You are on page 1of 2

Selection chart for cable entry devices into flameproof enclosures

Requirements for type d Flameproof enclosures (acc. to EN 60079-14) If you use a cable gland which meets the requirements of the EN 50018 and which is certified as part of the enclosure in combination with the used cable, the cable gland is suitable for usage. If your installation does not meet these requirements, please use the selection chart below to determine the correct cable gland. Start

yes

Does this enclosure contain an internal source of ignition? (see ***)

no

yes

Does the hazardous gas require IIC apparatus?

no

Use a suitable flameproof cable entry device with a sealing ring

Barrier Gland (* orf **) Type: CR-C CR-X CR-U CR-S

yes

Is the area of installation Zone 1?

E.g. for SWA/SWB cable:

no
Type CROCLOCK or EMD

yes

Is the volume of the enclosure greater than 2 dm?

no

* Flameproof sealing device such as stopping boxes or sealing chambers shall incorporate compound or other appropriate seals which permit stopping around individual cores. ** Flameproof cable entry devices incorporating compound filled seals around the individual cores or other equivalent sealing arrangements. *** Internal sources of ignition include sparks or equipment temperatures occurring in normal operation which can cause ignition.

Type of protection e Increased safety For applications with type of protection e Increased safety, EExe certified cable glands can be used, e.g. type CROCLOCK, EMD or 8161.

Cable glands suitable for type of protection d flameproof enclosures and type of protection e increased safety:
Type Explosion protection CR-C / CR-X / CR-U / CR-S ATEX I M2 II 2 GD, E Exd I & IIC CROCLOCK II 2 GD, EExd IIC II 2 GD, EExe II Type of protection Test certificate Material cable gland Compound around cores Degree of protection Gas / Dust / Mining SIRA 03 ATEX 1479X brass or stainless steel Yes IP 66 IP 68 @ 100 metres Ambient temperature p - 20 C+ 80 C Gas / Dust BAS 01 ATEX 2271X brass or stainless steel No IP 66 IP 68 @ 25 metres - 20 C+ 80 C

Type Explosion protection

EMD II 2 G, EExd IIC II 2 G, EExe II

8161 II 2 G, Eexe II

Type of protection Test certificate Material cable gland Compound around cores Degree of protection

Gas KEMA 98 ATEX 4311X brass or stainless steel No IP 55 IP 67 (with extra seal)

Gas PTB 00 ATEX 3119X polyamid No IP 66 IP 68 @ 6 bar 24h - 20 C+ 75 C

Ambient temperature

- 40 C+ 80 C (EMD-A & EMD-B) - 40 C+ 200 C (EMD-S)

All cable glands are suitable for armoured and/or unarmoured cable and are available with Metric and entry NPT thread. Detailed technical documentation is available on request or visit the website www.electromach.com.