Functional Specifications For CORIOLIS METER

Spec No : 3208 Rev. No : 2


Discipline: Instrumentation Page : 1 of 7

FUNCTIONAL SPECIFICATION FOR CORIOLIS METER

Rev 2 - Revised for updating ISO Format

PREPARED / REVISED BY ET

REVIEWED BY RS

APPROVED BY GRP

TOTAL No. OF PAGES 7

DATE 28.03.2007

REV. No. 2

ET ET

MC MC

RK AC

7 7

23.06.2005 13.05.2003

1 0

FORMAT No. DD/SOF/004A/B

Ref. PROCEDURE No. DD/SOP/008 TO 015

ISSUE No. 02

REV. No. 01

REV. DATE: 01/08/2006

Design Division Engg. Services ISO 9001:2000

Functional Specifications For CORIOLIS METER

Spec No : 3208 Rev. No : 2


Discipline: Instrumentation Page : 2 of 7

CONTENTS Clause No. 1.0 2.0 ITEM Scope Of This Document Standards And Specifications 2.1 2.2 3.0 4.0 Reference Specifications Other Specifications to be followed Page No. 3 3 3 3 3 4 4 4 4 5 5 5 5 5 6 6 6 6 6 6 7

Scope Of Supply Coriolis Meter 4.1 4.2 4.3 4.4 4.5 Application General Material Accuracy Transmitter

5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 Annexure I

Equipment Protection Installation Requirement Calibration, Inspection And Testing Documentation Tagging & Nameplates Review And Approval Vendor Pre-Qualification Requirements Preparation For Shipment Receipt And Storage Typical Data Sheet Coriolis Meter

FORMAT No. DD/SOF/004A/B

Ref. PROCEDURE No. DD/SOP/008 TO 015

ISSUE No. 02

REV. No. 01

REV. DATE: 01/08/2006

Design Division Engg. Services ISO 9001:2000

Functional Specifications For CORIOLIS METER

Spec No : 3208 Rev. No : 2


Discipline: Instrumentation Page : 3 of 7

1.0 1.1

SCOPE OF THIS DOCUMENT: This specification describes the essential considerations in the selection, installation, calibration, testing and commissioning of Coriolis Meter. The Contractor shall be responsible for the procurement, packing, calibration, testing at yard and offshore, shipment to yard and offshore site, installation and commissioning at site of the Coriolis Meter.

1.2

2.0 2.1

STANDARDS & SPECIFICATIONS: Reference Specifications: a) Specification No. 3.6: Instrumentation Design Criteria b) Basic Bid Work Other Specifications To Be Followed: a) Manual of Petroleum Measurement Standards Measurement of Crude Oil by Coriolis Meters

2.2

3.0 3.1

SCOPE OF SUPPLY: The number of Coriolis Meters to be supplied and installed shall be as per the process requirements indicated in the Basic Bid Work and the P & IDs. The Coriolis Meter shall include the meter, transmitter and all other accessories necessary to make the system complete. The scope of supply shall also include commissioning spares and two years spares as required by clause 3.6.4.8 of Instrumentation Design Criteria, and as suggested by the Manufacturer.

3.2

3.3

FORMAT No. DD/SOF/004A/B

Ref. PROCEDURE No. DD/SOP/008 TO 015

ISSUE No. 02

REV. No. 01

REV. DATE: 01/08/2006

Design Division Engg. Services ISO 9001:2000

Functional Specifications For CORIOLIS METER

Spec No : 3208 Rev. No : 2


Discipline: Instrumentation Page : 4 of 7

4.0 4.1 4.1.1

CORIOLIS FLOW METER: Application: Coriolis Meter shall be used as the flow-measuring element and / or density-measuring element wherever dictated by the process requirements. In general Coriolis Meters shall be used for measurement of flow and / or density with process pressure < 40 kg/cm2. General: The Coriolis Meter shall be selected such that the nominal bore size of the sensor is equal to or less than the line size. The Coriolis Meter shall have flanged end connections, rated for the associated piping class. The Coriolis Meter shall be provided with a local LCD display (integral or separately mounted near the flow meter or as a part of the locally mounted transmitter). In case the display is not integral, all mounting accessories required for the display shall be provided by the Contractor. The Contractor shall also provide interconnecting cable (between the sensor and the local display unit) and the cable glands suitable for the specified area classification. These interconnecting cables shall be kept as short as practicable. Any special cable and / or hardware that are required to make the system complete shall be supplied by the Contractor. All weldings and castings (if any) shall be 100% radiographed. Material: The material requirements for Coriolis Meter shall in general be according to clause 3.6.4.5 of Instrumentation Design Criteria. The Contractor shall ensure that the sensor and all other wetted parts are compatible with the process fluid conditions. The sensor (metal tubing) shall be made of SS 316L as a minimum, unless the process conditions dictate the use of higher corrosion resistant materials.

