You are on page 1of 6

MUSCAT ELECTRONICS 05/26/2009

HEAT LOAD
DAIKIN DIVISION 04:07:47

Floor Room TR TON BTUH CFM AREA OCC. SHR


Ground Floor SHOW ROOM 34.0 19.1 407873.8 11522 9892 30 0.68

Ceiling Height 3.8 ERROR, Check Floor, Ceiling, Roof


Glass Height 1.8
North East South West NE NW SE
Wall 0 11.8 0 11.8 Wall 0 0 0
Glass 0 6 0 4 Glass 2 2 2
Partition 23.8 0 23.8 0 Partition 3 3 3

Total 23.8 17.8 23.8 15.8 Total 5 5 5

TOTAL Occupancy 30.00


Sq. Metre Sq. Feet Roof 0.00
Wall 93.48 1393 Floor
Glass 32.4 348.57 Ceiling
Partition 226.48 2436.56

PROJECT: SOHAIL MOSSA ISMAIL


DBT(°F) WBT(°F)
ROOM SHOW ROOM SEASON SUMMER OUTSIDE 115.00 95.00
FLOOR Ground Floor FA CFM 2054.90 INSIDE 73.40 66.20
CUSTOMER BYPASS 0.10 DIFF 41.60 28.80
AREA 23.8m x11.8m PEAK LD 4:00 PM
23.80 metres 11.80 metres (SFT) (FT) (CUFT)
LENGTH 78.06 WIDTH 38.70 AREA 9892.00 HEIGHT 12.46 VOL 123293.89
NO. CFM/P
SOLAR TRANSMISSION THRU GLASS PEOPLE 30.00 5.00
ACPH 1.00
AREA TEMP.DIFF FACTOR BTUH
SOUTH 0.00 12.00 0.56 0.00 ROOM LATENT HEAT
S.WEST 38.73 85.00 0.56 1843.56
EAST 116.19 12.00 0.56 780.80 PEOPLE 30.00 205.00
WEST 77.46 163.00 0.56 7070.59 APPL. 3750.00 1.25
NORTH 0.00 23.00 0.56 0.00
N.EAST 38.73 12.00 0.56 260.27 O/S AIR 2054.90 0.68
N.WEST 38.73 138.00 0.56 2993.07
S.EAST 38.73 12.00 0.56 260.27 ROOM LATENT HEAT
ROOF 0.00 41.60 0.56 0.00 WITH S.F OF 5%
ROOM LATENT HEAT (TOTAL)
SOLAR TRANSMISSION THRU WALLS
SHF 0.85 ADP
AREA TEMP.DIFF FACTOR BTUH
SOUTH 0.00 16.00 0.35 0.00 DIFF : RTEMP-ADP
S.WEST 83.92 14.00 0.35 1192.44
EAST 611.51 18.00 0.35 9545.63 DEHUMIDIFIED AIR QTY
WEST 568.47 12.00 0.35 7680.08
NORTH 0.00 4.00 0.35 0.00 RETURN AIR HEAT GAIN
N.EAST 43.03 10.00 0.35 551.26 AREA TEMP.DIFF
N.WEST 43.03 6.00 0.35 491.01 SOUTH 0.00 16.00
S.EAST 43.03 10.00 0.35 551.26 S.WEST 0.00 14.00
ROOF 0.00 63.00 0.25 0.00 EAST 0.00 18.00
WEST 0.00 12.00
ALL GLASS 348.57 41.60 1.13 16385.68 NORTH 0.00 4.00
PARTITION 2436.56 36.60 0.35 31212.36 N.EAST 0.00 10.00
CEILING 0.00 36.60 0.44 0.00 N.WEST 0.00 6.00
FLOOR 0.00 36.60 0.44 0.00 S.EAST 0.00 10.00
ROOF 0.00 58.40
O/S AIR 2054.90 1.08 9232.25 CEILING 0.00 36.60
PARTITION 0.00 36.60
PEOPLE 30.00 245.00 7350.00 TOTAL
LIGHT LOAD 14838.00 1.25 63061.50
EQPT.LOAD 3750.00 1.00 12750.00 AHU ROOM HEAT GAIN
AREA TEMP.DIFF
ROOM SENSIBLE HEAT 173212.04 SOUTH 0.00 16.00
WITH S.F OF 12.5% 21651.50 S.WEST 0.00 14.00
ROOM SENSIBLE HEAT(TOTAL) 194863.54 EAST 0.00 18.00
CFM FACTOR DIFF WEST 0.00 12.00
OASH 2054.90 1.08 41.60 83090.22 NORTH 0.00 4.00
OASLH 2054.90 0.68 76.00 95577.42 N.EAST 0.00 10.00
N.WEST 0.00 6.00
TOTAL SENSIBLE HEAT 277953.76 S.EAST 0.00 10.00
TOTAL LATENT HEAT 129920.00 ROOF 0.00 35.00
CEILING 0.00 36.60
GRAND TOTAL HEAT 407873.76 BTUH FLOOR 0.00 36.60
TONNAGE 33.99 TR TOTAL
EADBT 80.82 °F
EAWBT 71.34 °F
CFM / TR 338.98
SFT/TR 291.03

Yakub Qureshi.
MUSCAT ELECTRONICS 05/26/2009
HEAT LOAD
DAIKIN DIVISION 04:07:48

TR - FA 19.10 TR
SFT/TR-FA 517.89
Ratio of total sens & total heat 0.68 SHR

Yakub Qureshi.
MUSCAT ELECTRONICS 05/26/2009
HEAT LOAD
DAIKIN DIVISION 04:07:48

SW
1
2
3
Cel. ~ Far. 30.0 86.0
6 Far. ~ Cel. 115.0 46.1 North
East
AREA CALCULATION West
mtrs mtrs sq m sq ft South
4 3 12 129.12 NE
0 0 NW
0 0 SE
0 0 SW
12 129.12

RH(%) GR/LB
25.00 140.00
55.00 64.00
76.00

CFM
150.00
2054.90

6150.00
15937.50

10619.71

32707.21
1635.36
34342.57

56.00 °F

17.40 °F

11521.66 CFM

FACTOR BTUH
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.55 0.00
0.42 0.00
0.35 0.00
0.00

FACTOR BTUH
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.33 0.00
0.48 0.00
0.42 0.00
0.44 0.00
0.00

Yakub Qureshi.
MUSCAT ELECTRONICS 05/26/2009
HEAT LOAD
DAIKIN DIVISION 04:07:48

Yakub Qureshi.
MUSCAT ELECTRONICS 05/26/2009
HEAT LOAD
DAIKIN DIVISION 04:07:48

Ceiling Height Glass


3.8 1.8
3.8 1.8
3.8 1.8
3.8 1.8
3.8 1.8
3.8 1.8
3.8 1.8
3.8 1.8

Yakub Qureshi.
MUSCAT ELECTRONICS 05/26/2009
HEAT LOAD
DAIKIN DIVISION 04:07:48

Yakub Qureshi.

You might also like