You are on page 1of 13

Issued October 2009

DATA SHEET

EZC MCCB
Based on Schneider ABTED107171EN Catalogue

12476

12476

The EasyPact range

Selection table

EasyPact circuit breakers

EZC100-1P.

EZC100-2P.

Number of poles
Rated current (A)

In

Rated insulation voltage (V)


Rated impulse withstand voltage (kV)
Rated operational voltage (V)

Ui
Uimp
Ue

at 40 C

AC 50/60 Hz
DC

Electrical characteristics as per IEC 60947-2, EN 60947-2, JIS C8201-2-1


Ultimate breaking capacity (kA rms)

Icu

Rated service breaking capacity (kA rms)

Ics

Suitability for isolation


Utilisation category
Pollution degree
Endurance (C-O cycles)

AC 50/60 Hz 110/130 V
220/230/240 V
380 V
400/415 V
440 V
550 V
DC
125 V (1P)
250 V
(2P in series)
% Icu
110-400 V
415-550 V

Mechanical
Electrical
In/415 V

Electrical characteristics as per NEMA-AB1


Breaking capacity (kA rms)

HIC

AC 50/60 Hz 240 V
277/480 V

Protection
Overload protection
Instantaneous protection

Bimetal
Magnetic

Fixed (20 %)

Auxiliary switch
Alarm switch
Combined AX + AL
Shunt trip release
Undervoltage release

AX
AL
AXAL
SHT
UVR

Auxiliaries
Indication contacts
EZC100-3P.
Voltage releases

Installation
Connection
Accessories

Crimp lugs/bars
Box lugs for bare cables
Rotary handles

Direct
Extended

Terminal extensions
Spreaders
Phase barriers
Terminal shields
Padlocking system
DIN rail adaptor

EZC100-4P.

Dimension and weight


Dimensions (mm)

DxH
W

Weight (kg)

EZC250-3P.

Based on Schneider ABTED107171EN Catalogue

Page 1 of 12

12476

EZC100B

EZC100F

EZC100N

EZC250F

EZC250N

EZC250H

3
15, 16, 20, 25,
30, 32, 40, 45,
50, 60

1
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
415
125

3-4
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
550
250

1
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
415
125

2-3-4
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
550
250

3
100, 125, 150,
160, 175, 200,
225, 250

3
100, 125, 150,
160, 175, 200,
225, 250

2-3
100, 125, 150,
160, 175, 200,
225, 250

690
6
550
-

3
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
550
250

EZC100H

690
6
550
250

690
6
550
250

690
6
550
250

10
10
7.5
7.5
5
2.5
-

25
25
10
10
7.5
5
5
5

25
18
2.5
2.5
5
-

25
25
18
15
10
5
5
5

50
25
5
5
10
-

100
100 (1)
30
30
20
10
10
10

25
25
18
18
15
5
5
5

50
50
25
25
20
8
20
20

25 %
25 %

50 %
50 %

50 %
50 %

50 %
50 %

50 %
50 %

50 %
25 %

50 %
50 %

50 %
50 %

A
3
8 500
1 500

A
3
8 500
1 500

A
3
8 500
1 500

A
3
8 500
1 500

A
3
8 500
1 500

A
3
8 500
1 500

A
3
10 000
5 000

A
3
10 000
5 000

A
3
10 000
5 000

10
10 (2)

25
10

18
18 (2)

100
18 (3)

25
15

fixed
fixed

fixed
fixed

fixed
fixed

fixed
fixed

fixed
fixed

fixed
fixed

fixed
10 In

fixed
10 In

p
p
p
p
p

p
p
p
p
p

p
p
p
p
p

p
p
p
p
p

p
p
p
p
p

p
p
p
p
p

p
p
p
p
p

p
p
p
p

p
p
p
p

p
p

p
p
p
p

p
p

p
p
p (3)
p (3)

p
p
p
p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

p
p
p
p
p

p
p
p
p
p

60 x 130
75

60 x 130
75

60 x 130
25

60 x 130
75 (3P),
100 (4P)

