Displays Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight,

etc. Feature linearisation, scaling, and difference measurement functions for programming via PReset software. Ex interfaces Interfaces for analogue and digital signals as well as HART signals between sensors / I/P converters / frequency signals and control systems in Ex zone 0, 1 & 2 and for some modules in zone 20, 21 & 22. Isolation Galvanic isolators for analogue and digital signals as well as HART signals. A wide product range with both loop-powered and universal isolators featuring linearisation, inversion, and scaling of output signals. Temperature A wide selection of transmitters for DIN form B mounting and DIN rail modules with analogue and digital bus communication ranging from applicationspecific to universal transmitters. Universal PC or front programmable modules with universal options for input, output and supply. This range offers a number of advanced features such as process calibration, linearisation and auto-diagnosis.

DK Side 1 UK Page 23 FR Page 45 DE Seite 67

5714
Programmable LED Indicator
No. 5714V101-IN (0951) F r o m s e r. n o . 0 6 0 1 3 7 0 0 1

SIGNALS THE BEST

Programmable LED indicator PReview 5714

Table of contents
Warnings............................................................................. Safety instructions. .............................................................. Declaration of Conformity................................................... Front and back layout......................................................... Applications. ........................................................................ Technical characteristics..................................................... Mounting............................................................................. Applications. ........................................................................ Order................................................................................... Electrical specifications. ...................................................... Sensor error detection........................................................ Connections........................................................................ Block diagram..................................................................... Routing diagram. ................................................................. Scrolling help text............................................................... Configuration / operating the function keys....................... Graphic depiction of the relay function setpoint ............... 24 25 27 28 29 29 29 30 31 29 35 36 37 38 40 42 43

22

23

WARNING!
This module is designed for connection to hazardous electric voltages. Ignoring this warning can result in severe personal injury or mechanical damage. To avoid the risk of electric shock and fire, the safety instructions of this manual must be observed and the guidelines followed. The specifications must not be exceeded, and the module must only be applied as described in the following. Prior to the commissioning of the module, this manual must be examined carefully. Only qualified personnel (technicians) should install this module. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Safety instructions
Definitions: Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000 Volt AC. Technicians are qualified persons educated or trained to mount, operate, and also troubleshoot technically correct and in accordance with safety regulations. Operators, being familiar with the contents of this manual, adjust and operate the knobs or potentiometers during normal operation. Receipt and unpacking: Unpack the device without damaging it. The packing should always follow the device until this has been permanently mounted. Check at the receipt of the device whether the type corresponds to the one ordered. Environment: Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. All modules fall under Installation Category II, Pollution Degree 1, and Insulation Class II. Mounting: Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these should connect the module. Should there be any doubt as to the correct handling of the module, please contact your local distributor or, alternatively, PR electronics A/S, Lerbakken 10, DK-8410 Rnde, Denmark, tel: +45 86 37 26 77. Mounting and connection of the module should comply with national legislation for mounting of electric materials, i.a. wire cross section, protective fuse, and location. Descriptions of Input / Output and supply connections are shown in the block diagram and side label.

GENERaL

WARNING!
HAzARD OUS VOLTAGE
Until the module is fixed, do not connect hazardous voltages to the module. The following operations should only be carried out on a disconnected module and under ESD safe conditions: Troubleshooting the module. Repair of the module must be done by PR electronics A/S only.

Symbol identification
Triangle with an exclamation mark: Warning / demand. Potentially lethal situations. The CE mark proves the compliance of the module with the essential requirements of the directives.

