You are on page 1of 23

ON-LOAD TAP CHANGER TYPE D General Manual

CONTENTS
1. 2. 3. Specification Details ..................................................................................... 2 Description of the On Load Tap Changer ..................................................... 4 Principal Parts of the On Load Tap Changer ................................................ 5 3.1 3.2 3.3 3.4 3.5 4. Diverter Switch Oil Tank .................................................................... 5 Diverter Switch .................................................................................. 6 Transition Resistors .......................................................................... 7 Tap Selector .......................................................................................7 Delta Tap Changer ............................................................................ 9

Electrical Characteristics ......... ................................................................... 9 4.1 4.2 4.3 Electrical Strength ............................................................................. 9 Short Circuit Withstand ..................................................................... 11 Tap Changing Cycle .......................................................................... 11

5 6. 7. 8.

Motor Drive ................................................................................................... 14 Drying Out the On Load Tap Changer... ....................................................... 15 Inspection ..................................................................................................... 15 Protective Relay ........................................................................................... 16

ON-LOAD TAP CHANGER TYPE D General Manual

On Load Tap Changer Type D


1. Specification Details Layout: Installed fully sunk in the transformer tank. (Can also be mounted in a separate tank). Diverter switch operates in its own oil space (diverter switch oil tank isolated from the transformer oil. On load tapchanger D III 200, D Ill 400, D Ill 500, as star point tapchanger for three phase transformers and On load tapchanger D Ill 200, D Ill 400 D Ill 500 for application to delta connected transformers or On load tapchanger D 1 400, D I 500, D I 600, D I 800 and D I 1200 as single phase tap changer for single phase transformers or for three phase transformers in any mode of connection. Star point tap changers are used mainly for transmission system transformers and single phase tap changers for auto transformers and industrial transformers supplying furnaces and electrolysis plants. Insulation level voltage to earth 30, (45), 60, (80), 110, 150kV. Tap selector Series 60, 110,150. To earth: according to insulation level voltages to IS, BS, lEC, VDE, ASA, etc. Internal selector insulation: withstand voltages for all insulation distance on application. 200, 400, 500 A when star or delta connected 400, 500, 600, 800, 1200 A single phase in any connection. 50........60 Hz Thermal test: 20 times the rated current (rms), duration 3 seconds. Dynamic test: 50 times the rated current (peak value). Particulars of permissible step voltages on application. The values depend on tap selector insulation and circular pitch. Tap selector with preselector (coarse tap selector or reversing switch): 8,10,12,14,16 steps with 3 mid position (up to a maximum of 33 working positions differing in voltage). 9, 11, 13, 15, 17 steps with one mid position (up to a maximum of 35 working positions differing in voltages). Tap selector without preselector: 4 5 6, 7, 8 steps (up to a maximum of 17 working positions differing in voltage). Driving Motor drive as standard equipment can be started and stopped by push buttons from the drive cabinet and also from the control room. Manual operation by crank available if needed. Remote position indication. Versions for parallel operation and for connection to voltage regulators.
3

Applications:

Insulation: A.C. test voltage: (50Hz 1,2/50s) Current rating: Rated Frequency: Short circuit withstand: Step voltage Number of taps:

ON-LOAD TAP CHANGER TYPE D General Manual

2.Description of the On - Load Tap Changer Fig. 13 shows an on-load tap changer Type D in the form of D III400 three phase unit with an insulation level voltage of 110 kV to earth and a 110 series tap selector for + 13 steps conforming to the design specified in section 1. The principal parts are numbered consecutively and detailed in thelist belonging to Fig.12. The same part numbers are given in brackets throughout the text in the this publication . Models of the on load tap changer type D designed for higher or lower insulation level voltages or tap selector series result in correspondingly larger or smaller vertical dimensions of the diverter switch or tap selector. As in the familar Jansen on load tap changers in the higher range of ratings, which have become firmly established since 1926 the type D on load tap changer likewise retains the same subdivision into a tap selector and a diverter switch giving high speed change over , both units however have been further developed to confer high switching capacity and short circuit withstand and long span,as is described in further details below.The tap selector and diverter switch are mounted as a unit in the transformer tank.

