Professional Documents
Culture Documents
The type of network requires us to consider a fourth one that of short-circuit power.
Short-circuit power
REMEMBER
t a given point, the short-circuit power depends on the network configuration and on its components : generators, lines, cables, transformers, motors
A T
hort-circuit power is the maximum power that a network can supply to equipment with a fault in it. It is expressed either in MVA or in effective kA for a given service voltage.
he rated short time withstand current and its peak value are dependent on the shortcircuit current at a given point of the panel. The breaking and closing capacities required in circuit breakers are determined on the basis of these values.
date
12/91 12 - B
revis
ed
4 05/200
s Merlin Gerin s Square D s Telemecanique
Design rules
Short-circuit power
Introduction
Example 1: 25 kA at an operating voltage of 11 kV
R E
Zcc L
Isc
# The short-circuit power depends directly on the network configuration and the impedance of its components: lines, cables, transformers, motors... through which the short-circuit current passes. # It is the maximum power that the network can provide to an installation during a fault, expressed in kA rms for a given operating voltage or in MVA.
A U B Zs
S sc=
U I sc
U Isc
: :
operating voltage (kV) short-circuit current (kA rms.) Ref: following pages
The short-circuit power can be assimilated to an apparent power. # The value of short-circuit power is generally imposed to us because we rarely have the information required to calculate it. Determination of the short-circuit power requires analysis of the power flows feeding the short-circuit in the worst possible case.
T2
Isc2
Isc3
Example 2: # Feedback via LV Isc5 is only possible if the transformer (T4) is powered by another source. # Three sources (T1-A-T2) are flowing in the switchboard 5 short circuit at A :the CB (D1) sees Isc2 + Isc3 + Isc4 + Isc5 5 short circuit at B :the CB (D2) sees Isc1 + Isc3 + Isc4 + Isc5 o short circuit at C :the CB (D3 sees Isc1 + Isc2 + Isc4 + Isc5
LV T3
Isc5
A D1
B D2 10 kV
C D3
D6 MV
D4
D5
D7
Isc4
T4 LV MV
date
12/91 12 - B -
ed revis
4 05/200
Design rules
Short-circuit currents
All electrical installations have to be protected against short-circuits, without exception, whenever there is an electrical discontinuity; which more generally corresponds to a change in conductor cross-section. The short-circuit current must be calculated at each stage in the installation for the various configurations that are possible within the network; this is in order to determine the characteristics that the equipment has to have withstand or break this fault current.
# In order to choose the right switchgear (circuit breakers or fuses) and set the protection functions, three short-circuit values must be known: 5 minimal short-circuit current:
Isc = kA (rms)
(example: 19 kA rms)
This corresponds to a short-circuit at one end of the protected link (fault at the end of a feeder (see fig.1)) and not just behind the breaking mechanism. Its value allows us to choose the setting of thresholds for overcurrent protection devices and fuses; especially when the length of cables is high and/or when the source is relatively impedant (generator, UPS). 5 short-time withstand current (rms value) :
Ik = kA (rms.) 1 s or 3 s (example: 25 kA rms. 1 s)
This corresponds to a short-circuit in the immediate vicinity of the upstream terminals of the switching device (see fig.1). It is defined in kA for 1 or 3 second(s) and is used to define the thermal withstand of the equipment.
Ik
R MV cable X Isc
5 peak value of the short-circuit current: (value of the initial peak in the transient period)
Ip = (kA peak)
figure 1
(example:2.5 25 kA = 63.75 kA peak IEC 60 056 or 2.7 25 kA = 67.5 kA peak ANSI ) - Ip is equal to: 2.5 Isc at 50 Hz (IEC) or, 2.6 Isc at 60 Hz (IEC) or, 2.7 Isc (ANSI) ( Isc short-circuit current calculated at a given point in the network). It determines the breaking capacity and closing capacity of circuit breakers and switches, as well as the electrodynamic withstand of busbars and switchgear.
DC component
current
I peak= I p
- The IEC uses the following values: 8 - 12.5 - 16 - 20 - 25 - 31.5 - 40 kA rms. These are generally used in the specifications.
time
N.B.: # A specification may give one value in kA rms and one value in MVA as below: Isc = 19 kA rms or 350 MVA at 10 kV 5 if we calculate the equivalent current at 350 MVA we find:
350 I sc = ----------------- = 20.2 kA rms 3 / 10 The difference lies in the way in which we round up the value and in local habits. The value 19 kA rms is probably the most realistic. 5 another explanation is possible: in medium and high voltage, IEC 60909 applies a coefficient of 1.1 when calculating maximal Isc.
