You are on page 1of 63

INSTITUT SUPERIEUR DES ETUDES

TECHNOLOGIQUES DE SFAX
DEPARTEMENT GENIE CIVIL
Ralis par : ELLOUZE SAMIR
WERDA YOSRI
ZOUARI WISSERM
ISET
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 2
Tables des matires
I. PARTIE TECHNOLOGIE.
1. TERMINOLOGIE ET CONCEPTION DUNE CONSTRUCTION EN METAL.
2. LA TECHNOLOGIE DES ASSEMBLAGES EN CONSTRUCTION METALLIQUE
II. LES EFFETS CLIMATIQUES.
1. EFFET DE LA NEIGE SUR LES CONSTRUCTIONS.
2. LEFFET DU VENT SUR LES CONSTRUCTIONS.
3. EFFET DU VENT SUR CONSTRUCTIONS PRISMATIQUES A BASE
QUADRANGULAIRE.
III. CALCUL DES OSSATURES SELON LES REGLES EUROCODE 3
1. BASES DE CLCULS DU REGLEMENT EUROCODE 3 :
2. CLASSIFICATION DES SECTIONS TRANSVERSALES :
3. JUSTIFICATION DES SECTIONS TRANSVERSALES SELON LE REGLEMENT
EUROCODE 3 :
4. LES PHENOMENES DINSTABILITE ELASTIQUE
5. ASSEMBLAGE PAR BOULONS
6. LES ASSEMBLAGES PAR SOUDURES
7.ORGANIGRAMMES RECAPITULATIFS DE CALCULS :
IV. ANNEXES.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 3
LES EFFETS CLIMATIQUES
Selon le rglement neige et vent NV65 modifi 99 et N84 modifi 96
1. EFFET DE LA NEIGE SUR LES CONSTRUCTIONS.
2. LEFFET DU VENT SUR LES CONSTRUCTIONS.
3. EFFET DU VENT SUR CONSTRUCTIONS PRISMATIQUES A BASE
QUADRANGULAIRE.
Chapitre 1 :
EFFET DE LA NEIGE
SUR LES CONSTRCTIONS
1. LES VALEURS DES SURCHARGES NORMALES ET SURCHARGES
EXTREMES:
Elles sont fixes en fonction de la rgion et de laltitude. Jusqu deux cents mtres daltitude, les
surcharges verticales normales p
n0
et extrmes p
n0
uniformment rparties dues la neige, ont pour
valeurs en projection horizontale celles indiques par le tableau suivant.
Rgion A
Rgion B
SURCHARGES NORMALES
p
n0
SURCHARGES EXTRMES
p
n0
45 daN/m
2
35 daN/m
2
75 daN/m
2
60 daN/m
2
Les rgions sont dfinies par la carte (ANNEXE 1).
2. INFLUENCE DE LALTITUDE :
Au del de 200 m daltitude et quelle que soit la rgion considre, la loi de variation des
surcharges en fonction de p
n0
ou de p
n0
et de laltitude A est donne par le tableau suivant :
Altitude p
n (
daN/m
2
) P
n (
daN/m
2
)
200 m A 500 m
10
) 200 A (
Pn
0

