DESCRIPTION
2
CONFIGURATION
3
FUNCTIONS
11
4
APPLICATION EXAMPLES
21
5
CONSTRUCTION
29
6
TECHNICAL DATA
33
7
CONNECTIONS
47
8
INFORMATION
57
IndustrialIT
REF542plus has been tested and certified as IndustrialIT Enabled, Level 1 - connectivity. All product information is supplied in interactive electronic format, compatible with ABB Aspect ObjectTM technology. The IndustrialIT commitment from ABB ensures that every enterprise building block is equipped with the integral tools necessary to install, operate, and maintain efficiently throughout the product lifecycle. REF542plus belongs to the ProtectIT suite. Detailed information on IndustrialIT is available at <http://www.abb.com/industrialit>.
1
DESCRIPTION
4 6 7
DESCRIPTION
Introduction
REF542plus integrates in a single unit all the secondary functions for a medium voltage switchgear: Protection; Control; Measurement; Monitoring and self-diagnosis; Communication. A medium voltage switchgear equipped with REF542plus becomes a complete, efficient and effective system for power distribution and management. The unit can be used indifferently in solidly earthed, low-resistance, compensated or unearthed networks; with radial, multifeeders or loop topology. The wealth of available protection functions makes the unit suitable for any kind of applications. Time-overcurrent either with definite or inverse time, directional time-overcurrent protections are implemented. Also the distance protection for overhead lines can be instantiated in the REF542plus. Motor protection functions include starting supervision, number of starts counting, locked rotor, thermal supervision, under power, reverse power and unbalanced load. ATEX certified versions for explosive environment, according to the directive 94/9/EC, are available. Large power transformers can be protected, among others, with the differential and the restricted earth fault protections. Power quality features such as power factor controller with resonance protection are available. For demanding applications, a REF542plus based system including a SUE 3000 unit, grants fast transfer switch between two incoming feeders in less than 30 ms.
Under voltage and over voltage protections, synchrocheck and frequency protection complete the set of protection functions for bus tie panels, incoming feeders and whenever needed. Time synchronization with an external master clock makes the fault-recording feature and events stamping with accuracy better than 1 ms. Four different communications protocols and an embedded WEB server open the REF542plus to any control system architecture. All these features are complemented with exceptional automation functions capabilities. Automatic transfer switch, motor restarts and reacceleration, load shedding, any kind of user defined automation sequence can be easily implemented inside the unit. The presence of a CAN Open standard interface allows connectivity to the huge market of CAN standard products such as terminal blocks and intelligent IO modules. The automation possibilities become almost unlimited. The following pictures show REF542plus installation examples in several switchgear.
The REF542plus is composed of two parts, a Base Unit and a Local Detached Human Machine Interface (LD HMI). The two parts are connected with a serial cable. The Base Unit contains the power supply, the main module, the analog and binary input and output (I/ O) modules. Optional modules can be inserted for supplementary functions. The HMI is an easy-to-use unit for the switchgear local control. The HMI is equipped with its own power supply. It can be installed on the low voltage compartment door or in a dedicated compartment close to the Base Unit. The HMI is used to locally operate the primary objects in the switchgear, to set the protection parameters, to visualize events and measurements. The separation between HMI and Base Unit grants several advantages and an overall increased flexibility: Blind Base Units (without HMI) are possible; One single HMI for several Base Units; Easier HMI integration in the most convenient place; Simplified Base Unit integration in the low voltage cubicle.
DESCRIPTION
The following figure shows an installation of the Base Unit and of the HMI in the low voltage compartment of the switchgear.
Base Unit mounting in the low voltage compartment and the HMI on the door.
The binary inputs and outputs modules interface the primary process to send commands and to acquire status information. The analog input module acquires the current and voltage signals, both from instrument transformers or noninductive sensors. The optional analog 0/4 ... 20 mA output module and analog 4 ... 20 mA input module allow exchanging information with the 4... 20 mA or 0... 20 mA current loop.
Communication Module
Main Module
13 12 11 5
10 6 9
7 8 Object control: Open - Close - Select 9 Electronic keys sensor 10 Text 11 SLD view 12 Circuit-breaker fast opening 13 Unit ready
The HMI includes: Unit Ready. This green led is turned on when the unit is in the operational state. This led is switched off when the power supply is not present or when the unit is not operational.
1 2 3 4 5 6 7
Network communication Alarm Interlocking error 8x4 pages user programmable Leds Measurements bars PC interface Menu navigation
REF542plus HMI. 7
1
DESCRIPTION
Network Communication. This led is meaningful only when the REF542plus is equipped with a communication module and configured to use it. When a communication module is detected inside the unit, the led turns on to green. If a communication module is not detected or fails, the led turns from green to red. When the unit is not configured for the communication, this led is switched off. Alarm. This led turns to red when user defined alarms become true. Several arbitrary alarm conditions can be defined and configured with the operating tool. Alarm conditions could be the trip of a protection function, loss of SF6 in the circuit breaker, etc. When this led is on, it is not possible to close the circuit breaker or to download a new configuration. The alarm condition has to be removed and the alarm must be acknowledged first. Interlocking Error. This led is usually green. The led turns temporarily to red when the user attempts an operation that would violate the programmed interlocking conditions; for example switching a disconnector with the circuit breaker in closed position. Electronic Keys Sensor. This is the sensor for recognizing the electronic keys. Two different electronic keys are provided. One key allows changing the parameters of the protection functions. The other one is used to change the control modes. The sensor automatically detects which key has been inserted. The two keys are labeled Protect and Control, to distinguish them. When required, a general key to access both modes can be provided. It is also possible to program an 8 characters custom code in the keys to increase the security levels or for any other specific reason. This can be done very easily with a program available on request. Object Control. These push buttons allow operating the primary objects. Menu Navigation. These push buttons allow navigating trough the REF542plus menu. 8 x 4 pages user programmable leds. 8 freely programmable, three-color leds are available for indications. There are 4 pages of these leds. The assignment of the led to a specific condition is done with the Operating Tool.
PC interface. This is the optical serial interface port to connect the REF542plus with a personal computer. By using the appropriate cable and the Operating Tool, the following actions are possible: Download a configuration into the unit, Upload the current configuration from the unit, Upload the fault recorder, Upload other information (measurements, binary inputs status, binary output status). Measurements Bars. 3 freely programmable bars have been provided for a quick inspection of the switchgear load situation. The three bars are marked M1, M2, and M3. Each bar is composed of twelve leds: ten green and two red. The ten green leds are normally dedicated to display between 0% and 100% of the nominal value of the configured measurement, each led corresponding then to 10% of the nominal value. The two red leds indicates an overload condition of 20%. The measurement displayed by the bar is set with the Operating Tool. M1..M3 reference text can be configured and displayed on the display graphical side. Text. This is the textual part of the LCD. It shows the menu, the measurement values, the events and any information accessible through the menu structure. SLD view. This is the graphical part of the LCD. This part shows the single line diagram of the switchgear. The status of the primary objects is dynamically updated after every operation: if for example the circuit breaker has been opened, its representation will reflect it. CB Fast Opening. When pressed simultaneously with the normal open button, this button allows opening the circuit breaker, independently from the selected control mode. This feature must be enabled in the unit with the Operating Tool. Moreover, it is also possible to have several, completely user defined command buttons on the HMI. These virtual push buttons are available from the dedicated HMI menu. During REF542plus configuration, the user defines what command buttons are required. Typical examples might be: start of a transfer switch or of any other automation sequence, fault recorder activation, start of a load shedding sequence, etc. Thanks to the user defined command buttons, REF542plus automation capabilities can cope with any requirements.
