DOCUMENT SUBMISSION STATUS: AP

C B
REV OWNER

26.01.10 06.01.10
DATE

Modify in accordance with CS2-M2-E-00048 Modify in accordance with CS2-M2-E-M2-DSL-0600


DESCRIPTION

MLe MLe
DRWN

ASc ASc
CHKD

TBr TBr
APPN

OWNERS CONSULTANT

VIETNAM OIL AND GAS GROUP (PVN)


EPC CONTRACTOR

POYRY ENERGY LTD


EPC CONTRACTORS CONSULTANT

VIETNAM MACHINERY INSTALLATIONCORPPORATION (LILAMA)


PROJECT TITLE

WORLEYPARSONS PTE LTD

VUNG ANG 1 THERMAL POWER PLANT 2 x 600MW PACKAGE TITLE


CONTRACT No.

DRAWING TITLE

SINGLELINE DIAGRAM COAL HANDLING SYSTEM SUB-CONTRACTOR FUNCTION DRWN CHKD APPD DOCUMENT No. VA1-FLS-00100-E-M2-DSL-0600 NAME M.Leinenbach A.Scholz T.Brwer SCALE REV C SIGN DATE 07.12.09 07.12.09

10

A Power Plant

MVA

10 kV 3Ph 50Hz

MVB

Scope by others Scope of supply FLS-Koch

10kV 2500kVA, AN 690V Uk= 6% Dyn 11 2 x 2,5%


Auto switch unit

10kV 2500kVA, AN 690V Uk= 6% Dyn 11 2 x 2,5%

Substation TT2

10kV 400kVA, AN 400V Uk= 4% Dyn 11 2 x 2,5%


Auto switch unit

10kV 400kVA, AN 400V Uk= 4% Dyn 11 2 x 2,5%

D
I > IR=2500 A IR=1600 A I > IR=2500 A I> IR=630 A

I > IR=630 A IR=400 A

690V 3ph, 4 wire, 50Hz, Ikmax= 43 kA

690V 3ph, 4 wire, 50Hz, Ikmax= 43 kA

400V 3ph, 4 wire, 50Hz, Ikmax = 15kA

400V 3ph, 4 wire, 50Hz, Ikmax = 15kA

I> IR=160 A

I>

IR=80 A

IR=250 A

IR=63 A

IR=100 A

IR=400 A

IR=125 A

IR=200 A

IR=80 A

IR=315 A

IR=80 A

IR=250 A

IR=63 A

IR=100 A

IR=400 A

IR=125 A

IR=200 A

IR=80 A

IR=315 A

IR=160 A

80 A I> IR=100 A
230V 50Hz

80 A I> IR=100 A
230V 50Hz

I=80 A*

I=250A*

I=58A*

I=95A*

I=400A*

I=114A*

I=80A*

I=200A*

I=80 A*

I=250A*

I=58A*

I=95A*

I=400A*

I=114A*

I=80A*

I=200A*

Capacitor bank

390m, 2 x 95mm

400m, 2 x 120mm

50m, 2 x 95mm

320m, 185mm

670m, 2 x 95mm

60m, 2 x 95mm

520m, 150mm

320m, 185mm

470m, 120mm

500m, 70mm

350m, 95mm

595m, 95mm

500m, 70mm

605m, 95mm

Capacitor bank

Capacitor bank

Capacitor bank

115m, 35mm

400m, 35mm

115m, 35mm

190m, 50mm

190m, 50mm

400m, 35mm

242m, 35mm

242m, 35mm

60m, 25mm

60m, 25mm

24V DC

24V DC

193m, 70mm
M 3~ M 3~ M 3~ M 3~ M 3~ M 3~ M 3~

217m, 120mm
M 3~ M 3~ M 3~ M 3~ M 3~ M 3~ M 3~

193m, 70mm

217m, 120mm
M 3~ M 3~

120m, 16mm

M 3~

00EAU01 49KW
Lighting Stockpile A 100A Lighting & Power sockets Transfer Towers 100A

120m, 16mm
AUX.

M 3~

00EAU02 49kW
Lighting Stockpile B 100A Lighting & Power sockets Transfer Towers 100A

AUX.