+
6
) 200 A (
n ' P
0

+
500 m A 1500 m
4
) 500 A (
30 Pn
0

+ +
4 . 2
) 500 A (
50 n ' P
0

+ +
1500 m A 2000 m
5 . 2
) 1500 A (
280 Pn
0

+ +
5 . 1
) 1500 A (
467 n ' P
0

+ +
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 4
ANNEXE 1
3. INFLUENCE DES CARATERISTIQUES DE LA TOITURE :
Les surcharges de neige par mtre carr de projection horizontale restent gales aux valeurs
fixes dans les paragraphes 1 et 2 quand linclinaison de la surface du toit sur lhorizontale ne
dpasse pas 25.
Ces surcharges sont rduites de 2 % par degr dinclinaison supplmentaire sur toute partie de
couverture dont linclinaison dpasse 25, lorsque rien ne soppose au glissement de la neige sur le
versant considr.
4. COMBINAISON DES EFFETS DE LA NEIGE ET DU VENT :
Les effets de la neige et du vent sont considrs simultanment lorsque leur combinaison produite
dans la construction des actions plus dfavorables que si la neige ou le vent agissait seul.
Lorsque la rpartition de la neige sur la toiture est sensiblement uniforme on prend :
La surcharge normale ou extrme du vent soufflant dans les diffrentes directions est prise en
totalit ;
La surcharge normale ou extrme de la neige est rduite de moiti.
V + 0.5 Sn
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 5
Chapitre 2 :
LEFFET DU VENT SUR LES CONSTRCTIONS
I. DEFINITIONS ET PRINCIPES GENERAUX.
1. direction du vent :
Pour le calcul des constructions, on suppose que la direction densemble moyenne du vent est
horizontale.
2. Exposition des surfaces.
Si on claire la construction par un faisceau de rayons lumineux parallles la direction
densemble du vent :
Les surfaces claires (exposes au vent) sont dites au vent.
Les surfaces non claires (non exposes au vent) ou sous incidence rasante (parallles la
direction du vent) sont dites sous le vent.
3. Action exerce par le vent sur une des faces dune paroi.
Laction exerce par le vent sur une des faces dun lment de paroi est considre comme
normale cet lment. Elle est en fonction :
a. de la vitesse du vent.
b. De la catgorie de la construction et de ses proportions densemble ;
c. De lemplacement de llment considr dans la construction et de son orientation par
rapport au vent ;
d. Des dimensions de llment considr ;
e. De la forme de la paroi (plane ou courbe) laquelle appartient llment considr.
4. Pression dynamique et coefficient de pression.
Laction lmentaire unitaire exerce par le vent sur une des faces dun lment de paroi est
donne par un produit (C. q), dans le quel :
q dsigne la pression dynamique fonction de la vitesse du vent.
C un coefficient de pression fonction des dispositions de la construction.
Une des faces dun lment appartenant une construction est dite soumise :
a. une pression (ou une surpression) lorsque la force normale cette face est dirige vers
elle. Dans ce cas, par convention, c est positif.
b. une succion (ou une dpression) lorsque la force est dirige en sens contraire. Dans ce cas,
par convention, c est ngatif.
Surpression
Dpression
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 6
II. PRESSION DYNAMIQUE :
1. Dfinition
La pression dynamique q en (daN/m) est donne en fonction de la vitesse v du vent en mtres par
seconde par la formule suivante :
3 . 16
v
q =
2. Pression dynamique normale et pression dynamique extrme.
On doit envisager dans les calculs une pression dynamique normale et une pression dynamique
extrme ; le rapport de la seconde la premire est pris gal 1,75.
3. Pression dynamique de base.
Dfinition
Par convention, les pressions dynamiques de base normale et extrme sont celles qui sexercent
une hauteur de 10 m au-dessus du sol, pour un site normal sans effet de masque sur un lment dont
la plus grande dimension est gale 0,50 m.
Valeurs
Elles varient avec les rgions et une altitude infrieure ou gale 1 000 m sont donnes par le
tableau suivant.
Rgion I
Rgion II
Rgion III
Pression dynamique
De base normale
Pression dynamique
de base extrme
50 daN/m
70 daN/m
90 daN/m
87.5 daN/m
122.5 daN/m
157.5 daN/m
Au del de 1 000 m daltitude, le cahier des charges doit obligatoirement prescrire les pressions
dynamiques de base prendre en compte dans les calculs.
Valeur des vitesses du vent correspondant celles des pressions dynamiques pour les diffrentes
rgions donnes par le tableau suivant.
Rgion I
Rgion II
Rgion III
Rgion IV
Valeurs normales Valeurs extrmes
28.6 m/s ou 103.0 km/h
33.8 m/s ou 121.7 km/h
38.3 m/s ou 137.9 km/h
44.2 m/s ou 159.2 km/h
37.8 m/s ou 136.1 km/h
44.7 m/s ou 160.9 km/h
50.7 m/s ou 182.5 km/h
58.5 m/s ou 210.6 km/h
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 7
Les rgions sont dfinies par la carte (ANNEXE 2).
Valeurs fixes par le cahier des charges
Le cahier des charges peut prescrire des pressions dynamiques de base normale et extrme
suprieures celles des rgles et modifier leur rapport suivant les rsultats des observations, les
conditions locales, et la destination du btiment, en particulier lorsque sa prennit doit tre assure
avec un large coefficient de scurit.
4. Modifications des pressions dynamiques de base.
a. Effet de la hauteur au-dessus du sol
Soit q
H
la pression dynamique agissant la hauteur H au-dessus du sol exprime en mtres.
q
10
la pression dynamique de base 10 m de hauteur.
Pour H compris entre 0 et 500 m, le rapport entre q
H
et q
10
est dfini par la formule :
60 H
18 H
5 . 2
q
q
10
H
+
+
=
Voir ANNEXE 3
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 8
Pour les constructions en bordure immdiate du littoral, on adopte une pression constante entre
0 et 10 m gale celle rgnant 10 m.
La hauteur H est compte partir du sol environnant suppos sensiblement horizontal dans un
grand primtre en plaine autour de la construction.
Lorsque le sol environnant la construction prsente des dnivellations avec fortes pentes, la
hauteur H est compte partir dun niveau infrieur celui du pied de la construction. Les cas
extrmes sont ci-aprs :
- Si la pente est infrieure ou gale 0,3, la hauteur H peut tre compte partir du pied
de la construction.
- Si la pente est gale ou suprieur 2, la hauteur H pour des constructions situes dans
une zone de largueur gale la diffrence de niveau z
2
-z
1
, partir de la ligne de crte,
doit tre compte partir du niveau du terrain au pied de la dnivellation.
H
Pente <0.3
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 9
Remarque :
Le diagramme des pressions en fonction de la hauteur H, qui est utilis pour le calcul des
constructions peut tre simplifi, sous rserve de donner des rsultats suprieurs ou quivalents pour
les sollicitations maximales tant que pour les ractions dappuis que pour les moments de flexion ou
de renversement.
b. Effet de site ks :
Les Rgles considrent trois types de sites :
Site protg : Fond de cuvette bord de collines sur tout son pourtour et protg ainsi pour
toutes les directions du vent.
Site normal : Plaine ou plateau de grande tendue pouvant prsenter des dnivellations peu
importantes, de pente infrieure (vallonnements, ondulations).
Site expos : Au voisinage de la mer : le littoral en gnral (sur une profondeur denviron 6
km) ; le sommet des falaises ; les les A lintrieur du pays : les valles troites les
montagnes isols ou leves
Les valeurs des pressions dynamiques de base normale et extrme dj dfinies doivent tre
multiplies par un coefficient de site k
s
gal :
Site protg
Site normal
Site expos
Rgion I Rgion II Rgion III Rgion IV
0 ,80
1,00
1,35
0,80
1,00
1,30
0,80
1,00
1,25
Pas de site protg
1,00
1,20
c. Effet de masque km :
Il y a effet de masque lorsquune construction est masque partiellement ou totalement par
dautres constructions ayant une grande probabilit de dure.
Leffet de masque peut se traduire :
Soit par une aggravation des actions du vent, lorsque la construction situe derrire le masque se
trouve dans une zone de sillage turbulent. Dans ce cas Il nest pas possible de formuler de
rgles ; seuls des essais en soufflerie peuvent donner des renseignements prcis.
Soit par une rduction des actions du vent dans les autres cas. Les pressions dynamiques de base
peuvent alors tre rduites de 25%, donc km = 0.75
Les surfaces intresses doivent remplir simultanment les deux conditions suivantes :
Z
2
- Z
1 Z
1
Z
2
H
Pente >2
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 10
- tre abrites entirement par le masque pour toutes les directions du vent dans le plan
horizontal.
- tre situes au-dessous de la surface dcrite par une gnratrice ayant une pente de 20%
vers le sol, dirige vers lintrieur du masque et prenant appui sur le contour apparent
des constructions protectrices.
d. Effet des dimensions o:
Les pressions dynamiques sexerant sur les lments constitutifs dune construction (panneaux,
potelets, lisses, poutres, poteaux, etc.) doivent tre affectes dun coefficient de rduction fonction
de la plus grande dimension (horizontale ou verticale) de la surface offerte au vent intressant
llment considr, et de la cote H du point le plus haut de cette surface.
Voir (ANNEXE 4).
e. Pression dynamique modifie :
f. Rduction maximale des pressions dynamiques de base
Pour les constructions dfinitives, la totalit des rductions autorises par les rgles Effet de
masque et Effet des dimensions ne doit, en aucun cas, dpasser 33%.
g. Valeurs limites des pressions dynamiques corriges
Les valeurs limites maximales ne sont pas applicables en Rgion IV.
Quels que soient la hauteur H au-dessus du sol, le site, leffet de masque et leffet des
dimensions, les valeurs de la pression dynamique corrige sont limites comme ci-dessous.
q = K
h
.K
s
.K
m
.o.q
10
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 11
Pression dynamique normale corrige.
Pression dynamique extrme corrige.
Valeurs maximales Valeurs minimales
170 daN/m
297.5 daN/m
30 daN/m
52.5 daN/m
III. CLASSEMENT DES CONSTRUCTIONS EN CATEGORIES :
Les Rgles dfinissent les constructions daprs leur:
1. Forme densemble : Les Rgles distinguent
Les constructions prismatiques base quadrangulaire.
Les constructions prismatiques base polygonale rgulire ou circulaire.
Les panneaux pleins et les toitures isoles.
Les constructions ajoures et les constructions en treillis.
Les constructions diverses ne rentrant pas dans les catgories prcdentes.
2. Position dans lespace : Les Rgles envisagent :
a. les constructions reposant sur le sol ou accoles un plan de grandes dimensions
(Immeuble ou mur) ;
b. les constructions arodynamiquement isoles dans lespace, pour lesquelles les distances au sol
et une paroi voisine sont respectivement suprieures ou gales leur dimension suivant la
verticale ou suivant une perpendiculaire cette paroi ;
c. les cas intermdiaires entre le cas a et le cas b ;
d. les constructions comprises entre deux plans parallles de grandes dimensions
(Immeubles ou murs).
3. Permabilit des parois :
Une paroi a une permabilit au vent de % si elle comporte des ouvertures de dimensions
quelconques dans la somme des aires reprsente % de son aire totale.
Daprs le degr de permabilit des parois, les rgles considrent trois types de constructions Une
construction est dite :
ferme : si ses parois prsentent des fuites et des petites ouvertures uniformment rparties, la
permabilit moyenne de ces parois 5%. Si toutes les parois ont une permabilit nulle,
paroi la de totale surface
ouvertures des surface
% =
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 12
cest dire si elles ne laissent absolument pas pass lair mme de faon accidentelle, la
construction est dite ferme tanche.
Partiellement ouverte : si lune des parois au moins prsente ou peut prsenter certains
moments une permabilit moyenne comprise entre 5 et 35% ;
Ouverte : si lune des parois au moins prsente ou peut prsenter certains moments une
permabilit 35%.
IV. ACTIONS STATIQUES EXERCEES PAR LE VENT :
1. Actions extrieures et actions intrieures :
Quelle que soit la construction, la face extrieure de ses parois est soumise :
- des succions, si les parois sont sous le vent .
- des pressions ou des succions, si elles sont au vent .
Ces actions sont dites actions extrieures Ce.
Dans les constructions fermes, ouvertes ou partiellement ouvertes, les volumes intrieurs
compris entre les parois peuvent tre dans un tat de surpression ou de dpression suivant
Lorientation des ouvertures par rapport au vent et leur importance relative. Il en rsulte sur les
faces intrieures des actions dites actions intrieures Ci.
2. Actions sur les parois
On rappelle que laction lmentaire unitaire du vent sur une face est donne par lexpression
(C.q)
Laction rsultante unitaire p sur une paroi : est la combinaison des actions lmentaires sur
chacune des faces de la paroi :
p = (Ce Ci) q
Laction rsultante totale P sur une paroi : est la rsultante P sur une paroi plane de surface S
est :
P = p S
3. Action densemble sur une construction.
Cest la rsultante gomtrique R

