of equipment supplied.

5.9

Page 3 of 3

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
1.0 1.1

ITEM
Switchgear Ratings Nominal System Voltage Phases & Frequency

UNIT

CLIENTS SPECIFICATION

11kV, 3.3kV 3 PH & 50 HZ

1.2

System Neutral Earthing

Earthed through resistance to limit fault current to 400A 12 kV for 11kV & 3.6 kV for 3.3 kV

1.3

Maximum System Voltage

1.4

Power Frequency Withstand Voltage 1.2/50 Sec. Impulse Withstand Voltage

28kV for 11kV, 10kV for 3.3kV 75kV for 11 kV 40kV for 3.3kV

1.5

1.6

Short Circuit Withstand a) Short Time (1 Sec.) At Rated Voltage b) Short Time (3 Sec.) At Rated Voltage c) Dynamic Rating Reference Site Ambient Temperature Continuous Current Rating Of Bus Bars Under Reference Site Ambient Temp. Maximum Temperature Of Bus Bars And Droppers/Connectors Under Conditions Specified Sr. Nos. 1.7 And 1.8 Above

40 kA (rms) NA 105 kA (peak)

1.7

500C

1.8

Shall be as per requirement

1.9

900C for bus bars having non- silver plated joints. 1050C for bus bars having silver plated joints

Page 1 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
1.10

ITEM
APPLICABLE STANDARDS

UNIT

CLIENTS SPECIFICATION
As per Data Sheet A2

3.0

Switchgear Constructional Requirements

3.1

Clearance In Air

Ph-Ph

120 mm

3.2

Bus Bar Insulation

HR PVC Sleeve. Removable bus bar joints with shrouds of 12kV, 3.6kV insulation. Silver faced

3.3

Bus Bar Joints/Connections

3.4

Bus Bar Support Insulators

12kV, 3.6kV

3.5

Bus Bar Rating

Shall be as per requirement

3.6

Degree Of Protection

Bus bar IPH 4X For other IPH 6X

3.7

Bus Duct Connection

Bus duct/cable connection

Page 2 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
3.8 Earthing Bus

ITEM

UNIT
Material GS

CLIENTS SPECIFICATION

Size

Shall be as per Notes & details.

3.9

Colour Finished Shade

Interior

RAL 7032

Exterior

RAL 7032

3.10

Thickness Of Sheet Steel Enclosures, Doors And Covers

Door and covers 1.6 mm and Load bearing 2.0 mm

4.1

Breaker Particulars

4.1.1

Applicable Standards

As per data sheet A2

4.1.2

Circuit Breaker Type

VCB

Page 3 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
4.1.3

ITEM
Voltage, Frequency, & No.Of Phases

UNIT

CLIENTS SPECIFICATION
11kV, 3.3kV 50Hz 3Ph

4.1.4

Rated Operating Duty

O3 MINCO3-MINCO

4.1.5

Rated Current At Reference Site Ambient Temperature

Shall be as per requirement

4.1.6

Rated Breaking Current

40kA(rms)

4.1.7

Rated Making Current

105 kA (peak)

4.1.8

Short Time Current Withstand For 1 Sec. Duration.

40kA (rms)

4.1.9

Asymmetrical Breaking Current

Ac Compone nt D.C. Compone nt

As per IEC-56

As per IEC-56

4.1.10

Total Opening Time

CYCLES / Msec

< 3 cycles

Page 4 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
4.1.11

ITEM
Total Closing Time

UNIT
Cycles / Msec

CLIENTS SPECIFICATION
< 5 cycles

4.1.12

Operating Mechanism, Type

Motor spring charged, manual trip & close facility also to be provided.

4.1.13

Trip Free

--

YES

4.1.14

Anti Pumping Feature

--

To be Provided

4.1.15

Minimum No. Of Auxiliary Contacts

5 NO + 5 NC for Purchasers use

4.1.16

Power Frequency Withstand Test Voltage

ONE MINUTE

28kV for 11kV, 10kV for 3.3kV rms

4.1.17

Auxiliary Control Voltage

A) For Closing/Tripping Coil

DC

220 V

B) For Spring Charging Motors

AC / DC

220 V DC

Page 5 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO ITEM
C) For Space Heaters & Lighting AC

UNIT
1PH

CLIENTS SPECIFICATION
240 VOLTS

4.1.18

Breaker Application

A) Transformer Control

YES

B) Motor Control

YES

C) Furnace Control

NO

D) Capacitor Control

NO

4.2

Vacuum Contactor

YES

4.2.1

Application (Controlled Eqpt.)

For CHP & AHP systems

4.2.2

Max. System Voltage & Frequency

11kV, 3.3kV,50 Hz.