2
CONFIGURATION
Configuration
10
2
CONFIGURATION
The REF542plus unit is configured for the specific application using the Operating Tool running on a personal computer. With the graphical editor, the needed functions blocks are combined together. The available protection functions are represented with specific function blocks, which can be combined with logic functions to define the required protection and automation scheme. This flexibility is very advantageous for defining control functions and automation sequences, which can, for example, include the interlocking of the switching devices, blocking the release of specific protection functions, as well as starting switching sequences. The REF542plus unit provides a wide range of logical functions so that each specific requirement can be met.
The functions includes any kind of logical gates such as AND, OR, timers, counters, pulse generators, flip-flops etc. All functions in the switchgear are specified in collaboration with ABB. The REF542plus configuration is a file, which is then downloaded into the unit via the optical serial port on the HMI. The Operating Tool allows also these additional functions, once connected to the HMI via the serial cable: Protection functions setting Measurement values read-out On line binary inputs and outputs status readout Fault recorder data acquisition. The Operating Tool allows on line, real time monitoring of the internal control signals and logic states, a powerful tool for applications debugging.
10
3
FUNCTIONS
Measurements Monitoring and self-diagnosis Protection Control Events and fault recording Time synchronization Interface to the primary process CAN Open Analog Output 4/0 20mA Analog Input 4 20mA Interfacing a Station Automation System Embedded Web Server
12 12 13 13 14 16 16 17 18 18 18 19
11
FUNCTIONS
REF542plus Multifunction Protection and Switchbay Control Unit integrates all the secondary functions into a single unit. This multifunction unit also features a self-monitoring function. This versatility makes it possible to use the REF542plus on any switchgear independently from the specific required application.
The available measurements depend upon the analog input configuration. With the maximum configuration, the following are obtained. Directly acquired values Phase currents; Phase-to-ground or phase-to-phase voltages Earth current (it can also be calculated); Residual voltage (it can also be calculated); Frequency. From the above, the following values can be calculated. Computed values Phase voltages(2), Average/maximum current value, three-phase (determined over several minutes); Apparent, active and reactive power; Power factor; Active and reactive energy; THD (Total Harmonic Distortion).
(1)
Measurements
REF542plus can have a maximum of 8 analogue input channels for measuring current and voltage signals. These channels are organized into three groups: three channels in group 1 and in group 2, two channels in group 3. Group 1 and group 2 have to be homogeneous, which means they can measure 3 currents or 3 voltages. For example, measurement of 1 current and 2 voltages is not allowed. Group 3 can get any type of signals: 2 currents, 2 voltages, 1 current and 1 voltage. REF542plus analogue inputs are very flexible, as this flexibility is needed to support all the protection functions. Group 1 and group 2 can be used for homogeneous current or voltage measurements either from instrument transformers or noninductive sensors. Group 3 can be used in a heterogeneous way, either with instrument transformers or with sensors. One of the most common configurations uses three current and three voltage inputs and one earth fault current input. All these values are shown on the HMI display. The following measurements, registered over an extended period of time, are permanently saved in non-volatile memory: Operating hours; Active and real energy; Max and average current for each phase; Max voltage (available only from the communication module); Average voltage (available only from the communication module); Sum of interrupted currents; Number of switching cycles; Fault recorder data; HMI Key status. After a power supply loss, this data is still available.
(1) REF542 plus can use both phase-to-phase and phase-to-ground voltage transformers. (2) When phase-to-ground voltage transformers are used. 12
Protection
The REF542plus offers a wide range of protection functions to cover all medium voltage applications. These protections can be combined together to implement the required scheme. When directional protections are used, some binary inputs and outputs can be dedicated to the logic selectivity. The following protections and related functions are available. Current Protection Inrush blocking (68) Overcurrent Instantaneous (50) Overcurrent definite time, 2 thresholds (51) Overcurrent directional, 2 thresholds (67) Overcurrent IDMT (51 IDMT) Earth fault, 2 thresholds (51N) Earth fault IDMT (51 IDMT) Earth fault directional, 2 thresholds (67N) Earth fault directional sensitive (67S) Earth fault directional sector (67NS), 10 thresholds.
Other protections and related functions Frequency protection (81), 6 thresholds per net Synchrocheck (25) Fault recorder Autoreclosure (79) Lock out (86) Reverse power (32). At most 24 protection functions can be instantiated inside the REF542plus unit. The maximum number is anyway dependent upon the available processing power.
Control
The control and automation capabilities inside the REF542plus are extremely powerful. Traditional wired logic with electromechanical relays is replaced by software control schemes inside the unit. Simple interlocking against switching errors as well complex load shedding schemes can be easily implemented with the control possibilities offered by the REF542plus. It is also possible to implement interlocking between switchbays connected to the same bus bar system. This requires the availability of status information of the switching devices to and from other switchgear. The status information must be provided by: Conventional, hard-wired ring bus system; Using the ABB station automation system allowing horizontal communication among the REF542plus units connected on the interbay bus; Using the CAN Open digital fieldbus. The REF542plus foresees different control modes, selectable with the control key. In local mode, the HMI control buttons are used to operate on the primary objects. Remote operations are inhibited. In remote control mode, only switching actions from a remote control device like a station automation system are permitted. Local control from the HMI is inhibited. All the possibilities to operate on the primary objects can be inhibited setting the unit to the no control mode.
Voltage protection Over voltage Instantaneous (59) Over voltage definite time, 2 thresholds (59) Under voltage Instantaneous (27) Under voltage definite time, 2 thresholds (27) Residual over voltage, 2 thresholds (59N) Line Protection Distance (21) Differential Protection Differential protection for motors and transformer (87) Restricted earth fault for transformer (87N) Thermal protection For cables, motors and transformers (49) Motor specific protection Number of starts counting (66) Locked rotor (51LR) Motor start (51MS) Low load (37) Unbalanced load (46) Power Quality Mitigation Power factor controller (55) Switching resonance protection THD Protection
13
FUNCTIONS
Fault recorder The REF542plus unit is equipped with a powerful and flexible fault recorder function. This function can be used to record at most eight analog input channels and thirty-two binary signals. The analog input signals are recorded with a sampling rate of 1.2 kHz for a time interval of at least 1 second and for a maximum of 5 seconds. The recording time is a combination of pre- and post fault time. The total recording capability is of 5 seconds: there can then be configured 5 records of 1 seconds or a single record of 5 seconds. The recording can be started by a protection event, by a binary signal change or by any user defined condition.
