Air Conditioners

Technical Data
Outdoor unit - pair application

EEDEN12-100

RXS-K

Outdoor Unit Pair application RXS-K

TABLE OF CONTENTS RXS-K

1 2

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 5 6

3 4 5 6 7 8 9 10

Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling/Heating Capacity Tables
.................................... 8 14

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensional Drawings

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 15

Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centre of Gravity

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 16

Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Piping Diagrams

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 17

Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams - Single Phase

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Sound Pressure Spectrum
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 19

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation Range

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

1
k ic Sni Ul p- pr ao t o K i dr - l ti S pauX PS RO

Features
Energy efficient units: up to class A energy labels Seasonal efficiency, optimized for all seasons. Seasonal efficiency gives an indication on how efficient an air conditioner operates over an entire heating or cooling season. Compact casing (575mm in width and depth) enables unit to fit flush into ceilings and match standard architectural modules, without cutting ceiling tiles Modern style decoration panel in white (RAL9010) Whisper quiet operation: down to 24.5dBA sound pressure level Comfortable vertical auto swing ensures draughtfree operation and prevents ceiling soiling Fresh air intake for healthy living Since the flaps can move to a 0 degree position, virtually no draught can be experienced Possibility to shut 1 or 2 flaps for easy installation in corners Easy maintenance: switch box can be reached by simply removing the suction grille Standard drain pump with 750mm lift No optional adapter needed for DIII-connection: standard plug and play connection with centralised control systems, intelligent touch controller, intelligent manager, ... Outdoor units for pair application Energy efficient units: full range A class energy labels Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall Energy saving during standby mode: reduces current consumption by about 80% when operating In standby. If no people are detected for more than 20 minutes, the system will automatically switch to the current-saving mode. Outdoor unit silent operation: "silent" button on the remote control lowers the operation sound of the outdoor unit by 3dBA to ensure a quiet environment for the neighbourhood. Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency Anti-corrosion treated outdoor heat exchanger fin

1
1

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

Specifications
FTXS20K2V1B / RXS20K2V1B FTXS25K2V1B / RXS25K2V1B

2-1 Nominal Capacity And Nominal Input


Cooling capacity Min. Nom. Max. Heating capacity Min. Nom. Max. Piping connections Liquid Gas Drain Heat insulation Annual energy consumption EER COP Energy label Power input Cooling Heating Cooling Min. Nom. Max. Heating Min. Nom. Max. Notes (1) Energy label: scale from A (most efficient) to G (less efficient) kW kW kW kW kW kW kWh OD OD OD kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h mm mm mm

1.3 4,400 2.0 (3) 6,800 (3) 2.8 9,600 1.3 4,400 2.5 (4) 8,500 (4) 4.3 14,700 6.35 9.5 18.0 Both liquid and gas pipes 215 4.65 4.55 A A 0.320 0.430 0.760 0.310 0.550 1.120 0.620 1.410 0.570 1.000 285 4.39 4.52 2.8 (4) 9,600 (4) 4.7 16,000 2.5 (3) 8,500 (3) 3.2 10,900

3 1
2

(2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB, 24CWB; equivalent piping length: 5m (4) Heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m (5) 220V (6) 230V (7) 240V

2-1 Nominal Capacity And Nominal Input


Cooling capacity Heating capacity Annual energy consumption EER COP Energy label Power input Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m Cooling Heating Cooling Heating Nom. Nom. kW kW Nom. Nom. kW kW kWh

FDXS25E7VMB / RXS25K2V1B

2.40 (3) 3.20 (4) 345 3.48 3.52 A B 0.69 0.91

2-1 Nominal Capacity And Nominal Input


Cooling capacity Heating capacity Annual energy consumption EER Nom. Nom. kW kW kWh

FLXS25BAVMB / RXS25K2V1B

2.50 (3) 3.40 (4) 325 3.85

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

Specifications
FLXS25BAVMB / RXS25K2V1B

2-1 Nominal Capacity And Nominal Input


COP Energy label Cooling Heating Power input Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m Cooling Heating Nom. Nom. kW kW

3.47 A B 0.65 0.98

1
2

2-1 Nominal Capacity And Nominal Input


Cooling capacity Heating capacity Annual energy consumption EER COP Energy label Power input Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m Cooling Heating Cooling Heating Nom. Nom. kW kW Nom. Nom. kW kW kWh

FVXS25FV1B / RXS25K2V1B

2.50 (3) 3.40 (4) 285 4.39 4.30 A A 0.57 0.79

2-1 Nominal Capacity And Nominal Input


Cooling capacity Heating capacity Annual energy consumption EER COP Energy label Power input Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m Cooling Heating Cooling Heating Nom. Nom. kW kW Nom. Nom. kW kW kWh

