INTERNATIONAL CONSTRUCTION & INVESTMENT CONSULTANCY CO.

,LTD
Address : 2nd floor , 140 Nguyen Van Thu Street. Dakao Ward , District 1 , HCM City VietNam Tel: (84-8) 9111915 - 9111916 ; Fax : (84-8) 9111914 Email : m_e@icic.com.vn ; Website : www.icic.com.vn

Cng trnh/Project : Khu nh Estella II Hng mc/Service : Pressurization - Calculation sheet

F06-DME Ngy/Date : 31/12/2013 Reason for issue : Concept; Tender; Approval; Construction; Boq; Information; Action; Comment; Revision S lng pht hnh/Number of copies Issued - a CD/Disk : - Bn in/Print paper : - Bn photo/Photo paper : - Khc/Others :

Danh sch pht hnh/Distribution List : - Khch hng/Client : Keppel land - Kin trc/Architect : - T vn C-in/M&E Consultant : ICIC - Nh thu chnh/Main Contractor : - Khc/Others :

1./ -

Standard refer : Singapore CP-13 Mechanical ventilation and air conditioning in building

Standard *Floor Area (A) : *Efficient Area : *Height Level(Efficient): *Air changes per hour (ACH) Normal operating : Emergency operating : *Exhaust air flow : Normal operating : Emergency operating : *Fresh air flow : Normal operating : Emergency operating : Block 5: *Pump room area : Height : Air Changes per Hour : Exhaust air flow : *LV switch room : Height : Air Changes per Hour : Exhaust air flow : Block 6: *Pump room area : Height : Air Changes per Hour : Exhaust air flow : *LV switch room : Height : Air Changes per Hour : Exhaust air flow : Block 7: *Pump room area : Height : Air Changes per Hour : Exhaust air flow : *Swimming pool Pump room area : Height : Air Changes per Hour :

CALCULATION SHEET OF VENTILATION OF BASEMENT Singapore CP 13 : 1999 15225 10420 2.5 6.0 9.0 43417 65125 34733 52100 m
2 2

m m

ACH ACH L/s L/s L/s L/s Adopt Adopt Adopt Adopt 43000 65000 35000 52000 L/s L/s L/s L/s

58 3 8 322 38 3 6 158

m m ACH L/s m m ACH L/s


2

Adopt

320

L/s

Adopt

160

L/s

48 3 8 267 26 3 6 108

m m ACH L/s m m ACH L/s


2

Adopt

270

L/s

Adopt

110

L/s

68 3 8 378 105 3 8

m m ACH L/s m m ACH


2

Adopt

380

L/s

Page 1 of 10

Exhaust air flow : *LV switch room : Height : Air Changes per Hour : Exhaust air flow :

583 52 3 6 217

L/s m m ACH L/s


2

Adopt

580

L/s

Adopt

220

L/s

Prepared Name : Thi Phong Signature :

Checking 01 Name : Thi Phong Signature :

Checking 02&03 Name : L Vn Xun Signature :

Page 2 of 10

INTERNATIONAL CONSTRUCTION & INVESTMENT CONSULTANCY CO.,LTD


Address : 2nd floor , 140 Nguyen Van Thu Street. Dakao Ward , District 1 , HCM City VietNam Tel: (84-8) 9111915 - 9111916 ; Fax : (84-8) 9111914 Email : m_e@icic.com.vn ; Website : www.icic.com.vn

Cng trnh/Project : Khu nh Estella II Hng mc/Service : Pressurization - Calculation sheet

F06-DME Ngy/Date : 31/12/2013 Reason for issue : Concept; Tender; Approval; Construction; Boq; Information; Action; Comment; Revision S lng pht hnh/Number of copies Issued - a CD/Disk : - Bn in/Print paper : - Bn photo/Photo paper : - Khc/Others :

Danh sch pht hnh/Distribution List : - Khch hng/Client : Keppel land - Kin trc/Architect : - T vn C-in/M&E Consultant : ICIC - Nh thu chnh/Main Contractor : - Khc/Others :