Page 6 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
4.2.3 No. Of Poles

ITEM

UNIT
3

CLIENTS SPECIFICATION

Mechanism

5.1

Spring Charging

By motor

5.2

Type

Universal motor

5.3

Rating Voltage

240V

5.4

Rating

kW

As required

5.5

Other

-NIL-

Disconnectors

6.1

Application (Controlled Eqpt.)

NOT APPLICABLE

Page 7 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
6.2 Type

ITEM

UNIT

CLIENTS SPECIFICATION

6.3

Rated Current At Referance Site Ambient Temperature

6.5

Rated Making & Breaking Capacitive Current

6.6

S.C. Withstand Currents

A) Momentary

B) 1 Sec. Current

6.7

Operating Mechanism

Closing & Opening

Control Voltage

6.8.1

Power Frequency Withstand Test Voltage

One Min.

Page 8 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
6.8.2

ITEM
Impulse Withstand Voltage

UNIT
1.2/50 S

CLIENTS SPECIFICATION

6.9

Applicable Standards

6.10

Minimum No. Of Aux. Contacts

6.11

Hrc Fuses (Rating To Suit Appln.)

See Proj. Drawings

Current Transformers

7.1

Applicable Standard (S)

As per data sheet A2

7.2

Type

Cast resin (completely encapsulated) Bar primary

7.3

System Voltage & Frequency

11kV, 3.3kV, 50Hz

7.4

Class Of Insulation

Class-B or better

Page 9 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
7.5

ITEM
Rated Primary Current & Ratio

UNIT

CLIENTS SPECIFICATION
To be decided by bidder

7.6

Accuracy Class & Burden

Metering

Energy meters 0.2s, other meters 0.5, As required

Protn.

differential and core balance CTs - PS other protection CTs - 5P20 40 kA (rms) 105 kA (peak)

7.7

Short Time 1 Sec. Current Rating & Dynamic Rating

Voltage Transformer

8.1

Applicable Standard (S)

As per data sheet A2

8.2

Type

Cast Resin (Completely encapsulated) Draw out type

8.3

Rated Voltage

Primary

11000/3 Volts, 3300/3 Volts

Secondary

S1

110/3 Volts

Page 10 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
Secondary

ITEM
S2

UNIT

CLIENTS SPECIFICATION
110 /3 Volts

8.4

Method Of Connection Primary

P1

STAR

Secondary

S1

STAR

Secondary

S2

STAR

8.5

Rated Voltage Factor

1.2 (Continuous) 1.9 FOR 8 HOURS

8.6

Class Of Insulation

Class B or better

8.7.1

Power Frequency Withstand Test Voltage

ONE MIN.

28kV for 11kV, 10kV for 3.3kV

8.7.2

Impulse Withstand Voltage

1.2/50 S

75kV for 11 kV 40kV for 3.3kV

8.7.3

Accuracy Class

P class for protection and 0.5 for metering

Page 11 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
H.V.Fuses

ITEM

UNIT

CLIENTS SPECIFICATION

9.1

Applicable Standard(S)

As per data sheet A2

9.2

Rated Current

As per requirement

9.3

Voltage Class

kV

12kV, 3.6kV

9.4

Sym. Interrupting Rating

kA (rms)

40kA

Meters

10.1

Applicable Standard (S)

As per data sheet A2

10.2

Accuracy Class

CL 0.2s for Energy meters and 0.5 for others

10.3

Type Of Meters

Digital

Page 12 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A1

HT SWITCHGEAR
SI. NO
Relays

ITEM

UNIT

CLIENTS SPECIFICATION

11.1

Applicable Standards

As per data sheet A2

11.2

Type

NUMERICAL for all protective relays.

11.3

Other Specification

Page 13 of 13

BEC POWER PRIVATE LIMITED


DATA SHEET A2

HT SWITCHGEAR

APPLICABLE CODES & STANDARDS


1 2 METAL ENCLOSED SWITCHGEAR CIRCUIT BREAKERS IS : 3427 IS : 13118 IEC : 298 IEC : 62271

SWITCHES & SWITCH DISCONNECTORS ABOVE 1000 V & UPTO 11 KV (OFF LOAD) DISCONNECTORS ARRANGEMENT FOR SWITCHGEAR BUSBARS, MAIN CONNECTION AND AUXILIARY WIRING

IEC : 265

4 5

IEC : 129 IS :5578,11353 IEC :

BUSBARS B) ALUMINIUM

A) COPPER IS: 5082 IS : 2544 IS : 3427 IS : 2705 IS : 3156 IS : 722 IS : 1248 IEC: IEC : IEC : 529 IEC : 185 IEC : 186 IEC : IEC : 51

7 8 9 10 11 12

BUSBAR SUPPORT INSULATORS DEGREE OF PROTECTION CURRENT TRANSFORMERS POTENTIAL TRANSFORMERS A.C. ELECTRICITY METERS ELECTRICAL INDICATING INSTRUMENTS ELECTRICAL RELAYS FOR POWER SYSTEM PROTECTION