24

25

The following apply to fixed hazardous voltages-connected modules: The max. size of the protective fuse is 10 A and, together with a power switch, it should be easily accessible and close to the module. The power switch should be marked with a label telling it will switch off the voltage to the module. UL installation requirements: For use on a flat surface of a type 1 enclosure Use 60/75C copper conducters only Max. ambient temperature...................... 60C Max. wire size, pins 41...46.................... AWG 30-16 Max. wire size, others............................. AWG 30-12 UL file number. ........................................ E248256 Calibration and Adjustment: During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the specifications of this manual. The technician must use tools and instruments that are safe to use. Normal operation: Operators are only allowed to adjust and operate modules that are safely fixed in panels, etc., thus avoiding the danger of personal injury and damage. This means there is no electrical shock hazard, and the module is easily accessible. Cleaning: When disconnected, the module may be cleaned with a cloth moistened with distilled water. Liability: To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.

DECLARATION OF CONFORMITY
As manufacturer PR electronics A/S Lerbakken 10 DK-8410 Rnde hereby declares that the following product: Type: 5714 Name: Programmable LED indicator is in conformity with the following directives and standards: The EMC Directive 2004/108/EC and later amendments EN 61326-1 For specification of the acceptable EMC performance level, refer to the electrical specifications for the module. The Low Voltage Directive 2006/95/EC and later amendments EN 61010-1

Rnde, 22 December 2009

Kim Rasmussen Manufacturers signature

26

27

Front and back layout


Programmable LED indicator PReview 5714


4-digit 14-segment LED indicator Input for mA, V, potentiometer, RTD and TC 2 relays and analogue output Universal voltage supply Front key programmable

Application:
Display for digital readout of current, voltage, temperature or potentiometer signals. Picture 1: Front of PReview 5714. Process control with 2 pairs of potential-free relays and / or analogue output. For local readout in extremely wet atmospheres with a specially designed splash-proof cover.

Technical characteristics:
4-digit LED indicator with 13.8 mm 14-segment characters. Max. display read out -1999...9999 with programmable decimal point, relay ON / OFF indication. All operational parameters can be adjusted to any application by use of the front keys. PReview 5714 is available fully-configured acc. to specifications ready for process control and visualisation. Help texts in eight languages can be selected via a menu item. In versions with relay outputs the user can minimise the installation test time by activating / deactivating each relay independently of the input signal. Picture 2: Back of PReview 5714.

Mounting:
To be mounted in front panel. The included rubber packing must be mounted between the panel cutout hole and the display front to obtain IP65 (NEMA 4) tightness. For extra protection in extreme environments, PReview 5714 can be delivered with a speially designed splash-proof cover as accessory.

28

29

Applications
Input signals:
Current
+

Order: 5714

Type
46 RTD Potentio Connection, wires 4 3 2 meter 45 44 TC 43 42
1 2

Version Standard . . . . . . . . . . . . . . . . . . : 2 relays . . . . . . . . . . . . . . . . . . . : Analogue output . . . . . . . . . . . . : Analogue output and 2 relys . . . : A B C D

5714

2-wire transmitter

Voltage
+

NB! Please order the splash-proof cover seperately. Order No. 8335.

41

Electrical specifications: Specifications range: -20C to +60C Common specifications: Supply voltage, universal............................. 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC Consumption
26 25 24

Output signals:

Type 5714A 5714B 5714C 5714D

Internal consumption 2.2 W 2.7 W 2.7 W 3.2 W

Max. consumption 2.5 W 3.0 W 3.0 W 3.5W

12
+

23 22

11 Analogue, 0/4...20 mA 21 2 changeover relays

Supply:
32 21.6...253 VAC or 19.2...300 VDC 31

Isolation voltage, test / operation............... 2.3 kVAC / 250 VAC Signal- / noise ratio..................................... Min. 60 dB (0...100 kHz) Response time (0...90 %, 100...10 %), programmable: Temperature input. ................................. 1...60 s Current / voltage input.......................... 0.4...60 s Calibration temperature.............................. 20...28C Accuracy, the greater of general and basic values:
General values Input type Absolute accuracy 0.1% of reading Temperature coefficient 0.01% of reading / C

