EasyPact
General contents
Presentation
Circuit breakers
Installation guide
43
Busbars
65
EasyPact
PB101844-27 PB101848-35 PB102114-40
TM
EZC100.
EZC250.
EZC400.
DB115728
PB101848-34
PB101851-34
Easy to choose
EasyPact brings you easy solutions b From 15 A to 400 A b Up to 50 kA at 415 V b Up to 4 poles b In only three frame sizes b With a complete range of auxiliaries and accessories
EZCV250.
EZC250.
Easy to install
b Fixed front mounting b Front connections b Bare cables connected through cable lugs, screwed inside the breaker b Field-installable auxiliaries and accessories b Built-in earth-leakage protection b Interchangeable MCCB and ELCB
DB112479
Easy to use
b A thermal calibration suitable for MCCB use at 50C without derating b Positive contact indication for safety and reliability
DB106482
EasyPact
Circuit breakers
6 10 14
14 15 16 17 18 19 19 20 20 21 21
22
22 23 24 25
26
26 28
Direct rotary handle 100-250AF Extended rotary handle 100-250AF Power connections and cable lugs 100-250AF DIN rail adaptor, padlocking, sealing screws 100-250AF Electrical auxiliaries 400AF
0
30 31 32 34 36
36 37
AX - AL SHT - UVR
Direct rotary handle 400AF Extended rotary handle 400AF Power connections, cable lugs, spreaders and extensions 400AF Insulation of live parts and padlocking 400AF
Installation guide Busbars
38 39 40 41
43 65
Circuit breakers
General characteristics
EasyPact circuit breakers and auxiliaries comply with the following international standards: b IEC 60947-1 - general rules b IEC 60947-2 - low-voltage switchgear and controlgear, part 2 (circuit breakers) b European (EN 60947-1 and EN 60947-2) and the corresponding national standards b GB 14048.2 b JIS C8201-2-1 Annex 1 and Annex 2, for molded case circuit breakers b JIS C8201-2-2 Annex 1 and Annex 2, for earth-leakage circuit breakers b NEMA-AB1 (High Interrupting Capacity): American standard b UL508/CSA 22-2 no. 14.
DB112374
certification by independent laboratories (ASEFA, KEMA, TV) marking certified by third party Tilva certified by third party Underwriter Laboratories as a Manual Motor Controller (EZC250/EZCV250/EZC400).
EasyPact circuit breakers resist mechanical vibrations and shocks. Tests are carried out in compliance with standard IEC 60068-2-6 for the levels required by merchant-marine inspection organisation IACS: International Association of Classification Societies (Veritas, Germanisches Lloyds, Rina, USSR, Lloyds Register): b 2 to 13.2 Hz: amplitude 1 mm b 13.2 to 100 Hz: acceleraton 0.7 g.
Standardised characteristics indicated on the rating plate: Ui: rated insulation voltage Uimp: rated impulse withstand voltage Ue: rated operational voltage Icu: ultimate breaking capacity, for various values of the rated operational voltage Ue Cat: utilisation category Ics: service breaking capacity In: rated current suitability for isolation
Pollution degree
EasyPact circuit breakers are certified for operation in pollution-degree III . environments as defined by IEC standard 60947 (industrial environments)
Tropicalisation
EasyPact circuit breakers have successfully passed the tests prescribed by the following standards for extreme atmospheric conditions: b IEC 60068-2-1 - dry cold (-55 C) b IEC 60068-2-2 - dry heat (+85 C) b IEC 60068-2-30 - damp heat (95 % relative humidity at 55 C) b IEC 60068-2-52 - salt mist (severity level 2).
PB101844-25
EZ101PR-28
All EasyPact circuit breakers are suitable for isolation as defined in IEC standard 60947-2: b the isolation position corresponds to the O (OFF) position b the operating handle cannot indicate the O (OFF) position (green colour visible) unless the contacts are effectively open b padlocks may not be installed unless the contacts are open b installation of a rotary handle does not alter the reliability of the position-indication system. The isolation function is certified by tests guaranteeing: b the mechanical reliability of the position indication system b the absence of leakage currents b overvoltage withstand capacity between upstream and downstream connections.
Environmental protection
EasyPact circuit breakers take into account important concerns for environmental protection. Most components are recyclable and the parts are marked as specified in applicable standards.
Circuit breakers
b EasyPact circuit breakers has been particularly designed to hold 100 % In at 50C without tripping in normal condition (except for earth-leakage circuit breakers). b EasyPact circuit breakers may be used between -25 C and +70 C. b The permissible storage-temperature range for EasyPact circuit breakers in the original packing is -35 C to +85 C.
Ambient temperature
DB106003
Installation
EasyPact circuit breakers are designed for easy installation in the various types of switchboards. They may be mounted vertically, horizontally or flat on their back without any derating of characteristics.
Installation positions.
DB106037
Power supply
EasyPact circuit breaker can be supplied from either the top or the bottom (reverse feeding) without any reduction in performance. For earth-leakage circuit breakers, reverse feeding is possible only up to 240 V AC. This capability facilitates connection when installed in a switchboard.
Degree of protection
Reverse feeding.
As per standards IEC 60529 (IP degree of protection) and EN 50102 (IK degree of protection against external mechanical impacts).
IP20
IK07
IP40
IK07
IP40
IK07
DB106016
IP54
IK07
IP54
IK08
Circuit breakers
Earth-leakage protection
PB101851-37
EasyPact circuit breakers have a specific version including earth-leakage protection. This protection is fully integrated inside the breaker and does not require any additional space. EasyPact circuit breakers and earth-leakage circuit breakers are fully interchangeable.
EasyPact earth-leakage circuit breakers comply with all the international standards listed page 6 : b IEC 60947-1 b IEC 60947-2 b EN 60947-1 b EN 60947-2 b GB 14048.2 b JIS C8201-2-2 Annex 1 and Annex 2 b NEMA-AB1 (High Interrupting Capacity) b UL508/CSA 22-2 no. 14. They also comply with: b VDE 664, operation down to -25 C b IEC 60255-4 and IEC 60801-2 to 60801-5 covering protection against nuisance tripping due to transient overvoltages, lightning strikes, switching of devices on the distribution system, electrostatic discharges, radiofrequency interference.
DB112379
Power supply
Reverse feeding EasyPact earth-leakage circuit breakers can be supplied from either the top or the bottom for voltages up to 300 V AC. For voltages over 300 V AC, only supply from the top is possible (Line-Load indication on the cover of the breaker). Power supply of the electronics EasyPact earth-leakage circuit breakers are self-supplied by the distribution-system voltage and therefore do not require any external source. They fully comply with new IEC requirements (Annex B): they are powered from the three phases and continue to function even if one phase is missing.
Dielectric tests
EasyPact earth-leakage circuit breakers are equipped with a disconnecting switch in order to protect the electronics during dielectric tests. When the disconnecting switch is activated, the circuit breaker is automatically tripped. It is mechanically impossible to switch on the circuit breaker, until the earthleakage function is re-energised.
Tripping features
Tripping indications: b EasyPact earth-leakage circuit breakers have a yellow mechanical indicator to locally signal tripping due to an earth fault. b EasyPact earth-leakage circuit breakers may be equipped with an earth-leakage alarm switch (ALV) to remotely signal tripping due to an earth fault. Resetting EasyPact earth-leakage circuit breakers are fully reset by the operating handle. After resetting, tripping indicators (mechanical and ALV) come to normal position.
1 2 3 4 5 6
Line-Load (Ue > 300 V AC) Mechanical indicator (ELCB) Adjustable settings IDn and time delay ELCB test button Push to trip button (MCCB) Dielectric tests: disconnecting switch
Circuit breakers
DB112375
Circuit breakers
Selection table
In
at 40 C
Rated insulation voltage (V) Rated impulse withstand voltage (kV) Rated operational voltage (V) EZC100-1P.
Ui Uimp Ue
AC 50/60 Hz DC AC 50/60 Hz 110/130 V 220/230/240 V 380 V 400/415 V 440 V 550 V 125 V (1P) DC 250 V (2P in series) % Icu 110-400 V 415-550 V
PB101840-15
Rated service breaking capacity (kA rms) Suitability for isolation Utilisation category Pollution degree Endurance (C-O cycles)
Ics
EZC100-2P.
