You are on page 1of 14

Cooling Tower Specification: Capacity : 25 TR kore 250 Tr pojonto briddi poy ebong 250 tr hote 50 TR kore briddi poy.

Fins/PVC Filling : 18 upto 250 RT 24 more than 300 Rt Types of Cooling Tower 1 Natural Cooling Tower 2. Mechanical (a) Induced draft (Counter Flow & Cross Flow) (b) Forced Draft.

Way of Best Choice of Cooling tower 1. Capacity a) Cooling Capacity in RT b) Heat Load in Kcal/Hr c) Circulation water flow rate 2. Overall Dimension a) Width(W) b) Length (L) c) Overall height(H) d) Height 3. Fan Assembly a) Diameter b) Fan speed

c) Air flow m3/h d) Motor rated output 4. Piping Diameter a) Hot water inlet hole b) Cold water outlet hole c) Drain pipe d) Overflow pipe e) Manual make-up water inlet pipe f) Automatic makeup water inlet pipe 5. Make Up a) Evaporation loss % 0.87 b) Drift loss % 0.01 6. Weight a) Dead weight b) Operating weight : almost double of dead weight. 7. Number of Cell NB: 1. Total pump head required for cooling tower circulation pump is the sum of condenser water pressure drop, piping friction loss and tower head. 2. Nominal Tons are defined as 13 Ltr/min/Ton (3.43 US ,GPM/Ton), Cooled from 37 deg C to 32 deg C with 27 deg C wet bulb temperature.

Cooling Tower Infill


ART-H & X Series Counter-Flow Infill improves water distribution by splitting the water stream as it descends through the fill pack. Artisans ART-H & X series design splits the water stream 8 times in a 12 (305mm) vertical path. High thermal performance ( high KaV/L) and low pressure

drop are achieved through engineered flute/microstructure design and the highest manufacturing standards.

1. Bonded edge with dedicated bond points for added durability. 2. Engineered microstructure for improved water distribution and thermal mixing. 3. High thermal performance. 4. Improved water distribution. 5. Square pack that efficiently direct water to both sides of sheet. 6. It is designed according to the water quality.

General Brochure

SL No. Property Unit Typical Value 1 Specific Gravity gm./cu.cm 1.45 max 2 Tensile Strength psi 6000 min 3 Flexural Strength psi 11000 min 4 Elastic Modulus psi 360000 min 5 Heat Deflection oF(264 psi) 160 min 6 Flame Speed rating Less than 5

Surface Area Model ft2/ft3 (m2/m3) ART-H 57 48 (157.5) ART-H 37 48 (157.5) ART-X 37 51 (167.4)

Dimension Sheet Spacing Flute mm Angle 19 19 19 300 300 N/A Sheets per Height ft (mm) 20 20 16 Length (mm) Width (mm) 12'' (305) 12'' (305) 12'' (305)

6.5'' ( 165) 57''(1450) 6.5'' ( 165) 37'' (940) 72" (1829) 37'' (940)

Model ART-H 37 Product Code: PC04001 Model ART-H 37 schematic drawing

Model ART-H 57 Product Code: PC04001 Model ART-H 57 schematic drawing

Model ART-X 37 Product Code: PC04002 Model ART-X 37 schematic drawing

Sprinkler Head Our Cooling Tower Sprinkler Head has its own unique features:
1. Special design to rotate in 5-7 rpm, which gives good thermal performance.

2. Durable, robust sprinkler head is ready for working in very bad quality water 3. Die-casted Aluminum 4. Light weight

General Brochure

Base Pipe Dia: 1.5 inches, 40 NB Distribution Pipe Dia: inches, 20 NB No. of Distribution Point: 4 MOC: Aluminum Threaded End Product Code: PC03007

Base Pipe Dia: 2 inches, 50 NB Distribution Pipe Dia: 1 inches, 25 NB No. of Distribution Point: 4 MOC: Aluminum Threaded End Product Code: PC03008

Base Pipe Dia: 2.5 inches, 65 NB Distribution Pipe Dia: 1 inches, 25 NB No. of Distribution Point: 4 MOC: Aluminum Threaded End Product Code: PC03009