00EAD01 110 kVA

00EAD02 110 kVA

00EAF01 240 kVA

00EAF02 240 kVA

00EAD03 10 kW

00EAD04 10 kW

00EAC10 75 kW IN= 80A

00EAC09 250 kW IN=250 A

00EAC08 55 kW IN=58 A

00EAC02 00EAC01 00EAC06 110 kW 400 kW 90 kW IN=95 A IN=400 A IN=114A

00EAE01 75 kW IN=80 A

00EAC05 132 kW IN=135 A

00EAC20 75 kW IN=80 A

00EAC19 250 kW IN=250 A

00EAC18 00EAC12 00EAC11 00EAC07 400KW 90 kW 55 kW 110 kW IN=95 A IN=400 A IN=114 A IN=58 A

00EAE02 75 kW IN=80 A

00EAC04 132 kW IN=135 A

00EAC03 37 kW IN=75 A

|- all other consumers -||-- Lighting & Socket --|

00EAC13 37 kW IN=75 A

|- all other consumers -||-- Lighting & Socket --|

10kV 1229 KW

10kV 1229 KW

00EAA01

00EAA02

NOTE:

* = intelligent motor protection relay


Fuses for motor protection aM caracteristic Fuses for switchgear protection gL/gG caracteristic

** I

KMAX

if tie breaker is closed and one transformer supply both busbar, worsed case

Adapted according to CS-M2-E-00048 Deleted Substation Storage Adapted installed power Index / Rev. Mitteilung / Remark

26.01.10 30.11.09 29.09.09 Datum / Date

MLe MLe MLe Name

Date Author appr. Norm

04.09.09 W.T. BACH IEC

Kunde / Client

Firma / Company

Zeichnung / Drawing

Angebotsnr. / Offer No.:

2.2040
Blatt / Page: von / of: 1 1

PVN COAL FIRED POWER PLANT

VA1-FLS-00100-E-M2-DSL-0600 Rev. C

Datei / File PVN_Single_Linediag.vsd

10

11

12

C
Transformer 1.1A.1 Sn = 2.500 kVA ukr = 6 % 10/0,69 kV Dyn5 Transformer 1.1B.1 Sn = 2.500 kVA ukr = 6 % 10/0,69 kV Dyn5

LV-B 1.1A.1 Busbar 5m LDA5623

LV-B 1.1B.1 Busbar 5m LDA5623

LVMD 1.1A TN-S Un = 690 V

CB 1.1ABa Circuit-breaker In = 2.500 A

LV-CB 1.1A.1b Circuit-breaker In = 2.500 A

LV-CB 1.1B.1b Circuit-breaker In = 2.500 A

LVMD 1.1B TN-S Un = 690 V

CB 1.1A.1a Circuit-breaker In = 500 A

CB 1.1B.11a Circuit-breaker In = 500 A

C 1.1A.1 Capacitor Qn = 500 kvar Un = 690 V

C 1.1B.11 Capacitor Qn = 500 kvar Un = 690 V

C/L 1.1A.2 Cable/Line 500 m Cu 1(3x70/-/35)

C/L 1.1A.3 Cable/Line 320 m Cu 1(3x150/-/70)

C/L 1.1A.4 Cable/Line 60 m Cu 1(3x25/-/25)

C/L 1.1A.6 Cable/Line 115 m Cu 1(3x35/-/16)

C/L 1.1A.5 Cable/Line 60 m Cu 2(3x95/-/50)

C/L 1.1A.7 Cable/Line 190 m Cu 1(3x50/-/25)

C/L 1.1A.8 Cable/Line 506 m Cu 1(3x70/-/35)

C/L 1.1A.12 Cable/Line 595 m Cu 1(3x95/-/50)

C/L 1.1A.10 Cable/Line 566 m Cu 2(3x95/-/50)

C/L 1.1A.11 Cable/Line 520 m Cu 1(3x150/-/70)

C/L 1.1B.1 Cable/Line 500 m Cu 1(3x70/-/70)

C/L 1.1B.2 Cable/Line 320 m Cu 1(3x185/-/95)

C/L 1.1B.3 Cable/Line 60 m Cu 1(3x25/-/25)

C/L 1.1B.4 Cable/Line 115 m Cu 1(3x35/-/35)

C/L 1.1B.5 Cable/Line 50 m Cu 2(3x95/-/50)

C/L 1.1B.6 Cable/Line 190 m Cu 1(3x50/-/25)

C/L 1.1B.7 Cable/Line 632 m Cu 1(3x120/-/120)

C/L 1.1B.8 Cable/Line 566 m Cu 1(3x70/-/70)

C/L 1.1B.9 Cable/Line 566 m Cu 2(3x95/-/50)

C/L 1.1B.10 Cable/Line 632 m Cu 2(3x95/-/50)

3~

00EAC10 Motor In = 77,6 A Un = 690 V 3-pole

3~

00EAC09 Motor In = 250 A Un = 690 V 3-pole

3~

00EAC08 Motor In = 56,9 A Un = 690 V 3-pole

3~

00EAC02 Motor In = 93,1 A Un = 690 V 3-pole

3~

00EAC01 Motor In = 400 A Un = 690 V 3-pole

3~

00EAC06 Motor In = 111 A Un = 690 V 3-pole

00EAD01 Outer zone In = 100 A Un = 690 V 3-pole

3~

00EAE01 Motor In = 76,6 A Un = 690 V 3-pole

00EAF01 Outer zone In = 181 A Un = 690 V 3-pole

3~

00EAC05 Motor In = 133 A Un = 690 V 3-pole

3~

00EAC20 Motor In = 78,4 A Un = 690 V 3-pole

3~

00EAC19 Motor In = 250 A Un = 690 V 3-pole

3~

00EAC18 Motor In = 56,9 A Un = 690 V 3-pole

3~

00EAC12 Motor In = 93,1 A Un = 690 V 3-pole

3~

00EAC11 Motor In = 400 A Un = 690 V 3-pole

3~

00EAC07 Motor In = 111 A Un = 690 V 3-pole

00EAD02 Outer zone In = 100 A Un = 690 V 3-pole

3~

00EAE02 Motor In = 76,7 A Un = 690 V 3-pole

00EAF02 Outer zone In = 181 A Un = 690 V 3-pole

3~

00EAC04 Motor In = 133 A Un = 690 V 3-pole

SIMARIS design 5.0.1102 Project name: Planner: Design office: Client:

VA1-FLS-100-E-M2-DSL-0600 mal-de FLSmidth MVT Lilama PVN


11
Location: Created on: Changed on:

Vietnam 12/4/09 1/5/10


12

10

10

11

12

C
Transformer 1.1A.1 In1 = 144 A In2 = 2.092 A u = 0,908 % Transformer 1.1B.1 In1 = 144 A In2 = 2.092 A u = 0,909 %