PB101843-22
Protection
Overload protection Instantaneous protection Bimetal Magnetic Auxiliary switch Alarm switch Combined AX + AL Shunt trip release Undervoltage release Crimp lugs/bars Box lugs for bare cables Rotary handles Terminal extensions Spreaders Phase barriers Terminal shields Padlocking system DIN rail adaptor Fixed (20 %) AX AL AXAL SHT UVR
Auxiliaries
Indication contacts EZC100-3P. Voltage releases
Installation
PB102172-27
Connection Accessories
Direct Extended
EZC100-4P.
DxH W
Weight (kg)
EZC250-3P.
10
Circuit breakers
EZC100B
3 15, 16, 20, 25, 30, 32, 40, 45, 50, 60 690 6 550 10 10 7.5 7.5 5 2.5 25 % 25 % b A 3 8 500 1 500 fixed fixed b b b b b b b b b b b b b b 60 x 130 75 0.78
EZC100F
3 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 550 250 25 25 10 10 7.5 5 5 5 50 % 50 % b A 3 8 500 1 500 fixed fixed b b b b b b b b b b b b b b 60 x 130 75 0.78
EZC100N
1 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 415 125 25 18 2.5 2.5 5 50 % 50 % b A 3 8 500 1 500 10 10 (2) fixed fixed b b b b b 60 x 130 25 0.28 3-4 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 550 250 25 25 18 15 10 5 5 5 50 % 50 % b A 3 8 500 1 500 25 10 fixed fixed b b b b b b b b b b b b b b 60 x 130 75 (3P), 100 (4P) 0.78 (3P), 1.0 (4P)
EZC100H
1 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 415 125 50 25 5 5 10 50 % 50 % b A 3 8 500 1 500 18 18 (2) fixed fixed b b b b b 60 x 130 25 0.28 2-3-4 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 550 250 100 100 (1) 30 30 20 10 10 10 50 % 25 % b A 3 8 500 1 500 100 18 (3) fixed fixed b b b b b b b b (3) b (3) b b b (3) b b 60 x 130 50 (2P), 75 (3P), 100 (4P) 0.6 (2P), 0.78 (3P), 1.0 (4P)
EZC250F
3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 25 25 18 18 15 5 5 5 50 % 50 % b A 3 10 000 5 000 25 15 fixed 10 In b b b b b b b b b b b b b b 60 x 165 105 1.3
EZC250N
3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 50 50 25 25 20 8 20 20 50 % 50 % b A 3 10 000 5 000 50 18 fixed 10 In b b b b b b b b b b b b b b 60 x 165 105 1.3
EZC250H
2-3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 85 85 36 36 25 10 30 30 50 % 50 % b A 3 10 000 5 000 85 25 (3) fixed 10 In b b b b b b b b b b b b b b 60 x 165 105 1.1 (2P), 1.3 (3P)
(1) 50 kA for 2 poles. (2) For 277 V only. (3) For 3 poles only.
11
Circuit breakers
In
at 40C
Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue
AC 50/60 Hz DC AC 50/60 Hz 220/230/240 V 380 V 400/415 V 440 V 550 V DC 125 V (1P) 250 V (2P in series) % Icu In/415 V
PB101854-34
Rated service breaking capacity (kA rms) Suitability for isolation Utilisation category Pollution degree Endurance (C-O cycles)
Protection
PB102114-28
Bimetal Magnetic
fixed ( 20 %)
Earth-leakage protection
Sensitivity (A) Time-delay (ms) Max. breaking time (s)
IDn Dt at 2 IDn
adjustable adjustable
Auxiliaries
Indication contacts
Auxiliary switch Alarm switch Combined AX + AL Earth-alarm switch Shunt trip release Undervoltage release
Voltage releases
Installation
EZC400-3P. Connection Accessories
Crimp lugs / bars Box lugs for bare cables Rotary handles Direct Extended Terminal extensions Spreaders Phase barriers Terminal shields Padlocking system
PB102115-36
DxH W
Weight (kg)
EZC400-4P.
12
Circuit breakers
EZC250N
4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 50 25 25 20 8 20 20 50 % b A 3 10 000 5 000 50 18 fixed 10 In
EZC250H
4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 85 36 36 25 10 30 30 50 % b A 3 10 000 5 000 85 25 fixed 10 In b b b b b b b b b b b b b b 68 x 165 140 1.8
EZCV250N
3-4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 440 6 440 85 25 25 20 50 % b A 3 10 000 5 000 50 fixed 10 In 0.1/0.3/0.5/1 0/200/500/1000 0.15/0.4/1/2 b b b b b b b b b b b b b b b 68 x 165 105 (3P) 140 (4P) 1.6 (3P) 2.1 (4P)
EZCV250H
3-4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 440 6 440 -
EZC400N
3-4 250, 300, 320, 350, 400 690 8 550 250 85 36 36 36 15 20 50 % b A 3 4 000 1 000 50 25 fixed 10 In b b b b b b b b b b b b b b 103 x 257 140 (3P) 185 (4P) 5 (3P) 7.5 (4P)
EZC400H
3-4 250, 300, 320, 350, 400 690 8 550 250 100 50 50 50 20 40 50 % b A 3 4 000 1 000 85 35
fixed 10 In
fixed 10 In
b b b b b b b b b b b b b b
b b b b b b b b b b b b b b
13
Circuit breakers
PB101841-20
3P 15 - 16 - 20 - 25 - 30 - 32 - 40 - 45 - 50 - 60
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) Ue = 550 V AC 220/230/240 10 25 % Ui = 690 V 380/400/415 7.5 25 % Uimp = 6 kV 440 5 25 % 550 2.5 25 %
Rating
15 A 16 A 20 A 25 A 30 A 32 A 40 A 45 A 50 A 60 A
Cat. no.
EZC100B3015 EZC100B3016 EZC100B3020 EZC100B3025 EZC100B3030 EZC100B3032 EZC100B3040 EZC100B3045 EZC100B3050 EZC100B3060
EZC100F 15 to 100 A
PB101842-20
3P 15 - 16 - 20 - 25 - 30 - 32 - 40 - 45 - 50 - 60 - 63 75 - 80 - 100
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) AC 220/230/240 25 50 % Ue = 550 V Ui = 690 V 380/400/415 10 50 % Uimp = 6 kV 440 7.5 50 % 550 5 50 % 125 (1P) 5 50 % DC 250 (2P) 5 50 %
Rating
15 A 16 A 20 A 25 A 30 A 32 A 40 A 45 A 50 A 60 A 63 A 75 A 80 A 100 A
Cat. no.
EZC100F3015 EZC100F3016 EZC100F3020 EZC100F3025 EZC100F3030 EZC100F3032 EZC100F3040 EZC100F3045 EZC100F3050 EZC100F3060 EZC100F3063 EZC100F3075 EZC100F3080 EZC100F3100
14
Circuit breakers
EZC100N 15 to 100 A
PB101838-10
1P, 3P and 4P 15 - 16 - 20 - 25 - 30 - 32 - 40 - 45 - 50 - 60 - 63 -75 - 80 100 Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1
Ue (V) Ue = 550 V Ui = 690 V Uimp = 6 kV 110/130 220/230/240 380 400/415 440 550 DC 125 (1P) 250 (2P) Breaking capacities (kA rms) as NEMA-AB1 Ue (V) HIC (kA) 1P AC 240 277 10 277/480 AC Icu (kA) 1P 25 18 2.5 2.5 5 3P - 4P 25 25 18 15 10 5 5 5 Ics (% Icu) 1P - 3P - 4P 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %
EZC100N-1P.
PB101843-20
3P - 4P 25 10 4P 3t EZC100N4015 EZC100N4016 EZC100N4020 EZC100N4025 EZC100N4030 EZC100N4032 EZC100N4040 EZC100N4045 EZC100N4050 EZC100N4060 EZC100N4063 EZC100N4075 EZC100N4080 EZC100N4100
Rating
EZC100N-3P. 15 A 16 A 20 A 25 A 30 A 32 A 40 A 45 A 50 A 60 A 63 A 75 A 80 A 100 A
Cat. no.
1P EZC100N1015 EZC100N1016 EZC100N1020 EZC100N1025 EZC100N1030 EZC100N1032 EZC100N1040 EZC100N1045 EZC100N1050 EZC100N1060 EZC100N1063 EZC100N1075 EZC100N1080 EZC100N1100 3P EZC100N3015 EZC100N3016 EZC100N3020 EZC100N3025 EZC100N3030 EZC100N3032 EZC100N3040 EZC100N3045 EZC100N3050 EZC100N3060 EZC100N3063 EZC100N3075 EZC100N3080 EZC100N3100
PB102171-25
EZC100N-4P.