Base Pipe Dia: 3 inches, 75 NB Distribution Pipe Dia: 1.5 inches, 20 NB No. of Distribution Point: 4 MOC: Aluminum Threaded End Product Code: PC03010

Base Pipe Dia: 4 inches, 100 NB Distribution Pipe Dia: 2 inches, 50 NB No. of Distribution Point: 4 MOC: Aluminum SS Nut & Bolt, Teflon Oil Sealed Bearing Product Code: PC03011

Base Pipe Dia: 4 inches, 100 NB Distribution Pipe Dia: 1.5 inches, 40 NB No. of Distribution Point: 6 MOC: Aluminum SS Nut & Bolt, Teflon Oil Sealed Bearing Product Code: PC03012

Base Pipe Dia: 5 inches, 125 NB Distribution Pipe Dia: 2 inches, 50 NB No. of Distribution Point: 4 MOC: Aluminum SS Nut & Bolt, Teflon Oil Sealed Bearing Product Code: PC03013

Base Pipe Dia: 6 inches, 150 NB Distribution Pipe Dia: 3 inches, 75 NB No. of Distribution Point: 4 MOC: Aluminum SS Nut & Bolt, Teflon Oil Sealed Bearing Product Code: PC03014

Base Pipe Dia: 8 inches, 200 NB Distribution Pipe Dia: 3 inches, 75 NB No. of Distribution Point: 6 MOC: Aluminum SS Nut & Bolt, Teflon Oil Sealed Bearing Product Code: PC03015

Base Pipe Dia: 10 inches, 250 NB Distribution Pipe Dia: 3 inches, 75 NB No. of Distribution Point: 8 MOC: Aluminum SS Nut & Bolt, Teflon Oil Sealed Bearing Product Code: PC03017

Base Pipe Dia: 12 inches, 300 NB Distribution Pipe Dia: 3 inches, 75 NB No. of Distribution Point: 10 MOC: Aluminum SS Nut & Bolt, Teflon Oil Sealed Bearing Product Code: PC03018

Cooling Tower Fan

General Brochure

Tip to tip Distance:2950mm (116 inch) Hub Dia:360mm (14 inch) Blade Length: 1070mm (51 inch) SS Clamp with SS Nut & Bolt Product Code: PC03019 Tip to tip Distance:2470mm (97 inch) Hub Dia:330mm (13 inch) Blade Length: 1070mm (42 inch) SS Clamp with SS Nut & Bolt Product Code: PC03020 Tip to tip Distance:2325mm (91.5 inch) Hub Dia:330mm (13 inch) Blade Length: 990mm (39 inch) SS Clamp with SS Nut & Bolt Product Code: PC03021 Tip to tip Distance:2210mm (87 inch) Hub Dia:330mm (13 inch) Blade Length: 940mm (37 inch) SS Clamp with SS Nut & Bolt Product Code: PC03022 Tip to tip Distance:1880mm (74 inch) Hub Dia:305mm (12 inch) Blade Length: 790mm (31 inch) SS Clamp with SS Nut & Bolt Product Code: PC03023 Tip to tip Distance:1780mm (70 inch) Hub Dia:305mm (12 inch) Blade Length: 740mm (29 inch) SS Clamp with SS Nut & Bolt Product Code: PC03024 Tip to tip Distance:1480mm (58 inch) Hub Dia:305mm (12 inch) Blade Length: 590mm (23 inch) SS Clamp with SS Nut & Bolt Product Code: PC03025

Tip to tip Distance:920mm (36 inch) Hub Dia:105mm (4 inch) Blade Length: 410mm (16 inch) SS Nut & Bolt Product Code: PC03026 Tip to tip Distance:610mm (24 inch) Hub Dia:105mm (4 inch) Blade Length: 250mm (10 inch) SS Nut & Bolt Product Code: PC03027 Tip to tip Distance:440mm (17 inch) Hub Dia:80mm (3 inch) Blade Length: 175mm (7inch) SS Nut & Bolt Product Code: PC03028

Cooling-tower-motor

General Brochure

Power rating: 0.75 Kw 1440 rpm TEFC, Insulation Class-F, IP-55 V-440, CI Body PC03001