Fault records can be transferred locally to a personal computer from the HMI optical port with the Operating Tool on from the communication interface. When extracted with the Operating Tool or from the embedded WEB Interface, the fault records are automatically converted into the standard COMTRADE format. When retrieved from the communication interface, they can be converted with a utility program. Fault records are stored in non-volatile memory, so they remain available also after a power loss.
15
FUNCTIONS
Time synchronization
REF542plus is equipped with an internal real time clock, which is used to time stamp events. The internal clock is buffered by a special super capacitor. In case of power loss, the stored electrical energy in the capacitor ensures the internal clock operation for at least twenty-four hours. The date and time of the clock can be set via the HMI Control Unit. REF542plus internal clock can be kept synchronized to an external clock in different ways. When connected to a station automation system, REF542plus can be kept synchronized via interbay bus using the facilities of the used protocol, if available. Accuracy depends upon the protocol features and may vary from 3 ms (LON LAG 1.4) to tens of milliseconds (SPABUS). When better accuracy is required, REF542plus can be synchronized using the dedicated optical input port and a master clock, typically a GPS. The accepted time formats are IRIG format B000, B002 and B003. The picture shows the time distribution architecture for the synchronization. When synchronized through IRIG B, REF542plus unit guarantees an accuracy better of 1 ms and a resolution of +/- 500us. Very precise fault analysis is then possible.
GPS satellite Satellite antenna Substation Master clock Substation Master clock and distributor
Switchboard starcoupler
Synchronization of the internal clock by a GPS master clock and IRIG B port.
Wide rated range; No accuracy versus burden calculation; Standardized components; No saturation, no ferroresonance; Combined current and voltage sensor together in the same physical unit. The current sensor is based on the principle of the Rogowski coil, which consists of a single air-cored coil. Due to the lack of an iron core, the saturation effects of conventional current transformers do not exist anymore. Current sensors are thus well suited to be used with the distance and the differential protection functions. The current sensor output is a voltage signal proportional to the derivative of the primary current being measured. The numerical integration of the signal is performed by the DSP inside the REF542plus unit. Four current sensors only with nominal currents 80160A, 160-480A, 480-1250A, 1600-3200A cover all the applications.
The voltage sensor is based on the resistive divider principle, the measuring signal is directly proportional to the measured value and it cannot saturate. The signal is thus linear throughout the whole measuring range. The output signal is a voltage that is directly proportional to the primary voltage. The figure shows an example of a combined sensors. The current and voltage sensors are encapsulated into a single resin unit, and that is the reason why they are often referred as combined or combi sensors. Coupling electrode is incorporated in the sensor, for voltage detecting systems (VDS) or for voltage presence indicating systems (VPIS). Binary inputs and outputs The REF542plus unit acquires the primary objects status with auxiliary contacts, which are read by binary inputs, and sends commands using binary outputs. Several signals coming from other components are also monitored. Among the others, the following operations are implemented using binary inputs and outputs: Primary objects control and interlocking in the switchgear; Primary objects status acquisition (e.g. circuit breaker in opened/closed position); Circuit breaker spring supervision (when applicable). Binary inputs are isolated by opto-couplers. Binary outputs can be implemented either with mechanical relays or with static (semiconductor) devices. In a switchgear with directly driven motors, static power outputs are usually required.
In addition, the digital bus moves the intelligence closer to the process, allowing the construction of switchgear systems with increased configuration and maintenance flexibility. The CAN Open interface allows connecting any off-the-shelf product compliant with the CAN Open standard, thus making the automation capabilities of the REF542plus almost unlimited. The picture below describes an architecture where two REF542plus units and some IO modules are connected with the CAN Open.
FIELDBUS
I/O modules
REF542plus
CAN Open
The REF542plus is equipped on the main module with a CAN Open standard interface. The CAN Open interface has two main purposes: Replacing the switchgear internal hard-wired connections by means of a high-speed digital bus; CAN Open standard devices connectivity (intelligent IO modules, sensors, ...). Replacing the switchgear internal hard-wired connections by means of a high-speed digital bus allows building new highly standardized switchgear with a more efficient life cycle. Fast interlocking data among several REF542plus units can be exchanged on the CAN Open bus.
REF542plus configuration tool Intra-panel wiring
Circuitbreaker
Panel A
FUNCTIONS
(*) Only passive sensors can be connected to the analog input 4 ... 20 mA module. The module itself supplies the sensor.
GPS Clock
REF542plus
REF542plus
REF542plus
RE542 plus units connected to an ABB station automation system. Time synchronization is done over the interbay bus.
18
Motor
Control Network Communication Alarm Interlocking error Last update English Local and remote / Operational 2002/12/13 14:42:30
WEBREF
0 seconds Deutsch
Monitor Control
Control Protection
Service Configuration
Help
0% M3 0%
50%
100%
50%
100%
WEBREF
WEB Switcboard
Motor Feeder 1
10.41.72.80
10.41.72.82 Next
< >
Switchgear equipped with REF542 plus : single line diagram as seen from the Internet browser. 19
20
4
APPLICATION EXAMPLES
Automatic transfer switchover High speed transfer system (HSTS) Motor management Power transformer management Distribution networks management Overhead and cable lines Power quality
22 23 24 25 25 26 27
21
APPLICATION EXAMPLES
This section illustrates a few typical REF542plus applications; where its flexibility is of utmost advantage both in terms of safety of operations and cost effectiveness. In all the following applications, the REF542plus is the only unit installed in the switchgear. No additional relays or devices are needed. It is worth noting that in all the different applications, the REF542plus hardware is always the same, customized to the specific needs by means of software configuration only. The software customization guarantees several important benefits to the user: Maximum flexibility also after switchgear commissioning, changes and extensions are done via software. No new wirings are needed. One kind only of spare parts instead of several different relay types for incoming feeders, motor feeders etc. Spare parts costs are kept at the real minimum. One human machine interface only to learn.
Automatic switching is required in installations where the power supply must always be guaranteed to meet process continuity requirements. REF542plus carries out the automatic transfer switchover in about 500 milliseconds (circuitbreaker operating time included); the exact time value depends upon the software complexity of the required commutation logic. Switchgear equipped with suitably programmed REF542plus units constitute a complete, efficient system able of controlling the switching between one power supply system and another alternative one, or reconfiguring the network by switching from dual radial distribution to a single system in a fully automatic way. User personnel can also carry out the same switching manually from a station automation system or standing in front of the switchgear. Manual switching involves performing the parallel passing: the power supply lines are closed simultaneously using the synchro-check function when the two voltage vectors are synchronous, and then subsequently returning to the disconnected state when the switching has been completed. These applications do not require any instrumentation in addition to the REF542plus.
