You are on page 1of 24

Page 1 of 24

Tecom Compressor AS Series:


Service Manual

Model :
Pressure :
Serial Number :
Page 2 of 24

Ownership Information

Compressor model: Serial number:


Capacity: Rated pressure:
Air dryer model: Dryer serial number:
Capacity:
Motor model: Motor serial number:
Airend model: Airend serial number:
Delivery date: First startup date:

Selected Lubricant Information


Compressor: Capacity:
Motor bearing grease:
Dryer gear box: Capacity:

Local Tecom Representative


Name:
Address:
Phone 1: Email:
Phone 2: Website:
Fax:

Notes:
Page 3 of 24

Safety Precautions
Read Safety Precautions before installing, operating, or repairing the unit. Failure to do so may result in
severe injury or death.

The unit operator must employ safe working practices and observe all related local work safety requirements
and ordinances.

The owner is responsible for maintaining the unit in safe operating conditions.

Only authorized, trained and competent personnel should perform installation, operation maintenance and
repair.

Any modification on the compressor may only be performed in agreement with Tecom Compressor and under
supervision of authorized competent personnel.

If any statement in this book, especially with regard to safety, does not comply with local legislation, the
stricter of the two shall apply.

Installation
1. Compressor or air dryer must only be lifted in accordance with local safety rules. Loose or pivoting parts
must be securely fastened before lifting. Before lifting the machine must be turned off and
disconnected from the power source.
2. Remove any blanking flanges, plugs or caps from the compressor’s pipe connections. Be sure to use
appropriate size connections and pipes, with suitable operating pressures.
3. Be sure to supply the unit with the cleanest coolest ambient air possible. If necessary, install a suction
duct at the air intake panel of the unit. Be sure that exhaust air has no possibility to recirculate to the inlet.
4. Keep compressor area free of flammable substances during normal operation.
5. On units that have automatic start/stop, or are remotely controlled, additional warning signs must be
placed in the units immediate area.
6. If using multiple compressors in the same system, use manual valves between the compressors to isolate
each one from the system. Check valves are not sufficient for this task.
7. If the ground the compressor is being placed on, consult Tecom Compressor or Tecom Compressor’s
local representative first.
8. Be sure the compressor is properly grounded and fuses to protect against short circuits are in place.
9. A padding material may be used between the unit and the floor to reduce noise if necessary.

Operation
1. All air hoses must be of the appropriate size and they must be rated for an appropriate working pressure.
Make sure system is completely depressurized before making any changes to the air piping system, or
changing any hoses.
2. Your unit is not considered capable of producing breathing quality air. Additional filtering is needed for
breathing quality air. See local regulations.
3. Do not operate unit in the presence of any flammable or combustible substances.
4. Do not operate unit below or in excess of the pressure limits indicated by the manufacturer.
5. Keep cabinet closed at all times. Before performing any work inside the unit, make sure it is shut down
and disconnected from the main power supply.
6. Do not remove or alter sound damping material.
7. Keep grounded conductive objects such as tools away form the compressor while it is running.
8. Keep suitable BC or ABC fire extinguishers nearby the compressor at all times.

Maintenance
1. Maintenance and repair work shall only be carried out by an authorized person(s).
2. Use only genuine spare parts.
3. Do not perform any maintenance work (other than a visual inspection) without first stopping the unit, and
disconnecting it from the power supply. Wait until the compressor has cooled down before starting work.
4. Before removing any pressurized component, be sure the compressor is isolated from the system and
that all stored compressed air is completely discharged.
5. Never use a flammable solvent for cleaning the compressor. Avoid using any cleaning solutions that
produce toxic vapors.
6. Be careful to not allow any foreign particles to enter any of the exposed openings during maintenance.
Covering openings with a cloth as often as possible is highly recommended.
7. Never do any heat operations (for example welding) near the oil system. The oil tanks must be completely
purged before carrying such work.
Page 4 of 24

8. DO NOT MODIFY PRESSURE VESSEL in any way.


9. Before putting the unit back into service after maintenance, check the operating pressures, temperatures
and time settings and check that the control and shutdown devices are functioning correctly.
10. When changing the separator element, examine the discharge pipe and the inside of the oil separator
vessel for carbon deposits and remove them.
11. Be sure to use appropriate eye, hand and body protection when performing maintenance operations in
accordance with work place regulations. This should include gloves and goggles where appropriate.
12. Keep area free of sparks and other ignition sources during oil change. In the event of an oil spill, clean
immediately.
13. Keep electrical wiring in good condition. Replace any wiring that has cracked, severed, or otherwise
degraded insulation. Replace any terminals that are worn, discolored or corroded.
14. Keep suitable BC or ABC fire extinguishers nearby the compressor at all times.