U E I sc = 1 ,1 / ---------------------- = -------3 / Zsc Z sc This coefficient of 1.1 takes account of a voltage drop of 10 % across the faulty installation (cables, etc).
date
12/91 12 - B
revis ed
4 05/200
Design rules
Short-circuit currents
Transformer
In order to determine the short-circuit current across the terminals of a transformer, we need to know its short-circuit voltage (Usc %). # Usc % is defined in the following way:
The short-circuit current depends on the type of equipment installed on the network (transformers, generators, motors, lines, etc).
potentiometer
U : 0 Usc
primary
secondary
I : 0 Ir
1 the voltage transformer is not powered: U = 0 2 place the secondary in short-circuit 3 gradually increase voltage U at the primary up to the rated current I in r
the transformer secondary circuit. Example: # Transformer Sr=20 MVA # Voltage Ur=10 kV # Usc% = 10 % # Upstream power: infinite 20 000 Sr - = 1 150 A - = ----------------I r = -----------------------------3 * Ur 3 / 10 Ir 1 150 I k = -------- = -------------------- = 11 500 A = 11.5 kA U sc % 10 100
Usc% = Usc*100 / Ur
# The short-circuit current, expressed in kA, is given by the following equation: Ir I k = --------U s c%
date
12/91 12 - B
revis
ed
4 05/200
Design rules
Short-circuit currents
Example: Calculation method for an alternator or a synchronous motor # Alternator 15 MVA # Voltage U = 10 kV # Xd = 20 % Sr 15 I r = ---------------- = ---------------------------- = 870 A / Ur / 10 000 Ir 870 I sc = ----------------------= --------------- = 4 350 A = 4.35 kA Xsc trans. 20/100
Ir
fault appears
Isc
time
sub-transient stage
transient stage
permanent stage
short-circuit
Ir I sc = --------X sc%
1
X sc
: short-circuit reactance in %
Sub-transient Xd
10 - 20 %
Transient Xd
15 - 25 %
Permanent Xd
200 - 350 %
Asynchronous motor
# For asynchronous motors 5 the short-circuit current across the terminals equals the start-up current Isc
date
12/91 12 - B
revis ed
5 the contribution of the motors (current feedback) to the short-circuit current is equal to: I 3 Ir The coefficient of 3, takes account of motors when stopped and the impedance to go right through to the fault.
5
4 05/200
5 at 8 Ir
Design rules
Short-circuit currents
# Three-phase short-circuit
S sc I sc U2 1.1 * U * I sc * 3 = -------Z sc 1.1 * U -------------------- with 3 * Z sc Z sc =
R + X
R --- = X
sub-transient 10 to 20 % 15 to 25 %
transient 15 to 25 % 25 to 35 %
# Transformers
(order of magnitude: for real values, refer to data given by manufacturer)
E.g.:
20 kV/410 V; Sr = 630 kVA; Usc = 4 % 63 kV/11 V; Sr = 10 MVA; Usc = 9 % U 2 U sc (%) Z( ) = ------ ---------------Sr 100
Sr (kVA) Usc (%) 100 to 3150 4 to 7.5 MV/LV 5000 to 5000 8 to 12 HV/MV
# Cables
date
12/91 12 - B
revis
ed
4 05/200
Design rules
Short-circuit currents
only sub-transient
Isc Isc
# Fault arcing I sc I d = ------------------1.3 to 2 # Equivalent impedance of a component through a transformer 5 for example, for a low voltage fault, the contribution of an HV cable upstream of an HV/LV transformer will be:
2 R2 = R1 (U2) et U1 2 X2 = X1 (U2) U1 2 Z2 = Z1 (U2) U1
ainsi
This equation is valid for all voltage levels in the cable, in other words, even through several series-mounted transformers.