15
Circuit breakers
EZC100H 15 to 100 A
PB101839-10
1P, 2P, 3P and 4P 15 - 16 - 20 - 25 - 30 - 32 - 40 - 45 - 50 - 60 - 63 75 - 80 - 100 Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1
Ue (V) Ue = 550 V Ui = 690 V Uimp = 6 kV AC 110/130 220/230/240 380/400 415 440 550 125 (1P) 250 (2P) Icu (kA) 1P 50 25 5 5 10 2P 100 50 30 30 20 10 10 10 3P - 4P 100 100 30 30 20 10 10 10 Ics (% Icu) 1P - 2P - 3P - 4P 50 % 50 % 50 % 25 % 25 % 25 % 50 % 50 %
EZC100H-1P.
PB101840-15
DC
Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) HIC (kA) 1P 2P AC 240 18 100 277 18 277/480 EZC100H-2P.
3P - 4P 100 18 3P EZC100H3015 EZC100H3016 EZC100H3020 EZC100H3025 EZC100H3030 EZC100H3032 EZC100H3040 EZC100H3045 EZC100H3050 EZC100H3060 EZC100H3063 EZC100H3075 EZC100H3080 EZC100H3100
Rating
15 A 16 A 20 A 25 A 30 A 32 A 40 A 45 A 50 A 60 A 63 A 75 A 80 A 100 A
Cat. no.
1P EZC100H1015 EZC100H1016 EZC100H1020 EZC100H1025 EZC100H1030 EZC100H1032 EZC100H1040 EZC100H1045 EZC100H1050 EZC100H1060 EZC100H1063 EZC100H1075 EZC100H1080 EZC100H1100 2P EZC100H2015 EZC100H2016 EZC100H2020 EZC100H2025 EZC100H2030 EZC100H2032 EZC100H2040 EZC100H2045 EZC100H2050 EZC100H2060 EZC100H2063 EZC100H2075 EZC100H2080 EZC100H2100
PB101844-20
EZC100H-3P.
Rating
15 A 16 A 20 A 25 A 30 A 32 A 40 A 45 A 50 A 60 A 63 A 75 A 80 A 100 A
Cat. no.
EZC100H-4P.
4P 3t EZC100H4015 EZC100H4016 EZC100H4020 EZC100H4025 EZC100H4030 EZC100H4032 EZC100H4040 EZC100H4045 EZC100H4050 EZC100H4060 EZC100H4063 EZC100H4075 EZC100H4080 EZC100H4100
PB102172-27
16
Circuit breakers
PB101845-29
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) Ue = 550 V AC 220/230/240 25 50 % Ui = 690 V 380/400/415 18 50 % 15 50 % Uimp = 6 kV 440 550 5 50 % 125 (1P) 5 50 % DC 250 (2P) 5 50 % Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) 240 AC 277/480 HIC (kA) 25 15
Rating
100 A 125 A 150 A 160 A 175 A 200 A 225 A 250 A
Cat. no.
EZC250F3100 EZC250F3125 EZC250F3150 EZC250F3160 EZC250F3175 EZC250F3200 EZC250F3225 EZC250F3250
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) AC 220/230/240 50 50 % Ue = 550 V Ui = 690 V 380/400/415 25 50 % 20 50 % Uimp = 6 kV 440 550 8 50 % 125 (1P) 20 50 % DC 250 (2P) 20 50 % Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) 240 AC 277/480 HIC (kA) 50 18
Rating
100 A 125 A 150 A 160 A 175 A 200 A 225 A 250 A
Cat. no.
EZC250N3100 EZC250N3125 EZC250N3150 EZC250N3160 EZC250N3175 EZC250N3200 EZC250N3225 EZC250N3250
17
Circuit breakers
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) 2P 3P 220/230/240 85 85 50 % Ue = 550 V AC Ui = 690 V 380/400/415 36 36 50 % 25 25 50 % Uimp = 6 kV 440 10 10 50 % 550 125 (1P) 30 30 50 % DC 250 (2P) 30 30 50 % EZC250H-2P. Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) AC 240 277/480 HIC (kA) 2P 85 -
PB101848-29
Rating
100 A 125 A 150 A 160 A 175 A 200 A 225 A 250 A EZC250H-3P.
Cat. no.
2P EZC250H2100 EZC250H2125 EZC250H2150 EZC250H2160 EZC250H2175 EZC250H2200 EZC250H2225 EZC250H2250
18
Circuit breakers
PB101852-36
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) Ue = 550 V AC 220/230/240 50 50 % Ui = 690 V 380/400/415 25 50 % Uimp = 6 kV 440 20 50 % 550 8 50 % DC 125 (1P) 20 50 % 250 (2P) 20 50 % Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) AC 240 277/480 HIC (kA) 50 18 4P 4t EZC250N44063 EZC250N44080 EZC250N44100 EZC250N44125 EZC250N44150 EZC250N44160 EZC250N44175 EZC250N44200 EZC250N44225 EZC250N44250
Rating
63 A 80 A 100 A 125 A 150 A 160 A 175 A 200 A 225 A 250 A
Cat. no.
4P 3t EZC250N4063 EZC250N4080 EZC250N4100 EZC250N4125 EZC250N4150 EZC250N4160 EZC250N4175 EZC250N4200 EZC250N4225 EZC250N4250
EZC250H 63 A to 250 A
PB101853-36
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) Ue = 550 V AC 220/230/240 85 50 % Ui = 690 V 380/400/415 36 50 % Uimp = 6 kV 440 25 50 % 550 10 50 % DC 125 (1P) 30 50 % 250 (2P) 30 50 % Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) AC 240 277/480 HIC (kA) 85 25 4P 4t EZC250H44063 EZC250H44080 EZC250H44100 EZC250H44125 EZC250H44150 EZC250H44160 EZC250H44175 EZC250H44200 EZC250H44225 EZC250H44250
Rating
63 A 80 A 100 A 125 A 150 A 160 A 175 A 200 A 225 A 250 A
Cat. no.
4P 3t EZC250H4063 EZC250H4080 EZC250H4100 EZC250H4125 EZC250H4150 EZC250H4160 EZC250H4175 EZC250H4200 EZC250H4225 EZC250H4250
19
Circuit breakers
PB101850-26
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1/C8201-2-2 Ue (V) Icu (kA) Ics (% Icu) Ue = 440 V AC 220/230/240 85 50 % Ui = 440 V 380/400/415 25 50 % 20 50 % Uimp = 6 kV 440 Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) 240 AC Earth-leakage characteristics Sensitivity IDn (A) Time delay Intentional delay (ms) Max. breaking time (s) HIC (kA) 50
EZCV250N-3P.
PB101854-38
adjustable 0.1/0.3/0.5/1 adjustable 0/200/500/1000 0.15/0.4/1/2 4P 3t EZCV250N4063 EZCV250N4080 EZCV250N4100 EZCV250N4125 EZCV250N4150 EZCV250N4160 EZCV250N4175 EZCV250N4200 EZCV250N4225 EZCV250N4250 4P 4t EZCV250N44063 EZCV250N44080 EZCV250N44100 EZCV250N44125 EZCV250N44150 EZCV250N44160 EZCV250N44175 EZCV250N44200 EZCV250N44225 -
Rating
63 A 80 A 100 A 125 A 150 A 160 A 175 A 200 A 225 A 250 A
Cat. no.
3P EZCV250N3063 EZCV250N3080 EZCV250N3100 EZCV250N3125 EZCV250N3150 EZCV250N3160 EZCV250N3175 EZCV250N3200 EZCV250N3225 EZCV250N3250
EZCV250N-4P.
EZCV250H 63 A to 250 A
PB101851-28
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1/C8201-2-2 Ue (V) Icu (kA) Ics (% Icu) Ue = 440 V AC 220/230/240 100 50 % Ui = 440 V 380/400/415 36 50 % 25 50 % Uimp = 6 kV 440 Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) 240 AC EZCV250H-3P. Earth-leakage characteristics Sensitivity IDn (A) Time delay Intentional delay (ms) Max. breaking time (s) HIC (kA) 85
adjustable 0.1/0.3/0.5/1 adjustable 0/200/500/1000 0.15/0.4/1/2 4P 3t EZCV250H4063 EZCV250H4080 EZCV250H4100 EZCV250H4125 EZCV250H4150 EZCV250H4160 EZCV250H4175 EZCV250H4200 EZCV250H4225 EZCV250H4250 4P 4t EZCV250H44063 EZCV250H44080 EZCV250H44100 EZCV250H44125 EZCV250H44150 EZCV250H44160 EZCV250H44175 EZCV250H44200 EZCV250H44225 -
Rating
PB101855-36
Cat. no.
