AUXILIARY RELAYS FOR TRIPPING APPLICATIONS

This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products described here.

Moving together

INDEX
4. 4.

Answers for any tripping application Technical standards General characteristics Range of products Trip relays Trip and lockout relays Trip circuit supervision relays Auxiliary supply circuit supervision relays High / low burden configuration Breaking capacity Pick-up voltage/release voltage-temperature charts Model selection Dimensions and panel mounting cut-off

5. . 6.

7. 11.

13. 14. 15.

16. 22.

24. 26.

Auxiliary relays | Tripping applications

ANSWER FOR ANY TRIPPING APPLICATION


ARTECHE offers a wide range of relays specially designed to be used in circuit breaker tripping applications.

Interface Trip Trip The

between protection and control equipments and HV and/or MV circuit breakers, eliminating risks in case of internal failure of the circuit breaker. contacts multiplication, to operate directly on the circuit breaker and transmit the corresponding alarms in a minimum time. and lock-out, with electric or hand reset to avoid accidental closing of circuit breakers associated to power transformers, generators or machines. surveillance of the trip circuit, guarantees it is in perfect conditions to allow the trip when it is needed.

TECHNICAL STANDARDS
GENERAL STANDARDS
In addition to the specific applicable standards, ARTECHE auxiliary relays are designed based on the fulfilment of the following standards:

IEC 61810: Electromechanical all-or-nothing relays. IEC 60255: Electrical relays. Measuring relays
equipment.

and protection

IEC 61812: Specified time relays for industrial use. IEC 61812: Rels de tiempo especificado para IEC 60947: Low-voltage switchgear and controlgear. IEC 61000: Electromagnetic compatibility.
industriales.

aplicaciones

Auxiliary relays | Tripping applications

GENERAL CHARACTERISTICS
Some of the general characteristics of the ARTECHE trip relays are:

High

Fast

isolation level between input and output circuit, which guarantees that a problem in the circuit breaker will not cause irreparable damages on the protection system. operating times, down to 3 ms, minimizing the impact on the total trip time. operation on highly inductive circuits.

High breaking capacity, which allows direct Sturdy design, which ensures high reliability. Wide range of auxiliary voltage (Vdc and Self-cleaning of the contacts. Security contacts according to EN 50205. Easy installation (plug-in relays with Designed
different installation possibilities). to work in permanent service, even at high temperature for the whole voltage range. to work in environments with relative humidity of 100%. characteristics, allowing their use in installations which can be subject to vibrations, as for example in power stations or in regions with high risk of seism. protection degree (IP40), with transparent cover, making them appropriate for tropical and saline environments. of the most demanding standards: IEC, EN, IEEE, CE and UL mark. Vac).

Possibility Seismic High

Fulfilment

No maintenance needed.

In addition, the different number of alternatives that are offered when the equipment is selected, both technically (increase of the breaking capacity by serial contacts or by the magnetic blow out, high speed operation of the output contacts, possibility of adding different options to the relay) and in the assembly method (front, rear or flush mounted sockets, with screws or fastons) must be considered.

E322124
UL Recognized Component Marks for USA and Canada: The combined UL signs for the USA and Canada are recognized by the authorities of both countries. All auxiliary relays identified with this mark meet the requirements of both countries. Auxiliary relays | Tripping applications

RANGE OF PRODUCTS
TRIP RELAYS
Instantaneous trip relays, whose contacts change instantaneously from the rest position to the working position when the coil is energized. The contacts return to the rest position when the coil is no longer energized. This range includes relays with 2, 4 and 8 contacts, with operating times from 3 ms to 8 ms, depending on the model. All the relays include a diode in parallel with the coil (see auxiliary relays with overvoltage protection characteristic) and comply with the sock and vibration standards, related to the relays with seismic characteristics.

TRIP AND LOCKOUT RELAYS


Trip relays with 2 stable positions for the output contacts. Depending on which coil is energized, the contacts will change from one position to the other. The design of the ARTECHE relays has no consumption in permanence, and prevents both coils from being energized simultaneously. This range includes relays with 3, 4 and 8 contacts, with operating times below 10 ms, depending on the model, and possibility of manual reset. The position change is made with 2 sets of coils with separated entrances, in BF-3 and BJ-8, and with breaking-flame contacts for each set of coils.

TRIP CIRCUIT SUPERVISION RELAYS


For single phase or three phase circuit breakers. Through a small supervision current the whole circuit is supervised, in both positions of the circuit breaker (opened or closed). The correct state of the circuit is showed with a green LED on the front plate of the relay. The output contacts change its position if the relay detects a failure in the continuity of the circuit.

AUXILIARY SUPPLY CIRCUIT SUPERVISION RELAYS


Auxiliary relay with four changeover contacts, aimed to supervise the failure of trip supply. Connecting the relay across the trip circuit supply, the equipment is normally energized. Faults will occur when the trip voltage is lost, so the relay drops off in those cases, providing the related signs and alarms.In order to avoid faulty alarms due to instantaneous supply voltage dips, the drop off time of the relay is delayed over 100 ms so those non-permanent failures of trip supply would not be considered.

Auxiliary relays | Tripping applications

TRIP RELAYS

World-class range of

auxiliary relays for energy sector, specially designed for the most demanding applications

Auxiliary relays | Tripping applications

TRIP RELAYS (I)


Model RD-2R RD-2XR RF-4R RF-4XR

Applications

Intended for tripping applications where high demanding requirements in operating time (with tripping time from 8ms to 3 ms) and breaking capacity are needed, that is the case of tripping HV and MV circuit breakers.

High burden configuration Construction characteristics Contacts no.

not available

See page 15 for technical details

2 Changeover

4 Changeover
11 3 7 12 4 5 (-) 1 6 8 13 9 14 10

(+) 2 3

7 5 8 6

(+) 2

Connections
(-) 1

Options Weight (g) Dimensions (mm) Coil characteristics Standard voltages(1)

With 0P options LED included Diode in parallel with the coil included 125 22,5 x 50,4 x 72 250 42,5 x 50,4 x 72 (F short Type)

24, 48, 110, 125, 220, 250 (4) Vdc /110, 127, 230 Vac (50-60Hz)

24, 48, 110, 125, 220, 250 (4) Vdc

24, 48, 110, 125, 220, 250 (4) Vdc / 110, 127, 230 Vac (50-60 Hz)

24, 48, 110, 125, 220, 250 (4) Vdc

Voltage range Pick-up voltage Release voltage Consumptions In permanence (UN) Peak 96 Vdc Peak >96 Vdc Operating time Pick-up time Drop-out time Contacts Contact material Contacts resistance(2) Distance between contacts Permanent current Instantaneous current Max. making capacity Breaking capacity Max. breaking capacity Umax opened contact Perfomance data Mechanical endurance Operating temperature Storage temperature Max. operating humidity Operating altitude(3)
(1) (2)

+10% -20% UN See pick-up/release voltage-temperature curves 0,95 W 0,8 A / 20 ms 0,3 A / 20 ms 2,5 A / 20 ms 0,8 A / 20 ms 0,8 A / 20 ms 0,3 A / 20 ms 1W 2,5 A / 20 ms 0,8 A / 20 ms

<8 ms (<10 ms Vac) Vdc: <40 ms Vac: <50 ms

<5,5 ms Vdc: <40 ms

<8 ms (<10 ms Vac) Vdc: <40 ms Vac: <50 ms

<5,5 ms Vdc: <40 ms

AgNi 30 m 1,2 mm 10 A 30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms 40 A / 0,5 s / 110 Vdc See breaking capacity curves (Contact configuration type B) See value for 50.000 operations 250 Vdc / 400 Vac

107 operations -25C +70C -30C +70C 93% / +40C <2000 m


(3) (4)

Other voltage upon request Guarantee data for relays just manufactured

Ask for higher altitudes Voltage not recognized by UL

Auxiliary relays | Tripping applications

TRIP RELAYS (II)


Model RJ-8R RJ-8XR RJ-4XR4

Applications High burden configuration Construction characteristics Contacts no.

Intended for tripping applications where high quality requirements in operating time (with models even tripping in less than 3 ms) and breaking capacity are needed, that is the case of tripping HV and MV circuit breakers.

