38ARZ/ARD

Commercial Air-Cooled Split


Sizes 007 - 028
With 40RM007-028
5-24 Nominal Tons - 50Hz

Product Data
The 38ARZ/ARD condensing units with scroll compressors match Carriers 40RM
indoor-air

handlers for a wide selection of dependable commercial cooling solutions.

Carriers air-cooled split systems:


provide a logical solution for
commercial needs
have a rugged, dependable
construction

Features/Benefits
These
dependable
split
systems
match
Carriers
indoor-air handlers and directexpansion coils with outdoor
condensing units for a wide
selection
of
commercial
cooling solutions.
Up to 11.0 EER
The high efficiency split commercial split
system combining the 38ARZ/ARD
outdoor condensing unit with 40RM air
handling unit can save 20-27% of energy
consumption.

Constructed for long life


The 38ARZ (single circuit, scroll
compressor) and 38ARD (dual circuit,
scroll compressor) models are designed and
built to last. The copper tube-aluminum fin
outdoor coil construction provides years of
trouble-free operation. Where conditions
require, a range of Enviro-Shield coil
protection options are available. Cabinets
are constructed of prepainted galvanized
steel, delivering unparalleled protection
from the environment. Inside and outside
surfaces are protected to ensure long life,
good looks, and reliable operation. Safety
controls are used for enhanced system
protection
and
reliability.

38AR-03 PD

Efficient operation
Building owners will appreciate the high unit EERs
(Energy Efficiency Ratios) offered by the 38AR units.
These units provide greater efficiency than similar
units in the marketplace, which translates into yearround operating savings.

Controls for performance dependability


The 38AR condensing units offer the building owner
operating controls and components designed for
performance dependability. The highly efficient
compressors are engineered for long life and
durability. The compressors include overload
protection and vibration isolation for quiet operation.
The high pressure switch protects the entire
refrigeration system from abnormally high operating
pressures. A low pressure switch protects the system
from loss of charge.
The 38ARD014-028 units feature 2 compressors and 2
refrigerant circuits that provide continuous air
conditioning and design flexibility.
All units include a crankcase heater to eliminate liquid
slugging at start-up. The latest safety standards for
38AR units are UL, compliant.

Innovative Carrier 40RM packaged air


handlers are custom matched to 38AR
condensing units
The 40RM Series has excellent fan performance,
efficient direct-expansion (DX) coils, a unique
combination of indoor-air quality options, and is easy
to install. Its versatility and state-of-the art features
help to ensure economical performance of the split
system both now and in the future.
Indoor-air quality (IAQ) features
The unique combination of IAQ features in the 40RM
Series air handlers help to ensure that only clean,
fresh, conditioned air is delivered to the occupied
space.
Direct-expansion (DX) cooling coils prevent the buildup of humidity in the room, even during part-load
conditions. Unit sizes of 10 tons and larger feature
dual-circuit coils for improved temperature control.
Standard 1-in. aluminum washable filters remove dust
and airborne particles from the occupied space for
cleaner air.

The pitched, non-corroding drain pan can be adjusted


for a right-hand or left-hand connection to suit many
applications and provide positive drainage and prevent
standing condensate.
Economy The 40RM Series packaged air handlers
have low initial costs, and provide reduced installation
expense and energy-efficient performance.
Quick installation is ensured by the multipoise design.
Units can be installed in either the horizontal or
vertical configuration without modifications. Fan
motors and contactors are prewired and thermostatic
expansion valves (TXVs) are factory-installed on all
40RM models.
High efficiency, precision-balanced fans minimize air
turbulence, surging, and unbalanced operation, cutting
operation expenses.
Rugged dependability The 40RM series units are
made to last. The die-formed galvanized steel panels
ensure structural integrity under all operating
conditions. Galvanized steel fan housings are securely
mounted to a galvanized steel fan deck. Rugged
pillow-block bearings (40RM014-034) are securely
fastened to the solid steel fan shaft with split collets
and clamp locking devices. Smaller unit sizes have
spider-type bearings.
Coil flexibility Model 40RM directexpansion coils
have galvanized steel casings; inlet and outlet
connections are on the same end. The coils are
designed for use with R-22 refrigerant and have 3/8-in.
diameter copper tubes mechanically bonded to
aluminum sine-wave fins.
The coils include matched, factoryinstalled
thermostatic expansion valves (TXVs) with matching
distributor nozzles.
Easier installation and service
The multipoise design and component layout ensures
quick unit installation and operation. Units can be
converted from horizontal to vertical operation by
simply repositioning the unit. Drain pan connections
are duplicated on both sides of the unit. The filters,
motor, drive, TXVs, and coil connections are all easily
accessed by removing side panels.

Model number nomenclature


38AR

Type
38ARCommercial AirCooled Condenser

007

--

S - High Ambient
Packaging
1 - Standard

Z-Single Circuit
D- Dual Circuit
Nominal Capacity in-Tons
007 - 5.0 Tons
008 - 7 0
. Tons
012 - 8.7 Tons
014 - 10.8 Tons
016 - 14 Tons
024 - 18.1 Tons
028 - 24 Tons

Design Series
0 - Original Design

Voltage
9 400350

Fin Type
-- - Standard Bare Fins
C- Cu/Cu Coil
P- Pre-Coated Blue Fins

-- - Not Used

Table of Contents
Page.

38ARZ/ARD
Features/Benefits.
ModelNumber Nomenclature..
Physical Data.
Options and accessories .
Electrical Data
Base Unit Dimensions..
Performance data
Application Data
Typical Wiring Schematic.

1
3
4
5
5
6-8
9-12
13
14-18

40RM
Model number nomenclature..
Physical Data.
Base Unit Dimensions..
Fan Performance Data ..
Electrical Data
Typical piping and wiring
Application Data

19
20
21-24
25-27
28
29
31

Guide Specifications
Guide Specifications 38ARZ007-012..
Guide specifications 38ARD014-028 .
Guide specifications 40RM

34,35
36,37
38,39

Physical Data
UNIT 38AR
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Aluminium Coils (Standard)
Cooper Coils (Optional)
COMPRESSOR
Qty
Oil Charge (oz)
REFRIGERANT TYPE *
Operating Charge, Typical (lb) **
Shipping Charge (lb)
FINISH
CONDENSER FAN
QtyRPM
Diameter
Nominal Air Flow (Total CFM)
Motor HP-Shaft
CONDENSER COIL (Qty)
Face Area (sq ft Total))
RowsFins/in.
Storage Capacity (lb)***
CONTROLS
Pressurerestart Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
DISCHARGE GAS THERMOSTAT (0F)
Cutout
Cut-in
PRESSURE RELIEF
Location
Tempreature
PIPING CONNECTION
QtySuction
QtyLiquid
Hot Gas Stub

UNIT 38AR
SHIPPING DIMENSIONS (in) (W X H X D)

007
5.0

ARZ
008
7. 0

012
9.3

014
10. 8

ARD
016
14

024
18 .1

028
24

300
352

383
484

430
531

676
822

740
886

764
904

1279
1532

60(ea)

85(ea)

110(ea)

111(ea)

Scroll
88

90

R22
12

20
2.0

22

14/circuit 17.97/circuit

11.5/circuit
3.1

Gray
Propeller Type
2700

2920
22 in

5000
2x1/8

5800
2x1/4

2900
26 in
9210
2x1/2

2900
30 in
13000
2x1

29.2
315
48

50.4
316
-

428 10
320 20
27 4
44 7

428 10
320 20
27 4
44 7

---

---

Liquid Line
200

Liquid Line
200

21 3/8
2 1/2
3/8

21 3/8
2 5/8
-

2
29.2
117
17.3

217
34.2

428 10
320 20
27 3
44 5
270 9
190 13

---

Suction Line
200
11 1/8
1 3/8

007

11 1/8
1 3/8

ARZ
008
012
(59.2X45.5X39)

*Unit is factory-supplied with holding charge only.


**Typical operating charge with 25 ft of interconnecting piping.
***Storage capacity of condenser coil with coil 80% full of liquid R-22 at 95 F.

110

11 3/8
1 1/2

ARD
014
016
024
(72.6X44.25X41.7)

028
(96.5X49.6 X54.3)

Options and accessories


38AR, options
Enviro-Shield condenser options offer pre-coated coils that provide protection in mild coastal
environments. Several options are available to match coil protection to site conditions for optimum durability.
See table below. Consult your Carrier representative for further information.
Non-fused disconnect switch to remove power locally at the condensing unit. This switch also includes a
power lockout capability to protect the service person. This lockout switch saves the service person time and
effort because there is no need to access a distant disconnect switch while servicing the unit.
Carriers line of thermostats provide both programmable and non-programmable capability with the new
Debonair line of commercial programmable thermostats. The Commercial Electronic thermostats provide
7-day programmable capability for economical applications.
PremierLink Controller is a field retrofit split system control compatible with the Carrier Comfort Network
(CCN) and other building automation systems (BAS). This control is designed to allow users the access and
ability to change factory-defined settings thus expanding the function of the standard unit.

CONDENSER COIL OPTIONS


COPPERTUBECOILS
WITHENVIROSHIELDOPTION
AlFins(StandardCoils)
CuFins

Standard
X

ENVIRONMENT
MildCoastal

ModerateCoastal
X

AlFins,PreCoated
LEGEND
Al Aluminum
Cu Copper

Electrical data
VOLTAGE
RANGE*

COMPRESSOR
1

COMPRESSOR
2

UNIT
SIZE
38AR

NOMINAL
VOLTAGE
V-Ph-Hz

MIN

MAX

RLA

LRA

RLA

LRA

Z007
Z008
Z012
D014
D016
D024
D028

400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50

360
360
360
360
360
360
360

440
440
440
440
440
440
440

9.6
13.5
20.7
9.6
13.5
20.7
22.9

82
95
130
82
95
130
145

---9.6
13.5
20.7
22.9

---82
95
130
145

LEGEND
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC, Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (compressor)

FAN MOTORS
(Qty 2)
FLA
LRA
(ea)
(ea)
0.5
0.9
0.8
1.6
0.8
1.6
1.7
-1.7
-1.7
7.5
3.0
--

POWER
SUPPLY
MCA

MOCP

12.4
17.9
26.9
27.8
38.0
56.0
63.3

20
30
45
30
45
70
80

*Units are suitable for use on electrical systems where voltage


supplied to the unit terminals is not below or above the listed
limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with
theNational Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters Laboratories (UL), Standard 1995.