de toute les actions P

sur les diffrentes parois de la construction


peut tre dcompose :
Suivant la direction horizontale du vent en une composante T (trane) produisant un effet
dentranement et de renversement.
Suivant une verticale ascendante en une composante U (portance) produisant un effet de
soulvement et ventuellement de renversement.
V. ACTIONS DYNAMIQUES EXERCEES PAR LE VENT :
Aux effets statiques prcdemment dfinis, sajoutent des effets dynamiques qui dpendent
des caractristiques mcaniques et arodynamiques de la construction.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 13
Cas des surcharges normales.
Pour tenir compte de leffet des actions parallles la direction du vent, les pressions dynamiques
normales servant au calcul de laction densemble, sont multiplies chaque niveau par un
coefficient de majoration au moins gal lunit. Ce coefficient | est donn par la formule
) 1 ( t u | + = dans laquelle :
: Coefficient de rponse, est donn en fonction de la priode T du mode fondamental
doscillation et pour des ouvrages de divers degrs damortissement.
: coefficient de pulsation.
: coefficient global qui dpend du type de construction.
Pour les constructions prismatiques base polygonale rgulire ou circulaire lexception
des constructions usage dhabitation ou de bureau ou pour les ensembles prismatiques des
constructions ajoures ou des constructions en treillis = 1.
Pour les autres cas est donn en fonction de H
s
de leur sommet par :
o = 0.7 pour H
s
30 m.
o = 0.7 + 0.01 (H
s
30) pour 30 m H
s
60 m.
o = 1 pour H
s
60 m.
Voir ANNEXE 5.
Cas des surcharges normales extrmes.
Pour tenir compte de leffet des actions parallles la direction du vent, les pressions
dynamiques extrmes servant au calcul de laction densemble sont multiplies par lexpression
| ||
u
.
2
5 . 0 + au moins gale lunit.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 14
Chapitre 3 :
EFFET DU VENT SUR CONSTRUCTIONS
PRISMATIQUES A BASE QUADRANGULAIRE
1. CONSTRUCTIONS PRISMATIQUES A BASE RECTANQULAIRE REPOSANT
SUR LE SOL
a. Rapport de dimensions :
Pour une direction de vent donne, le rapport de dimensions est le rapport de la hauteur h
de la construction la dimension horizontale de la face frappe :
a
h
a
= et
b
h
b
=
b. Caractristiques :
leur forme gnrale en plan est un rectangle de dimensions a et b (ab) ;
leur hauteur totale est dsigne par h et la flche de leur toiture par f ;
leur couverture est :
- soit une toiture-terrasse,
- soit une toiture un, deux ou plusieurs versants plans,
- soit une toiture en vote,
- soit unique,
- soit multiple,
toutes leurs parois verticales sont sensiblement planes et reposent sur le sol ;
leurs parois verticales peuvent tre fermes ou bien partiellement ouvertes ou ouvertes sous
rserve quune paroi au moins sur les quatre soit ferme.
c. Coefficient
0
:
Ce coefficient est donn par le diagramme (ANNEXE 6)
pour un vent normal la grande face S
a
:
si 5 . 0
a
> par le quadrant suprieur gauche en fonction de
a
et de
a
b
;
si 5 . 0
a
< par le quadrant infrieur gauche en fonction de
b
;
pour un vent normal la petite face S
b
:
si 1
b
> par le quadrant suprieur droit en fonction de
b
et de
a
b
;
si 1
b
< par le quadrant infrieur droit en fonction de
a
;
f
h
b
a
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 15
2. ACTIONS EXTERIEURES
Actions moyennes.
Les coefficients de pression Ce donns ci-aprs correspondent un vent ne traversant pas la
construction. Lorsquil la traverse, certains coefficients peuvent ne plus tre valables
Parois verticales
- Vent normal
Face au vent Ce= +0.8 (quel que soit ) o
Face sous le vent Ce= - (1.3 ) 8 . 0 o
- Vent oblique
Dans certains cas particuliers o il serait ncessaire davoir une indication sur laction dun
vent oblique sur une paroi verticale.
Toitures uniques
Les coefficients de pression Ce applicables la toiture seule sont dtermines comme suit :
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 16
- Dans le cas de toitures versants plans dont la flche
2
h
f s ; les coefficients de pression Ce
sont dtermins par le diagramme en fonction de langle dinclinaison (en degrs) du versant
considr sur la direction du vent et du coefficient
o
(ANNEXE 7).
- Dans le cas de toitures versants plans dont la flche h f
5
h 4
s s ; les coefficients de pression
Ce sont considrs comme indpendants des coefficients o de la construction et sont
dtermins par le diagramme en fonction de langle dinclinaison (en degrs) du versant
considr sur la direction du vent (ANNEXE 8).
- Dans le cas de toitures versants plans dont la flche
5
h 4
f
2
h
s s ; les coefficients de pression
Ce sont dtermins par interpolation linaire entre les Valeurs lues pour les deux autres cas en
fonction du rapport
h
f
.
- Dans le cas de toitures en vote directrice circulaire parabolique ou en chanette dont la flche
f est comprise entre le dixime et la moiti de la corde a ou b (plein cintre) et infrieur aux
3
2
de la hauteur h de la construction, les coefficients de pression Ce sont dtermins par le
diagramme en chaque point de la vote en fonction de langle dinclinaison (en degrs) de la
tangente en ce point sur la direction du vent, et du coefficient
o
(ANNEXE 9).
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 17
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 18
3. ACTION INTERIEURES Ci.
La pression dynamique prendre en compte pour la dtermination des actions intrieures dans un
volume dtermin est pour chaque direction du vent, gale la pression dynamique, sexerant sur
la face extrieure correspondante du volume considr.
Les actions intrieures sont dtermines par des coefficients Ci calculs au moyen de formules
variables pour chaque cas. Lorsque ces dterminations conduisent des coefficients compris entre
0.20 et 0, on prend 0.20, et lorsquils sont compris entre 0 et + 0.15, on prend + 0.15.
Constructions fermes
Les parois ont une permabilit 5 s %.
On applique simultanment sur les faces intrieures de tous les compartiments :
soit une surpression avec Ci= + 0.6 (1.8 1.3 o ).
Soit une dpression avec Ci = - 0.6 (1.3 o - 0.8).
Constructions ouvertes comportant une paroi ouverte
La paroi ouverte a une permabilit 35 > %, les autres parois y compris les versants de
toiture ont des permabilits 5 s %.
On applique :
Lorsque la paroi ouverte est au vent :
- Une surpression avec Ci =+ 0.8 sur la face intrieure des parois fermes y compris les
versants de toiture.
- Une dpression avec Ci = - 0.6 (1.3
o
- 0.8) sur la face intrieure de la paroi ouverte.
Lorsque la paroi ouverte est sous le vent :
- Une dpression avec Ci = - (1.3 ) 8 . 0
o
sur la face intrieure des parois fermes y
compris les versants de toiture.
- Une surpression avec Ci = + 0.6 (1.8 1.3
o
) sur la face intrieure de la paroi ouverte.
Constructions ouverte comportant deux parois opposes ouvertes.
Les parois ouvertes ont une permabilit 35 > %, les autres parois ont des permabilits 5 s %.
Vent normal aux parois :
Parois situes dans le courant dair : on calcule les parties de la paroi ou de constructions
intrieures situes dans le courant dair, comme si elles taient isoles dans lespace abstraction
faite des autres parties de la construction.
Paroi situe hors du courant dair : on applique toutes les parties de parois ou de
constructions intrieures situes hors du courant dair.
Lorsque les parois de permabilit 35 > % sont normales au vent :
- Soit une surpression Ci =+ 0.6 (1.8 1.3 )
o
;
- Soit une dpression Ci = - 0.6 (1.3 ) 8 . 0
o
;
Lorsque les parois de permabilit 35 > % sont parallles au vent :
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 19
- Soit une surpression Ci = + 0.6 (1.8 1.3 )
o
:
- Soit une dpression Ci = - (1.3 ). 8 . 0
o
Remarque : cas de paroi partiellement ouverte
Lorsquon est en prsence de paroi partiellement ouverte les cfficients de pression Ci sont
dtermins par interpolation linaires partir des cas correspondants aux constructions fermes et
constructions ouvertes.
) 5 .(
5 35
) 5 ( Ci ) 35 ( Ci
) 5 ( Ci ) ( Ci

+ =
On fait interpolation entre valeurs de mme signe
4. ACTIONS RESULTANTES. (Ce Ci)
Pour chaque lment, on combine de la faon la plus dfavorable les actions extrieures moyennes
et les actions intrieures moyennes.
Lorsque cette combinaison conduit des coefficients compris entre 0.30 et 0, on prend 0.30 et
lorsquils sont compris entre 0 et +0.30, on prend +0.30.
Laction rsultante unitaire p sur une paroi : p = (Ce Ci) q
Avec q la pression dynamique modifie q = K
h
.K
s
.K
m
.o.q
10
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 20
CALCUL DES OSSATURES SELON
LE REGLEMENT EUROCODE 3
1. BASES DE CLCULS DU REGLEMENT EUROCODE:
2. CLASSIFICATION DES SECTIONS TRANSVERSALES :
1. JUSTIFICATION DES SECTIONS TRANSVERSALES :
2. LES PHENOMENES DINSTABILITE ELASTIQUE.
3. ORGANIGRAMMES RECAPITULATIFS DE CALCULS
4. ASSEMBLAGE PAR BOULONS
5. LES ASSEMBLAGES PAR SOUDURES
Chapitre 1 :
BASES DE CALCULS DU REGLEMENT EUROCODE
1. ETATS LIMITES :
Un tat limite est un tat particulier, au de la du quel une structure ne satisfait plus aux exigences
pour les quelles elle a t conue est dimensionne.
On distingue deux types dtats limites :
Ltat limite de service (E.L.S) qui correspond lutilisation courante et quotidienne de
louvrage et qui limite les dformations de la structure afin dviter des dsordres secondaires et
garantir la prennit de louvrage (limitation de la flche, de la fissuration du bton).
Ltat limite ultime (E.L.U) qui correspond un cas de charge exceptionnel ultime (par
exemple neige trentenaire, crue centenaire) pour le quel la stabilit de louvrage doit tre
garantie bien qutant la limite de la ruine. Un tat limite est atteint lorsque lon con, state un
perte dquilibre, une instabilit de forme, une rupture dlment, une dformation plastique
exagr
2. ACTIONS PRISES EN COMPTE DANS LES CALCULS :
Les actions agissant sur une structure sont de trois types :
Charges permanentes G:
- poids propre de tous les lments constituant louvrage termin.
- action de la prcontrainte,
- dplacement diffrentiel des appuis,
- dformation impose la construction.
Les actions variables Q:
- les charges dexploitation,
- action du vent,
- action de la neige,
- action des gradients thermiques (variation relative de longueur de 4.10
-4
+3.10
-4
, ce qui
correspond une variation de temprature de 33 +25, par rapport la temprature
ambiante).
Les actions accidentelles A:
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 21
- explosion,
- chocs de vhicules.
Ce dernier type dactions est rarement pris en compte ; uniquement sil est spcifi sur le cahier des
charges du march.
3. COEFFICIENTS PARTIELS DE SECURITE
Actions permanentes
Actions variables de
base
Actions variables
daccompagnement
Effet dfavorable 35 . 1
G
= 50 . 1
Q
= 50 . 1
Q
=
Effet favorable 00 . 1
G
= 0
Q
= 0
Q
=
Une action variable se prsente de plusieurs faons qui dpendent de la dure dapplication et de sa
frquence :
Valeur nominale : Q
Valeur de combinaison Q . 0
Valeur frquente : Q . 1
Valeur quasi-permanente : Q . 2
Les valeurs de figure dans le tableau suivant.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 22
4. COMBINAISONS DACTIONS :
Combinaisons dactions LELU.
Combinaison fondamentale :
Q1 : une action variable de base avec sa valeur nominale
Q : actions variables daccompagnement avec leurs valeurs de combinaison Q 0
Q . . Q . G .
0 Q 1 Q G
1
E + +
Combinaison simplifie : dont le but de simplifier cette combinaison, on, la remplace par
celle des combinaisons ci-aprs qui ce rvle la plus contraignante.
- Avec prise en compte uniquement de laction variable la plus dfavorable : Q . G .
Q G
+
- Avec prise en compte de toutes les actions variables dfavorables : Q . . 9 . 0 G .
0 Q G
E +
Combinaisons dactions LELS.
Elles servent exclusivement pour le calcul et la vrification des dformations (flches et
dplacements).
Combinaisons rares. Q . Q G
0 1
E + +
Combinaisons frquentes. Q . Q . G
2 1 1
E + +
Combinaisons quasi-permanentes. Q . G
2
E +
Les combinaisons dactions courantes sont donnes dans le tableau suivant :
Nombre dactions variables ELU
ELS
(vrification des dformations)
Avec prise en compte uniquement
de laction variable la plus
dfavorable
1.35 G
max
+ G
min
+ 1.5Q G + Q
Avec prise en compte de toutes les
actions variables dfavorables
1.35 G
max
+ G
min
+ 1.35 Q
i
G + 0.9 Q
i
avec G
max
: action permanente dfavorable
G
min
: action permanente favorable
Q: action variable dfavorable.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 23
5. VALEURS LIMITES DES DEFORMATIONS :
Le rglement EUROCODE 3 recommande des limites qui sont les suivantes et qui restent
approximatives :
verticalement
toitures en gnral
200
L
f =
250
L
2
< o
planchers en gnral
250
L
f =
300
L
2 < o
planchers supportant des poteaux
400
L
f =
500
L
2
< o
horizontalement
poteaux de portiques en gnral
125
h
u =
poteaux de portiques avec un pont
roulant
180
h
u =
f : flche dans ltat final, par rapport la droite reliant les appuis dune poutre.
0 2 1
f o o + o = .
o
0
: pr cintrage (contre flche) de la poutre non charg.
o
1
: variation de la flche de la poutre due aux charges permanentes immdiatement appliques
aprs la mise encharge.
o
2
: variation de la flche de la poutre due aux charges variables augmente de toutes les
dformations dans le temps due aux charges permanentes.
L : porte.
u : dplacement horizontal en tte de poteaux.
H : hauteur du poteau.
o
2
o
1
o
0
L
f
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 24
Chapitre 2 :
CLASSIFICATION DES SECTIONS TRANSVERSALES
LEUROCODE 3 a instaur une classification des sections transversales, en fonction de critres
divers :
Elancements des parois,
Rsistance de calcul,
Capacit de rotation plastique,
Risque de voilement local,
Etc.
Quatre classes de sections ont t dfinies, allant de la section de classe 1 (la plus performante) la
section de classe 4 (la plus fragile). Le tableau suivant dfini les quatre classes de sections
transversales.
Classe
Capacit
des sections
transversales
Modle
de
comportement
Rsistance
De
calcul
Capacit
de rotation
plastique
1
Les sections de classe 1 peuvent
former une rotule plastique avec
une capacit de rotation
importante.
Plastique sur section
complte
Importante
2
Les sections de classe 2 peuvent
former une rotule plastique mais
avec une capacit de rotation
limite.
Plastique sur section
complte
Limite
3
Les sections de classe 3 ne
peuvent pas former une rotule
plastique. Le moment flchissant
les sollicitant peut atteindre le
moment lastique M
el
mais le
voilement local est susceptible
dempcher le dveloppement du
moment plastique M
pl
.
Elastique sur section
complte
Aucune
4
Les sections de classe 4 ne
peuvent pas former une rotule
plastique. le voilement local est
susceptible dempcher le
dveloppement du moment
lastique M
el
.
Elastique sur section
efficace
Aucune
fy
f
y
fy
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 25
Remarque :
- Les diffrentes parois comprimes dune section transversale (me ou semelle) sont souvent de
classes diffrentes. La classe de la section sera, en ce cas, la classe (la plus dfavorable).
- Le fait de dterminer la classe dune section permet de choisir la mthode de calculs (analyse
plastique ou lastique).
- Dans le cas de sections uniformment comprimes, les lancements limites de parois pour les
classes 1 et 2 sont identiques ceux de la classe 3 car aucune capacit de rotation plastique nest
alors ncessaire (pas de rotule plastique) pour assurer une redistribution des sollicitions dans
llment considr.
- Les tableaux suivants permettent de dterminer la classe dune section. Les parois prsentant un
lancement suprieur llancement limite de la classe 3 sont de classe 4.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 26
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 27
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 28
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 29
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 30
Les profils lamins courants (I ou H), sollicits soit en compression seule, soit en flexion simple, les
tableaux suivants donnent directement les classes.
Acier : F
y
= 235 MPa
Type du profil
lamin
Rfrence du profil
Classe des sections
Compression seule Flexion seule
PA 80 160 1 1
IPEA
180 240 2 1
270 330 3 1
360 600 4 1
IPE
80 240 1 1
270 360 2 1
400 500 3 1
550 et 600 4 1
Acier : F
y
= 275 MPa
Type du profil
lamin
Rfrence du profil
Classe des sections
Compression seule Flexion seule
PA
80 140 1 1
160 2 1
IPEA
180 2 1
200 240 3 1
270 600 4 1
IPE
80 220 1 1
240 300 2 1
330 400 3 1
450 600 4 1
Acier : F
y
= 335 MPa
Type du profil
lamin
Rfrence du profil
Classe des sections
Compression seule Flexion seule
PA
100 et 120 1 1
140 2 1
160 3 1
IPEA
180 3 1
200 270 4 1
300 4 2
330 600 4 1
IPE
80 160 1 1
180 240 2 1
270 3 1
300 600 4 1
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 31
Acier : F
y
= 235 MPa
Type du profil
lamin
Rfrence du profil
Classe des sections
Compression seule Flexion seule
HEA
100 240 1 1
260 300 2 2
320 500 1 1
550 et 600 2 1
HEB 100 600 1 1
HEM 100 600 1 1
Acier : F
y
= 275 MPa
Type du profil
lamin
Rfrence du profil
Classe des sections
Compression seule Flexion seule
HEA
100 160 1 1
180 240 2 2
260 300 3 3
320 2 1
340 450 1 1
500 et 550 2 1
600 3 1
HEB
100 550 1 1
600 2 1
HEM 100 600 1 1
Acier : F
y
= 335 MPa
Type du profil
lamin
Rfrence du profil
Classe des sections
Compression seule Flexion seule
HEA
100 et 120 1 1
140 et 160 2 2
180 0 340 3 3
360 2 2
400 et 450 2 1
500 3 1
550 et 600 4 1
HEB
100 450 1 1
500 et 550 2 1
600 3 1
HEM 100 600 1 1
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 32
Mthode de dtermination des sections efficaces :
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 33
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 34
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 35
Chapitre 3 :
JUSTIFICATION DES SECTIONS TRANSVERSALES
SELON LE REGLEMENT EUROCODE 3
1. CARACTERISTIQUES DES ACIERS :
Comportement des aciers doux:
Les principales caractristiques mcaniques des aciers de construction sont :
le module dlasticit longitudinale E = 210000 MPa ;
le module dlasticit transversale G = E/[2(1+v)]= 81000 MPa ;
le coefficient de poisson v = 0.3 ;
le poids volumique de lacier = 78.5 KN/m
3
.
Coefficient de dilatation linaire = 12.10
-6
/C
Nous nous limitons en construction trois nuances principales (S.235 est utilise dans la majorit
des cas, S.275 et S.355 plus rarement)
Caractristiques mcaniques des aciers
en fonction de leur paisseur t
Nuance des aciers
S.235 S.275 S.355
Limites lastique f
y
(MPa)
t 16 mm
16 t 40 mm
40 t 63 mm
235
225
215
275
265
255
355
345
335
Contraintes de rupture en traction f
u
(MPa)
t 3 mm
3 t 100 mm
360/510
340/470
430/580
410/560
510/680
490/630
Allongement minimal moyen
t 3 mm
3 t 150 mm
18%
23%
15%
19%
15%
19%
2. CARACTERISTIQUES DES SECTIONS TRANSVERSALES :
a. Section brute A : Les caractristiques de la section brute sont dtermines en utilisant les
dimensions nominales sans dduction des trous ventuels.
b. Aire nette : Laire nette (A
net
) dune section transversale est gale son aire brute diminue des
aires des trous.
E
o
B
A
o
c
f
y
f
u
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 36
3. COEFFICIENTS PARTIELS DE SECURITE :
Les coefficients partiels de scurit pour vrifier la rsistance des sections sont donns dans le
tableau suivant :
Classe des sections 1,2 et 3 4
Section brute