See page 15 for technical details

See page 15 for technical details

not available

8 Changeover
10 1 2 3 11 20 21 30 31 40 4 5 (-) a 6 7 8 41 50 51 60 61 70 71 80 81

4 Changeover + 4 Fast Singles-Inversors without break power


10 1 2 3 (+) d 4 11 20 30 31 40 41 50 (-) a 51 60 6 7 8 61 70 71 80 81 High breaking capacity 5 Trip 21

Connections

(+) d

Options Weight (g) Dimensions (mm) Coil characteristics


Standard voltages(1)

With 0P options LED included Diode in parallel with the coil included

500 82,5 x 50,4 x 72 (J short type)

335 42,5 x 50,4 x 82,5 (F short Type)

24, 48, 110, 125, 220, 250 (4) Vdc/110, 127, 230 Vac (50-60 Hz)

24, 48, 110, 125, 220, 250(4) Vdc

110, 125, 220, 250

(4)

Vdc

Voltage range Pick-up voltage / Release voltage Consumptions In permanence (UN) Peak 96 Vdc Peak >96 Vdc Operating time Pick-up time Drop-out time Contacts Contact material Contacts resistance(2) Distance between contacts Distance between contacts Instantaneous current Max. making capacity Breaking capacity Max. breaking capacity Umax opened contact Perfomance data Mechanical endurance Operating temperature Storage temperature Max. operating humidity 0,8 A / 20 ms 0,3 A / 20 ms

+10% -20% UN See pick-up/release voltage-temperature curves 1,4 W 2,5 A / 20 ms 0,8 A / 20 ms

+15% -20% UN 6,5 W 25 W / 5 ms

<8 ms Vdc (<10 ms Vac) (Range 24 Vdc <10 ms) Vdc: <40 ms Vac: <50 ms

<6,5 ms Vdc: <40 ms

Contacts 1-4: <3 ms Contacts 5-8: <20 ms Contacts 1-4: <25 ms Contacts 5-8: <50 ms

AgNi 30 m 1,2 mm 10 A

Contacts 1-4: AgNi 10 Contacts 5-8: Ag1000

Contacts 5-8: 1,2 mm Contacts 5-8: 15 A Contacts 1-4: 8 A

30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms 40 A / 0,5 s / 110 Vdc See breaking capacity curves (Contact configuration type B) See value for 50,000 operations 250 Vdc / 400 Vac

107 operations -25C +70C -30C +70C 93% / +40C <2000 m


(3) (4)

Operating altitude(3)
(1) (2)

Other voltage upon request Guarantee data for relays just manufactured

Ask for higher altitudes Voltage not recognized by UL

Auxiliary relays | Tripping applications

TRIP RELAYS (III)


Model RXR-4

Applications

Tripping applications with very high speed requirements

High burden configuration


Construction characteristics Contacts no.

not available

4 Changeover

NC1 C1 NO1 NC2 C2 NO2 NC3 C3 NO3 NC4 C4 NO4

Connections

(-) 1

(+) 2

Options Weight (g) Dimensions (mm) Coil characteristics Standard voltages(1) Voltage range Pick-up voltage Release voltage Consumptions Operating time Pick-up time Drop-out time Contacts Contact material Permanent current Max. making capacity Breaking capacity Umax opened contact Performance data Mechanical endurance Operating temperature Storage temperature Max. operating humidity Operating altitude(2)
(1) (2)

No options available 126 53 x 90 x 58

110, 125, 250 Vdc

+10% -20% UN 40% 28% <3 W

<3 ms <3 ms

AgNi 8A 15 A during 4s See breaking capacity curves 250 Vdc / 400 Vac

107 operations
-10C +55C -30C +70C 93% / +40C <2,000 m

Other voltage upon request Ask for higher altitudes

10

Auxiliary relays | Tripping applications

TRIP AND LOCKOUT RELAYS (I)


Model BF-3R BF-4R BJ-8R

Applications High burden configuration Construction characteristics Contacts no.

Intended for trip and lockout applications where high demanding requirements in operating time and breaking capacity are needed.

not available

See page 15 for technical details

See page 15 for technical details

3 Changeover

4 Changeover

8 Changeover
10 1 2 Set d + c Reset = b + a 3 4 5 6 7 8 11 20 21 30 31 40 41 50 51 60 61 70 71 80 81

Set -

11 3 4 5 7 12 8 13 9

Set -

Connections

+ 2 1

+ 1

11 3 4 7 12 8 13 5 9 14 6 10

Reset =

Reset =

+ 14 10

2 + B1

Options Weight (g) Dimensions (mm) Coil characteristics Standard voltages(1) Voltage range Pick-up voltage Consumptions only in the change-over Operating time Pick-up time Contacts Contact material Distance between contacts Permanent current Instantaneous current Max. making capacity Breaking capacity Max. breaking capacity Umax opened contact Performance data Mechanical endurance Operating temperature Storage temperature Max. operating humidity Operating altitude(2)
(1) (2)