3P EZCV250H3063 EZCV250H3080 EZCV250H3100 EZCV250H3125 EZCV250H3150 EZCV250H3160 EZCV250H3175 EZCV250H3200 EZCV250H3225 EZCV250H3250
20
Circuit breakers
PB102114-28
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) Ue = 550 V AC 220/230/240 85 50 % Ui = 690 V 380/400/415 36 50 % Uimp = 8 kV 440 36 50 % 15 50 % 550 250 (2P) 20 50 % DC Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) 240 AC 277/480 HIC (kA) 50 25 4P 3t EZC400N4250 EZC400N4300 EZC400N4320 EZC400N4350 EZC400N4400 4P 4t EZC400N44250 EZC400N44300 EZC400N44320 EZC400N44350 EZC400N44400
EZC400N-3P.
Rating
250 A 300 A 320 A 350 A 400 A
Cat. no.
3P EZC400N3250 EZC400N3300 EZC400N3320 EZC400N3350 EZC400N3400
PB102115-36
EZC400N-4P.
Breaking capacities (kA rms) as per IEC 60947-2, EN 60947-2, JIS C8201-2-1 Ue (V) Icu (kA) Ics (% Icu) Ue = 550 V AC 220/230/240 100 50 % Ui = 690 V 380 50 50 % Uimp = 8 kV 400/415 50 50 % 440 50 50 % 20 50 % 550 250 (2P) 40 50 % DC Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) 240 AC 277/480 HIC (kA) 85 35 4P 3t EZC400H4250 EZC400H4300 EZC400H4320 EZC400H4350 EZC400H4400 4P 4t EZC400H44250 EZC400H44300 EZC400H44320 EZC400H44350 EZC400H44400
EZC400H-3P.
Rating
PB102115-36
Cat. no.
3P EZC400H3250 EZC400H3300 EZC400H3320 EZC400H3350 EZC400H3400
EZC400H-4P.
21
Circuit breakers
DB112364
22
Circuit breakers
DB112365
23
Circuit breakers
DB112366
24
Circuit breakers
DB115251
Phase barriers
Terminal shield
Spreaders
padlocking system
25
Circuit breakers
EZC100
DB112322
EZC100-2P.
EZC100-3P.
DB114564
EZC100-4P.
EZC250
EZC100.
DB112323
EZC250-3P.
PB102164-33
EZC250-4P.
EZCV250
DB112324
EZCV250-3P.
EZCV250-4P.
Indication contacts
Provide remote circuit breaker status information. They can be used for indications, electrical locking, relaying, etc. Common-point changeover contacts.
PB102166-35
Auxiliary switch (ON/OFF) AX indicates the position of the circuit breaker contacts. Alarm switch (trip indication) b AL indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v operation of a voltage release. b ALV indicates that the circuit breaker has tripped due to an of earth-leakage fault. They return to de-energised state when the circuit breaker is reset.
AXAL electrical auxiliaries on EZC250.
Characteristics
Contacts
Rated thermal current (A) Minimum load Utilisation category (IEC 60947-5-1) Operational current (A) 24 V 48 V 125 V 250 V 5 10 mA at 24 V AC12 AC15 5 5 5 5 5 3 3 2
PB102168-42
Connections
Connection wire length Cross-section 450 mm EZC100: 1 mm2, EZC250/EZCV250: 1.5 mm2
26
Circuit breakers
PB101862-21
PB101876-21
DB112376
Designation
Auxiliary switch (AX) Alarm switch (AL) Auxiliary/Alarm switch (AXAL) Earth-leakage alarm switch (ALV) (1) only EZCV250.
Cat. no.
EZC100 EZAUX10 EZAUX01 EZAUX11 EZC250/EZCV250 EZEAX EZEAL EZEAXAL EZEALV (1)
27
Circuit breakers
EZC100
DB112325
EZC100-2P.
EZC100-3P.
DB114565
EZC100-4P.
EZC250
DB112326
EZC250.
EZC250-3P.
PB102165-35
EZC250-4P.
EZCV250
DB112327
EZCV250-3P.
EZCV250-4P.
Remote tripping
Shunt Trip (SHT) or Under Voltage Release (UVR/UVRN). Shunt Trip (SHT) b This release trips the circuit breaker when the control voltage rises above 0.7 x Un b Control signals can be of the impulse type (u 20 ms) or maintained. Under Voltage Release (UVR/UVRN) b This release trips the circuit breaker when the control voltage drops below a tripping threshold b Tripping threshold between 0.35 and 0.7 times the rated voltage b Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage. Operation When the circuit breaker has been tripped by an SHT or UVR/UVRN release, it must be reset locally: b SHT or UVR/UVRN tripping takes priority over manual closing b in the presence of a standing trip order, closing of the contacts, even temporary, is not possible. Circuit breaker tripping by an SHT/UVR/UVRN release meets the requirements of standard IEC60947-2.
PB102167-35
PB102163-39
Characteristics
Mechanical Electrical
SHT UVR UVRN UVRN release on EZCV250. pick-up consumption response time seal-in consumption response time seal-in consumption response time Mechanical endurance 10 % of MCCB mechnical endurance
EZC100
AC/DC < 30 VA < 50 ms < 5 VA < 50 ms < 5 VA < 50 ms
EZC250/EZCV250
AC < 30 VA < 50 ms < 5 VA < 50 ms < 5 VA < 50 ms pre-wired (0.5 mm2) screws (< 2 mm2) pre-wired (0.5 mm2) DC < 35 W < 100 ms < 10 W < 100 ms < 10 W < 100 ms
Connections
SHT UVR UVRN
EZC100
pre-wired (1 mm2) pre-wired (1 mm2) pre-wired (1 mm2)
EZC250/EZCV250
28
Circuit breakers
Installation b EZC100 SHT and UVR: internal mounting b EZC250/EZCV250: v SHT: internal mounting v UVR: external mounting v UVRN: internal mounting Cat. no. Designation
Shunt Trip EZESHT. SHT Shunt trip release AC 100-130 V 200-277 V 380-480 V 24 V 48 V 110-130 V 200-240 V 277 V 380-415 V 440-480 V 24 V 48 V 125 V 110-130 V 200-240 V 277 V 380-415 V 440-480 V 24 V 48 V 125 V EZC100 EZASHT100AC EZASHT200AC EZASHT380AC EZASHT024AC EZASHT048AC EZAUVR110AC EZAUVR200AC EZAUVR277AC EZAUVR380AC EZAUVR440AC EZAUVR024DC EZAUVR048DC EZAUVR125DC 110-120 V 120-130 V 200-240 V 277 V 380-440 V 440-480 V EZC250/EZCV250 EZESHT100AC EZESHT120AC EZESHT200AC EZESHT277AC EZESHT400AC EZESHT440AC EZESHT024DC EZESHT048DC EZEUVRN110AC EZEUVRN200AC EZEUVRN277AC EZEUVRN400AC EZEUVRN440AC EZEUVRN024DC EZEUVRN048DC EZEUVRN125DC EZEUVR110AC EZEUVR200AC EZEUVR277AC EZEUVR400AC EZEUVR440AC EZEUVR024DC EZEUVR048DC EZEUVR125DC
PB101865-16
PB101879-18
UVRN Under voltage release (only EZC250-4P and EZCV250 3/4P) DC Under Voltage Release EZEUVRN. UVR Under voltage release AC
PB101866-18
DC AC
PB101888015
PB101894-27
DC
29
Circuit breakers
Suitable for Motor Control Centre (MCC) switchboards. b Degree of protection IP40 or IP54, IK07 (IP54 with gasket supplied). b The direct rotary handle maintains: v suitability for isolation v indication of the three positions O (OFF), I (ON) and tripped v circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter 5 for EZC100, 8 for EZC250/EZCV250 v door opening disabled when the circuit breaker is ON v circuit breaker closing is disabled if the door is open. IP40 or IP54
DB112011
PB102159-30
PB101881-33
DB112012
Padlocking
PB102157-33
EZC100.