LV-B 1.1A.1 Iz = 2.500 A ftot = 1 Ib = 1.022 A

LV-B 1.1B.1 Iz = 2.500 A ftot = 1 Ib = 1.023 A

LVMD 1.1A Ib =1.022 A cos() = 0,983 (ind.) u = 0,0433 % gi = 1

CB 1.1ABa IR =1.125 A

LV-CB 1.1A.1b IR = 2.250 A

LV-CB 1.1B.1b IR = 2.250 A

LVMD 1.1B Ib =1.023 A cos() = 0,983 (ind.) u = 0,0433 % gi = 1

CB 1.1A.1a IR = 450 A

CB 1.1B.11a IR = 450 A

C 1.1A.1 Qe = 400 kvar cos() = 0,119 (cap.) u = 0,0433 %

C 1.1B.11 Qe = 400 kvar cos() = 0,119 (cap.) u = 0,0433 %

C/L 1.1A.2 Iz =183 A ftot = 0,8 Ib = 77,6 A

C/L 1.1A.3 Iz = 297 A ftot = 0,8 Ib = 250 A

C/L 1.1A.4 Iz = 95,2 A ftot = 0,8 Ib = 56,9 A

C/L 1.1A.6 Iz = 118 A ftot = 0,8 Ib = 93,1 A

C/L 1.1A.5 Iz = 445 A ftot = 0,8 Ib = 400 A

C/L 1.1A.7 Iz =143 A ftot = 0,8 Ib =111 A

C/L 1.1A.8 Iz =183 A ftot = 0,8 Ib =100 A

C/L 1.1A.12 Iz = 222 A ftot = 0,8 Ib = 76,6 A

C/L 1.1A.10 Iz = 445 A ftot = 0,8 Ib = 181 A

C/L 1.1A.11 Iz = 297 A ftot = 0,8 Ib = 133 A

C/L 1.1B.1 Iz =183 A ftot = 0,8 Ib = 78,4 A

C/L 1.1B.2 Iz = 339 A ftot = 0,8 Ib = 250 A

C/L 1.1B.3 Iz = 95,2 A ftot = 0,8 Ib = 56,9 A

C/L 1.1B.4 Iz = 118 A ftot = 0,8 Ib = 93,1 A

C/L 1.1B.5 Iz = 445 A ftot = 0,8 Ib = 400 A

C/L 1.1B.6 Iz =143 A ftot = 0,8 Ib =111 A

C/L 1.1B.7 Iz = 258 A ftot = 0,8 Ib = 100 A

C/L 1.1B.8 Iz =183 A ftot = 0,8 Ib = 76,7 A

C/L 1.1B.9 Iz = 445 A ftot = 0,8 Ib = 181 A

C/L 1.1B.10 Iz = 445 A ftot = 0,8 Ib = 133 A

3~

00EAC10 Pmech = 75 kW cos() = 0,87 (ind.) u = 2,67 % u dyn. = 9,9 %

3~

00EAC09 Pmech = 250 kW cos() = 0,9 (ind.) u = 2,94 % u dyn. = 9,79 %

3~

00EAC08 Pmech = 55 kW cos() = 0,87 (ind.) u = 0,636 % u dyn. = 2,11 %

3~

00EAC02 Pmech = 90 kW cos() = 0,87 (ind.) u = 1,4 % u dyn. = 5 %

3~

00EAC01 Pmech = 400 kW cos() = 0,89 (ind.) u = 0,324 % u dyn. = 2,95 %

3~

00EAC06 Pmech = 110 kW cos() = 0,88 (ind.) u = 1,98 % u dyn. = 8,88 %

00EAD01 P = 95,6 kW cos() = 0,8 (ind.) u = 3,7 %

3~

00EAE01 Pmech = 75 kW cos() = 0,89 (ind.) u = 0,31 % u dyn. = 9,79 %

00EAF01 P =193 kW cos() = 0,89 (ind.) u = 3,05 %

3~

00EAC05 Pmech = 132 kW cos() = 0,88 (ind.) u = 2,55 % u dyn. = 10 %

3~

00EAC20 Pmech = 75 kW cos() = 0,87 (ind.) u = 2,7 % u dyn. = 9,44 %

3~

00EAC19 Pmech = 250 kW cos() = 0,9 (ind.) u = 2,52 % u dyn. = 9,73 %

3~

00EAC18 Pmech = 55 kW cos() = 0,87 (ind.) u = 0,636 % u dyn. = 2,11 %

3~

00EAC12 Pmech = 90 kW cos() = 0,87 (ind.) u = 1,4 % u dyn. = 5 %

3~

00EAC11 Pmech = 400 kW cos() = 0,89 (ind.) u = 0,277 % u dyn. = 2,46 %

3~

00EAC07 Pmech = 110 kW cos() = 0,88 (ind.) u = 1,98 % u dyn. = 7,62 %

00EAD02 P = 95,6 kW cos() = 0,8 (ind.) u = 3 %

3~

00EAE02 Pmech = 75 kW cos() = 0,88 (ind.) u = 0,371 % u dyn. = 9,82 %

00EAF02 P = 193 kW cos() = 0,89 (ind.) u = 3,05 %

3~

00EAC04 Pmech =132 kW cos() = 0,88 (ind.) u = 2,25 % u dyn. = 9,36 %

SIMARIS design 5.0.1102 Project name: Planner: Design office: Client:

VA1-FLS-100-E-M2-DSL-0600 mal-de FLSmidth MVT Lilama PVN


11
Location: Created on: Changed on:

Vietnam 12/4/09 1/5/10


12

10

10

11

12

C
S =1.221,7 kVA P =1.200,8 kW Q = -224,5 kvar Ibs =1.022,2 A S =1.222,5 kVA P =1.201,5 kW Q = -225,1 kvar Ibs =1.022,9 A

LVMD 1.1A S =1.221,7 kVA P =1.200,8 kW Q = -224,5 kvar Ibs =1.022,2 A

LVMD 1.1B S =1.222,5 kVA P =1.201,5 kW Q = -225,1 kvar Ibs =1.022,9 A

S = 402,9 kVA P = 48,0 kW Q = 400,0 kvar Ibs =337,1 A (L1,L2,L3)

S = 402,9 kVA P = 48,0 kW Q = 400,0 kvar Ibs =337,1 A (L1,L2,L3)

3~

S = 92,7 kVA P = 80,6 kW Q = -45,7 kvar Ibs = 69,8 A (L1, L2, L3)

3~

S = 298,7 kVA P = 268,8 kW Q = -130,2 kvar Ibs = 224,9 A (L1, L2, L3)

3~

S = 68,0 kVA P = 59,1 kW Q = -33,5 kvar Ibs = 51,2 A (L1, L2, L3)

3~

S =111,2 kVA P = 96,8 kW Q = -54,8 kvar Ibs = 83,8 A (L1, L2, L3)

3~

S = 478,1 kVA P = 425,5 kW Q = -218,0 kvar Ibs = 160,0 A (L1, L2, L3)

3~

S =133,0 kVA P =117,0 kW Q = -63,2 kvar Ibs =100,1 A (L1, L2, L3)

S = 119,5 kVA P = 95,6 kW Q = -71,7 kvar Ibs =100,0 A (L1, L2, L3)

3~

S = 91,6 kVA P = 81,5 kW Q = -41,8 kvar Ibs = 7,7 A (L1, L2, L3)

S = 216,9 kVA P = 193,0 kW Q = -98,9 kvar Ibs = 181,5 A (L1, L2, L3)

3~

S =158,7 kVA P =139,7 kW Q = -75,4 kvar Ibs = 119,5 A (L1, L2, L3)

3~

S = 93,7 kVA P = 81,5 kW Q = -46,2 kvar Ibs = 70,6 A (L1, L2, L3)

3~

S = 298,7 kVA P = 268,8 kW Q = -130,2 kvar Ibs = 224,9 A (L1, L2, L3)

3~

S = 68,0 kVA P = 59,1 kW Q =-33,5 kvar Ibs = 51,2 A (L1, L2, L3)

3~

S =111,2 kVA P = 96,8 kW Q = -54,8 kvar Ibs = 83,8 A (L1, L2, L3)

3~

S = 478,1 kVA P = 425,5 kW Q =-218,0 kvar Ibs = 160,0 A (L1, L2, L3)

3~

S =133,0 kVA P =117,0 kW Q = -63,2 kvar Ibs =100,1 A (L1, L2, L3)

S =119,5 kVA P = 95,6 kW Q = -71,7 kvar Ibs =100,0 A (L1, L2, L3)

3~

S = 91,6 kVA P = 80,6 kW Q = -43,5 kvar Ibs = 7,7 A (L1, L2, L3)

S = 216,9 kVA P = 193,0 kW Q = -98,9 kvar Ibs = 181,5 A (L1, L2, L3)

3~

S =158,7 kVA P =139,7 kW Q = -75,4 kvar Ibs =119,5 A (L1, L2, L3)

SIMARIS design 5.0.1102 Project name: Planner: Design office: Client:

VA1-FLS-100-E-M2-DSL-0600 mal-de FLSmidth MVT Lilama PVN


11
Location: Created on: Changed on:

Vietnam 12/4/09 1/5/10


12

10

4.6 Explanation of formulaic symbols


Symbol [unit] 1ph_n [] 1ph_pe [] 1 min/max [] 2 [] 3 [] 3 min/max [] motor [] u [%] U [V] u_tr [%] U_tr [V] u [%] Description Efficiency Phase angle at Ik1ph_n min/max Phase angle at Ik1ph_pe min/max Phase angle at Ik1 min/max Phase angle at Ik2min Phase angle at Ik3 min/max Phase angle at Ik3 min/max Phase angle at Ikmotor Relative voltage drop between the beginning and end of a line section Relative voltage drop between the beginning and end of a line section Relative voltage drop over the transformer winding Absolute voltage drop over the transformer winding Summated relative voltage drop up to a given point with/without voltage drop over the transformer winding according to the selected settings Summated absolute voltage drop up to a given point with/without voltage drop over the transformer winding according to the selected settings Summated relative voltage drop at the starting motor with/without voltage drop over the transformer winding according to the selected settings

U [V]

u dyn. [%]

U dyn. [V]

Summated absolute voltage drop at the starting motor with/without voltage drop over the transformer winding according to the selected settings Capacity factor Minimum/maximum voltage factor in accordance with IEC 60909-0 Power factor The indicated short-circuit current refers to a fault in the medium-voltage busbar The indicated short-circuit current refers to a fault at the primary side of the transformer The indicated short-circuit current refers to a fault at the secondary side of the transformer Reduction factor Nominal frequency Simultaneity factor Simultaneity factor Phase energizing current of overcurrent module of DMT relay Phase energizing current of high-current module of DMT relay Conventional fusing current Let-through energy Let-through energy downstream of the lower switching device or at the target distribution board / consumer Let-through energy upstream of the lower switching device Let-through energy downstream of the upper switching device Let-through energy at the output distribution board or upstream of the upper switching device Let-through energy of the switching device at the transition to the I-release Let-through energy of the switching device in the event of maximum short-circuit current Let-through energy of the switching device in the event of minimum short-circuit current Rated let-through energy of RCD Let-through energy of fuse

ai c min/max cos(), F1 F2 F3 ftot fn [Hz] gf gi I> [A] I> [A] I2 [A] I2t [kA2s] I2t a [kA2s]

I2t b [kA2s] I2t c [kA2s] I2t d [kA2s] I2t(Ii) [kA2s] I2t(Ikmax) [kA2s] I2t(Ikmin) [kA2s] I2t(RCD) [kA2s] I t(fuse) [kA s]
2 2

I2t(soll) [kA2s] I2t value Itmax(base) [kA2s] Ia/In Ib [A] Ibb [A] Ibel [A] Ibem [A] Ibs [A] Ibw [A] c value [kA]

Let-through energy requirement on the connecting line Let-through energy of the switching device at Ikmax from the characteristic curve file Permissible I2t value of the fuse base Starting current ratio Operating current Reactive load current Load current Rated set-point current of the switching device Apparent load current Active load current Cut-off current of the switching device at Ikmax from the characteristic curve file (instantaneous value) Cut-off current of the fuse Rated short-circuit making capacity Rated short-circuit current of the fuse base Rated short-circuit breaking capacity acc. to IEC 60898-1 Rated ultimate short-circuit breaking capacity acc. to IEC 60947-2 Requirement on the rated ultimate short-circuit breaking capacity downstream of the lower switching device or at the target distribution board (controlled short-circuit current) Requirement on the rated ultimate short-circuit breaking capacity upstream of the lower switching device (controlled short-circuit current) Requirement on the rated ultimate short-circuit breaking capacity downstream of the upper switching device (controlled short-circuit current) Requirement on the rated ultimate short-circuit breaking capacity at the output distribution board or upstream of the upper switching device (controlled short-circuit current) Rated ultimate short-circuit breaking capacity fuse Required short-circuit breaking capacity for the protective device at the mounting location Rated short-time withstand current 1s

Ic (fuse) [kA] Icm [kA] Icmax (base) [kA] Icn [kA] Icu [kA] Icu korr a [kA]

Icu korr b [kA]

Icu korr c [kA]

Icu korr d [kA]

Icu(fuse) [kA] Icu/Icn [kA] required Icw 1s [kA]