Options are not available 300 45 x 45 x 96,5 (F short Type) 600

90 x 50 x 100,5 (J short Type)

24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac (50-60 Hz) +10% -20% UN See pick-up voltage / temperature curves for Latching relays 27 W 23 W 35,5 W

<10 ms (Vdc) <20 ms (Vac)

<10 ms (Vdc) <20 ms (Vac)

AgNi 1,8 mm 10 A 880 A during 200 ms / 200 A during 10 ms 40 A / 0,5 s / 110 Vdc See breaking capacity curves (Contact configuration type A) See value for 50.000 operations 250 Vdc / 400 Vac

107 operations -40C +70C -40C +70C 93% / +40C <2000 m

Other voltage upon request Ask for higher altitudes

Auxiliary relays | Tripping applications

11

TRIP AND LOCKOUT RELAYS (II)


Model BF-4RP BJ-8RP

Applications High burden configuration Construction characteristics Contacts no.

Intended for tripping and locking applications where high quality requirements in operating time and breaking capacity are needed, with manual reset.

See page 15 for technical details


4 Changeover

See page 15 for technical details


8 Changeover
10 1 2 Set 11 20 21 30 3 4 5 6 7 8 31 40 c Reset = b + a 41 50 51 60 61 70 71 80 81

Set -

Connections

+ 1

11 3 4 7 12 8 13 5 9 14 6 10

d +

2 Reset = + B1

Options Weight (g) Dimensions (mm) Coil characteristics Standard voltages(1) Voltage range Pick-up voltage (20C) Consumptions only in the change-over Operating time Pick-up time Contacts Contact material Distance between contacts Permanent current Instantaneous current Max. making capacity Breaking capacity Max. breaking capacity Umax opened contact Performance data Mechanical endurance Operating temperature Storage temperature Max. operating humidity Operating altitude(2)
(1) (2)

Options are not available 300 45 x 45 x 96,5 (F short Type) 600

90 x 50 x 100,5 (J short Type)

24, 48, 72, 110, 125, 220 Vdc 63,5, 110, 127, 230 Vac (50-60 Hz)

+10% -20% UN See pick-up voltage / temperature curves for Latching relays 23 W 35,5 W

<10 ms (Vdc) <13 ms (Vac)

<10 ms (Vdc) <20 ms (Vac)

AgNi 1,8 mm 10 A 80 A during 200 ms / 200 A during 10 ms 40 A / 0,5 s / 110 Vdc See breaking capacity curves (Contact configuration type A) See value for 50,000 operations 250 Vdc / 400 Vac

107 operations -40C +70C -40C +70C 93% / +40C <2000 m

Other voltage upon request Ask for higher altitudes

12

Auxiliary relays | Tripping applications

TRIP CIRCUIT SUPERVISION RELAYS


Model VDF-10 VDJ-30

Applications Construction characteristics Timing Contacts no.

Trip circuit supervision for single-phase circuit breakers

Trip circuit supervision for three-phase circuit breakers

2 Changeover

2 Changeover

+ FU TRIP SUPPLY
FU

Connections
6 5

Trip contact

TRIP SUPPLY
1 Trip contact 2 Trip contact 3 Trip contact

1 K2

K1

h 40 30 41 10 21

52b

52b

52a

52b

CB1

CB2

CB3
CIRCUIT BREAKER

CB
CIRCUIT BREAKER
FU TRIP SUPPLY -

FU TRIP SUPPLY -

Options Weight (g) Dimensions (mm) Coil characteristics Standard voltages(1) Voltage range Pick-up voltage (23 C) Release voltage (23 C) Consumptions Operating time Drop-out time Contacts Contact material Permanent current Instantaneous current Max. making capacity Max. breaking capacity Umax opened contact Performance data Mechanical endurance Operating temperature Storage temperature Max. operating humidity Operating altitude(2)
(1) (2)

Options are not available 100 42,5 x 50,4 x 96,6 (F short Type) 163 82,5 x 50,5 x 96,6 (J short Type)