Failure to adhere to these precautions, or by non-observance of ordinary caution and due care require
in handling, operating, maintenance or repair – even if not expressly mention in this manual – may
result in damage to the unit and injury or even death to operator. Tecom Compressor is not liable in
this case.

Warranty Information:
1. The manufacturer guarantees their products free of material or manufacturing defects for 24 months from
the delivery date, on the entire unit and all components contained within the unit.
2. Only an authorized service center or the manufacturer may carry out repairs or servicing claimed under
warranty.
3. Products can only be delivered to the manufacturer for warranty claims only after receiving prior
authorization from the manufacturer.
4. The warranty covers free-of-charge repairs/replacement of faulty machine parts.
5. The warranty becomes null and void in case of accidental damage due to negligence, incorrect/improper
use, or failure to follow any other guidelines set forth by the manufacturer.
6. The warranty does not cover any transportation costs related to the warranty claim nor does it cover labor
costs related to the warranty claim.
7. The warranty is only valid if the purchaser has met all contractual and payment requirements.
8. Only original spare parts supplied by the manufacturer may be used.
Page 5 of 24

Congratulations! You are the proud owner of a new Tecom Compressor rotary screw compressor, a truly wise
investment in the future of your company. This instruction book describes what you need to know about your
new investment to help ensure a safe, efficient, long life for your unit. Please take the time to read this book
before putting the machine into operation to ensure correct handling, operation and maintenance. A proactive
strategy to protect your investment guarantees the reliability and longevity of your unit. Be sure to keep this
book available to the operator of the unit and make sure that the machine is operated according to the
guidelines listed here.

Be sure to record operating data and any maintenance performed on the unit. Repairs may only be carried
out by personnel authorized to do so by the manufacturer. Do not attempt to perform maintenance
yourself. Be sure to contact your local Tecom Compressor partner. If contacting the manufacturer be sure to
give the serial number on the unit’s data plate.

Tecom Compressor and its partner companies reserve the right to make changes without prior notice.

Table of Contents
SECTION PAGE(S)
1. Safety Precautions and Warranty 3-4
2. Getting Started 6-9
Principle of Operation 6
Installation Instructions 7
Initial Startup 8
3. Maintenance, Service and Spare Parts 10-15
Filter Changes 11
Periodic Maintenance Guide 13
4. Electric Circuit Diagram 16
APPENDICES
A. Periodic Maintenance Table 17
B. Connections Sizes 18
C. Quality Control Report 19
D. Service Log 20
E. Declaration of Conformity (CE) 22
F. Initial Startup Checklist 23
G. Additional Useful Information 24
H. Compressor Technical Data 25
Page 6 of 24

Principle of Operation
Rotary-screw compressors from Tecom Compressor use a pair of asymmetrical helical screws to compress
ambient air. As the motor begins turning the screws, suction is created. The screw unit (airend) begins to pull
in ambient air from within the compressor cabinet. Air enters the cabinet through large cartridge type panel
filters on the compressor cabinet. These filters are cheap and easily replaced. Their primary function is to
remove the largest of particles from the air. Large particles pose a serious a risk to the life of the screw unit.
These panel filters therefore should be replaced periodically. Check the maintenance section for guidelines on
replacing panel filters and all components discussed in this section.

Air inside the compressor cabinet enters the screw unit through the air intake filter and the attached intake
valve. The intake filter is of dry replaceable cartridge type, and it is located inside the filter housing, which is
attached to the intake valve. The intake valve controls the intake of air into the screw unit and prevents the
back flow of air.

Air entering into the screw unit, is compressed by the rotating motion of the rotors. During the compression
cycle, oil is injected into the system. This oil serves several purposes:

1. Filling the gap between rotors and casing, creating a liquid seal that prevents the compressed air from
returning to the suction side.
2. Creating an oil film on the surface of the rotors, thus preventing metal-to-metal contact between the
rotors. If lubricated properly, the two rotors should not touch each other during normal operation.
3. Lubricating the bearings in the screw unit.
4. By circulating through the after cooler, the oil also acts as a coolant. Air that is compressed creates
heat. This heat is partly taken away by the oil injected into the screw unit. The oil that takes the heat is
cooled in oil cooler. The constant circulation of a cooling fluid makes the compression cycle more
efficient by making the cycle as close to isothermal compression as possible..

After leaving the screw unit, the compressed air and oil mixture passes to the oil tank and then up through the
separator and minimum pressure valve assembly. The oil separator acts removes the majority of oil vapor
from the compressed air to approximately 5 ppm. The minimum pressure valve keeps the pressure within the
system above 4.5 barg. This is the minimum amount of pressure needed to keep oil circulating in the
compressor and therefore the screw unit flooded with oil. If the compressor were to operate at a pressure
below 4.5 barg, oil cannot circulate properly and the screw unit will be damaged.