M0
= 1 si lacier agrs

M0
= 1.1 si lacier non agrs

M1
= 1.1
Section nette au droit des trous
M2
=1.25
4. RESISTANCE DES SECTIONS TRANSVERSALES :
a. Effort axial de traction (N
T
):
Dans un lment sollicit en traction axiale, leffort de traction N dans chaque section transversale
doit satisfaire la condition :
N
T
N
R
Avec N
R
= min (N
pl
; N
u
; N
net)
dfinie dans le tableau suivant :
0 M
y
pl
f . A
N

= Rsistance plastique de la section brute


2 M
u net
u
f . A 9 . 0
N

=
Rsistance ultime de la section nette au droit des trous de fixation
0 M
y net
net
f . A
N

=
Rsistance plastique de la section nette pour les assemblages par
boulons prcontraints lELU
f
Y
: limite dlasticit dun acier.
f
u
: contrainte de rupture dun acier.
b. Effort axial de compression (N
C
) :
Dans un lment sollicit en compression axial, leffort de compression N
C
dans chaque section
transversale doit satisfaire la condition :
N
C
N
R
Avec N
R
dfini dans le tableau suivant
Classes N
R
1,2 et 3
0 M
y
R
f . A
N

= Rsistance plastique de la section brute


4
1 M
y eff
0 R
f . A
N N

= = Rsistance de calcul de la section brute au voilement local


A
eff
= aire efficace de la section.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 37
c. Moment flchissant (M) :
En labsence deffort tranchant, le moment flchissant M dans chaque section transversale doit
satisfaire la condition :
M M
R
Avec M
R
dfini dans le tableau suivant
Classes M
R
Rsistance au moment flchissant
1 ou 2
0 M
y pl
PL
f . W
M

= Moment de rsistance plastique de la section brute


3
0 M
y el
el
f . W
M

= Moment de rsistance lastique de la section brute


4
1 M
y eff
0
f . W
M

= Moment de rsistance de la section brute au voilement local


W
el
: module de rsistance lastique
W
pl
: module de rsistance plastique
W
eff
: module de rsistance efficace
d. Effort tranchant (V) :
Leffort tranchant V dans chaque section transversale doit satisfaire la condition :
0 M
v y
pl
A . f 58 . 0
V V

= s
(Av : Aire de cisaillement qui peut tre dtermin partir du tableau suivant.)
V
pl
: La valeur de calcul de rsistance plastique au cisaillement
Type de profils A
v
= aire de cisaillement (effort parallle lme
Profils lamins I ou H A- 2 b t
f
+(t
w
+2r) t
f
Profils lamins U A- 2 b t
f
+(t
w
+r) t
f
Profils reconstitus souds I ou H (h- 2 t
f
) t
w
e. Moment flchissant et effort tranchant (M+V):
Le moment de rsistance plastique dune section transversale est rduit par lexistence de
cisaillement.
- Si leffort tranchant est faible V 0.5 V
pl
, cette rduction est ngligeable (et compense par
lcrouissage du matriau).
M M
R
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 38
- Mais, lorsque leffort tranchant V > 0.5 V
pl
, il faut prendre en compte son interaction sur le
moment de rsistance plastique
M M
v
M
V
: moment rsistant plastique rduit du fait de leffort tranchant, dtermin en utilisant une
limite dlasticit rduite f
red
pour laire de cisaillement seule, soit :
f
red
= (1-) f
y
=
2
pl
1
V
V 2
(


Pour les sections transversales semelles gales et flchies suivant laxe de forte inertie, on
obtient :
0 M
y
w
v
pl v
f
t 4
A
W M


=
Qui peut se reprsenter graphiquement comme ci-dessous :
V/V
pl
f. Flexion bi axiale (dvie) (M
y
+ M
z
) :
A. Sections de classe 1 et 2 :
On doit vrifier que 1
M
M
M
M
plz
z
2
ply
y
s
(
(

+
(
(

B. Sections de classe 3 :
Les sections de classes 3 sont considres comme satisfaisante, si la contrainte normale maximale
vrifier la condition :
0 M
y
elz
z
ely
y
f
W
M
W
M

s + = o
Ou autrement 1
M
M
M
M
elz
z
2
ely
y
s
(

+
(
(

0.5 1
M
semelles
M
R
M
pl
M
V
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 39
g. Moment flchissant + effort axial (M+N) :
A. Sections de classe 1 et 2 :
On doit vrifier que M M
N
M
N
= moment rsistant plastique rduit du fait de leffort axial ;
- Pour un plat :
(
(

|
|
.
|

\
|
=
2
pl
l
p N
N
N
1 M M
On doit donc vrifier : 1
N
N
M
M
2
pl pl
s
(
(

+
(
(

- Pour une section comportant des semelles :


Laire de lme : A
w
= A 2 b t
f
a. Si leffort normal est faible N min [0.25 N
pl
; 0.5 A
w
f
y
/
M0
]
alors M
N
=M
pl
b. Si leffort normal est important N > min [0.25 N
pl
; 0.5 A
w
f
y
/
M0
], les valeurs de M
N
sont
donnes au tableau suivant :
Mode de flexion Valeur de M
N
Autour de yy M
N
= M
pl
[(1-n)/(1-0.5a)]
Autour de zz M
N
= M
pl
[1-((n-a)/(1-a))
2
]
Flexion bi axiale pour des sections
en I ou H
(M
Y
/M
Ny
)

+( M
Z
/M
NZ
)

1
= 2 et = 5n ( 1)
a = min ( A
W
/A ; 0.5 ) ; n = N / N
pl
B. Sections de classe 3 :
Les sections de classes 3 sont considres comme satisfaisante, si la contrainte normale maximale
vrifier la condition :
0 M
y
elz
z
ely
y
f
W
M
W
M
A
N

s + + = o
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 40
C. Sections de classe 4 :
Les sections de classe 4 sont considres comme satisfaisante, si la contrainte normale maximale
calcule en utilisant les largeurs efficaces des parois comprimes, vrifier la condition :
( )
( )
1 M
y
) eff ( elz
z z
) eff ( ely
y y
eff
f
W
Ne M
W
Ne M
A
N

s
+
+
+
+ = o
- A
eff
= aire de la section transversale suppose soumise une compression uniforme (M=0);
- W
eff
= module de rsistance de la section efficace, la section transversale tant suppose
soumise uniquement un moment flchissant suivant laxe concern (N = 0) ;
- e = dcalage de laxe neutre concern, la section transversale tant suppose soumise une
compression uniforme (M = 0).
h. Moment flchissant +effort tranchant + effort axial (M + N + V) :
- Si leffort tranchant est faible V 0.5 V
pl
, On fait comme si leffort tranchant
nexiste pas
- Mais, lorsque leffort tranchant V > 0.5 V
pl
, il faut prendre en compte son effet,
ainsi que celui de leffort axial, pour calculer le moment rsistant plastique rduit.
La rsistance de calcul de la section transversale aux combinaisons de moment et effort axial doit
tre calcule en utilisant une limite dlasticit rduite f
red
pour laire de cisaillement A
v
.
f
red
= (1-) f
y
= (2V/V
pl
1.)
2
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 41
Chapitre 4 :
LES PHENOMENES DINSTABILITE ELASTIQUE
Le calcul dune structure exige que, sous toutes les combinaisons dactions possibles, dfinies
rglementairement, la stabilit statique soit assure,
- tant globalement, au niveau de la structure
- quindividuellement au niveau de chaque lment.
Les actions dveloppent diverses sollicitations, qui gnrent des contraintes au sein du matriau et
des dformations des lments.
Il sagit donc, afin de garantir le degr de scurit souhait ou souhaitable, de vrifier que les
contraintes et les dformations restent en de des limites admissibles.
A. LE FLAMBEMENT
formule dEULER.
La force critique partir de laquelle apparat le phnomne de flambement est dfinie par Euler de
la manire suivante :
L
EI
F
c
c
t
=
Fc: force critique.
E : module d'lasticit longitudinale, caractristique du matriau.
I : moment quadratique minimal de la section de la pice.
L
c
: longueur libre de flambement dpendant de la longueur relle de la pice et du mode de fixation
des extrmits.
Conditions
dappuis
Elment bi
articule
Elment
articul -
encastr
Elment libre-
encastre
Elment bi
encastre
Elment bi
encastre
avec translation
Flambement
simple
Lc L 0.7L 2L L/2 L
Fc
L
EI
Fc
t
=
L
EI 2
Fc
t
=
L 4
EI
Fc
t
=
L
EI 4
Fc
t
=
L
EI
Fc
t
=
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 42
On remarquera que la force critique dpend de :
- La gomtrie de la section travers le moment quadratique.
- La longueur de la pice (longueur relle et du mode de fixation des extrmits).
Rayon de giration :
S
I
i
z
z
=
S
I
i
y
y
=
Elancement : Soit lancement
i
Lc
=
Aspect rglementaire du flambement
La thorie dEuler, tablie pour des structures idales, est trs insuffisante, en regard des
imperfections de centrage, de rectitude, de verticalit et de la prsence de contraintes rsiduelles.
Il est donc ncessaire de prendre en compte ces imperfections ou leurs effets. Les rglements ont
notamment dfini un facteur dimperfection o.
1. Flambement simple :
Le risque de flambement nest considrer que si 2 , 0 > ; dans ce cas, la sollicitation N de
compression doit satisfaire :