24/30, 60, 110/125, 220 Vdc, 110/127, 230 Vac (50-60 Hz)

+10% -25% UN 70% UN 50% UN 3,1 W 3,63 W

>200 ms

AgNi 8A 15 A 15 A during 4 s 0,3 A / 110 Vdc 250 Vdc / 400 Vac

107 operations -10C +55C -30C +70C 93% / +40C <2000 m

Other voltage upon request Ask for higher altitudes

52b

10

14

13

12

20

11

52a

52a

52a

70

31

71

K23

K22

K13

K21

K12

K11

Auxiliary relays | Tripping applications

13

AUXILIARY SUPPLY SUPERVISION RELAYS


Model RUT-4

Applications Construction characteristics Timing Contacts no.

Supervise only the auxiliary supply circuit of the protection equipments, avoiding false alarms due to short-time drop of supply

4 Changeover

11 3 (+) 1
Connections

7 12 8 13 9 14 10

4 5

(-) 2 6
Options Weight (g) Dimensions (mm) Coil characteristics Standard voltages (1) Voltage range Pick-up voltage Release voltage Consumptions in permanence Operating time Pick-up time Drop-out time To minimum voltage Maximum <20 ms >100 ms <400 ms

Options are not available


250 42,5 x 50,4 x 96,6 (F large Type)

24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac

+10% -20% UN See pick-up release voltage-temperature curves for standard relays 3,9 W

Contacts Contact material Contacts resistance (2) Distance between contacts Permanent current Instantaneous current Max. making capacity Breaking capacity Max. breaking capacity Umax opened contact Performance data Mechanical endurance Operating temperature Storage temperature Max. operating humidity Operating altitude(3)
(1) (2) (3)

AgNi

30 m
1,8 mm

10 A
80 A during 200 ms / 200 A during 10 ms 40 A / 0,5 s / 110 Vdc See breaking capacity curves (Contact Configuration Type A) See value for 50.000 operations 250 Vdc / 400 Vac

107 operations -10C +55C -30C +70C 93% / +40C <2000 m

Other voltage upon request Guarantee data for relays just manufactured Ask for higher altitudes

14

Auxiliary relays | Tripping applications

HIGH / LOW BURDEN CONFIGURATION


(HIGH SPEED TRIPPING RELAYS ONLY)
The standard high speed tripping relays are manufactured with a low burden configuration, considering that the initiating contact is placed close to the tripping relay. However, and in order to avoid unwanted trip relay operation due to pickup or transients, particularly if the relay operating coil is connected to extensive wiring, ARTECHE tripping relays could be manufactured with a high burden configuration, complying with ESI 48-4 international standard, as EB2 class relays. These EB2 class relays are suitable for use in high security circuit breaker tripping circuits, increasing their immunity to capacitance discharge currents. For relays with rated voltage up to and including the 125 V, the relays will withstand, without operating, a discharge into their operate circuits of a 10F capacitor charged to 120% of the higher rated voltage for the relay. For relays with rated voltage of 220 V, the relays will withstand, without operating a discharge into their operate circuits of a 10F capacitor charged to 100% of the higher rated voltage for the relay, i.e 242 V. Specifications: ESI 48-4 EB1: 1983 ESI 48-4 EB2: 1983 Low Burden High Burden

HIGH BURDEN RELAYS CONSUMPTIONS


Instantaneous relays (self reset relays): same consumption as low burden configuration Latching relays (electric and hand&electric reset): See table below

Electrical reset and hand and electrical reset relays

Standard Voltage Consumption (only in commutation)

220 Vdc < 150 W (peak)

125 Vdc < 100 W (peak)

24 Vdc < 75 W (peak)

Auxiliary relays | Tripping applications

15

BREAKING CAPACITY

With devices operating


worldwide, also heavy industries like oil & gas sector trust in our relays.

16

Auxiliary relays | Tripping applications

BREAKING CAPACITY
The breaking capacity is a critical parameter on the design and the applications of the relays. Its mechanical life could be considerably reduced, depending on the value of the load (especially with heavy duty loads), the number of operations and the environmental conditions in which the relay is operating. In any configuration, ARTECHEs auxiliary relays have a high breaking capacity values. These limits are showed in the table below, in terms of power and current values. In all the cases, these relays guarantee a right performance during 50,000 operations. Likewise, the values showed in the following charts have been obtained in standard conditions in the laboratory, and they could be different in real conditions. In any case, the possibility of connecting serial contacts or a bigger distance between contacts makes these values to be considerably increased.