60 x 130
25

0.78

0.78

0.28

0.78 (3P),
1.0 (4P)

0.28

p
-

p
p

p
p
p
p
p

p
-

p
p

50 %
50 %

85
85
36
36
25
10
30
30

p
p
p (3)
p
p
60 x 130
50 (2P),
75 (3P),
100 (4P)
0.6 (2P),
0.78 (3P),
1.0 (4P)

50
18

85
25 (3)
fixed
10 In

60 x 165
105

60 x 165
105

60 x 165
105

1.3

1.3

1.1 (2P),
1.3 (3P)

(1) 50 kA for 2 poles.


(2) For 277 V only.
(3) For 3 and 4 poles only.

Based on Schneider ABTED107171EN Catalogue

Page 2 of 12

12476

The EasyPact range

Selection table (cont.)

EasyPact circuit breakers


Number of poles
Rated current (A)

In

Rated insulation voltage (V)


Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V)
Ue

at 40C

AC 50/60 Hz
DC

Electrical characteristics as per IEC 60947-2, EN 60947-2 and JIS C8201-2-1/C8201-2-2


Ultimate breaking capacity (kA rms)

Icu

Rated service breaking capacity


(kA rms)
Suitability for isolation
Utilisation category
Pollution degree
Endurance (C-O cycles)

Ics

EZC250.

AC 50/60 Hz 220/230/240 V
380 V
400/415 V
440 V
550 V
DC
125 V (1P)
250 V
(2P in series)
% Icu

Mechanical
Electrical

In/415 V

Electrical characteristics as per NEMA-AB1


EZCV250-4P.

Breaking capacity (kA rms)

HIC

AC 50/60 Hz 240 V
277/480 V

Protection
Overload protection
Instantaneous protection

Bimetal
Magnetic

fixed ( 20 %)

Earth-leakage protection
Sensitivity (A)
Time-delay (ms)
Max. breaking time (s)

adjustable
adjustable

IDn
Dt
at 2 IDn

Auxiliaries
Indication contacts

Voltage releases

Auxiliary switch
Alarm switch
Combined AX + AL
Earth-alarm switch
Shunt trip release
Undervoltage release

AX
AL
AXAL
ALV
SHT
UVR

Installation
EZC400-3P.

Connection
Accessories

Crimp lugs / bars


Box lugs for bare cables
Rotary handles
Direct
Extended
Terminal extensions
Spreaders
Phase barriers
Terminal shields
Padlocking system

Dimension and weight


Dimensions (mm)

DxH
W

Weight (kg)

EZC400-4P.

Based on Schneider ABTED107171EN Catalogue

Page 3 of 12

12476

EZC250N

EZC250H

EZCV250N

EZCV250H

EZC400N

EZC400H

4
63, 80, 100, 125,
150, 160, 175, 200,
225, 250
690
6
550
250

4
63, 80, 100, 125,
150, 160, 175, 200,
225, 250
690
6
550
250

3-4
63, 80, 100, 125,
150, 160, 175, 200,
225, 250
440
6
440
-

3-4
63, 80, 100, 125,
150, 160, 175, 200,
225, 250
440
6
440
-

3-4
250, 300, 320,
350, 400

3-4
250, 300, 320,
350, 400

690
8
550
250

690
8
550
250

50
25
25
20
8
20
20

85
36
36
25
10
30
30

85
25
25
20
-

100
36
36
25
-

85
36
36
36
15
20

100
50
50
50
20
40

50 %

50 %

50 %

50 %

50 %

50 %

A
3
10 000
5 000

A
3
10 000
5 000

A
3
10 000
5 000

A
3
10 000
5 000

A
3
4 000
1 000

A
3
4 000
1 000

50
18

85
25

50
-

85
-

50
25

85
35

fixed
10 In

fixed
10 In

fixed
10 In

fixed
10 In

fixed
10 In

fixed
10 In

0.1/0.3/0.5/1
0/200/500/1000
0.15/0.4/1/2

0.1/0.3/0.5/1
0/200/500/1000
0.15/0.4/1/2

p
p
p

p
p
p

p
p
p

p
p

p
p
p
p
p
p

p
p
p

p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

p
p
p
p
p
p
p
p
p

68 x 165
140

68 x 165
140

1.8

1.8

68 x 165
105 (3P)
140 (4P)
1.6 (3P)
2.1 (4P)