Base Unit Dimensions 38ARZ 007 012


38ARZ Size
007
008
012

Approximate Shipping Weight


With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG
LB
KG
LB
154
339
178
392
192
422
238
524
213
467
259
570

Approx. Shipping Dimensions


(AxBxC)
mm
inch
(1504X1157X992)

(59.2X45.5X39)

Base Unit Dimensions 38ARD 014 024


38ARD Size
014
016
024

Approximate Shipping Weight


With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG
LB
KG
LB
357
785
423
931
386
849
452
994
397
873
461
1014

Approx. Shipping Dimensions


(AxBxC)
mm
inch
(1844X1124X1058)

(72.6X44.25X41.7)

Base Unit Dimensions 38ARD 028

38ARZ
size
028

Approximate shipping weight


With standard Al/Cu Coil With optional Cu/Cu Coil
KG
LB
KG
LB
580
1279
695
1532

Approx. shipping dimensions


(ABC)
mm
Inch
245113801282 96.554.350.5

Performance data 50Hz


38ARZ007 / 40RM007
Temp (F) Air
Entering Condenser
(Edb)

90
95
111
115
118.4
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

57
55.6
55.6
4.11
54.5
54.5
4.35
52.2
52.2
5.18
51.5
51.5
5.37
50.8
50.8
5.55
49.8
49.8
5.92

61
56.2
53.9
4.12
55.5
53.4
4.36
52.5
51.5
5.19
51.9
51.0
5.37
51.2
50.5
5.55
49.8
49.8
5.92

38ARZ007 / 40RM008
Temp (F) Air
Entering Condenser
(Edb)

90
95
111
115
118.4
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

90
95
111
115
118.4
125

62
58.4
49.9
4.16
57.5
49.1
4.4
54.4
47.3
5.23
53.7
46.8
5.4
52.9
46.3
5.60
51.7
45.4
5.97

67
61.2
44.2
4.21
60.4
43.7
4.45
56.6
42.4
5.28
55.8
42.0
5.46
55.0
41.7
5.64
53.6
40.9
6.01

72
65.8
35.8
4.29
64.6
35.3
4.57
60.7
33.9
5.36
59.9
33.6
5.55
59.0
33.3
5.73
57.3
57.3
6.10

57
63.4
63.4
4.24
62.4
62.1
4.48
60.7
60.7
5.33
59.2
59.2
5.52
57.7
57.7
5.70
56.2
56.2
6.08

Evaporator Air Cfm


3,000
Evaporator Air Ewb (F)
61
62
67
72
63.4
64.8
66.1
69.9
63.4
59.8
56.1
44.7
4.24
4.27
4.29
4.36
62.4
63.7
64.9
68.7
62.1
58.9
55.6
44.2
4.48
4.51
4.53
4.6
60.7
60.8
60.8
64.5
60.7
57.2
53.7
42.6
5.32
5.34
5.35
5.44
59.2
59.6
59.9
63.5
59.2
56.2
53.2
42.3
5.51
5.53
5.54
5.63
57.7
58.4
59.1
62.4
57.7
55.2
52.7
41.9
5.70
5.72
5.73
5.81
56.2
56.7
57.2
60.4
56.2
54.1
51.9
41.6
6.07
6.09
6.10
6.17

57
73.0
73.0
5.45
72.0
71.8
5.77
67.9
67.9
6.86
67.1
67.1
7.10
66.2
66.2
7.34
64.5
64.5
7.82

Evaporator Air Cfm


2,400
Evaporator Air Ewb (F)
61
62
67
72
74.0
76.8
80.5
86.3
70.6
66.6
60.1
46.7
5.46
5.49
5.53
5.63
72.8
75.5
79.0
84.8
69.9
65.6
59.4
46.2
5.78
5.81
5.85
5.95
68.6
71.1
74.2
79.5
67.2
62.6
57.2
44.4
6.87
6.91
6.95
7.06
67.6
70.0
73.0
78.3
66.6
61.9
56.8
43.9
7.11
7.15
7.19
7.31
66.5
69.0
71.8
77.1
65.9
61.3
56.3
43.3
7.35
7.39
7.43
7.55
64.8
67.2
69.8
75.0
64.5
59.9
55.2
42.7
7.83
7.87
7.91
8.04

2,250
57
59.0
59.0
4.16
58.1
58.1
4.4
54.9
54.9
5.23
54.2
54.2
5.42
53.5
53.5
5.60
52.2
52.2
5.96

61
59.0
58.7
4.16
58.1
58.1
4.4
54.9
54.9
5.23
54.2
54.2
5.42
53.5
53.5
5.60
52.2
52.2
5.97

38ARZ008 / 40RM007
Temp (F) Air
Entering Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

57
60.4
60.4
4.18
59.4
59.4
4.42
56.2
56.2
5.27
55.6
55.6
5.46
54.9
54.9
5.64
53.5
53.5
6.01

Evaporator Air Cfm


2,400
Evaporator Air Ewb (F)
61
62
67
72
60.4
62.2
63.9
68.0
60.4
55.7
51.0
40.6
4.19
4.22
4.25
4.33
59.4
61.1
62.7
67.0
59.4
54.9
50.4
40.1
4.43
4.46
4.49
4.57
56.2
57.6
58.9
62.7
56.2
52.5
48.7
38.5
5.26
5.30
5.32
5.4
55.6
56.8
58.1
61.9
55.6
51.9
48.2
38.4
5.45
5.48
5.50
5.59
54.9
56.1
57.3
61.0
54.9
51.4
47.9
38.2
5.64
5.67
5.69
5.77
53.5
54.6
55.6
59.0
53.5
50.3
47.1
37.5
6.01
6.03
6.05
6.14

1,800

62
61.2
53.7
4.20
60.2
53.0
4.4
56.7
50.5
5.27
55.6
50.0
5.5
55.2
49.4
5.64
53.5
48.4
6.00

67
63.4
48.4
4.24
62.2
47.9
4.48
58.4
46.1
5.31
56.9
45.7
5.50
56.9
45.3
5.68
54.8
44.6
6.04

72
67.9
38.6
4.32
66.7
38.1
4.56
62.4
36.8
5.4
61.6
36.5
5.58
60.7
36.2
5.76
58.7
35.5
6.13

1,800
57
66.5
66.2
5.39
65.6
65.2
5.7
62.1
61.8
6.76
61.4
61.1
7.00
60.7
60.4
7.23
59.0
58.7
7.70

61
69.2
61.2
5.41
68.0
61.0
5.72
63.8
58.7
6.8
62.9
58.2
7.04
62.0
57.7
7.27
60.4
56.7
7.74

62
71.6
59.5
5.44
70.4
58.6
5.8
66.4
55.9
6.83
65.5
55.3
7.1
64.6
54.8
7.30
62.8
53.4
7.78

67
76.6
52.7
5.48
75.2
52.0
5.8
70.6
49.9
6.89
69.6
49.5
7.13
68.5
49.1
7.36
66.6
48.1
7.85

72
82.6
41.2
5.57
81.1
41.5
5.89
76.1
39.5
7
75.1
39.1
7.25
74.0
38.6
7.49
72.0
37.9
7.97

3,000
57
63.4
63.4
4.24
62.5
62.5
4.48
59.0
59.0
5.33
58.4
58.4
5.52
57.8
57.8
5.70
56.2
56.2
6.07

61
63.4
63.4
4.24
62.5
62.5
4.48
59.0
59.0
5.32
58.4
58.4
5.51
57.8
57.8
5.69
55.9
55.9
6.06

62
64.6
59.9
4.26
63.6
59.2
4.50
59.9
56.5
5.34
59.1
56.0
5.53
58.3
55.6
5.71
56.7
54.3
6.08

67
65.8
56.4
4.28
64.7
55.8
4.52
60.8
54.0
5.35
59.8
53.5
5.54
58.8
53.3
5.72
57.1
52.4
6.09

72
69.9
45.0
4.36
68.4
44.5
4.60
64.1
42.9
5.43
63.3
42.6
5.62
62.4
42.3
5.80
60.4
41.6
6.17

67
68.0
62.5
4.33
66.3
61.4
4.66
62.7
59.4
5.4
61.8
58.9
5.59
60.9
58.3
5.77
58.9
57.2
6.14

72
71.3
50.2
4.39
68.4
44.5
4.60
65.5
48.1
5.46
64.5
47.8
5.65
63.4
47.4
5.83
61.2
46.7
6.20

67
76.6
52.7
5.48
79.8
61.9
5.87
76.4
62.9
6.99
75.4
62.4
7.23
74.3
61.9
7.47
72.1
60.7
7.96

72
88.7
51.2
5.66
87.2
50.4
5.98
81.5
48.8
7.1
80.4
48.3
7.35
79.2
47.8
7.59
76.8
47.1
8.08

3,750
57
66.9
66.9
4.3
65.7
65.7
4.54
62.0
62.0
5.39
61.2
61.2
5.58
60.4
60.4
5.76
58.7
58.7
6.13

61
66.9
66.9
4.3
65.7
65.7
4.54
62.0
62.0
5.39
61.2
61.2
5.58
60.4
60.4
5.76
58.7
58.7
6.14

62
67.5
64.7
4.32
66.0
63.6
4.60
62.4
60.7
5.40
61.5
60.1
5.58
60.7
59.4
5.77
58.8
58.0
6.14

3,000
57
77.7
77.7
5.51
76.6
76.6
5.83
72.3
72.3
6.93
71.3
71.3
7.17
70.3
70.3
7.41
68.6
68.6
7.89

61
77.7
77.7
5.51
76.6
76.5
5.83
72.3
72.3
6.92
71.1
71.1
7.16
69.9
69.9
7.40
68.2
68.2
7.88

62
77.2
65.2
5.50
78.2
69.3
5.85
74.4
67.6
6.96
73.3
66.9
7.20
72.3
66.1
7.44
70.4
64.7
7.93

38ARZ008 / 40RM008
Temp (F) Air
Entering Condenser
(Edb)

90
95
111
115
118.4
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

57
70.9
70.9
5.43
69.9
69.8
5.74
66.2
66.2
6.83
65.4
65.4
7.07
64.5
64.5
7.30
62.8
62.8
7.78

