TECHNICAL DATA

Split-Sky Air
R(E)Y
Pair Application

Split
Sky Air
ISO14001 assures an effective environmental
management system in order to help protect
human health and the environment from the potential
impact of our activities, products and services and to
assist in maintaining and improving the quality of
the environment

Daikin units comply with the European


regulations that guarantee the safety of
the product.

Daikin Europe NV is approved by LRQA for its Quality


Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.

Daikin Europe NV is participating


in the EUROVENT Certification Programme.
Products are as listed in the EUROVENT
Directory of Certified Products.

Specifications are subject to change without prior notice

DAIKIN PRODUCTS ARE DISTRIBUTED BY :

Internet http://www.daikin.be

Prepared in Belgium by Goekint Graphics 07/2001

Zandvoordestraat 300, B-8400 Oostende

Pair Application R-22 R(E)Y18-250

TABLE OF CONTENTS
R(E)Y

Features

Specifications

......................................................................................................

........................................................................................

2
3

Technical specifications
Electrical specifications

Capacity tables

Dimensional drawings

....................................................................................

13

.................................................................

44

Operation range

................................................................................

47

Piping diagrams

.................................................................................

49

Wiring diagrams

................................................................................

54

Sound level

.............................................................................................

60

Sound level data


Sound pressure spectrum

Accessories

..............................................................................................

67

Standard accessories
Optional accessories

10

Centre of gravity

11

Safety device settings

12

Installation

...............................................................................

69

...................................................................

70

...............................................................................................

71

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Features

Outdoor units for pair application


Daikin outdoor units are neat and sturdy and can be mounted
easily on a roof or terrace or simply placed against an outside
wall. They are fitted with either rotary or scroll compressor,
renowned for low noise and high energy efficiency.

24
1

Split - Sky Air Outdoor Units

A special acryl precoated fin for anti-corrosion treatment on


the heat exchanger ensures greater resistance against severe
weather conditions.

Pair Application R-22 R(E)Y18-250

Specifications

TECHNICAL SPECIFICATIONS
OUTDOOR UNITS
DIMENSIONS

WEIGHT
MATERIAL
COLOUR
SOUND LEVEL

FAN

Unit

Unit
Unit
Unit
Sound pressure
(cooling/heating) (1)
Sound power
(cooling/heating) (2)
Air flow rate
(cooling/heating)
Speed

H
W
D

mm
mm
mm
kg

REY18GA7V1
540
750
270
29

high
low

dBA
dBA
dBA

44/45
57/58

high

m3/min

24/22

steps
high
low

rpm
rpm

Type
Qty x model
Qty x motor output
HEAT EXCHANGER Type
Rows x stages x fin pitch
Face area
REFRIGERANT
Refrigerant type
CIRCUIT
Refrigerant charge
No. of circuits
COMPRESSOR
Type
Qty x model
No. of cylinders
Speed
Oil type
Oil charge
Crankcase heater
PIPING CONNECTIONS
liquid
gas
drain
INSULATION
Heat insulation
MATERIAL

685
280
1 x F62P15S22
1 x 15

mm
m2

1 x 20 x 2.0
0.381

kg

0.65
max. 1

rpm

1 x RC21V1N-R
2,850

!
W
mm
mm
mm

0.4
6.4
9.5
18 x 4

Split - Sky Air Outdoor Units

REY40GA7V1
RY22DB7V1
660
540
880
750
350
270
50
37
Painted metal
Ivory white
46/49
44/45
59/62
57/58
34/31

25/23

2 steps
560-610
710
320-350
330
1 x 19TFB6062
1 x F62P15S22
1 x 30
1 x 15
WL fin, Hi-XA U-cooling tube
1 x 24 x 2.0
1 x 20 x 2.0
0.513
0.381
R-22
1.1
0.85
max. 1
max. 1
Hermetically sealed rotary compressor
1 x RC60V1TNRT
1 x PS36AKRV1
1
2,850
2,850
SUNISO 4GSDI
0.85
0.4
6.4
6.4
12.7
9.5
18 x 3
18
Both liquid and gas pipes

RY35DA7V1
660
880
350
50

46/47
59/60
36/32

610
350
1 x 19TFB6062
1 x 30
2 x 24 x 2.0
0.513
1.2
max. 1

24
2

1 x RC53V1TNRT
2,850
0.85
6.4
12.7
18 x 3

Pair Application R-22 R(E)Y18-250

Specifications

ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS
CURRENT

OUTDOOR UNITS
POWER SUPPLY
NOMINAL
DISTRIBUTION
SYSTEM VOLTAGE

Nominal running
cooling/heating A
current
Max. running current cooling/heating A
Starting current
cooling/heating A

Phase
Frequency
Voltage

Hz
V

REY18GA7V1
2.8

REY40GA7V1
7.3

RY22DB7V1
5.4/5.6

RY35DA7V1
6.8/6.3

5.6
24

8.8
35/35

REY18GA7V1
V1
1
50
230

REY40GA7V1
V1
1
50
230

RY22DB7V1
V1
1
50
230

RY35DA7V1
V1
1
50
230

NOTES

24

The sound pressure level is measured at 1m distance from the unit. For measuring conditions: please refer to item 8 of this chapter.

The sound power level is an absolute value indicating the power which a sound source generates.

Maximum allowable distance between indoor and outdoor unit: 15m (for REY18-40GA7 / RY22DB7), 20m (for RY35DA7)
Maximum allowable level difference: 10m (for REY18GA7), 15m (for REY40GA7 / RY22DB7 / RY35DA7).

Additional refrigerant charge: 30g/m if piping length >8m (for REY18-40GA7), 10m >30g/m >15m (for RY22DB7), 30g/m if piping length
>10m (for RY35DA7).

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Specifications

TECHNICAL SPECIFICATIONS
OUTDOOR UNITS
DIMENSIONS

WEIGHT
MATERIAL
COLOUR
SOUND LEVEL

FAN

Unit

Unit
Unit
Unit
Sound pressure
(cooling/heating) (1)
Sound power
(cooling/heating) (2)
Air flow rate
(cooling/heating)
Speed

H
W
D

mm
mm
mm
kg

high
low

dBA
dBA
dBA

high

m3/min

steps
high
low

rpm
rpm

Type
Qty x model
Qty x motor output
HEAT EXCHANGER Type
Rows x stages x fin pitch
Face area
REFRIGERANT
Refrigerant type
CIRCUIT
Refrigerant charge
No. of circuits
COMPRESSOR
Type
Qty x model
No. of cylinders
Speed
Oil type
Oil charge
Crankcase heater
PIPING CONNECTIONS
liquid
gas
drain
INSULATION
Heat insulation
MATERIAL

RY45DB7V1
RY60FA7V1
RY71B7V1/W1
RY100B7V1/W1
660
660
860
1,215
880
880
880
880
350
350
320
320
57
72
89/86
104/99
Painted metal
Painted galvanised steel plate
Ivory white
47/48
54/55
49/51
52/54
60/61
67/68
61/64/31/28

43/39

51/46

94/85

2 steps

W
mm
m2
kg

rpm
!
W
mm
mm
mm

3 steps
785
455
1 x AF-220-49-6-1
1 x P47L11S
2 x P47L11S
1 x 49
1 x 75
1 x (80 + 85)
WL fin, Hi-XA U-cooling tube
2 x 24 x 2.0
2 x 24 x 2.0
2 x 38 x 2.0
2 x 54 x 2.0
0.481
0.481
0.719
1.022
R-22
1.8
1.9
2
2.5
max. 1
max. 1
Hermetically sealed rotary compressor
Hermetically sealed scroll compressor
1 x RC70AV1TRT
1 x NH41VMDT
1 x (JT95BC-V1/JT95BC-YE)
1 x (JT125BC-V1/JT125BC-YE)
1
1
2,850
2,850
SUNISO 4GSDI
DIAMOND MS32(N-1)
SUNISO 4GSDID-K
1
1.2
1.2
1.5
33
33
6.4
9.5
9.5
9.5
12.7
15.9
15.9
19.1
18 x 3
18 x 3
26 x 3
26 x 3
Both liquid and gas pipes
585
335
1 x 19TFB6062
1 x 30

Split - Sky Air Outdoor Units

24
2

Pair Application R-22 R(E)Y18-250

Specifications

TECHNICAL SPECIFICATIONS
OUTDOOR UNITS
DIMENSIONS

WEIGHT
MATERIAL
COLOUR
SOUND LEVEL

FAN

HEAT EXCHANGER

24
2

Unit

Unit
Unit
Unit
Sound pressure
(cooling/heating) (1)
Sound power
(cooling/heating) (2)
Air flow rate
(cooling/heating)
Speed

H
W
D

mm
mm
mm
kg

RY125B7W1
1,215
880
320
102

high
low

dBA
dBA
dBA

high

m3/min

steps
high
low

rpm
rpm

Type
Qty x model
Qty x motor output
Type

Rows x stages x fin pitch


Face area
REFRIGERANT
Refrigerant type
CIRCUIT
Refrigerant charge
No. of circuits
COMPRESSOR
Type
Qty x model
No. of cylinders
Speed
Oil type
Oil charge
Crankcase heater
PIPING CONNECTIONS
liquid
gas
drain
INSULATION
Heat insulation
MATERIAL

mm
m2

RY250F7W1
1,440
1,290
700
195

52/54
64/-

RY200F7W1
1,220
1,290
700
170
Painted galvanised steel plate
Ivory white
57/57
77/78

91/82

160

170

3 steps
2 x P47L11S
1 x (80+85)
Non symm. waffle louvre, Hi-XA
U-cooling tube
2 x 54 x 2.0
1,022

kg

3
-

rpm

1 x JT60BC-YE
-

!
W
mm
mm
mm

1.5
33
9.5
19.1
26 x 3

Split - Sky Air Outdoor Units

57/57
77/78

2 steps
1 x P55J11F
1 x JT236D-YE@2
1 x (230+190)
1 x (230+140)
J8 Hi-XA tube assymetric louvre

2 x 40 x 2
1,57
R-22
4.65
Hermetically sealed scroll compressor
1 x JT236D-YE@2
2,900
SUNISO 4GSDID-K
4
50
12.7 x 0.90
28.6 x 1.15
26 x 6
Both liquid and gas pipes

2 x 50 x 2
1,97
6.425
1 x JT300D-YE@2
2,900
4
50
15.9 x 0.95
28.6 x 1.15
26 x 6

Pair Application R-22 R(E)Y18-250

Specifications

ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS
CURRENT

OUTDOOR UNITS
POWER SUPPLY
NOMINAL
DISTRIBUTION
SYSTEM VOLTAGE

Nominal running
cooling/heating A
current
Max. running current cooling/heating A
Starting current
cooling/heating A

Phase
Frequency
Voltage
Voltage tolerance

Hz
V
%

RY45DB7V1
8.9/8.1

RY60FA7V1
10.9/10.7

RY71B7V1/W1
-

RY100B7V1/W1
-

11.5/11.5
39/39

13.5/13.5
53/53

RY45DB7V1
V1
1
50
230
-

RY60FA7V1
V1
1
50
230
-

RY71B7V1/W1
V1/W1
1/3N
50
230/400
+/-10

RY100B7V1/W1
V1/W1
1/3N
50
230/400
+/-10

ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS
CURRENT

OUTDOOR UNITS
POWER SUPPLY
NOMINAL
DISTRIBUTION
SYSTEM VOLTAGE

cooling/heating A
Nominal running
current
Max. running current cooling/heating A
Starting current
cooling/heating A

Phase
Frequency
Voltage
Voltage tolerance

Hz
V
%

RY125B7W1
-

RY200F7W1
18.4

RY250F7W1
19.2

21.5
-

22.5
-

RY125B7W1
W1
3N
50
400
+/-10

RY200F7W1
W1
3N
50
400
+/-10

RY250F7W1
W1
3N
50
400
+/-10

24
2

NOTES
1

The sound pressure level is measured at 1m distance from the unit. For measuring conditions: please refer to item 8 of this chapter.

The sound power level is an absolute value indicating the power which a sound source generates.

Maximum allowable distance between indoor and outdoor unit: 25m (for RY45DB7 / RY60FA7), 50m (for RY71-125B7), 50m-70m
equivalent (for RY200-250F7).
Maximum allowable level difference: 15m (for RY45DB7 / RY60FA7), 30m (for RY71-125B7 / RY200-250F7).

Additional refrigerant charge: 30g/m if piping length >10m (for RY35DA7 / RY45DB7), 50g/m if piping length >10m (for RY60FA7), 7.5m
>50g/m >50m (for RY71-125B7), 30g/m >7.5m (for RY200F7), 50g/m >7.5m (for RY250F7).

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Specifications

ELECTRICAL DATA
REY18GA7V1

Connection ratio (%)

Indoor unit

FTY18JV1B

Hz-Volts
50-220
50-230
50-240

Power supply
Voltage range
MAX. 264V
MIN. 198V

MCA TOCA MFA


3.2

15.0

Compressor
LRA RLA

OFM
FLA

FLA

FLA

15

15

0.2

19

0.2

2.3

IFM

EH

3TW01041-3B

REY40GA7V1

Connection ratio (%)

Indoor unit

FTY40GV1B

FLY40GAV1NB

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA TOCA MFA

Compressor
LRA RLA

OFM
FLA

IFM
FLA

EH
FLA

Max. 264V
Min. 198V

8.8

20.0

34

6.6

30

0.3

18

0.2

Max. 264V
Min. 198V

8.8

20.0

34

6.6

30

0.3

34

0.3

3TW0111-3C

RY22DB7V1

Connection ratio (%)

Indoor unit

24

FTY22JV1B

FLY22GAV1NB

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA TOCA MFA

Compressor
LRA RLA

OFM
FLA

IFM
FLA

EH
FLA

MAX. 264V
MIN. 198V

6.8

15.0

24

5.1

15

0.2

19

0.2

MAX. 264V
MIN. 198V

6.7

15.0

24

5.0

15

0.2

34

0.3

3TW00061-2C

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W
EH

:
:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)
Electric Heater

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19.0CWB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed operation
range limits
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA + 1.25 x EH FLA
MFA < 2.25 x RLA + ea. FLA + 2.25 x EH FLA
(next lower standard fuse rating, min.15A)

Pair Application R-22 R(E)Y18-250

Specifications

RY35DA7V1

Connection ratio (%)

Indoor unit

FTY35JV1B

FLY35GAV1NB

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA TOCA MFA

Compressor
LRA RLA

OFM
FLA

IFM
FLA

EH
FLA

MAX. 264V
MIN. 198V

8.5

15.0

33

6.4

30

0.3

19

0.2

MAX. 264V
MIN. 198V

8.4

15.0

33

6.2

30

0.3

34

0.3

3TW00641-2D

RY45DB7V1

Connection ratio (%)

Indoor unit

FTY45GAV1B

FLY45GAV1NB

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA TOCA MFA

Compressor
LRA RLA

OFM
FLA

IFM
FLA

EH
FLA

MAX. 264V
MIN. 198V

12.3

25.0

36

9.4

30

0.3

130

0.2

MAX. 264V
MIN. 198V

12.3

25.0

36

9.3

30

0.3

34

0.3

3TW01141-2C

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W
EH

:
:
:
:
:
:
:
:
:
:

NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27CDB/19.0CWB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed operation
range limits
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA + 1.25 x EH FLA
MFA < 2.25 x RLA + ea. FLA + 2.25 x EH FLA
(next lower standard fuse rating, min.15A)

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)
Electric Heater

24
2

RY60FA7V1

Connection ratio (%)

Indoor unit

FTY60GAV1B

Hz-Volts
50-220
50-230
50-240

Power supply
Voltage range
MAX. 254V
MIN. 198V

MCA

TOCA

MFA

13.0

20

Compressor
LRA
RLA
52
9.9
55
9.6
58
9.3

OFM

IFM

FLA

FLA

55.3

0.3

130

0.6

3TW01152-2B

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temperature 27CDB/19CWB
Outdoor temperature 35CDB
2. TOCA means the total value of each OC set.
3. Maximum allowable voltage variation between phases is 2%
4. Select wire size based on the larger value of MCA or TOCA.
5. Instead of fuse, use circuit breaker
6. Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed operation
range limits

Pair Application R-22 R(E)Y18-250

Specifications

RY71B7V1/W1

Connection ratio (%)

Indoor unit

FHYC71/ FUY71

RY71B7V1

FHY71

Power supply
Voltage range

Compressor
LRA
RLA

MCA

TOCA

MFA

50-230

18.8

23.3

32

93

RY71B7V1

50-230

18.8

23.3

32

FHYK71

RY71B7V1

50-230

18.7

23.2

FAY71

RY71B7V1

50-230

18.5

FHYB71

RY71B7V1

50-230

FHYC71/ FUY71

RY71B7W1

FHY71

24

Hz-Volts

OFM

IFM

KW

FLA

KW

FLA

14.0

0.075

0.7

0.045

0.6

93

14.0

0.075

0.7

0.062

0.6

32

93

14.0

0.075

0.7

0.045

0.5

23.0

32

93

14.0

0.075

0.7

0.046

0.3

19.1

23.6

32

93

14.0

0.075

0.7

0.125

0.9

50-400/230

7.6

8.8

16

46

5.0

0.075

0.7

0.045

0.6

RY71B7W1

50-400/230

7.6

8.8

16

46

5.0

0.075

0.7

0.062

0.6

FHYK71

RY71B7W1

50-400/230

7.5

8.7

16

46

5.0

0.075

0.7

0.045

0.5

FAY71

RY71B7W1

50-400/230

7.3

8.5

16

46

5.0

0.075

0.7

0.046

0.3

FHYB71

RY71B7W1

50-400/230

7.9

9.1

16

46

5.0

0.075

0.7

0.125

0.9

Max. 50Hz-264V
Min. 50Hz-198V

Max. 50Hz-456V/264V
Min. 50Hz-342V/198V

2
3TW23209-2

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
KW

10

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps (See note 7)
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19,5CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed operation
range limits
4. Maximum allowable voltage unbalance between phases is 2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating min 16A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker

Pair Application R-22 R(E)Y18-250

Specifications

RY100B7V1/W1

Connection ratio (%)

Indoor unit

FHYC100/
FUY100

RY100B7V1

50-230

FHY100

RY100B7V1

50-230

Hz-Volts

Power supply
Voltage range

Compressor
LRA
RLA

MCA

TOCA

MFA

24.0

28.5

40

114

17.2

23.7

28.2

40

114

17.2

Max. 50Hz-264V
Min. 50Hz-198V
FAY100

RY100B7V1

50-230

23.4

27.9

40

114

17.2

FHYB100

RY100B7V1

50-230

24.0

28.5

40

114

17.2

FHYC100/ FUY100

RY100B7W1

50-400/230

10.3

12.5

16

53

6.2

FHY100

RY100B7W1

50-400/230

10.0

12.2

16

53

6.2

Max. 50Hz-456V/264V
Min. 50Hz-342V/198V
FAY100

RY100B7W1

50-400/230

9.7

11.9

16

53

6.2

FHYB100

RY100B7W1

50-400/230

10.3

12.5

16

53

6.2

OFM
KW
FLA
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7

IFM
KW

FLA

0.09

1.0

0.13

0.7

0.049

0.4

0.135

1.0

0.09

1.0

0.13

0.7

0.049

0.4

0.135

1.0

3TW23249-2

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
KW

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps (See note 7)
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output

Split - Sky Air Outdoor Units

24
2

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19,5CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed operation
range limits
4. Maximum allowable voltage unbalance between phases is 2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating min 16A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker

11

Pair Application R-22 R(E)Y18-250

Specifications

RY125B7W1

Unit combination
Indoor
Outdoor

Hz-Volts

FHYC125/ FUY125

RY125B7W1

50-400/230

FHY125

RY125B7W1

50-400/230

Power supply
Voltage range

Compressor
LRA
RLA

MCA

TOCA

MFA

12.0

15.5

20

70

7.6

11.7

15.2

20

70

7.6

Max. 50Hz-456V/264V
Min. 50Hz-342V/198V
FDY125

RY125B7W1

50-400/230

15.2

18.7

20

70

7.6

FHYB125

RY125B7W1

50-400/230

12.4

15.9

20

70

7.6

OFM
KW
FLA
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7
0.085
0.84
+
+
0.08
0.7

IFM
KW

FLA

0.09

1.0

0.13

0.7

0.5

4.2

0.225

1.4

3TW23279-2

RY200-250F7W1

Unit combination
Indoor
Outdoor
FDY200F7V1

Hz-Volts

RY200F7W1

Power supply
Voltage range

50-400

MCA
16.1

Max. 440V
Min. 360V

24

FDY250F7V1

RY250F7W1

50-400

19.3

MFA
25
+
16
32
+
16

109

10.7

109

13.4

OFM
KW
0.19
+
0.23
0.14
+
0.23

IFM
FLA
1.28
+
1.43
1.1
+
1.43

KW

FLA

650

6.8

1000

7.6

3TW21481-2

2
SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
KW

12

Compressor
LRA
RLA

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps (See note 7)
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19.0CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed operation
range limits
4. Maximum allowable voltage unbalance between phases is 2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating min 16A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker

Pair Application R-22 R(E)Y18-250

Capacity tables

Model
AFR
BF

REY18GA7V1 + FTY18JV1B
Cooling capacity

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

TC
1.81
1.96
2.10
2.25
2.33
2.55
2.70

230V [50Hz]

20
SHC
1.62
1.68
1.74
1.81
1.84
1.93
2.00

PI
0.42
0.43
0.44
0.45
0.45
0.47
0.48

TC
1.65
1.80
1.94
2.09
2.17
2.39
2.54

25
SHC
1.55
1.61
1.67
1.74
1.77
1.86
1.93

PI
0.46
0.47
0.48
0.49
0.50
0.51
0.52

Outdoor temperature (C)


32
35
SHC
PI
TC
SHC
1.45
0.53
1.33
1.41
1.51
0.54
1.48
1.47
1.58
0.55
1.63
1.53
1.64
0.56
1.78
1.60
1.67
0.56
1.85
1.63
1.76
0.58
2.07
1.72
1.83
0.59
2.22
1.78

TC
1.43
1.57
1.72
1.87
1.95
2.17
2.32

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

PI
0.56
0.57
0.58
0.59
0.59
0.61
0.62

40
SHC
1.34
1.40
1.46
1.53
1.56
1.65
1.71

TC
1.17
1.32
1.47
1.62
1.69
1.91
2.06

43
SHC
1.30
1.36
1.42
1.48
1.52
1.61
1.67

PI
0.63
0.64
0.65
0.66
0.66
0.68
0.69

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

(CWB)
(CDB)
(kW)
(kW)
(kW)

Model
AFR

REY18GA7V1 + FTY18JV1B
Heating capacity

24
3

FTY
6.6

230V [50Hz]

Indoor
EDB
C
16.0
18.0
20.0
21.0
22.0
24.0

TC
1.08
1.23
1.37
1.52
1.60
1.82
1.97

NOTES
(m3/min)

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

Caution:
TC and SHC are shown by kW

EWB
C
9.0
11.0
12.0
13.0
14.0
15.0

PI
0.60
0.61
0.62
0.63
0.64
0.65
0.66

FTY
7.1
0.27

10
TC
0.96
0.92
0.89
0.87
0.85
0.82

6
PI
0.43
0.44
0.45
0.46
0.47
0.48

TC
1.26
1.22
1.19
1.17
1.16
1.12

PI
0.45
0.46
0.48
0.48
0.49
0.50

TC
1.56
1.52
1.49
1.47
1.46
1.42

Outdoor temperature (C)


0
6
PI
TC
0.47
1.92
0.48
1.88
0.50
1.85
0.50
1.83
0.51
1.82
0.52
1.78

10
PI
0.49
0.51
0.52
0.53
0.53
0.55

TC
2.16
2.12
2.09
2.07
2.06
2.02

15
PI
0.51
0.52
0.54
0.54
0.55
0.56

TC

2.39
2.37
2.36
2.32

PI

0.56
0.56
0.57
0.58
3TW01042-1B

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC is shown by kW

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Capacities are based on the following conditions
Corresponding refrigerant piping length
7.5 m
Level difference
0m
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
4. Direct interpolation is permissible
Do not extrapolate.

13

Pair Application R-22 R(E)Y18-250

Capacity tables

Model FHEYB
AFR
BF

REY18GA7V1 + FHEYB18BA7V1
Cooling capacity

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

TC
1.76
1.90
2.05
2.19
2.26
2.48
2.62

230V [50Hz]

20
SHC
1.52
1.58
1.64
1.70
1.73
1.82
1.88

PI
0.44
0.45
0.46
0.47
0.48
0.49
0.50

TC
1.60
1.75
1.89
2.04
2.11
2.33
2.47

25
SHC
1.46
1.51
1.57
1.63
1.66
1.75
1.81

PI
0.49
0.50
0.51
0.52
0.52
0.54
0.55

Outdoor temperature (C)


32
35
SHC
PI
TC
SHC
1.36
0.55
1.29
1.32
1.42
0.56
1.44
1.38
1.48
0.58
1.58
1.44
1.54
0.59
1.73
1.50
1.57
0.59
1.80
1.53
1.66
0.61
2.02
1.62
1.72
0.62
2.16
1.68

TC
1.39
1.53
1.68
1.82
1.89
2.11
2.25

PI
0.58
0.59
0.60
0.61
0.62
0.64
0.65

40
SHC
1.26
1.32
1.38
1.43
1.46
1.55
1.61

TC
1.14
1.28
1.43
1.57
1.65
1.86
2.01

PI
0.63
0.64
0.65
0.66
0.67
0.68
0.69

18
6.50
0.43

TC
1.05
1.19
1.34
1.48
1.55
1.77
1.91

43
SHC
1.22
1.28
1.34
1.39
1.42
1.51
1.57

PI
0.66
0.67
0.68
0.69
0.70
0.71
0.72

3TW01042-2A

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

24
3

NOTES
(m3/min)

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Add the correction value to power input (W) as shown above
5. Direct interpolation is permissible Do not extrapolate.
6. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW

Model FHEYB
AFR

REY18GA7V1 + FHEYB18BA7V1
Heating capacity

230V [50Hz]

Indoor
EWB
C
9.0
11.0
12.0
13.0
14.0
15.0

EDB
C
16.0
18.0
20.0
21.0
22.0
24.0

18
7.10

10
TC
0.84
0.79
0.74
0.71
0.69
0.64

6
PI
0.46
0.48
0.49
0.50
0.51
0.52

TC
1.19
1.14
1.09
1.06
1.04
0.99

PI
0.49
0.50
0.52
0.53
0.53
0.55

TC
1.53
1.48
1.43
1.41
1.38
1.33

Outdoor temperature (C)


0
6
PI
TC
0.51
1.95
0.53
1.90
0.54
1.85
0.55
1.82
0.56
1.80
0.57
1.75

10
PI
0.55
0.56
0.58
0.58
0.59
0.60

TC
2.23
2.18
2.13
2.10
2.08
2.03

15
PI
0.57
0.58
0.60
0.60
0.61
0.63

TC
----2.47
2.45
2.42
2.37

PI
----0.62
0.63
0.64
0.65
3TW01042-3A

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC is shown by kW

14

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Capacities are based on the following conditions
Corresponding refrigerant piping length
7.5 m
Level difference
0m
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
4. Direct interpolation is permissible
Do not extrapolate.

Pair Application R-22 R(E)Y18-250

Capacity tables

REY40GA7V1 + FTY40GV1B
+ FLY40GAV1NB
Cooling capacity

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

TC
3.46
3.71
3.96
4.22
4.34
4.72
4.98

230V [50Hz]

20
SHC
2.76
2.80
2.85
2.89
2.91
2.97
3.02

PI
1.21
1.23
1.26
1.28
1.29
1.33
1.36

TC
3.31
3.56
3.82
4.07
4.20
4.58
4.83

25
SHC
2.70
2.74
2.79
2.83
2.85
2.91
2.96

PI
1.32
1.34
1.37
1.39
1.41
1.44
1.47

Outdoor temperature (C)


32
35
SHC
PI
TC
SHC
2.62
1.47
3.01
2.58
2.66
1.50
3.27
2.62
2.70
1.52
3.52
2.67
2.74
1.55
3.77
2.71
2.77
1.56
3.90
2.73
2.83
1.60
4.28
2.79
2.87
1.63
4.53
2.84

TC
3.10
3.36
3.61
3.86
3.99
4.37
4.62

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Model
AFR
BF

FTY
8.5
0.2

FLY
7
0.2

PI
1.54
1.57
1.59
1.62
1.63
1.67
1.69

TC
2.87
3.12
3.37
3.63
3.75
4.13
4.38

PI
1.65
1.68
1.70
1.73
1.74
1.78
1.81

TC
2.78
3.03
3.28
3.54
3.66
4.04
4.30

SHC
0
43
SHC
2.49
2.53
2.57
2.61
2.63
2.70
2.74

PI
-0.005

PI
1.72
1.74
1.77
1.80
1.81
1.85
1.87

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

(CWB)
(CDB)
(kW)
(kW)
(kW)

REY40GA7V1 + FTY40GV1B
+ FLY40GAV1NB

Model
AFR

Heating capacity

FTY
9.1

24
3

FLY
7.8

230V [50Hz]

Indoor
EDB
C
16.0
18.0
20.0
21.0
22.0
24.0

40
SHC
2.52
2.56
2.61
2.65
2.67
2.73
2.78

TC
0

NOTES
(m3/min)

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

Caution:
TC and SHC are shown by kW

EWB
C
9.0
11.0
12.0
13.0
14.0
15.0

Correction
FLY

10
TC
2.88
2.80
2.71
2.67
2.63
2.54

6
PI
1.20
1.24
1.27
1.29
1.31
1.34

TC
3.50
3.42
3.33
3.29
3.25
3.16

PI
1.31
1.35
1.38
1.40
1.42
1.45

TC
4.12
4.04
3.95
3.91
3.87
3.78

Outdoor temperature (C)


0
6
PI
TC
1.42
4.87
1.45
4.78
1.49
4.70
1.51
4.66
1.53
4.62
1.56
4.53

10
PI
1.55
1.58
1.62
1.64
1.66
1.69

TC
5.37
5.28
5.20
5.15
5.11
5.03

15
PI
1.64
1.67
1.71
1.72
1.74
1.78

TC

5.82
5.78
5.73
5.65

PI

1.82
1.83
1.85
1.89
3TW01112-1C

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC is shown by kW

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Capacities are based on the following conditions
Corresponding refrigerant piping length
7.5 m
Level difference
0m
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
4. Direct interpolation is permissible
Do not extrapolate.

15

Pair Application R-22 R(E)Y18-250

Capacity tables

RY22DB7V1 + FTY22JV1B
FLY22GAV1NB
Cooling capacity

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

TC
2.49
2.65
2.81
2.97
3.05
3.29
3.45

230V [50Hz]

20
SHC
2.04
2.10
2.16
2.22
2.24
2.33
2.39

PI
0.88
0.89
0.90
0.91
0.92
0.93
0.94

TC
2.32
2.48
2.64
2.80
2.88
3.12
3.28

25
SHC
1.94
2.00
2.06
2.12
2.15
2.23
2.29

PI
0.94
0.95
0.96
0.97
0.98
0.99
1.00

Outdoor temperature (C)


32
35
SHC
PI
TC
SHC
1.81
1.03
1.99
1.75
1.86
1.04
2.15
1.80
1.92
1.05
2.31
1.86
1.98
1.06
2.47
1.92
2.01
1.06
2.55
1.95
2.10
1.08
2.79
2.04
2.16
1.09
2.95
2.10

TC
2.09
2.25
2.41
2.57
2.65
2.89
3.05

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

24
3

Model
AFR
BF

FTY
6.6
0.24

FLY
7.6
0.21

PI
1.06
1.07
1.08
1.09
1.10
1.12
1.13

TC
1.83
1.99
2.14
2.30
2.38
2.62
2.78

PI
1.13
1.14
1.15
1.16
1.16
1.18
1.19

TC
1.63
1.79
1.95
2.10
2.18
2.42
2.58

SHC
PI
0 +0.06
43
SHC
1.53
1.59
1.65
1.71
1.74
1.82
1.88

PI
1.20
1.21
1.22
1.23
1.24
1.25
1.26

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

(CWB)
(CDB)
(kW)
(kW)
(kW)

RY22DB7V1 + FTY22JV1B
FLY22GAV1NB

Model
AFR

Heating capacity

FTY
7.3

FLY
9.2

230V [50Hz]

Indoor
EDB
C
16.0
18.0
20.0
21.0
22.0
24.0

40
SHC
1.65
1.71
1.77
1.82
1.85
1.94
2.00

TC
0

NOTES
(m3/min)

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

Caution:
TC and SHC are shown by kW

EWB
C
9.0
11.0
12.0
13.0
14.0
15.0

Correction
FLY

10
TC
1.93
1.91
1.88
1.87
1.86
1.83

6
PI
0.97
0.99
1.00
1.01
1.02
1.04

TC
2.34
2.32
2.29
2.28
2.27
2.24

PI
1.01
1.03
1.05
1.05
1.06
1.08

TC
2.76
2.73
2.71
2.69
2.68
2.66

Outdoor temperature (C)


0
6
PI
TC
1.05
3.25
1.07
3.23
1.09
3.20
1.10
3.19
1.11
3.18
1.12
3.15

10
PI
1.11
1.12
1.14
1.15
1.16
1.17

TC
3.58
3.55
3.53
3.52
3.50
3.48

15
PI
1.14
1.16
1.17
1.18
1.19
1.21

TC

3.94
3.93
3.92
3.89

PI

1.22
1.23
1.23
1.25
3TW00062-2C

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC is shown by kW

16

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Capacities are based on the following conditions
Corresponding refrigerant piping length
7.5 m
Level difference
0m
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
4. Direct interpolation is permissible
Do not extrapolate.

Pair Application R-22 R(E)Y18-250

Capacity tables

RY35DA7V1 + FTY35JV1B
+ FLY35GAV1NB
Cooling capacity

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

TC
3.46
3.61
3.77
3.92
3.99
4.22
4.38

230V [50Hz]

20
SHC
2.63
2.67
2.70
2.74
2.76
2.81
2.85

PI
1.04
1.06
1.09
1.12
1.13
1.17
1.19

TC
3.30
3.45
3.60
3.75
3.83
4.06
4.21

25
SHC
2.55
2.58
2.62
2.65
2.67
2.72
2.76

PI
1.14
1.17
1.19
1.22
1.23
1.27
1.30

Outdoor temperature (C)


32
35
SHC
PI
TC
SHC
2.43
1.29
2.97
2.37
2.46
1.31
3.12
2.41
2.50
1.34
3.27
2.45
2.53
1.36
3.42
2.48
2.55
1.38
3.50
2.50
2.60
1.42
3.73
2.55
2.64
1.44
3.88
2.59

TC
3.07
3.22
3.37
3.52
3.60
3.83
3.98

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Model
AFR
BF

FTY
7.8
0.28

FLY
8.7
0.31

PI
1.35
1.38
1.40
1.43
1.44
1.48
1.50

TC
2.80
2.95
3.11
3.26
3.34
3.56
3.72

Correction
FLY
40
SHC
2.29
2.32
2.36
2.40
2.41
2.47
2.50

43
SHC
2.19
2.22
2.26
2.29
2.31
2.36
2.40

TC
2.60
2.76
2.91
3.06
3.14
3.37
3.52

PI
1.58
1.60
1.63
1.66
1.67
1.71
1.73

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

(CWB)
(CDB)
(kW)
(kW)
(kW)

RY35DA7V1 + FTY35JV1B
+ FLY35GAV1NB

Model
AFR

Heating capacity

FTY
8.0

24
3

FLY
10

230V [50Hz]

Indoor
EDB
C
16.0
18.0
20.0
21.0
22.0
24.0

SHC
PI
0 +0.03

NOTES
(m3/min)

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

Caution:
TC and SHC are shown by kW

EWB
C
9.0
11.0
12.0
13.0
14.0
15.0

PI
1.45
1.48
1.50
1.53
1.54
1.58
1.61

TC
0

10
TC
2.59
2.55
2.52
2.50
2.48
2.45

6
PI
1.26
1.29
1.31
1.33
1.34
1.37

TC
3.08
3.05
3.01
3.00
2.98
2.94

PI
1.32
1.34
1.37
1.39
1.40
1.43

TC
3.58
3.54
3.51
3.49
3.47
3.44

Outdoor temperature (C)


0
6
PI
TC
1.38
4.17
1.40
4.14
1.43
4.10
1.44
4.08
1.46
4.07
1.49
4.03

10
PI
1.45
1.47
1.50
1.51
1.53
1.56

TC
4.57
4.53
4.50
4.48
4.46
4.43

15
PI
1.49
1.52
1.55
1.56
1.57
1.60

TC
4.99
4.97
4.95
4.92

PI
1.60
1.62
1.63
1.66

3TW00642-10C

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC is shown by kW

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Capacities are based on the following conditions
Corresponding refrigerant piping length
7.5 m
Level difference
0m
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
4. Direct interpolation is permissible
Do not extrapolate.

17

Pair Application R-22 R(E)Y18-250

Capacity tables

RY45DB7V1 + FTY45GAV1B
+ FLY45GAV1NB
Cooling capacity

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

TC
4.57
4.84
5.12
5.39
5.53
5.94
6.22

230V [50Hz]

20
SHC
3.20
3.26
3.32
3.38
3.41
3.50
3.56

PI
1.44
1.48
1.52
1.56
1.58
1.64
1.68

TC
4.36
4.63
4.91
5.18
5.32
5.73
6.01

25
SHC
3.13
3.19
3.25
3.31
3.34
3.43
3.49

PI
1.60
1.64
1.68
1.72
1.74
1.80
1.84

Outdoor temperature (C)


32
35
SHC
PI
TC
SHC
3.02
1.82
3.94
2.98
3.08
1.86
4.21
3.04
3.14
1.90
4.49
3.10
3.20
1.94
4.76
3.16
3.23
1.96
4.90
3.19
3.32
2.02
5.31
3.28
3.38
2.06
5.59
3.34

TC
4.06
4.34
4.61
4.89
5.03
5.44
5.71

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

24
3

FLY
10.7
0.23

PI
1.92
1.96
2.00
2.04
2.06
2.12
2.16

TC
3.73
4.00
4.28
4.55
4.69
5.10
5.38

Correction
FLY
40
SHC
2.90
2.96
3.02
3.08
3.11
3.20
3.26

PI
2.08
2.12
2.16
2.20
2.22
2.28
2.32

TC
SHC
-0.20 -0.13

TC
3.48
3.75
4.03
4.30
4.44
4.85
5.13

43
SHC
2.81
2.87
2.93
2.99
3.02
3.11
3.17

PI
0

PI
2.28
2.32
2.36
2.40
2.42
2.48
2.52

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

(CWB)
(CDB)
(kW)
(kW)
(kW)

RY45DB7V1 + FTY45GAV1B
+ FLY45GAV1NB

Model
AFR

Heating capacity

FTY
14.9

FLY
11.5

Correction
FLY

TC
0

PI
+0.01

230V [50Hz]

Indoor
EDB
C
16.0
18.0
20.0
21.0
22.0
24.0

FTY
11.8
0.23

NOTES
(m3/min)

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

Caution:
TC and SHC are shown by kW

EWB
C
9.0
11.0
12.0
13.0
14.0
15.0

Model
AFR
BF

10
TC
3.65
3.62
3.59
3.57
3.56
3.53

6
PI
1.62
1.65
1.68
1.70
1.71
1.74

TC
4.26
4.23
4.20
4.18
4.17
4.14

PI
1.69
1.72
1.75
1.77
1.78
1.81

TC
4.87
4.84
4.81
4.80
4.78
4.75

Outdoor temperature (C)


0
6
PI
TC
1.76
5.61
1.79
5.58
1.82
5.55
1.83
5.54
1.85
5.52
1.88
5.49

10
PI
1.84
1.87
1.90
1.92
1.93
1.96

TC
6.10
6.07
6.04
6.03
6.01
5.98

15
PI
1.89
1.92
1.95
1.97
1.98
2.01

TC

6.66
6.64
6.63
6.60

PI

2.02
2.04
2.05
2.08
3TW01142-1C

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC is shown by kW

18

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Capacities are based on the following conditions
Corresponding refrigerant piping length
7.5 m
Level difference
0m
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
4. Direct interpolation is permissible
Do not extrapolate.