|
_ s
1 M
y
A
f
. A . . N
Avec :
-
1
A
= |
: pour les sections transversales de classe 1, 2 ou 3
-
A
Aeff
A
= |
: pour les sections transversales de classe 4
- _ : est le coefficient de rduction pour le mode de flambement considrer.
Pour les lments section transversale constante, sollicits en compression axiale constante, la
valeur de _ pour llancement rduit , peut tre dtermine par la formule :
1 mais
2 2
1
5 , 0
s _
(


| + |
= _
O :
- ( ) | |

+ o + = |
2
2 , 0 1 5 , 0
- o : est un facteur dimperfection
-
| | |
|
.
|

\
|

=
(
(

| =
A
N
cr
f
y
. A .
A
5 , 0
1
5 , 0
- : est llancement pour le mode de flambement considrer.
-
c =
(
(

t =

. 9 , 93
f
y
E
5 , 0
1
-
( )
mm
/ N en
f
f
y
235 2
y
5 , 0
(
(

= c
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 43
- N
cr
: est leffort axial critique lastique pour le mode de flambement appropri.
Le facteur dimperfection o correspondant la courbe approprie de flambement vaut :
Courbe de flambement a b c d
Facteur dimperfection o 0,21 0,34 0,49 0,76
Les courbes de flambement sont les
courbes donnant le coefficient de
rduction _ en fonction de llancement
rduit
Plus simplement et plus rapidement, _ peut tre obtenu en fonction de llancement rduit , au
moyen du tableau suivant :
Coefficients de rduction

Valeurs de _ pour la courbe de flambement


a b c d
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
2,1
2,2
2,3
2,4
2,5
2,6
2,7
2,8
2,9
3,0
1,0000
0,9775
0,9528
0,9243
0,8900
0,8477
0,7957
0,7339
0,6656
0,5960
0,5300
0,4703
0,4179
0,3724
0,3332
0,2994
0,2702
0,2449
0,2229
0,2036
0,1867
0,1717
0,1585
0,1467
0,1362
0,1267
0,1182
0,1105
0,1036
1,0000
0,9641
0,9261
0,8842
0,8371
0,7837
0,7245
0,6612
0,5970
0,5352
0,4781
0,4269
0,3817
0,3422
0,3079
0,2781
0,2521
0,2294
0,2095
0,1920
0,1765
0,1628
0,1506
0,1397
0,1299
0,1211
0,1132
0,1060
0,0994
1,0000
0,9491
0,8973
0,8430
0,7854
0,7247
0,6622
0,5998
0,5399
0,4842
0,4338
0,3888
0,3492
0,3145
0,2842
0,2577
0,2345
0,2141
0,1962
0,1803
0,1662
0,1537
0,1425
0,1325
0,1234
0,1153
0,1079
0,1012
0,0951
1,0000
0,9235
0,8504
0,7793
0,7100
0,6431
0,5797
0,5208
0,4671
0,4189
0,3762
0,3385
0,3055
0,2766
0,2512
0,2289
0,2093
0,1920
0,1766
0,1630
0,1508
0,1399
0,1302
0,1214
0,1134
0,1062
0,0997
0,0937
0,0882
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 44
B. Flambement + flexion
Les lments sollicits simultanment en flexion et en compression axiale, doivent satisfaire
diverses conditions, selon la classe de leur section transversale.
- Sections de classe 1 et 2 :
1
.
.
N
1 M
plz
z z
1 M
ply
y y
1 M
pl
min
M
M k
M
M k
N
s + +

_
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 45
Avec :
-
f
N
y
pl
A. =
-
f
W M
y
pl pl
. =
-
5 , 1
. .
1 s =
k
f
k y
y y
y
y
avec
A
N
_

-
( ) 9 , 0 4 2 s
(
(


+ =
|

y
ely
ely ply
My
y
y
avec
W
W W
-
5 , 1
.
.
1 s =
k
f
k z
y z
z
z
avec
A
N
_

-
( ) 9 , 0 4 2 s
(
(


+ =
|

z
elz
elz plz
Mz
z
z
avec
W
W W
-
_
min
: est la plus petite des valeurs de
_ _
z y
et
-
_ _
z y
et
: sont les coefficients de rduction dfinis prcdemment.
-
| |
Mz My
et
: sont les facteurs de moment uniforme quivalent pour le
flambement par flexion ;
Si le dversement reprsente un mode potentiel de ruine, il faut galement vrifier :
1
.
.
.
.
N
1 M
plz
z z
1 M
ply
LT
y LT
1 M
pl
z
M
M k
M
M k
N
s + +

_

_
Avec :
-
1 1 s =
k
f
k LT
y z
LT
LT
avec
A
N
_

- 9 , 0 15 , 0 15 , 0 s =
|

LT MLT
z
LT
avec
- . : t dversemen le pour quivalent uniforme moment de facteur un est
MLT
|
- Sections de classe 3 :
Les formules tablies pour les sections 1 et 2, que ce soit avec ou sans risque de dversement,
restent valables la condition de remplacer
. . par .
f W M f W M y el el y pl pl
= =
- Sections de classe 4 :
Les formules deviennent, en introduisant les sections et modules efficaces :
1
. N .
. N .
. .
N
1 M
y
z . eff
Nz z z
1 M
y
y . eff
Ny y y
1 M
y
eff
min
f
W
e M k
f
W
e M k
f
A
s
+
+
+
+

_
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 46
Si le dversement reprsente un mode potentiel de ruine, il faut galement vrifier :
1
. N .
.
. N .
. .
N
1 M
y
z . eff
Nz z z
1 M
y
y . eff
LT
Ny y LT
1 M
y
eff
z
f
W
e M k
f
W
e M k
f
A
s
+
+
+
+

_

_
Les facteurs de moment uniforme quivalent
| | |
MLT Mz My
et ,
doivent tre calculs en fonction de
lallure du diagramme des moments flchissant entre points de maintien. (Voir tableau suivant)
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 47
Chapitre 6 :
ASSEMBLAGE PAR BOULONS
I. PRECAUTIONS CONSTRUCTIVES.
Les assemblages constituent des zones particulires plus fragiles que les zones courantes des
pices, car les sections sont rduites du fait des perages ou la nature de lacier affaiblie par la
chauffe du soudage. En outre, les assemblages sont soumis des sollicitations qui peuvent
sinverser et les contraintes peuvent changer de sens (une poutre de charpente peut flchir dans le
sens positif sous charge de neige et dans le sens ngatif sous soulvement par le vent).
Cest pourquoi il faut tre particulirement vigilant dans la conception et le calcul des assemblages,
afin de se prmunir contre tout risque de rupture brutale.
Il faut assurer, au travers de lassemblage la transmission parfaite des forces, afin de ne pas crer
deffort ou de moments secondaires parasites .Pour cela, quelques prcautions lmentaires sont
prendre :
1. il faut proscrire tout assemblage par recouvrement simple (figure6) et utiliser un assemblage
symtrique par double couvre joint (figure 7).
En effet, dans le cas de la figure 6, la dissymtrie cre un moment de flexion parasite et
lassemblage se dforme, comme le montre la figure 8.
La contrainte maximale de traction vaut, pour une largeur b de tle :
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 48
I
v . M
S
N
+ = o Avec

=
=
=
6
be
v
I
2
e
. N M
e . b S
La valeur de la contrainte est donc :
- dans le cas de la figure 1 :
e . b
N . 4
= o
- dans le cas de la figure 2 :
e . b
N
= o
La contrainte est donc quadruple et les ttes de boulons risquent larrachement.
Il faut par ailleurs sassurer que les axes neutres des barres soient concourants aux nuds des
treillis, dans les systmes rticuls .Ce nest souvent pas le cas pour les treillis raliss en cornires.
II. ASSEMBLAGES BOULONNES :
Le fonctionnement mcanique des assemblages boulonns sollicits au
cisaillement diffre selon le mode de boulonnage utilis.
Les boulons ordinaires
Les boulons prcontraints.
Caractristiques des boulons :
Caractristiques gomtriques :
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 49
Caractristiques mcaniques :
Caractristiques mcaniques des boulons selon leur classe dacier
Valeur de la limite dlasticit f
yb
et de la rsistance la traction f
ub
des boulons
Classe de qualit 4.6 4.8 5.6 5.8 6.6 6.8 8.8 10.9
f
yb
(N/mm
2
) 240 320 300 400 360 480 640 900
f
ub
(N/mm
2
) 400 400 500 500 600 600 800 1000
La classe est dfini par deux nombres X.Y sachant que : XY 10 fyb = et X 100 fub = en MPa.
III. ASSEMBLAGES PAR BOULONS ORDINAIRES :
1. Coefficients partiels de scurit :
- Rsistance des boulons au cisaillement : 25 . 1 Mb =
- Rsistance des boulons la traction : 50 . 1 Mb =
2. Assemblages sollicits au cisaillement
Critre de vrification : Il faut vrifier :
) F , F ( min V
B v 1
s
- dune part la rsistance au cisaillement des boulons,
- dautre part la rsistance la pression diamtrale des pices.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 50
V
1
: effort de cisaillement appliqu un boulon (
n
V
V
1
= ) ; n : nombre de boulons.
Rsistance au cisaillement dun boulon :
Si le plan de cisaillement passe par la partie filet
- Pour les classes de qualit 4.6 5.6 6.6 et 8.8 :
Mb
s
ub v
m . A
f 6 . 0 F