22
The picture shows the system single line diagram for a two breakers configuration.
VS/FDI
VS/FDI
Fast VM1
SUE3000
Fast VM1
Busbar
23
APPLICATION EXAMPLES
Feeder 1 is normally closed and feeds the bus bar. Feeder 2 is the stand by alternative feeder. The two REF542plus units on Feeder 1 and Feeder 2 take care of the usual control and protection functions. In addition, they have active the voltage supervision VS/FDI (Voltage Sensing Fast Detection Indicator) function block to immediately detect and signal any power loss/drop. The VS/FDI allows alerting the SUE 3000 controller in less than 3ms. When the REF542plus feeder terminal 1 detects a power loss, it communicates it to the SUE 3000 that gives simultaneously the opening command to Feeder 1 and the closing command to Feeder 2. The SUE 3000 continuously monitors the two feeder voltages to verify that the proper conditions for the high speed transfer are met. The SUE 3000 compares, on a permanent basis, the phase angle and the frequency difference between the voltage of the bus bar and of the stand-by feeder. Also the voltage amplitude of the stand by feeder is verified, to be above a certain threshold. This continuous monitoring ensures that the minimum short transfer time is achieved, the transient effects of which represent no danger to the connected loads.
Motor management
The REF542plus unit is suitable for controlling and protecting medium voltage motors of any size. The motor can be actuated using both circuit breakers and contactors with mechanical or electric hold operating mechanisms. When configured accordingly, the REF542plus is able to manage motor shutdown, acceleration and restarting. Following a failure or transient voltage drop in the power supply, the REF542plus is able to supervise the motor disconnection and if required to send the command for re-insertion, in complete autonomy. Here below there is a typical example of motor management sequence. The installed motor control configuration intervenes when the power supply voltage falls below the set value that causes opening. The REF542plus unit starts then timing the power supply failure duration. When the power supply is restored, the REF542plus unit decides what action to take: if the power supply failure time is less than the set acceleration time, it will close the actuator immediately, thus accelerating the motor; if the power loss time is greater than the acceleration time but less than the restarting time, it will start timing a different delay motors by motors to switch them back in again in a predefined order; if both time periods have been exceeded, the REF542plus unit will reset the procedure, awaiting an external command.
The sequence for the circuit-breakers being switched, the voltage thresholds, time delays and restarting enabling functions are configured in the REF542plus unit.
Ring network
Relay
Relay
Radial network
25
APPLICATION EXAMPLES
The fault location is indirectly identified using the impedance per unit of length of the line. In this case, the line impedance Z (with a homogeneous line) is proportional to the fault distance. The distance protection comprises a starting logic, an impedance measuring logic and a direction identification logic. Starting logic: it detects the fault condition. Impedance measuring logic: it determines the distance of the zone in which the fault has occurred. Direction identification logic: it verifies whether the fault is located in the same direction as the line being protected. The REF542plus distance protection offers 5 different zones, 2 of them for predefined use (overreach and directional back up). There is also a non-directional tripping zone, independent from the impedance, for back up. The extremely flexible auto reclosing function complements the REF542plus distance protection. For example, in case of mixed cable-overhead lines sections, it is possible to block the auto reclosing function for cable faults using the autoreclosing stop zone. The pictures show an example of zones configuration and I-Z plane diagram.
26
Power quality
The REF542plus is equipped with functions both to monitor and to increase the power quality. Industrial loads are becoming more and more sensitive to power quality parameters like harmonic contents; while utilities billing policy penalize poor power factor. Integrated power factor controller with resonance protection The REF542plus unit offers a power factor controller able to switch up to four capacitor banks. This function allows integrating the reactive power compensation in the medium voltage switchgear, without the need of additional components. Rated power up to tens of Mvar can be switched on and off to follow the set target power factor for any load conditions. A problem that might occur when power factor correction capacitors are switched on is harmonic resonance. The power system becomes tuned to a specific frequency due the combination of the loads inductance and the added capacitance. The power system is then resonating at this frequency. Harmonic resonance results in severe voltage and current distortions, with increased losses and equipment overheating.
The resonance protection (ABB patented) in the REF542plus unit prevents these dangerous resonance conditions. Sensing the increase in the harmonic content, the resonance protection switches off the inserted bank, de-tuning the power system. Depending on the setting, the power factor controller can then undertake other remedial actions to follow the set target power factor. The following figure shows the voltage total harmonic distortion (THD) increase when switching on a capacitor bank. The THD remains above the set trip threshold level after the typical hundred of milliseconds of the transient. The resonance protection then clears the dangerous condition switching off the capacitor bank.
THD protection
Harmonics have significant unwanted impact on power distribution systems and the loads they feed. Typical negative effects are overheating, current demand increases, over voltages. Negative sequence harmonics reduce forward torque in motors, while increasing the current. REF542plus THD (Total Harmonic Distortion) protection prevents these negative effects. The protection issues the trip when the harmonic content is higher than the set threshold. The content is analyzed up to 1500Hz, which results in the 25th harmonic for 60Hz system and the 30th for 50Hz one.
28
5
CONSTRUCTION
30 30 31
29
CONSTRUCTION
Backplane differs from 4/0 ... 20 mA analog output module and communication module. The backplane type has to be specified. The wide housing can additionaly house: other 2 binary input and output modules, the communication module, alternatevly the 4/0 ... 20 mA analog output module or the 4 ... 20 mA analog input module. Note: the 4 ... 20 mA analog input module can be used with the wide housing only. Standard housing summary One power supply; One mainboard module; One analog input module; At most two binary input and output modules; Optionally the communication module or the 4/0 ... 20 mA analog output one.
External dimensions
Wide housing summary One power supply; One mainboard module; One analog input module; At most three binary input and output modules; Optionally the communication module; Optionally the 4 ... 20 mA analog input module or the 4/0 ... 20 mA analog output module.
HMI
The HMI dimensions are shown in the following picture.
HMI dimensions.
32
6
TECHNICAL DATA
Analog inputs and measurements Protection functions technical data Configuration restriction Binary inputs and outputs Interfaces Power supply Environmental conditions Protection degree Type test
34 37 42 43 44 45 45 45 45
33
TECHNICAL DATA
Analog inputs
Measurements The REF542plus unit uses the same analog inputs both for measurements and protections. The measurement classes are according to the following table. Quantity Phase current, earth current Line voltage, phase voltage Active, reactive, apparent power Active, reactive energy Cos Frequency Accuracy 0.5% 0.5% 1% 2% 1% 0.02% Range 0.1-4In 0.2-1.5Vn 01 -
To achieve highest accuracy the instrument transformers or the sensors must have 0.5% accuracy or better in the same range.
Protection Class 3.