61
72.7
67.6
5.45
71.5
66.8
5.76
67.2
64.5
6.84
66.2
64.0
7.08
65.2
63.5
7.32
63.1
62.1
7.80

38ARZ012 / 40RM008
Temp (F) Air
Entering Condenser
(Edb)

90
95
111
115
118.4
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

90
95
111
115
118.4
125

10

62
75.2
63.1
5.49
73.9
62.2
5.8
69.7
59.4
6.89
68.7
58.7
7.1
67.8
58.1
7.37
65.9
56.8
7.85

67
79.4
55.2
5.54
77.9
54.5
5.85
73.1
52.5
6.94
72.1
52.1
7.19
71.0
51.7
7.43
68.9
50.7
7.91

72
85.3
44.7
5.61
83.8
44.2
5.93
78.5
42.3
7.04
77.5
42.0
7.29
76.4
41.6
7.53
74.0
40.6
8.02

57
93.8
93.5
7.49
92.4
92.0
7.83
87.3
87.0
8.95
86.1
86.0
9.20
84.9
84.9
9.45
82.9
82.9
9.95

Evaporator Air Cfm


3,000
Evaporator Air Ewb (F)
61
62
67
72
95.5
98.8
103.8
110.9
89.4
83.1
72.7
59.0
7.54
7.62
7.75
7.94
91.4
97.3
102.1
108.8
88.4
82.0
71.9
58.3
7.87
7.95
8.07
8.28
88.4
91.4
95.4
102.0
84.6
78.1
69.1
55.6
8.98
9.07
9.18
9.37
87.2
90.1
94.1
100.5
83.9
77.3
68.6
55.1
9.23
9.31
9.42
9.62
85.9
88.8
92.7
98.9
83.2
76.5
68.0
54.6
9.47
9.56
9.66
9.86
83.2
86.3
89.7
95.9
81.5
74.9
66.9
53.6
9.96
10.06
10.17
10.30

57
104.1
104.1
7.75
102.4
102.4
8.09
96.6
96.6
9.2
95.2
95.2
9.45
93.8
93.8
9.70
91.1
91.1
10.20

Evaporator Air Cfm


4,000
Evaporator Air Ewb (F)
61
62
67
72
104.4
107.5
110.9
117.7
103.4
94.9
85.8
67.9
7.75
7.85
7.94
8.13
102.5
105.6
108.7
115.5
101.9
93.7
84.9
67.2
8.09
8.18
8.27
8.47
96.2
99.0
101.5
107.8
96.2
89.0
81.5
64.5
9.19
9.28
9.36
9.56
94.9
97.6
100.0
106.1
94.9
88.0
80.8
64.0
9.44
9.52
9.60
9.78
93.5
96.2
98.5
104.4
93.5
86.9
80.0
63.5
9.68
9.77
9.83
10.00
90.8
93.2
95.2
101.0
90.8
84.9
78.7
62.1
10.20
10.25
10.29
10.50

2,250
57
84.9
84.3
7.31
83.7
83.1
7.65
79.5
78.8
8.78
78.5
78.0
9.03
77.5
77.1
9.28
75.7
75.4
9.79

61
89.1
77.5
7.39
87.6
76.5
7.72
82.6
73.4
8.84
81.4
72.7
9.09
80.2
72.0
9.33
77.8
70.6
9.83

38ARZ012 / 40RM012
Temp (F) Air
Entering Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

57
77.8
77.4
5.51
76.3
76.2
5.83
72.3
72.3
6.93
71.3
71.3
7.17
70.3
70.3
7.41
68.6
68.6
7.90

Evaporator Air Cfm


3,000
Evaporator Air Ewb (F)
61
62
67
72
77.8
80.6
83.4
88.7
77.1
70.7
63.9
50.8
5.6
5.55
5.59
5.66
76.5
79.0
81.7
87.2
76.1
69.8
63.3
50.4
5.83
5.87
5.91
5.98
72.3
74.5
76.7
81.5
72.3
66.8
61.2
48.5
6.93
6.97
7.01
7.09
71.3
73.4
75.6
80.4
71.3
66.0
60.6
48.0
7.17
7.21
7.26
7.34
70.3
72.4
74.4
79.2
70.3
65.2
60.0
47.4
7.41
7.46
7.50
7.58
68.2
70.4
72.1
76.8
68.2
63.8
58.9
46.7
7.90
7.94
7.98
8.07

2,250

62
91.7
73.9
7.46
90.2
72.9
7.8
85.2
69.4
8.91
84.0
68.7
9.2
82.8
68.0
9.41
80.6
66.6
9.89

67
98.4
63.4
7.61
96.6
62.6
7.94
90.8
59.9
9.04
89.5
59.4
9.29
88.1
58.8
9.53
85.4
57.7
9.98

72
105.4
52.5
7.79
103.7
51.8
8.12
97.2
49.5
9.22
95.9
48.8
9.46
94.5
48.1
9.70
91.8
47.1
10.20

3,000
57
97.2
96.9
7.57
95.8
95.4
7.91
90.4
90.1
9.03
89.2
88.9
9.28
88.0
87.7
9.52
85.6
85.6
10.00

61
98.9
93.1
7.61
97.0
92.2
7.94
91.1
88.4
9.05
89.7
87.5
9.30
88.4
86.7
9.54
85.6
85.0
10.00

62
102.1
86.5
7.70
100.4
85.3
8.0
94.3
81.1
9.14
92.9
80.2
9.4
91.6
79.2
9.62
88.9
77.7
10.09

67
106.9
76.1
7.83
104.9
75.2
8.16
98.1
72.2
9.25
96.6
71.5
9.49
95.1
70.8
9.72
92.1
69.7
10.17

72
114.0
61.4
8.03
112.0
60.7
8.36
104.7
58.0
9.45
103.0
57.3
9.69
101.3
56.6
9.93
98.3
55.3
10.40

3,750
57
82.2
82.2
5.57
81.0
81.0
5.89
76.4
76.4
7
75.4
75.4
7.25
74.4
74.4
7.49
72.3
72.3
7.98

61
82.2
82.2
5.57
81.0
81.0
5.89
76.4
76.4
7
75.4
75.4
7.25
74.4
74.4
7.49
72.3
72.3
7.98

62
84.0
76.8
5.60
82.7
75.8
5.92
77.8
72.3
7.02
76.7
71.5
7.27
75.6
70.7
7.51
73.4
69.1
8.00

67
85.8
71.4
5.62
84.3
70.6
5.94
79.1
68.2
7.04
77.9
67.6
7.29
76.7
67.0
7.53
74.4
65.9
8.02

72
91.1
56.3
5.69
89.4
55.8
6.01
83.6
53.9
7.13
82.4
53.6
7.38
81.2
53.2
7.62
78.5
52.2
8.11

67
107.4
81.3
7.85
105.4
80.3
8.18
98.7
77.3
9.27
97.2
76.7
9.51
95.7
76.0
9.74
92.7
74.5
10.27

72
114.3
64.5
8.04
112.4
63.8
8.37
104.7
61.4
9.46
103.2
60.8
9.70
101.7
60.1
9.94
98.3
59.0
10.40

67
113.5
93.9
8.02
111.4
93.0
8.35
104.2
89.5
9.43
102.6
88.7
9.67
100.9
87.9
9.91
97.5
86.3
10.39

72
120.1
74.0
8.2
117.7
73.3
8.53
109.9
70.6
9.62
108.2
70.1
9.86
106.5
69.6
10.10
102.7
68.2
10.60

3,750
57
100.0
100.0
7.64
98.3
98.3
7.98
92.8
92.8
9.09
91.6
91.6
9.34
90.4
90.4
9.58
87.7
87.7
10.10

61
100.3
98.6
7.65
98.6
97.4
7.99
92.8
92.8
9.09
91.4
91.4
9.34
90.0
90.0
9.58
87.7
87.7
10.10

62
103.7
90.7
7.75
101.9
89.3
8.08
95.8
85.1
9.18
94.4
84.1
9.42
93.1
83.2
9.66
90.2
81.1
10.19

5,000
57
108.8
108.8
7.88
107.1
107.1
8.22
100.7
100.7
9.33
99.3
99.3
9.57
97.9
97.9
9.81
94.9
94.9
10.30

61
108.8
108.8
7.88
107.1
107.1
8.22
100.7
100.7
3.92
99.3
99.3
6.87
97.9
97.9
9.81
94.9
94.9
10.30

62
111.2
101.4
7.95
109.3
100.1
8.29
102.4
95.1
9.38
100.9
94.0
9.62
99.4
92.9
9.86
96.2
90.6
10.35

38ARD014/40RM014
Temp (F) Air Entering
Condenser
(Edb)

85
95
105
115
118.4
122

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

62
130.9
119.8
8.4
128.0
118.4
8.9
121.3
113.8
10.3
116.3
109.1
11.3
114.5
107.8
11.6
113.5
106.3
12.0

38ARD016/40RM016
Temp (F) Air Entering
Condenser
(Edb)

85
95
105
115
118.4
122

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

85
95
105
115
118.4
122

67
141.7
101.0
8.5
138.4
109.3
9.0
130.2
96.6
10.3
123.9
94.2
11.4
120.0
93.3
11.7
115.1
93.3
12.1

72
220.2
109.2
11.33
211.1
106.1
11.96
201.5
102.9
14.01
191.4
99.5
15.27
187.7
98.3
15.77
184.0
97.0
16.34

Evaporator Air Cfm


5,700
Evaporator Air Ewb (F)
62
67
72
188.6
197.3
221.8
161.8
132.2
111.1
10.73
11.03
11.36
180.8
204.5
212.6
158.0
137.0
107.9
11.64
11.82
11.98
172.9
186.8
202.7
154.6
130.7
104.7
13.34
13.67
14.04
164.8
172.6
192.6
150.7
127.7
101.3
14.84
15.07
15.30
161.9
169.5
188.8
149.0
125.4
100.0
15.34
15.57
15.80
159.1
166.5
185.1
147.5
123.2
98.8
15.73
16.05
16.37

5,400
62
186.9
157.9
10.70
179.3
154.3
11.61
171.3
150.7
13.30
163.2
147.0
14.81
160.3
145.6
15.31
157.4
144.2
15.70