Fig. 1

The diverter switch has its own oil tank, whilst the tap selector is immersed in the same oil as the transformer. The tap selector and diverter switch are thus housed in seperate oil chambers. The only fittting projecting above the transformer cover is the tap changer head. This is no higher than the metal bases of the H.T. bushings and thus allows full use to be made of the available space above the transformer head where they are readily accessible. As shown in Fig.2. and 12, the on load tap changer designed on these principles is a unit which hangs from the head (103) and can be bolted either to the transformer cover or to an annexe on the side of the transformer tank after welding on a mounting flange(101).
4

ON-LOAD TAP CHANGER TYPE D General Manual

When filling the transformer tank with oil ,the air which collects inside the mounting flange (101) must be released through a small pipe (102) to atmosphere (valve plug). The on-load tapchanger head (103) contains the principal items of the driving mechanism and the position indicators for the diverter switch and tap selector. The driving mechanism is only visible after removing the cover (106) on the on-load tap changer head whereas the position indicators can be seen through a window (114) even when the cover is in position. The parts mainly concerned are the primary gear unit (121) together with the two Geneva drives (401) giving alternate operation of the two tap selector contact systems (408, 409) and the spring-operated energy accumulator (304) providing a high speed drive to the diverter switch. In addition, there is an important electrical supervisory device, namely the protective relay RS 2001. Directly suspended from the previously mentioned on-load tapchanger head, which in turn bolts to the mounting flange on the transformer cover, is the diverter switch oil tank (203). Screwed to the base (207) of the latter is the tap selector (400) which at one end carries the preselector (500) and which is driven via the tubular driving shafts (402) from the mechanism (121, 401) in the on-load tapchanger head.

Fig . 2 Load Tap Changer D III 400, 60 kV, Tap Selector Series 110

3 Principal Parts of the On-Load Tap Changer 3.1 Diverter Switch Oil Tank The diverter switch (300) is housed in its own oiltank (203). The oil in this tank is kept entirely separated from the transformer oil. The oil is, of course, of the same type as that used in the transformer tank, since ordinary transformer oil is perfectly suitable for use as a switch oil. Owing to the contamination brought about in service by arcing, however, the switch oil is kept separate from the transformer oil. It is impossible for the contaminated switch oil, to pass from the diverter switch compartment into the surrounding transformer oil (yellow). The diverter switch oil tank consists of high-grade insulation which in the vertical direction withstands the full working voltage to earth (under earth fault conditions also). Grading rings (208) fitted outside and inside the oil tank (bare up to 45 kV, insulated from 60 kV upwards) promote satisfactory field distribution with a low voltage gradient along the vertical insulation path. Its connection to the conservator ensures that the diverter switch oil tank is kept completely full of oil at all times.

ON-LOAD TAP CHANGER TYPE D General Manual

3.2

Diverter Switch

The most important part of the on-load tapchanger is the diverter switch. On the rear cover the diverter switch unit together with the spring-operated energy accumulator is shown withdrawn from the oil tank. Details are shown in Fig. 3 and 4. The main parts of the snap action diverter switch are the transition contacts (323), the transition resistors (315) and the short circuit-proof main contacts (322). The diverter switch has been designed in particular for maximum dependability and freedom from contact bounce. The kinematic principle of the contact system combined with the high speed operation achieved by the spring-operated energy accumulator gives short arcing times which minimize contamination of the switch oil. To extend their working life the diverter switch contacts are faced with a sintered tungsten-copper alloy, for 400 A and 500 A Units. Along with the transition resistors associated with it, the diverter switch is attached to the bottom end of the vertical diverter switch suspension cylinder (307) which is made of fibre reinforced plastic (FRP). At the top end of this cylinder is the diverter switch head (301) with the driving mechanism consisting of the diverter switch drive coupling (303), the spring-operated energy accumulator (304) and the tubular driving shaft (308) (coupling the energy accumulator to the contact system). This has enabled the energy accumulator drive to be accommodated close alongside the main gear unit (121) in the on load tapchanger head (103) where it is accessible at any time for inspection.