supply Ra, Xa
MV cable R1, X1
# Triangle of impedances Z = (R + X
2 2
Z X
date
12/91 12 - B
r
05/200
evised
7 7
n
5 to 8 Ir 3 Ir ,
A
LV cable R2, X2
Design rules
Short-circuit currents
# The method involves: 5 breaking down the network into sections 5 calculating the values of R and X for each component 5 calculating for the network: - the equivalent value of R or X - the equivalent value of impedance - the short-circuit current. Example 1: # The three-phase short-circuit current is:
Network layout
Tr1 Tr2
Isc =--------------------
U 3 Z sc
Equivalent layouts
Zr Zt1 Za Zt2
Isc U Zsc
: : :
short-circuit current (in kA) phase to phase voltage at the point in question before the appearance of the fault, in kV. short-circuit impedance (in ohms)
Za
12/91 12 - B
revis
10 Isc = - = 21.38 kA 3 0, 72
ed
4 05/200
Design rules
Short-circuit currents
Exercice data
Supply at 63 kV Short-circuit power of the source: 2 000 MVA # Network configuration: Two parallel mounted transformers and an alternator. # Equipment characteristics: 5 transformers: - voltage 63 kV / 10 kV - apparent power: 1 to 15 MVA, 1 to 20 MVA - short-circuit voltage: Usc = 10 % 5 Alternator : - voltage: 10 kV - apparent power: 15 MVA - Xd transient: 20 % - X"d sub-transient: 15 % # Question: 5 determine the value of short-circuit current at the busbars, 5 the breaking and closing capacities of the circuit breakers D1 to D7.
63 kV
Transformer 15 MVA Usc = 10 %
T2
D3
D1 10 kV
D2
Busbars
D4
D5
D6
D7
date
12/91 12 - B
revis
ed
4 05/200
Design rules
Short-circuit currents
Zr = network impedance
Za = alternator impedance different according to state (transient or subtransient) Z20 = transformer impedance 20 MVA
busbars
Experience shows that the resistance is generally low compared with, reactance, so we can therefore deduce that the reactance is equal to the impedance (X = Z).
date
12/91 12 - B
revis ed
4 05/200
10
Design rules
Short-circuit currents
Component
Calculation U 10 Zr = -------- = -------------S sc 2 000 10 10 U -----Z15 = ---- U s c = -----15 100 Sr U 10 10 Z20 = --- ------ U s c = -----20 100 Sr
2 Za = U ----- Xsc Sr 2 20 10 Zat = -------- -----15 100 2 2 2 2 2 2
Z = X (ohms)
0.05
Network Ssc = 2 000 MVA U op. = 10 kV 15 MVA transformer (Usc = 10 %) U op. = 10 kV 20 MVA transformer (Usc = 10 %) U op. = 10 kV 15 MVA alternator U op. = 10 kV Transient state (Xsc = 20 %) Sub-transient state (Xsc = 15 %) Busbars Parallel-mounted with the transformers Series-mounted with the network and the transformer impedance Parallel-mounting of the generator set Transient state Sub-transient state
0.67 0.5
15 10 Zas = -------- -----15 100 0.67 0.5 Z15 Z20 Z15 ||Z20 = --------------------------- = ------------------------Z15 + Z20 0.67 + 0.5 Zr + Zet = 0 . 05 + 0 . 29 Zer Zat 0.34 1.33 Zer || Zat = ------------------------- = ---------------------------Zer + Zat 0.34 + 1.33 Zer Zat 0.34 1 - = --------------------Zer || Zat = ------------------------Zer + Zat 0.34 + 1 Breaking capacity
in kA rms. 10 1 U2 I s c = ---------------------- = ------ -------3 Zsc 3 Zsc
Circuit breaker
Equivalent circuit
Z (ohm)
Closing capacity
2.5 Isc (in kA peak)
N.B.: a circuit breaker is defined for a certain breaking capacity of an rms value in a steady state, and as a percentage of the aperiodic component which depends on the circuit breakers opening time and on R --X of the network (about 30 %). For alternators the aperiodic component is very high; the calculations must be validated by laboratory tests.
D4 to D7
Zr Za Z15 Z20
21.40
17 Zsc = 0.34
17 2.5 = 42.5
date
12/91 B12
revis ed
12.4 2.5 = 31
4 05/200
Zt = (Zr + Z15)//Za 11
7 7
0.27 0.25
Design rules
Busbar calculation
Introduction
# The dimensions of busbars are determined taking account of normal operating conditions. The voltage (kV) that the installation operates at determines the phase to phase and phase to earth distance and also determines the height and shape of the supports. The rated current flowing through the busbars is used to determine the cross-section and type of conductors. # We then ensure that the supports (insulators) resist the mechanical effects and that the bars resist the mechanical and thermal effects due to short-circuit currents. We also have to check that the period of vibration intrinsic to the bars themselves is not resonant with the current period. # To carry out a busbar calculation, we have to use the following physical and electrical characteristics : Busbar electrical characteristics
Ssc Ur U Ir : : : : network short-circuit power* rated voltage operating voltage rated current MVA kV kV A
In reality, a busbar calculation involves checking that it provides sufficient thermal and electrodynamic withstand and non-resonance.