38ARD024/40RM024
Temp (F) Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

72
162.7
69.9
8.9
159.0
68.7
9.4
149.7
65.6
10.8
142.5
63.3
11.8
139.9
62.5
12.2
137.2
61.7
12.6

Evaporator Air Cfm


4,750
Evaporator Air Ewb (F)
62
67
72
132.2
142.7
163.8
122.8
103.4
70.9
8.3
8.5
8.9
127.6
140.3
157.4
119.4
110.8
68.8
9.2
9.1
9.8
122.8
131.0
150.6
115.2
98.9
66.6
10.2
10.4
10.8
117.8
125.3
143.3
110.9
96.4
64.3
11.2
11.4
11.8
116.0
120.7
140.7
109.4
95.6
63.4
11.6
11.9
12.2
114.2
116.0
138.0
107.8
94.7
62.6
12.0
12.3
12.6

4,500

67
192.4
128.9
11.00
198.5
133.0
11.79
185.5
126.9
13.64
170.2
125.0
15.04
168.6
124.2
15.54
165.2
122.2
16.02

6,000
62
200.0
173.6
14.5
193.0
169.8
15.7
185.0
166.1
17.0
177.0
161.3
18.3
173.6
159.3
18.9
169.0
156.6
19.7

67
216.0
144.4
14.9
207.0
141.5
16.2
198.0
137.7
17.4
189.0
134.9
18.8
185.1
133.3
19.4
180.0
131.1
20.2

72
233.0
114.2
15.5
224.0
110.4
16.7
214.0
107.6
17.9
204.0
103.8
19.2
199.7
102.6
19.8
194.0
101.0
20.6

Evaporator Air Cfm


6,500
Evaporator Air Ewb (F)
62
67
72
199.9
215.9
232.9
173.5
144.3
114.1
14.4
14.8
15.4
192.9
206.9
223.9
169.7
141.4
110.3
15.6
16.1
16.6
184.9
197.9
213.9
166.0
137.6
107.5
16.9
17.3
17.8
176.9
188.9
203.9
161.2
134.8
103.7
18.2
18.7
19.1
173.5
185.0
199.6
159.2
133.2
102.5
18.8
19.3
19.7
168.9
179.9
193.9
156.5
131.0
100.9
19.6
20.1
20.5

5,000
62
133.4
133.8
8.3
129.0
128.7
9.2
124.3
123.2
10.2
119.3
117.4
11.3
117.4
115.8
11.6
115.5
113.9
12.0

67
143.7
105.8
8.5
142.9
112.9
9.2
131.8
101.2
10.4
126.7
98.8
11.5
121.5
97.9
12.0
116.8
95.5
12.5

72
164.9
71.8
8.9
158.3
69.7
9.8
151.4
67.5
10.8
144.1
65.2
11.9
141.4
64.4
12.3
138.7
63.5
12.6

6,000
62
190.1
165.4
10.77
182.4
162.1
11.67
174.5
158.5
13.38
166.4
154.1
14.87
163.6
152.2
15.37
160.6
150.8
15.76

67
201.8
137.2
11.06
206.0
140.1
11.85
188.0
135.4
13.70
173.6
128.4
15.10
170.5
126.2
15.60
167.9
124.2
16.08

72
223.3
112.9
11.40
213.9
109.8
12.02
204.1
106.5
14.07
193.6
103.1
15.32
189.9
101.8
15.83
186.1
100.6
16.40

7,000
62
205.5
185.4
14.6
198.0
180.7
15.8
190.5
175.5
17.1
182.5
169.4
18.5
179.1
166.7
19.1
174.5
163.2
19.9

67
220.0
155.2
15.1
211.0
151.9
16.3
201.5
148.1
17.5
187.6
140.5
20.0
184.4
139.8
20.5
180.2
136.8
21.1

72
237.0
120.8
15.6
227.5
117.0
16.9
217.5
114.2
18.1
207.0
110.4
19.4
202.5
109.2
20.00
196.5
107.6
20.8

11

38ARD028/40RM028
Temp (F) Air Entering
Condenser
(Edb)
TC
85
SHC
kW
TC
95
SHC
kW
TC
105
SHC
kW
TC
115
SHC
kW
TC
118.4
SHC
kW
TC
122
SHC
kW

7,000
62
268.4
257.2
19.60
258.6
252.4
20.60
248.8
243.5
23.00
243.1
239.7
24.80
239.5
237.0
25.60
234.7
233.3
26.70

67
287.3
215.3
20.20
275.5
210.8
21.00
263.1
200.5
23.50
256.4
192.7
25.30
252.0
191.3
26.10
246.1
189.5
27.20

72
309.5
167.6
21.00
297.1
162.3
22.00
284.0
158.4
24.20
275.7
153.1
26.00
270.8
152.2
26.80
264.3
151.1
27.80

Evaporator Air Cfm


7,500
Evaporator Air Ewb (F)
62
67
72
268.3
287.2
309.4
257.1
215.2
167.5
19.54
20.14
20.94
258.5
275.4
297.0
252.3
210.7
162.2
20.54
20.94
21.94
248.7
263.0
283.9
243.4
200.4
158.3
22.94
23.44
24.14
243.0
256.3
275.6
239.6
192.6
153.0
24.74
25.24
25.94
239.4
251.9
270.7
236.9
191.2
152.1
25.54
26.04
26.74
234.6
246.0
264.2
233.2
189.4
151.0
26.64
27.14
27.74

8,000
62
271.5
264.9
19.70
261.2
257.3
20.70
252.2
248.4
23.10
246.7
243.0
25.00
243.2
239.5
25.90
238.5
234.9
27.00

-Entering indoor air conditions at 80F db / 67F wb


LEGEND
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Compressor Motor Power Input

12

SHC Sensible Heat Capacity (kBtuh) Gross


TC Total Capacity (kBtuh) Gross

67
288.2
223.0
20.30
27.6
218.0
21.10
263.7
212.9
23.60
257.2
199.3
25.30
252.6
196.9
26.10
246.5
193.8
27.20

72
310.1
171.1
21.10
297.2
166.0
22.10
284.3
162.2
24.30
275.6
157.1
26.10
270.5
156.1
26.90
263.7
154.8
28.00

Application data
Operating limits SI (English)
52 C (125 F)

Maximum Outdoor
Temperature
Minimum Outdoor Ambient

LIQUID LINE DATA 38ARD014-028 UNITS


See Minimum Outdoor-Air
Operating Temperature
table below.

Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge Superheat

13 C (55 F)
35 C (95 F)
-4 to 13 C (25 to 55 F)

REFRIGERANT PIPING SIZES


UNIT
38AR

MAXIMUM REFRIGERANT CHARGE


R-22
kg
7.7
15.5
15.5
(2)7.7
(2) 15.5
(2) 15.5
(2) 12.5

Z007
Z008
Z012
D014
D016
D024

UNIT
38AR

MINIMUM OUTDOOR-AIR OPERATING


TEMPERATURE
COND
TEMP
C (F)

MINIMUM OUTDOOR TEMP C (F)

38ARZ007-012
38ARD014-024

32 (90)

10 (50)

38ARD028

32 (90)

15 (59)

Std

1.1 (2)

For refrigerant lines longer than 75 lineal ft, a


liquid line solenoid valve installed at the indoor
unit and a suction accumulator are required. Refer
to the Refrigerant Specialties
Part Numbers table.

For applications with liquid lift greater than 6 m


(20 ft), use 1/2-in. liquid line where 3/8 in. is shown;
use 5/8-in. liquid line where 1/2 in. is shown. The
maximum liquid lift is 18 m (60 ft).

UNIT 38AR

48.8 (7)

It is recommended that the refrigerant piping for all


commercial split systems include a liquid line
solenoid valve, a liquid line filter drier and a sight
glass.

Liquid line

Z007
Z008
Z012
D014
D016
D024
D028

18.2 (60)

IMPORTANT: Do not bury refrigerant piping


underground.

16 C (60 F)

lb
17.3
34.2
34.2
(2)17.3
(2)34.2
(2)34.2
(2)27.5

38ARZ007-012
38ARD014-028

LIQUID LINE
Max Allow.
Max Allow.
Pressure Drop
Temp Loss
kPa (psi)
C(F)

Refrigerant piping

135 C (275 F)

NOTES:
1. Select air handler at no less than 40 L/s per kW (300 cfm/ton)
(nominal condensing unit capacity).
2. Total combined draw of the field-supplied liquid line
solenoid valve and air handler fan contactor must not exceed 22
va. If the specified va must be exceeded, use a remote relay to
control the load.

UNIT 38AR

UNIT 38AR

MAX
ALLOW.
LIFT
m(ft)

D028

07.6(0-25)
L
3/8
3/8
1/2
1/2
1/2
1/2

S
1 1/8
1 1/8
1 3/8
1 1/8
1 3/8
1 3/8

04 (0-13.1 )
L
5/8

S
1 3 /8

LINEAR LENGTH OF PIPING M (FT)


7.615.2(25-50)
15.222.4(50-75)
22.430.5(75-100)
Line Size (in. OD)
L
S
L
S
L
S
3/8
1 1/8
3/8
1 1/8
3/8
1 1/8
1/2
1 1/8
1/2
1 1/8
1/2
1 3/8
1/2
1 3/8
1/2
1 3/8
1/2
1 3/8
1/2
1 1/8
1/2
1 1/8
1/2
1 1/8
1/2
1 3/8
1/2
1 3/8
5/8
1 3/8
1/2
1 3/8
5/8
1 3/8
5/8
1 3/8

LINEAR LENGTH OF PIPING M (FT)


4-10 (13.1-32.8 )
10-22 (32.8-72.2)
2230.5(72.2-100)
Line Size (in. OD)
L
S
L
S
L
S
7/8
1 5/8
5/8
1 5/8
5/8
1 5/8

LEGEND
L Liquid Line S Suction Line
NOTES:
1. Pipe sizes are based on a 2 F loss for liquid and
suction lines.
2. Pipe sizes are based on the maximum linear length,
shown for each column, plus a 50% allowance for fittings.
3. Charge units with R-22 refrigerant in accordance with
unit installation instructions.

REFRIGERANT SPECIALTIES PART NUMBERS


UNIT
38ARZ007
38ARZ008
38ARZ012
38ARD014
38ARD016
38ARD024
38A RD028

LIQUID
LINE SIZE
(in.)