68 x 165
105 (3P)
140 (4P)
1.6 (3P)
2.1 (4P)

103 x 257
140 (3P)
185 (4P)
5 (3P)
7.5 (4P)

103 x 257
140 (3P)
185 (4P)
5 (3P)
7.5 (4P)

p
p

Based on Schneider ABTED107171EN Catalogue

p
p

p
p

Page 4 of 12

12476

The EasyPact range

Auxiliaries and accessories

Indication contacts
Auxiliary switch AX (ON/OFF)

p Indicates the position of the circuit breaker contacts

Alarm switches (trip indication)

p AL indicates that the circuit breaker has tripped due to:


an overload, a short-circuit or operation of a voltage release
p ALV indicates that the circuit breaker has tripped due to:
an earth-leakage fault.

Remote tripping
Shunt Trip (SHT)

p This release trips the circuit breaker when the control voltage rises above 0.7 x Un
p Control signals can be of the impulse type ( > 20 ms) or maintained

Under Voltage Release (UVR)

p This release trips the circuit breaker when the control voltage drops below a
tripping threshold
p Tripping threshold between 0.35 and 0.7 times the rated voltage
p Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage
All these electrical auxiliaries are easily snap with the breaker, after opening the
unloosable rotary cover.
No need of any fixing screws nor adjustments.

Rotary handles
Direct rotary handle

p Degree of protection IP40 or IP54, IK07 (IP54 with gasket supplied)

Extended rotary handle

p To operate circuit breakers installed at the back of switchboards, from the


switchboard front.
p Degree of protection IP40 or IP54, IK08 (IP54 with gasket supplied).
p The extended rotary handle is made up of:
a unit on the front cover of the circuit breaker (secured by screws)
an assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally
an extension shaft that must be adjusted to the distance between back of circuit
breaker and door.

Rotary handles (direct and extended) maintains

p Suitability for isolation.


p Indication of the three positions O (OFF), I (ON) and tripped.
p Circuit breaker locking capability in the OFF position by one to three padlocks
(padlock not supplied).
p Door opening disabled when the circuit breaker is ON.
p Circuit-breaker closing is disabled if the door is open.

Padlocking system
p Locking in the OFF position guarantees isolation as per IEC 60947-2.
p Padlocking system can receive up to (padlocks not supplied) :
two padlocks 5 mm for EZC100
three padlocks 8 mm for EZC250/ECZV250
three padlocks 8 mm for EZC400

Based on Schneider ABTED107171EN Catalogue

Page 5 of 12

12476

Power connections

p EasyPact circuit breakers are supplied in standard with terminal screws


p Connection of insulated bars or cables with crimp lugs:
y 17

y25

y32

h (mm)

d+10

d+10

d+10

d (mm)

y7

y8

y10

e (mm)

y6

y6

y10

(mm) y50 A

5.5

> 50 A

8.5

10

y50 A
> 50 A

M5
M8

M8

M10

L (mm)

y 17

y25

y32

h (mm)

y9

y8

y10

(mm) y50 A

5.5

> 50 A

8.5

10

y50 A

2 Nm

> 50 A

5.5 Nm

13 Nm

30 Nm

Terminal screws
Crimp lugs

EZC100 EZC250/EZCV250 EZC400

L (mm)

Tightening torque

p Connection of bare cables lugs are screwed directly to the standard connections
(option)

EZC100

h (mm)
Section (mm2)
Torque

EZC250/EZCV250 EZC400

15 A - 50 A

60 A - 100 A 100 A - 250 A

250 A - 400 V

12
2.5 to 16
3 Nm

14
10 to 50
6 Nm

30
35 to 300
30 Nm

21
42 to 152
10 Nm

Spreaders

p Increase the pitch of the terminals:


from 25 mm to 35 mm for EZC100
from 35 mm to 45 mm for EZC250/EZCV250
from 44 mm to 70 mm for EZC400.