301

307

309

311
Fig. 3 Diverter Switch Unit, 21000

Three basic designs of Diverter switch are available. Diverter Switch Type D 21000: This diverter switch Fig .12 has a current carrying capacity of 200A per phase . This is used in Tap Changers type D III 200, D I500 and D I 600. Diverter Switch Type D 04 66: This diverter switch has a current carrying capacity of 400A per phase. This is used in Tap Changers type DIII 400, D I800 and D I 1200. A reinforced design of D 04 66 is used in tap Changers type D III 500

Fig . 4 Diverter Switch Type 21000

ON-LOAD TAP CHANGER TYPE D General Manual

Diverter Switch type D 0444: This is basically a single phase switch with a current carrying capacity of 400A and is used in Delta tapchanger of 400 A capacity. As in the case of D 04 66, a reinforced version is available for current carrying capacity of 500A, and this is used in tapchangers type D III 500 Delta. A modified form of D 0444 is used in Delta Switch D III 200 Delta. 3.3 Transition Resistors These are wound with high-grade chrome-nickel alloy wire of circular section and consist of paper laminate panels, the long sides of which are provided with porcelain carriers. Each of the three segments of the diverter switch has four transition resistors making twelve for the diverter switch as a whole. These resistors are mounted as a singe group in an insulated drum and are connected to the diverter switch contacts by screws which cannot work loose. The insulation distances between the individual resistor panels make it necessary for the resistor drum to be filled for the greater part with oil; only a small space is occupied by the active resistance elements. This open type of construction allows very rapid cooling of the resistors which only carry the load during the transition time. The resistors are so designed that there is no need to limit the number of tap changes which can be made in close succession. 3.4 Tap Selector The function of the tap selector is to prepare the tapchange by connecting the diverter switch to the required tap on the transformer (Fig. 6). During this stage the contact system of the diverter switch stays in its original position until the tap selector (Fig. 5) has arrived at the new tap. Thereupon the contact system effects the change-over to bring the new tap into operation. For this purpose the tap selector contacts (407) which connect to the transformer taps are arranged one above the other on the vertical bars of the insulator cage (404). Via these tap selector contacts and rotatable contact bridges (411 , 41 0) the necessary inter-connections to suit operating conditions are made between the transformer taps and central take-off rings (411). The latter are connected by conductors (412) and sliding contacts (204) to the contacts (328, 329) of the diverter switch. The current path between the diverter switch and the starpoint output terminal (circular bus-bar 324) includes three further pairs of sliding contacts. The alternate connecting of even-numbered and odd numbered tap selector contacts to the diverter switch contacts takes place on the same switching principles as employed in Jansen switches since as long ago as 1926. With this arrangement the tap selector contacts for each phase are divided into two groups odd-numbered contacts 1, 3, 5. and even-numbered contacts 2, 4, 6... which are disposed in two planes on separate cage bars. Two shortcircuit proof contact bridges (411, 410) cooperate with these groups of contacts and are moved alternately from one position to the next in unison with
7