Current and voltage transformer input values Rated current In Rated voltage Un Rated frequency fn 0.2 A or 1 A or 5 A 100 V ... 125 V 50 Hz / 60 Hz
Thermal load capacity Current path Voltage path 250 In (peak value), dynamic 100 In for 1s, 5 In continuous 2 Un /3 continuous
Consumption Current path Voltage path < 0.1 VA with In < 0.25 VA with Un
Current and voltage sensor input values Voltage at rated current In Voltage at rated voltage Un Rated frequency fn 150 mV (rms)/50 Hz/60Hz 2V (rms) 50 Hz/60 Hz
34
Code 1VCF 750170R0804 1VCF 750170R0806 1VCF 750170R0807 1VCF 750170R0809 1VCF 750170R0812 1VCF 750170R0817 1VCF 750170R0819 1VCF 750170R0821 1VCF 750170R0822 1VCF 750170R0824 1VCF 750170R0825 1VCF 750170R0826 1VCF 750170R0827 1VCF 750170R0828 1VCF 750138R0803 1VCF 750170R0843 1VCF 750170R0846 1VCF 750170R0847 1VCF 750170R0851 1VCF 750170R0852 1VCF 750170R0853 1VCF 750170R0854 1VCF 750170R0855
Description 3 CT+3 VT+1 CT 0.2A+1 VT 3 VT+3 VT+1 CT 0.2A+1 CT 0.2A 3 CT+3 CT 3 CT+3 CT+1 CT 0.2A+1 VT 3 VT+3 VT+1 VT 3 CT+3 VT+1 CT 3 CT+3 VT+1 CT+1 VT 3 CT+ +1 CT 3 CT+ +1 CT 0.2A 3 CT+3VT+1CT+1CT 3 CT+3 VT+1 CT 0.2A+1 CT 0.2A 3 CT+3 VT+1 VT +1 VT 3 CT+3 CT+1 CT +1 CT 3 CT+3 CT+1 CT +1 VT 3 S+3 S+1 S+1 S 3 S+3 S+1 CT 0.2A+1 VT 3 S+3 VT+1 CT 0.2A+1 VT 3 S+3 S+1 CT 3 S+3 S+1 CT+1 VT 3 S+3 S+1CT 0.2A 3 S+3 S+1 VT+1 VT 3 S+3 CT+1 CT 0.2A+1 VT 3 S+3 CT+1 CT 0.2A+1 CT 0.2A
35
TECHNICAL DATA
Reaction time
In this context the protection reaction time is defined as the time elapsed between the fault detection and the closing of the contact that gives supply to the circuit breaker tripping coil (or the equivalent tripping mechanism for magnetic drive or contactors). This time is the sum of different intervals: 1 Fault detection time; 2 User defined pre set delay (for definite time protection functions); 3 Trip information processing; 4 Relay output contact actuation. The REF542plus is a protection and control unit and the programmed automation logic is executed cyclically in a PLCstyle mode. The cycle time, in the range of ten millisecond, is depending upon the logic complexity. The REF542plus has an internal fixed compensation both for the relay output contact actuation time and for the logic execution time. Nevertheless, the actual trip information processing time depends upon the complexity of the actual logic programmed inside the unit.
As a result, the protection reaction time, in the worst case, can be the user-defined pre set delay plus twice the cycle time. Direct channel In really demanding applications, the protection has to react as fast as possible and the system behavior has to be absolutely deterministic. The REF542plus offers then to the protection system designer the direct channel option. Using this option, the programmed logic execution flow inside the unit is skipped and the trip command is instantly delivered to the switching object representing the circuit breaker. All the interlocking conditions are nevertheless respected and assured. Should the circuit breaker be blocked for any reason, e.g. insufficient SF6 pressure, the trip command is not actuated. The direct channel option grants then an absolutely deterministic behavior to the REF542plus protection functions.
36
Current protection functions 68 Inrush stabilization (only in connection with 50 and 51) N = 2.0 8.0 M = 3.0 4.0 Time = 200 100.000 ms 68 Inrush Harmonic Min current threshold = 0.05 ... 40.00 In Harmonic ratio threshold = 5.00 ... 50.00% Fault current threshold = 0.05 ... 40.00 In 50 Overcurrent instantaneous I>>> = 0.10 ... 40.00 In t = 15 ... 30.000 ms 51 Overcurrent high I>> = 0.05 ... 40.00 In t = 20 ... 300.000 ms 51 Overcurrent low I > = 0.05 ... 40.00 In t = 20 ... 300.000 ms 51 IDMT Overcurrent IDMT (inverse definite minimum time) Normal-, Very-, Extremely- or Longtime- inverse time characteristic Ie = 0.05 ... 40.00 In K = 0.05 ... 1.5 67 Overcurrent directional high I>> = 0.05 ... 40.00 In t = 40 ... 30 000 ms Direction = backward, forward 67 Overcurrent directional low IE> = 0.05 ... 40.00 In t = 40 ... 30 000 ms Direction = backward, forward
Earth Fault (1) 51N Earth fault high IE>> = 0.05 ... 40.00 In t = 40 ... 30 000 ms 51N Earth fault low IE> = 0.05 ... 40.00 In t = 40 ... 30 000 ms 51N IDMT Earth fault IDMT (inverse definite minimum time) Curve type= normal, very, extremely or long time inverse time characteristic Ie = 0.05 ... 40.00 In K = 0.05 ... 1.5
(1) The use of the current balance transformer (accuracy class 1) is recommended to apply the lowest setting (0,05 In). 37
TECHNICAL DATA
67N
67N
67S
67N Sector
Earth fault directional high IE>> = 0.05 ... 40.00 t = 40 ... 30.000 ms Vo = 0,02 ... 0,7 Un direction=forward, backward net type=isolated (sin ), earthed (cos) Earth fault directional low IE> = 0.05 ... 40.00 In t = 40 ... 300.000 ms Vo = 0,02 ... 0,7 Vn direction=forward, backward net type=isolated (sin ), earthed (cos) Earth fault directional sensitive I0 = 0.05 ... 2.00 In t = 100 ... 10.00 ms Angle = 0 ... 20 Angle = -180 ... 180 Vo = 0.05 ...0.70 Un Earth Fault directional Sector (10 thresholds available) Direction = Enable (directional behavior)Disable (non directional behavior) Start Criteria = neutral current magnitude/ neutral current basic angle Io = 0,0028,0 In Vo = 0,0040,7 Un T = 3060,000 ms Sector Basic Angle = -180 180 Sector Width = 0.0 360.0 Io drop off delay = 01.000 ms Vo drop off delay = 01.000 ms
Voltage protection functions 59 Overvoltage instantaneous U>>> = 0.10 ... 3.00 Un t = 15 ... 300.000 ms 59 Overvoltage high U>> = 0.10 ... 3.00 Un t = 40 ... 30.000 ms 59 Overvoltage low U> = 0.10 ... 3.00 Un t = 40 ... 30.000 ms 27 Undervoltage instantaneous U<<< = 0.10 ... 1.2 Un t = 15 ... 30.000 ms 27 Undervoltage high U<< = 0.1 ... 1.2 Un t = 40 ... 30.000 ms 27 Undervoltage low U< = 0.1 ... 1.2 Un t = 40 ... 30.000 ms
38
25
59N
59N
Synchronism check Delta Voltage ( U) = 0.02 ... 0.40 Un Time = 0.2 ... 1.000,00 s Delta Phase ( ) = 5 ... 50 Residual overvoltage high UNE>> = 0.05 ... 3.00 Un t = 20 ... 300.000 ms Residual overvoltage low UNE> = 0.05 ... 3.00 Un t = 20 ... 300.000 ms