Pair Application R-22 R(E)Y18-250

Capacity tables

RY60FA7V1 + FTY60GAV1B
Cooling capacity

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

TC
5.60
5.94
6.28
6.62
6.79
7.30
7.64

230V [50Hz]

20
SHC
4.22
4.28
4.34
4.40
4.43
4.52
4.58

PI
1.51
1.57
1.63
1.69
1.72
1.81
1.87

TC
5.34
5.68
6.02
6.36
6.53
7.04
7.38

25
SHC
4.14
4.20
4.26
4.32
4.35
4.44
4.50

PI
1.75
1.81
1.87
1.93
1.96
2.05
2.11

Outdoor temperature (C)


32
35
SHC
PI
TC
SHC
4.04
2.08
4.81
3.99
4.10
2.14
5.15
4.05
4.16
2.20
5.49
4.11
4.22
2.26
5.83
4.17
4.25
2.29
6.00
4.20
4.34
2.38
6.51
4.29
4.40
2.44
6.85
4.35

TC
4.97
5.31
5.65
5.99
6.16
6.67
7.01

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Model
AFR
BF

PI
2.22
2.28
2.34
2.40
2.43
2.52
2.58

40
SHC
3.92
3.98
4.04
4.10
4.13
4.22
4.28

TC
4.55
4.89
5.23
5.57
5.74
6.25
6.59

43
SHC
3.83
3.89
3.95
4.01
4.04
4.13
4.19

PI
2.74
2.80
2.86
2.92
2.95
3.04
3.10

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

(CWB)
(CDB)
(kW)
(kW)
(kW)

Model
AFR

RY60FA7V1 + FTY60GAV1B
Heating capacity

24
3

FTY
15.5

230V [50Hz]

Indoor
EDB
C
16.0
18.0
20.0
21.0
22.0
24.0

TC
4.23
4.57
4.91
5.25
5.42
5.93
6.27

NOTES
(m3/min)

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

Caution:
TC and SHC are shown by kW

EWB
C
9.0
11.0
12.0
13.0
14.0
15.0

PI
2.46
2.52
2.58
2.64
2.67
2.76
2.82

FTY
13.3
0.2

10
TC
4.11
4.07
4.03
4.01
3.99
3.95

6
PI
1.47
1.55
1.63
1.67
1.71
1.79

TC
5.09
5.05
5.01
4.99
4.97
4.93

PI
1.71
1.79
1.87
1.91
1.95
2.03

TC
6.06
6.02
5.98
5.96
5.94
5.90

Outdoor temperature (C)


0
6
PI
TC
1.95
7.23
2.03
7.19
2.11
7.15
2.15
7.13
2.19
7.11
2.27
7.07

10
PI
2.24
2.32
2.40
2.44
2.48
2.56

TC
8.01
7.97
7.93
7.91
7.89
7.85

15
PI
2.43
2.51
2.59
2.63
2.67
2.75

TC

8.90
8.88
8.86
8.82

PI

2.83
2.87
2.91
3.0
3TW01152-1B

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC is shown by kW

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Capacities are based on the following conditions
Corresponding refrigerant piping length
7.5 m
Level difference
0m
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
4. Direct interpolation is permissible
Do not extrapolate.

19

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYB3560FK7V1 + RY35DA7V1/RY45DB7V1/RY60FA7V1
Cooling capacity

Outdoor

35

45

24

60

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
3.69
3.87
4.04
4.20
4.29
4.33
4.54
4.71
3.98
4.26
4.54
4.83
4.97
5.04
5.40
5.70
5.57
5.95
6.39
6.73
6.87
7.59
8.02

20
SHC
2.60
2.64
2.67
2.71
2.73
2.73
2.77
2.82
2.98
3.03
3.09
3.14
3.17
3.19
3.25
3.31
4.56
4.56
4.61
4.75
4.80
4.90
4.94

PI
1.22
1.25
1.29
1.31
1.33
1.33
1.36
1.40
1.55
1.57
1.60
1.63
1.64
1.65
1.68
1.70
1.84
1.89
1.89
1.94
1.99
2.05
2.10

TC
3.53
3.70
3.88
4.04
4.13
4.17
4.38
4.55
3.86
4.13
4.39
4.67
4.81
4.88
5.23
5.51
5.43
5.77
6.10
6.53
6.73
7.35
7.83

25
SHC
2.52
2.57
2.60
2.63
2.65
2.65
2.70
2.74
2.92
2.97
3.03
3.08
3.11
3.12
3.19
3.25
4.42
4.42
4.47
4.56
4.56
4.70
4.75

PI
1.33
1.36
1.39
1.42
1.43
1.44
1.47
1.51
1.68
1.72
1.75
1.78
1.80
1.80
1.85
1.88
1.99
1.99
2.05
2.10
2.16
2.16
2.21

TC
3.30
3.47
3.65
3.81
3.90
3.94
4.15
4.32
3.66
3.92
4.17
4.43
4.56
4.62
4.95
5.21
5.05
5.38
5.77
6.10
6.39
6.92
7.35

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.42 1.47 3.20 2.37
2.46 1.51 3.38 2.41
2.49 1.53 3.55 2.45
2.52 1.56 3.71 2.48
2.54 1.57 3.80 2.50
2.55 1.58 3.80 2.50
2.60 1.62 4.05 2.54
2.63 1.65 4.22 2.59
2.81 1.89 3.57 2.78
2.87 1.94 3.82 2.83
2.92 1.98 4.07 2.89
2.98 2.03 4.32 2.94
3.01 2.04 4.45 2.97
3.03 2.05 4.59 3.03
3.09 2.11 4.83 3.05
3.14 2.14 5.07 3.11
4.17 2.21 4.90 4.12
4.17 2.26 5.23 4.12
4.22 2.26 5.57 4.17
4.37 2.31 5.95 4.32
4.42 2.36 6.15 4.32
4.52 2.41 6.77 4.47
4.56 2.46 7.20 4.52

PI
1.54
1.57
1.60
1.63
1.64
1.65
1.68
1.72
1.99
2.04
2.08
2.13
2.15
2.16
2.22
2.26
2.36
2.41
2.46
2.51
2.51
2.56
2.61

TC
3.04
3.21
3.39
3.55
3.64
3.68
3.89
4.06
3.40
3.64
3.88
4.12
4.24
4.30
4.60
4.84
4.66
4.95
5.23
5.62
5.82
6.48
6.87

40
SHC
2.29
2.34
2.37
2.40
2.42
2.42
2.47
2.51
2.70
2.76
2.81
2.87
2.90
2.92
2.98
3.03
4.03
4.03
4.08
4.17
4.22
4.37
4.42

PI
1.64
1.67
1.71
1.73
1.75
1.75
1.78
1.82
2.16
2.22
2.26
2.32
2.34
2.35
2.42
2.46
2.56
2.61
2.66
2.71
2.76
2.81
2.86

TC
2.84
3.02
3.19
3.35
3.44
3.49
3.69
3.87
3.19
3.41
3.64
3.86
3.97
4.03
4.31
4.53
4.32
4.66
4.90
5.23
5.43
6.05
6.48

46
SHC
2.21
2.24
2.27
2.32
2.33
2.34
2.38
2.41
2.62
2.68
2.73
2.79
2.81
2.83
2.90
2.95
3.84
3.84
3.89
4.03
4.08
4.17
4.32

PI
1.77
1.79
1.83
1.86
1.87
1.88
1.92
1.94
2.38
2.44
2.50
2.55
2.58
2.60
2.66
2.72
2.92
2.97
3.03
3.03
3.08
3.18
3.23

3TW00642-6A + 3TW01152-2C

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

20

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
BF
AFR
BF
AFR
BF

FHYB
11.5
0.15
14
0.16
17.0
0.11

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYB71125FK7V1 + RY71100B7V1
RY71125B7W1
Cooling capacity

Outdoor

71

100

125

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
6.3
6.7
7.3
7.8
8.1
8.1
8.8
9.6
8.3
8.9
10.1
10.8
11.1
11.2
12.2
13.0
11.2
12.0
12.9
13.6
13.9
14.0
15.3
16.2

20
SHC
4.9
4.9
5.0
5.2
5.3
5.3
5.4
5.4
7.0
7.0
7.1
7.4
7.5
7.5
7.6
7.7
9.2
9.2
9.3
9.6
9.7
9.7
9.9
10.0

PI
2.2
2.3
2.3
2.4
2.4
2.4
2.5
2.5
2.8
2.9
2.9
3.0
3.0
3.0
3.1
3.2
3.3
3.4
3.4
3.5
3.6
3.6
3.7
3.7

TC
6.2
6.6
7.1
7.6
7.8
8.0
8.6
9.3
8.3
8.8
9.8
10.5
10.8
11.0
11.8
12.7
10.9
11.6
12.3
13.2
13.6
13.8
14.8
15.8

25
SHC
4.8
4.8
4.9
5.0
5.2
5.2
5.3
5.3
6.9
6.9
7.0
7.3
7.4
7.4
7.5
7.6
8.9
8.9
9.0
9.2
9.2
9.2
9.5
9.6

PI
2.5
2.6
2.6
2.6
2.6
2.6
2.7
2.7
3.1
3.1
3.2
3.2
3.3
3.3
3.3
3.4
3.6
3.6
3.7
3.7
3.8
3.8
3.8
3.9

TC
5.8
6.1
6.6
7.3
7.4
7.5
8.1
8.7
8.1
8.6
9.1
9.8
10.1
10.3
11.2
11.9
10.2
10.9
11.6
12.3
12.9
13.0
14.0
14.8

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.7
5.6
4.6
4.7
2.8
6.0
4.6
4.8
2.8
6.4
4.7
4.9
2.9
6.9
4.8
5.0
2.9
7.2
4.8
5.0
2.9
7.3
4.8
5.2
3.0
8.0
4.9
5.2
3.1
8.5
5.0
6.7
3.5
7.8
6.6
6.7
3.5
8.3
6.6
6.8
3.6
8.9
6.7
6.9
3.6
9.6
6.8
7.0
3.7
10.0
6.9
7.0
3.7
10.1
6.9
7.1
3.8
11.0
7.0
7.3
3.9
11.7
7.1
8.4
3.9
9.9
8.3
8.4
4.0
10.6
8.3
8.5
4.0
11.2
8.4
8.8
4.1
12.0
8.7
8.9
4.2
12.4
8.7
8.9
4.2
12.6
8.8
9.1
4.3
13.7
9.0
9.2
4.4
14.5
9.1

PI
2.9
2.9
3.0
3.1
3.1
3.1
3.2
3.2
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.1
4.2
4.3
4.4
4.5
4.5
4.5
4.6
4.7

TC
5.3
5.6
6.1
6.5
6.7
6.8
7.5
8.1
7.5
7.8
8.4
9.0
9.4
9.5
10.4
11.1
9.4
10.0
10.6
11.3
11.7
11.9
13.1
13.9

40
SHC
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.8
6.2
6.2
6.3
6.6
6.7
6.7
6.9
7.0
8.1
8.1
8.2
8.4
8.5
8.5
8.8
8.9

PI
3.2
3.2
3.3
3.3
3.4
3.4
3.4
3.5
4.1
4.1
4.2
4.2
4.3
4.3
4.4
4.5
4.6
4.7
4.7
4.8
4.9
4.9
5.0
5.1

TC
4.9
5.3
5.6
6.1
6.3
6.4
6.9
7.5
6.9
7.5
7.8
8.3
8.6
8.8
9.6
10.3
8.7
9.4
9.9
10.6
10.9
11.1
12.2
13.1

46
SHC
4.2
4.2
4.3
4.5
4.6
4.6
4.6
4.6
6.0
6.0
6.1
6.2
6.3
6.3
6.6
6.7
7.8
7.8
7.8
8.1
8.2
8.2
8.4
8.7

PI
3.5
3.5
3.6
3.7
3.7
3.7
3.8
3.9
4.5
4.5
4.6
4.7
4.8
4.8
4.9
5.0
5.2
5.2
5.3
5.3
5.4
5.4
5.6
5.7

24
3

3TW20382-3B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model

FHYB
19
0.11
27
0.20
35
0.14

AFR
BF
AFR
BF
AFR
BF

71
100
125

7. Add the following correction value to power input (kW) of each unit

Model

NOTES

71

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FHYB
0.1
0.0
0.2
0.0
0.0

21

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYB3560FK7V1 + RY35DA7V1/RY45DB7V1/RY60FA7V1
Heating capacity

Outdoor

35

45

60

24

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
2.67
2.67
2.66
2.66
2.66
2.66
3.78
3.78
3.78
3.78
3.78
3.77
4.14
4.08
4.07
4.01
3.99
3.93

-5
PI
1.26
1.28
1.30
1.31
1.32
1.35
2.00
2.05
2.09
2.13
2.15
2.19
1.59
1.63
1.68
1.69
1.72
1.76

TC
3.12
3.10
3.09
3.08
3.07
3.06
4.30
4.29
4.28
4.28
4.27
4.25
5.07
5.54
4.99
4.98
4.96
4.92

PI
1.30
1.32
1.35
1.36
1.37
1.39
1.95
1.99
2.04
2.06
2.08
2.13
1.78
1.83
1.90
1.92
1.96
2.01

TC
3.61
3.59
3.55
3.53
3.52
3.50
4.88
4.86
4.84
4.83
4.82
4.80
6.05
6.01
5.97
5.95
5.93
5.88

10
PI
1.40
1.43
1.45
1.47
1.48
1.51
1.89
1.93
1.96
1.97
1.99
2.03
2.24
2.32
2.40
2.44
2.49
2.57

TC
4.70
4.67
4.62
4.59
4.58
4.53
6.23
6.19
6.15
6.13
6.11
6.07
8.03
8.00
7.94
7.93
7.91
7.84

15
PI
1.46
1.49
1.52
1.54
1.55
1.59
1.89
1.92
1.94
1.95
1.96
1.99
2.49
2.59
2.68
2.73
2.78
2.88

TC
5.21
5.19
5.16
5.11
6.90
6.88
6.85
6.80
8.95
8.93
8.87
8.84

PI
1.61
1.63
1.64
1.68
1.94
1.94
1.95
1.97
2.98
3.03
3.09
3.20
3TW00642-7A
3TW01152-3C

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
EDB:
TC:
PI:

Air flow rate


Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

22

outdoor temperature (CWB)


0
6
PI
TC
1.41
4.25
1.44
4.22
1.47
4.20
1.48
4.15
1.49
4.14
1.52
4.10
1.89
5.66
1.93
5.63
1.95
5.60
1.97
5.60
1.98
5.57
2.02
5.53
2.28
7.23
2.38
7.20
2.46
7.15
2.50
7.15
2.54
7.12
2.63
7.07

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
AFR
AFR

FHYB
11.5
14
17.0

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYB71125FK7V1 + RY71100B7V1
RY71125B7W1
Heating capacity

Outdoor

71

100

125

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
6.7
6.7
6.7
6.7
6.7
6.7
9.0
8.9
8.9
8.9
8.9
8.8
12.0
12.0
12.0
12.0
12.0
11.8

-5
PI
2.8
2.8
2.9
3.0
3.0
3.1
3.5
3.7
3.8
3.9
4.0
4.1
4.1
4.2
4.3
4.4
4.5
4.6

TC
7.2
7.2
7.2
7.2
7.2
7.2
9.8
9.7
9.7
9.6
9.6
9.6
13.0
13.0
12.8
12.8
12.8
12.8

PI
2.9
2.9
3.0
3.0
3.1
3.2
3.7
3.8
3.9
4.0
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8

TC
7.9
7.9
7.8
7.8
7.8
7.8
10.7
10.7
10.5
10.5
10.5
10.3
14.0
14.0
13.9
13.9
13.9
13.8

outdoor temperature (CWB)


0
6
PI
TC
2.9
8.7
3.0
8.6
3.1
8.6
3.1
8.6
3.2
8.6
3.3
8.5
3.8
11.8
3.9
11.7
4.0
11.6
4.1
11.6
4.2
11.6
4.3
11.4
4.4
15.3
4.5
15.2
4.6
15.2
4.8
15.2
4.8
15.2
5.0
15.1

10
PI
3.0
3.1
3.1
3.2
3.3
3.4
3.9
4.0
4.1
4.2
4.3
4.4
4.5
4.7
4.8
4.9
5.0
5.1

TC
9.3
9.3
9.1
9.1
9.1
9.1
12.5
12.5
12.4
12.3
12.3
12.1
16.3
16.2
16.2
16.1
16.1
16.1

15
PI
3.0
3.1
3.2
3.3
3.3
3.4
4.0
4.1
4.2
4.3
4.4
4.5
4.7
4.8
5.0
5.0
5.1
5.3

TC
10.0
10.0
9.8
9.8
13.4
13.4
13.3
13.3
17.7
17.4
17.4
17.1

PI
3.3
3.4
3.4
3.5
4.3
4.4
4.5
4.7
5.1
5.2
5.3
5.5
3TW20382-8B

24
3

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
EDB:
TC:
PI:

Air flow rate


Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

FHYB
19
0.11
27
0.2
35
0.14

6. Add the following correction value to power input (kW) of each unit

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

Model
71
100
125

Supply
V1
W1
V1
W1
W1

FHYB
0.05
0.0
0.2
0.0
0.0

23

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYK3560FJV1 + RY35DA7V1/RY45DB7V1/RY60FA7V1
Cooling capacity

Outdoor

35

45

24

60

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
3.98
4.17
4.36
4.53
4.63
4.67
4.90
5.08
4.30
4.59
4.90
5.21
5.36
5.43
5.83
6.15
5.57
5.95
6.39
6.73
6.87
7.59
8.02

20
SHC
2.80
2.84
2.88
2.91
2.94
2.94
2.98
3.03
3.22
3.28
3.34
3.40
3.43
3.45
3.52
3.58
4.56
4.56
4.61
4.75
4.80
4.90
4.94

PI
1.12
1.15
1.18
1.20
1.22
1.22
1.25
1.28
1.48
1.50
1.53
1.55
1.56
1.57
1.60
1.63
1.84
1.89
1.89
1.94
1.99
2.05
2.10

TC
3.81
3.99
4.18
4.36
4.45
4.50
4.72
4.91
4.17
4.45
4.74
5.04
5.19
5.27
5.64
5.94
5.43
5.77
6.10
6.53
6.73
7.35
7.83

25
SHC
2.71
2.76
2.80
2.83
2.85
2.85
2.90
2.95
3.15
3.21
3.27
3.33
3.36
3.37
3.45
3.51
4.42
4.42
4.47
4.56
4.56
4.70
4.75

