You are on page 1of 4

ArcEliminator

R A P I D E L I M I N A T I O N O F I N T E R N A L A R C I N G

Arc Eliminator

The Arc Eliminator is an innovative design of an extremely fast acting switch, grounding all phases within 5 ms after occurrence of an open arc in the switchgear. The very fast operation means not only that the thermal damages by the extreme heat of the arc is totally omitted, but also that the pressure increase due to heating of the air (or other insulation gas) is drastically reduced. A conventional arc light detector triggers the operation. After an operation recharging is done electrically. The Arc Eliminator fulfils the demands for a 40 kA fault at 24 kV. It has been developed to be a standard component for ABB switchgear, and only having the same dimensions as a standard 24 kV insulator. It is also possible to use it for increasing the personnel safety and reliability of other switchgear, including non-arc proof ones in service. An open arc in a switchgear is a severe event, normally destroying the eguipment totally. The Arc Eliminator brings an important value to the customer by an extremely short time for the switchgear to be taken back into service again after an arc fault. This gives important savings in repair cost and down time. Due to the limitation in pressure increase, no pressure relief system is necessary, which simplifies the design and reduces the cost for both switchgear and buildings.

The Arc Eliminator mounted as busbar-support insulator in AX1 switchgear.

0 ms An arc occurs.

1 ms The arc is detected by the Arc Eliminator.

2 ms A trig signal is sent to the Arc Eliminator which starts to operate.

5 ms All phases are closed to earth potential and the arc is eliminated. The fault is cleared by the up-stream breaker.

Operation sequence.

Assembly drawing

Trigger unit

Earth connection bar (not included)

Cable stem to control unit Eliminator control unit

Cable stem to eliminator Arc Eliminator

Arc light detector

Dimension prints
Arc Eliminator Eliminator control unit Trigger unit

M24

146

Cable stem to control unit


210

Cable length 2 m

Cable stem to eliminator

90

D = 150

265
290

156 168

M16

126 140

265

560

Technical data
Rated voltage Un Basic insulation level BIL Rated short-time current Supply voltage Power consumption
Complies with EMC standard EN 50081-2, EN 50082-2

up to 24 kV 130 kV 40 kA, 1 sec 80 - 265 V DC 10 VA

Ordering
Article Arc Eliminator complete including below 4 items Arc Eliminator set (3-phase) Eliminator control unit Trigger unit with power cables (2 m) and control wires (2 m) Screw set for Arc Eliminator Arc light detectors with fibre optic cables, 2 m 4m 6m 8m 10 m 15 m 20 m 30 m 1SFA 663 003 1SFA 663 003 1SFA 663 003 1SFA 663 003 1SFA 663 003 1SFA 663 003 1SFA 663 003 1SFA 663 003 R1020 R1040 R1060 R1080 R1100 R1150 R1200 R1300 Order no.

1VEB 542515-AFB

Note: An earth connection bar of minimum 200 mm2 must be used, see assembly drawing.

ABB Power Technologies Medium Voltage Products 77180 L u d v i k a Sweden Tel: +46-240-78 20 00 Fax: +46-240-78 40 00 E-mail: www.abb.com/mediumvoltage

1VET 954910-910

ReklamCenter 99365 Printed in Sweden, ARKPRESSEN 99.12