NEW

RMS10, RMS12 Protection Releases (GTU-D)


for Spectronic ACBs

Salient features
RMS10, RMS12 Available in 2 variants - RMS10, RMS12 Microprocessor based technology Current metering with graphical backlit display as standard Wider range of O/L, S/C, Inst. and G/F settings Thermal memory & load shedding Two way communication through Modbus Reduced Energy Let Time (RELT) safety feature Zone selective Interlocking Upgradeable using voltage conditioners for voltage & power parameters Additional protections - under/over voltage, current and voltage unbalance as well as reverse power Ease of settings with touch buttons Wide range of rating plugs

02

RMS10, RMS12 Protection Releases

RMS10, RMS12 Protection Releases

03

Parameters Graphical backlit Display Settable range(LT) Overload protection Settable delay(LTD) Settable range (ST) Short circuit Protection Settable delay(STD) 0.5 to 1In in steps of 0.05 Class 0.5 to 30 @6Ir.There are 19 thermal CB type curves and 22 fuse (IsqT)type bands availbale for selection. 1.5 to 9Ir in steps of 0.5xLT 90msec to 400msec (11 settings).Both slope setting and xed time delay settings (independent)are availbale.3 nos. of IsqT slopes settings available 2In to 15In (depending upon the rating) in steps of 0.5In 1.5In to 15In in steps of 0.5In ( Settable through Communication/24Vac or dc signal through wiring from Input1) 0.2 to upto 0.6 CT current depending on rating (Max 1200A) in steps of 0.01x CT 58 msec to 417 msec Pick up adjustable from 10% to 50% in steps of 1% and adjustable delay from 1-15sec( option to disable) Pick up adjustable from 10% to 50% in steps of 1% and adjustable delay from 1-15sec( option to disable) Pick up adjustable from 50% to 90% in steps of 1% and adjustable delay from 1-15sec( option to disable) Pick up adjustable from 110% to 150% in steps of 1% and adjustable delay from 1-15sec( option to disable)

RMS10 Available Available Available Available Available

RMS12 Available Available Available Available Available

RMS10, RMS12 releases are equipped with programmable inputs/outputs which can be programmed as follows:Input
Inputs can be assigned to two main functionalities: Reduced Energy Let-Through (RELT) Trip the breaker

Instantaneous Protection

Adjustable (Inst.)

Available

Available

Input OFF TRIP

Input 1 Assignment

Summary Description No action taken. Causes a breaker to trip. Causes unit to use the RELTsetpoint as long as input is active.

RELT

Adjustable Adjustable GF pick up/alarm Settable delay Voltage unbalance Current unbalance Undervoltage

Available

Available

Ground Fault

Available Available NA NA NA NA

Available Available Available Available Available Available Available Available Available Available Available Available Available Available Available Available Available Available Available Available Available

1 RELT*

Output The number of outputs available varies by breaker. These outputs are relay contact outputs to secondary disconnect (any one can be used). Each output can be configured per Table below:Group Description 1 2 3 GF alarm Over-current trip (GF, INST, LT, ST) Protective relays Function Function Summary Turns on when GF alarm is activated. Over-voltage trip turns ON the relay. When protective relay trips the relay contact closes Exceeding current alarm pick-up turns closes the relay contact. Exceeding current alarm pick-up turns closes the relay contact. Relay contact will be closed or opened depending on the health contact setting. Output relay contact closes when the RELT pickup is enabled.

Protective relay functions Overvoltage Power reversal Power direction set up Communication Modbus Current Voltage Real Power Reactive power Apparent power Metering Peak Power demand Energy Frequency Power factor Zone Selective Interlocking Thermal memory Load shedding

Adjustable from 10KW to 990KW in steps of 10KW and NA adjustable delay from 1-15 sec( option to disable) Selects to normal power ow direction for breaker from line to load or vice versa No modbus concentrator required.Cable to be directly connected to RS485 port on release Phase A,B,C,neutral (unit A) Phase L1,L2,L3 (unit V) Phase L1,L2,L3 and total -KW Phase L1,L2,L3 and total-KVAR Phase L1,L2,L3 and total-KVA Total -Auto ranging from 0.00KWH to 999mWH Phase A,B,C and total-Auto ranging from 0.00KWH to 999mWH Hz % NA NA NA NA NA NA NA NA NA NA NA NA Available NA

Current alarm 1

Current alarm 2

*Health status

RELT*

*RELT needs to be factory enabled. Once RELT is enabled, the input and output contact available are dedicated to this features and no other options for input / output will available for use.