Professional Documents
Culture Documents
( )
\
|
|
(
(
IA0_r1
v
( )
2
.00001 +
:=
(3)
Fig. 12 produces a forward/reverse fault impedance plane.
If the resulting impedance calculation is below the forward
threshold (and all of the supervisory conditionals are met), the
fault is declared forward. Conversely, if the impedance is
above the reverse threshold, the fault is declared reverse.
Zero-Sequence
Impedance Plane X
0
R
0
Reverse Fault
Forward Fault
3V
0
3I0 (Forward Fault)
3I0 (Reverse Fault)
(a) Zero-Seq. Phasors (b) Impedance-Plane Directional
Element Characteristics
Fig. 12. Ground Directional Element Characteristics
Similarly, Fig. 13 is a MathCAD produced forward/reverse
fault impedance plane showing the relationship between 3V
0
and 3I
0
for forward and reverse faults. Positive Z
0T
indicates a
forward fault as indicated in Fig. 13a. Negative Z
0T
indicates
a reverse fault as indicated in Fig. 13b.
0 5 10 15 20 25 30
3000
2000
1000
0
1000
VA0_r1
v
IA0_r1
v
Z0A_r1
v
Z0A_r2
v
v
RS
(a) In-line section
0 5 10 15 20 25 30
500
0
500
1000
1500
2000
VA0_r3
v
IA0_r3
v
Z0A_r3
v
Z0A_r4
v
v
RS
(b) Out-of-section
Fig. 13. Ground Directional Decision
As mentioned above relay manufacturers use their own
algorithms for relay protection elements. As such, our relay
model utilizes the 32 element in Equations (4)-(6), which
represents the ground directional protection of an SEL relay,
which utilizes the 32 element. The 50 element is essentially
the level equation enabled. Equation (4) consists of zero-
sequence algorithm resulting in Equation (6) equating to
Fig. 11.
F32G_r1
v
Z0A_r1
v
Z
0Forward
( )
IA0_r1
v
a
0
IA1_r1
v
( )
:=
(4)
Level1G_r1_pu
v
1 IA0_r1
v
Level_1_50G_r1 if
1 Level1G_r1_pu
v 1
0.01 if
0 otherwise
:=
(5)
TR67G_r1
v
T32G_r1
v
TR50G_r1
v
:=
(6)
VII. SIMULATION RESULTS
After modeling the power system in ATP, the generated a
COMTRADE file is incorporated into MathCAD to test the
relay algorithm. Fig. 14 shows differential element correctly
isolates fault by asserting both Relay 1 and Relay 2, only,
isolating two- and three-phase fault conditions on the faulted
line while leaving the unaffected line in tact. Additionally,
even though a ground phase may have been involved in both
the two- and three-phase faults i.e. double line-to-ground fault
the zero sequence algorithm remains low for all four relays
such that its associated element, 67N, did not pick-up.
0 10 20 30
0
0.5
1
1.5
2
Tr_R1
v
Tr_R2
v
v
RS
0 10 20 30
0
0.5
1
1.5
2
Tr_R3
v
Tr_R4
v
v
RS
(a) In-line section (b) Out-of section
Differential Element
0 10 20 30
0
0.5
1
1.5
2
Ind_R1
v
Ind_R2
v
v
RS
0 10 20 30
0
0.5
1
1.5
2
Ind_R3
v
Ind_R4
v
v
RS
(a) In-line section (b) Out-of section
Ground Directional Element
Fig. 14. Differential Protection Results
Likewise, Fig. 15 shows ground fault protection
appropriately indicates a single line-to-ground on the faulted
line. This is seen as a high signal on ground detection graph
and no state change for the unaffected line or an assert signal
by the differential protection graph.
0 10 20 30
0
0.5
1
1.5
2
Tr_R1
v
Tr_R2
v
v
RS
0 10 20 30
0
0.5
1
1.5
2
Tr_R3
v
Tr_R4
v
v
RS
(a) In-line section (b) Out-of section
Differential Element
0 10 20 30
0
0.5
1
1.5
2
Ind_R1
v
Ind_R2
v
v
RS
0 10 20 30
0
0.5
1
1.5
2
Ind_R3
v
Ind_R4
v
v
RS
(a) In-line section (b) Out-of section
Ground Directional Element
Fig. 15. Ground Directional Protection Results
All three ATP models in Fig. 7 resulted in identical fault
isolation responses for both differential and ground fault
protection. The difference is a setting change in MathCAD.
VIII. CONCLUSIONS
Using two different software packages to develop models
requires a thorough knowledge of relay principles. The
current flow direction in ATP affects the MathCAD results.