Terminal Extensions

p Extend power connection of the EZC250/EZCV250 at 35 mm pitch.


p Extend power connection of the EZC400 at 44 mm pitch.

Phase barriers
p
p
p
p
p

Safety accessories for maximum insulation at the power connection points.


Slide easily onto the circuit breaker.
Usable with all other connection accessories, except terminal shields.
Each breaker is delivered with a set for the incoming side.
Additionnal phase barriers are designed for maximum insulation on load side,
or between two breakers.

Terminal shields

p Insulating accessories used for:


protection against direct contact
and improvement of the degree of protection (IP-IK)
p Designed for front connection only (long terminal shield).
p Designed for 3-pole EZC100 / 2, 3, 4-pole EZC250/EZCV250 / 3,4-pole EZC400.

Sealing screws

p Safety accessory to seal the terminal shields on the EZC100.

Din rail adaptor

p Specific adaptor to mount EZC100 on an optional DIN rail.

Based on Schneider ABTED107171EN Catalogue

Page 6 of 12

12476

The EasyPact range

General characteristics

Installation

EasyPact circuit breakers are designed for Easy installation in the various types of
switchboards. They may be mounted vertically, horizontally or flat on their back
without any derating of characteristics.
Installation positions.

Power supply

EasyPact circuit breaker can be supplied from either the top or the bottom (reverse
feeding) without any reduction in performance. For earth-leakage circuits breakers,
reverse feeding is possible only up to 240 V AC. This capability facilitates connection
when installed in a switchboard.

Degree of protection
Bare circuit breaker with terminal shields
With toggle

IP20

IK07

With direct rotary handle standard

IP40

IK07

Circuit breaker installed in a swtichboard


With toggle

IP40

IK07

With direct rotary handle standard VDE MCC

IP54

IK07

With extended rotary handle

IP54

IK08

Ambient temperature
Reverse feeding.

EasyPact devices are equipped with fixed thermal-magnetic trip units.


EasyPact has been particularly designed to hold 100 % In at 50 C without tripping in
normal condition.
EasyPact circuit breakers may be used between -25 C and +70 C.
EasyPact circuit breakers should be put into service under normal ambient operating
temperature conditions. Exceptionally, the circuit breaker may be put into service
when the ambient temperature is between -35 C and -25 C.
The permissible storage-temperature range for EasyPact circuit breakers in the
original packing is -35 C to +85 C.
To determine tripping times using time/current curves, use Ir values corresponding to
the thermal setting on the device, corrected as indicated in the tables below.

Rated
25 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C
current (A)