ON-LOAD TAP CHANGER TYPE D General Manual

the diverter switch action by means of a Geneva mechanism (401). This mechanism is housed in the On load tap changer head (103) where it is readily accessible for checking, and it drives the two contact bridges of the tap selector via a pair of insulated shafts (402) and a reduction gear unit (403) The space-saving layout of the even-numbered and odd-numbered groups of tap selector contacts and the central position of the tap selector conductors (412) from the take-off rings to the conductors at the bottom of the tap selector are features which make for a compact arrangement. The transverse forces brought about by the large number of leads connected to the tap selector are resisted by the metal structure of the selector the central suspension tube of which (413) joins together the upper and lower tap selector cage ring.The tap selector can be built for various numbers of positions. Depending on the circuit arrangement used for connection the regulating winding of the transformer to the tap selector there are types with 8,10,12,14 or16 tapping positions, with three mid-positions, and others with 9,11,13,15 or 17 tapping positions and only one mid-position. Fig. 6 shows the principal basic circuit arrangements for tap selectors of any circular pitch. The numbers of tapping positions indicated apply to tap selectors with preselector. The on load tapchanger may be provided with a reversing switch or coarse tap selector (502, 504, 506) mounted on the side of the tap selector to keep the interconnecting leads short. The reversing switch gives buck and boost connection of the regulating winding relative to the main winding of the transformer (see Fig. 6 top circuit diagrams), whilst the coarse tap selector connects the regulating winding, either direct or through a coarse tap winding, to the main winding (see Fig. 6, basic circuit diagrams). While the tap selector contact K is in operation, the reversing switch and coarse tap selector are actuated by a driving mechanism (501) running in unison with the motion of the tap selector contact bridge (411) for the odd-numbered contacts. The position of the reversing switch or coarse tap selector can be checked at any time from the position indicator (119) visible through a window (116) in the on-load tapchanger head. Alongside to right and left, the position of the tap selector bridges controlling the odd-numbered and evennumbered contacts can be seen from the numbered dials on the two Geneva units (401). The tap selector and reversing switch or coarse tap selector are immersed in the transformer oil. Insulation distances in the vertical direction are protected against electrical over-stressing by projecting electrodes. In the horizontal direction all insulation paths are through oil. These arrangements give a high standard of protection against surge conditions. 3.5 Delta Tap Changers

In the case of tap changers intended for use in Delta connected transformers, it is necessary to provide phase to phase insulation of appropriate value, in both the diverter switch and tap selector. In these cases, three separate diverter switches are necessary, with insulated supports and

ON-LOAD TAP CHANGER TYPE D General Manual

drive shafts between them. If the interphase insulation required is small, it is possible to house the three diverters, which are now axially separated, as also the tap selector in one column, and such delta units look about the same for external appearance as star or single phase units. Where interphase clearance required is high, it may become necessary to mount the diverter switch, and tap selectors in two different columns (See Fig.15) 4 Electrical Characteristics of On-Load Tap Changer 4.1 Electric Strength

The electric strength of the insulation to earth corresponds with the stipulated test voltages of the national and international standards systems including IS, BS, VDE, ASA, IEC etc. The withstand voltage to earth of the various insulation paths is higher than, or at least equal to the test values referred to above. The insulation of the on-load tapchanger to earth can be dimensioned independently of the internal insulation of the on-load tapchanger and, in particular, independently of the insulation of the tap selector. The latter is governed by the voltage stressing of the transformer and is graded accordingly in the various sections. The internal electric strength of the tapchanger is determined primarily of the impulse withstand and a.c. withstand voltage of the tap slector. The dimensioning of the tap selector is based in the majority of cases, however on the impulse voltage stressing of the regulating winding. The internal electric strength of the tap selector is provided by allowing appropriate insulation distances in oil and along the selector bars. Through suitable grading of these distances (tap selector contact circle diameter and tap selector length) three different tap selector series have been developed (60, 110 and 150) so that the transformer manufacturer can match the tap selector size to the voltage stressings of the regulating winding arising in service.

ON-LOAD TAP CHANGER TYPE D General Manual

10

ON-LOAD TAP CHANGER TYPE D General Manual

The standard of insulation quality achieved is confirmed by the excellent results given during years of service by many thousands of on-load tapchangers operating under the most diverse conditions in large transformers upto 220 kV. The transformer manufacturer is responsible for ensuring correct coordination between the electric strength of the on-load tapchanger and the voltage stressing arising in the transformer. 4.2 Short Circuit Withstand The current paths and all contacts in the on-load tapchanger will withstand a thermal short circuit loading at 20 times the rated current for 3 seconds without suffering any damage. They will also withstand dynamic loading up to 50 times the rated current (peak value) without damage. The values specified in the IEC recommendations are thus greatly surpassed. 4.3 Tap Changing Cycle The diverter switch effects the no-break transfer of the current from the tap in service to the tap which has been pre-selected. During the change-over pure ohmic resistance is cut in on the circuit. This gives optimum arc extinction conditions at the critical points in the diverter switch, since the current through the switch is always in phase with the recovery voltage regardless of the power factor (cos) of the transformer load. The change-over action of the diverter switch D is illustrated in the diagram showing a tap change sequence (Fig. 7) and in the oscillogram of a tapchange at the rated load (Fig. 8, 9). The following description outlines the relationship between the various positions of the onload tapchanger and the characteristics of the oscillograms. The diverter switch of the D Ill 200 on load tap changer (200 A rated current) does not have the auxiliary contacts a2 and b2 or the associated transition resistors R2. As will be seen from the above state-by-state description, a tap change involves three circuit-closing and three circuit-opening actions. A tapchange can therefore be divided into three steps. The first step lasts from t1 to t2 (positions 2 to 4), the second from t3 to t5 (positions 4 to 6) and the third from t5 to t7 (positions 6 to 8). Each such step must have a duration of not less than one half cycle of the system frequency. In the example quoted this is the case.

