Grandfjra 28

N-6415 Molde, Norway


Tel. + 47 71 20 68 00
Fax. + 47 71 20 68 01
E-mail: aquaterm@aquaterm.no

Condensers series TK
A

F*

F*

C
E

Optional

2 pas s

4 pas s

Titanium
Condensers

Dimensions (all measurements in mm)


Type

E
2 pass

E
4 pass

F*

R507

(empty weight)
NH3
kg

8-20
8-25
8-30
8-40

2160
2660
3160
4160

120
120
120
120

480
480
480
480

260
260
260
260

DN 65
DN 65
DN 65
DN 65

DN 50
DN 50
DN 50
DN 50

48.3
48.3
48.3
48.3

33.7
33.7
33.7
33.7

33.7
33.7
33.7
33.7

94
114
135
177

10-20
10-25
10-30
10-40

2160
2660
3160
4160

120
120
120
120

530
530
530
530

310
310
310
310

DN 80
DN 80
DN 80
DN 80

DN 65
DN 65
DN 65
DN 65

48.3
48.3
48.3
48.3

48.3
48.3
48.3
48.3

33.7
33.7
33.7
33.7

130
158
186
243

The Aquaterm condensers are designed for Heavy Duty use in RSW-, freezing-,
and AC systems. The condensers are produced in land- and marine versions.
Marine condensers longer than 2,5 metres have drainage tubes in the edges,
compensating for the rolling of the ship.

12-20
12-25
12-30
12-40

2160
2660
3160
4160

210
210
210
210

640
640
640
640

400
400
400
400

DN 100
DN 100
DN 100
DN 100

DN 80
DN 80
DN 80
DN 80

48.3
48.3
48.3
48.3

48.3
48.3
48.3
48.3

33.7
33.7
33.7
33.7

184
224
263
343

The TK series is built with tubes and tubesheets of pure titanium, and offers a
corrosion proof alternative for sea water, brackish water, and other corrosive liquids.

14-20
14-25
14-30
14-40

2240
2740
3240
4210

320
320
320
320

580
580
580
580

440
440
440
440

DN 125
DN 125
DN 125
DN 125

DN 100
DN 100
DN 100
DN 100

60.3
60.3
60.3
60.3

48.3
48.3
48.3
48.3

48.3
48.3
48.3
48.3

235
285
336
437

16-20
16-25
16-30
16-40

2160
2160
3160
4160

200
200
200
200

690
690
690
690

450
450
450
450

DN 125
DN 125
DN 125
DN 125

DN 100
DN 100
DN 100
DN 100

60.3
60.3
60.3
60.3

60.3
60.3
60.3
60.3

48.3
48.3
48.3
48.3

308
374
440
573

The condensers have plain tubes (no fins at the refrigerant side). Consequently,
they are mainly designed for ammonia systems. Plain tubes are less efficient for
the R 507 refrigerant, but for use in corrosive environments, the titanium version
may be a cost efficient alternative also for R 507.

18-20
18-25
18-30
18-40

2120
2620
3120
4120

380
380
380
380

740
740
740
740

540
540
540
540

DN 150
DN 150
DN 150
DN 150

DN 125
DN 125
DN 125
DN 125

88.9
88.9
88.9
88.9

60.3
60.3
60.3
60.3

48.3
48.3
48.3
48.3

347
420
493
639

20-20
20-25
20-30
20-40
20-60

2120
2620
3120
4120
6120

460
460
460
460
460

790
790
790
790
790

600
600
600
600
600

DN 200
DN 200
DN 200
DN 200
DN 200

DN 125
DN 150
DN 150
DN 150
DN 150

88.9
88.9
88.9
88.9
88.9

88.9
88.9
88.9
88.9
88.9

60.3
60.3
60.3
60.3
60.3

481
584
688
895
1310

*Condensers of length -20 and -25 are equipped with one gas nozzle, length -30, 40 and -60 have two nozzles
Design pressure, water side:
Design pressure, refrigerant side:
Design code:
Classification:
Certificat:

6 bar
25 bar
DNV Pt.4 Ch.3
Pressure vessel Class 1
DNV (Det Norske Veritas)

25.09.2003 Subject to change without notice

The connections between the tubes and the tube sheet are welded.
The shell is produced of seamless tube, St 35.8, sand blasted inside and outside,
and protected with two coats of paint.
The water heads are produced of polyethylene (small models) or vinyl ester
for (large models) supported by hot dip galvanized steel plates.
The water connections are DIN PN 10 flanges.

Selection of condenser
To select a condenser, start by calculating the load ratio, which is the condenser
capacity in kW divided by the difference between the condensation temperature
and the incoming water temperature:

Q
kW/C
( T cond - T in)
Select a condenser with an LR that is higher than the calculated value from the
tables on the following pages.

LR =

Grandfjra 28