DB112013
DB112001
EZC250/EZCV250.
Designation
Direct rotary handle (red/yellow) for EZC250/EZCV250. Direct rotary handle (black) Direct rotary handle (red/yellow)
Cat. no.
EZC100 EZAROTDS EZAROTDSRY EZC250/EZCV250 EZEROTDS EZEROTDSRY
30
Circuit breakers
Makes possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. b Degree of protection IP40 or IP54, IK08 (IP54 with gasket supplied). b The extended rotary handle maintains: v suitability for isolation v indication of the three positions O (OFF), I (ON) and tripped v circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter: 5 for EZC100, 8 for EZC250/EZCV250 v door opening disabled when the circuit breaker is ON.
Extended rotary handle (black) for EZC100.
PB102158-46
b The extended rotary handle is made up of: v a unit on the front cover of the circuit breaker (secured by screws) v an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally v an extension shaft that must be adjusted to the distance between back of circuit breaker and door. IP40 or IP54
DB112014
PB101882-40
DB112015
EZC250/EZCV250.
Padlocking
PB102156-42
DB112016
DB112002
EZC250/EZCV250.
Designation
Extended rotary handle (black) Extended rotary handle (red/yellow)
Cat. no.
EZC100 EZAROTE EZAROTERY EZC250/EZCV250 EZEROTE EZEROTERY
31
Circuit breakers
EZC100 15 to 50 A
E88221
EZC100 60 to 100 A
E88222
Screw M8
EZC250/EZCV250 63 to 250 A
DB112345
Screw M8
EZC100 Bars
DB112346
(mm)
y 50 A > 50 A
y 17 d + 10 y7 y6 5.5 8.5
EZC250/ EZCV250 y 25 d + 10 y8 y6 9
Crimp lugs
L (mm) d (mm)
(mm)
Tightening torque y 50 A > 50 A
y 50 A > 50 A
y 25 y8 9 13 N.m
Cable lugs
DB106032
> 50 A (EZC100)
DB115938
u 100 A (EZC250/EZCV250)
Designation
Cable lug up to 50 A (set of 2) Cable lug up to 50 A (set of 3) Cable lug from 60 A up to 100 A (set of 2) Cable lug from 60 A up to 100 A (set of 3) Cable lug from 100 A up to 250 A (set of 3) Cable lug from 100 A up to 250 A (set of 4)
Cat. no.
EZC100 EZALUG0502 EZALUG0503 EZALUG1002 EZALUG1003 EZC250/EZCV250 EZELUG2503 EZELUG2504
32
Circuit breakers
Spreaders
PB101858-32
Increase the pitch of the circuit breaker terminals: b EZC100 from 25 mm to 35 mm b EZC250/EZCV250 from 35 mm to 45 mm.
Spreader.
Terminal extensions
DB106041
Terminal extensions.
Designation
Spreaders for 3-pole breaker (set of 3) Spreaders for 4-pole breaker (set of 4) Terminal extension for 3-pole breaker (set of 3) Terminal extension for 4-pole breaker (set of 4)
Cat. no.
Phase barriers
PB101861-23
b Safety accessories for maximum insulation at the power connection points b Usable with all other connection accessories, except terminal shields b Each breaker is delivered with a set of phase barriers (1 for 2 poles, 2 for 3 poles and 3 for 4 poles breaker) b Additional set of phase barriers available for insulation between outgoings or between 2 side by side mounted breakers.
PB101875-15
Designation
Phase barriers for EZC250/ EZCV250. Phase barriers for 60 mm depht (set of 2) Phase barriers for 68 mm depht (set of 3)
Cat. no.
EZC100 EZAFASB2 -
PB101859-26
PB101874-25
b Insulating accessories for protection against direct contact with power circuits b Designed for front connection only (long terminal shield).
Terminal shields
DB106026
Designation
Terminal shield 3P, 60 mm depth (set of 2) Terminal shield 3P, 68 mm depth (set of 2) Terminal shield 4P, 60 mm depth (set of 2) Terminal shield 4P, 68 mm depth (set of 2)
Cat. no.
33
Circuit breakers
Breaker mounting on a DIN rail is possible by using special adaptator (EZC100 only). Number of adaptators: b one for two 1P, or one 2P or one 3P b two for one 4P.
DB112338
PB101917-15
Designation
Din rail adaptor
Cat. no.
EZC100 EZADINR EZC250/EZCV250 -
Padlocking system
PB101869-22
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking system can receive: b up to 2 padlocks 5 mm (padlocks not supplied) for EZC100 b up to 3 padlocks 8 mm for EZC250/EZCV250 (padlocks not supplied).
DB112339 DB112340
PB101920-20
Padlocking device for EZC250/EZCV250. Toggle locking using a removable device: for EZC100
for EZC250/EZCV250
Designation
Padlocking system Padlocking system for EZC250-3P Padlocking system for EZC250-4P and EZCV250-3/4P
Cat. no.
EZC100 EZALOCK EZC250/EZCV250 EZELOCK EZELOCKN
Sealing screws
PB101860-30 DB106029
Designation
Sealing screws (set of 2)
Cat. no.
EZC100 EZASSCR EZC250/EZCV250 -
34
35
Circuit breakers
EZC400-3P.
EZC400-4P.
Indication contacts
Provide remote circuit breaker status information. They can be used for indications, electrical locking, relaying, etc. Common-point changeover contacts. Auxiliary switch (ON/OFF) AX indicates the position of the circuit breaker contacts. Alarm switch (trip indication) AL indicates that the circuit breaker has tripped due to: b an overload b a short-circuit b operation of a voltage release. It returns to de-energised state when the circuit breaker is reset. Functions (AL or AX) is determined by the mounting location of the auxiliary
PB102170-32
Characteristics
Contacts
Rated thermal current (A) Minimum load Utilisation category (IEC 60947-5-1) Operational current (A) 24 V AX and 2 AL. 48 V 125 V 250 V
PB102129-21
Connections
Connection wire length Cross-section
PB102128-21
DB112349
Designation
Signalling switch (AX or AL) Double signalling switch (2 AX or 2 AL)
Cat. no.
EZ4AUX EZ4AUX2
36
Circuit breakers
EZC400-3P.
EZC400-4P.
Remote tripping
Shunt Trip (SHT) or Under Voltage Release (UVR). Shunt Trip (SHT) b This release trips the circuit breaker when the control voltage rises above 0.7 x Un b Control signals can be of the impulse type (u 20 ms) or maintained. Under Voltage Release (UVR) b This release trips the circuit breaker when the control voltage drops below a tripping threshold b Tripping threshold between 0.35 and 0.7 times the rated voltage b Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage. Operation When the circuit breaker has been tripped by an SHT or UVR release, it must be reset locally: b SHT or UVR tripping takes priority over manual closing b in the presence of a standing trip order, closing of the contacts, even temporary, is not possible. Circuit breaker tripping by an SHT or UVR release meets the requirements of standard IEC60947-2.
SHT or UVR voltage release.
PB102169-32
Characteristics
Mechanical Electrical
AC DC < 35 W < 100 ms < 10 W < 100 ms Mechanical endurance 10 % of MCCB mechanical endurance
PB102130-13
PB102131-13
SHT UVR
Connections
Connection wire length Cross-section Shunt Trip SHT. Shunt Trip UVR.
Cat. no.
EZ4SHT048ACDC EZ4SHT200ACDC EZ4SHT277AC EZ4SHT400AC EZ4SHT048ACDC EZ4SHT200ACDC EZ4UVR024ACDC EZ4UVR048ACDC EZ4UVR110ACDC EZ4UVR130ACDC EZ4UVR200AC EZ4UVR277AC EZ4UVR400AC EZ4UVR024ACDC EZ4UVR048ACDC EZ4UVR130ACDC
DC
37
Circuit breakers
Suitable for Motor Control Centre (MCC) switchboards b Degree of protection IP50, IK07. b The direct rotary handle maintains: v suitability for isolation v indication of the three positions O (OFF), I (ON) and tripped v circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter 8 v door opening disabled when the circuit breaker is ON v circuit breaker closing is disabled if the door is open. IP50
DB112360
Padlocking
DB112361
Designation
Direct rotary handle
Cat. no.