EZC100

15
16
20
25
30
32
40
45
50
60
63
75
80
100

17.0
18.1
21.8
26.9
34.5
36.8
42.8
48.8
54.2
64.4
67.6
78.6
84.4
109

15.7
16.7
20.4
25.7
31.4
33.5
40.9
46.9
52.1
61.8
64.9
76.8
82.2
103

15.3
16.3
20.2
25.3
30.7
32.7
40.4
45.9
51.0
60.9
63.9
75.9
81.1
101

15.0
16.0
20.0
25.0
30.0
32.0
40.0
45.0
50.0
60.0
63.0
75.0
80.0
100

14.7
15.7
19.7
24.7
29.4
31.4
39.5
44.4
49.3
59.0
62.0
73.5
78.6
99

14.6
15.6
19.2
24.5
29.1
31.0
38.0
43.3
48.1
57.5
60.4
70.4
77.3
94

14.2
15.1
18.9
24.3
28.5
30.4
37.6
42.6
47.3
56.6
59.4
69.8
76.7
94

13.8
14.7
18.5
24.0
28.0
29.9
37.1
41.9
46.6
55.7
58.5
69.1
76.1
93

63
80
100
125
150
160
175
200
225
250

77
93
115
148
174
186
207
236
268
297

69
86
106
135
160
171
188
215
244
270

66
83
103
130
155
166
182
208
235
260

63
80
100
125
150
160
175
200
225
250

60
77
96
120
145
154
168
192
215
239

56
74
93
114
139
148
161
184
205
228

53
71
89
109
134
142
153
175
194
215

49
68
85
103
128
136
145
166
182
203

63
80
100
125
150
160
175
200
225
250

72
89
113
140
163
177
194
223
245
277

63
80
100
125
150
160
175
200
225
250

60
77
95
120
145
154
168
192
218
240

56
73
91
114
141
148
161
183
211
230

53
70
86
108
136
141
154
175
203
220

49
66
80
102
131
135
146
165
196
209

44
62
74
95
125
127
138
155
180
198

39
58
68
88
120
120
126
144
162
180

250
300
320
350
400

293
351
374
410
468

268
321
342
375
428

260
312
333
364
416

250
300
320
350
400

240
288
307
336
384

228
273
291
319
364

218
261
278
305
348

208
249
266
291
332

EZC250

EZCV250

EZC400

Based on Schneider ABTED107171EN Catalogue

Page 7 of 12

12476

The EasyPact range

Tripping curves

EasyPact 100 TM
15-16 A

20 A

25 A

30-32 A

10 000
5 000

10 000
5 000

10 000
5 000

10 000
5 000

2 000

2 000

2 000

2 000

1 000
500

1 000
500

1 000
500

1 000
500

200
100
50

200
100
50

200
100
50

200
100
50

20
10
5

20
10
5

20
10
5

20
10
5

t(s)

t(s)

2
1
.5

t(s)

2
1

t(s)

2
1
.5

.5

2
1
.5

.2
.1

.2
.1

.2
.1

.2
.1

.05

.05

.05

.05

.02

.02

.02

.02

.01
.005

.01
.005

.01
.005

.01
.005

.002
.001
.5 .7 1

3 4 5 .7 10

.002
.001
.5 .7 1

20 30 50 70 100 200300

I / Ir

3 4 5 .7 10

.002
.001
.5 .7 1

20 30 50 70 100 200300

.002
.001

20 30 50 70 100 200300

.5 .7 1

I / Ir

I / Ir

40 A

3 4 5 .7 10

45-50 A

60-63 A

75 A

10 000
5 000

10 000
5 000

10 000
5 000

2 000

2 000

2 000

2 000

1 000
500

1 000
500

1 000
500

1 000
500

200
100
50

200
100
50

200
100
50

200
100
50

20
10
5

20
10
5

20
10
5

20
10
5

t(s)

2
1
.5

t(s)

2
1
.5

2
1

.2
.1

.2
.1

.2
.1

.05

.05

.05

.02

.02

.02

.02

.01
.005

.01
.005

.01
.005

.01
.005

3 4 5 .7 10

.002
.001
.5 .7 1

20 30 50 70 100 200300

3 4 5 .7 10

.002
.001
.5 .7 1

20 30 50 70 100 200300

I / Ir

80 A

100 A

10 000
5 000

10 000
5 000

2 000

2 000

1 000
500

1 000
500

200
100
50

200
100
50

20
10
5

t(s)

2
1
.5

20 30 50 70 100 200300

.5

.2
.1

I / Ir

t(s)

t(s)

2
1
.5

.05

.002
.001
.5 .7 1

3 4 5 .7 10
I / Ir

10 000
5 000

t(s)