PI
1.22
1.25
1.27
1.30
1.31
1.32
1.35
1.38
1.60
1.64
1.67
1.70
1.72
1.72
1.76
1.80
1.99
1.99
2.05
2.10
2.16
2.16
2.21

TC
3.56
3.75
3.94
4.11
4.21
4.25
4.47
4.66
3.95
4.23
4.50
4.78
4.92
4.99
5.34
5.62
5.05
5.38
5.77
6.10
6.39
6.92
7.35

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.61 1.35 3.46 2.55
2.64 1.38 3.64 2.60
2.68 1.40 3.83 2.63
2.71 1.43 4.01 2.67
2.74 1.44 4.10 2.69
2.75 1.45 4.10 2.69
2.80 1.48 4.37 2.74
2.83 1.51 4.56 2.78
3.04 1.81 3.85 3.00
3.10 1.85 4.12 3.06
3.16 1.89 4.39 3.12
3.22 1.93 4.66 3.18
3.25 1.94 4.80 3.21
3.27 1.95 4.95 3.28
3.34 2.01 5.21 3.30
3.40 2.04 5.47 3.36
4.17 2.21 4.90 4.12
4.17 2.26 5.23 4.12
4.22 2.26 5.57 4.17
4.37 2.31 5.95 4.32
4.42 2.36 6.15 4.32
4.52 2.41 6.77 4.47
4.56 2.46 7.20 4.52

PI
1.41
1.44
1.46
1.49
1.50
1.51
1.54
1.57
1.90
1.94
1.99
2.03
2.05
2.06
2.11
2.16
2.36
2.41
2.46
2.51
2.51
2.56
2.61

TC
3.28
3.47
3.65
3.83
3.92
3.97
4.19
4.38
3.67
3.93
4.19
4.44
4.57
4.64
4.96
5.22
4.66
4.95
5.23
5.62
5.82
6.48
6.87

40
SHC
2.47
2.51
2.55
2.58
2.61
2.61
2.65
2.70
2.92
2.98
3.04
3.10
3.13
3.15
3.22
3.28
4.03
4.03
4.08
4.17
4.22
4.37
4.42

PI
1.50
1.53
1.56
1.58
1.60
1.60
1.63
1.66
2.06
2.11
2.16
2.21
2.23
2.24
2.30
2.35
2.56
2.61
2.66
2.71
2.76
2.81
2.86

TC
3.07
3.26
3.44
3.62
3.71
3.76
3.98
4.17
3.44
3.68
3.93
4.17
4.29
4.34
4.65
4.89
4.32
4.66
4.90
5.23
5.43
6.05
6.48

46
SHC
2.37
2.41
2.44
2.49
2.50
2.51
2.56
2.60
2.83
2.89
2.95
3.01
3.04
3.06
3.13
3.19
3.84
3.84
3.89
4.03
4.08
4.17
4.32

PI
1.62
1.64
1.67
1.70
1.71
1.72
1.75
1.77
2.27
2.33
2.38
2.43
2.46
2.47
2.54
2.59
2.92
2.97
3.03
3.03
3.08
3.18
3.23

3TW00642-8A + 3TW01152-2C

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

24

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
BF
AFR
BF
AFR
BF

FHYK
12
0.16
12
0.18
17.0
0.07

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYK71FJV1 + RY71B7V1
RY71B7W1
Cooling capacity

Outdoor

71

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
6.4
6.8
7.4
7.9
8.2
8.2
8.9
9.7

20
SHC
4.9
4.9
5.0
5.2
5.3
5.3
5.4
5.4

PI
2.1
2.2
2.2
2.3
2.3
2.3
2.4
2.4

TC
6.3
6.7
7.2
7.7
7.9
8.1
8.7
9.4

25
SHC
4.8
4.8
4.9
5.0
5.2
5.2
5.3
5.3

PI
2.4
2.5
2.5
2.5
2.5
2.5
2.6
2.6

TC
5.9
6.2
6.7
7.4
7.5
7.6
8.2
8.8

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.6
5.7
4.6
4.7
2.7
6.1
4.6
4.8
2.7
6.5
4.7
4.9
2.8
7.0
4.8
5.0
2.8
7.3
4.8
5.0
2.8
7.4
4.8
5.2
2.9
8.1
4.9
5.2
3.0
8.6
5.0

PI
2.8
2.8
2.9
3.0
3.0
3.0
3.1
3.1

TC
5.4
5.7
6.2
6.6
6.8
6.9
7.6
8.2

40
SHC
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.8

PI
3.1
3.1
3.2
3.2
3.3
3.3
3.3
3.4

TC
5.0
5.4
5.7
6.2
6.4
6.5
7.0
7.6

46
SHC
4.2
4.2
4.3
4.5
4.6
4.6
4.6
4.6

PI
3.4
3.4
3.5
3.6
3.6
3.6
3.7
3.8

3TW20382-4B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Model
71

FHYK
17
0.07

7. Add the following correction value to power input (kW) of each unit

Model

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

AFR
BF

71

Supply
V1
W1

FHYK
0.1
0.0

24
3

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

25

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYK3560FJV1 + RY35DA7V1/RY45DB7V1/RY60FA7V1
Heating capacity

Outdoor

35

45

60

24

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
2.77
2.77
2.76
2.76
2.76
2.76
3.91
3.91
3.91
3.91
3.91
3.90
4.14
4.08
4.07
4.01
3.99
3.93

-5
PI
1.21
1.23
1.25
1.26
1.27
1.29
1.94
1.99
2.03
2.06
2.08
2.13
1.59
1.63
1.68
1.69
1.72
1.76

TC
3.24
3.21
3.20
3.19
3.18
3.17
4.45
4.44
4.43
4.43
4.42
4.40
5.07
5.54
4.99
4.98
4.96
4.92

PI
1.25
1.27
1.29
1.30
1.31
1.33
1.89
1.93
1.98
2.00
2.02
2.06
1.78
1.83
1.90
1.92
1.96
2.01

TC
3.73
3.71
3.68
3.66
3.65
3.63
5.05
5.03
5.01
5.00
4.99
4.97
6.05
6.01
5.97
5.95
5.93
5.88

10
PI
1.34
1.37
1.39
1.41
1.42
1.45
1.84
1.87
1.90
1.91
1.93
1.96
2.24
2.32
2.40
2.44
2.49
2.57

TC
4.87
4.84
4.79
4.75
4.75
4.69
6.45
6.41
6.37
6.35
6.33
6.29
8.03
8.00
7.94
7.93
7.91
7.84

15
PI
1.40
1.43
1.46
1.48
1.49
1.52
1.84
1.86
1.88
1.89
1.90
1.93
2.49
2.59
2.68
2.73
2.78
2.88

TC
5.40
5.38
5.35
5.29
7.15
7.13
7.10
7.04
8.95
8.93
8.87
8.84

PI
1.54
1.56
1.57
1.61
1.88
1.88
1.89
1.91
2.98
3.03
3.09
3.20
3TW00642-9A
3TW01152-3C

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
EDB:
TC:
PI:

Air flow rate


Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

26

outdoor temperature (CWB)


0
6
PI
TC
1.35
4.40
1.38
4.37
1.41
4.35
1.42
4.30
1.43
4.29
1.46
4.24
1.84
5.86
1.87
5.83
1.89
5.80
1.91
5.80
1.92
5.77
1.95
5.73
2.28
7.23
2.38
7.20
2.46
7.15
2.50
7.15
2.54
7.12
2.63
7.07

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
AFR
AFR

FHYK
12
12
17.0

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYK71FJV1 + RY71B7V1
RY71B7W1
Heating capacity

Outdoor

71

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
6.8
6.8
6.8
6.8
6.8
6.8

-5
PI
2.7
2.7
2.8
2.9
2.9
3.0

TC
7.3
7.3
7.3
7.3
7.3
7.3

PI
2.8
2.8
2.9
2.9
3.0
3.1

TC
8.0
8.0
7.9
7.9
7.9
7.9

Outdoor temperature (CDB)


0
6
PI
TC
2.8
8.8
2.9
8.7
3.0
8.7
3.0
8.7
3.1
8.7
3.2
8.6

10
PI
2.9
3.0
3.0
3.1
3.2
3.3

TC
9.4
9.4
9.3
9.3
9.3
9.3

15
PI
2.9
3.0
3.1
3.2
3.2
3.3

TC
10.1
10.1
9.9
9.9

PI
3.2
3.3
3.3
3.4
3TW20382-9A

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
EDB:
TC:
PI:

Air flow rate


Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CDB)
(kW)
(kW)

Model
71

AFR
BF

FHYK
17
0.07

6. Add the following correction value to power input (kW) of each unit

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71

NOTES

Supply
V1
W1

FHYK
0.1
0.0

24
3

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

27

Pair Application R-22 R(E)Y18-250

Capacity tables

FHY3560BJV1 + RY35DA7V1/RY45DB7V1/RY60FA7V1

FHY

Cooling capacity

Outdoor

35

45

24
3

60

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
22.0 30.0
24.0 32.0

Model
AFR
BF

230V [50Hz]

TC
3.98
4.17
4.36
4.53
4.63
4.67
4.90
5.08
4.30
4.59
4.90
5.21
5.36
5.43
5.83
6.15
5.57
5.95
6.39
6.73
6.87
7.59
8.02

20
SHC
2.80
2.84
2.88
2.91
2.94
2.94
2.98
3.03
3.22
3.28
3.34
3.39
3.42
3.44
3.51
3.57
4.56
4.56
4.61
4.75
4.80
4.90
4.94

PI
1.18
1.22
1.25
1.27
1.29
1.29
1.32
1.36
1.48
1.50
1.53
1.55
1.56
1.57
1.60
1.63
1.84
1.89
1.89
1.94
1.99
2.05
2.10

TC
3.81
3.99
4.18
4.36
4.45
4.50
4.72
4.91
4.17
4.45
4.74
5.04
5.19
5.27
5.64
5.94
5.43
5.77
6.10
6.53
6.73
7.35
7.83

25
SHC
2.71
2.76
2.80
2.83
2.85
2.85
2.90
2.95
3.15
3.21
3.27
3.33
3.36
3.36
3.44
3.50
4.42
4.42
4.47
4.56
4.56
4.70
4.75

PI
1.29
1.32
1.34
1.38
1.39
1.40
1.43
1.46
1.60
1.64
1.67
1.70
1.72
1.72
1.76
1.80
1.99
1.99
2.05
2.10
2.16
2.16
2.21

TC
3.56
3.75
3.94
4.11
4.21
4.25
4.47
4.66
3.95
4.23
4.50
4.78
4.92
4.99
5.34
5.62
5.05
5.38
5.77
6.10
6.39
6.92
7.35

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.61 1.43 3.46 2.55
2.64 1.46 3.64 2.60
2.68 1.48 3.83 2.63
2.71 1.52 4.01 2.67
2.74 1.53 4.10 2.69
2.75 1.54 4.10 2.69
2.80 1.57 4.37 2.74
2.83 1.60 4.56 2.78
3.04 1.81 3.85 3.00
3.10 1.85 4.12 3.06
3.16 1.89 4.39 3.12
3.22 1.93 4.66 3.18
3.25 1.94 4.80 3.21
3.27 1.95 4.95 3.28
3.34 2.01 5.21 3.30
3.39 2.04 5.47 3.36
4.17 2.21 4.90 4.12
4.17 2.26 5.23 4.12
4.22 2.26 5.57 4.17
4.37 2.31 5.95 4.32
4.42 2.36 6.15 4.32
4.52 2.41 6.77 4.47
4.56 2.46 7.20 4.52

PI
1.49
1.53
1.55
1.58
1.59
1.60
1.63
1.66
1.90
1.94
1.99
2.03
2.05
2.06
2.11
2.16
2.36
2.41
2.46
2.51
2.51
2.56
2.61

TC
3.28
3.47
3.65
3.83
3.92
3.97
4.19
4.38
3.67
3.93
4.19
4.44
4.57
4.64
4.96
5.22
4.66
4.95
5.23
5.62
5.82
6.48
6.87

40
SHC
2.47
2.51
2.55
2.58
2.61
2.61
2.65
2.70
2.92
2.98
3.04
3.10
3.13
3.15
3.22
3.28
4.03
4.03
4.08
4.17
4.22
4.37
4.42

PI
1.59
1.62
1.65
1.68
1.70
1.70
1.73
1.76
2.06
2.11
2.16
2.21
2.23
2.24
2.30
2.35
2.56
2.61
2.66
2.71
2.76
2.81
2.86

TC
3.07
3.26
3.44
3.62
3.71
3.76
3.98
4.17
3.44
3.68
3.93
4.17
4.29
4.34
4.65
4.89
4.32
4.66
4.90
5.23
5.43
6.05
6.48

35
13
0.2

45
13
0.09

46
SHC
2.37
2.41
2.44
2.49
2.50
2.51
2.56
2.60
2.83
2.89
2.95
3.01
3.04
3.06
3.13
3.19
3.84
3.84
3.89
4.03
4.08
4.17
4.32

PI
1.72
1.74
1.77
1.80
1.81
1.82
1.86
1.88
2.27
2.33
2.38
2.43
2.46
2.47
2.54
2.59
2.92
2.97
3.03
3.03
3.08
3.18
3.23

3TW00642-4B + 3TW01152-2C

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

28

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
BF
AFR
BF
AFR
BF

FHY
13
0.20
13
0.09
16.0
0.10

Pair Application R-22 R(E)Y18-250

Capacity tables

FHY71125BJV1 + RY71100B7V1
RY71125B7W1
Cooling capacity

Outdoor

71

100

125

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
6.4
6.8
7.4
7.9
8.2
8.2
8.9
9.7
8.3
8.9
10.1
10.8
11.1
11.2
12.2
13.0
11.2
12.0
12.9
13.6
13.9
14.0
15.3
16.2

20
SHC
4.9
4.9
5.0
5.2
5.3
5.3
5.4
5.4
7.0
7.0
7.1
7.4
7.5
7.5
7.6
7.7
9.2
9.2
9.3
9.6
9.7
9.7
9.9
10.0

PI
2.1
2.2
2.2
2.3
2.3
2.3
2.4
2.4
2.6
2.7
2.7
2.8
2.8
2.8
2.9
3.0
3.3
3.4
3.4
3.5
3.6
3.6
3.7
3.7

TC
6.3
6.7
7.2
7.7
7.9
8.1
8.7
9.4
8.3
8.8
9.8
10.5
10.8
11.0
11.8
12.7
10.9
11.6
12.3
13.2
13.6
13.8
14.8
15.8

25
SHC
4.8
4.8
4.9
5.0
5.2
5.2
5.3
5.3
6.9
6.9
7.0
7.3
7.4
7.4
7.5
7.6
8.9
8.9
9.0
9.2
9.2
9.2
9.5
9.6

PI
2.4
2.5
2.5
2.5
2.5
2.5
2.6
2.6
2.9
2.9
3.0
3.0
3.1
3.1
3.1
3.2
3.6
3.6
3.7
3.7
3.8
3.8
3.8
3.9

TC
5.9
6.2
6.7
7.4
7.5
7.6
8.2
8.8
8.1
8.6
9.1
9.8
10.1
10.3
11.2
11.9
10.2
10.9
11.6
12.3
12.9
13.0
14.0
14.8

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.6
5.7
4.6
4.7
2.7
6.1
4.6
4.8
2.7
6.5
4.7
4.9
2.8
7.0
4.8
5.0
2.8
7.3
4.8
5.0
2.8
7.4
4.8
5.2
2.9
8.1
4.9
5.2
3.0
8.6
5.0
6.7
3.3
7.8
6.6
6.7
3.3
8.3
6.6
6.8
3.4
8.9
6.7
6.9
3.4
9.6
6.8
7.0
3.5
10.0
6.9
7.0
3.5
10.1
6.9
7.1
3.6
11.0
7.0
7.3
3.7
11.7
7.1
8.4
3.9
9.9
8.3
8.4
4.0
10.6
8.3
8.5
4.0
11.2
8.4
8.8
4.1
12.0
8.7
8.9
4.2
12.4
8.7
8.9
4.2
12.6
8.8
9.1
4.3
13.7
9.0
9.2
4.4
14.5
9.1

PI
2.8
2.8
2.9
3.0
3.0
3.0
3.1
3.1
3.5
3.5
3.6
3.6
3.7
3.7
3.8
3.9
4.2
4.3
4.4
4.5
4.5
4.5
4.6
4.7

TC
5.4
5.7
6.2
6.6
6.8
6.9
7.6
8.2
7.5
7.8
8.4
9.0
9.4
9.5
10.4
11.1
9.4
10.0
10.6
11.3
11.7
11.9
13.1
13.9

40
SHC
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.8
6.2
6.2
6.3
6.6
6.7
6.7
6.9
7.0
8.1
8.1
8.2
8.4
8.5
8.5
8.8
8.9

PI
3.1
3.1
3.2
3.2
3.3
3.3
3.3
3.4
3.9
3.9
4.0
4.0
4.1
4.1
4.2
4.3
4.6
4.7
4.7
4.8
4.9
4.9
5.0
5.1

TC
5.0
5.4
5.7
6.2
6.4
6.5
7.0
7.6
6.9
7.5
7.8
8.3
8.6
8.8
9.6
10.3
8.7
9.4
9.9
10.6
10.9
11.1
12.2
13.1

46
SHC
4.2
4.2
4.3
4.5
4.6
4.6
4.6
4.6
6.0
6.0
6.1
6.2
6.3
6.3
6.6
6.7
7.8
7.8
7.8
8.1
8.2
8.2
8.4
8.7

PI
3.4
3.4
3.5
3.6
3.6
3.6
3.7
3.8
4.3
4.3
4.4
4.5
4.6
4.6
4.7
4.8
5.2
5.2
5.3
5.3
5.4
5.4
5.6
5.7

24
3

3TW20382-2B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model

FHY
17
0.10
24
0.14
30
0.13

AFR
BF
AFR
BF
AFR
BF

71
100
125

7. Add the following correction value to power input (kW) of each unit

Model

NOTES

71

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FHY
0.1
0.0
0.2
0.0
0.0

29

Pair Application R-22 R(E)Y18-250

Capacity tables

FHY3560BJV1 + RY35DA7V1/RY45DB7V1/RY60FA7V1
Heating capacity

Outdoor

35

45

60

24

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
2.77
2.77
2.76
2.76
2.76
2.76
3.91
3.91
3.91
3.91
3.91
3.90
4.14
4.08
4.07
4.01
3.99
3.93

-5
PI
1.24
1.26
1.28
1.29
1.30
1.32
1.98
2.03
2.07
2.11
2.13
2.17
1.59
1.63
1.68
1.69
1.72
1.76

TC
3.24
3.21
3.20
3.19
3.18
3.17
4.45
4.44
4.43
4.43
4.42
4.40
5.07
5.54
4.99
4.98
4.96
4.92

PI
1.28
1.30
1.32
1.33
1.34
1.36
1.93
1.97
2.02
2.04
2.06
2.11
1.78
1.83
1.90
1.92
1.96
2.01

TC
3.73
3.71
3.68
3.66
3.65
3.63
5.05
5.03
5.01
5.00
4.99
4.97
6.05
6.01
5.97
5.95
5.93
5.88

10
PI
1.37
1.40
1.42
1.44
1.45
1.48
1.87
1.91
1.94
1.95
1.97
2.01
2.24
2.32
2.40
2.44
2.49
2.57

TC
4.87
4.84
4.79
4.75
4.75
4.69
6.45
6.41
6.37
6.35
6.33
6.29
8.03
8.00
7.94
7.93
7.91
7.84

15
PI
1.43
1.46
1.49
1.51
1.52
1.55
1.87
1.90
1.92
1.93
1.94
1.97
2.49
2.59
2.68
2.73
2.78
2.88

TC
5.40
5.38
5.35
5.29
7.15
7.13
7.10
7.04
8.95
8.93
8.87
8.84

PI
1.57
1.59
1.60
1.64
1.92
1.92
1.93
1.9
2.98
3.03
3.09
3.20
3TW00642-5B
3TW01152-3C

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
EDB:
TC:
PI:

Air flow rate


Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

30

outdoor temperature (CWB)


0
6
PI
TC
1.38
4.40
1.41
4.37
1.44
4.35
1.45
4.30
1.46
4.29
1.49
4.24
1.87
5.86
1.91
5.83
1.93
5.80
1.95
5.80
1.96
5.77
2.00
5.73
2.28
7.23
2.38
7.20
2.46
7.15
2.50
7.15
2.54
7.12
2.63
7.07

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
AFR
AFR

FHY
13
13
16.0

Pair Application R-22 R(E)Y18-250

Capacity tables

FHY71125BJV1 + RY71100B7V1
RY71125B7W1
Heating capacity

Outdoor

71

100

125

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
6.8
6.8
6.8
6.8
6.8
6.8
9.0
8.9
8.9
8.9
8.9
8.8
12.0
12.0
12.0
12.0
12.0
11.8

-5
PI
2.7
2.7
2.8
2.9
2.9
3.0
3.2
3.3
3.4
3.5
3.6
3.7
4.0
4.1
4.2
4.3
4.4
4.5

TC
7.3
7.3
7.3
7.3
7.3
7.3
9.8
9.7
9.7
9.6
9.6
9.6
13.0
13.0
12.8
12.8
12.8
12.8

PI
2.8
2.8
2.9
2.9
3.0
3.1
3.3
3.4
3.5
3.6
3.7
3.8
4.2
4.3
4.4
4.5
4.6
4.7

TC
8.0
8.0
7.9
7.9
7.9
7.9
10.7
10.7
10.5
10.5
10.5
10.3
14.0
14.0
13.9
13.9
13.9
13.8

outdoor temperature (CWB)


0
6
PI
TC
2.8
8.8
2.9
8.7
3.0
8.7
3.0
8.7
3.1
8.7
3.2
8.6
3.4
11.8
3.5
11.7
3.6
11.6
3.7
11.6
3.8
11.6
3.9
11.4
4.3
15.3
4.4
15.2
4.5
15.2
4.7
15.2
4.7
15.2
4.9
15.1

10
PI
2.9
3.0
3.0
3.1
3.2
3.3
3.5
3.6
3.7
3.8
3.9
4.0
4.4
4.6
4.7
4.8
4.9
5.0

TC
9.4
9.4
9.3
9.3
9.3
9.3
12.5
12.5
12.4
12.3
12.3
12.1
16.3
16.2
16.2
16.1
16.1
16.1

15
PI
2.9
3.0
3.1
3.2
3.2
3.3
3.6
3.7
3.8
3.9
4.0
4.1
4.6
4.7
4.9
4.9
5.0
5.2

TC
/
/
10.1
10.1
9.9
9.9
/
/
13.4
13.4
13.3
13.3
/
/
17.7
17.4
17.4
17.1

PI
/
/
3.2
3.3
3.3
3.4
/
/
3.9
4.0
4.1
4.2
/
/
5.0
5.1
5.2
5.4
3TW20382-7A

AFR:
EDB:
TC:
PI:

5. Air flow rate and BF are tabulated below.

SYMBOLS
Air flow rate
Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

24

FHY
17
0.1
24
0.14
30
0.13

6. Add the following correction value to power input (kW) of each unit

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
outdoor air : 85 % RH. however, the condition on nominal
capacity is 7 CDB/6 CWB 7.5 m
Level difference: 0 m

Split - Sky Air Outdoor Units

Model
71
100
125

Supply
V1
W1
V1
W1
W1

FHY
0.1
0.0
0.2
0.0
0.0

31

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYC3560B7 + RY35DA7V1/RY45DB7V1/RY60FA7V1
Cooling capacity

Outdoor

35

45

24

60

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
3.50
3.66
3.83
3.98
4.06
4.10
4.30
4.46
4.30
4.59
4.90
5.21
5.36
5.43
5.83
6.15
5.57
5.95
6.39
6.73
6.87
7.59
8.02

20
SHC
2.46
2.50
2.53
2.56
2.58
2.58
2.62
2.66
3.22
3.28
3.34
3.39
3.42
3.44
3.51
3.57
4.56
4.56
4.61
4.75
4.80
4.90
4.94

PI
1.21
1.25
1.28
1.30
1.32
1.32
1.36
1.39
1.58
1.51
1.54
1.57
1.58
1.59
1.62
1.64
1.84
1.89
1.89
1.94
1.99
2.05
2.10

TC
3.34
3.51
3.67
3.83
3.91
3.95
4.15
4.31
4.17
4.45
4.74
5.04
5.19
5.27
5.64
5.94
5.43
5.77
6.10
6.53
6.73
7.35
7.83

25
SHC
2.39
2.43
2.46
2.49
2.51
2.51
2.55
2.59
3.15
3.21
3.27
3.33
3.36
3.36
3.44
3.50
4.42
4.42
4.47
4.56
4.56
4.70
4.75

PI
1.32
1.36
1.38
1.41
1.42
1.43
1.47
1.50
1.62
1.65
1.68
1.72
1.74
1.74
1.78
1.81
1.99
1.99
2.05
2.10
2.16
2.16
2.21

TC
3.13
3.29
3.46
3.61
3.69
3.73
3.93
4.09
3.95
4.23
4.50
4.78
4.92
4.99
5.34
5.62
5.05
5.38
5.77
6.10
6.39
6.92
7.35

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.29 1.47 3.03 2.24
2.32 1.50 3.20 2.28
2.36 1.52 3.36 2.31
2.39 1.55 3.52 2.35
2.41 1.56 3.60 2.37
2.42 1.58 3.60 2.37
2.46 1.61 3.84 2.41
2.49 1.64 4.00 2.45
3.04 1.82 3.85 3.00
3.10 1.87 4.12 3.06
3.16 1.91 4.39 3.12
3.22 1.95 4.66 3.18
3.25 1.96 4.80 3.21
3.27 1.97 4.95 3.28
3.34 2.03 5.21 3.30
3.39 2.06 5.47 3.36
4.17 2.21 4.90 4.12
4.17 2.26 5.23 4.12
4.22 2.26 5.57 4.17
4.37 2.31 5.95 4.32
4.42 2.36 6.15 4.32
4.52 2.41 6.77 4.47
4.56 2.46 7.20 4.52

PI
1.53
1.56
1.59
1.62
1.63
1.64
1.67
1.71
1.92
1.96
2.01
2.05
2.07
2.08
2.13
2.18
2.36
2.41
2.46
2.51
2.51
2.56
2.61

TC
2.88
3.04
3.21
3.36
3.45
3.49
3.68
3.85
3.67
3.93
4.19
4.44
4.57
4.64
4.96
5.22
4.66
4.95
5.23
5.62
5.82
6.48
6.87

40
SHC
2.17
2.21
2.24
2.27
2.29
2.29
2.33
2.38
2.92
2.98
3.04
3.10
3.13
3.15
3.22
3.29
4.03
4.03
4.08
4.17
4.22
4.37
4.42

PI
1.63
1.66
1.70
1.72
1.74
1.74
1.77
1.81
2.08
2.13
2.18
2.23
2.25
2.26
2.33
2.37
2.56
2.61
2.66
2.71
2.76
2.81
2.86

TC
2.69
2.86
3.02
3.18
3.26
3.30
3.50
3.66
3.44
3.68
3.93
4.17
4.29
4.34
4.65
4.89
4.32
4.66
4.90
5.23
5.43
6.05
6.48

46
SHC
2.09
2.12
2.15
2.19
2.20
2.21
2.25
2.28
2.83
2.89
2.95
3.01
3.04
3.06
3.13
3.19
3.84
3.84
3.89
4.03
4.08
4.17
4.32

PI
1.76
1.78
1.82
1.85
1.86
1.87
1.90
1.93
2.30
2.35
2.40
2.46
2.49
2.50
2.56
2.62
2.92
2.97
3.03
3.03
3.08
3.18
3.23

3TW00642-2C
3TW01152-2C

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate..
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

32

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
BF
AFR
BF
AFR
BF

FHYC
14
0.16
15
0.12
18
0.10

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYC71125B7 + RY71100B7V1
RY71125B7W1
Cooling capacity

Outdoor

71

100

125

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
6.4
6.8
7.4
7.9
8.2
8.2
8.9
9.7
8.6
9.2
10.4
11.1
11.4
11.5
12.6
13.4
11.6
12.4
13.3
14.0
14.3
14.5
15.8
16.7

20
SHC
4.9
4.9
5.0
5.2
5.3
5.3
5.4
5.4
7.2
7.2
7.3
7.6
7.7
7.7
7.8
7.9
9.5
9.5
9.6
9.9
10.0
10.0
10.2
10.3

PI
2.1
2.2
2.2
2.3
2.3
2.3
2.4
2.4
2.7
2.8
2.8
2.9
2.9
2.9
3.0
3.1
3.4
3.5
3.5
3.6
3.7
3.7
3.8
3.8

TC
6.3
6.7
7.2
7.7
7.9
8.1
8.7
9.4
8.5
9.1
10.1
10.8
11.1
11.3
12.2
13.1
11.3
12.0
12.7
13.6
14.0
14.2
15.3
16.3

25
SHC
4.8
4.8
4.9
5.0
5.2
5.2
5.3
5.3
7.1
7.1
7.2
7.5
7.6
7.6
7.7
7.8
9.2
9.2
9.3
9.5
9.5
9.5
9.8
9.9

PI
2.4
2.5
2.5
2.5
2.5
2.5
2.6
2.6
3.0
3.0
3.1
3.1
3.2
3.2
3.2
3.3
3.7
3.7
3.8
3.8
3.9
3.9
3.9
4.0

TC
5.9
6.2
6.7
7.4
7.5
7.6
8.2
8.8
8.3
8.9
9.4
10.1
10.4
10.6
11.5
12.3
10.5
11.2
12.0
12.7
13.3
13.4
14.4
15.3

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.6
5.7
4.6
4.7
2.7
6.1
4.6
4.8
2.7
6.5
4.7
4.9
2.8
7.0
4.8
5.0
2.8
7.3
4.8
5.0
2.8
7.4
4.8
5.2
2.9
8.1
4.9
5.2
3.0
8.6
5.0
6.9
3.4
8.0
6.8
6.9
3.4
8.6
6.8
7.0
3.5
9.2
6.9
7.1
3.5
9.9
7.0
7.2
3.6
10.3
7.1
7.2
3.6
10.4
7.1
7.3
3.7
11.3
7.2
7.5
3.8
12.0
7.3
8.7
4.0
10.2
8.6
8.7
4.1
10.9
8.6
8.8
4.1
11.6
8.7
9.1
4.2
12.4
9.0
9.2
4.3
12.8
9.0
9.2
4.3
13.0
9.1
9.4
4.4
14.1
9.3
9.5
4.5
15.0
9.4

PI
2.8
2.8
2.9
3.0
3.0
3.0
3.1
3.1
3.6
3.6
3.7
3.7
3.8
3.8
3.9
4.0
4.3
4.4
4.5
4.6
4.6
4.6
4.7
4.8

TC
5.4
5.7
6.2
6.6
6.8
6.9
7.6
8.2
7.7
8.0
8.7
9.3
9.7
9.8
10.7
11.4
9.5
10.3
10.9
11.7
12.1
12.3
13.5
14.3

40
SHC
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.8
6.4
6.4
6.5
6.8
6.9
6.9
7.1
7.2
8.4
8.4
8.5
8.7
8.8
8.8
9.1
9.2

PI
3.1
3.1
3.2
3.2
3.3
3.3
3.3
3.4
4.0
4.0
4.1
4.1
4.2
4.2
4.3
4.4
4.7
4.8
4.9
5.0
5.1
5.1
5.2
5.3

TC
5.0
5.4
5.7
6.2
6.4
6.5
7.0
7.6
7.1
7.7
8.0
8.6
8.9
9.1
9.9
10.6
9.0
9.7
10.2
10.9
11.3
11.5
12.6
13.5

46
SHC
4.2
4.2
4.3
4.5
4.6
4.6
4.6
4.6
6.2
6.2
6.3
6.4
6.5
6.5
6.8
6.9
8.0
8.0
8.1
8.4
8.5
8.5
8.7
9.0

PI
3.4
3.4
3.5
3.6
3.6
3.6
3.7
3.8
4.4
4.4
4.5
4.6
4.7
4.7
4.8
4.9
5.4
5.4
5.5
5.5
5.6
5.6
5.8
5.9

24
3

3TW20382-1C

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

FHYC
18
0.10
28
0.16
31
0.07

7. Add the following correction value to power input (kW) of each unit

Model

NOTES

71

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FHYC
0.1
0.0
0.2
0.0
0.0

33

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYC3560B7 + RY35DA7V1/RY45DB7V1/RY60FA7V1
Heating capacity

Outdoor

35

45

60

24

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
2.96
2.96
2.95
2.95
2.95
2.95
3.91
3.91
3.91
3.91
3.91
3.90
4.14
4.08
4.07
4.01
3.99
3.93

-5
PI
1.32
1.35
1.37
1.38
1.37
1.41
1.97
2.02
2.06
2.09
2.12
2.16
1.59
1.63
1.68
1.69
1.72
1.76

TC
3.46
3.44
3.43
3.41
3.40
3.39
4.45
4.44
4.43
4.43
4.42
4.40
5.07
5.54
4.99
4.98
4.96
4.92

PI
1.37
1.39
1.41
1.42
1.43
1.45
1.92
1.96
2.01
2.03
2.05
2.09
1.78
1.83
1.90
1.92
1.96
2.01

TC
3.99
3.97
3.94
3.91
3.90
3.88
5.05
5.03
5.01
5.00
4.99
4.97
6.05
6.01
5.97
5.95
5.93
5.88

10
PI
1.47
1.50
1.52
1.54
1.55
1.59
1.86
1.90
1.93
1.94
1.96
2.00
2.24
2.32
2.40
2.44
2.49
2.57

TC
5.21
5.17
5.12
5.08
5.07
5.01
6.45
6.41
6.37
6.35
6.33
6.29
8.03
8.00
7.94
7.93
7.91
7.84

15
PI
1.53
1.56
1.60
1.62
1.63
1.66
1.86
1.89
1.91
1.92
1.93
1.96
2.49
2.59
2.68
2.73
2.78
2.88

TC
5.77
5.75
5.72
5.66
7.15
7.13
7.10
7.04
8.95
8.93
8.87
8.84

PI
1.68
1.71
1.72
1.76
1.91
1.91
1.92
1.94
2.98
3.03
3.09
3.20
3TW00642-3C
3TW01152-3C

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
EDB:
TC:
PI:

Air flow rate


Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

34

outdoor temperature (CWB)


0
6
PI
TC
1.48
4.71
1.51
4.67
1.54
4.65
1.55
4.59
1.56
4.58
1.60
4.54
1.86
5.86
1.90
5.83
1.92
5.80
1.94
5.80
1.95
5.77
1.98
5.73
2.28
7.23
2.38
7.20
2.46
7.15
2.50
7.15
2.54
7.12
2.63
7.07

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
AFR
AFR

FHYC
14
15
18

Pair Application R-22 R(E)Y18-250

Capacity tables

FHYC71125B7 + RY71100B7V1
RY71125B7W1
Heating capacity

Outdoor

71

100

125

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
6.8
6.8
6.8
6.8
6.8
6.8
9.5
9.4
9.4
9.4
9.4
9.3
12.1
12.1
12.1
12.1
12.1
11.9

-5
PI
2.7
2.7
2.8
2.9
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
4.0
4.1
4.2
4.3
4.4
4.5

TC
7.3
7.3
7.3
7.3
7.3
7.3
10.3
10.2
10.2
10.1
10.1
10.1
13.0
13.0
12.9
12.9
12.9
12.9

PI
2.8
2.8
2.9
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
4.2
4.3
4.4
4.5
4.6
4.7

TC
8.0
8.0
7.9
7.9
7.9
7.9
11.2
11.2
11.0
11.0
11.0
10.8
14.1
14.1
14.0
14.0
14.0
13.9

outdoor temperature (CWB)


0
6
PI
TC
2.8
8.8
2.9
8.7
3.0
8.7
3.0
8.7
3.1
8.7
3.2
8.6
3.3
12.4
3.4
12.3
3.5
12.2
3.6
12.2
3.7
12.2
3.8
12.0
4.3
15.4
4.4
15.3
4.5
15.3
4.7
15.3
4.7
15.3
4.9
15.2

10
PI
2.9
3.0
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
4.4
4.6
4.7
4.8
4.9
5.0

TC
9.4
9.4
9.3
9.3
9.3
9.3
13.2
13.2
13.1
13.0
13.0
12.7
16.4
16.3
16.3
16.2
16.2
16.2

15
PI
2.9
3.0
3.1
3.2
3.2
3.3
3.5
3.6
3.7
3.8
3.9
4.0
4.6
4.7
4.9
4.9
5.0
5.2

TC
10.1
10.1
9.9
9.9
14.1
14.1
13.9
13.9
17.8
17.6
17.6
17.2

PI
3.2
3.3
3.3
3.4
3.8
3.9
4.0
4.1
5.0
5.1
5.2
5.4
3TW20382-6B

AFR:
EDB:
TC:
PI:

5. Air flow rate and BF are tabulated below.

SYMBOLS
Air flow rate
Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

24

FHYC
18
0.1
28
0.16
31
0.07

6. Add the following correction value to power input (kW) of each unit

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

Model
71
100
125

Supply
V1
W1
V1
W1
W1

FHYC
0.1
0.0
0.2
0.0
0.0

35

Pair Application R-22 R(E)Y18-250

Capacity tables

FAY71100FJV1 + RY71100B7V1
RY71100B7W1
Cooling capacity

Outdoor

71

100

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
6.4
6.8
7.4
7.9
8.2
8.2
8.9
9.5
8.6
9.2
10.4
11.1
11.4
11.5
12.6
13.4

20
SHC
4.9
4.9
5.0
5.2
5.3
5.3
5.4
5.4
7.2
7.2
7.3
7.6
7.7
7.7
7.8
7.9

PI
2.0
2.1
2.1
2.2
2.2
2.2
2.3
2.3
2.5
2.7
2.7
2.8
2.8
2.8
2.9
3.0

TC
6.3
6.7
7.2
7.7
7.9
8.1
8.7
9.4
8.5
9.1
10.1
10.8
11.1
11.3
12.2
13.1

25
SHC
4.8
4.8
4.9
5.0
5.2
5.2
5.3
5.3
7.1
7.1
7.2
7.5
7.6
7.6
7.7
7.8

PI
2.3
2.4
2.4
2.4
2.4
2.4
2.5
2.5
2.8
2.8
2.9
2.9
3.0
3.0
3.0
3.1

TC
5.9
6.2
6.7
7.4
7.5
7.6
8.2
8.8
8.3
8.9
9.4
10.1
10.4
10.6
11.5
12.3

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.5
5.7
4.6
4.7
2.6
6.1
4.6
4.8
2.6
6.5
4.7
4.9
2.7
7.0
4.8
5.0
2.7
7.3
4.8
5.0
2.7
7.4
4.8
5.2
2.8
8.1
4.9
5.2
2.9
8.6
5.0
6.9
3.2
8.0
6.8
6.9
3.2
8.6
6.8
7.0
3.3
9.2
6.9
7.1
3.3
9.9
7.0
7.2
3.4
10.3
7.1
7.2
3.4
10.4
7.1
7.3
3.5
11.3
7.2
7.5
3.6
12.0
7.3