11

ON-LOAD TAP CHANGER TYPE D General Manual

Fig.8 Oscillogram of a tap change (single phase)

12

ON-LOAD TAP CHANGER TYPE D General Manual

Top changer position 1 Transition from 1 to 2

Oscillogram Main contact at working position A. Main contact A opens. Current transfer from main contact A to transition contact a takes place without arc formation, hence not recognizable in oscillogram (current IA).

Auxiliary contact a2 closes. Transition contact a opens. Starting at time t1, current la forms arc, recognizable in oscillogram by occurrence of arc voltage UA.

Transition from 2 to 3 3 4

current la flows as arc from t1, to t2, extinguished at current zero (t2). UA occurs as arc voltage from t1, to t2. UA occurs as recovery voltage from t2 to t3 at transition contact voltage drop across R1 and R2. Auxiliary contact b2 closes, recognizable in oscillogram by of commencement of current I b2 (t3). Auxiliary contact a1 opens, current la1 occurs as arc starting at t3.

Transition from 4 to 5

Current Ia1 occurs as arc at auxiliary contact a1 from t3 to t4, extinguished at current zero (t4). UA occurs as recovery voltage from t4 to t5 at auxiliary contact a1, brought about by voltage drop across R2 and R2 connected in parallel. Auxiliary contact b1 closes, recognizable in oscillogram by commencement of current I b1 (t5 ). Auxiliary contact a2 opens, current, I a2 occurs as arc starting at t5.

Transition from 6 to 7 7 8

Current I a2 occurs as arc at auxiliary contact a, from t5 to t6, extinguished at current zero (t6). UA occurs as recovery voltage from t6 to t7 at auxiliary contact a2 being equal to the sum of the voltage drop across R2 and R1 plus the tap voltage. Transition contact b closes, recognizable in oscillogram by commencement of current lb (t7 ). Auxiliary contacts b2 and b1 shorted by the closing of transition contact b so that no arc occurs on the opening of auxiliary contact b2.

9.

Main contact B closes thereby taking up working position B and passing working current; not recognizable in oscillogram. Tap change completed.
13

ON-LOAD TAP CHANGER TYPE D General Manual

5.

Motor Drive

The on load tapchanger type D is operated by a motor drive unit MA2 mounted outside the transformer tank. The motor drive MA2, however, is limited to on load tap changers having not more than 35 tapping positions. All the components which belong to the motor drive are contained in a sheet metal housing designed for outdoor mounting and consisting of a case and a door. The Drive shaft is the mechanical connection between motor drive and tap changer head. The bevel gear serves for diverting motion from the vertical to the horizontal direction. The vertical drive shaft has to be mounted be.tween motor drive and Bevel Gear and the horizontal drive shaft between bevel gear and tap changer. The motor drive unit is powered by a 415V, 50 Hz three phase motor (phase sequence RYB clockwise) and with a stepping mechanism for direct and remote operation. Over travel in either direction is prevented by comprehensive mechanical and electrical safety features. The equipment also includes a six figure counter showing the number of operations performed by the diverter switch, and a dial indicating the present position of the on load tapchanger. Remote indication of on load tapchanger setting at any time can be given by a digital display unit. The built in electric heater prevents condensate forming in the drive housing. For emergency operation and for setting up the motor drive unit when putting the on load tap changer into service, a crank handle is provided. When pushed on to its shaft, this handle interrupts the motor circuit. Re-engagement of the motor drive is brought about by pushing back the locking pin on the shaft after the crank handle has been removed.