Clean air leaves the separator and passes through the after cooler before exiting the compressor to the
system. The after cooler is cooled by air being blown over it from within the compressor cabinet. Compressed
air enters the oil cooler at around 85-90°C, and exits at around above the ambient temperature 10°C.

The cooler also acts to cool the oil. Oil leaves the oil tank through the bottom of the tank (a separate outlet
from the compressed air) and circulates through an oil filter and then the cooler. Oil enters the cooler at
around 85-90° C, and exits at about around 70°C.

Temperature probes within the compressor monitor the temperature and display it either via an analog control
or on the PLC screen. An alarm will sound when the compressor temperature rises above 100°C. Should the
temperature hit 105°C, the compressor will stop.

2. Getting Started
Page 7 of 24

Air-oil circuit diagram

Installation Instructions
Immediately upon receiving your compressor, check it for any damages acquired during delivery. If damaged,
report immediately to your local Tecom Compressor agent or to Tecom Compressor, describing in detail the
nature of the damage. Do this before installing the unit.

1. Apply all related safety precautions listed in the section of this manual relating to safety. Apply all local
safety precautions as well.
2. Be sure to install the compressor on a level floor capable of supporting the weight of the compressor. The
maximum acceptable incline of the floor is 5 degrees.
3. The pressure drop over the air outlet pipe can be calculated using the following formula

Dp = pressure drop (recommended maximum = 0.1


bar)
L= length of outlet pipe in meters
L ×450 ×Qc1.85 d = the inside diameter of the outlet pipe in
dp = millimeters
d 5 ×p p = absolute pressure at the compressor outlet in
bar(a)
Qc = free air delivery of the compressor in liters per
second

4. If not using a ventilation system make sure that there is at least 1000 mm between the top of the
compressor and ceiling. Also be sure that there are at least 1000 mm of unobstructed space on all sides
of the unit.
5. Ventilation system should be made in a way that ensures recirculation of cooling air does not occur. The
fan capacity of the ventilation system should match the compressor fan capacity at a pressure head equal
to the pressure drop caused by the coiling air outlet ducts. The maximum pressure drop over the ducts
should not be more than 0.001 bar. The following formula can be used to calculate the required ventilation
capacity.

2. Getting Started
Page 8 of 24

Qv = required ventilation capacity in m3/s


Qv =0.93 ×N dT N = shaft input power of the compressor in kW
dt = temperature increase in compressor room.

6. Necessary steps should be taken to keep the ambient air temperature between 0 and 40 degrees Celsius.
Otherwise consult your local Tecom Compressor Agent, or Tecom Compressor.
7. Be sure to place the compressor in a place that is free from all fumes or other hazardous materials. It is
recommended to have a dedicated compressor room that has no risk of contamination by toxic,
flammable, combustible or otherwise hazardous substances.
8. Inspect all air openings and make sure that there are no coverings, or other obstructions before
connecting the compressor to the air distribution system.
9. Insert a manual isolation valve at the outlet of the compressor so that the compressor can be isolated
from the system if necessary.
10. Do not install the compressor on the same piping or manifold with a reciprocating compressor. If there is a
reciprocating compressor in the plant air system, connect all compressors with separate piping to a
common air receive to damp the pulsations caused by the reciprocating compressor.
11. Consult appendix B for required cable sizes. Consult B for recommended outlet pipe diameters
12. Although the compressor is fitted with an after cooler and a moisture separator, it is recommended that a
refrigerated air dryer be used in conjunction with your unit. Particle and oil removal filters are also
recommended as complimentary products to your compressed air system, depending on your clean air
requirements. Consult your local Tecom Compressor representative if there are any questions.
13. Be sure that grounding cable of the unit has a resistance of less than 5 Ohms
14. Be sure that the line voltage is within acceptable values (+/- 5% of nameplate voltage)

The compressor is supplied with an oversized after cooler. A refrigerated or desiccant air dryer, particle and oil
removal filters are recommended in air systems where various degrees of dry and clean air is required

Initial Startup Instructions


Before starting your unit or if the unit has been unused for more than one year, be sure to go through the initial
startup checklist and return a signed copy to Tecom Compressor. The checklist can be found in appendix A of
this manual. This checklist outlines the procedure to be followed during the initial startup of the unit. Be sure
that you have read through this manual and it’s entirety before attempting to start your unit.