PI
2.7
2.7
2.8
2.9
2.9
2.9
3.0
3.0
3.4
3.4
3.5
3.5
3.6
3.6
3.7
3.8

TC
5.4
5.7
6.2
6.6
6.8
6.9
7.6
8.2
7.7
8.0
8.7
9.3
9.7
9.8
10.7
11.4

40
SHC
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.8
6.4
6.4
6.5
6.8
6.9
6.9
7.1
7.2

PI
3.0
3.0
3.1
3.1
3.2
3.2
3.2
3.3
3.8
3.8
3.9
3.9
4.0
4.0
4.1
4.2

TC
5.0
5.4
5.7
6.2
6.4
6.5
7.0
7.6
7.1
7.7
8.0
8.6
8.9
9.1
9.9
10.6

46
SHC
4.2
4.2
4.3
4.5
4.6
4.6
4.6
4.6
6.2
6.2
6.3
6.4
6.5
6.5
6.8
6.9

PI
3.3
3.3
3.4
3.5
3.5
3.5
3.6
3.7
4.2
4.2
4.2
4.3
4.4
4.4
4.5
4.6

3TW20382-5B

24
3

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)

Model

(CWB)
(CDB)
(kW)
(kW)
(kW)

71

FAY
27
0.10
27
0.10

7. Add the following correction value to power input (kW) of each unit

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71

NOTES

100

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

36

100

AFR
BF
AFR
BF

Split - Sky Air Outdoor Units

Supply
V1
W1
V1
W1

FAY
0.1
0.0
0.2
0.0

Pair Application R-22 R(E)Y18-250

Capacity tables

FAY71100FJV1 + RY71100B7V1
RY71100B7W1
Heating capacity

Outdoor

71

100

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
6.5
6.5
6.5
6.5
6.5
6.5
9.3
9.2
9.2
9.2
9.2
9.1

-5
PI
2.6
2.6
2.7
2.8
2.8
2.9
3.4
3.5
3.6
3.7
3.8
3.9

TC
6.9
6.9
6.9
6.9
6.9
6.9
10.2
10.1
10.1
10.0
10.0
10.0

PI
2.7
2.7
2.8
2.8
2.9
3.0
3.5
3.6
3.7
3.8
3.9
4.0

TC
7.7
7.7
7.6
7.6
7.6
7.6
11.0
11.0
10.8
10.8
10.8
10.6

outdoor temperature (CWB)


0
6
PI
TC
2.7
8.4
2.8
8.3
2.9
8.3
2.9
8.3
3.0
8.3
3.1
8.2
3.6
12.2
3.7
12.1
3.8
12.0
3.9
12.0
4.0
12.0
4.1
11.8

10
PI
2.8
2.9
2.9
3.0
3.1
3.2
3.7
3.8
3.9
4.0
4.1
4.2

TC
8.9
8.9
8.8
8.8
8.8
8.8
13.0
13.0
12.9
12.8
12.8
12.5

15
PI
2.8
2.9
3.0
3.1
3.1
3.2
3.8
3.9
4.0
4.1
4.2
4.3

TC
9.7
9.7
9.5
9.5
13.8
13.8
13.7
13.7

PI
3.1
3.2
3.2
3.3
4.1
4.2
4.3
4.4

3TW20382-10A

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
EDB:
TC:
PI:

Air flow rate


Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100

AFR
BF
AFR
BF

FAY
27
0.1
27
0.1

24
3

6. Add the following correction value to power input (kW) of each unit

Model

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
outdoor air : 85 % RH. however, the condition on nominal capacity
is 7 CDB/6 CWB
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

71
100

Supply
V1
W1
V1
W1

FAY
0.1
0.0
0.2
0.0

37

Pair Application R-22 R(E)Y18-250

Capacity tables

FUY(71-125)FJV1 + RY71-100B7V1
RY100-125B7W1
Cooling capacity

Outdoor

71

100

24

125

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
6.4
6.8
7.4
7.9
8.2
8.2
8.9
9.7
8.3
8.9
10.1
10.8
11.1
11.2
12.2
13.0
11.6
12.4
13.3
14.0
14.3
14.5
15.8
16.7

20
SHC
4.9
4.9
5.0
5.2
5.3
5.3
5.4
5.4
7.2
7.2
7.3
7.6
7.7
7.7
7.8
7.9
9.5
9.5
9.6
9.9
10.0
10.0
10.2
10.3

PI
2.2
2.3
2.3
2.4
2.4
2.4
2.5
2.5
2.7
2.8
2.8
2.9
2.9
2.9
3.0
3.1
3.4
3.5
3.5
3.6
3.7
3.7
3.8
3.8

TC
6.3
6.7
7.2
7.7
7.9
8.1
8.7
9.4
8.3
8.8
9.8
10.5
10.8
11.0
11.8
12.7
11.3
12.0
12.7
13.6
14.0
14.2
15.3
16.3

25
SHC
4.8
4.8
4.9
5.0
5.2
5.2
5.3
5.3
7.1
7.1
7.2
7.5
7.6
7.6
7.7
7.8
9.2
9.2
9.3
9.5
9.5
9.5
9.8
9.9

PI
2.5
2.6
2.6
2.6
2.6
2.6
2.7
2.7
3.0
3.0
3.1
3.1
3.2
3.2
3.2
3.3
3.7
3.7
3.8
3.8
3.9
3.9
3.9
4.0

TC
5.9
6.2
6.7
7.4
7.5
7.6
8.2
8.8
8.1
8.6
9.1
9.8
10.1
10.3
11.2
11.9
10.5
11.2
12.0
12.7
13.3
13.4
14.4
15.3

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.7
5.7
4.6
4.7
2.8
6.1
4.6
4.8
2.8
6.5
4.7
4.9
2.9
7.0
4.8
5.0
2.9
7.3
4.8
5.0
2.9
7.4
4.8
5.2
3.0
8.1
4.9
5.2
3.1
8.6
5.0
6.9
3.4
7.8
6.8
6.9
3.4
8.3
6.8
7.0
3.5
8.9
6.9
7.1
3.5
9.6
7.0
7.2
3.6
10.0
7.1
7.2
3.6
10.1
7.1
7.3
3.7
11.0
7.2
7.5
3.8
11.7
7.3
8.7
4.0
10.2
8.6
8.7
4.1
10.9
8.6
8.8
4.1
11.6
8.7
9.1
4.2
12.4
9.0
9.2
4.3
12.8
9.0
9.2
4.3
13.0
9.1
9.4
4.4
14.1
9.3
9.5
4.5
15.0
9.4

PI
2.9
2.9
3.0
3.1
3.1
3.1
3.2
3.2
3.6
3.6
3.7
3.7
3.8
3.8
3.9
4.0
4.3
4.4
4.5
4.6
4.6
4.6
4.7
4.8

TC
5.4
5.7
6.2
6.6
6.8
6.9
7.6
8.2
7.5
7.8
8.4
9.0
9.4
9.5
10.4
11.1
9.7
10.3
10.9
11.7
12.1
12.3
13.5
14.3

40
SHC
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.8
6.4
6.4
6.5
6.8
6.9
6.9
7.1
7.2
8.4
8.4
8.5
8.7
8.8
8.8
9.1
9.2

PI
3.2
3.2
3.3
3.3
3.4
3.4
3.4
3.5
4.0
4.0
4.1
4.1
4.2
4.2
4.3
4.4
4.7
4.8
4.9
5.0
5.1
5.1
5.2
5.3

TC
5.0
5.4
5.7
6.2
6.4
6.5
7.0
7.6
6.9
7.5
7.8
8.3
8.6
8.8
9.6
10.3
9.0
9.7
10.2
10.9
11.3
11.5
12.6
13.5

46
SHC
4.2
4.2
4.3
4.5
4.6
4.6
4.6
4.6
6.2
6.2
6.3
6.4
6.5
6.5
6.8
6.9
8.0
8.0
8.1
8.4
8.5
8.5
8.7
9.0

PI
3.5
3.5
3.6
3.7
3.7
3.7
3.8
3.9
4.4
4.4
4.5
4.6
4.7
4.7
4.8
4.9
5.4
5.4
5.5
5.5
5.6
5.6
5.8
5.9

3TW20382-11A

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
DB*:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Dry bulb temp. (CDB)
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

71
100
125

AFR
BF
AFR
BF
AFR
BF

FUY
19
0.07
29
0.07
32
0.07

7. Add the following correction value to power input (kW) of each unit

Model
71

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

38

Model

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FUY
0.1
0.0
0.2
0.0
0.0

Pair Application R-22 R(E)Y18-250

Capacity tables

FUY(71-125)FJV1 + RY71-100B7V1
RY71-125B7W1
Heating capacity

Outdoor

71

100

125

Indoor
EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

230V [50Hz]

-10
TC
6.8
6.8
6.8
6.8
6.8
6.8
9.5
9.4
9.4
9.4
9.4
9.3
12.1
12.1
12.1
12.1
12.1
11.9

-5
PI
2.7
2.7
2.8
2.9
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
4.0
4.1
4.2
4.3
4.4
4.5

TC
7.3
7.3
7.3
7.3
7.3
7.3
10.3
10.2
10.2
10.1
10.1
10.1
13.0
13.0
12.9
12.9
12.9
12.9

PI
2.8
2.8
2.9
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
4.2
4.3
4.4
4.5
4.6
4.7

TC
8.0
8.0
7.9
7.9
7.9
7.9
11.2
11.2
11.0
11.0
11.0
10.8
14.1
14.1
14.0
14.0
14.0
139.0

outdoor temperature (CWB)


0
6
PI
TC
2.8
8.8
2.9
8.7
3.0
8.7
3.0
8.7
3.1
8.7
3.2
8.6
3.3
12.4
3.4
12.3
3.5
12.2
3.6
12.2
3.7
12.2
3.8
12.0
4.3
15.4
4.4
15.3
4.5
15.3
4.7
15.3
4.7
15.3
4.9
15.2

10
PI
2.9
3.0
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
4.4
4.6
4.7
4.8
4.9
5.0

TC
9.4
9.4
9.3
9.3
9.3
9.3
13.2
13.2
13.1
13.0
13.0
12.7
16.4
16.3
16.3
16.2
16.2
16.2

15
PI
2.9
3.0
3.1
3.2
3.2
3.3
3.5
3.6
3.7
3.8
3.9
4.0
4.6
4.7
4.9
4.9
5.0
5.2

TC
0.0
0.0
10.1
10.1
9.9
9.9
0.0
0.0
14.1
14.1
13.9
13.9
0.0
0.0
17.8
17.6
17.6
17.2

PI
0.0
0.0
3.2
3.3
3.3
3.4
0.0
0.0
3.8
3.9
4.0
4.1
0.0
0.0
5.0
5.1
5.2
5.4

3TW20382-12A

AFR:
EDB:
TC:
PI:

5. Air flow rate and BF are tabulated below.

SYMBOLS
Air flow rate
Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

24

FUY
19
0.07
29
0.07
32
0.07

6. Add the following correction value to power input (kW) of each unit

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Direct interpolation is permissible.
Do not extrapolate.
4. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

Model
71
100
125

Supply
V1
W1
V1
W1
W1

FUY
0.1
0.0
0.2
0.0
0.0

39

Pair Application R-22 R(E)Y18-250

Capacity tables

RY125B7W1 + FDY125B7V1
Cooling capacity

Outdoor

125

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
11.1
11.9
12.6
13.5
13.9
15.2
16.1

20
SHC
9.6
9.7
9.8
10.4
9.5
9.7
9.8

PI
3.6
3.7
3.8
3.9
3.9
4.1
4.2

TC
10.8
11.5
12.2
13.0
13.4
14.7
15.6

25
SHC
9.4
9.5
9.5
10.1
10.7
10.7
10.6

PI
4.0
4.0
4.1
4.2
4.3
4.4
4.5

TC
10.2
10.9
11.6
12.3
12.7
13.9
14.8

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
9.0
4.5
10.0
8.8
9.1
4.6
10.6
8.9
9.2
4.7
11.3
9.0
9.7
4.8
12.0
9.6
10.3
4.8
12.4 10.1
10.3
5.0
13.6 10.1
10.2
5.1
14.4 10.1

PI
4.8
4.8
4.9
5.0
5.1
5.3
5.4

TC
9.5
10.1
10.8
11.5
11.8
13.0
13.7

40
SHC
8.5
8.6
8.7
9.2
9.8
9.8
9.8

PI
5.2
5.3
5.4
5.5
5.6
5.8
5.9

TC
8.9
9.5
10.1
10.8
11.1
12.2
12.9

46
SHC
8.1
8.2
8.3
8.8
9.4
9.4
9.4

PI
5.8
5.9
6.0
6.1
6.2
6.4
6.5

3TW20422-11A

6. Air flow rate and BF are tabulated below.

SYMBOLS

24
3

AFR:
BF:
EWB:
EDB:
DB*:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Dry bulb temp. (CDB)
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

40

Split - Sky Air Outdoor Units

Model
125

AFR
BF

FDY
45
0.25

Pair Application R-22 R(E)Y18-250

Capacity tables

RY125B7W1 + FDY125B7V1
Heating capacity

230V [50Hz]

Indoor
Outdoor

125

EDB
(C)
9.0
11.0
12.0
13.0
14.0
15.0

EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0

-10
TC
10.6
10.6
10.6
10.6
10.6
10.4

-5
PI
3.8
3.9
4.0
4.1
4.2
4.3

TC
11.5
11.5
11.3
11.3
11.3
11.3

PI
4.0
4.1
4.2
4.3
4.4
4.5

TC
12.3
12.3
12.3
12.3
12.3
12.2

outdoor temperature (CWB)


0
6
PI
TC
4.1
13.5
4.2
13.4
4.3
13.4
4.5
13.4
4.5
13.4
4.7
13.3

10
PI
4.2
4.4
4.5
4.6
4.7
4.8

TC
14.4
14.3
14.3
14.2
14.2
14.2

15
PI
4.4
4.5
4.7
4.7
4.8
5.0

TC
15.6
15.3
15.3
15.1

PI
4.8
4.9
5.0
5.2

3TW20422-12A

5. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
WB:
TC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Wet bulb temperature
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(CDB)
(kW)
(kW)

Model
125

AFR
BF

FDY
45
0.25

24

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

NOTES
1. Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2.
Shows nominal capacities
3. Operative down to 21C outdoor temp.
Outdoor air: 85% RH. However, when outdoor temperature is
7CDB, wet bulb temperature is 6CWB.
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m
4. Direct interpolation is permissible.
Do not extrapolate.

Split - Sky Air Outdoor Units

41

Pair Application R-22 R(E)Y18-250

Capacity tables

RY(200-250)F7W1 + FDY(200-250)B7V1
Cooling capacity

Outdoor

200

250

Indoor
EWB
EDB
(C)
(C)
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
22.0 30.0
24.0 32.0
12.0 18.0
14.0 20.0
16.0 22.0
18.0 25.0
19.0 27.0
22.0 30.0
24.0 32.0

230V [50Hz]

TC
17.5
18.7
20.0
21.3
21.9
24.1
25.6
22.4
24.0
25.6
27.2
28.1
30.9
32.8

20
SHC
15.3
15.4
15.5
16.4
17.4
17.3
17.4
19.6
19.7
19.8
21.0
22.2
22.2
22.2

PI
5.9
6.0
6.1
6.2
6.2
6.4
6.5
7.0
7.1
7.2
7.3
7.4
7.6
7.7

TC
16.8
17.9
19.2
20.4
21.1
23.2
24.6
21.5
23.0
24.6
26.2
27.0
29.7
31.6

25
SHC
14.8
14.9
15.0
16.0
16.9
16.9
16.9
18.9
19.1
19.2
20.4
21.6
21.6
21.7

PI
6.3
6.4
6.5
6.6
6.7
6.9
7.0
7.6
7.7
7.8
7.9
8.0
8.2
8.3

TC
15.8
16.9
18.1
19.3
20.0
22.0
23.4
20.2
21.7
23.2
24.8
25.6
28.2
30.0

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
14.1
7.1
15.4 13.9
14.3
7.2
16.5 14.0
14.4
7.3
17.7 14.1
15.3
7.4
18.9 15.1
16.3
7.5
19.5 16.0
16.3
7.7
21.5 16.0
16.3
7.8
22.9 16.0
18.1
8.5
19.7 17.8
18.3
8.6
21.2 18.0
18.4
8.7
22.7 18.1
19.6
8.9
24.2 19.3
20.8
8.9
25.0 20.5
20.8
9.2
27.6 20.5
20.9
9.3
29.4 20.5

PI
7.5
7.6
7.7
7.8
7.9
8.1
8.3
8.9
9.0
9.2
9.3
9.4
9.7
9.8

TC
14.8
15.9
17.0
18.2
18.8
20.7
22.1
18.9
20.3
21.8
23.3
24.1
26.5
28.3

40
SHC
13.4
13.6
13.7
14.7
15.6
15.6
15.6
17.2
17.4
17.6
18.8
20.0
20.0
20.0

PI
8.2
8.3
8.4
8.6
8.6
8.9
9.0
9.8
9.9
10.0
10.2
10.3
10.5
10.7

TC
14.1
15.1
16.2
17.4
17.9
19.8
21.1
18.0
19.4
20.8
22.3
23.0
25.4
27.1

46
SHC
13.0
13.1
13.2
14.2
15.1
15.1
15.1
16.6
16.8
16.9
18.2
19.4
19.4
19.4

PI
9.2
9.3
9.4
9.6
9.7
9.9
10.1
10.9
11.1
11.2
11.4
11.5
11.8
12.0

3TW21502-1

24
3

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

42

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Pair Application R-22 R(E)Y18-250

Capacity tables

RY(200-250)F7W1 + FDY(200-250)B7V1
Heating capacity

230V [50Hz]

Indoor
Outdoor

200

200

EDB
(C)
9.0
11.0
12.0
13.0
14.0
15.0
9.0
11.0
12.0
13.0
14.0
15.0

EDB
(C)
16.0
18.0
20.0
21.0
22.0
24.0
16.0
18.0
20.0
21.0
22.0
24.0

-10
TC
15.2
15.0
14.8
14.7
14.6
14.4
17.6
17.3
17.1
16.9
16.8
16.6

-5
PI
5.8
5.9
6.1
6.1
6.2
6.4
6.9
7.0
7.2
7.3
7.4
7.6

TC
16.9
16.8
16.5
16.4
16.2
16.0
19.5
19.4
19.1
18.9
18.7
18.4

PI
5.8
6.0
6.1
6.2
6.3
6.5
6.9
7.1
7.3
7.4
7.5
7.7

TC
19.8
19.7
19.6
19.6
19.5
19.5
22.9
22.7
22.6
22.6
22.5
22.5

outdoor temperature (CWB)


0
6
PI
TC
6.1
23.7
6.2
23.5
6.4
23.4
6.5
23.3
6.6
23.3
6.8
23.2
7.2
27.3
7.4
27.1
7.6
27.0
7.7
26.9
7.9
26.9
8.1
26.8

10
PI
6.4
6.6
6.8
6.9
7.0
7.2
7.6
7.9
8.1
8.2
8.3
8.6

TC
26.7
26.5
26.3
26.3
26.2
26.1
30.8
30.6
30.4
30.3
30.3
30.2

15
PI
6.7
6.9
7.1
7.2
7.4
7.6
8.0
8.2
8.5
8.6
8.8
9.0

TC
30.7
30.5
30.4
30.3
30.2
30.1
35.4
35.2
35.0
34.9
34.9
34.8

PI
7.2
7.4
7.6
7.7
7.8
8.1
8.5
8.8
9.1
9.2
9.3
9.7
3TW21502-2

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for


indoor fan motor heat
2.
Shows nominal capacities
3. Operative down to 21C outdoor temp.
Outdoor air: 85% RH. However, when outdoor temperature is
7CDB, wet bulb temperature is 6CWB.
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m
4. Direct interpolation is permissible.
Do not extrapolate.