EZ4ROTDS
38
Circuit breakers
Makes possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. b Degree of protection IP54, IK08. b The extended rotary handle maintains: v suitability for isolation v indication of the three positions O (OFF), I (ON) and tripped v circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter: 8 v door opening disabled when the circuit breaker is ON. b The extended rotary handle is made up of: v a unit on the front cover of the circuit breaker (secured by screws) v an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally v an extension shaft that must be adjusted to the distance between of circuit breaker and door. IP54
DB112362
Padlocking
DB112363
Designation
Extended rotary handle
Cat. no.
EZ4ROTE
39
Circuit breakers
DB112350
Bars
DB112353
y 32 d + 10 y 10 y 10 10
Crimp lugs
Tightening torque
y 32 y 10 10 30 N.m
PB102116-30
Cable lugs
Cable lugs directly screwed on standard circuit breaker terminals, for cables from 35 to 300 mm.
DB112352
Designation
Cat. no.
EZ4LUG4003 EZ4LUG4004
Spreaders
Terminal extensions
Spreaders.
DB112354
Designation
Cat. no.
EZ4SPDR73P EZ4SPDR74P
40
Circuit breakers
Phase barriers
PB102124-30
b Safety accessories for maximum insulation at the power connection points b Usable with all other connection accessories, except terminal shields b Each breaker is delivered with a set of phase barriers ( 2 for 3 poles and 3 for 4 poles breaker) b Additional set of phase barriers available for insulation between outgoings or between 2 side by side mounted breakers.
DB112356 DB112357
Designation
Phase barriers for 3-pole breaker (set of 2) Phase barriers for 4-pole breaker (set of 3)
Cat. no.
EZ4FASB2 EZ4FASB3
Terminal shields
PB102122-30
b Insulating accessories for protection against direct contact with power circuits b Designed for front connection only (long terminal shield).
DB112358
Designation
Terminal shield for 3P (set of 2 parts) Terminal shield for 4P (set of 2 parts)
Cat. no.
EZ4TSHD3P EZ4TSHD4P
Padlocking system
PB102134-25
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking system can receive up to 3 padlocks 8 mm (padlocks not supplied).
DB112359
Designation
Padlocking system
Cat. no.
EZ4LOCK
41
42
EasyPact
Installation guide
2 5
Dimensions
EasyPact 100 EasyPact 250 EasyPact 400 EasyPact 100 accessories EasyPact 250 accessories EasyPact 400 accessories
44
44 46 48 50 51 52
Safety clearances and minimum distances Temperature derating Tripping curves Current-limiting curves Cascading Cascading tables Motor protection Capacitor protection
Busbars
53 55 56 58 59 60 62 64
65
43
Installation guide
Dimensions
1P
DB111973 DB111974 DB111975
2P
DB111976
3P
DB115254
4P
Mounting on plate
1P
DB111977 DB115255
2P
or
3P
DB111979 DB115259
4P
or
44
Installation guide
2P
DB114581
4P
2P
3P
DB111988 DB114582
4P
45
Installation guide
EZC250/EZCV250
Dimensions (EZC250)
2P, 3P
DB111947 DB111948
4P
35
50
44 22 100 105
Dimensions (EZCV250)
3P
DB111951 DB111952 DB112493
DB111949
?? 52.5 35
4P
DB111971
3P, 4P ELCB
Mounting on plate
2P, 3P
DB111953 DB111954
4P
46
Installation guide
EZC250/EZCV250
Door cut-out (small)
2P, 3P
DB111955 DB111956 DB111957
4P
4P
Dimensions (mm)
EZC 2/3P EZC 4P EZCV 3P EZCV 4P A 60 68 B 65 73 C 85.5 95 D 45.5 80.5 E 67 75 F 61 69
47
Installation guide
Dimensions
DB111842 DB111843
3P
DB111855
4P
Mounting on plate
3P
DB111870 DB111871
4P
48
Installation guide
3P
DB111872
4P
4P
49
Installation guide
Terminal shields
DB111989 DB111990
3P
DB115256
4P
Phase barriers
DB111991 DB111992
2P
DB111993
3P
DB115257
4P
3P
DB115258
4P
DB111996
3P, 4P
3P, 4P
DB111999
3P, 4P
50
Installation guide
Terminal shields
DB111961 DB111962
3P, 4P
DB111963
Phase barriers
DB111964
3P, 4P
3P
DB111967
4P
DB111968
3P, 4P
3P, 4P
DB111972
3P, 4P
Dimensions (mm)
EZC 2/3P EZC 4P EZCV 3P/4P A 58.5 66.5 B 55 63 C 93 to 97 101 to 105 D 145 153 E 137 to 414 145 to 422
51
Installation guide
Terminal shields
DB111851 DB111854 DB111844
Phase barriers
DB111845
4P
DB111927
3P, 4P
3P, 4P
52
Installation guide
When installing a circuit breaker, minimum distances (safety clearances) must be maintained between the device and panels, bars and other protection devices installed nearby. These distances, which depend on the ultimate breaking capacity, are defined by tests carried out in accordance with standard IEC 60947-2. If installation conformity is not checked by type tests, it is also necessary to: b use insulated bars for circuit-breaker connections b block off the busbars using insulating screens. For EasyPact breaker, terminal shields, inter-phase barriers or an insulation isolator are recommended and may be mandatory depending on the utilisation voltage and the type of installation. Minimal distance between two adjacent circuit breakers
E88230
Minimal distance between the circuit breaker and top, bottom or side panels
DB106055 DB112377
Minimal distance between the circuit breaker and front or rear panels
Dimensions (mm)
EasyPact circuit breaker C1 D1 D2 D1 D2 E EZC100B/F/N 40 45 45 75 45 40 EZC100H 40 60 45 75 45 40 EZC250F/N-EZCV250N 50 60 45 140 45 42.5 EZC250H-EZCV250H 50 80 45 140 45 42.5 EZC400N 50 120 100 250 100 40 EZC400H 80 140 100 250 100 40 The mandatory distances when installing EasyPact circuit breakers are calculated from the device case, not taking into account the terminal shields or the phase barriers.
Installation in an enclosure
E44458
EasyPact circuit breakers can be installed in a metal enclosure together with other devices (contactors, motor-protection circuit breakers, LEDs, etc.).
53
54
Installation guide
Temperature derating
EasyPact devices are equipped with fixed thermal-magnetic trip units. b EasyPact has been particularly designed to hold 100 % In at 50 C without tripping in normal condition (except for earth-leakage circuit breakers). b EasyPact circuit breakers may be used between -25 C and +70 C. b EasyPact circuit breakers should be put into service under normal ambient operating temperature conditions. Exceptionally, the circuit breaker may be put into service when the ambient temperature is between -35 C and -25 C. b the permissible storage-temperature range for EasyPact circuit breakers in the original packing is -35 C to +85 C. To determine tripping times using time/current curves, use Ir values corresponding to the thermal setting on the device, corrected as indicated in the tables below. Rated current 25C (A)
EZC100 15 16 20 25 30 32 40 45 50 60 63 75 80 100 EZC250 63 80 100 125 150 160 175 200 225 250 EZCV250 63 80 100 125 150 160 175 200 225 250 EZC400 250 300 320 350 400 17.0 18.1 21.8 26.9 34.5 36.8 42.8 48.8 54.2 64.4 67.6 78.6 84.4 109 77 93 115 148 174 186 207 236 268 297 72 89 113 140 163 177 194 223 245 277 293 351 374 410 468
Ambient temperature
40C
15.7 16.7 20.4 25.7 31.4 33.5 40.9 46.9 52.1 61.8 64.9 76.8 82.2 103 69 86 106 135 160 171 188 215 244 270 63 80 100 125 150 160 175 200 225 250 268 321 342 375 428
45C
15.3 16.3 20.2 25.3 30.7 32.7 40.4 45.9 51.0 60.9 63.9 75.9 81.1 101 66 83 103 130 155 166 182 208 235 260 60 77 95 120 145 154 168 192 218 240 260 312 333 364 416
50C
15.0 16.0 20.0 25.0 30.0 32.0 40.0 45.0 50.0 60.0 63.0 75.0 80.0 100 63 80 100 125 150 160 175 200 225 250 56 73 91 114 141 148 161 183 211 230 250 300 320 350 400
55C
14.7 15.7 19.7 24.7 29.4 31.4 39.5 44.4 49.3 59.0 62.0 73.5 78.6 99 60 77 96 120 145 154 168 192 215 239 53 70 86 108 136 141 154 175 203 220 240 288 307 336 384
60C
14.6 15.6 19.2 24.5 29.1 31.0 38.0 43.3 48.1 57.5 60.4 70.4 77.3 94 56 74 93 114 139 148 161 184 205 228 49 66 80 102 131 135 146 165 196 209 228 273 291 319 364
65C
14.2 15.1 18.9 24.3 28.5 30.4 37.6 42.6 47.3 56.6 59.4 69.8 76.7 94 53 71 89 109 134 142 153 175 194 215 44 62 74 95 125 127 138 155 180 198 218 261 278 305 348
70C
13.8 14.7 18.5 24.0 28.0 29.9 37.1 41.9 46.6 55.7 58.5 69.1 76.1 93 49 68 85 103 128 136 145 166 182 203 39 58 68 88 120 120 126 144 162 180 208 249 266 291 332
55
Installation guide
Tripping curves
20 A
DB115732
25 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
t(s)
t(s)
t(s)
30-32 A
DB115733 DB115734
40 A
DB115735
45-50 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
t(s)
t(s)
t(s)
60-63 A
DB115736 DB115737
75 A
DB115738
80 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005
2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
t(s)
t(s)
t(s)
.002 .001 .5 .7 1
3 4 5 .7 10 I / Ir
20 30 50 70 100 200300
56
Installation guide
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
t(s)
150-160-175-200 A
DB115742
225-250 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
t(s)
t(s)
t(s)
.002 .001 .5 .7 1
3 4 5 .7 10 I / Ir
20 30 50 70 100 200300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 .7 10 I / Ir 20 30 50 70 100 200300
t(s)
57
Installation guide
Current-limiting curves
The limiting capacity of a circuit breaker is its aptitude to limit short-circuit currents.
