Professional Documents
Culture Documents
This chapter discusses a number of useful control techniques that are not covered in previous chapters. The topics included are: Split-range control Cross-limiting control Floating control Techniques for increasing effective valve rangeability Time proportioning control
SPLIT-RANGE CONTROL
A common application for split-range control is when a temperature control loop must at times apply heat to a process and at other times must apply cooling. This is normally accomplished by using two valves, one called the heating valve, the other the cooling valve. In the usual installation, each valve operates through one-half of the controllers output range, applying the maximum heating or cooling at the extremes of the controllers output range. At the midpoint of the range, neither heating nor cooling is applied. Figure 16-1 shows a traditional installation using pneumatic instrumentation. The 315 psi controller output goes to both valves in parallel. From 39 psi (0 50%), the cooling valve strokes from open to closed. From 915 psi (50 -100%), the heating valve strokes from closed to open. If valve-spring ranges alone are used to achieve this schedule, then the heating valve is selected to be fail-closed and the cooling valve to be fail-open. Alternatively, valve positioners can be used, rather than relying on the valve-spring ranges to achieve the schedule. Not only will this provide more accurate and precise range splitting, but it will also make the overall design of the installation more flexible. For instance, if the application requires that both valves be fail closed and also operate in split-range fashion during normal operation, then one of the positioners can be reverse-acting, as shown in Figure 16-2.
CHAPTER 16 335
336 CHAPTER 16
Both Figures 16-1 and 16-2 are based on the traditional method of designing split-range applications and on the use of traditional hardware. Let us rethink both of these. First, consider the way the controller output signal is split. Many control engineers have never considered anything other than a 050 and 50100 split. But suppose the strength of the heating valves control effect is much greater than that of the cooling valve. For example, suppose the maximum flow rate through each valve is the same, but the temperature differential between the heating fluid and the process is much greater than the temperature differential between the cooling fluid and the process. In this case, the process gain when the controller output is in the heating valve range is much greater than when it is in the cooling valve range. If one-size-fits-all tuning is used, then the temperature controller will have to be tuned for the worst case, that is, for the temperature range when the process gain is the highest. In the cooling range, the control loop may be too sluggish. A preferred method for scheduling the valve operation would be to shift the split point toward the cooling side. For example, let the cooling valve operate from 0% (valve open) to 33% (valve closed) and the heating valve from 33% (valve closed) to 100% (valve open). This will reduce heating range process gain by 25% and increase the cooling range process gain by 50%. Some other split point may be chosen experimentally. The objective is for the process gains to be approximately the same for both the heating and cooling regime, and for transition between the heating and cooling regimes to be transparent to the control loop behavior. In general, the split can be made in the field, using one analog output and adjustments to the valves or positioners. However, it may be very difficult, if not impossible, to shift the split point to some arbitrary value as described above. With a digital processor (DCS or PLC), however, the split can be performed in software, for instance by the use of characterizer function blocks as shown in Figure 16-3. There are significant advantages to using two analog outputs and performing the split in the software. It is much easier to adjust in software than on field equipment. Also, by not adjusting the field equipment maintenance personnel can more easily replace valves and positioners without having to readjust for the split. There are undoubtedly other configurations which will achieve the same concept shown in Figure 16-3, depending upon the type of function blocks available in a particular processor and also upon whether or not valve positioners are used. The split could even be performed in fieldbus function blocks in the valve actuators, if a fieldbus communication architecture is used. One further point: Some control engineers prefer that there be a slight overlap in the valve operation, as shown in Figure 16-4. The advantages of an overlap are that it insures that there will not be a dead band between operation of the valves and that it provides an artificial live load on the control loop when the valves are operating near the closed position. The disadvantage is the cost of the additional utilities as the price being paid for improved controllability in the transition region.
CHAPTER 16 337
CROSS-LIMITING CONTROL
Cross-limiting control (often called lead-lag control) is a technique applied to large combustion units such as steam generators and process heaters. During steady operation, a nominal fuel-to-air ratio is maintained. This ratio can be manually set; more than likely, however, it will be set from a stack analyzer control system (see chapters 9 and 11). During transient con338 CHAPTER 16
ditions, the objective is to avoid a fuel-rich situation, which could be a safety hazard. Thus on an increase in firing demand, the air flow is increased first (air leads). When there has been a proven increase in air, the fuel rate is increased (fuel lags) to satisfy the air-to-fuel ratio control requirements. On a decrease in firing demand, the fuel is decreased first; when there has been a proven decrease in fuel, the air flow rate is decreased. The configuration shown in Figure 16-5 will accomplish this objective. The scaling of the components in the output of the O2 controller should be such that when its output is 50%, it is requesting a 1-to-1 nominal air-to-fuel ratio. Its allowable range of request should be limited. For instance, at 0% output, the required air-to-fuel ratio could be 80% of nominal; at 100% output, the ratio could be 120% of nominal.
FLOATING CONTROL
Floating control refers to a technique whereby the set point of a process controller is varied automatically in response to changes in demand on the control loop. The usual objective is energy savings. This technique is closely related to sliding pressure control for steam boilers. We will first illustrate the concept for pressure control of a distillation column, and then cite several additional candidate applications. Our objective is not to provide complete details for implementation, but to provide a sufficient number of examples so as to provoke thought as to how this concept can be utilized, possibly in completely different applications.
words, during times when the cooling water temperature is less than maximum, only a portion of the condensing capacity is being utilized. For many hydrocarbon feedstocks, it is economically advantageous to operate at the lowest possible pressure. At lower pressures, there is an increase in relative volatility of the components so that the material can be separated to the same product specifications with less energy input (see Ref. 16-1). One possible strategy would be to arbitrarily decide upon a nearly wide open valve position (say, 95%), then issue instructions to the operator to gradually lower the pressure controller set point when the controller output is running less than 95%, and gradually increase the set point tends to run more than 95%. The reasons for choosing a value less than 100% are that we want to have some valve movement available for short-term pressure control, and we also want to be able to detect when there is a need to increase the set point. If this strategy were dil-
340 CHAPTER 16
igently followed, we would be operating at all times at the lowest pressure consistent with available condensing capacity; hence, we would be operating at minimum utility usage. Rather than relying upon operator diligence, however, we can automate this strategy by employing another controller called a valve position controller. Its process variable is the output of the pressure controller; its output adjusts the set point of the pressure controller. The set point of the valve position controller is the desired long-term valve position, say 95%. The valve position controller should have integral-only control action to prevent passing proportional steps back to the pressure controller. It should also be tuned for very slow response so that, in the short term, the pressure controller reacts as if it had a constant set point. These requirements, an integral action controller and tuning for slow response, are common to all floating control applications. Figure 16-6 depicts a control loop configuration for floating pressure control.
Two other points should be made regarding floating pressure control for distillation. The technique will only have economic benefit if the product quality for all draw streams is maintained constant. If the composition of one stream, say the bottom product stream, is not controlled,
CHAPTER 16 341
then at reduced column pressure, the purity of that stream will merely increase with no savings in utilities. The other point is that if temperature measurements are used as indicators of composition, these measurements must be pressure compensated.
The choice of set point for the valve position controller (VPC) must be made judiciously. Since the pressure controller set point will be adjusted rather slowly, there must be enough room above the set point of the VPC to accommodate rapid increases in load on a particular process unit. For example, if the set point for the VPC is set at 70%, then the most demanding user would have an additional 30% valve travel to accommodate short term load increases. If a few of the users are more susceptible to large load increases than the others, then the demand signal from those users can be artificially biased, thus allowing a higher set point for the valve position controller. This concept can be extended to systems with multiple headers, where low pressure headers are provided by exhaust steam from a higher pressure header, plus supplemental steam from a pressure reducing station. The output of a reducing station pressure controller, along with the
342 CHAPTER 16
demand signal from other users is auctioneered through a high signal selector to determine the demand of the most demanding user; this becomes the PV for the VPC setting the pressure set point for the higher level header (see Figure 16-8).