=
- Pour les classes de qualit 4.8 5.8 - 6.8 et 10.9:
Mb
s
ub v
m . A
f 5 . 0 F

=
Si le plan de cisaillement passe par la partie non filet :
Mb
ub v
m . A
f 6 . 0 F

=
m : nombre de sections cisailles par boulon
Rsistance la pression diamtrale des pices assembles :
Mb
u B
t
d f 5 . 2 F

o =
O o est la plus petites des valeurs suivantes.
(

= o 1 ,
f
f
,
4
1
d 3
P
,
d 3
e
min
u
ub
0
1
0
1
3. Assemblages sollicits la traction :
Critre de vrification :
T F T s
T : effort de traction appliqu un boulon.
La rsistance la traction des boulons vaut :
Mb
s
ub T
A
f 9 . 0 F

=
4. Assemblages sollicits simultanment au cisaillement et la traction :
Critre de vrification : Les boulons sont soumis des efforts combins de cisaillement V et de
traction T, doivent satisfaire aux conditions suivantes :
1
F 4 . 1
T
F
V
T v
s +
V : effort de cisaillement appliqu un boulon.
T : effort de traction appliqu un boulon.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 51
Rsistance de
cisaillement par plan
de cisaillement F
v
25 . 1 Mb =
m : nombre de
sections cisailles par
boulon
Le plan de
cisaillement passe par
la partie filete du
boulon
les classes de qualit
4.6 5.6 -6.6 et 8.8
Mb
s
ub v
m . A
f 6 . 0 F

=
les classes de qualit
4.8 5.8 - 6.8 et 10.9
Mb
s
ub v
m . A
f 5 . 0 F

=
Le plan de cisaillement passe par la partie non
filete du boulon
Mb
ub v
m . A
f 6 . 0 F

=
Rsistance la
pression diamtrale
des pices
assembles :
o o est la plus petites des valeurs suivantes.
(

= o 1 ,
f
f
,
4
1
d 3
P
,
d 3
l
min
u
ub
0
1
0
1
Mb
u B
t
d f 5 . 2 F

o =
25 . 1 Mb =
La rsistance la traction des boulons
5 . 1 Mb =
Mb
s
ub T
A
f 9 . 0 F

=
Assemblages sollicits simultanment au cisaillement et la
traction
1
F 4 . 1
T
F
V
T v
s +
IV. ASSEMBLAGES PAR BOULONS PRECONTRAINTS (HR) :
Si F
p
est leffort de prcontrainte axial dans un boulon et F
s
leffort de cisaillement transmis
par lassemblage et sollicitant ledit boulon, il faut vrifier que linterface des pices en contact
puisse transmettre leffort tangent, sans glissement, soit :
p s
F F s
Le coefficient de frottement doit correspondre sa valeur de calcul. Cela ncessite une
prparation des surfaces, par brossage ou grenaillage, pour liminer toute trace de rouille et de
calamine, de graisse, etc
Classement Description du traitement
classe A
Surfaces dcape par grenaillage ou sablage et mtallises par
projection daluminium.
Surfaces dcape par grenaillage ou sablage et mtallises par
projection dun revtement base de zinc, garanti dassurer un
coefficient de glissement qui ne doit pas tre infrieur 0.5
50 . 0 =
Axe du boulon
F
s
F
p
F
p
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 52
classe B Surfaces dcape par grenaillage ou sablage et peintes 40 . 0 =
classe C Surfaces nettoyes par brossage mtallique ou la flamme
avec enlvement de toutes les plaques de rouille non
adhrentes. 30 . 0 =
classe D Surfaces non traites. 20 . 0 =
Caractristiques mcaniques des boulons HR
Il existe deux classes de boulons HR, dfinies en fonction de leur contrainte limite dlasticit f
yb
et
de leur contrainte de rupture f
ub
.
Les boulons HR1 ou HR 10.9
Les boulons HR2 ou HR 8.8
Repre
Appellation
f
ub
(MPa) f
yb
(MPa) AL/L (%)
HR 1 HR 10.9 1000 900 > 8
HR 2 HR 8.8 800 640 > 12
1. Assemblages rsistant au glissement.
Rsistance au glissement.
La rsistance au glissement F
s
dun boulon HR prcontraint vaut :
MS
p
s s
F
. . m . k F

=
Avec :
F
p
: leffort de prcontrainte autoris dans les boulons vaut :
s ub p
A . f . 7 , 0 F =
m : nombre dinterfaces de frottement,
Ks : est un coefficient de la dimension des trous de perage et vaut :
Types de trous ks
Trous normaliss (tolrances normales)
1 mm pour les boulons d12 et d14
2 mm pour les boulons d16 d 24
3 mm pour les boulons d27 et plus
1
Trous circulaires surdimensionns et les trous oblongs
courts
0.85
Trous oblongs longs 0.7
MS Coefficients partiels de scurit :
Trous normaliss et oblongs dont laxe de la fente
est perpendiculaire la direction de leffort
ELU
ELS
1.25
1.1
Trous circulaires surdimensionns et oblongs dont
laxe de la fente est parallle la direction de
leffort
ELU 1.40
2. Assemblages sollicits simultanment au cisaillement et la traction :
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 53
Si un assemblage rsistant au glissement est soumis un effort de traction T concomitant un effort
de cisaillement V, qui tend provoquer le glissement.
La rsistance au glissement par boulon doit tre calcule selon la formule ci-aprs.
MS
P
S S V
) T . 8 , 0 F (
. . m . k F F

= s
3. Assemblages par platines sollicits par un moment flchissant, un effort tranchant.
Rsistance de lassemblage leffort tranchant V :
Il faut vrifier leffort admissible V
1
par boulon et par plan de glissement :
MS
p
s s 1
F
. . m . k F
n
V
V

= s =
n: nombre de boulons.
Rsistance de lassemblage au moment flchissant:
le moment rsistant M
R
de lassemblage est obtenu par la somme des produits des efforts de traction
dans les boulons situs dans la zone tendue par la distance des boulons respectifs la face intrieure
de la semelle comprime:
F
V
T
M>0
V
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 54
M
R
=N
1
.d
1
+N
2
.d
2
+.= N
i
.d
i
Efforts N
i
dans les boulons :
.....
d
N
d
N
d
N
3
3
2
2
1
1
= = =
Soit n: nombre de files verticales de boulons.
M
R
= [N
1
. d
1
+ N
2
. d
2
+ N
3
.d
3
+ ].n
=n. ...
d d d
.[
d
N 2
3
2
2
2
1
1
1
+ + + ]
=n.
d
.
d
N 2
i
1
1
E
Do :
d
'. n
d
.
M
N
2
i
1 R
1
E
= Ou bien encore
p
2
i
i R
i
F '. n
.
d
d M
N
s
E
=
La condition de rsistance de lassemblage doit vrifier que M
R
> M
e
.
d
1
d
2
d
3
d
4
d
5
N
1
M
N
1
N
2
N
3
N
2
V
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 55
Chapitre 7 :
LES ASSEMBLAGES PAR SOUDURES
I. DISPOSITIONS CONSTRUCTIVES
1. Soudures bout bout
Jusqu des paisseurs de pices de 5 6 mm, les soudures peuvent tre effectues sur des
pices non chanfreines, affranchies dquerre (A).
Au-del de 6 mm, il faut raliser des chanfreins sur les rives dassemblage, le talon C devant
tre infrieure la plus petite des 2 valeurs : 3 mm ou t/5
- Les chanfreins en V (B) et en U (C) permettent de souder sans retourner la pice, mais donnent
lieu, lors du refroidissement, des dformations angulaires fortes. Le chanfrein en U est plus
onreux, du fait de lusinage.
- Les chanfreins en double U (D ) ou en double V (E ), symtriques, liminent les phnomnes de
dformations ou de contraintes internes , si les cordons sont excuts simultanment sur les 2
faces ,par tronons alterns .En outre , ils permettent une conomie sur le mtal d apport et sur
le temps de main- d uvre,( nombre de passes).
- Les chanfreins en K (F) constituent une solution intermdiaire.
2. Soudures dangle
Les cordons peuvent tre plats et / ou bombs.
d =1 3
t < 6
A
t =5 15
60
c
B
c
t /2
t = 10 25
C
t = 30 60
c
t/2
D
E
60
t = 12 40 t = 12 40
50
F
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 56
c. Soudures en T
t (mm) 4 6 7 8 10 12 14 16 18
a (mm) 3 4 5 6 7 8 10 11 13
II. Calculs des cordons de soudures
1. Les soudures bout bout :
Les soudures bout bout ne se calculent pas. On admet qu il y a continuit de matire, donc
continuit des pices. Deux conditions doivent tre vrifies :
- lpaisseur de la soudure soit au moins gale lpaisseur de la plus faible des pices
assembles
- que le mtal dapport ait des caractristiques mcaniques au moins gale celle du mtal de
base.
2. Soudures dangle :
Notations
- a : paisseur utile ou gorge, distance minimale de la racine la surface du cordon (figure 32)
- l : longueur utile du cordon.
- N: effort pondr appliqu chaque cordon, il est suppos centr au milieu de la longueur du
cordon.
- o, t , t : sont les composantes de la contrainte moyenne rapporte la section de la gorge du
cordon, al. Soit :
o : composante perpendiculaire la section.
t : composante dans le plan de la section perpendiculaire laxe longitudinal du
cordon.
t : composante dans le plan de la section parallle laxe longitudinal du
cordon.
mm t 12 s mm t 25 s mm t 25 >
a
t
a a a
a
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 57
3. Formule fondamentale
Les dimensions du cordon de soudure doivent satisfaire la condition :