DB106049
The exceptional limiting capacity of the EasyPact range greatly reduces the forces created by fault currents in devices. The result is a major increase in breaking performance. The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising the following operations: b break three times consecutively a fault current equal from 25% to 100% of Icu b check that the device continues to function normally: v it conducts the rated current without abnormal temperature rises v protection functions perform within the limits specified by the standard v suitability for isolation is not impaired.
Currentlimiting circuit breakers greatly reduce the negative effects of shortcircuits on installations. Thermal effects Less temperature rise in conductors, therefore longer service life for cables. Mechanical effects Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars being deformed or broken. Electromagnetic effects Less disturbances for measuring devices located near electrical circuits.
Cascading is a technique directly derived from current limiting. Circuit breakers with breaking capacities less than the prospective shortcircuit current may be installed downstream of a limiting circuit breaker. The breaking capacity is reinforced by the limiting capacity of the upstream device. It follows that substantial savings can be made on downstream equipment and enclosures.
Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which are a function of the prospective shortcircuit current (the current which would flow if no protection devices were installed): b the actual peak current (limited current), b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor with a resistance of 1 W.
80 60 50 40 30 20 kA peak
3 2 10 5
6
10 8 7 6 5 4 2 3 4 6 10 kA rms 20 30 40 60 100
3 2 10 5
5
10
20 kA rms
30 40
60
100
58
Installation guide
Cascading
What is cascading?
Cascading is the use of the current limiting capacity of circuit breakers at a given point to permit installation of lower-rated and therefore lower-cost circuit breakers downstream. The upstream compact circuit breakers acts as a barrier against short-circuit currents. In this way, downstream circuit breakers with lower breaking capacities than the prospective short-circuit (at their point of installation) operate under their normal breaking conditions. Since the current is limited throughout the circuit controlled by the limiting circuit breaker, cascading applies to all switchgear downstream. It is not restricted to two consecutive devices.
With cascading, the devices can be installed in different switchboards. Thus, in general, cascading refers to any combination of circuit breakers where a circuit breaker with a breaking capacity less than the prospective Isc at its point of installation can be used. Of course, the breaking capacity of the upstream circuit breaker must be greater than or equal to the prospective short-circuit current at its point of installation. The combination of two circuit breakers in cascading configuration is covered by the IEC 60947-2.
The use of a protective device possessing a breaking capacity less than the prospective short-circuit current at its installation point is permitted as long as another device is installed upstream with at least the necessary breaking capacity. In this case, the characteristics of the two devices must be coordinated in such a way that the energy let through by the upstream device is not more than that which can be withstood by the downstream device and the cables protected by these devices without damage. Cascading can only be checked by laboratory tests and the possible combinations can be specified only by the circuit breaker manufacturer.
For 1P + N or 2P circuit breakers connected between the phase and neutral on a 380/415 V network, with a TT or TNS neutral system, consult the 220/240 V cascading table to determine cascading possibilities between upstream and downstream circuit breakers.
Thanks to cascading, circuit breakers with breaking capacities less than the prospective short-circuit current may be installed downstream from a current limiting circuit breaker. It follows that substantial savings can be made on downstream switchgear and enclosures.
Cascading tables
Merlin Gerin cascading tables are: b drawn up on the basis of calculations (comparison between the energy limited by the upstream device and the maximum permissible thermal stress for the downstream device) b verified experimentally in accordance with IEC standard 60947-2. For distribution systems with 220/240 V, 380/415 V and 440 V between phases, the tables of the following pages indicate cascading possibilities between upstream Compact/EasyPact and downstream Multi 9 and EasyPact circuit breakers.
59
Installation guide
Cascading tables
Network 220/240 V
DB106106
Breaking capacity kA rms Downstream NC45 6 NC45N 10 NC45H 15 C60a 10 C60N 20 C60H 30 QO-E 10
Upstream
EZC100F EZC100N
EZC100H
Upstream
Breaking capacity kA rms Downstream EZC100B 10 EZC100F 25 EZC100N 25 EZC100H 100
Upstream
Breaking capacity kA rms Downstream EZC100B 10 EZC100F 25 EZC100N 25 EZC100H 100 EZC250F 25 EZC/EZCV250N 50 EZC/EZCV250H 85
EZ400N
EZ400H
NB400 NB630
NS400N NS630N
85 20 50 50 50 85 -
NS400H NS630H
100 20 50 50 50 85 100
Network 380/415 V
Breaking capacity kA rms Downstream NC45 5 NC45N 8 NC45H 10 C60a 6 C60N 10 C60H 15 QO-E 5 GV2M 15
Upstream
EZC100F EZC100N
EZC100H
DB106160
Upstream
Breaking capacity kA rms Downstream EZC100B 7.5 EZC100F 10 EZC100N 15 EZC100H 30
Upstream
Breaking capacity kA rms Downstream EZC100B 7.5 EZC100F 10 EZC100N 15 EZC100H 30 EZC250F 18 EZC/EZCV250N 25 EZC/EZCV250H 36
EZ400N
EZ400H
NB400 NB630
NS400N NS630N
50 20 45 20 36 45
NS400H NS630H
70 30 50 20 40 50
60
8 janvier 2008
545E4003_Ver7.0.indd
Installation guide
Cascading tables
Network 440 V
Upstream
Breaking capacity kA rms Downstream EZC100B 5 EZC100F 7.5 EZC100N 10 EZC100H 20
Upstream
Breaking capacity kA rms Downstream EZC100B 5 EZC100F 7.5 EZC100N 10 EZC100H 25 EZC250F 15 EZC/EZCV250N 20 EZC/EZCV250H 25
EZ400N
EZ400H
NB400 NB630
61
Installation guide
Motor protection
DB106108
DB106107
A circuit supplying a motor may include one, two, three or four switchgear or controlgear devices fulfilling one or more functions. When a number of devices are used, they must be coordinated to ensure optimum operation of the motor. Protection of a motor circuit involves a number of parameters that depend on: b the application (type of machine driven, operating safety, starting frequency, etc.) b the level of service continuity imposed by the load or the application b the applicable standards to ensure protection of life and property. The necessary electrical functions are of very different natures: b short circuit protection b overload protection dedicated for motor b control (generally with high endurance levels) b isolation.