Ie [A] Ig [A] Igb [A] Igs [A] Igw [A] IHHmin [A] Ii [A] Ik1D [kA] Ik1max [kA] Ik1max(F1) [kA] Ik1maxph_n [kA] Ik1maxph_pe [kA] Ik1max [kA] Ik1min(F2) [kA] Ik1min(F3) [kA] Ik1minph_n [kA] Ik1minph_pe [kA] Ik2min [A] Ik2min(F2) [kA] Ik2min(F3) [kA] Ik3(F3) [kA] Ik3D [kA] Ik3max [kA] Ik3max(F1) [kA] Ik3min [kA]

Earth energizing current of the DMT relay Setting value of the release for earth fault detection Total reactive current Total apparent current Total active current Minimum tripping current of the high-voltage highrupturing capacity fuse Setting value of instantaneous short-circuit (I)release 1-pole continuous short-circuit current Maximum 1-pole short-circuit current Maximum 1-pole short-circuit current in the event of a fault in the medium-voltage busbar Maximum 1-pole short-circuit current phase to neutral conductor Maximum 1-pole short-circuit current phase to protective conductor Minimum 1-pole short-circuit current Minimum 1-pole short-circuit current in the event of a fault at the transformer primary side Minimum 1-pole short-circuit current in the event of a fault at the transformer secondary side Minimum 1-pole short-circuit current phase to neutral conductor Minimum 1-pole short-circuit current phase to protective conductor Minimum 2-pole short-circuit current Minimum 2-pole short-circuit current in the event of a fault at the transformer primary side Minimum 2-pole short-circuit current in the event of a fault at the transformer secondary side 3-pole short-circuit current in the event of a fault at the transformer secondary side 3-pole continuous short-circuit current Maximum 3-pole short-circuit current Maximum 3-pole short-circuit current in the event of a fault in the medium-voltage busbar Minimum 3-pole short-circuit current

Ikmax [A] Ikmax a [kA]

Maximum short-circuit current of all short-circuit currents Maximum short-circuit current downstream of the lower switching device or at the target distribution board (uncontrolled short-circuit current) Maximum short-circuit current upstream of the lower switching device (uncontrolled short-circuit current) Maximum short-circuit current downstream of the upper switching device (uncontrolled short-circuit current) Maximum short-circuit current at the output distribution board or upstream of the upper switching device (uncontrolled short-circuit current) Ratio of maximum/minimum short-circuit current Minimum short-circuit current of all short-circuit currents 3-pole short-circuit current proportion of the motor Factor of energetic recovery short-circuit current Maximum rated current of busbar system Nominal/rated current Rated current of RCD Nominal/rated current of medium-voltage switchgear Nominal/rated current of medium-voltage fuse Rated device current at 40 C standard temperature Permissible switch load according to ambient temperature Rated current of transformer, primary side Rated current of transformer, secondary side Rated transformer current at nominal power Peak short-circuit current Conditional rated short-circuit current - motor starter combination Setting value for overload (L)-release Setting value of short-time delayed short-circuit (S)-release Calculated selectivity limit value between Ikmin and Ikmax

Ikmax b [kA]

Ikmax c [kA]

Ikmax d [kA]

Ikmax/Ikmin Ikmin [A] Ikmotor [kA] Ikre Imax [A] In [A] In (RCD) [mA] In (switch) [A] In (fuse) [A] In max [A] In zul [A] In1 [A] In2 [A] In [A] Ipk [kA] Iq [kA] IR [A] Isd [A] Isel-kurz [A]

Isel-ber [A] Iz, Izul [A] In [mA] L L1 L2 L3 max min MRPD MV N LV P [kW] PE Pk [kW] Pmech [kW] Pn [kW] P0, Pv [kW] pz Q [kvar] Qe [kvar] Qn [kvar] R/X R0 [m] R0 min/max [m] R0 N [m] R0 PE(N) [m] R0U [m] R0/R1