While this may be seem obvious, it is easy to include a
negative sign in MathCAD for direction as well.
A single line power system provides the concept of
differential and ground fault protection from a practical. In
doing so it teaches directional functionality. This becomes
more evident with the parallel line power system in that fault
isolation depends on relay settings. In other words, the
assertion of both relays in the single line system, does not
initially mean this occur for the parallel line system. Three
relays may assert, but this only means that the settings are
incorrect. The added benefit of the parallel is it use of explain
blocking schemes.
IX. REFERENCES
[1] M. Kezunovic, T. Popovic, D. Sevcik and H. DoCarmo, Transient
Testing of Protective Relays: Results Methodology and Tools,
International Conference on Power Systems Transients (IPST 2003),
New Orleans, Paper 5c-1, September 28November 2, 2003.
[2] B. W. Garret, Digital Simulation of Power System Protection under
Transient Conditions, Ph.D. thesis at the University of British
Columbia, 1987.
[3] R.E. Wilson and J.M. Nordstrom, EMTP Transient Modeling of a
Distance Relay and a comparison with EMTP Laboratory Testing,
IEEE Transactions on Power Delivery, Vol.8, No. 3, pp. 984992, July
1993.
[4] M.T. Glinkowski and J. Esztergalyos, Transient Modeling of
Electromechanical Relays: Part I, Armature Type Overcurrent Relay,
IEEE Transactions on Power Delivery, Vol. 11, No. 2, pp. 763770,
April 1996.
[5] M.T. Glinkowski and J. Esztergalyos, Transient Modeling of
Electromechanical Relays: Part II, Plunger Type 50 Relays, IEEE
Transactions on Power Delivery, Vol. 11, No. 2, pp. 771782,
April 1996.
[6] C. Henville, A. Hielbert, R. Folkers and R Wierckx, Dynamic
Simulations Challenge Protection Performance, Proceedings of the
Western Protective Relay Conference, October 2003, [Online].
Available: http://www.selinc.com/techpprs/6156.pdf
[7] P.G. McLaren, R. Kuffel, R. Wierckx, J. Giesbrecht and L Ardent, A
Real Time Digital Simulator for Testing Relays, IEEE Transactions on
Power Delivery, Volume 7, Number 1, pp. 207213, January 1992.
[8] C. Kim, M. Lee, R.K. Aggarwal, Educational Use of EMTP MODELS
for the Study of a Distance Relaying Algorithm for Protecting
Transmission Lines, IEEE Transactions on Power Systems, Vol. 15,
No. 1, pp. 915, February 2000.
[9] R.W. Wall and B.K. Johnson, Using TACS Functions Within EMTP to
Teach Protective Relaying Fundamentals, IEEE Transactions on Power
Delivery, Vol. 12, No. 1, pp. 310, February 1997.
[10] J.N. Peterson and R.W. Wall, Interactive Relay Controlled Power
System Modeling, IEEE Transactions on Power Delivery, Vol. 6,
No. 1, pp. 96102, January 1991.
[11] MATLAB, The MathWorks, Inc., 3 Apple Hill Drive, Natick MA
01760-2098 USA, http://www.mathworks.com/
[12] MATHCAD, MathSoft Inc., 101 Main Street, Cambridge,
Massachusetts, 02142 USA, http://www.mathsoft.com
[13] H.W. Dommel, Digital computer solution of electromagnetic transients
in single-and multi-phase networks, IEEE Transactions on Power
Apparatus and Systems, Vol. PAS-88, No. 4, pp. 388399, April 1969.
[14] J. Roberts, H.J. Altuve and D. Hou, "Review of ground fault protection
methods for grounded, ungrounded and compensated distribution
systems," presented at the 28th Annual Western Protective Relay Conf.,
Spokane, Washington, October 23-25, 2001. [Online]. Available:
http://www.selinc.com/techpprs/6123.pdf
X. BIBLIOGRAPHY
Louis Dusang received a Bachelor of Science in Electrical Engineering
degree from Mississippi State University in 1988 and is pursuing his MSEE at
the University of Idaho. He is a Registered Engineer in South Carolina. He
has been an electrical engineer with Northrop Grumman Shipbuilding since
November 2001. He is the lead project engineer for LDA Power Systems.
Prior to joining NGSB, Mr. Dusang worked as both an electrical engineer and
controls engineer for Jacobs.
Brian K. Johnson (M92, SM2006) received the Ph.D. in Electrical
Engineering from the University of Wisconsin-Madison in August 1992. He is
currently an associate professor in the Department of Electrical Engineering at
the University of Idaho. His interests include HVdc transmission, power
system protection, and the application of power electronics to utility systems
and realtime simulation of traffic systems.