Protection functions
Disconnection functions: Isolate a motor circuit prior to maintenance operations. Short-circuit protection: Protect the starter and the cables against major overcurrents (> 10 In). This type of protection is provided by a circuit breaker. Control: Start and stop the motor and, if applicable: b gradual acceleration b speed control. Overload protection: Protect the starter and the cables against minor overcurrents (< 10 In). Thermal relays provide protection against this type of fault. They may be: b integrated in the short-circuit protective device b separate. Additional specific protection: b limitative fault protection (while the motor is running) b preventive fault protection (monitoring of motor insulation with motor off). Overloads (I < 10 In) An overload may be caused by: b an electrical problem, for instance on the mains (loss of a phase, voltage outside tolerances, etc.) b a mechanical problem, for instance excessive torque due to abnormally high demands by the process or motor damage (bearing vibrations, etc.). A further consequence of these two origins is excessively long starting. Impedance short-circuit (10 < I < 50 In) Deterioration of motor-winding insulation is the primary cause. Short-circuit (I > 50 In) This type of fault is relatively rare. A possible cause may be a connection error during maintenance. Protection against insulation faults This type of protection may be provided by: b a residual current device (RCD) b an insulation monitoring device (IMD).
DB115260
62
8 janvier 2008
545E4003_Ver7.0.indd
Installation guide
Motor protection
Motors P (kW)
0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110
440 V I (A)
1 1.4 1.7 2.4 3.1 4.5 5.8 8 10.5 13.7 19 20 26.5 33 39 52 63 76 90 125 140 178
EZC250 EZC400
63
Installation guide
Capacitor protection
PB101843-22
PB101845-28
EasyPact circuit breaker is suitable for capacitor protection following the rules below:
b Inc = Nominal current of the capacitor
Inc = Nominal Current Capacitor (A) Qc = Reactive power (kVAR) U = Nominal Voltage (V)
EZC100.
EZC250.
DB115748
b Inb = Nominal current of the circuit breaker (EZC) v Inb = 1.36 x Inc for standard equipment v Inb = 1.5 x Inc for overrated type equipment v Inb = 1.12 x Inc for detuned type equipment: 2.7 tuning v Inb = 1.19 x Inc for detuned type equipment: 3.8 tuning v Inb = 1.31 x Inc for detuned type equipment: 4.3 tuning v the short-circuit (magnetic) protection-setting thresholds must enable passage of the energising transients: 10 x Inc for standard, overrated and detuned type equipment. b Icu = Ultimate breaking capacity of the circuit breaker (EZC) Icu short-circuit level is given by the installation.
Circuit Breaker
Example:
Contactor
Capacitor
64
EasyPact
Busbars
2 5 43
66 68 69 70
71 72 73
65
Busbars
Introduction
DB115263
66
Busbars
Introduction
The EasyPact Busbar - engineered and certified together with the EasyPact MCCB to provide superior performance, flexibility and value. Simply the best solution for your distribution panel needs: b available for 250 A, 400 A or 630 A main incoming current b available for 4, 6, 8, 10 or 12 Ways (3 poles) EasyPact 100 A (max.) outgoing MCCBs b 400 A and 630 A systems can accept an additional 2 or 4 EasyPact 250 or Compact NS250 outgoing MCCBs b designed and tested to meet IEC 60439-1 requirements b completely assembled in ISO certified facility for easy installation into locally made enclosures.
EZ116P-70
b Solid copper busbars and connectors for cool, care-free operation. b Electro-tin plating on all busbars and connectors for corrosion resistance in all environments. b Fiberglass reinforced nylon bus supports for strength and dimensional stability. b Molded thermoplastic phase barriers to maintain alignment and ensure electrical isolation between phases.
67
Busbars
Busbars characteristics
The EasyPact Busbar System is designed and certified to meet all international requirements specified in IEC 60439-1 relating to construction of Low Voltage switchgear and controlgear assemblies, including: b verification of temperature - rise limits b verification of dielectric properties b verification of short-circuit withstand strength b verification of clearances and creepage distances. In addition, the system has been type-tested in ASTA labs to confirm the short-circuit and short-time withstand ratings.
EZ148P-60
EZB250
4 6 8 12 18 24 6 8 12 4 6 8 No extension 10 30 14 10 12 36 18 12
EZB400
4 6 8 12 18 24 6 8 12 4 6 8 Yes (2 or 4 Ways) 10 30 14 10 12 36 18 12
EZB630
4 6 8 12 18 24 6 8 12 4 6 8 Yes (2 or 4 Ways) 630 550 690 40 10 30 14 10 12 36 18 12
Extension for EZ/NS breakers Electrical characteristics Rated incoming current (A) Rated operational voltage (V) AC 50/60 Hz Rated insulation voltage (V) Breaking capacity Rated short-time withstand 1 sec. current (kA rms) Dimensions Dimensions H x W x D (mm) 4 Ways 6 Ways 8 Ways 10 Ways 12 Ways
250 400 550 550 690 690 Refer to cascading tables page 60 30 40
268.5 x 416 x 82.5 343.5 x 416 x 82.5 418.5 x 416 x 82.5 493.5 x 416 x 82.5 568.5 x 416 x 82.5
290 x 416 x 107 365 x 416 x 107 440 x 416 x 107 515 x 416 x 107 590 x 416 x 107
290 x 416 x 107 365 x 416 x 107 440 x 416 x 107 515 x 416 x 107 590 x 416 x 107
68
Busbars
Main busbar
EZ149P-60
The core of the EasyPact Busbar System includes the main busbars and outgoing connectors for EasyPact MCCBs. Designation
Type Main busbar current rating Number of ways 4 Ways 6 Ways 8 Ways 10 Ways 12 Ways
Cat. no.
EZB250 250 A EZB250W04 EZB250W06 EZB250W08 EZB250W10 EZB250W12 EZB 400 400 A EZB400W04 EZB400W06 EZB400W08 EZB400W10 EZB400W12 EZB630 630 A EZB630W04 EZB630W06 EZB630W08 EZB630W10 EZB630W12
DB106025
DB106306
DB106307
For applications calling for larger than 100 A outgoing MCCBs, EasyPact Busbar rated 400 A and 630 A can accept the 2 Ways or 4 Ways EasyPact and Compact NS branch extension for up to four additional 250 A max. outgoing circuits. EasyPact and Compact NS branch extensions simply connect directly to the terminals provided on the EZB400 and EZB630 EasyPact Busbar. Designation
EZ/NS/NB branch breaker extension 2 Ways 4 Ways EasyPact and Compact NS branch breaker extension 2 Ways. EZBNS2 EZB2NS2
Cat. no.
69
Busbars
Accessories
Incoming cables with crimped lugs can connect directly to the terminals provided.
>10
= 37
Main connectors
EZ117P-60
For installing a main disconnect device (EasyPact or Compact NS MCCB or INS switch) ahead of EasyPact Busbar, use the tin-plated copper connector kits below. Designation
Main Busbar current rating Main disconnect device for EasyPact or Compact NS or INS switch
Cat. no.
250 A EZB250MCNS 400 A EZB400MCNS 630 A EZB630MCNS
Mechanical lugs
E88309-50
For incoming cables without crimped lugs, use the mechanical lug kits below. Each kit contains three aluminium lugs suitable for copper or aluminium cables. Designation
Main Busbar current rating Incoming cable size Lug kit
DB106043 DB112475
Cat. no.
250 A 16-150 mm2 EZB250MLUG 400 A 35-300mm2 EZB400MLUG 630 A 25-240 mm2 2 cables per phase EZB630MLUG
Connector caps
E88310-54
Connector caps are available to isolate the ends of connectors in positions where branch breakers are not installed. Mounting screws are provided for an insulating barrier (locally provided) to cover the branch connectors when IP2X finger safety is specified. Designation
Connector caps (set of 3) Caps for 100 A outgoings Caps for 250 A outgoings
DB10639
Cat. no.
EZB100CAP EZB250CAP
70
Busbars
Panel layout using the EasyPact Busbar is simple using the guides below. In addition to the mounting locations for the busbar and main disconnect components (if required), make note of the minimum clearances required to the top, bottom and sides of the enclosure.
DB106102
Trim cut-out
DB106120
DB106053
187.4 182.4 -
52 76 -
92.7 90.2 -
24 29 -
109.5 108 -
126 125 -
71
Busbars
Trim cut-out
DB106132
Note: to avoid excess temperature rise on incoming MCCB terminals, panels using 630 A main breaker with these minimum enclosure dimensions require a 7000 mm2 ventilation opening (after subtracting effects of screening) at each of the 4 corners of the enclosure.
72
Busbars
DB106104
270 384 -
175 275 -
57.5 78.5
24 29
61 45.5
52 76
249 232
Trim cut-out
DB106569
73
Notes
74
Notes
75
Notes
76