LIQUID LINE
SOLENOID VALVE
(LLSV)

LLSV COIL

SIGHT GLASS

FILTER DRIER

SUCTION LINE
ACCUMULATOR

3/8
3/8
1/2
1/2
1/2

200RB5T4M
200RB5T4M
200RB5T4M
200RB6T4M
200RB5T4M Qty 2

AMG-24/50-60
AMG-24/50-60
AMG-24/50-60
AMG-24/50-60
AMG-24/50-60 Qty 2

AMI1TT3
AMI1TT3
AMI1TT4
AMI1TT4
AMI1TT4 Qty 2

P502-8304S
P502-8304S
P502-8304S
P502-8307S
P502-8304S Qty 2

S-7063S
S-7063S
S-7063S
S-7063
S-7063S Qty 2

1/2

200RB5T4M Qty 2

AMG-24/50-60 Qty 2

AMI1TT4 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

5/8

200RB5T5M Qty 2

AMG-24/50-60 Qty 2

AMI1TT5 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

1/2

200RB6T4M Qty 2
200RB6T5M Qty 2
200RB6T5M Qty 2

AMG-24/50-60 Qty 2
AMG-24/50-60 Qty 2
AMG-24/50-60 Qty 2

AMI1TT5 Qty 2
AMI1TT5 Qty 2
AMI1TT5 Qty 2

P502-8307S* Qty 2
P502-8307S* Qty 2
P502-8307S* Qty 2

S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2

5/8
5/8

13

Typical wiring schematic


38ARZ 400V

14

Typical wiring schematic


38ARD 400V

15

Typical wiring schematic


38ARD ( Cont. )

Component Arrangement
Control Box

16

Typical wiring schematic


38ARD-028 400V

17

Typical wiring schematic


38ARD-028 400V ( Cont. )

Component Arrangement
Control Box

18

40RM007-034
6-25 Nominal Tons 50 Hz

Model number nomenclature - 40RM

4 0 R M - 0 1 6 S D

40RM

Commercial Packaged
Air Handler

Cooling Coil
-

B 5

E D

Factory-Installed Options

ED

Painted, Standard Motor and


Standard Drive

FD

Painted, Standard Motor and


Medium-Static Drive (Not available
for 016-028 50 Hz units)

RD

Painted, Alternate Motor and


Medium-Static Drive (Available for
50 Hz sizes 016,024,028 only)

WD

Painted, Alternate Motor and


High-Static Drive

Direct Expansion

Nominal Capacity
007
6 (21)
008
7-1/2 (26)
012
10 (35)
014
12-1/2 (43)

Tons (kW)
016
15 (52)
024
20 (70)
028
25 (87)
034
30 (105)

S: SAMCO
D: Double Skin
Expansion Device

B
Thermostatic Expansion Valves (40RM )

Voltage Designation (V-Ph-Hz)


8
9

230-3-50
400-3-50

Revision Number
0
Original Model

Packaging
1
Standard Domestic
3
Export

Quality Assurance

19

Physical data
40RM
UNIT 40RM
007SD
008SD
012SD
014SD
016SD
024SD
028SD
034SD
NOMINAL CAPACITY (Tons)
6

71/2
10

121/2
15

20

25

30

OPERATING WEIGHT (lb)

Base Unit (Double skin) with TXV

448

452

472

804

819

824

1188

1198

Plenum
97

97

97

140

140

140

180

180

FANS

Qty...Diam. (in.)

1...15

1...15

1...15

2...15

2...15

2...15

2...18

2...18

Nominal Airflow (cfm)


2400

3000

4000

5000

6000

8000

10,000
12,000
Airflow Range (cfm)
1800-3000
2250-3750
3000-5000
3750-6250
4500-7500
6000-10,000 7500-12,500 9000-15,000
Nominal Motor Hp (Standard Motor)*

230-3-50, 400-3-50
2.4
2.4
2.9
2.9
2.9
5.0
7.5
10.0
Motor Speed (rpm)

230-3-50, 400-3-50
1425

REFRIGERANT
Operating charge (lb)
(approx per circuit)

DIRECT-EXPANSION COIL

Max Working Pressure (psig)


Face Area (sq ft)
No. of Splits
Split Type...Percentage
No. of Circuits per Split
Rows...Fins/in.

6.67
1

12

3...15

PIPING CONNECTIONS

Quantity...Size (in.)

DX Coil - Suction (ODF)

DX Coil - Liquid Refrigerant (ODF)

1...11/8
1...11/8
1...5/8

3.0

3.0

8.33
1

15

3...15

1.5/1.5

2...11/8

4.5/4.5

2...11/8

2...11/8

2...11/8
2...5/8

2...13/8

5.0/5.0

29.83
2

18

3...15

2...13/8

1...11/4 ODM/1 IDF


Washable
4...16 x 24 x 1

LEGEND
DX - Direct Expansion
TXV - Thermostatic Expansion Valve
*Refer to alternate Fan Motor Data table, page 49, for alternate motor data.
Units are shipped without refrigerant charge.

20

3.5/3.5

Enhanced Copper Tubes, Aluminum Sine-Wave Fins


435

10.0
13.25
17.67
19.88
24.86
2

Face...50/50
9

12

13

15

3...17

3...15

3...15

3...17

3...15

Condensate (PVC)
FILTERS
Quantity...Size (in.)
Access Location

R-22

2.5/2.5

2.0/2.0

Factory Supplied
4...16 x 20 x 1
4...16 x 24 x 1
Front

4...20 x 24 x 1

4...20 x 25 x 1

Dimensions

40RM007SD-012SD
UNIT

40RM007SD
40RM008SD
40RM012SD

UNIT WEIGHT
lb (kg)
448 (203)
452 (205)
472 (214)

All the above mentioned weights


are for double skin units.

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [
millimeters.
2.

] are in

Direction of airow .

3. Recommended clearance:
Rear: 39(76.2 mm) (28-69[762 mm]
with electric heat accessory)
Front: 28-69 (762 mm)
Right side: 28-69 (762 mm)
Left Side: 28-69 (762 mm)
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied and
field installed.

21

Dimensions (cont)

40RM014SD-024SD

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [ ] are in
millimeters.
2.
Direction of airflow.
UNIT

3. Recommended clearance:
Rear: 39 (76.2 mm) (28-69
[762 mm] with electric heat
accessory)
Front: 28-69 (762 mm)
Right side: 28-69 (762 mm)
Left Side: 28-69 (762 mm)
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT
40RM014SD
40RM016SD
40RM024SD

All the weights men


tioned in the table
are for double skin
units.

22

UNITWEIGHT
lb (kg)
804 (364)
819 (371)
824 (373)

Dimensions (cont)

40RM028SD,034SD

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [ ] are in
millimeters.
2.
Direction of airflow.
3. Recommended clearance:
Rear: 39 (76.2 mm)
Front: 28-69 (762 mm)
Right side: 28-69 (762 mm)
Left Side: 28-69 (762 mm)
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT
40RM028SD
40RM034SD

UNIT WEIGHT
lb (kg)
1188 (538)
1198 (542)

All the above mentioned weights are for


double skin units.

23

OVERHEAD SUSPENSION ACCESSORY


UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTE: Dimensions in [

24

] are millimeters.

FAN PERFORMANCE DATA 0.0-1.2 in. wg ESP 50 HZ, ENGLISH

Rpm

Bhp

Rpm

Bhp

EXTERNAL STATIC PRESSURE (in. wg)


0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp

1,800
2,100
2,400
2,700
3,000

320
373
427
480
533

0.22
0.31
0.42
0.54
0.69

442
483
526
570
616

0.32
0.42
0.53
0.67
0.82

534
569
606
646
687

0.42
0.53
0.64
0.78
0.94

611
642
676
712
750

0.52
0.63
0.75
0.89
1.05

678
708
739
773
808

0.61
0.73
0.86
1.00
1.16

739
767
796
828
862

2,250
2,600
3,000
3,400
3,750

359
415
478
542
598

0.32
0.45
0.62
0.82
1.03

472
516
569
624
673

0.44
0.57
0.75
0.95
1.17

560
599
645
695
740

0.55
0.68
0.86
1.08
1.29

634
669
712
758
800

0.65
0.79
0.98
1.20
1.42

700
732
773
815
855

0.75
0.90
1.09
1.31
1.60

40RM
012

3,000
3,500
4,000
4,500
5,000

444
518
592
666
740

0.58
0.82
1.11
1.44
1.83

541
604
669
735
803

0.71
0.95
1.25
1.59
1.98

621
677
736
797
861

0.83
1.08
1.38
1.72
2.12

691
742
797
854
914

0.94
1.20
1.51
1.86
2.26

753
801
853
907
964

40RM
014

3,750
4,300
5,000
5,700
6,250

363
416
484
552
605

0.37
0.53
0.81
1.17
1.51

475
517
573
631
678

0.58
0.78
1.08
1.47
1.83

566
601
650
702
744

0.80
1.02
1.35
1.76
2.15

645
676
719
766
805

1.02
1.26
1.62
2.06
2.47

40RM
016

4,500
5,300
6,000
6,800
7,500

391
460
521
590
651

0.51
0.80
1.13
1.60
2.10

495
551
602
663
718

0.75
1.08
1.43
1.93
2.45

581
629
675
730
779

1.00
1.35
1.73
2.26
2.81

657
700
741
791
837

40RM
024

6,000
7,000
8,000
9,000
10,000

503
586
670
754
838

1.07
1.64
2.37
3.28
4.39

587
660
735
812
891

1.37
1.98
2.74
3.69
4.83

661
726
795
867
941

1.67
2.31
3.12
4.09
5.27

40RM
028

7,500
8,750
10,000
11,250
12,500

412
481
549
618
687

1.15
1.76
2.55
3.52
4.71

492
550
610
672
735

1.53
2.17
2.99
4.00
5.22

568
616
669
725
783

40RM
034

9,000
10,500
12,000
13,500
15,000

471
550
628
707
785

1.78
2.72
3.93
5.44
7.27

539
608
679
752
826

2.17
3.15
4.40
5.94
7.81

604
665
730
797
867

UNIT

40RM
007

40RM
008

AIRFLOW
(Cfm)