* N.B.: It is is generally provided by the customer in this form or we can calculate it having the Isc U; see chapter on "Shortshort-circuit current lsc and the operating voltage U: (Ssc = circuit currents").
cm C C
n
( - n )
: :
aluminium edge-mounted
In summary: bar(s) of
date
cm
cm
per phase
12/91 12 - B
revis
ed
4 05/200
12
Design rules
Busbar calculation
Temperature rise
Taken from table V of standard IEC 60 694
Temperature (C)
( - n) with n = 40 C
50 65 60 75 75 60 65 65 60
date
12/91 12 - B
revis
ed
4 05/200
13
Design rules
Busbar calculation
Temperature rise
Extract from table V of standard IEC 60 694
Temperature (C)
( - n) with n = 40 C
75 90 80 105 105 90 90 90 90
35 50 40 65 65 50 50 50 50
1
According to its function, the same device may belong to several categories given in table V. In this case, the admissible values of temperature and temperature rise to take into consideration are the lowest for category concerned. For vacuum switchgear, the limit values of temperature and temperature rise do not apply to vacuum devices. Other devices must not exceed the values for temperature and temperature rise given in table V. All the necessary precautions must be taken so that absolutely no damage is caused to surrounding materials. When the contact components are protected in different manners, the temperatures and temperature rises that are allowed are those of the element for which table V authorises the lowest values. The quality of coating must be such that a protective layer remains in the contact zone: - after the making and breaking test (if it exists), - after the short time withstand current test, - after the mechanical endurance test, according to specifications specific to each piece of equipment. Should this not be true, the contacts must be considered as "bare". For fuse contacts, the temperature rise must be in conformity with publications concerning high voltage fuses.
date
12/91 12 - B
revis
ed
4 05/200
14
Design rules
Busbar calculation
Thermal withstand...
Lets check if the cross-section that has been chosen: ... bar(s) of ... x ... cm per phase satisfies the temperature rises produced by the rated current and by the short-circuit current passing through them for 1 to 3 second(s).
with:
I : permissible current expressed in amperes (A) derating in terms of current should be considered: - for an ambient temperature greater than 40C - for a protection index greater than IP5 ambient temperature (n 40C) permissible temperature rise* busbar cross section outside busbar perimete
(opposite diagram)
n
( - n)
: : : :
C C cm2 cm r
p
S
outside perimeter of the bars
20
: : : : :
1.83 cm 2.90 cm
conditions coefficient product of 6 coefficients (k1, k2, k3, k4, k5, k6), described below *(see table V of standard IEC 60 694 in the previous pages)
# Coefficient k1 is a function of the number of bar strips per phase for: 5 1 bar (k1 = 1) 5 2 or 3 bars, see table below:
0.05 0.06 no. of bars per phase 2 1.63 1.73 3 2.40 2.45 0.08 1.76 2.50 e/a 0.10 0.12 k1 1.80 1.83 2.55 2.60 0.14 1.85 2.63 0.16 1.87 2.65 0.18 1.89 2.68 0.20 1.91 2.70
e
date
12/91 12 - B
revis
ed
4 05/200
15
Design rules
Busbar calculation
# Coefficient k2 is a function of surface condition of the busbars: 5 bare: k2 = 1 5 painted: k2 = 1.15 # Coefficient k3 is a function of the position of the bars: 5 edge-mounted bars (vertical): k3 = 1 5 1 bar base-mounted (horizontal): k3 = 0.95 5 several base-mounted bars (horizontal): k3 = 0.75 # Coefficient k4 is a function of the place where the bars are installed: 5 calm indoor atmosphere: k4 = 1 5 calm outdoor atmosphere: k4 = 1.2 5 bars in non-ventilated ducting: k4 = 0.80 # Coefficient k5 is a function of the artificial ventilation: 5 without artificial ventilation: k5 = 1 5 ventilation should be dealt with on a case by case basis and then validated by testing. # Coefficient k6 is a function of the type of current: 5 for a alternatif current of frequency 60 Hz, k6 is a function of the number of bars n per phase and of their spacing. The value of k6 for a spacing equal to the thickness of the bars:
n k6 1 1 2 1 3 0.98