t t o
|
s + +
Mw
u
2 2 2
w
f
) .( 3 .
Les coefficients |
w
et
Mw
sont variables selon la nuance dacier :
Nuances dacier
Mw
|
w
|
w
.
Mw
f y
(MPa)
f u
(MPa)
235
275
355
360
430
510
1,25
1,30
1,35
0,80
0,85
0,90
1,00
1,10
1,20
Nous allons tablir ci-aprs des formules de calculs pour des cordons reliant :
- soit des pices orthogonales
- soit des pices obliques.
4. Cordons reliant des pices orthogonales
Les cordons peuvent tre frontaux,
Latraux et obliques.
Cordons frontaux
N
l N/2
N/2
N/2
N
N
N
N
N
l
N
l
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 58
N
n
=N
2
2
, dou
l a . 2
2 . N
l . a
Nn
E
=
E
= o
2
2
N N = , do t =
l . a . 2
2 . N
l . a
N
E
=
E
N = 0, do t =0
La formule fondamentale scrit :

E E
|
s +
Mw
u
2
2
2
2
2
2
w
f
) l (
a
N
) l (
a
N
. . 4
. 6
. . 4
. 2
.
Soit :
f u
Mw w
2 . N
. . l . a
|
> E
Cordons latraux
o =t =0
t =
l a
N
E .
La formule scrit :
f
3 . N
. . l . a
u
Mw w
| > E
Cordons obliques
o =t =
l . a . 2
sin . N
E
o
t =
l . a
cos . N
E
o
Dou :
f
sin
u
2
Mw w
3 . N
. . l . a
o
> E
|
l
N/2
N/2
N
N
N
N
N
o
t

2
N
l
l
N
o
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 59
5. Cordons reliant des pices obliques
u : Dsignant langle dune des faces dassemblage avec la perpendiculaire lautre face, on
distingue de la mme faon des cordons frontaux, latraux et obliques.
Cordons frontaux
Pour langle obtus :
)
2 4
cos(
l . a
N u

t
E
= o
t = )
2 4
sin(
l . a
N u

t
E
t = 0
Dou
f u
Mw w
sin 2 . N
. l . a
u
> E
|
Pour langle aigu :
Un calcul analogue conduit :
f u
Mw w
sin 2 . N
. l . a
u +
> E
|
Cordons latraux
De la mme faon que pour des pices orthogonales, on vrifie quel que soit langle, obtus ou
aigu, que :
f u
Mw w
3 . N
. l . a
|
> E
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 60
Cordons obliques
Dans le cas de cordons obliques, faisant un angle o avec la direction de leffort, on a :
Pour un angle obtus
f
sin
u
2
Mw w
). sin 1 ( 3 N
. l . a
o u +
> E
|
Pour un angle aigu
f
sin
u
2
Mw w
). sin 1 ( 3 N
. l . a
o u
> E
|
6. Formule enveloppe :
Il existe une formule enveloppe, qui dispense de tous les calculs prcdents, qui place en scurit,
quelle que soit lorientation de leffort et du cordon de soudure :
f u
Mw w
3 N
. l . a
|
> E
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 61
METHODE DE DETERMINATION DE LONGUEUR DE
FLAMBEMENT
1. Coefficient dencastrement en un nud :
On dsigne ici par :
La rigidit dun poteau, le rapport du moment dinertie de sa section pour le plan de flambement
considr la hauteur dtage (l
0
) ;
La rigidit dune poutre ou traverse, le rapport du moment dinertie de sa section, pour une
flexion dans un plan vertical, sa porte (distance entre axes des poteaux quelle relie).
On appelle coefficient dencastrement K des poteaux en un nud, le rapport de la somme des
rigidits des poutres ou traverses, aboutissant au nud et situes dans le plan de flambement du
poteau la somme des rigidits de toutes les barres aboutissant au nud (y compris le poteau
tudi). Toutefois, on ne tient compte que des poutres ou traverses solidarises avec le poteau
par un assemblage sans jeu dont la hauteur totale, mesure entre axes des boulons, rivets ou
cordons de soudure extrmes, est au moins gale trois fois le rayon de giration intervenant
dans le calcul du poteau. En cas dassemblages par des boulons ordinaires avec jeu normal, on
ne tient aucun compte dune poutre nexistant que dun seul ct du poteau ; sil existe de part et
dautre du poteau des poutres dont les assemblages satisfont la condition de hauteur ci-dessus,
on ne tient compte que de celle ayant la rigidit la plus faible.
Le coefficient dencastrement du poteau AB son nud infrieur A est :
e
se
w
sw
o
o
s
s
e
se
w
sw
A
L
I
L
I
L
I
L
I
L
I
L
I
K
+ + +
+
=
Le coefficient dencastrement du poteau AB son nud suprieur B est:
e
ne
w
nw
o
o
n
n
e
ne
w
nw
B
L
I
L
I
L
I
L
I
L
I
L
I
K
+ + +
+
=
L
e
L
w
E
I
sw
I
se
I
nw
I
ne
I
s
I
n
L
o
L
n
A
BI
o
L
s
Pour une articulation, on a K= 0 Pour un encastrement parfait, K = 1.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 62
2. Longueur de flambement dans les btiments nuds fixes :
Lorsque la stabilit dans la direction du flambement est assure par des contreventements ou
des murs de refend, le rapport l/l
0
est donn par la formule suivante, en fonction des coefficients
dencastrement K
A
et K
B
aux extrmits du tronon AB de poteau considr :
B A B A
B A B A
0
K K 28 . 0 ) K K ( 3
K K 84 . 0 ) K K ( 6 . 1 3
l
l
+ +
+ +
=
Cette formule se rduit :

A
A
0
K 3
K 6 . 1 3
l
l

= si lextrmit B est articule

A
A
0
K 36 . 0 1
K 38 . 0 7 . 0
l
l

= si lextrmit B est parfaitement encastre

A
A
0
K 2 . 0 1
K 6 . 0 1
l
l

= si les deux extrmits ont le mme coefficient dencastrement (K


A
=K
B
)
3. Longueur de flambement dans les btiments nuds libres de se dplacer :
Lorsque la stabilit dans la direction du flambement nest assure que par lencastrement des
poutres sur les poteaux, le rapport
0 l
l
est donn par la formule suivante, en fonction des coefficients
dencastrement K
A
et K
B
aux deux extrmits du tronon AB de poteau considr :
B A B A
B A B A
0
K K 5 . 5 K K
K K 1 . 1 ) K K ( 4 . 2 6 . 1
l
l
+ +
+ + +
=
Cette formule se rduit :

A
A
0
K
K 4 . 2 6 . 1
l
l +
= si lextrmit B est articule

A
A
0
K 5 . 6 1
K 5 . 3 4
l
l
+
+
= si lextrmit B est parfaitement encastre

A
A
0
K
K 2 . 0 8 . 0
l
l +
= si les deux extrmits ont le mme coefficient dencastrement (K
A
=K
B
)
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Notes de cours de charpente mtallique 63
BIBLIOGRAPHIE
ITBTP et CTICM : Linstitut Technique Du Btiment Et Des Travaux Publics Et Le Centre
Technique Industriel De La Construction Mtallique ; Rgles De Calcul Des Constructions En
Acier( C.M. 66) ; Les Editions EYROLLES ( 8
me
dition ) Paris 1979.
GCTT : Le Groupe De Coordination Des Textes Techniques ; Rgles Dfinissant Les Effets
De La Neige Et Du Vent Sur Les Constructions ( NV 65 et N 84 modifies 95) ; Les Editions
EYROLLES ( Douzime dition ) Paris 1976.
LEHEMBRE BERNARD ; La Construction Mtallique ; Les Editions NATHAN 1997.
MOREL JEAN ; Conception Et Calcul Des Structures Mtalliques ; Les Editions
EYROLLES (troisime dition) 1995.
MOREL JEAN ; Structures Mtalliques ; Les Editions EYRLLOS (2me tirage) 1997.
Didier- M. Le Brazidec- P. Nataf- G. Simon- R. Pralat- J. Thiesset- J.-P. Trotignon ;
Structures De Gnie Civil ; Editions Nathan Paris 1998.
MOREL JEAN ; Calcul Des Structures Mtalliques Selon LEUROCODE3 ; (troisime
tirage ) ; Editions EYROLLES 1997

You might also like