24
3

43

Pair Application R-22 R(E)Y18-250

Dimensional drawings

REY18GA7V1
RY22DB7V1
1
2
3
4
5
6
7
8

unit (mm)

Drain outlet
4x holes for anchor bolts (M8 or M10)
Service cover + wiring diagram
Power intake
Low pressure gas stop valve
Liquid stop valve (Cu1/4)
Low pressure service port
Name plate

Minimum installation space (mm)

RY22DB7V1
REY18GA7V1

24

j
5 JA
J9.5mm or 3/8CuT
J9.5mm or 3/8CuT

j
6 JB
J6.4mm or 1/4CuT
J6.4mm or 1/4CuT

Space for air passage

H
1000
> 1000

A
> 250
> 500
3TW01574-1B

RY35DA7
RY45DB7
RY60FA7
REY40GA7

unit (mm)

RY35DA7/RY45DB7
RY60FA7
REY40GA7

j
5 JA
J12.7mm or 1/2CuT
J15.9mm or 5/8CuT
J12.7mm or 1/2CuT

Minimum installation space (mm)

j
6 JB
J6.4mm or 1/4CuT
J9.5mm or 3/8CuT
J6.4mm or 1/4CuT

1
2
3
4
5
6
7
8
9

Drain outlet (3x)


4 holes for anchor bolts (M10)
Service cover
Power intake
Low pressure gas stop valve JA
Liquid stop valve JB
Low pressure service port
Name plate
Outdoor air thermostat

Space for air passage

H
1000
> 1000

A
> 300
> 600

3TW01754-1A

44

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Dimensional drawings

RY71B7

unit (mm)
Hole for anchor bolt
4-M12

Name plate

1
2
3
4
5

24

Gas pipe connection J15.9 flare


Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Drain outlet

3TW23184-1

RY100-125B7

unit (mm)
Hole for anchor bolt
4-M12

Name plate

1
2
3
4
5

Gas pipe connection J19.1 flare


Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Drain outlet

3TW23224-1

Split - Sky Air Outdoor Units

45

Pair Application R-22 R(E)Y18-250

Dimensional drawings

RY200F7
Liquid piping connection opening
Gas piping connection opening
Ground terminal
Power supply wiring outlet

(distance between foundation holes)

Foundation hole

(distance between
foundation holes)

1
2
3
4

unit (mm)

Note: The dimensions marked with z refer to distances


after fixing the accessory pipes.
(pipes connected to the
side)

24

Knock hole for lower piping

(pipes connected to
the front)

4
3TW21484-1C

R250F7
Liquid piping connection opening
Gas piping connection opening
Ground terminal
Power supply wiring outlet

(distance between foundation holes)

Foundation hole
(distance between
foundation holes)

1
2
3
4

unit (mm)

Note: The dimensions marked with z refer to distances


after fixing the accessory pipes.

(pipes connected to the


side)

Knock hole for lower piping

(pipes connected to
the front)

3TW21494-1C

46

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Operation range

REY18GA7V1
REY40GA7V1
Cooling

Continuous operation

Warming up period

Outdoor temp. (CWB)

Pull-down period

Outdoor temp. (CDB)

Continuous operation

Heating

24
5

Indoor temp. (CDB)

Indoor temp. (CWB)

Notes:
The graph is based on the following conditions:
1. Equivalent piping length
7.5m
2. Level difference
0m

Cooling

Indoor temp. (CWB)

Continuous operation

Warming up period

Pull-down period

Outdoor temp. (CWB)

Heating

Continuous operation

Outdoor temp. (CDB)

RY22DB7V1
RY35DA7V1
RY45DB7V1
RY60FA7V1

4TW01043-1

Indoor temp. (CDB)

Notes:
The graph is based on the following conditions:
1. Equivalent piping length
7.5m
2. Level difference
0m
3. Air flow rate
Hi speed

Split - Sky Air Outdoor Units

3TW00643-1

47

Pair Application R-22 R(E)Y18-250

Operation range

RY71-100-125B7
Cooling

Continuous operation

Warming up period

Outdoor temp. (CWB)

Pull-down period

Continuous operation

Outdoor temp. (CDB)

Heating

24
5
Indoor temp. (CWB)

Indoor temp. (CDB)

3TW23203-1

RY200-250F7
Cooling

Indoor temp. (CWB)

Continuous operation

Warming up period

Outdoor temp. (CWB)

Continuous operation

Outdoor temp. (CDB)

Heating

Indoor temp. (CDB)

3TW21503-1

48

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Piping diagrams

REY18GA7
Refrigerant flow

Filter

Cooling

Heating

Capillary tube

Heat exchanger
Propeller fan
Fan motor
Filter

Liquid line stop


valve

Compressor

Field piping

Accumulator

24

Gas line stop valve with service


port

O Check valve

L Flare connection

Y2R: Reversing solenoid valve


R1T: Outside air temperature thermistor
R4T: Defrost thermistor

M1C:Compressor motor
M2F: Fan motor

M Screw connection

N Flange connection

Z Pinched pipe

P Spinned pipe

3TW01045-1

REY40GA7
Refrigerant flow

Filter

Filter

Capillary tube (1)

Cooling

Heating

Capillary tube (2)

Heat exchanger
Propeller fan
Fan motor

Filter

Liquid line stop


valve

Field piping

Compressor
Accumulator

Gas line stop valve with service


port

M1C:Compressor motor
M2F: Fan motor

O Check valve

L Flare connection

M Screw connection

Y2R: Reversing solenoid valve


R1T: Outside air temperature thermistor
R4T: Defrost thermistor

N Flange connection

Split - Sky Air Outdoor Units

Z Pinched pipe

P Spinned pipe

3TW01115-1

49

Pair Application R-22 R(E)Y18-250

Piping diagrams

RY22DB7
Refrigerant flow
Cooling

Heating

Capillary tube (1)


Filter
Capillary tube (2)
Filter

Heat exchanger
Propeller fan
Fan motor

Compressor

24

Muffler

Liquid line stop


valve

Field piping
(6.4 CuT)

(9.5 CuT)

Accumulator
Gas line stop valve with
service port

M1C:Compressor motor
M2F: Fan motor

O Check valve

L Flare connection

M Screw connection

Y2R: Reversing solenoid valve


Y1S: Solenoid valve

N Flange connection

Z Pinched pipe

P Spinned pipe

3TW00065-1B

RY35DA7
Refrigerant flow
Cooling
Heat exchanger

Heating

Filter
Capillary tube (1)

Capillary tube (2)

Supplementary
capillary tube
Muffler

One way
valve

Liquid line stop valve

Capillary tube (3)

Field piping
(6.4 CuT)

(12.7 CuT)

Accumulators

Gas line stop valve with


service port
M1C: Compressor motor
M2F: Fan motor

O Check valve

50

L Flare connection

M Screw connection

Y2R: Reversing solenoid valve


Y1S: Solenoid valve

N Flange connection

Split - Sky Air Outdoor Units

Z Pinched pipe

P Spinned pipe

3TW00645-1C

Pair Application R-22 R(E)Y18-250

Piping diagrams

RY45DB7
Refrigerant flow
Cooling

Heating

Heat exchanger

Filter

Capillary tube (1)

Capillary tube (2)

Liquid line stop valve

Capillary tube (3)

Capillary tube (4)

Filter

Field piping
(6.4 CuT)
(12.7 CuT)

Accumulators
Gas line stop valve with
service port
M1C:Compressor motor
M2F: Fan motor

O Check valve

L Flare connection

Y2R: Reversing solenoid valve

M Screw connection

N Flange connection

Z Pinched pipe

24

P Spinned pipe

3TW01145-1B

RY60FA7
Heat exchanger
Capillary tube (1)
Filter

Capillary tube (2)


Capillary tube (3)
Capillary tube (4)

Liquid line stop valve

Capillary tube (6)

Refrigerant flow
Cooling

Heating

Field piping
(9.5 CuT)

(15.9 CuT)

Accumulators

Gas line stop valve with


service port
Y1S: Capacity control solenoid valve
Y2R: Reversing solenoid valve
Y7S: Defrost control solenoid valve

M1C: Compressor motor


M2F: Fan motor
S2PH: High pressure switch

O Check valve

L Flare connection

M Screw connection

N Flange connection

Z Pinched pipe

P Spinned pipe
3TW00665-1B

Split - Sky Air Outdoor Units

51

Pair Application R-22 R(E)Y18-250

Piping diagrams

RY71B7
Capillary tube

Filter

Electronic
expansion valve
Filter
Outdoor heat exchanger

Indoor heat exchanger


Pressure switch
(high-control)

4-way valve

Pressure switch
Pressure switch
(low)
(high)

Muffler

Service port
(1/4 flare)

Field piping J9.5 C122OT-O


Filter

24
6

Compressor

Field piping J15.9 C122OT-O


Accumulator

Indoor unit

Outdoor unit

Stop valve (with service port 1/4 flare)

Cooling
Heating

3TW23205-1

RY100-125B7

Capillary tube

Filter

Electronic
expansion valve
Filter
Outdoor heat exchanger

4-way valve

Indoor heat exchanger

Pressure switch
(low)

Pressure switch
(high)

Muffler

Service port
(1/4 flare)

Field piping J9.5 C122OT-O


Filter
Compressor

Field piping J19.1 C122OT-O


Accumulator

Indoor unit

Outdoor units
Stop valve (with service port 1/4 flare)

Cooling
Heating

52

Split - Sky Air Outdoor Units

3TW23245-1

Pair Application R-22 R(E)Y18-250

Piping diagrams

RY200-250F7
Capillary tube

Outdoor heat exchanger

Indoor heat exchanger

Filter

Propeller fan
Fan
Pressure switch (high)
Pressure switch (high)

Field piping J A

Low pressure
switch
Field pipingJ B

Indoor unit

Service port 1/4 flare

Accumulator

24

Compressor

Stop valve
(with service port 1/4 flare)

Model

12.7

28.6

RY200

15.9

28.6

RY250

Split - Sky Air Outdoor Units

6
Outdoor unit

3TW21505-1A

53

Pair Application R-22 R(E)Y18-250

Wiring diagrams

REY18GA7V1
L
N

: Live
: Neutral
R : Protective earth
g : Field wiring

Indoor

Outdoor

24

C1R,C2R
F1U
Fu
K1M
MR
M1C
M2F
PCB
Q1CL
Q3M

: Running capacitor
: Field fuse
: Fuse
: Compressor contactor
: Magnetic relay
: Compressor motor
: Fan motor
: Printed circuit board
: Overload protector (compressor)
: Thermal protector

Q5E
Rth1
R1T
R4T
SA

: Field earth leak protector


: PCB temperature thermistor
: Outside air temperature thermistor
: Defrost thermistor
: Surge absorber

S1,S3,...
: Connector on PCB
T1R
: Transformer
X1M
: Terminal strip
X10A,X11A,...: Connector
Y2R
: Reversing solenoid valve

3TW01046-B

REY40GA7V1

Indoor

L
N

: Live
: Neutral
: Protective earth

g : Field wiring

Outdoor
C1R,C2R
F1U
F6U, F7U
K1M
MR
M1C
M2F
PCB
Q2L

: Running capacitor
: Field fuse
: Fuse
: Compressor contactor
: Magnetic relay
: Compressor motor
: Fan motor
: Printed circuit board
: Overcurrent overload switch
(compressor)
Q3M, Q4M : Thermal protector

54

Q5E
Rth1
R1T
R4T
SA

: Field earth leak protector


: PCB temperature thermistor
: Outside air temperature thermistor
: Defrost thermistor
: Surge absorber

Split - Sky Air Outdoor Units

S1,S3,...
: Connector on PCB
T1R
: Transformer
X1M
: Terminal strip
X10A,X11A,...: Connector
Y2R
: Reversing solenoid valve

3TW01116-1A

Pair Application R-22 R(E)Y18-250

Wiring diagrams

RY22DB7V1
L
N

Live
Neutral
Protective earth

g Field wiring

Indoor

Outdoor

C1R,C2R
F1U
FU
K1M
MR
M1C
M2F

: Running capacitor
: Field fuse
: Fuse
: Compressor contactor
: Magnetic relay
: Compressor motor
: Fan motor

PCB
Q2L
Q3M
Q5E
R3T,R4T

: Printed circuit board


: Overload protector (compressor)
: Thermal protector
: Field earth leak protector
: Thermistor

24

S1,S3,...
: Connector on PCB
S2PH
: High pressure switch
SA
: Surge absorber
T1R
: Transformer
X1M
: Terminal strip
X10A,X11A... : Connector
Y1S
: Solenoid valve
Y2R
: Reversing solenoid valve
Z1F
: Noise filter

7
3TW00066-B

RY35DA7

g Field wiring

Indoor

L
N

Live
Neutral
Protective earth

C1R,C2R
F1U
F6U,F7U
K1M
K2R
MR
M1C
M2F
PCB
Q2L
Q3M,Q4M
Q5E
R3T,R4T,...

: Running capacitor
: Field fuse
: Fuse
: Compressor contactor
: Magnetic relay
: Magnetic relay
: Compressor motor
: Fan motor
: Printed circuit board
: Overload protector (compressor)
: Thermal protector
: Field earth leak protector
: Thermistor

Outdoor

SA
S1,S3,...
S2PH
T1R
X1M

: Surge absorber
: Connector on PCB
: High pressure switch
: Transformer
: Terminal strip

Split - Sky Air Outdoor Units

X10A,X11A,...: Connector
Y1S
: Solenoid valve
Y2R
: Reversing solenoid valve
Z1F
: Noise filter

3TW00646-E

55

Pair Application R-22 R(E)Y18-250

Wiring diagrams

RY45DB7V1

g Field wiring

Indoor

L
N

24
7

Live
Neutral
Protective earth

C1R,C2R
F1U
F6U,F7U
K1M
MR
M1C
M2F
PCB
Q2L
Q3M,Q4M
Q5E
Rth1

: Running capacitor
: Field fuse
: Fuse
: Compressor contactor
: Magnetic relay
: Compressor motor
: Fan motor
: Printed circuit board
: Overload protector (compressor)
: Thermal protector
: Field earth leak protector
: PCB temperature thermistor

Outdoor

R1T
R4T
SA
S1,S3,...
S2PH
T1R
X1M

: Outside air temperature thermistor


: Defrost thermistor
: Surge absorber
: Connector on PCB
: High pressure switch
: Transformer
: Terminal strip

X10A,X11A,...: Connector
Y2R
: Reversing solenoid valve
Z1F
: Noise filter

3TW01146-1C

RY60FA7V1

g Field wiring

Indoor

L
N

Live
Neutral
Protective earth

C1R,C2R
F1U
F6U,F7U
K1M
K2R
MR
M1C
M2F
PCB
Q3M,Q4M
Q5E
Rth1

: Running capacitor
: Field fuse
: Fuse
: Compressor contactor
: Relay
: Magnetic relay
: Compressor motor
: Fan motor
: Printed circuit board
: Thermal protector
: Field earth leak protector
: PCB temperature thermistor

Outdoor

R1T
R4T
SA
S1,S3,...
S2PH
T1R
X1M

: Outside air temperature thermistor


: Defrost thermistor
: Surge absorber
: Connector on PCB
: High pressure switch
: Transformer
: Terminal strip

X10A,X11A,...
Y1S
Y2R
Y7S
Z1F

: Connector
: Capacity control solenoid valve
: Reversing solenoid valve
: Defrost solenoid valve
: Noise filter

2TW01156-1A

56

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Wiring diagrams

RY71B7V1
Indoor
Note:
Do not operate the unit by short-circuiting S1LP

g Field wiring
D Terminal
L
: Live
N
: Neutral
a : Connector
c
: Wire clamp
b
: Protective earth (screw)
Colours
BLK: Black/ ORG: Orange/ BLU: Blue/
WHT: White/ RED: Red/ YLW:Yellow
Switch box

Outdoor

L-RED

N-BLU

A1P,A2P
BS1
C1R
C3R,C4R
DS1
F1C
F1U

Printed circuit board


Push button (forced defrost-pump down)
Capacitor (M1F)
Capacitor (M1C)
Selector switch (defrost)
Overcurrent relay (M1C)
Fuse (250V, 5A)

F3U
H1P
H2P,H3P
J1HC
K1M
M1C
M1F
Q1L

Field fuse
Light emitting diode
Light emitting diode (service monitor red)
Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Thermo switch (M1F)

Q3E
R1T
R2T
R3T
RC
RyC
RyF1-3
RyS
S1LP

Earth leak detector


Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F)
Magnetic relay (Y1R)
Pressure switch (low)

S1PH
S2PH
SD
SS1
T1R
TC
X1M
Y1E
Y1R

24

Pressure switch (high)


Pressure switch (high-control)
Safety devices input
Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)
4-way valve

7
2TW23206-1

RY71B7W1

Note:

Indoor

Do not operate the unit by short-circuiting S1LP

g Field wiring
D
: Terminal
F
: Connector

: Wire clamp
b
: Protective earth (screw)
Colours
BLK: Black/ BLU: Blue/ WHT: White/
RED: Red/ ORG: Orange/ YLW:Yellow

Outdoor

Switch box

L-RED

L2-WHT

L3-BLK

N-BLU

A1P,A2P
BS1
C1R
DS1
F1C
F1U,F2U
F3U
H1P

Printed circuit board


Push button (pump down)
Capacitor (M1F)
Selector switch (defrost)
Overcurrent relay (M1C)
Fuse (250V, 5A)
Field fuse
Light emitting diode (service monitor green)

H2P,H3P
J1HC
K1M
M1C
M1F
PRC
Q1L
Q3E

Light emitting diode (service monitor red)


Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Phase reverse circuit
Thermo switch (M1F)
Earth leak detector

R1T
R2T
R3T
RC
RyC
RyF1-3
S1LP
S1PH

Split - Sky Air Outdoor Units

Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F)
Pressure switch (low)
Pressure switch (high)

S2PH
SD
SS1
T1R
TC
X1M
Y1E
Y1R

Pressure switch (high-control)


Safety devices input
Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)
4-way valve

2TW23216-1

57

Pair Application R-22 R(E)Y18-250

Wiring diagrams

RY100B7V1

Note:
Do not operate the unit by short-circuiting S1LP
Indoor

g Field wiring
D Terminal
L
: Live
N
: Neutral
a : Connector
c
: Wire clamp
b
: Protective earth (screw)

Switch box

Colours
BLK: Black/ BLU: Blue/
WHT: White/ RED: Red/ YLW:Yellow

Outdoor

24
7

L-RED
A1P,A2P
BS1
C1R,C2R
C3R,C4R
DS1
F1C
F1U

N-BLU
Printed circuit board
Push button (forced defrost-pump down)
Capacitor (M1F-M2F)
Capacitor (M1C)
Selector switch (defrost)
Overcurrent relay (M1C)
Fuse (250V, 5A)

F3U
H1P

Field fuse
Light emitting diode (service monitor
green)
H2P,H3P Light emitting diode (service monitor red)
J1HC
Crankcase heater
K1M
Magnetic contactor (M1C)
M1C
Motor (compressor)
M1F,M2F Motor (fan)
Q1L,Q2L Thermo switch (M1F, M2F)

Q3E
R1T
R2T
R3T
RC
RyC
RyF1-4
RyS
S1LP

Earth leak detector


Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F,M2F)
Magnetic relay (Y1R)
Pressure switch (low)

S1PH
SD
SS1
T1R
TC
X1M
Y1E
Y1R

Pressure switch (high)


Safety devices input
Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)
4-way valve

2TW23246-1

RY100-125B7W1

Note:
Indoor

Do not operate the unit by short-circuiting S1LP

g Field wiring
D Terminal
L
: Live
N
: Neutral
a : Connector
c
: Wire clamp
b
: Protective earth (screw)
Switch box

Colours
BLK: Black/ ORG: Orange/ BLU: Blue/
WHT: White/ RED: Red/ YLW:Yellow

Outdoor

L1-RED
A1P,A2P
BS1
C1R,C2R
DS1
F1C
F1U,F2U
F3U
H1P

58

L2-WHT

L3-BLK

N-BLU

Printed circuit board


Push button (forced defrost-pump down)
Capacitor (M1F-M2F)
Selector switch (defrost)
Overcurrent relay (M1C)
Fuse (250V, 5A)
Field fuse
Light emitting diode (service monitor green)

H2P,H3P
J1HC
K1M
M1C
M1F,M2F
PRC
Q1L,Q2L
Q3E
R1T

Light emitting diode (service monitor red)


Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Phase reverse circuit
Thermo switch (M1F, M2F)
Earth leak detector
Thermistor (air)

R2T
R3T
RC
RyC
RyF1-4
RyS
S1LP
S1PH

Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F,M2F)
Magnetic relay (Y1R)
Pressure switch (low)
Pressure switch (high)

Split - Sky Air Outdoor Units

SD
SS1
T1R
TC
X1M
Y1E
Y1R

Safety devices input


Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)
4-way valve

2TW23256-1

Pair Application R-22 R(E)Y18-250

Wiring diagrams

RY200-250F7W1

Note:
Do not operate the unit by short-circuiting S1LP

Indoor

g Field wiring
D
: Terminal
F
: Connector

: Wire clamp
b
: Protective earth (screw)
Colours
BLK: Black/ BLU: Blue/ WHT: White/
RED: Red/ ORG: Orange/ YLW:Yellow

Switch box

Outdoor

L-RED

L2-WHT

L3-BLK

A1P,A2P
BS1
C1R,C2R
DS1
F1C
F1U,F2U
F3U
H1P

Printed circuit board


Push button (pump down)
Capacitor (M1F-M2F)
Selector switch (defrost)
Overcurrent relay (M1C)
Fuse (250V, 5A)
Field fuse
Light emitting diode (service monitor green)

24

N-BLU
H2P,H3P
J1HC
K1M
M1C
M1F,M2F
PRC
Q1L,Q2L,Q3L
Q3E

Light emitting diode (service monitor red)


Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Phase reverse circuit
Thermo switch (M1F, M2F)
Earth leak detector

R1T
R2T
RC
RyC
RyF1-2
RyS
S1LP
S1PH

Thermistor (air)
Thermistor (coil)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F-M2F)
Magnetic relay (Y1R)
Pressure switch (low)
Pressure switch (high)

Split - Sky Air Outdoor Units

S2PH
SD
SS1
T1R
TC
X1M
Y1R

Control pressure switch (high)


Safety devices input
Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
4-way valve

7
2TW21506-1A

59

Pair Application R-22 R(E)Y18-250

8
8-1

Sound level
Sound level data
Sound pressure level

REY18GA7V1

Sound power (H)

230V

Model

50Hz

Measuring location

H (cooling)

H (heating)

44

45

(cooling/heating)

57 / 58
0.8 m

Center

REY40GA7V1

46

49

59 / 62

Sound pressure level

24

Sound power (H)

230V

Model

50Hz

Measuring location

(cooling/heating)

H (cooling)

H (heating)

RY22DB7V1

44

45

RY35DA7V1

46

47

RY45DB7V1

47

48

60 / 61

RY60FA7V1

54

55

67 / 68

57 / 58
Center

59 / 60

8
8-1

Sound pressure level


Model

60

Sound power (H)

230V
50Hz

Measuring location

H (cooling)

H (heating)

RY71B7V1

49

51

RY71B7W1

49

51

RY100B7V1

52

54

(cooling/heating)

Location of microphone

61 / 61 / -

Coil

64 / Microphone

RY100B7W1

52

54

RY125B7W1

52

54

RY200F7W1

57

57

77 / 78

RY250F7W1

57

57

77 / 78

Split - Sky Air Outdoor Units

Switchbox

64 / 64 / -

Pair Application R-22 R(E)Y18-250

8
8-2

Sound level
Sound pressure spectrum
REY18GA7V1

Sound pressure level [dB(A)]

Heating

Sound pressure level [dB(A)]

Cooling

3TW01047-1

3TW01047-1
Octave band center frequency (Hz)

Octave band center frequency (Hz)

24
8
8-2

REY40GA7V1
Heating

Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

3TW01117-1

3TW01117-1
Octave band center frequency (Hz)

Octave band center frequency (Hz)

Notes

Data is valid at free field condition


Operation sound levels are valid at nominal operation condition 230V
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

Split - Sky Air Outdoor Units

61

Pair Application R-22 R(E)Y18-250

8
8-2

Sound level
Sound pressure spectrum
RY22DB7V1
Heating

Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

24

3TW00067-1

3TW00067-1
Octave band center frequency (Hz)

Octave band center frequency (Hz)

8
8-2

RY35DA7V1

3TW00647-1A

3TW00647-1A
Octave band center frequency (Hz)

Notes

62

Heating
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

Operation sound levels are valid at nominal operation condition 230V


Operation sound levels are valid at nominal operation condition 230V
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

Split - Sky Air Outdoor Units

Octave band center frequency (Hz)

Pair Application R-22 R(E)Y18-250

8
8-2

Sound level
Sound pressure spectrum
RY45DB7V1

Sound pressure level [dB(A)]

Heating

Sound pressure level [dB(A)]

Cooling

3TW00657-1A

3TW00657-1A
Octave band center frequency (Hz)

Octave band center frequency (Hz)

24
8
8-2

RY60FA7V1
Heating
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

3TW01157-1

3TW01157-1
Octave band center frequency (Hz)

Octave band center frequency (Hz)

Notes

Data is valid at free field condition 230V/50Hz


Operation sound levels are valid at nominal operation condition
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

Split - Sky Air Outdoor Units

63

Pair Application R-22 R(E)Y18-250

8
8-2

Sound level
Sound pressure spectrum

RY71DB7V1

RY71B7W1
Heating

Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

approximate
threshold hearing
for continuous
noise

24

approximate
threshold hearing
for continuous
noise

DU427-4261

DU427-4262
Octave band center frequency (Hz)

Octave band center frequency (Hz)

8
8-2

RY100B7W1

RY100B7V1

Heating

Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

approximate
threshold hearing
for continuous
noise

approximate
threshold hearing
for continuous
noise

DU428-4211

DU428-4210
Octave band center frequency (Hz)

Octave band center frequency (Hz)

Notes

64

Data is valid at free field condition 230V/50Hz


Operation sound levels are valid at nominal operation condition
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

Split - Sky Air Outdoor Units

50Hz, 220V
50Hz, 240V

Pair Application R-22 R(E)Y18-250

8
8-2

Sound level
Sound pressure spectrum

RY125B7V1

RY125B7W1
Heating

Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

approximate
threshold hearing
for continuous
noise

approximate
threshold hearing
for continuous
noise

DU429-4178

DU429-4177
Octave band center frequency (Hz)

Octave band center frequency (Hz)

24
8
8-2

RY200F7
Heating

Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

3TW21507-1A

3TW21507-1A
Octave band center frequency (Hz)

Octave band center frequency (Hz)

Notes
Data is valid at free field condition 230V/50Hz
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

Split - Sky Air Outdoor Units

50Hz, 220V
50Hz, 240V

65

Pair Application R-22 R(E)Y18-250

8
8-2

Sound level
Sound pressure spectrum
RY250F7

24

3TW21517-1A

3TW21517-1A
Octave band center frequency (Hz)

8
8-2

Notes
Data is valid at free field condition 230V/50Hz
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

66

Heating
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

Cooling

Split - Sky Air Outdoor Units

Octave band center frequency (Hz)

Pair Application R-22 R(E)Y18-250

9
9-1

Accessories
Optional accessories

REY18-40GA7
RY22-45DB7 / RY35DA7
RY60FA7

Option kit

EKDK01

Model
REY18GA7V1

EKDK02

EKDK03

REY40GA7V1

V
V

RY22DB7V1

V
V

RY35DA7V1

RY45DB7V1

RY60FA7V1

V
4TW00029-1

EKDK01: Drain kit (20 x socket / 10 x conn)


EKDK02: Drain kit (10 x joint)
EKDK03: Drain kit (20 x cap)

Available options for RY71-125B7(V1,W1)

24

Kit name

Name of option

RY71B

Central drain plug

RY100B

RY125B

KKPJ5F180
Twin

Refrigerant branch piping

Triple

KHRP79BA7
-

9-1
KHRP96H7
3TW23189-1

Available options for RY200-250F7W1

Option

Name of option

RY200F

Fan motor size up

NFM22C5

Fan motor size up

NFM22C10

Kit for discharge duct

EKND26A10

Refnet

KHRP79BA7

Refnet

KHRP102BA7

Refnet

KHRP127HA7

RY250F
X

Refer to the table with possible indoor combinations*


3TW21489-2A

table with possible combinations: see chapter RY (twin / triple / double twin application).

Split - Sky Air Outdoor Units

67

Pair Application R-22 R(E)Y18-250

9
9-1

Accessories
Optional accessories

Liquid side joint

Suction gas side joint

Others
Insulator
Installation manual

Outlet

Inlet
Inlet

Sky Air

KHRP79BA7

Outlet

Outlet

KHRP102BA7

Outlet
Outlet

Outlet

Inlet
Inlet
Outlet

Outlet

Liquid side joint

24

Others
Insulator
Installation manual

KHRP96H7

Inlet
Outlet
Outlet

Sky Air

Insulator
Installation manual

Inlet

KHRP127HA7

9-1

Suction gas side header


Inlet

Insulator
Installation manual

Inlet

Outlet
Outlet

Outlet

Outlet

Outlet

1TW21559-11A

68

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

10

Centre of gravity

RY200-250F7

24
10

4TW23619-1

Model

RY200F7W1

380

RY250F7W1

510

Split - Sky Air Outdoor Units

69

Pair Application R-22 R(E)Y18-250

11

Safety device settings

REY18GA7V1
REY40GA7V1

Model

REY18GA7V1

REY40GA7V1

Fan motor thermal protector

Off 135 5C
On 115 5C

Off 135 5C
On 115 5C

Compressor internal protector

Off 175 5C
On 100 10C

Off 150 7C
On 69 10C

Off 130 3C
On 95 10C

*Off 4.8A 22%

Safety device

Overload relay
Overcurrent relay

4TW01011-2B / 4TW01101-2A

Note: * shows U/T data (based on air temp. 100C)

RY22-35-45-60

24
11

Model

RY22DB7

RY35DA7

RY45DB7

RY60FA7V1

Fan motor thermal protector

Off 135 5C
On 90 25C

Off 135 5C
On 86 25C

Off 135 5C
On 86 15C

Off 135 5C
On 86 15C

Compressor internal protector

Off 185 5C
On 100 10C

Off 185 5C
On 100 5C

Off 175 5C
On 100 5C

Off 170 5C
On 110 9C

Overload relay

Off 150 7C
On 85 10C

Off 130 3C
On 95 10C

Off 130 3C
On 95 10C

Overcurrent relay

Off 19 2C
On 23 2C

Safety device

4TW00621-3B

Note: *shows data at 25C

70

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

12

Installation

REY18-40
Refrigerant piping
1. Field piping
All field piping must be provided by a licensed refrigeration technician
and must comply with the relevant local and national codes.
2. Pipe connections
Pipe connections must be made from the right side of the unit.
First installation
If pipe length (!) between indoor and outdoor unit exceeds 8 metres,
additional refrigerant R22 (30g/m) must be charged after vacuum drying
of the installation.
Pipe length (!) between indoor and outdoor unit is limited up to 15
meters.
Maximum allowable level difference (Hmax) between indoor and
outdoor unit is limited up to 10 meters.

24
12
RY22-35-45-60
1. Field piping
All field piping must be provided by a licensed refrigeration technician
and must comply with the relevant local and national codes.
2. Pipe connections
Pipe connections must be made from the right side of the unit.
First installation
If pipe length (!) between indoor and outdoor unit exceeds 10 meters,
additional refrigerant R22 (30g/m) must be charged after vacuum drying
of the installation.
Maximum allowable level difference (Hmax) between indoor and
outdoor unit is limited up to 15 meters, (10 meters for RY22).
Maximum allowable piping length (L) is limited as shown in figure.
RY60
If pipe length (!) between indoor and outdoor unit exceeds 10 meters,
additional refrigerant R22 (30g/m) must be charged after vacuum drying
of the installation.
Maximum allowable level difference (Hmax) between indoor and
outdoor unit is limited up to 15 meters.
Maximum allowable piping length (L) is limited as shown in figure.

RY22DB7 RY35DA7 RY45DB7 RY60FA7


15m

20m

25m

25m

Split - Sky Air Outdoor Units

71

Pair Application R-22 R(E)Y18-250

12

Installation

The numerical figures used here represent the dimensions for the models
RY71. The figures inside () indicate the dimensions for the models RY100 and
RY125. (Unit: mm)
The figures inside < > indicate the dimension of discharge grille when it is
installed facing downward
When installing multiple units in lateral connection, discharge grille cannot
be set to discharge air in Left/Right direction

(B) In case obstacles exist only in front of outlet side

+ Where there are no


obstacles above the unit.
1

Installation of single unit


+ In case obstacles exist only in
front of outlet side.

Installation of multiple units


in lateral connection (2 units
or more).

150 or more

(A) In case obstacles exist in front of the air inlet

20 mm or more
20 mm or more

+ Where there are no obstacles above


the unit

50 or more (100)

500 or less

100 or more

Installation of single unit


+ In case obstacles exist
only in front of outlet
side.

Installation of multiple
units in lateral connection
(2 units or more).

100 or more

12

1000 mm or
more

+ Where there are


obstacles above the
unit.

100 or more

Installation of multiple units in lateral


connection.

100 or more

24

Installation of single unit


+ In case obstacles exist only in front of the
air inlet.
+ In case obstacles exist in front of the air
inlet and on both sides of the unit.

20 mm or more
20 mm or more

+ In case obstacles exist in front


of the air inlet and on both
sides of the unit.

1000 mm or more

500 mm or more

500 or less
200 or more (300)

20 mm or more

1000 mm or more

20 mm or more

+ Where there are obstacles above the


unit.

+ In case obstacles
exist only in front of
outlet side.

1000 mm or more

500 or less

Installation of single unit


+ In case obstacles exist only in
front of outlet side.

20 mm or more

1000 mm or more

100 or more

(C) In case obstacles exist in


front of both the air inlet
and outlet sides.

500 or less
1000 mm or more

+ In case obstacles exist in


front of the air inlet and on
both sides of the unit.

Pattern 1
150 or more

150 or more

150 or more

+ Where there are no obstacles


above the unit.

20 mm or more

72

Installation of
single unit.

20 mm or more
20 mm or more

1000 mm or more

+ In case obstacles exist in front of


the air inlet and on both sides of
the unit.

50 or
more (100)
500 or more (1000)

500 or less
20 mm or more

1000 mm or more

Installation of multiple units in


lateral connection (2 units or
more).

Where obstacle in
front of the air
outlet is higher than
the unit.

Installation of
multiple units in
lateral connection
(2 units or more).

200 or more
(300)

200 or more (300)


200 mm or more

Split - Sky Air Outdoor Units

1000 or more
(1500)

Pair Application R-22 R(E)Y18-250

12

Installation

+ Where there are obstacles above the unit.

Installation of multiple units in


lateral connection (2units or
less).

500 or less
1000 mm or more

500 or less

Installation of single unit.

Relation of dimensions of H, A, and L are


shown in the table below.
LH
H<L

Relation of dimensions of H, A, and


L are shown in the table below.

1000 mm or more

LH
H<L

L
A
0 < L 1/2 H
750<1250>
1/2 H < L
1000<1500>
Set the frame to be L<=H

Installation of multiple units in lateral


connection (2 units or more).

Do not install more than 2 units


(D) In case of stacked installation
1 In case obstacles exist in front of the
outlet side.
Do not stack more than one unit.

500 or less

20 mm or
more

100 or more

H<L

1000 or more (1500)

Get the lower part of the frame sealed so


that air from the outlet does not bypass

Relation of dimensions of H, A, and L are


shown in the table below.
LH

20 mm or
more

150 or more (250)

Get the lower part of the frame sealed so


that air from the outlet does not bypass
2

L
A
0 < L 1/2 H
150 (250)
1/2 H < L
200 (300)
Set the frame to be L<=H

20 mm or more

About 100mm is required as the


dimension for laying the upper outdoor
units drain pipe.

L
A
0 < L 1/2 H
1000<1500>
1/2 H < L
1250<1750>
Set the frame to be L<=H

Get the portion A sealed so that air from


the outlet does not bypass.

1000 mm or more

200 or more (300)

Get the lower part of the frame sealed so


that air from the outlet does not bypass
Do not install more than 2 units

In case obstacles exist in front of the


air inlet.

24
12

20 mm or more

Do not stack more than one unit.


Pattern 2

Where obstacle in front of the air outlet


is lower than the unit.

About 100mm is required as the


dimension for laying the upper outdoor
units drain pipe.

+ Where there are no obstacles above


the unit.
1

Get the portion A sealed so that air from


the outlet does not bypass.

Installation of single unit.


50 or more (100)

200 or more (300)

Installation of multiple units in lateral


connection (2 units or more).

(E) In case of multiple-low installation


(for roof top use, etc.).

500 or more (1000)

1
Relation of dimensions of H, A, and L
are shown in the table below.
L
0 < L 1/2 H
1/2 H < L

In case of installing
one unit per row.

50 or
more (100)
1000 or more (2000)

20 mm or more
100 or more (200)

A
150 (250)
200 (300)

500 or more (1000)

+ Where there are obstacles above the


unit.
1

20 mm or more

In case of installing
multiple units (2 units
or more) in lateral
connection per row.

20 mm or more
20 mm or more

1000 or more (1500)

Installation of single unit.


500 or less
1000 mm or more

Relation of dimensions of H, A, and L are


shown in the table below.
LH
H<L

L
A
0 < L 1/2 H
50 (100)
1/2 H < L
100 (200)
Set the frame to be L<=H

Get the lower part of the frame sealed so


that air from the outlet does not bypass

2000 or more (3000)

400 or more (600)


1000 or more (1500)

Relation of dimensions of H, A, and L are


shown in the table below.
500 or more (1000)

LH
H<L

Split - Sky Air Outdoor Units

L
A
0 < L 1/2 H
150 (250)
1/2 H < L
200 (300)
Installation impossible

73

Pair Application R-22 R(E)Y18-250

12

Installation

RY200-250F7W1

Refrigerant pipe size


Pair system

Refrigerant pipe size


Gas

Liquid

RY200

J28.6

J12.7

RY250

J28.6

J15.9

Additional charge
The heatpump unit, requires additional charging of refrigerant according to the length of pipe connected at the site.
Pair system

RY200

G = (L-7.5)*0.03

RY250

G = (L-7.5)*0.05

One way length of main liquid pipe J9.5 (unit of measurement = m)

Allowable pipe length

24
12

Pair
Max.allowable piping length

50m

Max height difference

30m

Pair

3TW21489-3A

74

Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

12

Installation

Case 1

Case 1

Case 1

Case 2

Case 2

Case 2

Case 3

Case 3

suction side

front side

3TW23619-4

Case 1and case 2


+ Front wall height is 1500mm
+ Suction wall height is 500mm
+ Side wall height has no limit
+ Case 3 wall height has no limit
If the wall is higher than mentioned in note 1: ADO h2/2 (front
side) and ANO h1/2 (suction side) to the mentioned values for
installation. (h1 and h2: see figure to the left)
Before installing, please check the passage of humans and air at
the side, and select a place which is suitable for the case. (If there
are a lot of units to be installed, take care that there is no
shortcircuit of air)
Please install considering piping installation at the front side.

24

12

75
Split - Sky Air Outdoor Units

Pair Application R-22 R(E)Y18-250

Conentrated installation

Installation

Installation in a row

12

Split - Sky Air Outdoor Units

Single installation