Fig. 10 Motor Drive MA2


14

ON-LOAD TAP CHANGER TYPE D General Manual

6 Drying Out the On-Load Tap Changer The undermentioned drying out times should be lengthened accordingly if a fairly long period of storage is unavoidable. Prior to being put on load, the tapchanger must be dried out. The following are the minimum requirements for this process : 6.1 Heat up in air from room temperature to a maximum temperature of 110oC. The heating must be continued for at least 12 hours and a uniform rate of temperature rise must be ensured (< 10o/h). 6.2 Drying by air circulation at a maximum temperature of 110oC for not less than 20 hours. 6.3 Drying for at least 100 hours in vacuum at a residual pressure < 1 mm of mercury without oil, at a maximum temperature of 110oC. 6.4 Impregnating with prepared oil. The figures stated above represent the minimum drying out times which are necessary in order to maintain or restore the electical properties of the fibre laminate to a satisfactory standard. Over rapid dehumidification under conditions of high vacuum and high temperature is to be avoided, otherwise localized deterioration in the bonding of the material may result. The figures given under 6.1 and 6.2 for the preliminary drying stage should therefore be adhered to strictly. If the on-load tapchanger and transformer have to be dried out simultaneoulsy and if the latter has to be given an extra long period of drying, the final drying stage mentioned under 6.3 above may also be carried out under conditions other than those specified in regard to pressure, temperature and duration, subject to observance of the minimum requirements. Even considerably longer drying times need give rise to no anxiety. On no account, however, should the maximum temperature of 110oC mentioned earlier be exceeded. To prevent freeze drying the drying out temperature should not be below 60oC. 7 Inspection In the design and construction of the on load tapchanger special attention has been paid to ensuring that all parts subject to wear in the tapchanger itself and in the motor drive unit, such as the gearing, energy accumulator unit and diverter switch, are readily accessible for checking. as with all switchgear it is advisable that on load tap changers also should be given regular checks at intervals depending on the prevailing duty conditions (see appropriate inspection instructions). After the oil shut-off cock (123) has been closed, the few litres of oil drained off via the oil suction plug (201) and the cover (106) removed, the diverter switch unit can if necessary be withdrawn from the oil tank (203) for checking. This is a simple matter because the connections between the diverter switch and the oil tank are made by sliding contacts (317). After the diverter switch unit has been checked over and overhauled if necessary it goes back into the oil tank again without any possibility of being wrongly positioned. The electrical connections are restored by the sliding contacts already mentioned. At the same time the connection between the main gear unit (121) and the driving crank of the energy accumulator unit (304) is automatically made at a readily visible point in the on-load tapchanger head by means of the coupling (303) (Fig. 12). The tapchanger is now ready for service again. All mechanical movements can be observed with the on-load tapchanger head (103) opened, and the cover (106) need only be refitted after it has been verified that the mechanical functioning of the

15

ON-LOAD TAP CHANGER TYPE D General Manual

energy accumulator unit together with the latching devices and associated indicating gear is correct. Even with the cover closed, the position indicator is still visible through the window (114). Experience shows that under normal conditions skilled personnel should be able to carry out the necessary inspection on a three-phase on load tapchanger and of the motor-drive operating it in about eight hours. 8 Protective Relay RS 2001 The protective device needed for disconnecting a regulating transformer in which a fault condition has occured includes an oil Surge Operated relay RS 2001 specially developed by us for use with on load tap changers. The protective relay RS2001 (see Fig. 11) reacts to faults in the oil space of the diverter swtich. Under normal load and at the overload permitted for the unit the gases given off do not cause the protective relay to operate. In the event of unduly high pressure surges and in response to a specific rate of oil flow the lever system linked to the flap is operated.

Fig. 11. Protective Relay RS 2001

16

ON-LOAD TAP CHANGER TYPE D General Manual

18

ON-LOAD TAP CHANGER TYPE D General Manual

22

ON-LOAD TAP CHANGER TYPE D General Manual

23

You might also like