Air inlet Net

1. 1. PVC Air Inlet Louvre Product Code: PC04003

FRP chemical:
1) Resin Product Code: PC01001 2) Hardener Product Code: PC01002 3) Fibre-glass Product Code: PC01003

User Manuals

Cooling Tower Systems - Trouble Shooting

Lowering Cooling Capacity Trouble Motor Stoppage CAUSE REMEDY

Electric Blackout. Fuse Burn Out. Contact Power Co. 2 Get Proper Fuse. Insufficient Switch Capacity. Bad Switch Change the Proper Switch. Adjust Contact. Contact. Bad Star-Delta Contact. Too Heavy Loads. Lowering of Voltage. Bad Bearing. Adjusts Contact. Lighten to Proper Load. Consult Power Company. Exchange Bearing.

Sudden Lowering of Motor R.P.M. Fan Stoppage

Temperature Rise Motor Temp. Rise. Too Heavy Load. Lowering of Voltage. Lighten Load to Proper Level. Consult Power Company. Send High Surrounding. Out to Repair Shop.

Rise in Water Temperature Water Flow Above Specified Flow. Air Flow Below Specified Flow. Load Higher than Design. Fills Chocked or coated. Correct Flow Rate. Adjust Blade Angles Check and Clean Jali. Adjust Load to correct Flow Rate. Clean/Replace Fills. Use Proper Water Quality (Make Up)

Fresh Air Intake not sufficient or area sufficient or area Improve Ventilation and Ensure Exhaust air near tower not as specified. does not get recycled.

Water Bypassing Fills. Sprinkler Jammed/Water not being Sprinkled and Distributed.

Check Sprinkler Head and Pipe Leakages. Repair Sprinkler and Distribution System.

Water Flow Less Filters Chocked Sprinkler Pipe Chocked Level of Water Low in sump Pump Small Clean Water Filters Clean Pipes and Holes Adjust Float/Inlet Flow Proper Make-up Replace to Correct Flow Volume

Air Flow Low Fan Speed Low Fan Blade Angle Incorrect Inlet Jali Chocked Check Bearing/Motor Correct Blade Angle to Required Setting Clean Air Path

Noise & Vibration Fan Mounting Loose Tighten Mounting Bolts and Correct/Replace if needed. Tighten Blade in Hub Rebalance and Adjust Check and Grease or Replace Bearing on Motor Tighten and use end Plate and shims if required

Fan Blocks Loose Fan Unbalanced Motor Bearing Faulty Hub Mounting on Motor Shaft Loose

Many Parts Rubbing againt Tower Component Give Proper Clearance and Adjust/Align Components.

Water Carry Over Sprinkler Rotation too Fast Adjust Sprinkler Angles as to MAtch the specified rotation Clean up any blockage part Renew Eliminator Adjust as specified below 25 M.M. FT 8 TO FT-30 50 M.M. FT-40 TO FT-80 75 MM. FT-100 AND UP

Blocking of Filter Defective Eliminator Sprinkler too high above fills

Maintenance Schedule Every Day:


Vibrations Are Normal/Noise Normal. Water Distribution Proper. Fan Motor Current Normal. Inlet/Outlet Temperature Of Water Normal.

Every Week:

Clean Inlet Jali To Remove Entrained Matter. Clean Inlet Water Filter. Clean Sprinkler / Nozzles If Chocked. Check Growth of Alger Etc. And Remove From Sump.

Every Month:

Drain Tank, Flush Out and Remove Any Sediment. Check Fills If Clogged Due To Algae, Sediment / Salts, Etc. Check Structure / Frp Casing and Basin Damage and Repaired If Necessary. Clean From Outside With Soap and Water. Check And Tight All Bolts. Smear Bolts with Grease to Facilitate Easy Opening the Next Time.

Every Six Months:


Grease All Bearings Of Motors. Grease All Bearings Of Sprinklers. Check Run out On Fan Motor Shaft.

Clean Blades Of Foreign Matter. Check Fills If Damaged And Replace. Enlace Bearing Of Sprinkler Assembly After 2 Years And Fill With Grease.

You might also like