0.0

0.2

1.0
Rpm

1.2
Bhp

Rpm

Bhp

0.70
0.82
0.96
1.11
1.28

795
821
849
880
912

0.80
0.92
1.06
1.21
1.39

759
790
828
869
906

0.86
1.01
1.20
1.43
1.66

814
843
879
918
954

0.96
1.11
1.32
1.55
1.78

1.05
1.32
1.63
1.99
2.39

809
855
904
956
1010

1.17
1.44
1.75
2.12
2.53

862
906
953
1003
1055

1.28
1.56
1.88
2.24
2.66

715
743
782
826
862

1.24
1.50
1.89
2.36
2.79

779
805
841
881
915

1.47
1.74
2.16
2.66
3.11

839
862
896
934
966

1.69
1.99
2.44
2.96
3.43

1.25
1.63
2.04
2.59
3.16

725
764
801
847
890

1.50
1.91
2.34
2.92
3.52

787
823
858
901
941

1.76
2.20
2.65
3.26
3.88

845
878
911
951
990

2.02
2.48
2.96
3.60
4.24

727
787
851
918
988

1.97
2.65
3.49
4.50
5.70

789
844
904
967
1034

2.28
2.99
3.86
4.90
6.14

846
898
954
1014
1077

2.59
3.33
4.23
5.31
6.85

900
948
1001
1059
1120

2.90
3.67
4.61
5.72
7.02

2.00
2.66
3.50
4.53
5.78

640
680
726
777
830

2.56
3.22
4.07
5.12
6.38

710
742
782
827
876

3.22
3.86
4.70
5.76
7.04

776
802
836
876
922

3.98
4.58
5.40
6.45
7.74

840
860
889
925
966

4.83
5.38
6.17
7.21
8.49

2.63
3.64
4.92
6.49
8.39

667
720
779
841
907

3.17
4.18
5.48
7.08
9.01

728
774
827
885
947

3.78
4.79
6.09
7.71
9.66

788
827
874
928
986

4.46
5.45
6.76
8.38
10.35

845
878
921
970
1024

5.22
6.18
7.47
9.10
11.07

See Legend and Notes on page 47.

25

Performance data (cont)


FAN PERFORMANCE DATA 1.4-2.4 in. wg ESP 50 Hz, ENGLISH

Rpm

Bhp

Rpm

EXTERNAL STATIC PRESSURE (in. wg)


1.8
2.0
2.2
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp

40RM
007

1,800
2,100
2,400
2,700
3,000

847
872
899
928
959

0.89
1.02
1.16
1.32
1.49

896
920
946
974
1004

0.98
1.11
1.26
1.42
1.60

942
965
990
1018
1046

1.07
1.21
1.36
1.52
1.71

986
1008
1033
1059
1087

1.16
1.30
1.46
1.63
1.81

1027
1050
1073
1099
1126

40RM
008

2,250
2,600
3,000
3,400
3,750

865
893
928
965
1000

1.06
1.22
1.43
1.66
1.90

913
940
973
1010
1043

1.16
1.33
1.54
1.78
2.02

958
984
1017
1052
1084

1.27
1.43
1.65
1.89
2.13

1001
1027
1058
1092
1124

1.37
1.54
1.76
2.00
2.25

40RM
012

3,000
3,500
4,000
4,500
5,000

911
953
999
1047
1097

1.39
1.67
2.00
2.37
2.79

958
998
1042
1089
1138

1.50
1.79
2.12
2.50
2.92

1002
1041
1084
1129
1177

1.61
1.90
2.24
2.62
3.05

1044
1082
1124
1168

40RM
014

3,750
4,300
5,000
5,700
6,250

894
916
948
984
1014

1.91
2.23
2.71
3.25
3.75

947
967
997
1031
1060

2.14
2.48
2.98
3.55
4.07

996
1016
1044
1076
1104

2.37
2.73
3.26
3.86
4.39

40RM
016

4,500
5,300
6,000
6,800
7,500

899
930
961
999
1036

2.29
2.78
3.28
3.94
4.60

951
980
1009
1045
1080

2.56
3.08
3.60
4.28
4.97

999
1027
1055
1089
1123

40RM
024

6,000
7,000
8,000
9,000
10,000

950
996
1047
1102
1160

3.21
4.02
4.99
6.13
7.46

999
1042
1091
1143
1200

3.53
4.37
5.37
6.54
7.91

40RM
028

7,500
8,750
10,000
11,250
12,500

903
917
941
972
1010

5.79
6.26
7.01
8.02
9.29

963
972
991
1019
1053

40RM
034

9,000
10,500
12,000
13,500
15,000

901
928
966
1011
1062

6.07
6.98
8.24
9.86
11.84

UNIT

AIRFLOW
(Cfm)

1.4

See Legend and Notes on page 47.

26

1.6

2.4
Rpm

Bhp

1.25
1.40
1.55
1.73
1.92

1042
1067
1098
1131
1162

1.47
1.65
1.87
2.12
2.37

1.72
2.02
2.36
2.74

1084
1122
1162

1.83
2.13
2.48

1123
1159
1199

1.94
2.25
2.60

1044
1062
1089
1120
1147

2.60
2.98
3.53
4.16
4.71

1089
1107
1133
1162
1188

2.83
3.24
3.81
4.46
5.03

2.84
3.38
3.92
4.63
5.34

1046
1072
1098
1132
1164

3.12
3.68
4.24
4.98
5.71

1091
1116
1141
1173

3.41
3.99
4.57
5.33

1133
1157
1181

3.70
4.30
4.91

1045
1086
1133
1183

3.85
4.72
5.75
6.96

1089
1129
1173

4.17
5.07
6.13

1131
1169

4.50
5.43

1172

4.83

6.83
7.22
7.91
8.89
10.15

1021
1025
1040
1064
1095

7.98
8.26
8.89
9.83
11.05

1078
1078
1089

9.21
9.38
9.93

955
978
1011
1052

6.98
7.84
9.07
10.67

1008
1026
1055
1092

7.98
8.76
9.95
11.52

1060
1073
1098

9.05
9.74
10.88

Bhp ESP -

FACTOR Y-SUPPLIED FILTER PRESSURE DROP


- ENGLISH

LEGEND
Brake Horsepower Input to Fan
External Static Pressure

Bold indicates field supplied drive is required.

Plain type indicates standard motor and standard drive.

Underline indicates a different motor and drive combination other than

the standard motor and standard drive combination is required. Refer to

fan motor and drive tables, pages 57-59, to complete selection.


NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 1-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. For 50 Hz units, the medium- static drive and standard motor
combination is not available for 016-028 sizes. Use alternate
motor if medium-static drive is required for these sizes.

40RM
007

AIRFLOW
(Cfm)
1,800
2,400
3,000

PRESSURE DROP
(in. wg)
0.05
0.08
0.11

40RM
008

2,250
3,000
3,750

0.07
0.11
0.15

40RM
012

3,000
4,000
5,000

0.11
0.17
0.23

40RM
014

3,750
5,000
6,250

0.06
0.10
0.13

40RM
016

4,500
6,000
7,500

0.08
0.12
0.17

6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

UNIT

40RM
024
40RM
028
40RM
034

ACCESSORY PLENUM AIR THROW DATA ENGLISH


(Ft)

NOTE: Throw distances shown are for 75 fpm terminal velocity. Use
the following multipliers to determine throw values for other terminal
velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150

THROW FACTOR
X 1.50
X 0.75
X 0.50

VANE DEFLECTION
Straight
2112
45

UNIT

AIRFLOW
(Cfm)

40RM
007

2,400

39

33

24

40RM
008

3,000

45

38

28

40RM
012

4,000

55

46

33

40RM
014

5,000

45

38

28

40RM
016

6,000

50

43

31

40RM
024

8,000

60

51

37

40RM
028

10,000

76

65

47

40RM
034

12,000

85

72

52

27

Electrical data

STANDARD MOTORS
FAN MOTOR
UNIT

V*-PH-Hz

VOLTAGE
LIMITS

40RM
007
40RM
008

230-3-50
400-3-50
230-3-50
400-3-50

40RM
012

POWER SUPPLY
Minimum
Circuit
MOCP
Amps

Hp (kW)

FLA

207-253
360-440
207-253
360-440

2.4
2.4
2.4
2.4

(1.79)
(1.79)
(1.79)
(1.79)

5.2
2.6
5.2
2.6

6.5
3.3
6.5
3.3

15
15
15
15

230-3-50
400-3-50

207-253
360-440

2.9 (2.16)
2.9 (2.16)

7.5
3.4

9.4
4.3

15
15

40RM
014

230-3-50
400-3-50

207-253
360-440

2.9 (2.16)
2.9 (2.16)

7.5
3.4

9.4
4.3

15
15

40RM
016

230-3-50
400-3-50

207-253
360-440

2.9 (2.16)
2.9 (2.16)

7.5
3.4

9.4
4.3

15
15

40RM
024

230-3-50
400-3-50

207-253
360-440

5.0 (3.73)
5.0 (3.73)

15.2
7.6

19.0
9.5

30
15

40RM
028

230-3-50
400-3-50

207-253
360-440

7.5 (5.59)
7.5 (5.59)

22.8
11.4

28.5
14.3

50
25

40RM
034

230-3-50
400-3-50

207-253
360-440

10.0 (7.46)
10.0 (7.46)

32.2
16.1

40.3
20.1

70
30

ALTERNATE MOTORS
FAN MOTOR

POWER SUPPLY
Minimum
Circuit
MOCP
Amps

UNIT

V*-PH-Hz

VOLTAGE
LIMITS

Hp (kW)

FLA

40RM
007

230-3-50
400-3-50

207-253
360-440

2.4 (1.79)
2.4 (1.79)

5.2
2.6

6.5
3.3

15
15

40RM
008

230-3-50
400-3-50

207-253
360-440

2.9 (2.16)
2.9 (2.16)

7.5
3.4

9.4
4.3

15
15

40RM
012

230-3-50
400-3-50

207-253
360-440

5.0 (3.73)
5.0 (3.73)

15.2
7.6

19.0
9.5

30
15

40RM
014

230-3-50
400-3-50

207-253
360-440

5.0 (3.73)
5.0 (3.73)

15.2
7.6

19.0
9.5

30
15

40RM
016

230-3-50
400-3-50

207-253
360-440

5.0 (3.73)
5.0 (3.73)

15.2
7.6

19.0
9.5

30
15

40RM
024

230-3-50
400-3-50

207-253
360-440

7.5 (5.59)
7.5 (5.59)

22.8
11.4

28.5
14.3

50
25

40RM
028

230-3-50
400-3-50

207-253
360-440

10.0 (7.46)
10.0 (7.46)

32.2
16.1

40.3
20.1

60
30

LEGEND
FLA
Full Load Amps
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages
shown. Voltages should not exceed the limits shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance
with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Labo
ratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 400-3-50.