In our case: n=
giving k6 =
In fact we have: k=
I=
I=
date
12/91 12 - B
revis
ed
4 05/200
16
Design rules
Busbar calculation
cc
0 ,24 20 I k t k = -----------------------------------------------2 (n / S) c
2
with:
sc
c : : short-circuit temperature rise specific heat of the metal copper: aluminium: cross section of one bar number of bar(s) per phase is the short-time withstand current: (maximum short-circuit current, rms value ) : short-time withstand current duration (1 to 3 s) s
S n Ik :
: :
A rms
Example : How can we find the value of Ith for a different duration? Knowing: (Ik)2 t = constant # If Ik 2 = 26.16 kA rms. 2 s, what does Ith1 correspond to for tk = 1 s ? (Ik 2)2 t = constant (26.16 103)2 2 = 137 107
tk
density of the metal copper: aluminium: resistivity of the conductor at 20C copper: aluminium: permissible temperature rise
20
( - n)
so Ik 1 =
10 --------------------) ( 137 1
7
sc =
Ik 1 = 37 kA rms. for 1 s # In summary : 5 at 26.16 kA rms. 2 s, it corresponds to 37 kA rms. 1 s 5 at 37 kA rms. 1 s, it corresponds to 26.16 kA rms. 2 s
0.24 (
10-6 ( )2
)2
t =C sc =
( t = n + ( n ) + sc )
t =
n = ambiant temperature
Check:
date
12/91 12 - B
revis ed
4 05/200
Check that this temperature t is compatible with the maximum temperature of the parts in contact with the busbars (especially the insulator).
17
Design rules
Busbar calculation
Electrodynamic withstand
Forces between parallel-mounted conductors
We have to check if the bars chosen withstand the electrodynamic forces.
The electrodynamic forces are given by the equation:
l 8 F 1 = 2 -- l dyn 2 10 d
with
F1 Idyn
: :
force expressed in daN is the peak value of short-circuit expressed in A, to be calculated with the equation below: Ssc I p = k ----------- = k Ik U 3
F1 Ip F1 Ip
Ssc Ik U l d k
: : : : : :
short-circuit power short-time withstand current operating voltage distance between insulators on the same phase phase to phase distance 2.5 for 50 Hz ; 2.6 for 60 Hz for IEC and 2.7 according to ANSI
kVA
A rms
kV cm cm
Giving :
Ip =
A and F1 =
daN
H+h F = F 1 ------------H
d
with
F H h : : : force expressed insulator height distance from insulator head to busbar centre of gravity daN cm cm
h = e/2 F1 F H support
5
1.14
date
12/91 12 - B
revis
ed
4 05/200
# The force found after applying a coefficient k should be compared with the mechanical strength of the support to which we will apply a safety coefficient: 5 the supports used have a bending resistance F = daN check if F > F 5 we have a safety coefficient of F --- =
F
18
Design rules
Busbar calculation
F1 v = ------------ -12 l
with
: is the resultant strain, it must be less than the permissible strain for the bars this is: copper 1/4 hard: 1 200 daN/cm2 copper 1/2 hard: 2 300 daN/cm2 copper 4/4 hard: 3 000 daN/cm2 tin-plated alu: 1 200 daN/cm2 force between conductors distance between insulators in the same phase is the modulus of inertia between a bar or a set of bars
(choose the value in the table on the following page)
F1 l
: :
daN
cm
I/v
cm3
distance between the fibre that is neutral and the fibre with the highest strain (the furthest)
phase 1 b v h
phase 2
x'
phase 1 v b
phase 2 x
b h3 I = 2 ( -------------- + S d 2 ) 12
3 ) bh + S d 2 2 ------------- 12 I ------ = ---------------------------------------------1.5 h v
d h
S : cross section of one bar (in cm2)
x'
xx : perpendicular to the plane of vibration