4.1.2

4.2 4.2.1

4.2.2

4.2.3

4.2.4

4.2.5 4.3 4.3.1

4.3.2

FORMAT No. DD/SOF/004A/B

Ref. PROCEDURE No. DD/SOP/008 TO 015

ISSUE No. 02

REV. No. 01

REV. DATE: 01/08/2006

Design Division Engg. Services ISO 9001:2000

Functional Specifications For CORIOLIS METER

Spec No : 3208 Rev. No : 2


Discipline: Instrumentation Page : 5 of 7

4.4 4.4.1 4.4.2

Accuracy: Coriolis Meters shall have an accuracy of 60.2% of flow rate or better. Where a Coriolis meter is installed in a bypass line for density measurement, the design shall ensure that the flow rate through the meter provides the accuracy and response times required by the process. Transmitter: The Coriolis Meter Transmitter shall be SMART type with 24 V DC power supply and 2 numbers of 4 20 mA output with a local indicator. On high temperature applications, the transmitter shall be mounted separately from but local to the sensor. Sensor cables shall be kept as short as practicable.

4.5 4.5.1

4.5.2

5.0 5.1

EQUIPMENT PROTECTION: Coriolis Meter protection requirements shall in general be as per clause no. 3.6.4.4 of Instrumentation Design Criteria. The enclosure class for Coriolis Meter, Local Indicator and Transmitter, shall be Weather proof to IP 65 or better.
1

5.2

6.0 6.1

INSTALLATION REQUIREMENTS: The installation of Coriolis Meter shall in general be according to clause 3.6.4.6 of Instrumentation Design Criteria. Coriolis meters shall be installed in accordance with the Vendors recommendations.

6.2

7.0 7.1

CALIBRATION, INSPECTION & TESTING: Calibration, inspection and testing requirements shall in general be as per clause 3.6.4.7 of Instrumentation Design Criteria.

FORMAT No. DD/SOF/004A/B

Ref. PROCEDURE No. DD/SOP/008 TO 015

ISSUE No. 02

REV. No. 01

REV. DATE: 01/08/2006

Design Division Engg. Services ISO 9001:2000

Functional Specifications For CORIOLIS METER

Spec No : 3208 Rev. No : 2


Discipline: Instrumentation Page : 6 of 7

8.0 8.1

DOCUMENTATION: The documentation requirements shall in general be according to clause 3.6.6.2 of Instrumentation Design Criteria. Duly filled in data sheet shall be furnished along with the purchase specification. A typical blank data sheet is provided as Annexure I of this document. Coriolis Meter sizing calculations shall be furnished along with the purchase specification. TAGGING & NAMEPLATES: Tagging & Nameplate requirements shall in general be according to clause 3.6.6.1 of Instrumentation Design Criteria. The Tag Number and Service shall be clearly engraved on the instrument tag as a minimum. REVIEW & APPROVAL: Review and approval of purchase specifications and other related documents shall in general be according to clause 3.6.6.3 of Instrumentation Design Criteria. VENDOR PRE-QUALIFICATION REQUIREMENTS: The Vendor pre-qualification requirements shall in general be according to clause 3.6.6.4 of Instrumentation Design Criteria. PREPARATION FOR SHIPMENT: The Coriolis Meter shall be prepared for shipment in accordance to clause 3.6.6.5 of Instrumentation Design Criteria. RECEIPT & STORAGE: Receipt and storage of the Coriolis Meter shall be in accordance to clause 3.6.6.6 of Instrumentation Design Criteria.

8.2

8.3

9.0 9.1

9.2

10.0 10.1

11.0 11.1

12.0 12.1

13.0 13.1

FORMAT No. DD/SOF/004A/B

Ref. PROCEDURE No. DD/SOP/008 TO 015

ISSUE No. 02

REV. No. 01

REV. DATE: 01/08/2006

Design Division Engg. Services ISO 9001:2000

Functional Specifications For CORIOLIS METER

Spec No : 3208 Rev. No : 2


Discipline: Instrumentation Page : 7 of 7

ANNEXURE I
ANNEXURE III - Typical Data Sheet For Coriolis Meter
CORIOLIS METER UNITS: Flow Liquid M /HR. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
3

Gas NM /HR.

Pressure Kg/cm2

Temperature oC

Level/Length - M

GENERAL

METER

TRANSMITTER

SERVICE CONDITIONS

ITEM DETAILS

Tag Number Line Number Service Function Area Classification Enclosure Class Sensor Material End Connection & Face Finish End Connection Flange Material Sensor Spool Piece Material Other Wetted Parts Material Enclosure Material Measuring Range Adjustable Range Accuracy Sensitivity Repeatability Effect of Temperature Minimum Detection Limit Cable Entry Connection Local Display Power Supply Output Electrical Area Class Enclosure Cable Entry Fluid State Flow Min. Maximum Flow Normal Inlet Pressure Operating Maximum Temperature Operating Maximum Sp. Gr. At Oper. Temp. Mol. Wt. System Pressure Drop Operating Viscosity (Cp) Max. Allowable pressure drop across meter Density Maximum Water Content Normal Minimum Manufacturer Model No. Remarks

FORMAT No. DD/SOF/004A/B

Ref. PROCEDURE No. DD/SOP/008 TO 015

ISSUE No. 02

REV. No. 01

REV. DATE: 01/08/2006