Figure 16-8. Floating Pressure Control Extended to Multiple Header Steam Systems
A floating temperature control concept, very similar to the floating pressure control concept described for steam systems, can be employed. The demand signals (process controller output signals) from all users of the utility is collected and auctioneered through a high selector. The output, representing the demand of the most demanding user, becomes the PV for the valve position controller, which in turn adjusts the temperature controller set point. The same considerations apply here as stated previously: The VPC should be an integral only controller, and tuned for slow response. The set point for the VPC should be chosen judiciously so as to allow for rapid increases in demand.
344 CHAPTER 16
Figure 16-9. A Cooling Tower Optimization Control Scheme (Adapted from Ref. 16-2, Figure 8.10k.)
CHAPTER 16 345
346 CHAPTER 16
CHAPTER 16 347
To determine the operating ranges for the valves, the Cvs versus valve positions can be plotted on a semi-log graph, as shown in Figure16-12. The objective is for the valves to appear to have one continuous, equal percentage operating range. To determine the extremes for the operating range for each valve, use the following equation:
CV
where: CV R
CV max R
m 1
R =
Hence, calculating m from the equation above gives the following: The small valve should operate over a range of 0 to 59.6%, resulting in its Cv varying from 1.12 to 56.7 The large valve should operate over a range of 40.5% to 100%, resulting in its Cv varying from 16.2 to 808.
At any value of controller output, only one of the valves should be open. As the controller output rises from 0%, the small valve should open and the large valve should remain closed until the controller output reaches to just below 59.6%. At that point switching logic should open the large valve to approximately 32.2% and close the small valve. If the switching logic were
348 CHAPTER 16
not present, the large valve would have started to open when the controller output was 40.5%. When the controller output is falling from 100%, the small valve should be closed and the large valve stroked closed until the controller output reaches just above 40.5%. At that point, the switching logic should close the large valve and open the small valve to approximately 68%. Alternatively, the lower switching point could be raised, thus avoiding operating the large valve in the lower portion of its range, a region where its positioning resolution is likely to be poor.
If a valve characteristic other than equal percentage is required, Ref. 16-3, p. 64, recommends configuring a characterizer function block in the output signal of the controller.
CHAPTER 16 349
cal application is that of plastic extrusion, where the extruder barrel is heated by one or more zones of electric heating elements. Rather than a simple on-off temperature controller, the controller has normal proportionalintegral-derivative functions. Its output, a 0 to 100% analog (or digital modulating) signal, is then converted to a time proportioning signal, as shown in Figure16-13. The time proportioning signal is an on-off signal with a fixed cycle time, such as 10 seconds. The on time is a fraction of this time cycle, determined by the controller outputs analog value, as shown in Figure 16-14. For instance, if the controller output is 36%, then the electric heaters would be on for 36% of the cycle time and off for 64%. The mass of the extruder barrel provides a filtering effect so that the heat delivery to the product is a relatively even 36% of maximum.
In commercial time proportioning controllers, the PID controller and the analog-to-time proportioning converter may be integrated into one element, so that the analog signal is not externally accessible. Simulation results indicate that the controller can be tuned using any of the tuning techniques discussed in chapter 6. Prior to controller tuning, however, the time cycle must be set. If the time cycle is too long, the process filtering device (for instance, the extruder barrel in plastic extrusion applications) will be unable to adequately filter the signal and a ripple will be produced in the measured temperature. If the process exhibits an underdamped response to a set point or disturbance, then there should be, at a minimum, 12 to 15 time cycles per process cycle. On the other hand, there will likely be a minimum time resolution of the digital processor containing the time proportioning controller. If the time cycle is too short, the control loop will exhibit a ripple due to time resolution error. As a general guide, the time cycle should be at least 100 times as long as the minimum time resolution of the digital processor. For instance, if the cycle time of the digital processor is 100 ms, then the time cycle for time proportioning control should be 10 seconds or longer.
350 CHAPTER 16
Figure 16-14. Typical Analog Output and Its Corresponding Time Proportioning Signal
REFERENCES
16-1. 16-2. 16-3. F. G. Shinskey. Energy Conservation Through Control. Academic Press, 1978. Bela G. Liptk, ed. Instrument Engineers Handbook. Process Control. 3d ed. Chilton Book Co., 1995. F. G. Shinskey. Process Control Systems: Application, Design and Tuning. 4th ed. McGraw Hill, 1996.
CHAPTER 16 351