13

IS : 3231

IEC :

Page 1 of 1

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO
1.0 1.1 1.2 1.3 1.4 1.5 1.6 General Manufacturers name Applicable standard (s) Type of circuit beaker Nominal system voltage Maximum continuous voltage Power frequency withstand (one minute) voltage A) short circuit withstand B) momentary withstand 1.8 Impulse 1.2/50 sec withstand voltage

ITEM
kV kV kV

UNIT

TO BE FILLED BY BIDDER

1.7

kV (rms) kV (peak) kV (peak)

1.9 2.0 3.0 3.1

Type test report Compliance with specification Constructional features Dimensions A) switchgear cubicle B) adapter panel

Enclosed / Not Enclosed Yes / No, Deviations Attached

Page 1 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO ITEM
C) overall based on (a) & (b) 3.2 3.3 3.3.1 3.3.2 3.4 3.5 4.0 4.1 4.2 4.3 4.4 4.5 4.6 Minimum clear space required Weight Cubicle weight with circuit breaker Total switchgear weight Dynamic loading per cubicle Painting specification Busbars Material Applicable standard Busbar cross section Busbar insulation Standard to which the busbar arrangement conforms Minimum clearance : A) phase to phase B) phase to earth 5.0 5.1 Circuit breakers Feeder ratings mm mm Amps Compliance With Spec. Yes / No, Deviations Attached Kg. Kg. Kg. mm Front/rear

UNIT

TO BE FILLED BY BIDDER

Page 2 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO
5.2

ITEM
Switching overvoltage A) switching off motor running at no load B) switching off motor with its rotor locked C) switching off motor running at full load D) switching off unloaded transforme

UNIT

TO BE FILLED BY BIDDER

P.U./ms P.U./ms P.U./ms P.U./ms Volts Volts Yes / No

5.2.1 5.3 5.3.1

Maximum permissible chopping current. External switching overvoltage limitings devices required Details of voltage limiting device : A) Type B) Rated Voltage C) continuous withstand voltage between line and earth

5.4

Main contacts : A) Type B) Material Watts

5.5

Arcing contacts : A) Type B) Material

5.6

Trip coil consumption at rated voltage

Page 3 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO
5.7

ITEM
Satisfactory operation of closing between 80% - 100% of rated control voltage SF6 Gas details A) Standard To Which SF6 Gas Conforms B) SF6 Gas Pressure C) Gas Density Monitor Provided & Details Attached. D) Leakage Of SF6 Gas E) SF6 Gas Leakage Detector Provided F) Weight Of SF6 Gas Per Pole

UNIT

TO BE FILLED BY BIDDER
Yes / No

5.8

Yes / No

Yes / No

5.9 6.0 6.1 6.2 a)

Type test report Circuit breaker operating mechanism Type of closing mechanism Spring charging mechanism : Spring charging motor : i) ii) Rated Voltage Rating

Enclosed / Not Enclosed

Volts Watts RPM Yes / No, Deviations Attached

iii) Speed iv) Class Of Insulation v) Satisfactory Operation Of Spring Charging Motor Between 80% - 110% Of Rated Voltage

Page 4 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO ITEM
vi) Time Required To Charge The Spring From Fully Discharged Condition vii) Overload And Short Circuit Protection Particulars b) Adequate spring reserve for one O- CO operation without intentional time delay Mechanical indication for spring charged condition provided Vacuum contactors Makers name and country of manufacture Manufacturers type designation Applicable standards Type test report Clearances a) Between Phases b) Between Live Parts And Earth c) Centre To Centre Distance Between Phases 7.6 7.7 Whether the vacuum contactor is mechanically latched or electrically he a) Type Of Operating Mechanism b) Power For Operating Station Mechanism 7.8 Method of closing a) Normal Voltage Of Coil Battery or control transforme Volts Yes / No

UNIT
SEC.

TO BE FILLED BY BIDDER

Yes / No

c) 7.0 7.1 7.2 7.3 7.4 7.5

Yes / No

Enclosed / Not Enclosed

Page 5 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO ITEM
b) Power For Closing Mechanism 7.9 Number of operations the vacuum contactor is capable of performing without inspection Switching over voltages by the vacuum contactor Whether instruction manual is enclosed Instrument transformers Current transformers - metering and protection Make Type (bar / wound / any other) Applicable standard Class of insulation Core Balance CTs. (for each CT) a) Ratio b) Rated Va Burden c) Accuracy Class d) Minimum Knee-Point Voltage e) Maximum Magnetisation Current At Proposed Setting f) CT Secondary Resistance g) Magnetisation Characteristic Curv Attached

UNIT
Watts Nos.