1. Apply all related safety precautions listed in the section of this manual relating to safety. Apply all local
safety precautions as well.
2. In the event that the compressor is installed at high altitude, outdoors, or is in below freezing temperatures
(0 degrees Celsius) consult your local Tecom Compressor agent first.
3. Consult appendix B for electrical cable size.
4. Before starting the compressor check the following:
i. Power is turned off.
ii. All pipe connections are all tight and sturdy.
iii. Check oil level indicator to make sure the oil is at an acceptable level. Add more if needed.
iv. Dryer unit is setup and ready to run according to the dryer’s operating instructions.
v. Compressor is at least one meter away from other working machinery.
vi. Compressor is on a flat surface or a surface with an incline no greater than five degrees.
vii. Line voltage is within acceptable values (380±10V).
viii. Grounding cable’s resistance is below five ohms.
ix. Check that the cable is of an appropriate length and thickness
x. Unit’s doors are closed and locked.
xi. Connect the power and turn it on.
xii. Jog the compressor for about 4 to 6 seconds to allow the oil to fill all empty spaces.
xiii. Make sure there are no oil leaks.
xiv. Make sure the direction of rotation is correct. If not, turn off the main power, and reverse the
phases. Start again at step (xii).
xv. Run the compressor until the cooling fan turns on. When the oil temperature reaches about 70°C
the cooling fan will start. The fan should blow air out of the cabinet. If air is flowing in the opposite
direction, reverse the phases on the fan motor and check again.
xvi. Be sure that the compressor loads to the appropriate pressure and that it enters standby (doesn’t
produce air). The pressure inside the system should remain steady. After three minutes in standby
the compressor should shut itself off. It is important to check that the automatic shutoff is working

2. Getting Started
Page 9 of 24

properly.
xvii.Run the compressor and be sure that it unloads at the proper pressure. Open the manual
isolation valve and be sure that the compressor loads again.
xviii.While the compressor is under full load, check the supply voltage and the current draw of the
main motor and the fan motor. Check the pressure inside the compressor. Make of a record of
these readings.
xix. Stop the compressor and check the oil level. After the initial startup, the oil level may drop.
xx. Start the compressor again and let run for 15 minutes. Pay attention to any irregular sounds, or
any error messages registering on the PLC (warning lights if the compressor has manual
controls). If there are any problems and this manual does not address those problems, contact
your local Tecom Compressor representative, or Tecom Compressor directly. If after running for
15 minutes the room is significantly warmer (10 degrees warmer), the circulation in the room is
not sufficient and better circulation must be provided for.

2. Getting Started
Page 10 of 24

Maintenance, Service and Spare Parts


In general, your local Tecom partner knows what’s best for your compressor. However there are a few steps
that you can take yourself to help protect your investment even further. Please follow the few simple steps
listed in this section. Remember DO NOT try to perform maintenance yourself.

1. Be sure to talk to your local Tecom Compressor partner about which oil is best for your compressor.
There are several different options, and you will do well for yourself to take the time to learn about the
different options. Remember that Tecom’s local partner knows best in the end.

2. Visually inspect the compressor everyday. Taking two minutes each day to open up the
compressor and leak around inside for any leaks can be vital in catching problems early and
minimizing downtime for maintenance. If any leaking oil is visible, call your local Tecom partner
immediately.

3. Check the oil level of the compressor everyday. If the oil level drops too low, you can risk destroying
your compressor’s air end. Checking the oil level regularly will be a good indication if your compressor
has any oil leaks or other problems.

4. Ask your local Tecom partner to provide you with a schedule relating to the maintenance of your
compressor. You can follow and make sure that maintenance is performed regularly in accordance
with the schedule provided.

Rotary screw compressors are designed to operate reliably at maximum output for long periods of time. To
ensure that the compressor has a long product life with minimum down time, it is important that a regular
service schedule be followed. This section outlines the important steps required to maintain your compressor.
DO NOT try to perform maintenance unless you are a qualified service technician and employed by Tecom or
a Tecom representative. Should service work be done on the machine by a technician not employed by Tecom
or a Tecom representative, or by someone with no technical experience, the warranty on the machine will be
voided.

It is vital that before any maintenance work is performed that the compressor is switched off, and the
compressor is allowed to come to a complete stop and to cool down, and the main power is disconnected.
Follow all safety precautions listed in this manual in the section on safety.

Oil Selection
Oil selection is very important to the lifetime of your compressor. Please follow these guidelines when
choosing an oil.
1. All Tecom Compressors ship with viscosity 46 mineral oil hydraulic oil. Tecom Compressor
recommends using a viscosity 46 oil. Brand is no important, but the type of oil can make a difference.
If different oil is desired for future orders, it is no problem for Tecom Compressor to ship your future
units with a different oil.
2. If opening in cold climates (where temperatures drop below -10 oC, use a viscosity 32 oil. In colder
weather your compressor will have a hard time starting with viscosity 46 oil and will put unnecessary
strain on the air end and the motor.
3. Synthetic oil is recommended over mineral oil. Synthetic oil has about three times the lifetime of
mineral oil and it has better heat transfer properties. If the compressor is experiencing problems with
overheating, switching to synthetic oil will allow the compressor to work in higher temperatures.
DO NOT mix synthetic and mineral oil. Doing so can damage the compressor. Be sure to drain the
compressor completely of oil if switching between oil types.