Standard refer : Singapore CP-13 Mechanical ventilation and air conditioning in building BS EN 12101-6 : 2005 Smoke and heat control system TCVN 2622: 1995 Fire prevention and protection for buildings and structures - Design requirements TCVN 6160: 1996 Fire protection - High rise building - Design requirements System Calculation : Different pressure between staircase and Lobby : 5010 Pa when all doors shall be closed. Different pressure between staircase and Lobby : 10 Pa when final exit door & two adjoining doors at any storeys shall be opened and all others shall be closed. - Air velocity through by the opened doors : 0.75 m/s. - In normal condition, ventilation for staircase : 4 Air changes per hour. STAIRCASE PRESSURIZATION CALCULATION SHEET Standard: BS EN 12101-6 : 2005 System classification: Using class E for this design. I. Input data: * Velocity through the opened door (V - m/s) : 0.75 * Door area (A - m2) 1.6 * Number of opened door (n) : 3 II. Equation : Qsdo (m3/s) = A x V x n Qsdo (m3/s) = 0.83 x Ale x 10 OR QL (m /s) = 0.83 x Ale x QS (m /s) = QL x 1.5 Qsdo : Leakage air (Different pressure shall be 10 Pa) when three doors are opened (two doors at fire floor, adjacent floor and final exit) Q : Require flow (select the value is larger between Qs and Qsdo) QL : Leakage air when all doors are closed (Different pressure shall be 50 Pa) Ale : Gap of closed doors, Estimate follow the table A.3, Standard BS EN 12101-6 : 2005, A le III. Calculation : Data: Number of floors (N) = 20 Floors Calculate the value of Qs : 3 QL= 4.70 (m /s ) Qs= Calculate the value of Qsdo : - Air flow criterion : Qs= - Pressure criterion : Qs= Select QSDO =
3 13.49 (m /s ) 3 13.5 (m /s ) 3 3.60 (m /s ) 3 7.04 (m /s )

1./ 2./ -

50

0.02

IV. Result : The air supply for pressurization via the duct system so the required air flow shall be increased 3 Q = QSDO x 1.15 = 15.5 (m /s ) V. Estimation of size of Air release area at fire floor: 3 The air leak into the fire floor : 3 (m /s ) 2 Air release area = 1.6 (m ) VII. Door opening forces : The permissible pressure to limit the door opening forces : 100N VIII. Calculation size of Air relief damper : When all doors are closed : 3 Q' = Q - QL = 10.82 (m /s ) Page 3 of 10

15

Air relief area = Standard: Singapore CP 13 : 1999 I. Input data : * Staircase area (m2) - A * Hight (m) - H * Air changes per hour - n * Number of floor - N II. Equation : Qtg = AxHxn Qtg : Require flow (m3/hr) III. Result : Qtg = Qtg =

2 1.68 (m ) STAIRCASE VENTILATION CALCULATION SHEET

20 70 4 20

5600 1,600

(m3/h ) (l/s)

Prepared Name : Thi Phong Signature :

Checking 01 Name : Thi Phong Signature :

Checking 02&03 Name : L Vn Xun Signature :

Page 4 of 10

INTERNATIONAL CONSTRUCTION & INVESTMENT CONSULTANCY CO.,LTD


Address : 2nd floor , 140 Nguyen Van Thu Street. Dakao Ward , District 1 , HCM City VietNam Tel: (84-8) 9111915 - 9111916 ; Fax : (84-8) 9111914 Email : m_e@icic.com.vn ; Website : www.icic.com.vn

Cng trnh/Project : Khu nh Estella II Hng mc/Service : Pressurization - Calculation sheet

F06-DME Ngy/Date : 31/12/2013 Reason for issue : Concept; Tender; Approval; Construction; Boq; Information; Action; Comment; Revision S lng pht hnh/Number of copies Issued - a CD/Disk : - Bn in/Print paper : - Bn photo/Photo paper : - Khc/Others :

Danh sch pht hnh/Distribution List : - Khch hng/Client : Keppel land - Kin trc/Architect : - T vn C-in/M&E Consultant : ICIC - Nh thu chnh/Main Contractor : - Khc/Others :