AB = 393 v

BC = 403 v

AC = 396 v

393 + 403 + 396


Average Voltage =
3
1192
=
3
= 397

Determine maximum deviation from average voltage.


(AB) 397 393 = 4 v
(BC) 403 397 = 6 v
(AC) 397 396 = 1 v
Maximum deviation is 6 v.
Determine percent voltage imbalance.
6
397

% Voltage Imbalance = 100 x


= 1.5%

This amount of phase imbalance is satisfactory because it is below the maxi


mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con
tact your local electric utility company immediately.

28

Typical piping and wiring

VERTICAL INST ALLA TION - 40RM (TYPICAL)

NEC TXV -

LEGEND
National Electrical Code
Thermostatic Expansion Valve
Piping

*Field supplied.
Double riser may be required. Consult condensing unit product data catalog for
details.

29

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended
for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
migration to the compressor.
5. Internal factory-supplied TXVs not shown.

HORIZONT AL INST ALLA TION -

LEGEND
NEC - National Electrical Code
TXV - Thermostatic Expansion Valve
*Accessory item.
Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniqes. Refer
to Carrier System Design Manual for details.

40RM (TYPICAL)

2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a spe
cific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

30

CONTROL WIRING SCHEMA TIC -

TYPICAL

EQUIP
GND
HC
HTR
IFC
IFM
TB

LEGEND
Equipment
Ground
Heater Contactor
Heater Element
Indoor Fan Contactor
Indoor Fan Motor
Terminal Block
Factory Wiring
Field Wiring

Application data

Operating limits
Maximum fan speed . . . . . . . . . . . . . . . . 1200 rpm (20 r/s)
40RM007-024
40RM028,034 . . . . . . . . . . . . . . . . 1100 rpm (18.3 r/s)

General
Select equipment to match or to be slightly lessthan peak
load. This providesbetter humidity control, lessunit cycling,
and lesspart-load operation. Equipment should be selected
to perform at no lessthan 300 cfm/ton (40 L/s per kW).

The air handler fan must always be operating when the


condensingunit is operating.
Ductwork should be sized according to unit size, not
building load. For larger units with two fans, a split duct
transition is recommendedat the fan outlets, but a plenum
can be usedwith slight reduction in external static pressure
capability.
For variable air volume (VAV) systems with supply-to
return air recycling, usethe equipment room as a return air
plenum.

FACTOR Y-INST ALLED NOZZLE AND DISTRIBUTOR DATA


UNIT

40RM007
40RM008
40RM012
40RM014
40RM016
40RM024
40RM028
40RM034

TXV
Qty...Part No.*
1...XVE-5
1...SVE-8
2...XVE-4
2...XVE-5
2...XVE-8
2...XVE-10
2...SVE-15
2...SVE-15

*Sporlan Valve Co. part numbers shown.

31

DISTRIBUTOR
Qty...Part No.*
1...1116
1...1126
2...1115
2...1115
2...1116
2...1116
2...1126
2...1126

FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...1/4
15...1/4
9...1/4
9...1/4
12...1/4
13...1/4
15...1/4
18...1/4

NOZZLE
Qty...Part No.
1...E5
1...C6
2...E4
2...E5
2...E6
2...E8
2...C10
2...C12

Application data
FAN MOTOR DATA -ENGLISH
STANDARD MOTOR (230-3-50 and 400-3-50)
UNIT
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

1425
2.4
56Y

1425
2.4
56Y

1425
2.9
56Y

1425
2.9
56Y

1425
2.9
56Y

5/8

5/8

7/8

7/8

7/8

1425
5.0
184T
11/8

1425
7.5
S213T
13/8

1425
10.0
S215T
13/8

ALTERNATE MOTOR (230-3-50 and 400-3-50)


UNIT
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
NEMA -

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

1425
2.4
56Y

1425
2.9
56Y

1425
5.0
S184T

7/8

7/8

7/8

1425
5.0
S184T
11/8

1425
5.0
S184T
11/8

1425
7.5
S213T
13/8

1425
10.0
S215T
13/8

National Electrical Manufacturers Association (U.S.A.)

STANDARD DRIVE DATA, 5 0 Hz -

UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

ENGLISH

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

2.4-3.4

2.8-3.8

3.4-4.4

3.4-4.4

3.4-4.4

4.3-5.3

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

8.0
1
1-A
39.3

8.0
1
1-A
39.3

8.0
1
1-A
40.3

9.0
1 7/16
1-A
42.3

9.0
1 7/16
1-A
42.3

8.6
1 7/16
1-B
41.8

11.0
1 15/16
2-B
43.8

11.0
1 15/16
2-B
43.8

517
428-606
1200

588
499-677
1200

695
606-784
1200

618
538-697
1200

618
538-697
1200

795
713-878
1200

622
557-687
1100

622
557-687
1100

17.8

17.8

17.8

15.9

15.9

13.8

10.8

10.8

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32

9.12
10.99

6.67
9.43

6.67
9.43

32

MEDIUM-ST ATIC DRIVE DATA, 5 0 Hz -

UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

3.4-4.4

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.0-5.0

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

3.0

2.5

3.0

3.0

8.0
1
1-A
40.3

7.0
1
1-A
41.3

6.0
1
1-A
37.3

7.5
1 7/16
1-A
39.3

7.9
1 7/16
1-B
39.8

7.0
1 7/16
2-A
36.8

9.4
1 15/16
2-B
39.8

9.4
1 15/16
2-B
39.8

695
606-784
1200

794
692-896
1200

926
808-1045
1200

741
646-836
1200

756
667-848
1200

916
814-1018
1200

728
652-803
1100

728
652-803
1100

17.8

20.4

23.7

19.0

15.1

20.4

12.6

12.6

10.44
12.32

10.44
12.32

10.44
12.32

10.44
12.32

9.16
10.99

9.16
10.99

6.67
9.43

6.67
9.43

HIGH-ST ATIC DRIVE DATA, 5 0 Hz -

UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

ENGLISH

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

3.4-4.4

3.4-4.4

4.0-5.0

3.4-4.4

4.0-5.0

4.0-5.0

4.3-5.3

4.3-5.3

2.5

2.5

3.0

2.5

3.0

3.0

3.0

3.0

6.0
1
1-A
37.3

5.5
1
1-A
37.3

5.5
1
1-A
36.3

6.0
1 7/16
2-A
36.3

7.0
1 7/16
2-A
39.3

6.4
1 7/16
2-A
34.3

8.0
1 15/16
2-B
36.8

8.6
1 15/16
2-B
37.8

926
808
1045
1200

1010
881
1140
1200

1166
1036
1200*
1200

926
808
1045
1200

916
814
1018
1200

1002
891
1113
1200

855
766
944
1100

795
713
878
1100

23.7

25.9

21.6

23.7

17.0

18.5

14.8

13.8

10.44
12.32

10.44
12.32

916
10.99

9.16
10.99

9.16
10.99

8.16
10.02

6.67
9.43

6.67
9.43

*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.

33

ENGLISH

Guide Specifications 38ARZ007-012


Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 6 to 10 Tons, Nominal
Carrier Model Numbers: 38ARZ, Sizes 007-012
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall consist of a reciprocating or scroll airconditioning compressor assembly, an air-cooled
coil, propeller- type condenser fans, and a control
box. Unit shall discharge supply air upward as
shown on contract drawings. Unit shall be used in
a refrigeration circuit matched with a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 360-2000.
B. Unit construction shall comply with
ANSI/ASHRAE 15 safety code latest revision and
comply with NEC.
C. Unit shall be constructed in accordance with UL
1995 standard.
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(scribed specimen).
E. Air-cooled condenser coils for (38ARZ) shall be
leak tested at 200 psig, and pressure tested at 428
psig.
F. Unit shall be manufactured in a facility
registered to ISO 9001:2000 manufacturing quality
standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturers recommendations.
1.04 WARRANTY (FOR INCLUSION
SPECIFYING ENGINEER.)

BY

Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-22), and
special features required prior to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted
baked enamel finish.

2. A heavy-gage roll-formed perimeter base rail


with forklift slots and lifting holes shall be
provided to facilitate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller
type, discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC-coated steel wire safety
guards.
4. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
1. Compressor shall be of the hermetic scroll type
2. Compressor shall be mounted on rubber
grommets.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressor shall be equipped with internal high
discharge temperature protection (38ARZ007 and
012 only).
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include
liquid line service valve, suction line service valve,
a full charge of compressor oil, and a holding
charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped
with automatic reset (after resetting first at
thermostat), shall include:
a. High discharge pressure cutout.
b. Low pressure cutout.
c. High discharge temperature cutout (38ARZ008
only).
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of

34

_____ F. The power consumption at full load shall


not exceed _____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and
_____ F dry bulb, and air entering the condensing
unit at _____F.
3. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
_____ v, 3-ph, 50 Hz. The unit shall be capable of
satisfactory operation within voltage limits of ____
v to _____ v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v
transformer for unit control.
J. Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a field-installed accessory. This lowambient control shall regulate speed of the
condenser-fan motors in response to the saturated
condensing temperature of the unit. The control
shall maintain correct condensing pressure at
outdoor temperatures down to 20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal

35

environments. Coating shall be applied to the


aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide
protection
in
moderate
coastal
environments.
4. Thermostat Controls:
a. Programmable multi-stage thermostat shall have
7-day clock, holiday scheduling, large backlit
display, remote sensor capability, and Title 24
compliance.
b. Commercial Electronic Thermostat shall have 7day timeclock, auto-changeover, multi-stage
capability, and large LCD (liquid crystal display)
temperature display.
c. Carrier PremierLink Controller:
This control will function with CCN (Carrier
Comfort Network) and ComfortVIEW
software. It shall also be compatible with
ComfortLink controllers. It shall be ASHRAE
62-99 compliant and Internet ready. It shall accept
a CO2 sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready. The
communication rate must be 38.4K or faster. It
shall include an integrated economizer controller.

