You are on page 1of 5

DIgSILENT Technical Documentation

Siemens 7SJ80 Power Factory Relay model description

DIgSILENT GmbH Heinrich-Hertz-Strasse 9 D-72810 Gomaringen Tel.: +49 7072 9168 - 0 Fax: +49 7072 9168- 88 http://www.digsilent.de e-mail: mail@digsilent.de

Siemens 7SJ80 Power Factory Relay model description Published by DIgSILENT GmbH, Germany Copyright 2009. All rights reserved. Unauthorised copying or publishing of this or any part of this document is prohibited. doc.TechRef, Build 513 14 Februar 2013

Table of Contents

Table of Contents
1 MODEL GENERAL DESCRIPTION ........................................................................................................................... 4 2 RELAY NOT SUPPORTED FEATURES ...................................................................................................................... 5

Siemens 7SJ80

Power Factory relay model description

1 Model general description


The following functionalities are modelled:

Definite time overcurrent protection 50, 50N: 6 protective elements (I> 50_1, I>> 50_2, I>> 50_3 , Ie> 50N_1, Ie>> 50N_2, , Ie>> 50N_3 block) Inverse time overcurrent protection 51, 51N: 2 protective elements (Ip 51 and Iep 51N block) Directional inverse time overcurrent protection 67, 67N: 2 protective elements (Ip 67 TOC and Iep 67N TOC block) Directional definite time overcurrent protection 67, 50N: 4 protective elements (I> 67_1, I>> 67_2 , Ie> 67N_1, Ie>> 67N_2 block) Single phase overcurrent protection: 2 protective elements (50 1ph-1 and 50 1ph-2 block) Three-phase thermal overload protection for cables (Overload 49 block) Negative sequence protection: 3 protective elements (I2p 46 TOC, I2> 46-1, I2>> 46-2 block) Overvoltage protection 59: 7 protective elements (U> 59-1, U>> 59-2, U> 59-1 V2, U>> 59-2 V2, U> 59-1 V1, U>> 59-2 V1, Uo> 64 block) Undervoltage protection 27: 4 protective elements (U< 27-1, U<< 27-2, U< 27-1 V1, U<< 27-2 V1 block) Frequency protection 81 O/U: 4 protective elements with undervoltage blocking (81-1, 81-2, 81-3, 81-4 and 81vmin block) Automatic reclosing (79 block): 2 protective elements (Phase reclosing, Ground reclosing block). In the actual configuration the overcurrent protection and the directional overcurrent protection are triggering the reclosing sequence. Please modify the relay connection scheme if other protective elements are controlling the reclosing sequence. Please configure the Tab page of the 79 block to set the reclosing/lockup logic.

Siemens 7SJ80

Power Factory relay model description

2 Relay not supported features


The following features are not supported: In rush restraint Dynamic cold load pickup Motor starting protection 48 Motor restart inhibit 66 Intermittent ground fault protection Fault location Circuit breaker failure protection 50BF Flexible protection functions Synchronism and voltage check 25

Siemens 7SJ80

Power Factory relay model description