Standard refer : Singapore CP-13 Mechanical ventilation and air conditioning in building BS EN 12101-6 : 2005 Smoke and heat control system TCVN 2622: 1995 Fire prevention and protection for buildings and structures - Design requirements TCVN 6160: 1996 Fire protection - High rise building - Design requirements System Calculation : Different pressure between staircase and Lobby : 5010 Pa when all doors shall be closed. Different pressure between staircase and Lobby : 10 Pa when final exit door & two adjoining doors at any storeys shall be opened and all others shall be closed. - Air velocity through by the opened doors : 0.75 m/s. - In normal condition, ventilation for staircase : 4 Air changes per hour. STAIRCASE PRESSURIZATION CALCULATION SHEET Standard: BS EN 12101-6 : 2005 System classification: Using class E for this design. I. Input data: * Velocity through the opened door (V - m/s) : 0.75 * Door area (A - m2) 1.6 * Number of opened door (n) : 3 II. Equation : Qsdo (m3/s) = A x V x n Qsdo (m3/s) = 0.83 x Ale x 10 OR QL (m /s) = 0.83 x Ale x QS (m /s) = QL x 1.5 Qsdo : Leakage air (Different pressure shall be 10 Pa) when three doors are opened (two doors at fire floor, adjacent floor and final exit) Q : Require flow (select the value is larger between Qs and Qsdo) QL : Leakage air when all doors are closed (Different pressure shall be 50 Pa) Ale : Gap of closed doors, Estimate follow the table A.3, Standard BS EN 12101-6 : 2005, A le III. Calculation : Data: Number of floors (N) = 25 Floors Calculate the value of Qs : 3 QL= 5.87 (m /s ) Qs= Calculate the value of Qsdo : - Air flow criterion : Qs= - Pressure criterion : Qs= Select QSDO =
3 13.75 (m /s ) 3 13.8 (m /s ) 3 3.60 (m /s ) 3 8.80 (m /s )

1./ 2./ -

50

0.02

IV. Result : The air supply for pressurization via the duct system so the required air flow shall be increased 3 Q = QSDO x 1.15 = 15.8 (m /s ) V. Estimation of size of Air release area at fire floor: 3 The air leak into the fire floor : 3 (m /s ) 2 Air release area = 1.6 (m ) VII. Door opening forces : The permissible pressure to limit the door opening forces : 100N VIII. Calculation size of Air relief damper : When all doors are closed : 3 Q' = Q - QL = 9.95 (m /s ) Page 5 of 10

15

Air relief area = Standard: Singapore CP 13 : 1999 I. Input data : * Staircase area (m2) - A * Hight (m) - H * Air changes per hour - n * Number of floor - N II. Equation : Qtg = AxHxn Qtg : Require flow (m3/hr) III. Result : Qtg = Qtg =

2 1.55 (m ) STAIRCASE VENTILATION CALCULATION SHEET

20 87.5 4 25

7000 2,000

(m3/h ) (l/s)

Prepared Name : Thi Phong Signature :

Checking 01 Name : Thi Phong Signature :

Checking 02&03 Name : L Vn Xun Signature :

Page 6 of 10

INTERNATIONAL CONSTRUCTION & INVESTMENT CONSULTANCY CO.,LTD


Address : 2nd floor , 140 Nguyen Van Thu Street. Dakao Ward , District 1 , HCM City VietNam Tel: (84-8) 9111915 - 9111916 ; Fax : (84-8) 9111914 Email : m_e@icic.com.vn ; Website : www.icic.com.vn

Cng trnh/Project : Khu nh Estella II Hng mc/Service : Estimation sheet of cooling load

Ngy/Date : 31/12/2013 Reason for issue : Concept; Tender; Approval; Construction; Boq; Information; Action; Comment; Revision S lng pht hnh/Number of copies Issued - a CD/Disk : - Bn in/Print paper : - Bn photo/Photo paper : - Khc/Others :

Danh sch pht hnh/Distribution List : - Khch hng/Client : Keppel land - Kin trc/Architect : - T vn C-in/M&E Consultant : ICIC - Nh thu chnh/Main Contractor : - Khc/Others :

ESTIMATION OF COOLING LOAD


No. A 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 Room Name Room area Unit Cooling load m2 kW Cooling load kW Electrical capacity kW 3.6 2.0 0.8 0.8 3.6 2.0 0.8 0.8 3.6 2.0 0.8 0.8 3.6 2.0 0.8 0.8 4.1 2.5 0.8 0.8 4.9 2.5 0.8 0.8 0.8 4.9 2.5 0.8 0.8 0.8 4.9 2.5 0.8 0.8 0.8 4.9 2.5 0.8 0.8 0.8 6.8 4.0 1.2 0.8 0.8 6.8 4.0 1.2 0.8 0.8 11.2 4.0 Quantity Total kW 0.0 2.0 0.8 0.8 2.0 0.8 0.8 2.0 0.8 0.8 2.0 0.8 0.8 2.5 0.8 0.8 2.5 0.8 0.8 0.8 2.5 0.8 0.8 0.8 2.5 0.8 0.8 0.8 2.5 0.8 0.8 0.8 4.0 1.2 0.8 0.8 4.0 1.2 0.8 0.8