FFQ25B9V1B / RXS25K2V1B

2.50 (3) 3.20 (4) 365 3.43 3.48 A B 0.73 0.92

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

Specifications
RXS20K RXS25K

2-2 Technical Specifications


Fan Type Air flow rate Cooling High Low Super low Heating High Low Super low Dimensions Unit Height Width Depth Packed unit Height Width Depth Weight Piping connections Unit Packed unit Liquid Gas Drain Piping length OD OD ID OD OU - IU System Adiitional refrigerant charge Level difference Heat insulation Sound pressure level Cooling Heating Casing Heat exchanger Colour Length Rows Fin pitch Stages Tube type Fin Fan motor Model Output Speed Cooling Heating Sound power level Compressor Cooling Model Type Output Operation range Cooling Heating Ambient Ambient Min. Max. Min. Max. W CDB CDB CWB CWB High High High W rpm rpm dBA Super low rpm Super low rpm Type Quantity Quantity mm mm High Silent operation High Silent operation dBA dBA dBA dBA IU - OU Max. Max. m/min cfm m/min cfm m/min cfm m/min cfm m/min cfm m/min cfm mm mm mm mm mm mm kg kg mm mm mm mm m kg/m m Chargeless m

Propeller fan 33.5 1,183 30.1 1,063 28.3 999 25.6 904 550 765 285 612 906 364 34 38 6.35 9.5 18.0 20 10 0.02(for piping length exceeding 10m) 15 Both liquid and gas pipes 46 43 47 44 Ivory white 805 2 1.4 24 7 Hi-XA Waffle louvered fin D23H-28 23 860 780 860 740 61 1YC23AEXDC Hermetically sealed swing compressor 600 -10 46 -15 18

3 1
2

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

Specifications
RXS20K RXS25K

2-2 Technical Specifications


Refrigerant Type Charge kg l Type Charged volume

R-410A 1.0 FVC50K 0.375


RXS20K RXS25K

1
2

Refrigerant oil

2-3 Electrical Specifications


Power supply Phase Frequency Voltage Current Nominal running current Cooling (RLA) Heating Starting current Wiring connections Notes (1) 220V (2) 230V (3) 240V (4) SL: The silent fan level of the air flow rate setting For power supply Cooling Heating Remark Hz V A A A A

1~ 50 220-240 2.21 (1) / 2.12 (2) / 2.03 (3) 2.61 (1) / 2.52 (2) / 2.43 (3) 2.8 2.8 3.01 (1) / 2.92 (2) / 2.83 (3) 3.11 (1) / 3.02 (2) / 2.93 (3) 3.3 3.3

3 for power supply, 4 for interunit wiring (including earth wiring)

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

3
3-1

Electrical data
Electrical Data

3 1
3

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

4
4-1

Capacity tables
Cooling/Heating Capacity Tables

1
4

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

4
4-1

Capacity tables
Cooling/Heating Capacity Tables

3 1
4

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

4
4-1

Capacity tables
Cooling/Heating Capacity Tables

1
4

10

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

4
4-1

Capacity tables
Cooling/Heating Capacity Tables

3 1
4

Split - Sky Air Outdoor Unit

11

Outdoor Unit Pair application RXS-K

4
4-1

Capacity tables
Cooling/Heating Capacity Tables

1
4

12

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

4
4-1

Capacity tables
Cooling/Heating Capacity Tables

3 1
4

Split - Sky Air Outdoor Unit

13

Outdoor Unit Pair application RXS-K

5
5-1

Dimensional drawings
Dimensional Drawings

1
5

14

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

6
6-1

Centre of gravity
Centre of Gravity

3 1
6

Split - Sky Air Outdoor Unit

15

Outdoor Unit Pair application RXS-K

7
7-1

Piping diagrams
Piping Diagrams

1
7

16

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

8
8-1

Wiring diagrams
Wiring Diagrams - Single Phase

3 1
8

Split - Sky Air Outdoor Unit

17

Outdoor Unit Pair application RXS-K

9
9-1

Sound data
Sound Pressure Spectrum

1
9

18

Split - Sky Air Outdoor Unit

Outdoor Unit Pair application RXS-K

10

Operation range

10 - 1 Operation Range

3 1
10

Split - Sky Air Outdoor Unit

19

Daikins unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.

Please fill out the requested information Please fill out the requested information

Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com

Daikin products are distributed by:

The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

EEDEN1 2 - 1 0 0

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

EEDEN12-100 01/12 Copyright Daikin The present publication supersedes EEDEN11-100 Printed on non-chlorinated paper. Prepared by Goekint Graphics NV, Belgium Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende