NHNG TIU CHN THNG THNG CHO THIT K CC TON NH THNG MI V CNG CNG Applications Handbook 2003

American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE)

Category
Airport terminals Bars Bowling centers Bus terminals Cafeterias & luncheonettes

52.2 Filter Efficiency


MERV 7 or better MERV 7 MERV 5 MERV 7 with exfiltration MERV 7 or better

52.1 Filter Efficiency


35% or better 35% 10 to 15% 35% with exfiltration 35% or better

Air changes per hour


8 to 12 15 to 20 10 to 15 8 to 12 12 to 15

Air movement
25 to 30 fpm @ 6' above floor 30 fpm @ 6' above floor 50 fpm @ 6' above floor 25 to 30 fpm @ 6' above floor 50 fpm @ 6' above floor

Temperature & humidity, winter


70 to 74F 20 to 30% rh 70 to 74F 20 to 30% rh 70 to 74F 20 to 30% rh 70 to 74F 20 to 30% rh 70 to 74F a 20 to 30% rh

Temperature & humidity, summer


74 to 78F 50 to 60% rh 74 to 78F 50 to 60% rh 75 to 78F 50 to 55% rh 74 to 78F 50 to 60% rh 78F 50% rh

Comments
Positive air pressure required in terminal

Positive air pressure required in terminal

Garages d

MERV 5

10 to 15%

4 to 6

30 to 75 fpm

40 to 55F

80 to 100F

Kitchens

MERV 5

10 to 15% or better

30 to 50 fpm

12 to 15b

70 to 74F

85 to 88F

Negative air pressure required to rmove fumes; positive air pressure required in adjacent occupied spaces Negative air pressure required for odor control (see ASHRAE Handook, Applications, Chapter 31)

Museums (average)

Museums (archival)

MERV 7 to MERV 11 or better MERV 7 prefilters, charcoal, MEFV 13 to 14 final filters MERV 7 a

35 to 60% or better 35% prefilters, charcoal, 8595% final filters c 35% a

8 to 12

below 25 fpm

68 to 72F 40 to 45% rh

8 to 12

below 25 fpm

See ASHRAE Handbook for Applications or contact Camfil Farr 70 to 74F 20 to 30% rh 74 to 78F 50 to 60% rh

Nightclubs & casinos

20 to 30

below 25 fpm @ 5' above floor

27MEC Co.,Ltd Phin L c Khng Kh

Office buildings Radio & television stations Restaurants Shipping docks

MERV 7 to MERV 11 or better MERV 7 or better MERV 7 or better MERV 5

35 to 60% or better 35% or better

4 to 10

25 to 45 fpm, 0.75 to 2 cfm/ft2

70 to 74F 20 to 30% rh 74 to 78F 30 to 40% rh 70 to 74F 20 to 30% rh 70 to 74F 20 to 30% rh 72 to 78F 40 to 50% rh

74 to 78F 50 to 60% rh 74 to 78F 40 to 55% rh 74 to 78F 55 to 60% rh 74 to 78F 50 to 60% rh 72 to 78F 50 to 55% rh Positive air pressure required in waiting area Constant temperature & humidity required Constant temperature & humidity required

15 t0 40

below 25 fpm @ 12' above floor

35% or better 10 to 15%

8 to 12 8 to 12

25 to 30 fpm 25 to 30 fpm @ 6' above floor

Telephone terminal rooms Warehouses

MERV 13 or better MERV 5 to 7

85% or better

8 to 20

25 to 35 fpm

10 to 35%

1 to 4

N/A

Inside design temperature often depends on materials stored

Bng trn a ra nhng hng dn thit k khc nhau gia cc ta nh thng mi v cng cng, n khng ph i l tiu chun thit k. Mi d liu trong bng c tp hp t s tay v nhng tiu chun ASHRAE (handbook & Standard). Tra cu nhng thng s trn xc nh yu cu cho php nh nht. Khng kh ly t ngoi tri cn xem xt trang b cng su t lc kh ph hp i vi tng khu vc cng trinh (khu cng nghip, thnh th, khu dn c,..) hoc trang b nhng thit b lc kh v kh mi ph hp (kh i, khi xe, khi thuc,..). Tham kho thm trong tiu chun ASHRAE 62 v cch tnh ton ny hoc Chng 45 s tay ng dng ASHRAE v chng 13- s tay c bn ASHRAE (2011).
a

y thng ra nhng khu vc thc n nhanh hn l trong nh hng v cc ba n khng ko di lu nn khng yu cu yu cu thoi mi nh trong nh hng. V th ch tiu thit k ca n thp hn nhng vn m bo c iu kin thoi mi.
b

Thng thng c xc nh bi hng ht. Cn xem xt n vn x l kh nhim, lc ha cht. ( nhim ha hc cn c xem xt k) Bao gm c nhng trm dch v.

Thng tin thm c th tn trn www.ashrae.org Ngu n tham kh o: www.camfilfarr.com.vn