Production area

AHU-01
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Air outlet h Plemum Box Total safety 10 % total friction loss
2

80 L x 0.1

0.4

and V is velocity

V=

0.06889

1 0 0 2 0 0 2 0

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

14836 0.1 262.4 0.262

cfm in.w./100ft ft in w.g

1660 0.06889 0.34445

fpm in. w.g in. w.g

0.02 0 0 0.2 0 0 0.2 0 1.027 0.102685 1.130 281.254215

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

Production area
AHU-02
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) 2 No. of Elbows Elbows total friction loss (Hf 6 )= Take off friction loss (Ht) No. of take offs take off total friction loss (Ht 5 )= Motorized damper Fire damper Volume damper Flexible Duct Variable Air Volume (VAV) Air outlet Plemum Box Total safety 10 % total friction loss 0.4 and V is velocity V= 1600 0.064 0.384 fpm in. w.g in. w.g 41 L x 0.1 m 13143 0.1 134.48 0.134 cfm in.w./100ft ft in w.g

0.064

b-

cdefg h

1 0 0 2 0 0 2 0

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

0.02 0 0 0.2 0 0 0.2 0 0.938 0.093848 1.032 257.049672

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

Production area
AHU-03
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Air outlet h Plemum Box Total safety 10 % total friction loss
2

72 L x 0.1

0.4

and V is velocity

V=

0.0801025

1 0 0 2 0 0 2 0

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

15170 0.1 236.16 0.236

cfm in.w./100ft ft in w.g

1790 0.0801025 0.2403075

fpm in. w.g in. w.g

0.02 0 0 0.2 0 0 0.2 0 0.896 0.08964675 0.986 245.542448

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

Production area
AHU-04
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Air outlets h Plemum Box Total safety 10 % total friction loss
2

87 L x 0.1

0.4

and V is velocity

V=

0.08464

1 0 0 2 0 0 1 0

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

16437 0.1 285.36 0.285

cfm in.w./100ft ft in w.g

1840 0.08464 0.67712

fpm in. w.g in. w.g

0.02 0 0 0.2 0 0 0.1 0 1.282 0.128248 1.411 351.271272

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

Production area
AHU-05
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Jet diffusers h Plemum Box Total safety 10 % total friction loss
2

82 L x 0.1

0.4

and V is velocity

V=

0.0801025

1 0 0 2 0 0 1 0

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

15061 0.1 268.96 0.269

cfm in.w./100ft ft in w.g

1790 0.0801025 0.160205

fpm in. w.g in. w.g

0.02 0 0 0.2 0 0 0.1 0 0.749 0.0749165 0.824 205.196294

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

Production area
AHU-06
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Air outlets h Plemum Box Total safety 10 % total friction loss
2

53 L x 0.1

0.4

and V is velocity

V=

0.05476

1 0 0 2 3 1 2 1

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

8412 0.1 173.84 0.174

cfm in.w./100ft ft in w.g

1480 0.05476 0.43808

fpm in. w.g in. w.g

0.02 0 0 0.2 0.18 0.272 0.2 0.1 1.584 0.158392 1.742 433.835688

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

Production area
AHU-07
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Air outlets h Plemum Box Total safety 10 % total friction loss
2

50 L x 0.1

0.4

and V is velocity

V=

0.04761

2 0 0 2 3 1 2 1

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

5897 0.1 164 0.164

cfm in.w./100ft ft in w.g

1380 0.04761 0.33327

fpm in. w.g in. w.g

0.04 0 0 0.2 0.18 0.272 0.2 0.1 1.489 0.148927 1.638 407.911053

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

Production area
AHU-08
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Air outlets h Plemum Box Total safety 10 % total friction loss
2

48 L x 0.1

0.4

and V is velocity

V=

0.05776

1 0 0 1 3 1 1 1

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

9764 0.1 157.44 0.157

cfm in.w./100ft ft in w.g

1520 0.05776 0

fpm in. w.g in. w.g

0.02 0 0 0.1 0.18 0.272 0.1 0.1 0.929 0.092944 1.022 254.573616

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

Production area
AHU-09
AHU flow rate = Based on the design drawings friction loss will be duct length (L) 1- Duct friction loss = 2- Duct fittings:a- Elbows Hf = C x Hv Hf = C x (V/4000) 2 where C is loss coeffecient C= Hf = 0.4 x (1445/4000) No. of Elbows Elbows total friction loss (Hf 6 )= b- Take off friction loss (Ht) No. of take offs take offs take off total friction loss (Ht 5 )= c- Motorized damper d- Fire damper e- Volume damper Flexible Duct f- Variable Air Volume (VAV) g Air outlets h Plemum Box Total safety 10 % total friction loss
2

32 L x 0.1

0.4

and V is velocity

V=

0.0455625

2 0 0 1 3 1 2 1

0.02 0.06 0.06 0.1 0.06 0.272 0.1 0.1

Selected external static pressure is 1100 pa ,it is covering the calculated static pressure 540 pa

5216 0.1 104.96 0.105

cfm in.w./100ft ft in w.g

1350 0.0455625 0

fpm in. w.g in. w.g

0.04 0 0 0.1 0.18 0.272 0.2 0.1 0.997 0.099696 1.097 273.067344

in. w.g in. w.g in. w.g in. w.g

in. w.g in. w.g in. w.g Pa

ssure 540 pa

You might also like