All

30

31

Basic values Input type mA Volt Potentiometer Pt100 Ni100 TC type: E, J, K, L, N, T, U TC type: R, S, W3, W5, LR TC type: B 85...400C TC type: B 400...1820C Basic accuracy 4 A 20 V 0.1 0.2C 0.3C 1C 2C 4.5C 2C Temperature coefficient 0.4 A / C 2 V / C 0.01 / C 0.02C / C 0.03C / C 0.05C / C 0.2C / C 0.45C / C 0.2C / C

Sensor current, RTD. .................................... Effect of sensor cable resistance (3- / 4-wire), RTD. ........................................ Sensor error detection, RTD........................ Short curcuit detection, RTD....................... TC input: Type B E J K L N R S T U W3 W5 LR Min. value 0C -100C -100C -180C -200C -180C -50C -50C -200C -200C 0C 0C -200C Max. value +1820C +1000C +1200C +1372C +900C +1300C +1760C +1760C +400C +600C +2300C +2300C +800C

Nom. 0.2 mA < 0.002 / Yes < 15

Standard IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1 DIN 43710 IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1 DIN 43710 ASTM E988-90 ASTM E988-90 GOST 3044-84

EMC immunity influence...................................... < 0,5% of reading Auxiliary supplies: 2 wire supply (pin 46...45)............................ Wire size, pin 41...46 (max.)......................... Wire size, others (max.)................................ Relative humidity.......................................... Dimensions (HxWxD). ................................... Cutout dimensions....................................... Protection degree (mounted in panel). ......... Weight.......................................................... RTD and potentiometer input: Input type Pt100 Ni100 Potentiometer Min. value -200C -60C 10 Max. value +850C +250C 100 k 25...15 VDC / 0...20 mA 1 x 1.5 mm2 stranded wire 1 x 2.5 mm2 stranded wire < 95% RH (non cond.) 48 x 96 x 120 mm 44.5 x 91.5 mm IP65 230 g

NB.: TC input type B can be measured and configured down to 0C, but the basic accuracy is only valid in the range 85...1820C Cold junction compensation (CJC) via internally mounted sensor................ Sensor error detection, all TC types............ Sensor error detection................................. Sensor error current: when detecting. ..................................... else......................................................... Current input: Measurement range..................................... Programmable measurement ranges........... Input resistance............................................ Sensor error detection: loop break 4...20 mA.............................. Voltage input: Measurement range..................................... Programmable measurement ranges........... < 2.0C 0.2C/C Yes Yes Nom. 2 A 0 A 0...20 mA 0...20 and 4...20 mA Nom. 20 + PTC 25 Yes

Standard IEC60751 DIN 43760 -

Input for RTD types: Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000 Cable resistance pr. wire, RTD (max.).......... 50

0...12 VDC 0...1 / 0,2...1 / 0...10 / 2...10 VDC Input resistance............................................ Nom. 10 M

32

33

Outputs: Display: Display readout............................................ Decimal point............................................... Digit height................................................... Display updating.......................................... Input outside input range is indicated by. ................................................. Current outout: Signal range (span). ...................................... Programmable signal ranges.......................
Load (max.). .................................................. Load stability................................................ Sensor error detection................................. NAMUR NE 43 up / downscale................... Output limitation: on 4...20 and 20...4 mA signals............. on 0...20 and 20...0 mA signals............. Current limit.................................................. Relay outputs: Relay function.............................................. Hysteresis, in % / display counts................ On and Off delay.......................................... Sensor error detection................................. Max. voltage. ................................................ Max. current................................................. Max. AC power............................................ Max. current at 24 VDC............................... Marine approval: Det Norske Veritas, Ships & Offshore.......... GOST R approval: VNIIM, Cert. no.. ........................................... Observed authority requirements: EMC 2004/108/EC....................................... LVD 2006/95/EC........................................... UL, Standard for Safety............................... -1999...9999 (4 digits) Programmable 13.8 mm 2.2 times / s Explanatory text 0...20 mA 0...20 / 4...20 / 20...0 / 20...4 mA 20 mA / 800 / 16 VDC 0.01% of span / 100 0 / 3.5 / 23 mA / none 23 mA / 3.5 mA 3,8...20.5 mA 0...20.5 mA 28 mA Setpoint 0.1...25% / 1...2999 0...3600 s Make / Break / Hold 250 VRMS 2 A / AC 500 VA 1A Standard for Certification No. 2.4 See www.prelectronics.com Standard: EN 61326-1 EN 61010-1 UL 508