Motor protection functions 49 Thermal overload protection with total memory Nominal Temperature = 50 ... 400 C (nominal temperature at I nom) Nominal current (IMn) = 0.1 ... 5.0 In (primary value of the nominal motor current) Initial Temperature = 10 ... 400 C Time Constant at I < 0.1 IMn = 10 ... 100.000 s Time Constant at 0.1 IMn < I < 2 IMn = 10 ... 20.000 s Time Constant at I > 2 IMn = 10 ... 20.000 s Trip Temperature = 50 ... 400 C Warning Temperature = 50 ... 400 C Environmental Temperature = 10 ... 50 C Reset Temperature = 10 400 C 51MS Motor start (adiabatic characteristic) IMn = 0.2 ... 2 IMn (motor current) (2) Is = 1.00 ... 20.00 IMn (start value) t = 40 ... 30.000 ms I> = 0.2 ... 0.8 Is (motor start) 51LR Locked rotor (definite time characteristic) IMn = 0.2 ... 2.0 In (motor current) Is = 1.00 ... 20.00 IMn (start value) t = 40 ... 30.000 ms 66 Number of starts n (warm) = 1 ...10 (number of warm starts) n (cold) = 1 ...10 (number of cold starts) t = 1.00 .. 7200.00 s T (warm) = 20 ... 200 C (warm start temp. thereshold) 46 Unbalance load Is = 0.05 ... 0.3 In (start value of the negative phase sequence) K = 2.0 ... 30.0 t Reset = 0 ... 2000 s Timer decreasing rate = 0 100% 37 Low load Pn = 50 ... 1000 000 kW (primary values) Minimal load P = 5 ... 100% Pn Minimal current I = 2 ... 20 % In Op. time = 1 ... 1000 s
(2) The motor temperature assumed by the number of starts protection is the one computed by the thermal overload protection (49). If the thermal overload protection is not used, the number of starts protection always assumes a cold start. 39
TECHNICAL DATA
Differential protection functions 87 Differential Transformer group = 0 ... 11 Transformer earthing = primary and or secondary side Nom. current In on the primary side of the transformer = 10.0 ... 100.000 A (prim value) Nom. current In on the secondary side of the transformer = 10.0 ... 100.000 A (prim value) Threshold current = 0.10 ... 0.50 In Unbiased region limit = 0.50 5.00 In Slightly biased region threshold = 0.20 ... 2.00 In Slightly biased region limit = 1.00 ... 10.0 In Slope = 0.40 ... 1.00 Trip by Id> = 5.00 ... 40.0 In Blocking by 2nd harmonic = 0.10 0.30 In Blocking by 5th harmonic = 0.10 0.30 In 87 N Restricted earth Fault (Restricted differential) Reference nominal current = 1.00 ... 100000.00 A Unbiased region threshold = 0.05 ... 0.50 In Unbiased region limit = 0.01 ... 1.00 In Slightly biased region slope = 0.01 ... 2.00 Slightly biased region limit = 0.01 ... 2.00 In Heavily biased region slope = 0.10 ... 1.00 Relay Operate Angle = 60 ... 180 Time = 0.04 ... 100.00 s Frequency protection function 81 Frequency protection Start value = 40 ... 75 Hz step 0.01 Frequency gradient = 0.01 1 Hz/s step 0.01 Time = 0.1 ... 30.0 s Undervoltage threshold = 0.1 ... 1 Un Trip logic = freq. only / freq. and gradient / freq. or gradient Frequency supervision Frequency supervision Start value = 0.04 ... 5 Hz Time = 1 ... 300 s Distance protection function 21 Distance protection Net type = high/low ohmic earth start IE> used or unused switching onto faults = normal, overreach zone, trip after start Signal comparison overreach scheme time set = 30 . 300.000 ms U / I- Start characteristic: I>, IE> and IF> = 0.05 ... 4.00 In UF< = 0.05 ... 0.9 Un Phase selection = cyclic/acyclic
40
Earth factor: k = 0.00 ... 10.00, (k) = -60 ... 60 3 Impedance, 1 overreach stage and 1 autoreclose control stage: R = 0.05 ... 120 (secondary values) X = 0.05 ... 120 (secondary values) t = 20 ... 10.000 ms 1 directional stage Direction 0 ... 90 or -45 ... 135 t = 20 ... 10.000 ms 1 non directional stage t = 20 ... 10.000 ms Power Quality functions Power factor controller Switching sequence: linear, circular Switching histeresis: neutral zone 105 ... 200 % of Qco Pick up value: 0 ... 100 % of Qco Reactive power of smallest bank Qco: 1.000 ... 20.000 kVar Configuration banks: 1:1:1:1, 1:1:2:2, 1:2:2:2, 1:2:4:4, 1:2:4:8 Number of banks: 1 ... 4 Max switching cycles: 1 ... 10.000 Set point cos phi: 0.7 ... 1.000 Limiting value cos phi: 0.0 ... 1.00 Method of operation: direct integrating dicharge blocking time: 1 ... 7200 s dead time: 1 ... 120 s power on delay: 1 ... 7200 s duration of integration: 1 ... 7200 s High harmonic protection Voltage THD Startvalue = 5 ... 50% Voltage THD Time Delay = 0.01 ... 360.00 s Time = 0.05 ... 360.00 s Rms Voltage Startvalue = 0.10 ... 1.00 Un Switching resonance protection Voltage THD Start value = 5 ... 50% Delta Voltage THD Start Value = 1 ... 50 % Voltage THD Time Delay = 0.01 ... 60 s Time = 0.05 ... 60 s PFC OP Time = 0.01 ... 120 s Rms Voltage Start value = 0.1 ... 1.0 Un
41
TECHNICAL DATA
Other functions Fault recorder Recording time = 1000 ... 5000 ms Pre fault time: = 100 ... 2000 ms Post fault time = 100 ... 4900 ms Max. 5 records 79 Autorecloser Number of shots = 5 Reclam Time = 10 ... 1000 s Specfic time first shot = 0.04 ... 30 s Dead time first shot = 0.10 ...100s Specific tme second shot = 0.04 ... 30 s Dead time second shot = 0.10 ... 100 s Specific time third shot = 0.04 ... 30 s Dead time third shot = 0.10 ... 100 s Specfic time fourth shot = 0.04 ... 30 s Dead time fourth shot = 0.10 ... 100 s Specific tme fifth shot = 0,04 ... 30 s Dead time fifth shot = 0.10 ... 100 s 32 Directional power Direction = forward, backward Nominal real power Pn = 1 ... 1000 000 kW (primary values) Max. reverse load P> = 1 ... 50 % Pn Op. time = 1.0 ... 1000 s
Configuration restriction
There are some limitations that must be respected during the REF542plus configuration. At most 24 protection functions can be configured inside the unit. A protection function can activate only one single direct channel. The number of direct channel is limited to 24. The configuration cycle time must be below 30ms, to guarantee the proper unit working. At most 1000 wires can be drawn, and the connections are limited to 512. Only one store object can be configured. (The store object allows storing binary data between a power fail and the next start up, see the programming manual for more details). At most 62 switching objects can be configured (a switching object is used to represent a primary object like a circuit breaker, a contactor etc.)
At most 15 energy counters can be configured. At most 10 analog threshold objects per analog input can be configured (analog threshold objects allow to undertake some actions depending upon the level of voltage and current, see the programming manual for more details).
LCD and HMI At most ten icons can be displayed on the LCD. At most eight switching devices icons can be displayed on the LCD. When binary I/O modules with mechanical relays are used, a maximum of seven switching devices can be controlled. At most, 40 lines can be drawn. At most 32 signaling leds organized in 4 pages can be configured. At most 48 Analog Warning Objects can be installed.
42
For both voltage ranges, the modules can be equipped with an optional static output (power transistor) on binary output 7, instead of the normal electromechanical contact. This static output is usually needed to feed external energy meters with pulses. To make wiring easier, there are also available board versions with the binary inputs minus (-) connected together on the module by an internal line.
BIO module with mechanical output relays (type 3) Binary input and output modules type BIO3 are available in several versions. High voltage, with inputs able to withstand a voltage range from 85 up to 220VDC. The input threshold activation level is 50VDC. Low voltage, with inputs able to withstand a voltage range from 24 up to 90VDC. The input threshold activation level is 14VDC.
43
TECHNICAL DATA
BIO module with static outputs The technical data for the binary input and output module with static outputs are listed below. This module is full range and covers the complete voltage range from 48 up to 265VDC.
14 inputs (BI 1-14) Auxiliary voltage range: 48 to 265 VDC (Threshold 35 VDC) Hardware fixed filter time 1 ms. Additional filter time can be configured in software. 3 power outputs (BO1,2 and 7) Operating voltage Make current Load current Operating time 4 power outputs (BO3 to 6) Operating voltage Make current Load current Operating time 2 signal outputs (BO8,9) and 1 watchdog output (WD) 2 coil supervision circuits on BO1 and BO2 channels Operating voltage Make current Operating time 48 to 265 VDC 70 A for t 10 ms 12 A for t 30 s 1 ms 48 to 265 V DC 16 A for t 10 ms 10 A for t 30 s 1 ms 48 to 265 V DC 0.3 A 1 ms
Interfaces
HMI Serial optical/electrical RS 232 interface to a PC (at the front). Galvanically insulated RS 485 standard interface to the Base Unit (at the rear). Power supply. Base Unit Galvanically insulated RS 485 standard interface to the HMI. RS 232 standard service interface. Power supply. 0/4 ... 20 mA Analog output module (optional) Four output channels 0 to 20 mA or 4 to 20 mA, freely configurable. 4 ... 20 mA Analog input module (optional) Six input channels 4...20 mA.
Communication to a station automation system (optional) SPABUS, optical plastic fiber interface with snapin type connector; or glass fiber (multi mode) with F-SMA or ST connectors. LON (according to ABB LAG1.4), glass fiber (multi mode) optical interface with ST connectors. IEC 60870-5-103 with extension according to VDEW guidelines for controlling, glass fiber (multi mode) optical interface with ST connectors. MODBUS RTU/SPA-Bus electrical interface with two galvanically insulated SPA-Bus RS 485 ports or optical interface with four standard ST connectors for glass fiber (multi mode). Ethernet Interface Standard RJ45 connector on the main module. CAN Open (optional) Open style connector compliant with CAN Open standard and ISO11898.
44
Input for time synchronization (optional) The supported protocol is IRIG, format B000, B002, B003. Glass fiber Wavelength: 820nm Max distance: 1500m Connector type: ST Input for HSTS (optional) 2 glass fiber optical inputs, ST connectors. 1 glass fiber optical output, ST connector. Refer to SUE 3000 specific documentation for more details.
Type test
Detailed information on type tests are listed in the document: REF542plus. Type test certificate, 1VTA400250. Protection functions Protection functions are type tested according to IEC 60255 standard series. Electro magnetic compatibility All relevant tests are according to the following standard series: IEC 60255 for electromagnetic compatibility and product standard; EN 61000 for electromagnetic compatibility; EN 50263 for measuring relays and protection equipment. EN 60694 + IEC 60694 Amd.12000 for common specifications for high-voltage switchgear and control gears. Insulation resistance Greater than >100MOhm at 500V DC. Mechanical robustness According to IEC 60255-21-1. Climatic conditions Cold test according to IEC 60068-2-1. Dry heat test according to IEC 60068-.2-2 Certifications ATEX The REF542plus unit, when used as a motor protection, can optionally comply with the directive 94/9/EC from the European Community for explosives environments. This directive defines how motor protection units behave in potentially explosive environment. The EC type certification number from PTB (Physikalisch Technische Bundesanstalt) is PTB 02 ATEX 3000. When requested, ATEX certification must be specified at ordering time.
Power supply
Base Unit
Rated voltage 110 VDC (-30%, +10%) 220 VDC (-30%, +10%) or 48 to 220 VDC (-15%, +10%) Power consumption Inrush current Admissible ripple < 30 W (Typical, 2 BIOs) < 10 A peak value for 200 ms Less than 10%
HMI
Rated voltage Power consumption Admissible ripple 48 110 VDC (-15%, +10%) 110 220 VDC (-15%, +10%) <6W Less than 10%
Environmental conditions
Ambient operation temperature Ambient transport and storage temperature Ambient humidity Altitude
-10 + 55C -25 +70C Up to 95% without condensation < 1000m a.s.l.
Protection degree
Base unit Housing: IP20. HMI Front: Rear:
IP 44 IP 20.
45
46
7
CONNECTIONS
Connector plates Binary input and output connections Typical connection schemes
48 51 53
47
CONNECTIONS
Connector plates
The pictures show the connections for REF542plus both in the standard and wide housing versions. The wide housing version can house three binary input and output modules, the communication module, the 0/4 ... 20 mA analog output module or alternatively the 4 ... 20 mA analog input module. The standard housing version can house at most two binary input and output modules and alternatively the communication module or the analog output module.
