MR

MR

33KV SUB STATION EQUIPMENT Supply installation testing and commissioning of HV Air insulated distribution switch gear consisting of one 26.3 kA for 1 second rupturing capacity at 33 kV rated, metal clad, floor mounting, vertical isolation,horizontal drawout SF6 Cercuit breaker suitable to work on 3 ph.,50 Hz., 33 kV earthed system. the panel shall be equipped with following accessories as per Single line diagram and specification (suitable for indoor services complete as required) . Incoming cum outgoing one panel board completed as required 630 Amp. 3 pole, 26.3 kA, at 33 kV, motor operated, spring charged, trip free, mechanical as well as electrical interlock SF6 Circuite Breaker (Indoore Type) - 1 No. One trip free, motor charged, spring released closing mechanism fitted with shunt trip suitable for 230 volt AC operation complete with necessary auxliary switches, emergency hand trip device and mechanical on off indications. 100/60/5A ratio, 15 VA, class 1 Resin cast current transformer for metering purposes-3 nos. 100/60/5A ratio, 15 VA, class 10P 10 Resin cast current transformer for protection purposes-3 nos. Single phase Horizontal drawout type potential transformer of 33 kV/11kV with 50 VA burden complete connected star/star with fuses as per requirement. - 3 nos. Two Nos. over currewnt and One earth fault element with IDMT self powered relay with shunt trip coil on 230 volt AC with element for instenteneous trip relay arrangement. Instrument Panel One 96 SQMM ,scaled 0-33 kV flush type voltmeter with 3 way ON & OFF selector switch. One 96 SQMM ,scaled 0-100 A flush type Ammeter with 3 way & OFF selector switch. Anti pumping relay - One no. Trip circuite Supervision relay, trip annunciation relay and trip circuit healthy - One no. Lock out relay - One no. Gas pressure Low - One no.(Alarm Type) One set of Red/Green/indicating lamp for close andopen operation One set of White indicating lamp for Phases One set of Amber indicating lamp for Trip circuite Healthy indication Cable box with single compression gland suitable to receive XLPE cable of 3 core 240 SQ MM Supply installation testing and commissioning of HV Air insulated distribution switch gear consisting of five nos. 350MVA for 1 second rupturing capacity at 11 kV rated, metal clad, floor mounting, vertical isolation,horizontal drawout Vaccume Circuit breaker suitable to work on 3 ph.,50 Hz., 11 kV earthed system. the panel shall be equipped with following accessories as per Single line diagram and specification suitable for indoor complete as required . Incoming 400 Amp. 3 pole,350 MVA, at 11 kV, motor operated, spring charged, trip free, mechanical as well as electrical interlock VCB (Indoore Type) - 2 No. consisting of following One trip free, motor charged, spring released closing mechanism fitted with shunt trip suitable for 230 volt AC operation complete with necessary auxliary switches, emergency hand trip device and mechanical on off indications. 200/5A ratio,30VA, class 0.5 Resin cast current transformer for metering purposes-1 no. 200/5A ratio,30 VA, class 10P10 Resin cast current transformer for protection purposes- 1 no. Single phase Horizontal drawout type potential transformer of 11 kV/110V with 50 VA burden complete connected star/star with fuses as per requirement. - 1 no. Two Nos. over currewnt and One earth fault element with IDMT self powered relay with shunt trip coil on 230 volt AC Instrument Panel One 96 SQMM ,scaled 0-15 kV flush type voltmeter with 3 way ON & OFF selector switch. Anti pumping relay - One no. Trip circuite Supervision relay, trip annunciation relay and trip circuit healthy - One no. Lock out relay -One no. One set of Red/Green/indicating lamp for close and open operation One set of White indicating lamp for Phases One set of Amber indicating lamp for Trip circuite Healthy indication

Set of three phase 630 Amp. PVC Insulated copper Bus bar Outgoings 400 Amp. 3 pole, 350 MVA, at 11 kV, motor operated, spring charged, trip free, mechanical as well as electrical interlock Vaccume Circuite Breaker (Indoore Type) - One Bus Coupler with 200/5A 30 VA Class 1 Resin cast current transformer for metering purpose - 1no. 400 Amp. 3 pole, 350 MVA, at 11 kV, motor operated, spring charged, trip free, mechanical as well as electrical interlock Vaccume Circuite Breaker (Indoore Type) - 2 Nos .As out going consisting of following One trip free, motor charged, spring released closing mechanism fitted with shunt trip suitable for 230 volt AC operation complete with necessary auxliary switches, emergency hand trip device and mechanical on off indications. 200/5A ratio, 30 VA, class 1 Resin cast current transformer for metering purposes - 1 no. 200/5A ratio, 30 VA, class 10P 10 Resin cast current transformer for protection purposes - 1 no. Two Nos. over currewnt and One earth fault element with IDMT self powered relay with shunt trip coil on 230 volt AC Trip circuite Supervision relay, trip annunciation relay and trip circuit healthy - One no. Instrument Panel Two 96 SQMM ,scaled 0 -15 kV flush type voltmeter with 3 way & OFF selector switch. Two 96 SQMM ,scaled 0-200 A flush type Ammeter with 3 way & OFF selector switch. Lock out relay - Two nos. Two static pole Triple pole variable inverse definite mean time over current and earth fault relay with two outer elements connected tfor over current protection and the middle element for protection with adujstable over current and earth fault setting. Four set of Red/Green/indicating lamp for close andopen operation Four set of White indicating lamp for Phases Four set of Amber indicating lamp for Trip circuite Healthy indication Cable box with single compression gland suitable to receive XLPE cable of 3 core 240 SQ MM

OUTDOOR TRANSFORMER : Supply, Receiving, unloading Storing Installation, testing and commissioning of 2.0 MVA, 33/11 KV,step down, 3 phase, 50Hz, DYN 11 vector group,CT, Tapping on HV + 5% to 15% through Off Load Tap changer, Double Copper Wound, OTI, WTI and Bucholtz Relay, MOG along with Marshalling box with all standard fittings as per IS : 2026 and accessories and first filling of oil .

DG Set : Diesal Engine operating at 1500 rpm rated for continuous duty, with an additional 10 % overload capacity for one hour in a period of twelve hours of continuous operation conditions as per BS - 649/5514. The diesel engine is inclusive of all standard accessories such as suitable flywheel, flywheel housing complete with starte gearing, flexible coupling siutable to match flywheel, electrical starte motor 24 volt DC battery Charging , hydraulic Governer, Fuel Pump P T Type, ube Oil Pump, Lube Oil Cooler, water pump,air cleaner dry type , vaccume indicator , fuel and lube oil filter , corrosion resistor, safty control against low lube oil pressure and high cooling, high water temp.relay , lube oil by pas filter, scilencer, Flexible pi foot mounted with ball mand roller bearing on end shield .

The alternator shall confirm to IS - 4722/ BS -2613 and is siutable for tropical conditions. It should be copmlete with battery, base frame , fuel tank, anti vibration mounting pad, and manual control panel with sound proof enclosure pipe for silencer , raditor assembly, . It should be complete with instruments like starting switch with key, lube oil tepreture gauge , lube oil pressure gauge, Water temp. gauge, battery charging alternator, indicating lamps, starte push button, techometer with hour counter .

It should be comlete with alternator in SPDF enclosure, self regulated , slf excited. The manual change over switch (off load) of appropriate capacity is also to be provide in this item. 40.0 KVA