Sensor error detection / sensor error detection outside range:


Sensor error check in 5714 variants Variant: 5714A 5714B 5714C 5714D Configuration Always: ERR1=NONE, ERR2=NONE: else: O.ERR=NONE: else: ERR1=NONE, ERR2=NONE, O.ERR=NONE: else: Sensor error detection: ON OFF ON OFF ON OFF ON

Input VOLT

CURR POTM TEMP

Outside range readout (IN.LO, IN.HI): If the valid range of the A/D converter or the polynomial is exceeded Range Readout Limit IN.LO < -25 mV 0..1 V / 0.2..1 V IN.HI > 1.2 V IN.LO < -25 mV 0..10 V / 2..10 V IN.HI > 12 V IN.LO < -1.05 mA 0..20 mA / 4..20 mA IN.HI > 25.05 mA IN.LO < -0.5% IN.HI > 100.5% IN.LO < temperature range TC / RTD IN.HI > temperature range Sensor error detection (SE.BR, SE.SH):

Input CURR

Range Loop break (4..20mA) TC Pt100 2-wire No SE.SH for Pt10, Pt20 and Pt50

TEMP

Pt100 3-wire No SE.SH for Pt10, Pt20 and Pt50 Pt100 4-wire No SE.SH for Pt10, Pt20 and Pt50

Readout SE.BR SE.BR SE.BR SE.SH SE.BR SE.SH SE.BR SE.SH

Limit <= 3.6 mA; > = 21 mA > ca. 750 kohm / (1,25V) > ca. 15 kohm < ca. 15 ohm > ca. 15 kohm < ca. 15 ohm > ca. 15 kohm < ca. 15 ohm

Display readout below min. / above max. (-1.9.9.9, 9.9.9.9): Input CURR VOLT POTM Range All All Readout -1.9.9.9 9.9.9.9 -1.9.9.9 9.9.9.9 -1.9.9.9 9.9.9.9 Limit Display readout <-1999 Display readout >9999 Display readout <-1999 Display readout >9999 Display readout <-1999 Display readout >9999

34

35

Readout at hardware error Error search Test of internal communication uC / ADC Test of internal CJC sensor Check-sum test of the configuration in RAM Check-sum test of the configuration in EEPROM Readout HW.ER CJ.ER RA.ER EE.ER Error cause Permanent error in ADC CJC sensor defect Error in RAM Error in EEPROM
21.6...253 VAC or 19.2...300 VDC

Block diagram
Common Relay 1 N.O. Common Relay 2 N.O. Relay 1 N.C. Relay 2 N.C. R2 Supply Supply Gnd. I Output

32

31

12

I+

mA

11

21 22

23

24 25

! Error indications in the display blink once a second. The help text explains the error.

connections
RTD, 2-wire RTD, 3-wire RTD, 4-wire
2 3 4

Inputs:
41 42 43 44 45 46 41 42 43 44 45 46 41 42 43 44 45 46

R1

26

Version D

TC

2-wire transmitter

Current

41 42 43 44 45 46
+
Voltage

41 42 43 44 45 46

41 42 43 44 45 46
AD

0.2 mA

46

45

44

43

42
1

41
Input gnd.

41 42 43 44 45 46

41 42 43 44 45 46

2-wire supply > 15 VDC

Input +, mA

+V

TC

Supply:
31 32

Output:
Current Relays

Tx

RTD, wires

11 12

21 22 23 24 25 26

- mA +

Potm.