Oil Change
Make sure the system is shut down before attempting to change the oil. Appropriate protection for eyes,
hands and clothing, should be worn before attempting to change the oil.
1. Make sure the compressor is cooled down before trying to change the oil. If the compressor has been
working, let it cool for 10 minutes before attempting to change the oil.
2. Depressurize the compressor by turning the compressor to standby and letting the pressure drop to
zero.
3. Loosen the plug on top of the oil tank.
4. Drain the oil by opening the oil drain on the oil tank. Be sure to catch the draining oil in a pan. Be
Appendix A: Periodic Maintenance Table
Page 11 of 24

careful incase the oil is still hot.


5. Allow the oil to drain for 10 minutes. It is advisable to do the other tasks of servicing the compressor
while the oil is draining. Be sure to dispose of the oil according to local regulations. Close the oil drain.
6. Remove the oil filler plug and fill the oil tank with oil until the level reaches the desired level as
indicated on the oil gauge.
7. Close the filler plug. Check all other plugs and valves are closed properly.
8. Run the compressor for five minutes. If the oil level drops, begin the process again at step 6.

Oil drain Oil filler plug

Oil Filter Change


The oil filter needs to be changed periodically as indicated in the periodic maintenance table in the
appendices of this manual.
1. Stop the compressor, switch off the voltage and depressurize the air by turning the compressor off
and letting it completely depressurize. Be sure to isolate the compressor from the main power supply
to prevent accidental starting.
2. Place an oil pan or take other appropriate actions to prevent spills in the area of work.
3. Open the cartridge with the filter key. Be sure to apply the filter key at the bottom of the filter.
4. Get rid of the removed filter according to the local regulations.
5. Wipe down the oil filter connection.
6. Lightly oil the gaskets of the new filter.
7. Screw the new filter into place with the filter key and make sure the gaskets contact their seats and
tighten by hand.
8. Tighten the filter plug.

The picture shows the filter key being used to


tighten (turning clockwise) a separator. The
chain of the filter key must be used on the
metal lip around the edge of the separator.
The same technique is used to remove the oil
filter. In both cases, the filter is removed by
turning counterclockwise, and turning
clockwise tightens it.

Spin-on Separator Change


The separator is disposable and should be replaced every year or every 2000 hours, whichever happens first.
The separator should be immediately replaced if the pressure drop across the separator is high than 0.5 bar.
1. Stop the compressor, switch off the voltage and depressurize the air by turning the compressor off
and letting it completely depressurize. Be sure to isolate the compressor from the main power supply
to prevent accidental starting.
2. Remove the separator as indicated in the figure using the filter key. Be sure to apply the filter key at
the bottom of the filter.
3. Insert the new separator and tighten it with the filter key. Visual inspect to make sure it is installed
properly.
4. Get rid of the removed separator according to local regulations

Appendix A: Periodic Maintenance Table


Page 12 of 24

Deep Separator Change


The separator is disposable and should be replaced every year or every 2000 hours, whichever happens first.
The separator should be immediately replaced if the pressure drop across the separator is high than 0.5 bar.
Most of the same rules that apply to spin on separators apply to deep separators. However, the process of
changing a deep separator takes more work, and more time.
1. Stop the compressor, switch off the voltage and depressurize the air by turning the compressor off
and letting it completely depressurize. Be sure to isolate the compressor from the main power supply
to prevent accidental starting.
2. Remove all piping connections and the minimum pressure valve from the separator tank.
3. Remove all of the bolts from the separator lid and remove the lid.
4. Remove the top seal (colored orange in the picture) and pull out the separator cartridge.
5. Place a new cartridge in place of the old one and dispose of the used cartridge properly. Reverse the
steps to reassemble the separator tank. Make sure all connections are tightened properly.
6. DO NOT replace the seals. Be sure to reuse the seals. If the seals need to be replaced contact Tecom
Compressor directly. Replacing the seals without taking certain measures could result in serious
damage to your compressor.

Air Filter Change


The air filter on the air intake valve should be replaced every 500-1000 hours depending on the surrounding
environment. Regularly changing the air filter will ensure high quality compressed air and lead to a longer
product life for all the components in the compressor. The better quality air you have going into the air intake
valve, the longer your compressors life will be.
1. Stop the compressor, switch off the voltage and depressurize the stopping the compressor and
making sure the pressure has dropped to zero. Be sure to isolate the compressor from the main
power supply to prevent accidental starting.
2. Open the filter case and remove the cartridge. Clean the case with pressurized air no great than 5
bar.
3. Place the new filter in the case.
4. Dispose of the removed air filter cartridge according to local regulations and close the air filter case.