ELECTRICAL ENDURANCE MODEL RXR:


107

250 Vac resistive load


106

AgN90/10 2 x 8A

Cycles 105

DC-coll AC-coll

104

10

12

14

16

Switching current (A)

ELECTRICAL ENDURANCE OTHER MODELS

24 Vdc voltage Different loads configurations.


Resistive load: Highly inductive load:

L/R= 0 ms.
10000000 107

L/R= 40 ms.
10000000 107

No. operations

100000 105

100000 105

104 10000 0 0,00

5 5,00

10 10,00 Current

15,00 15

20,00 20

10000 104 0,00 25,00 25 0

No. operations

106 1000000

1000000 106

2,00 2

4,00 4

6,00 6
Current

8,00 8

10 10,00

12,00 12

Type A Type B

0 ms

20 ms

40 ms

Vdc

Contact configuration Type A

P(W)

I(A)

P(W)

I(A)

P(W)

I(A)

24 Type B

500 450

20,83 18,75

370 300

15,42 12,50

250 210

10,42 8,75

Auxiliary relays | Tripping applications

17

110 Vdc voltage Different loads configurations.


Resistive load: Highly inductive load:

L/R= 0 ms.
10000000 107
10000000 107

L/R= 40 ms.

No. operations

1000000 106

106 1000000

100000 105

100000 105

10000 104 0 0,00

No. operations

1 1,00

2 2,00

3 3,00

4 4,00

5 5,00 Current

6 6,00

7 7,00

8 8,00

9 9,00

10 10,00

104 10000 0 0,00

1 1,00

2 2,00

3 3,00

4 4,00

5 5,00

6 6,00

7 7,00

Type A Type B

2 contacts type A 2 contacts type B

Current

0 ms

20 ms

40 ms

Vdc

Contacts configuration Type A

P(W)

I(A)

P(W)

I(A)

P(W)

I(A)

170 125

1,55 1,14

140 100

1,27 0,91

90 65

0,82 0,59

Type B

110

2 contacts type A 2 contacts type B

1.360 874

12,36 7,95

1.106 742

10,05 6,74

730 482

6,63 4,38

125 Vdc voltage Different loads configurations.


Resistive load: Highly inductive load:

L/R= 0 ms.
10000000 107
107

L/R= 40 ms.

No. operations

No. operations

1000000 106

106

100000 105

105

104 10000 0 0,00

104 1 1,00 2 2,00 3 3,00 4 4,00 5 5,00 Current 6 6,00 7 7,00 8 8,00 9 9,00 10 10,00

0,5

1,5

2 Current

2,5

3,5

Type A Type B

2 contacts type A 2 contacts type B Auxiliary relays | Tripping applications

18

0 ms

20 ms

40 ms

Vdc

Contacts configuration Type A

P(W)

I(A)

P(W)

I(A)

P(W)

I(A)

158 125

1,26 1

120 96

0,96 0,77

75 65

0,60 0,52

Type B 125 2 contacts type A 2 contacts type B

987,5 528,547

7,90 4,23

733,809 395,983

5,87 3,17

472,972 263,827

3,78 2,11

220 Vdc voltage Different loads configurations.


Resistive load: Highly inductive load:

L/R= 0 ms.
10000000 107

L/R= 40 ms.
10000000 107

No. operations

100000 105

10000 104 0,00 0,00

0,20 0,20

0,40 0,40

0,60 0,60

0,80 0,80

1,00 1,00

1,20 1,20

1,40 1,40

1,60 1,60

No. operations

1000000 106

1000000 106

100000 105

10000 104 0,00 0,00

0,10 0,10

0,20 0,20

0,30 0,30

0,40 0,40

0,50 0,50

0,60 0,60

0,70 0,70

0,80 0,80

Current

Current

Type A Type B

2 contacts type A 2 contacts type B

0 ms

20 ms

40 ms

Vdc

Contacts configuration Type A

P(W)

I(A)

P(W)

I(A)

P(W)

I(A)

150 125

0,68 0,57

115 104

0,52 0,47

66 60

0,30 0,27

Type B 220 2 contacts type A 2 contacts type B

319 242

1,45 1,10

234 177

1,06 0,81

134 100

0,61 0,45

Auxiliary relays | Tripping applications

19

HOW TO SELECT THE CURVE OF MY RELAY


These charts show the breaking capacity values, either for resistive and highly inductive loads, in three voltage values of reference (ask for other voltage values). The charts show two different curves:

Type

Type

A: Breaking capacity of the relays with distance between contacts = 1.8 mm. B: Breaking capacity of the relays with distance between contacts = 1.2 mm. and distance between contacts=1.8 mm. and distance between contacts=1.2 mm.