REF542 plus standard housing connections with mixed analog input connector and connector for the communication module.
REF542 plus standard housing connections with mixed analog input connector and connector for the 0/4 ... 20 mA analog output module.
48
The connectors meaning is explained in the following table. A few connectors have different meaning depending upon the used communication module type. Sensors connectors X87 and X88 are placed instead of X80 when only sensors are used.
REF542plus HMI connections plate. X20 is the connection to the Base Unit. X10 is the power supply.
Connector X10 X20 X21 X30 X31 X40 X41 X50 X60 X61 X62 X63 X64 X65 X70 X71 X72 X73 X74 X75 X76 X77 X80 X81 X82 X83 X84 X85 X86 X87 X88
Meaning Base unit power supply First BIO, inputs First BIO, outputs Second BIO, inputs Second BIO, outputs Third BIO, inputs Third BIO, outputs Analog Output 0/4 ... 20 mA or Analog input 4 ... 20 mA Modbus RS 485, channel 2; COM L-COM I TX; SPABUS RX Modbus RS 485, channel 1; COM L-COM I RX; SPABUS TX Opt. Modbus, RX channel 1 Opt. Modbus, TX channel 1 Opt. Modbus, RX channel 2 Opt. Modbus, TX channel 2 Ethernet Interface CAN interface RS 232 Service port Connection to HMI Time synch optical input HSTS Input HSTS Input HSTS Output Connector for CTs and VTs Sensor 1 Sensor 2 Sensor 3 Sensor 4 Sensor 5 Sensor 6 Sensor 7 Sensor 8
49
CONNECTIONS
The following picture shows the first BIO3 outputs for the two different module types: electromechanical and static.
Binary outputs types, electromechanical types on the left and solid state on the right. 51
CONNECTIONS
In the electromechanical module, it is visible the trip coil supervision on BO2. Binary outputs BO7 and BO8, normally used for signaling, are exchange contacts. WD1 is the watchdog contact. In the static output module, there are two trip coil supervision circuits on BO1 and BO2. The REF542plus can also be equipped with binary input and output modules of BIO2 types. This module type has electromechanical relays for the outputs and presents slight differences with BIO3 Modules. An example of BIO2 module is in the picture.
CONNECTIONS
Feeder with differential protection The schematic diagram below shows the connection for a power transformer feeder with differential, earth fault and restricted earth fault protection.
The used analog input board has 8 inputs for currents. The first 6 channels are used for the differential protection; channel 7 is used for the restricted earth fault protection and channel 8 for the earth protection.
Incoming feeder with synchrocheck The picture below shows a possible connection diagram for a generic incoming feeder with synchrocheck function on the bus bar. Channels 1,2,3 are used for current sensing and current protection functions.
Channels 4,5,6 are used for phase to earth voltage measurements and protection of the incoming feeder. Channel 7 is used for the residual current for earth fault protection while channel 8 is used for bus bar phase-to-phase voltage to perform the synchrocheck.
56
8
INFORMATION
58 58
57
8
INFORMATION
Document information
Revision History
Document revision 1VTA100001-Rev 6, en 1VTA100001-Rev 7, en 1VTA100001-Rev 8, en Date 25.10.2002 15.09.2003 18.05.2004 Note Last revision for Rel 1.1, sw version V4C01 Rel 2.0, sw version V4D02 Revision for service pack 1, sw version V4D02
India ABB Limited - Design & Development MV Switchgear Division plot No. 79 Street No. 17 Nashik -PIN- 422007 Phone: +91 0253 2351095 Fax: +91 0253 2350644 Internet: http://www.abb.com Switzerland ABB Secheron SA Medium Voltage Rue des Sablieres 4-6 CH 1217 Meyrin Phone: +41 22 306 2646 Fax: +41 22 306 2682 E-mail: info.secheron@ch.abb.com Internet: http://www.abb.ch Egypt ABB Arab Technical Marketing Industrial Zone B1 10th of Ramadan City Phone: +2 15 36 1288 Fax: +2 15 36 1642 Internet: http://www.abb.com/eg Germany ABB Calor Emag Mittelspannung GmbH Product Management Oberhausener Strae. 33 40472 Ratingen Phone: +49 2102 12 1901 Fax: +49 2102 12 1808 1901 E-mail: calor.info@de.abb.com Internet: http://www.abb.de/calor Korea ABB Ltd. Power Technology Medium Voltage 513 Sungsung-dong (Chonan Foreign Invested-Enterprises Industrial Park) Chonan, Chungchong-namdo, Post 330-300 Phone: +82 41 529 2458 Fax: +82 41 529 2500 E-mail: swgr.info@kr.abb.com Internet: http://www.abb.com.kr Turkey ABB Elektrik Sanayi. A.S. Design & Engineering Organize Sanayi Blgesi 2 Cadde: No. 16 Yukar Dudullu 81260 Istanbul Phone: +90 216 365 2900 Fax: +90 216 365 2943 Internet: http://www.abb.com
Product Information
Australia ABB Australia Pty Limited PTMV / MV Air Insulated Panels and Switchboards Bapaume Road Moorebank NSW Australia 2170 Phone: +61 2 9821 0269 Fax: +61 2 9602 2454 E-mail: abbptmv.aus@au.abb.com Internet: http://www.abb.com/au China ABB Xiamen Switchgear Co. Ltd Engineering ABB Industrial Park, Torch Hi-Tech Industrial Development Zone, Xiao Dong Shan Xiamen S.E.Z., Fujian 361006 Phone: +86 592 6026-033 Ext. 4061 Fax: +86 592 603-0525 Internet: http://www.abb.com Czech Republic ABB s.r.o. MV Switchgear Videnska 117 61900 Brno Phone: +420 5 4715 2413 Fax: +420 5 4715 2190 E-mail: info.ejf@cz.abb.com Internet: http://www.abb.com Italy ABB Power Technologies S.p.A Unit Operativa SACE (PTMV) Product Management Via Friuli 4 I-24044 Dalmine (BG) Phone: +39 035 395 111 Fax: +39 035 395 874 E-mail: sacetms.tipm@it.abb.com Internet: http://www.abb.com/it Malaysia ABB Transmission & Distribution Sdn. Bhd. Manufacturing Lot 608, Jalan SS 13/1K 47500 Subang Jaya, Petaling Jaya Selanggor Darul Ehsan Phone: +603 5628 4888 Internet: http://www.abb.com Finland ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel +358 10 22 11 Fax +358 10 224 1094 www.abb.com/substationautomation
58
ABB Power Technologies S.p.A. Unit Operativa SACE (PTMV) Via Friuli, 4 I-24044 Dalmine Tel: +39 035 395111 Fax: +39 035 395874 E-mail: sacetms.tipm@it.abb.com Internet://www.abb.com
The data and illustrations are not binding. We reserve the right to make changes in the course of technical development of the product.