Appendix A: Periodic Maintenance Table


Page 13 of 24

Figure showing the air filter cartridge found inside the metal housing attached to the air intake valve. Different models will
have different size and different style air filter. The red and beige cartridge is disposable. The metal housing is reausable.

After Cooler
It is important to keep the after cooler clean to maintain cooling efficiency. The after cooler should be cleaned
with low-pressure compressed air (no greater than 5 bar). This should be done as needed. Check the cooler
every 1-3 months for dirt buildup. If there are overheating problems in your compressor, cleaning the after
cooler is a good place to start. If a more through cleaning is needed, remove the cooler, seal any openings
and clean it with pressurized water.

Belt Tension and Alignment


The tension of the belt on all belt drive machines needs to be controlled periodically. At the same time, the
alignment of the pulleys needs to be controlled. Both can be altered by using the setscrews, as shown in the
pictures below. Note that there are two different alignments. For the larger sizes of compressor, the airend and
the motor are side by side in what is referred to as a horizontal alignment/compressor. For smaller sizes, the
airend is above the motor in a vertical alignment.

Location of setscrews with Location of setscrews with horizontal alignment. Close up of setscrews
vertical alignment. with horizontal alignment.

Periodic Maintenance:
In the appendices of this manual is a chart outlining what maintenance needs to be performed on the
compressor and at what intervals. Consult this chart in order to schedule maintenance. Other general steps
that should be taken to ensure the well being of your compressor are:
1. Check display readings daily
2. Give the compressor a daily look over for any leaks.
3. Check the oil level daily
4. Clean the compressor with low-pressure compressed air (no greater than five bars) every 3 months or
as needed. Pay specific attention to cleaning the cooler. If using a cleaning solution, use only non-
flammable, non-corrosive one. Consult Tecom Compressor before using any cleaning solutions.
5. Check for air leaks in the compressor and the air distribution system every three months.

Intake Group
Replace: The intake filter needs to be replaced every 2000 hours throughout the
Intake Filter
lifetime of the compressor.
Replace: Replace the panel filters every 2,000 hours or as needed. Cleaning the
Panel Filter filters periodically is not enough. They must be replaced after several
cleanings.
Intake Valve Control: Check it for leaks every 2,000 hours. Check the connections with the

Appendix A: Periodic Maintenance Table


Page 14 of 24

solenoid.
Maintenance: Perform maintenance every 6000 hours using an intake valve
maintenance kit.

Screw Unit
Control: Visually inspect the screw unit every 2000 hours for any obvious problems.
General Control These include, leaks, cracks or discoloration of the material. If anything is
abnormal, consult your local Tecom representative or Tecom Compressor.
Control: After each servicing of the compressor (every 2000 hours), let the
Noise compressor run for 10 minutes and listen for any abnormal sounds come from
the screw unit. If anything is abnormal, consult Tecom Compressor.
Maintenance: Every 20,000 hours use a certified maintenance kit to replace the
Overhaul
included parts.

Air Circuits
Control: After each servicing of the compressor (every 2000 hours) inspect the air
Air Leaks lines for any leaks. Since oil and air travel together in the compressor, oil will be
visible if there are any leaks. Replace any damaged/nonfunctioning
components
Control: Check it for leaks every 2,000 hours. Check the connections with the
Minimum Pressure
solenoid.
Valve
Maintenance: Perform maintenance every 6000 hours using an intake valve
maintenance kit.
Control: Visually inspect for leaks every 2,000 hours.
Safety Valves
Maintenance: Replace every 20,000 hours using only CE certified safety valves.

Oil Circuits
Maintenance: Every 2,000 hours clean the air/oil after cooler or as needed. Use
Cleaning the Radiators
low-pressure compressed air (no greater than 5 bar).
Replace: The oil in the system should be replaced every 2,000 hours if using
Oil
mineral oil. If using synthetic oil, the oil should be replaced every 10,000 hours.
Follow the guidelines listed earlier in this section.
Replace: The oil filter should be replaced every 2000 hours, according to the
Oil Filter
guidelines given earlier in this section.

Control Lines
Control: If there are any problems about late or incomplete discharges, replace this
Solenoid Valves
valve.
Pressure Switch Control: If there are any problems with this valve, replace it.
Thermostatic Gauge Control: If compressor is operating at a different temperature than it should be,
(AS15 and smaller) replace this piece.
Pressure Gauges Control: If the compressor is operating at the wrong pressure, replace this piece.
(AS15 and smaller)

Coupling/V-Belts
Control: Measure the belt tension and make sure it is within acceptable ranges.
Belt Alignment/Tension
Replace: If a belt breaks, or is noticeable worn, replace it.
Maintenance: If the compressor contains a Siemen’s motor, the bearings need to
Motor Bearings be greased every 10,000 hours. WAT motor bearings do not need to be greased.
Replace: Both brands of motors need their bearings replaced every 20,000 hours.

Electrical Panel
Maintenance: Remove the contactors’ covers and clean with low pressure air (less
Contactors
than 5 bar) every 4,000 hours or as needed.
Control: Check the current at 6.5 bar and 8 bar for an 8 bar compressor. At 8.5 and
Current
10 bar for a 10 bar compressor. And at 11.5 bar and 13 bar for a 13 bar
(loaded/unloaded)
compressor.

Separator and
Receiver
Separator Replace: The separator element has to be replaced every 2,000 hours. Follow the

Appendix A: Periodic Maintenance Table


Page 15 of 24

guidelines listed earlier in this section.


Control: Check to make sure there is enough oil in the compressor every 2,000
Oil Level
hours.

All Mechanical Control: Visually inspect all mechanical connections every 2,000 hours for any
Connections obvious problems. These include, leaks, cracks or discoloration of the material.
If anything is abnormal, consult your local Tecom representative or Tecom
Compressor.
All Piping Control: Visually inspect all piping connections every 2,000 hours for any obvious
Connections problems. These include, leaks, cracks or discoloration of the material. If
anything is abnormal, consult your local Tecom representative or Tecom
Compressor.
Replace: Every 10,000 hours replace the piping connections to avoid any leakage
problems from developing.

Appendix A: Periodic Maintenance Table


Page 16 of 24

Appendix A: Periodic Maintenance Table


Page 17 of 24

Periodic Maintenance Table


2,000 hrs 4,000 hr 10000 hr 20,000 hr 40,000 hr
Time Period
C M R C M R C M R C M R C M R
Intake Group
• Intake Filter
• Panel Filter
• Intake Valve*
Screw Unit
• General Control
• Noise
• Overhaul
Air Circuits
• Air Leaks
• Minimum Pressure Valve*
• Safety Valves
Oil Circuit
• Clean Radiators
• Oil*
• Oil Filter
Control Lines
• Solenoid Valves
• Pressure Switch
• Thermostatic Switch/Gauge
• Pressure Gauges
V-Belts
• Belt Alignment/Tension
• Motor Bearings*
Electrical Panel
• Contactors and contacts
• Current (loaded/unloaded)
Separator and Receiver
• Separator
• Oil Level
All Mechanical Connections
All Piping Connections
C – Control, M – Maintenance, R – Replace (change)
* Reference the service section of this manual for the specific details of scheduling this part of the periodic maintenance.

Appendix A: Periodic Maintenance Table


Page 18 of 24

Connection Sizes
Consult this section when installing the compressor. It describes the necessary cable length, fuse size and the
connection size of each Tecom Compressor.

Air Outlet Mains Cable(mm²) Mains Cable (mm²) Isolation Switch


kW HP
(inches) (Length<15 m.) (Length>15 m.) Fuse (Amps)
4 5.5 1” 2.5 08 25
5.5 7.5 1” 4 08 32
7.5 10 1” 4 10 40
11 15 1” 6 10 50
15 20 1” 6 10 63
18 25 1” 10 10 63
22 30 1” 10 16 65
30 40 11/4” 16 25 100
37 50 11/4” 25 35 100
45 60 11/2” 35 35 100
55 75 11/2” 35 70 125
75 100 11/2” 70 95 160
90 125 2” 95 120 200
110 150 2” 120 185 250
132 180 2” 185 240 400
160 220 2” 240 240 400

Appendix B: Connections Sizes


Page 19 of 24

Product Quality Control


Final Test

Compressor Model: Serial #: Pressure: BAR

Brand Type Serial #


Airend
Main Motor
Fan Motor

Mechanical Checks Result


Check the oil level.
Check that the compressor shuts down automatically when overheated.
Check that the compressor run on both stand-by and at full load with no errors.
Check all the hydraulic and pneumatic connections.
Check all the assembly connections, nuts and bolts.
Check for oil leakages.
Check the cleanliness of the compressor.
Check all the documentation and stickers of the compressor.

Electrical Checks Result


Check all the klemens connections and cables.
Check the shut down timing of the compressor.
Check the electrical fuses.
Check that both the main motor and the fan motor turn in the right direction.
Check the functionality of the emergency start/stop button.
Check the compressor PLC system.

Measurements
Parameter Test Device Unit Value
Airend oil inlet oil temperature Infrared temperature probe °C
Airend oil outlet temperature Infrared temperature probe °C
Oil tank temperature Infrared temperature probe °C
Automatic turn off temperature PLC control system °C
Current drawn (loaded) Control board Amp
Current drawn (stand-by) Control board Amp
Fan motor current drawn (load) Control board Amp
Voltage value Control board Volt
Belt-pulley alignment Laser level mm
Sound pressure level Sound measuring device db(A)
Vibration levels and report Vibration detection device mm/s-rms
Air leakages Ultrasonic leak detector sensitive

Ambient temperature during test ˚C


Moisture level during test (%) %

Mechanical Quality Control Electrical Quality Control Quality Manager

Hakan KENAR Cüneyt ÖZMEN Neşe AŞCI


Document No: 2100/FR/09 Revision No:2 Date: 22/11/2006 Page No:1/1

Appendix C: Quality Control Report


Page 20 of 24

Service Record
This section is provided to keep track of service performed on the machine. This is only a suggestion. It is
more than likely that your service provider will track this information as well.

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension

Appendix D: Service Log


Page 21 of 24

Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Date:_____________
Oil Filter Separator Oil Change Air filter Control belt tension
Notes:

Appendix D: Service Log


Page 22 of 24

Declaration of Conformity
We:
TECOM COMPRESSOR
Makina San. Tic. Ltd. Sti.
Eski Silivri Yolu Cad. No. 44 Buyukcekmece
Istanbul, Turkey

Under our own responsibility herewith declare that the products:

Model Serial Number

AS ( POWER )

So as it has been manufactured by ourselves, complies to the following regulations specifically to:

98/37/EC Machinery Directive


73/23/EEC Low Voltage Directive
89/336/EEC Electro-Magnetically Compatibility Directive
97/23/EC PED Directive

No improper use of this declaration is allowed.

Place and date Authorized person Signature and stamp


responsible

İSTANBUL NEŞE AŞCI

Appendix E: Declaration of Conformity


Page 23 of 24

Initial Startup Checklist


It is important to execute the following steps in the order they are listed and that this document is returned,
signed and stamp, to Tecom Compressor. Failure to do so will void the compressor’s warranty. These steps
are to be followed in order and are in addition to the installation instructions section of this manual. Signing
this document confirms that you have followed all of Tecom’s directives for installing and starting your
compressor..

Date
Compressor Model
Compressor Serial Number

CHECK
Power is turned off. Compressor is isolated from both the power and the air system.
All pipe connections are all tight and sturdy.
Check oil level indicator to make sure the oil is at an acceptable level. Add more if needed.
Dryer unit is setup and ready to run according to the dryer’s operating instructions.
Compressor is at least one meter away from other working machinery.
Compressor is on a flat surface or a surface with an incline no greater than five degrees.
Line voltage is within acceptable values (380±10V).
Grounding cable’s resistance is below five ohms.
Check that the power cable is of an acceptable length and thickness.
Unit’s doors are closed and locked.
Connect the power and turn it on.
Jog the compressor for about 4 to 6 seconds to allow the oil to fill all empty spaces.
Make sure there are no oil leaks.
Make sure the direction of rotation is correct. If not, turn off the main power, and reverse the
phases.
Run the compressor until the cooling fan turns on. When the oil temperature reaches about 70°
C the cooling fan will start. The fan should blow air out of the cabinet. If air is flowing in the
opposite direction, reverse the phases on the fan motor and check again. Make sure that the
compressor enters standby mode and that it automatically shuts down after three minutes in
standby mode.
Run the compressor and be sure that it unloads at the proper pressure. Open the manual
isolation valve and be sure that the compressor loads again.
While the compressor is under full load, check the supply voltage and the current draw of the
main motor and the fan motor. Check the pressure inside the compressor. Make of a record of
these readings.
Stop the compressor and check the oil level. After the initial startup, the oil level may drop.
Start the compressor again and let run for 15 minutes. Pay attention to any irregular sounds, or
any error messages registering on the PLC (warning lights if the compressor has manual
controls). If there are any problems and this manual does not address those problems, contact
your local Tecom Compressor representative, or Tecom Compressor directly. Be sure that the
room is not heating up with the compressor. If the room is noticeably warmer (10 degrees) after
running the compressor for 15 minutes, the air circulation is not adequate.

Stamp and signature of service Stamp and signature of the customer

Printed Name Printed Name

Date Date

Appendix F: Initial Startup Checklist


Page 24 of 24

Other Useful Information


Unit conversion list of SI (metric) units to American units:
1 Bar = 14.504 psi
1 g = 0.035 oz
1 kg = 2.205 lb
1 kW = 1.341 hp
1 l = 0.264 US gal
1 l = 0.220 Imperial gal
1 l = 0.035 cu.ft
1 l/s = 2.117 cfm
1 mm = 0.039 in
1 mbar = 0.401 in of water
1 N = 0.225 lbf
1 Nm = 0.738 ft-lbf
1 degrees Celsius = 32+1.8*C degrees Fahrenheit

Appendix G: Additional Useful Information

You might also like