Calculated selectivity limit value in range less than Ikmin Permissible load current of a connecting line Rated earth-fault current RCD protection Phase Phase 1 Phase 2 Phase 3 Maximum Minimum Machine-readable product designation Medium voltage Neutral conductor Low voltage Active power, electric Protective conductor Short-circuit losses Active power, mechanical Nominal active power No-load losses, loss power (active) Number of poles, switchgear Reactive power Effective reactive capacitor power Nominal reactive power Ratio of resistance to reactance Resistance in the zero phase-sequence system Minimum/maximum resistance in the zero phasesequence system Resistance in the zero phase-sequence system Phase - N Resistance in the zero phase-sequence system Phase - PE(N) Resistance in the zero phase-sequence system for the voltage drop Resistance ratio of zero/positive phase-sequence system

r0ph-n [m/m]

Specific active resistance of the zero phasesequence system for the phase to neutral conductor loop Specific active resistance of the zero-phasesequence system for the phase to protective conductor loop Specific active resistance of positive phasesequence system Related resistance value in the positive phasesequence system Resistance in the positive phase-sequence system Resistance in the positive phase-sequence system for the voltage drop Minimum/maximum resistance in the positive phase-sequence system Sum of resistances of the earth electrode and possibly wired protective conductor between exposed conductive part and earth in the IT or TT network Minimum/maximum loop resistance Apparent power Thermal fault withstand capability of the cable Nominal apparent power Nominal apparent power of transformer Delay time for the overcurrent module of DMT relay Delay time for the high-current module of DMT relay Permissible switch disconnection time for the setting value of the I-release, without violating the condition k2S2>I2t Permissible switch disconnection time at maximum short-circuit current, without violating the condition k2S2>I2t Permissible switch disconnection time at minimum short-circuit current, without violating the condition k2S2>I2t Permissible disconnection time in compliance with DIN VDE 0100-410 (IEC 60364-4-41) Controlled permissible switch disconnection time Switchgear disconnection time for disconnect condition

r0ph-pe(n) [m/m]

r1 [m/m] r1 [%] R1 [m] R1U [m] R1 min/max [m] Ra+Rb max [m]

R0 min/max [m] S [kVA] S2K2 S [kVA] SnT [kVA] t> [s] t>> [s] ta zul (Ii) [s]

ta zul (Ikmax) [s]

ta zul (Ikmin) [s]

ta zul ABS [s] ta zul beeinfl [s] ta(min abs) [s]

ta(min kzs) [s] ta_max [s] te [s] tg [s] tR [s] tsd [s] Tu [C] ukr [%] Umax [V] Un [V] Uprim [kV] Usec [V] LVSD V X0 min/max [m] X0 N [m] X0 PE(N) [m] X0U [m] X0/X1 x0ph-n [m/m]

Switchgear disconnection time for short-circuit protection Maximum disconnection time of the switchgear to be evaluated Delay time of the earth energizing current of the DMT relay Time value of the G-release (absolute) Time value of the L-release Time value of the S-release Ambient device temperature Short-circuit voltage Maximum rated voltage of the busbar system Nominal voltage Primary voltage Secondary voltage Low-voltage sub-distribution (system) Load Minimum/maximum reactance in the zero phasesequence system Reactance of phase-N in the zero phasesequence system Reactance of phase-PE(N) in the zero phasesequence system Reactance of the zero phase-sequence system for voltage drop, independent of temperature Reactance ratio of zero/positive phase-sequence system Specific reactive resistance of the zero phasesequence system for the phase to neutral conductor loop Specific reactive resistance of the zero-phasesequence system for the phase to protective conductor loop Specific reactive resistance of positive phasesequence system Reactance in the positive phase-sequence system Minimum/maximum reactance in the positive phase-sequence system Reactance in the positive phase-sequence system for the voltage drop

x0ph-pe(n) [m/m]

x1 [m/m] X1 [m] X0 min/max [m] X1U [m]

xd [%] Xs min/max [m] Z0 [m] Z0 min/max [m] Z0U [m] Z1 [m] Z1 min/max [m] Z1U [m] Zs Zs min/max

Subtransient reactance Minimum/maximum loop reactance Impedance of zero phase-sequence system Minimum/maximum impedance in the zero phasesequence system Impedance in the zero phase-sequence system for the voltage drop Impedance of positive phase-sequence system Minimum/maximum impedance in the positive phase-sequence system Impedance in the positive phase-sequence system for the voltage drop Loop impedance Minimum/maximum loop resistance