2 contacts type A: Breaking capacity for relays with serial contacts,

2 contacts type B: Breaking capacity for relays with serial contacts,


The distance between contacts is shown in the tables of technical data.

HOW THE BREAKING CAPACITY CAN BE INCREASED


ARTECHEs auxiliary relays are power relays, designed specially to have a high breaking capacity. Thus, there are applications where the loads are so high that it is necessary to even increase the breaking capacity, keeping the reliability of the contacts of the auxiliary relays. Recommendations to increase breaking capacity:

Connect

Include the magnetic blow-out option: This option is indicated for

contacts in series. The breaking capacity is increased considerably, guaranteeing the right performance during a high number of operations. See curves for two contacts.

safety applications (back-up) where the load values are extremely high. The mechanical life of the relay is reduced, but it is able to open very high loads for a certain number of operations.

These values of high breaking capacity are represented in the following table, where the high capacity of the output contacts of ARTECHEs auxiliary relays is proved:

Equipe With contact configuration Type A + magnetic blow out (OP: 1XXXX) With contact configuration Type B + magnetic blow out (OP: 1XXXX) 2 contacts type A + magnetic blow out (OP: 1XXXX) 2 contacts type B + magnetic blow out (OP: 1XXXX)

L/R

5A

125 Vdc

40 ms

15 A

125 Vdc

40 ms

20

Auxiliary relays | Tripping applications

Arteche has more than 100 customer service technical points, an expert engineers network close to you everywhere.

PICK-UP VOLTAGE/RELEASE VOLTAGE-TEMPERATURE CHARTS

22

Auxiliary relays | Tripping applications

Variability of operative voltage range against temperature for the instantaneous auxiliary relays.

TRIPPING RELAYS
Operative range temperature.
200

against

ambient

Upper limit of the pick-up voltage


150

U/UN (%)

Pick-up voltage limit


100

Drop-out voltage limit Operative range of the coil voltage

50

0 -40

-30

-20

-10

10

20

30

40

50

60

70

80

Temperature (C)

TRIP AND LOCKOUT RELAY


Operative range temperature.
200

against

ambient

160

Upper limit of the pick-up voltage


120

U/UN (%)

Pick-up voltage limit


80

Operative range of the coil voltage

40

0 -40 -30 -20

-10

10

20

30

40

50

60

70

80

90

100

110 120 130

Temperature (C)

TRIP AND LOCKOUT RELAYS WITH RESET PUSH BUTTON


Operative range temperature.
U/Un [%]
200

against

ambient

160

Upper limit of the pick-up voltage U/UN (%)


120

Pick-up voltage limit


80

Operative range of the coil voltage

40

0 -40 -30 -20

-10

10

20

30

40

50

60

70

80

90

100

110 120 130

Temperature (C)
Auxiliary relays | Tripping applications

23

MODEL SELECTION
TRIP
Type Range Aux. Supply Options OP Relay type 2 contacts relay 2 contacts relay 4 contacts relay 4 contacts relay 8 contacts relay 8 contacts relay Ultra-fast (only Vdc) Ultra-fast (only Vdc) RD-2R RD-2XR RF-4R RF-4XR RJ-8R RJ-8XR RJ-4XR4 RXR-4 1 1 1 1 1 1 1 1 0 0 0 Restrictions

Range High Burden Low burden Aux. Supply Vdc o Vac Indicate voltage level and if it is VDC or VAC (ex: 24 VDC) Options High breaking capacity (magnetic arc blow-out) No Yes 0 1 HB -