Guide specifications 38ARD014-028


Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 121/2 to 20 Tons, Nominal
Carrier Model Number: 38ARD, Sizes 014-024
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall have 2 independent refrigeration
circuits. Unit shall consist of dual scroll
compressors, an aircooled coil, propeller-type
condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract
drawings. Unit shall be used in a refrigeration
circuit matched with a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 360-2000, and shall be certified and listed
in the latest ARI directory.
B. Unit construction shall comply with
ANSI/ASHRAE safety code, latest revision, and
comply with NEC.
C. Unit shall be constructed in accordance with UL
1995 standard and shall carry the UL and UL,
Canada label.
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(scribed specimen).
E. Air-cooled condenser coils shall be leak tested
at 150 psig, and pressure tested at 480 psig.
F. Unit shall be manufactured in a facility
registered to ISO 9001:2000 manufacturing quality
standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturers recommendations.
1.04 WARRANTY (FOR INCLUSION BY
SPECIFYING ENGINEER.)
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-22), and
special features required prior to field start-up.
B. Unit Cabinet:
Unit cabinet shall be constructed of G-90
galvanized steel, bonderized and coated with a
prepainted baked enamel finish.
C. Fans:
1. Condenser fans shall be direct driven,
propellertype, discharging air vertically upward.
2. Fan blades shall be balanced.

3. Condenser fan discharge openings shall be


equipped with PVC-coated steel wire safety
guards.
4. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
1. Compressors shall be of the hermetic scroll type.
2. Compressors shall be mounted on rubber
grommets.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressors shall be equipped with internal
high discharge temperature protection (38ARD016
and 024 only).
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include high
side pressure relief device, liquid line service
valve, suction line service valve, a full charge of
compressor oil, and a holding charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
c. Recycle time delay of five minutes to prevent
compressor short cycling.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat):
a. High discharge pressure cutout.
b. Loss-of-charge cutout.
c. Condenser fan motors to be protected against
overload condition by internal overloads.
Manual reset at the unit:
Electrical overload protection through the use of
define-purpose contactors and calibrated, ambient
compensated, magnetic trip circuit breakers.
Circuit breakers shall open all three phases in the
event of an overload in any one of the phases or a
single phase condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of
_____ F. The power consumption at full load shall
not exceed _____ kW.

36

2. The combination of the condensing unit and the


evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and _____ F
dry bulb, and air entering the condensing unit at
_____ F.
3. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
_____ v, 3-ph, 50 Hz. The unit shall be capable of
satisfactory operation within voltage limits of
_____ v to _____ v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v
transformer for unit control.
J. Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a factory-installed option or as a fieldinstalled accessory. This low-ambient control shall
regulate speed of the condenser-fan motors in
response to the saturated condensing temperature
of the unit. The control shall maintain correct
condensing pressure at outdoor temperatures down
to 20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal

37

environments. Coating shall be applied to the


aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide
protection
in
moderate
coastal
environments.
4. Thermostat Controls:
a. Programmable multi-stage thermostat with 7-day
clock, holiday scheduling, large backlit display,
remote sensor capability, and Title 24 compliance.
b. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multistage capability,
and large LCD (liquid crystal display) temperature
display.
c. Carrier PremierLink Controller:
This control will function with Carrier Comfort
Network (CCN) and ComfortVIEW software.
It shall also be compatible with ComfortLink
controllers. It shall be ASHRAE 62-99 compliant
and Internet ready. It shall accept a CO2 sensor in
the conditioned space and be Demand Control
Ventilation (DCV) ready. The communication rate
must be 38.4K or faster. It shall include an
integrated
economizer
controller.

Guide specifications 40RM

Commercial Packaged Air-Handling Unit


HVAC Guide Specifications
SizeRange: 2,400 to 12,000 CFM (1150 to 5650 L/s),
Nominal Airflow 6 t o 3 0 Tons (21 to
105 kW), Nominal Cooling
Carrier Model Numbers: 40RM (Direct-Expansion Coil)
Part 1 - GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commer
cial split systems.Unit shall have a multiposition de
sign and shall be capable of horizontal or vertical
installation on a floor or in a ceiling, with or without
ductwork. (Only vertical units are to be applied with
out ductwork.)
B. Unit with direct-expansioncoil shall be used in a re
frigerant circuit with a matching air-cooled con
densing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed & tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigera
tion (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL
(U.S.A.) and ETL, Canada, standardsand shall carry
the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with
NFPA-90A (U.S.A.)requirements for flame spread
and smoke generation.

D. Unit shall be manufactured in a facility registered to


the ISO 9002 manufacturing quality standard.
E. Direct-expansionand chilled water coils shallbe burst
and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer's
recommendations.
Par t 2 - Products
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit
that can be used in a suspended horizontal configu
ration or a vertical configuration. Unit shall consistof
forward-curved belt-driven centrifugal fan(s), motor &
drive assembly,prewired fan motor contactor, factory
installedrefrigerant metering devices(direct-expansion
coil units), cooling coil, 1-in. (25.4-mm) washable air
filters, and condensate drain pans for vertical or hori
zontal configurations.

A. Base Unit (Painted):


1. Cabinetshall be constructed of zinc coated steel
and polyester powder painted to protect them
from corrosion in the harsh Middle Eastern climate
and also to increase the colour life in high ultra
violet (UV) radiation regions.
2. Cabinet panels shall be fully insulated with 1/2 in.
(12.7-mm) fire-retardant material.
3. Unit shall contain PVC condensate drain pans for
both vertical and horizontal applications. Drain
pans shallhave connectionson right and left sides
of unit to facilitate field connection. Drain pans
shall have the ability to be sloped toward the right
or left side of the unit to prevent standing water
from accumulatingin pans.
4. Unit shall have factory-supplied 1-in. (25.4 mm)
washable-type filters installed upstream from the
cooling coil. Filter access shall be from the front
of the unit.
B. Coils:
Coils shall consist of 3 rows (40RM), of
coppertubes with sine-wave aluminum fins bonded
to the tubes by mechanical expansion. Suction and
liquid line connectionsor supply and discharge con
nections shallbe made on the same side of the coil.
1. Direct-expansioncoilsshallfeaturefactory-installed
thermostatic expansion valves (TXVs) for refrig
erant control. The TXVs shall be capable of ex
ternal adjustment. Direct-expansion heat pump
coils shall have a factory-installedbypassline and
check valve assemblyaround the TXVs to allow
liquid flow from the coil to the outdoor unit during
the heating mode. Coil tubing shall be internally
rifled to maximize heat transfer.
C. Operating Characteristics:
Unit shall be capable of providing
cfm (L/s)
airflow at an external static pressureof
in. wg
(kPag).
D. Motor:
Fan motor of the size and electrical characteristics
specified on the equipment scheduleshall be factory
supplied and installed.
Motors rated at 1.3 through 3.7 hp (0.97 through
2.76 kW) shall have internal thermal overload pro
tection. Motors rated at 5, 7 1/2 , and 10 hp (3.73,
5.60, and 7.46 kW) shall be protected by a circuit
breaker.

38

E. Factory-InstalledOptions:
1. Alternate Motor and Drive:
An alternate motor and/or medium- or high-static
drive shall be available to meet the airflow and
external static pressure requirements specified
on the equipment schedule.
F. Field-InstalledAccessories (ordered from NAO):
1. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt,
3-phase, 60 Hz; and 240, 400-volt, 3 phase,
50 Hz power supply shallbe factory-suppliedfor
field installationasshown on the equipmentdraw
ings. Electricheat assemblyshallbe ETL (U.S.A.)
and ETL, Canada, agency approved, and shall
have single-point power wiring. Heater assem
bly shallincludecontactorswith 24-V coils, power
wiring, 24-v control wiring terminal blocks, and
a hinged accesspanel. Electric heaters shall not
be used with air discharge plenum.
2. Air Discharge Plenum:
Plenum shall be factory supplied to provide free
blow air distribution for vertical floor-mounted
units. A grille with moveable vanes for hori
zontal or vertical airflow adjustment shall be
included. Plenum shall be field-assembledand
field-installedon the unit's fan deck for blow-thru
air distribution. Plenum shall not be used with
electric heaters.
3. Return Air Grille:
Grille shall be factory supplied for field installa
tion on the unit's return air opening.
4. Unit Subbase:
Subbaseassemblyshall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for
correct condensate drain connection.
5. Economizer:
Economizerfor ventilation or ``free'' cooling shall
be factory provided for field installation on either
return air opening of air handler. For free cool
ing applications, economizershallbe compatible
with separate thermostat; economizer dampers
shall open when outdoor air enthalpy is suitable
for free cooling. Economizershall be compatible
with separate CO2 sensor accessory; economizer
dampersshall open when indoor CO2 level rises
abovepredetermined setpoint. Economizershall
include enthalpy control and damper actuator.

6. Thermostat Controls:
a. Debonair programmablemulti-stagethermo
statwith 7-dayclock, holiday scheduling,large
Thermoglow display, remote sensorcapa
bility, and Title 24 compliance.
b. TEMP System programmable communicat
ing multi-stage thermostat with fan switch,
time clock, LCD display,F/C capability,and
CCN compatiblity.
c. CommercialElectronicThermostatwith 7-day
time clock, auto-changeover, multi-stageca
pability, and large LCD temperature display.
d. Non-programmablethermostatwith fan switch
subbase.
7. Overhead SuspensionPackage:
Package shall include necessary brackets to
support units in a horizontal ceiling installation.
8. CO2 Sensor:
Sensorshallprovide the ability to signalthe econo
mizer to open when the spaceCO2 levelexceeds
the predetermined set point. Sensor shall have
the capability of being connected to Comfort
System relay pack or to economizer using field
supplied and -installed Honeywell dc adapter
no. Q769C1004.
9. CondensateDrain Trap:
Trap shall have transparent, serviceabledesign
for easycleaning. Kit shallinclude overflow shut
off switch and wiring harnessfor connection to
an alarm if desired.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

2011

38AR-02 PD 50HZ - for Kuwait use