date
12/91 12 - B 4
Check:
ed revis
05/200
< Bars Cu or Al
(in daN/cm2)
19
Design rules
Busbar calculation
Choose your cross-section S, linear mass m, modulus of inertia I/v, moment of inertia l for the bars defined below: Busbar dimensions (mm)
S cm2 Arrangement* m Cu linear mass kg/cm
x
100 x 10 10 0.089 0.027 0.83 1.66 83.33 16.66 21.66 14.45 166.66 33.33 82.5 33 250 50
80 x 10 8 0.071 0.022 0.66 1.33 42.66 10.66 17.33 11.55 85.33 21.33 66 26.4 128 32
80 x 6 4.8 0.043 0.013 0.144 0.48 25.6 6.4 3.74 4.16 51.2 12.8 14.25 9.5 76.8 19.2
80 x 5 4 0.036 0.011 0.083 0.33 21.33 5.33 2.16 2.88 42.66 10.66 8.25 6.6 64 16
80 x 3 2.4 0.021 0.006 0.018 0.12 12.8 3.2 0.47 1.04 25.6 6.4 1.78 2.38 38.4 9.6
50 x 10 5 0.044 0.014 0.416 0.83 10.41 4.16 10.83 7.22 20.83 8.33 41.25 16.5 31.25 12.5
50 x 8 4 0.036 0.011 0.213 0.53 8.33 3.33 5.54 4.62 16.66 6.66 21.12 10.56 25 10
50 x 6 3 0.027 0.008 0.09 0.3 6.25 2.5 2.34 2.6 12.5 5 8.91 5.94 18.75 7.5
50 x 5 2.5 0.022 0.007 0.05 0.2 5.2 2.08 1.35 1.8 10.41 4.16 5.16 4.13 15.62 6.25
I
x
x
cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3
I/v I
x
x
I/v I
x
x
I/v I
x
x
I/v I
x
x
I/v I
I/v
f E
: :
resonant frequency in Hz modulus of elasticity: for copper = 1.3 106 daN/cm2 for aluminium A5/L = 0.67 106 daN/cm2 linear mass of the busbar (choose the value on the table above) length between 2 supports or bushings moment of inertia of the busbar cross-section relative to the axis x'x, perpendicular to the vibrating plane kg/cm
cm
cm4 (see formula previously explained or choose the value in the table above)
date
12/91 12 - B
revis
giving
f=
Hz
ed
05/200
We must check that this frequency for 50Hz: is outside of the values that must be avoided, in other words between 42 and 58and 80 and 115 Hz.
20
Design rules
Busbar calculation
Exercise data
# Consider a switchboard comprised of at least 5 MV cubicles. Each cubicle has 3 insulators(1 per phase). Busbars comprising 2 bars per phase, inter-connect the cubicles electrically.
10 18 70 40 50
cm2 cm cm C C
n
( - n) profile material
Ccubicle 1 Ccubicle 2 Ccubicle3 Ccubicle 4 Ccubicle 5
flat busbars in copper 1/4 hard, with a permissible strain = 1 200 daN/cm2 edge-mounted
arrangement:
d d
# The busbars must be able to withstand a rated current Ir = 2,500 A on a permanent basis and a short-time withstand current Ik = 31,500 A rms. for a time of tk = 3 seconds. # Rated frequency fr = 50 Hz # Other characteristics: 5 parts in contact with the busbars can withstand a maximum temperature of max = 100C 5 the supports used have a bending resistance of F = 1 000 daN
1 cm
1 cm
10 cm 5 cm
12 cm
date
12/91 12 - B
revis
ed
4 05/200
21
Design rules
Busbar calculation
0
24.9 ( n ) S p I = K ------------------------------------------------------------------20 [ 1 + ( 20 )]
with:
l : : : : : : permissible current expressed in amperes (A) ambient temperature permissible temperature rise* busbar cross-section busbar perimeter resistivity of the conductor at 20C copper: 1.83 cm
n
( - n) S
40 50 10 22
C C cm2 cm
p
e
p20
0.004
condition coefficient product of 6 coefficients (k1, k2, k3, k4, k5, k6), described below
e /a
0.05 0.06 0.08 0.10 number of bars per phase 2 1.63 1.73 1.76 1.80 3 2.40 2.45 2.50 2.55 0.12 0.14 k1 1.83 1.85 2.60 2.63 0.16 1.87 2.65 0.18 1.89 2.68 0.20 1.91 2.70
giving k1 =
12/91 12 - B ed revis
4 05/200
22
Design rules
Busbar calculation
# Coefficient k2 is a function of the surface condition of the bars: k2 = 1 5 bare: k2 = 1.15 5 painted: # Coefficient k3 is a function of the busbar position: k3 = 1 5 edge-mounted busbars: 5 1 bar flat-mounted: k3 = 0.95 k3 = 0.75 5 several flat-mounted bars: # Coefficient k4 is a function of where the bars are installed: k4 = 1 5 calm indoor atmosphere: 5 calm outdoor atmosphere: k4 = 1.2 5 bars in non-ventilated ducting: k4 = 0.80 # Coefficient k5 is a function of the artificial ventilation: k5 = 1 5 without artificial ventilation: 5 cases with ventilation must be treated on a case by case basis and then validated by testing. # Coefficient k6 is a function of the type of current: 5 for alternatif current at a frequency of 60 Hz, k6 is a function of the number of busbars n per phase and of their spacing. The value of k6 for a spacing equal to the thickness of the busbars:
n k6 1 1 2 1 3 0.98
In our case: n= 2
giving k6 = 1
0.8
= 1.44
0 . 61 0.5 0 . 39 24 . 9 ( n ) S p I = K -----------------------------------------------------------------------------20 [ 1 + ( 20 ) ]
I=
date
2 689
12/91 12 - B
ed revis
05/200
Ir < I
23
Design rules
Busbar calculation
The equation below can be used to calculate the temperature rise due to short-circuit:
0 . 24 20 I th 2 t k cc = ----------------------------------------------------------2 (n S) c
with: c S
n
specific heat of the metal copper: is the cross section expressed in cm2 number of bars per phase is the short-time withstand current
(rms. value of the maximum shortcircuit current)
: : :
Ith tk
20
: :
short-time withstand current duration (1 to 3 secs) density of the metal copper: resistivity of the conductor at 20C copper: permissible temperature rise
in secs
( - n) :
5 The temperature rise due to the short circuit is: Calculation of t must be looked at in more detail because the required busbars have to withstand Ir = 2 500 A at most and not 2 689 A.
cc =
t = n + ( n ) + cc
=
40 94
+ C
50
date
for I =
2 689
12/91 12 - B
revis
ed
4 05/200
24
Design rules
Busbar calculation
# Let us fine tune the calculation for t for Ir = 2 500 A (rated current for the busbars) 5 the MELSON & BOTH equation (cf: page 31), allows us to deduce the following: I = constant (- n) 0.61 et Ir = constant () 0.61 therefore= I = (-n) 0.61 Ir ()
( )
2 689 2 500
( ( ) )
50
0.61
50 =
689 ( 22 500 )
1
0.61
50 = 1.126 = 44.3 C 5 temperature t of the conductor after short-circuit, for a rated current Ir = 2 500 A is: t = n + + cc
=
40
+ 44.3
= 88.3
C for Ir = 2 500 A
date
12/91 12 - B
revis
ed
4 05/200
25
Design rules
Busbar calculation
F1 = 2 l d
ldyn2 G 10-8
l d k
: : :
70 18
cm cm
2.5
Idyn :
F1 = 2 / (70/18) / 78 7502 /10-8 = 482.3 daN Forces at the head of the supports or busducts
Equation to calculate forces on a support :
F = F1 G H + h H
with
F H h : : : force expressed in daN insulator height distance from the head of the insulator to the busbar centre of gravity
12 5
cm cm
5 1,14 daN
giving F = 683
date
778
12/91 12 - B
r evised
The supports used have a bending resistance F = 1 000 daN calculated force F = 778 daN. The solution is OK
05/200
26
Design rules
Busbar calculation
12
with
l : : is the resultant strain in daN/cm2 distance between insulators in the same phase : is the modulus of inertia of a busbar or of a set of busbars
(value chosen in the table below)
70
cm
I/v
14.45 cm3
.3 70 1 = 482 - 12 14 . 45 = 195 daN / cm2 The calculated resultant strain ( = 195 daN / cm2) is less than the permissible strain for the copper busbars 1/4 hard (1200 daN / cm2) : The solution is OK Busbar dimensions (mm)
100 x 10 Arrangement
x
S m daN/cm I
cm2 Cu A5/L cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3 cm4 cm3
10 0.089 0.027 0,83 1.66 83.33 16.66 21.66 14.45 166.66 33.33 82.5 33 250 50
x x
I/v I
x x
I/v I
x x
I/v I
x x
I/v I
date
12/91 12 - B
ed revis
x x
I/v I
4 05/200
I/v
27
Design rules
Busbar calculation
m l
: :
0.089 70
daN/cm
cm
21.66
cm4
f is outside of the values that have to be avoided, in other words 42 to 58 Hz and 80 to 115 Hz:
The solution is OK
In conclusion
bars of
date
12/91 12 - B
revis ed
4 05/200
28