Apartment Type 2A Dinning & Living room 24 Master Bed room 12 Bed room 2 7.5 Type 2B Dinning & Living room 23 Master Bed room 8.5 Bed room 2 6.6 Type 2C Dinning & Living room 22 Master Bed room 10 Bed room 2 7 Type 2D Dinning & Living room 21 Master Bed room 11.5 Bed room 2 9 Type 2E Dinning & Living room 33 Master Bed room 14 Bed room 2 14 Type 3A Dinning & Living room 27 Master Bed room 9 Bed room 2 8.6 Bed room 3 7 Type 3B Dinning & Living room 29 Master Bed room 14 Bed room 2 9 Bed room 3 7 Type 3C Dinning & Living room 26 Master Bed room 9 Bed room 2 9 Bed room 3 7 Type 3D Dinning & Living room 30 Master Bed room 11 Bed room 2 12 Bed room 3 10 Type 3A-SINGLE PENTHOUSE Dinning & Living room 65 Master Bed room 25 Bed room 2 12 Bed room 3 10 Type 3B-SINGLE PENTHOUSE Dinning & Living room 65 Master Bed room 26 Bed room 2 10 Bed room 3 10 Type 4-LOWER DUPLEX PENTHOUSE Lower Dinning & Living room 53

0.25 0.15 0.15 0.25 0.15 0.15 0.25 0.15 0.15 0.25 0.15 0.15 0.25 0.15 0.15 0.25 0.15 0.15 0.15 0.25 0.15 0.15 0.15 0.25 0.15 0.15 0.15 0.25 0.15 0.15 0.15 0.2 0.15 0.15 0.15 0.2 0.15 0.15 0.15

6.00 1.80 1.13 5.75 1.28 0.99 5.50 1.50 1.05 5.25 1.73 1.35 8.25 2.10 2.10 6.75 1.35 1.29 1.05 7.25 2.10 1.35 1.05 6.50 1.35 1.35 1.05 7.50 1.65 1.80 1.50 13.00 3.75 1.80 1.50 13.00 3.90 1.50 1.50

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

0.25

13.25

Page 7 of 10

2 3 1 2 3 1 2 3 4

1 2 3 4 1 2 3 1 2 3 3 4 1 2 3 4 5 6

Master Bed room 17 Bed room 3 10 Upper Family room 25 Master Bed room 24 Bed room 2 14 Type 4-SINGLE PENTHOUSE Dinning & Living room 82 Master Bed room 23 Junior master Bed room 19 Bed room 2 13 Type 5-LOWER DUPLEX PENTHOUSE Lower Dinning & Living room 60 Junior master Bed room 15 Bed room 3 11 Bed room 4 12 Upper Family room 22 Master Bed room 17 Bed room 5 14 Type 5A-SINGLE PENTHOUSE Dinning & Living room 76 Master Bed room 12 Junior master Bed room 12 Bed room 4 12 Bed room 5 12 Type 5B-SINGLE PENTHOUSE Dinning & Living room 100 Master Bed room 15 Junior master Bed room 13 Bed room 3 10 Bed room 4 12 Bed room 5 12

0.15 0.15 0.25 0.15 0.15 0.25 0.15 0.15 0.15

2.55 1.50 6.25 3.60 2.10 20.50 3.45 2.85 1.95

0.8 0.8 4.0 0.8 0.8 9.4 7.0 0.8 0.8 0.8 10.0 4.0 0.8 0.8 0.8 2.0 0.8 0.8 10.2 7.0 0.8 0.8 0.8 0.8 13.0 9.0 0.8 0.8 0.8 0.8 0.8

1 1 1 1 1 1 1 1 1

0.8 0.8 4 0.8 0.8 7.0 0.8 0.8 0.8

0.25 0.15 0.15 0.15 0.25 0.15 0.15 0.25 0.15 0.15 0.15 0.15 0.25 0.15 0.15 0.15 0.15 0.15

15.00 2.25 1.65 1.80 5.50 2.55 2.10 19.00 1.80 1.80 1.80 1.80 25.00 2.25 1.95 1.50 1.80 1.80

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

4.0 0.8 0.8 0.8 2.0 0.8 0.8 7.0 0.8 0.8 0.8 0.8 9.0 0.8 0.8 0.8 0.8 0.8

Prepared Name : Thi Phong Signature :

Checking 01 Name : Thi Phong Signature :

Checking 02&03 Name : L Vn Xun Signature :

Page 8 of 10

INTERNATIONAL CONSTRUCTION & INVESTMENT CONSULTANCY CO.,LTD

F06-DME

Concept; Tender; Approval; Construction; Boq; Information; Action; Comment; Revision

ESTIMATION OF COOLING LOAD


Remarks

Page 9 of 10

Page 10 of 10