R1

R2

36

Int. CJC

Potentiometer

PTC

20 W

Tx

EEPROM

CPU

5714
37

Power up 1.2
1 2

F.SET
1 2 REL1 REL2

1.3

SETP
1 2 -1999 9999 /OFF

50.0
1.0

Fast setpoint adjustment and relay test 1 Increase setpoint 2 Decrease setpoint 3 Save and exit the menu 1 and 2 simultaneously = change relay state 1.4

If no keys are activated for 2 minutes the display returns to default state 1.0 without saving configuration changes.. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Accept the chosen parameter and go to the next menu Hold 3 Back to previous menu / return to menu 1.0 without saving

Routing diagram

1.1

PASS
1 2 0000 9999

IN
1 2

DEC.P
1 2 1111 1.1.1.1

DI.LO

DI.HI

1 2 a999 9999

1 2 a999 9999

REL.U

1 2 PERC DISP

REL.1

3 3

1 2 SET SKIP OFF

SETP

1 2 a999 9999

ACT1

1 2 INCR DECR

HYS1

1.5

1 2 1 2999

ERR1
1 2 HOLD ACTI DEAC NONE

ON.DE

1 2 0000 3600

OF.DE

1 2 0000 3600

3 Hold
To 1.0

CURR 3 RANG
1 2 4-20 0-20

3 3
1.6

REL.2
1 2 SET SKIP OFF

SETP

LANG
1 2 DE_DK ES_FR IT_SE UK_CZ

VOLT 3 RANG 3

1 2 a999 9999

ACT2

1 2 INCR DECR

HYS2

1.5

1 2 1 2999

ERR2
1 2 HOLD ACTI DEAC NONE

ON.DE

1 2 0000 3600

OF.DE

1 2 0000 3600

1 2 0-10 2-10 0.2-1 0.0-1

1.6

1.6 1.7
1 2 a999 9999

POTM 3 CA.LO
1 2 YES NO

CA.HI

1.4

A.OUT
1 2 4-20 0-20 20-4 20-0

O.LO

1.7

O.HI

1.5

1 2 YES NO

1 2 a999 9999

O.ERR
1 2 3.5mA 0mA 23mA NONE

RESP

1 2 0.0 60.0

E.PAS

1 2 YES NO

N.PAS

3
NO

1 2 0000 9999

TEMP 3 TYPE
1 2
1.0 = Default state 1.1 = Only if passwordprotected 1.2 = Only is FastSet is enabled 1.3 = FastSet and relay test disabled at password 5000...9999. 1.4 = No relay outputs 1.5 = Not valid for these input signals: Potentiometer, 0...20 mA and voltage 1.6 = No analogue output 1.7 = Only if input signal is temperature

PT

PT.TY
1 2 10 1000

CON.W

To default state 1.0

----

1 2 4W 3W 2W

3
DEC.P UNIT

NI

NI.TY
1 2 50 1000

CON.W

1 2 4W 3W 2W

1 2 1111 111.1

1 2 'C 'F

TC

3 TC.TY
1 2 TC.B TC.E TC.J TC.K TC.L TC.N TC.R TC.S TC.T TC.U TC.W3 TC.W5 TC.LR

3
39

38

Scrolling help text


Display in default state xxxx, hardware error: SE.BR --> SENSOR WIRE BREAKAGE SE.SH --> SENSOR SHORT CIRCUIT IN.HI --> INPUT OVERRANGE IN.LO --> INPUT UNDERRANGE 9.9.9.9 --> DISPLAY OVERRANGE -1.9.9.9 --> DISPLAY UNDERRANGE HW.ER --> HARDWARE ERROR EE.ER --> EEPROM ERROR CHECK CONFIGURATION RA.ER --> RAM MEMORY ERROR CJ.ER --> CJC SENSOR ERROR Fastset (Enabled): F.SET REL1 --> FAST SET MENU SELECT RELAY REL2 --> SETP xxxx --> RELAY SETPOINT - PRESS OK TO SAVE Fastset (Disabled): SETP xxxx --> RELAY SETPOINT - READ ONLY Configuration menus: LANG DE --> DE - WAEHLE DEUTSCHEN HILFETEXT DK --> DK - VAELG DANSK HJAELPETEKST ES --> ES - SELECCIONAR TEXTO DE AYUDA EN ESPANOL FR --> FR - SELECTION TEXTE DAIDE EN FRANCAIS IT --> IT - SELEZIONARE TESTI DI AIUTO ITALIANI SE --> SE - VALJ SVENSK HJALPTEXT UK --> UK - SELECT ENGLISH HELPTEXT CZ --> CZ - VYBER CESKOU NAPOVEDU PASS xxxx --> SET CORRECT PASSWORD IN C.LIN* --> TEXT ENTERED BY USER IN PRESET CURR --> CURRENT INPUT VOLT --> VOLTAGE INPUT POTM --> POTENTIOMETER INPUT TEMP --> TEMPERATURE SENSOR INPUT RANG When current selected: 0-20 --> INPUT RANGE IN mA 4-20 --> INPUT RANGE IN mA RANG When voltage selected: 0-10 --> INPUT RANGE IN VOLT 2-10 --> INPUT RANGE IN VOLT 0.0-1 --> INPUT RANGE IN VOLT 0.2-1 --> INPUT RANGE IN VOLT CA.LO YES --> CALIBRATE POTENTIOMETER LOW NO --> CALIBRATE POTENTIOMETER LOW CA.HI YES --> CALIBRATE POTENTIOMETER HIGH NO --> CALIBRATE POTENTIOMETER HIGH DEC.P 1111 --> 111.1 --> 11.11 --> 1.111 --> DI.LO xxxx --> DI.HI --> xxxx --> REL.U PERC --> DISP --> TYPE PT --> NI --> TC --> PT.TY 10 --> 20 --> 50 --> 100 --> 200 --> 250 --> 300 --> 400 --> 500 --> 1000 --> NI.TY 50 --> 100 --> 120 --> 1000 --> CONN 2W --> 3W --> 4W --> TC.TY TC. B --> TC. E --> TC. J --> TC. K --> TC. L --> TC. N --> TC. R --> TC. S --> TC. T --> TC. U --> TC.W3 --> TC.W5 --> TC.LR --> DEC.P 1111 --> 111.1 --> DECIMAL DECIMAL DECIMAL DECIMAL POINT POINT POINT POINT POSITION POSITION POSITION POSITION REL1 SET --> SKIP --> OFF --> SETP xxxx --> ACT1 INCR --> DECR --> HYS1 xxxx --> ERR1 HOLD --> ACTI --> DEAC --> NONE --> ON.DE xxxx --> OF.DE xxxx --> REL2 SET --> SKIP --> OFF --> SETP xxxx --> ACT2 INCR --> DECR --> HYS2 xxxx --> ERR2 HOLD --> ACTI --> DEAC --> NONE --> ON.DE xxxx --> OF.DE xxxx --> A.OUT 0-20 --> 4-20 --> 20-0 --> 20-4 --> O.LO xxxx --> O.HI xxxx --> ENTER RELAY 1 SETUP SKIP RELAY 1 SETUP RELAY 1 DISABLED RELAY SETPOINT ACTIVATE AT INCREASING SIGNAL ACTIVATE AT DECREASING SIGNALL RELAY HYSTERESIS HOLD RELAY AT ERROR ACTIVATE RELAY AT ERROR DEACTIVATE RELAY AT ERROR UNDEFINED STATUS AT ERROR RELAY ON-DELAY IN SECONDS RELAY OFF-DELAY IN SECONDS ENTER RELAY 2 SETUP SKIP RELAY 2 SETUP RELAY 2 DISABLED RELAY SETPOINT ACTIVATE AT INCREASING SIGNAL ACTIVATE AT DECREASING SIGNAL RELAY HYSTERESIS HOLD RELAY AT ERROR ACTIVATE RELAY AT ERROR DEACTIVATE RELAY AT ERROR UNDEFINED STATUS AT ERROR RELAY ON-DELAY IN SECONDS RELAY OFF-DELAY IN SECONDS OUTPUT OUTPUT OUTPUT OUTPUT RANGE RANGE RANGE RANGE IN IN IN IN mA mA mA mA O.ERR 23 mA --> 3,5 mA --> 0mA --> NONE --> RESP xxx,x --> E.PAS NO --> YES --> N.PAS xxxx --> NAMUR NE43 UPSCALE AT ERROR NAMUR NE43 DOWNSCALE AT ERROR DOWNSCALE AT ERROR UNDEFINED OUTPUT AT ERROR ANALOGUE OUTPUT RESPONSE TIME IN SECONDS ENABLE PASSWORD PROTECTION ENABLE PASSWORD PROTECTION SELECT NEW PASSWORD

DISPLAY READOUT LOW DISPLAY READOUT HIGH SET RELAY IN PERCENTAGE SET RELAY IN DISPLAY UNITS SELECT PT SENSOR TYPE SELECT NI SENSOR TYPE SELECT TC SENSOR TYPE SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT PT PT PT PT PT PT PT PT PT PT NI NI NI NI SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE

When Pt and Ni sensor selected SELECT 2-WIRE SENSOR CONNECTION SELECT 3-WIRE SENSOR CONNECTION SELECT 4-WIRE SENSOR CONNECTION SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT SELECT TC TC TC TC TC TC TC TC TC TC TC TC TC SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE TYPE

When temperature selected DECIMAL POINT POSITION DECIMAL POINT POSITION

DISPLAY VALUE FOR OUTPUT LOW DISPLAY VALUE FOR OUTPUT HIGH

UNIT C --> DISPLAY AND RELAY SETUP IN CELSIUS F --> DISPLAY AND RELAY SETUP IN FAHRENHEIT

40

41

Configuration / Operating the function keys


Documentation for routing diagram. In general: When configuring the display you are guided through all parameters, you can choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in the display, this starts after 5 seconds if no key has been activated. Configuration is carried out by using the 3 function keys.

Graphic depiction of the relay function setpoint:


Relay units Relay units

100 90 80 70 60 50 40 30 20 10
Off N.O. On N.C. On N.O. Off N.C. Off N.O. On N.C.

100 90 80 70 60
Setpoint = 50 Hysteresis = 10 Hysteresis = 10 Setpoint = 50

50 40 30 20
Off N.O.

will increase the numerical value or choose the next parameter. will decrease the numerical value or choose the previous parameter. will accept the chosen value and end the menu.

On N.O. Off N.C.

Off N.O.

10

On N.C.

On N.C.

0 10 20 30 40 50 Relay action: Increasing

60

70

80

90 100

0 10 20 30 40 50 Relay action: Decreasing

60

70

80

90 100

If a function does not exist in the display all parameters are skipped to make the configuration as simple as possible. Once the configuration has been entered the display will show ----. Pressing and holding 3 will return to the previous menu or return to the default state (1.0) without saving the changed values or parameters. If no key is activated for 2 minutes, the display will return to the default state (1.0) without saving the changed values or parameters. Further explanations: Fast setpoint adjustment and relay test: These menus allow you to change the set point quickly and to check the operation of the relays. Pressing 1 and 2 at the same time will change the state of the relay this change is indicated by the diodes on the display. Pressing 3 will save the set point change. Holding down 3 for more than 0.5 seconds will return the unit to the default state without changing the set point.

Password protection:
Using a password will stop access to the menu and parameters. There are two levels of password protection. Passwords between 00004999 allow access to the fast set point adjustment and relay test. (Using this password stops access to all other parts of the menu). Passwords between 50009999 stop access to all parts of the menu, fast set point and relay test. (Current set point is still shown). By using the master password 2008, all configuration menus are available.

42

43