TO BE FILLED BY BIDDER

7.10 7.11 8.0 8.1 8.1.1 8.1.2 8.1.3 8.1.4 8.1.5

Per unit peak line t earth YES / NO VA Volts Ma Ohms Yes/No Compliance With Spec. Yes / No, Deviations Attached

Page 6 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO ITEM
h) Dimensioned Drawing Attached i) Applicable Standard 8.1.6 8.2 8.2.1 8.2.2 8.2.3 8.2.4 8.2.5 9.0 9.1 9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.1.6 9.1.7 Type Test Report For All CT Designs Voltage Transformers Make Type Applicable Standard Type Of Insulation Type Test Report Indicating Meters General Make Applicable Standard Type Of Movement Size Scale Size (In Degrees) Mounting, Flush Type Other Accuracy

UNIT
Yes/No mm

TO BE FILLED BY BIDDER

Enclosed / Not Enclosed Compliance With Spec. Yes / No, Deviations Attached

Enclosed / Not Enclosed Compliance With Spec. Yes / No, Deviations Attached

Page 7 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO
9.1.8 9.1.9 9.2 9.2.1 9.2.2 9.2.3 9.2.4 9.2.5 9.2.6 9.2.7 9.2.8 9.2.9 9.2.10 9.2.11 9.2.12 10.0 10.1 10.2

ITEM
Range As Per Specification VA Burden For Each Type Watt Hour Meter Make Type Standard To Which It Conforms Maximum Number Of Digits Voltage Coil Rating Current Rating VA Burden Accuracy Range As Per Specification Draw Out / Non Drawout Type Mounting, Flush Type Other Test Plug/Test Blocks Testing Terminals With Links Protection Relays Inverse Time Over-Current Relay Instantaneous Over-Current Relay

UNIT

TO BE FILLED BY BIDDER
Yes / No, Deviations Attached

Volts Amps. VA Yes / No, Deviations Attached

Page 8 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO
10.3 10.4 10.5 10.6 10.7 10.8 10.9 10.10

ITEM
Thermal Overload Protection Relay Locked Rotor Protection Relay Thermal Overload Alarm Relay Negative Sequence Voltage Operated Relay Earth Leakage Relay For Use With Core Balance CT Earth Fault Relay For Use In The Residual Circuit Of Main CTs. Differential Relay (High Stability Circulating Current Type) Differential Relay For Use With Through-Type CTs.

UNIT

TO BE FILLED BY BIDDER

10.11 11.0 11.1

Voltage Operated Earth Fault Relay (Neutral Displacement Relay) Termination / Wiring Colour Coding For Wires For : a) D.C. control circuits b) A.C. auxiliary power circuit like panel space heater, panel illumination etc. c) A.C. metering circuit d) Earthing

Yes / No Yes / No Compliance With Spec. Yes / No, Deviations Attached

11.2 11.3

Numbered ferrules at both ends Insulated sleeves provided at wire terminations

Page 9 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET B

HT SWITCHGEAR
SI. NO
11.4 Terminals : a) Make b) Current Rating c) Clamp Type / Bolt Type d) Moulded Inter-Terminal Barriers Provided e) Maximum Conductor Size And Number Of Conductors Which It Can Receive f) Disconnecting Type For CT Circuits g) Terminal Marking Facility Provided h) Crimp Type Connectors Provided At The Terminals i) 10% Spare Terminal Provided 11.5 12.0 12.1 Type test report for wiring materials Spares List of recommended spares for normal maintenance for a period of 3 years furnished Tests All test certificates on bought items be furnished List of routine tests to be carried out attached Drawings and data Drawings submitted along with bid sq.mm Yes / No

ITEM

UNIT

TO BE FILLED BY BIDDER

Amps Yes / No

Yes / No Yes / No Yes / No Yes / No Enclosed / Not Enclosed

13.0 13.1 13.2 14.0 14.1

Yes / No Yes / No Enclosed / Not Enclosed Yes / No

Page 10 of 10

BEC POWER PRIVATE LIMITED


DATA SHEET C

HT SWITCHGEAR
DATA TO BE FURNISHED AFTER THE AWARD OF CONTRACT. 1. Switchgear cubicle: outline dimensions and GA, including plan, front elevation, rear elevation, side

elevation and relevant cross sectional views. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Switchgear layout plan including floor opening and fixing arrangement Schematic control circuit diagram Bus bar sizing / Temperature rise calculation. Short circuit force calculation. Filled up data sheets Type Test & Routine test certificates. Detail wiring diagram including terminal block numbers, ferrule numbers and cable connection. Relay and instrument panel GA Inter panel interconnection wiring diagram. Relay setting and relay co-ordination. Installation, Operational and maintenance manuals for the major components like VCB, Relays etc.

Page 1 of 1