Front LED

No Yes No Yes

0 1 0 1

Mechanical contact position indicator

Trip flag

No Yes

0 1

Push to test button

No Yes

0 1

24

Auxiliary relays | Tripping applications

Trip and lockout

Type

Range

Aux. Supply

Relay type 3 contacts relay 4 contacts relay 4 contacts relay 8 contacts relay 8 contacts relay BF-3R BF-4R BF-4RP BJ-8R BJ-8R -

Range High Burden Low burden Aux. Supply Vdc o Vac Indicate voltage level and if it is VDC or VAC (ex: 24 VDC) HB -

Trip circuit supervision

Type

Aux. Supply

Relay type One phase Three phase VDF-10 OP VDJ-30 OP

Aux. Supply Vdc o Vac Indicate voltage level and if it is VDC or VAC (ex: 24 VDC)

Auxiliary supply circuit supervision

Type

Aux. Supply

Relay type One phase RUT-4 OP

Aux. Supply Vdc o Vac Indicate voltage level and if it is VDC or VAC (ex: 24 VDC)

Auxiliary relays | Tripping applications

25

DIMENSIONS OF THE RELAYS


Type D Type F
F Short

Type J
J Short

Type RXR

53 22,5
50,4 50,4

42,5
50,4

82,5
90

10,5

Relay dimensions

F Long

10,5

J Long

10,5

72

72

72

42,5
50,4 50,4

82,5

58 53

10,5

10,5

96,6

*100,5 96,6
*depending on the model

33,1

14,19

SOCKETS: DIMENSIONS AND CUT-OUT


Sockets Relay Type TIP10 Front connection D IP20 Front connection Rear connection IP10 Front connection F IP20 Front connection IP20 Rear connection IP20 Flush mounting IP10 Front connection J IP20 Front connection IP20 Rear connection IP20 Flush mounting Screw DN-DE IP10 DN-DE IP20 DN-TR OP FN-DE IP10 FN-DE IP20 FN-TR OP F-EMP OP JN-DE IP10 JN-DE IP20 JN-TR OP J-EMP OP JN-DE2C IP10 JN-DE2C IP20 JN-TR2C OP Accessories Faston Double faston DN-DE2C IP10 DN-DE2C IP20 DN-TR2C OP FN-DE2C IP10 FN-DE2C IP20 FN-TR2C OP Weight (g) 60 60 50 110 110 90 300 225 225 180 400 Accessories Retaining clips Function signs on the extraction ring Security pins

26

Auxiliary relays | Tripping applications

45

Relays type D
DN-DE IP10 DN-DE2C IP10

Relays type F
FN-DE IP10 FN-DE2C IP10

Relays type J
JN-DE IP10 JN-DE2C IP10

24 23

44 43
64 64 105 105

84 83
64 105

Front connection for double faston IP10 sockets DN-DE2C IP10 FN-DE2C IP10 JN-DE2C IP10

Sockets for DIN rail


(1) (2)

28

29 32,3

29 48 32,3 88

29 32,3

DN-DE IP20 DN-DE2C IP20

FN-DE IP20 FN-DE2C IP20

JN-DE IP20 JN-DE2C IP20

22,7 19,8

31 29

42,7 39,8

31 29

82,7 79,8

31 29

112

112

112

lateral connection for the rest of the sockets

DN-TR OP DN-TR2C OP

FN-TR OP FN-TR2C OP

JN-TR OP JN-TR2C OP

51,2

51,2

21
= = =

- 0,2 40,5 +

41,8

42

- 0,2 80,5 +

42

42

F-EMP OP F-EMP (short) OP

J-EMP OP J-EMP (short) OP

80

80

75

120

Sockets for ush mounting

15 12,5

F-EMP OP F-EMP (long) OP

J-EMP OP J-EMP (long) OP


80

80

75

15 8 12,5 8 15 12,5

106 96 66 57

4,5

66 57

Cut-out

90 min

125

Cut-out

66 57

R2

80 min
Cut-out

90 min
(1)

DIN rail according to EN50022

(2)

Minimum distance between sockets will depend on type of relay and

DIN46277/3

sockets. Please request sockets user manual for more detailed information.

90 min

61 50

Cut-out

42

12,5

120

4,5

41,8 15
106 96
4,5

51,2

Sockets for rear connection

24 20

43 6

44 40

43

84 80

43

101,5
124

101,5
124

125

Auxiliary relays | Tripping applications

27

Updates: ARTECHE_CT_Tripping-relays_EN Version: C1

www.arteche.com

Arteche