3 4 5 .7 10

.002
.001
.5 .7 1

20 30 50 70 100 200300

I / Ir

3 4 5 .7 10

20 30 50 70 100 200300

I / Ir

20
10
5
2
1
.5

.2
.1

.2
.1

.05

.05

.02

.02

.01
.005

.01
.005

.002
.001
.5 .7 1

3 4 5 .7 10

.002
.001
.5 .7 1

20 30 50 70 100 200300

I / Ir

3 4 5 .7 10

20 30 50 70 100 200300

I / Ir

EasyPact 250 TM

EasyPact 400 TM

100-125 A

150-160-175-200 A

225-250 A

250-300-320-350-400 A

10 000
5 000

10 000
5 000

10 000
5 000

10 000
5 000

2 000

2 000

2 000

2 000

1 000
500

1 000
500

1 000
500

1 000
500

200
100
50

200
100
50

200
100
50

200
100
50

20
10
5

20
10
5

20
10
5

20
10
5

t(s)

t(s)

2
1
.5

t(s)

2
1
.5

t(s)

2
1

2
1
.5

.5

.2
.1

.2
.1

.2
.1

.2
.1

.05

.05

.05

.05

.02

.02

.02

.02

.01
.005

.01
.005

.01
.005

.01
.005

.002
.001

.5 .7 1

3 4 5 .7 10
I / Ir

20 30 50 70 100 200300

.002
.001

.5 .7 1

3 4 5 .7 10

20 30 50 70 100 200300

I / Ir

Based on Schneider ABTED107171EN Catalogue

.002
.001
.5 .7 1

3 4 5 .7 10
I / Ir

20 30 50 70 100 200300

.002
.001
.5 .7 1

3 4 5 .7 10

20 30 50 70 100 200300

I / Ir

Page 8 of 12

12476

The EasyPact range

Dimensions EZC100

Dimensions
1P

2P

Y
Y

3P

4P

Mounting on DIN tail

Mounting on plate
1P

2P

3P

YY

xX

xX

or

4P

YY

xX
xX

ou

Door cut-out (small)


1P, 3P

2P

YY

4P

Y
Y

YY

Door cut-out (large)


1P

xX

2P

YY

3P

YY

xX

xX

4P

YY

xX

YY

X
x

Based on Schneider ABTED107171EN Catalogue

Page 9 of 12

12476

The EasyPact range

Dimensions EZC250 / EZCV250

Dimensions
2P, 3P

50

4P

YY

YY

??
52.5
35

35

3P (EZCV250)

YY

144
X
102

19.5

25

22
100
105

44

Dimensions (mm)
EZC 2/3P
EZC 4P
EZCV 3P/4P

A
60
68
68

B
65
73
73

C
85.5
95
95

E
67
75
75

F
61
69
69

Mounting on plate
2P, 3P

4P

X
x

X
x

Door cut-out (small)


2P, 3P

YY

4P

Y
Y

xX

xX

Door cut-out (large)


2P, 3P

4P

YY

X
x

X
x

YY

X
x

Based on Schneider ABTED107171EN Catalogue

Page 10 of 12

12476

The EasyPact range

Dimensions EZC400

Dimensions
3P

4P

Y
Y

Xx

Mounting on plate
3P

4P

Y
Y

YY

Xx

X
x

Door cut-out (small)


3P

4P

Y
Y

Xx

Door cut-out (large)


3P

X
x

Y
Y

4P

X
x

YY

xX

Based on Schneider ABTED107171EN Catalogue

Page 11 of 12

12476

The EasyPact range

Dimensions

EZC100
Direct rotary handle

Extended rotary handle


3P

Door cut-out 3P
YY

3P

Door cut-out 3P
YY

xX

X
x

xX

xX

xX

EZC250
Direct rotary handle
3P

Door cut-out 3P, 4P

4P
YY

Y
Y

Y
Y

xX

Xx

Extended rotary handle


Door cut-out 3P, 4P

3P, 4P
Y

xX

Dimensions (mm)
C
EZC 2/3P
93 to 97
EZC 4P
101 to 105
EZCV 3/4P

D
145
153

Xx

E
137 to 414
145 to 422

EZC400
Direct rotary handle
3P

Door cut-out 3P, 4P

4P
YY

Xx

YY

Xx

Xx

Xx

Extended rotary handle


3P, 4P

xX

Door cut-out 3P, 4P

YY

Y
Y

xX

Based on Schneider ABTED107171EN Catalogue

Page 12 of 12