You are on page 1of 40

AFCEE Iraq Construction Standards

September 2006

Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

INTENT AND USE


The intent of this document is to aid all stakeholders, whether Contractor, Government, Title II Quality Assurance Representatives, or end-users associated with the construction project in determining the specificiations to be used and which standards and codes are applicable for each phase of construction. Due to the unique nature of reconstruction in Iraq, which included at the outset varying levels of skilled tradesmen and widely-ranging qualities of construction materials, as well as the continuing lack of a uniformly enacted and enforced Iraqi National Building Code, AFCEE contracts have previously specified that the International Building Code (IBC) was to be utlized whererever feasible. With nearly three years experience providing construction in Iraq for AFCEE, AFCEE now recognizes there has been significant development in contractor capabilities and expects our WERC, HERC, and Iraqi subcontractors to build to the International Buidling Code standards as the norm. Recognizing that the Iraq reconstruction program continues amidst hostilities, shortages in skilled manpower and quality materials, logisitical challenges and tight deadlines, AFCEE realizes that the standards of the International Buidling Codes may not in all cases be achievable. AFCEE's intent is to deliver the end-users the highest quality facilities possible within the given schedule and budget. In keeping with this intent; where the contractor cannot comply with the requirements of the International Building Code, as a minimum, the contractror will comply with the requirements of the existing Iraqi specification for that particular phase of construction.

The document is based on the AFCEE Statement of Requirements (SOR) section provided with AFCEE Task Orders. The Statements of Requirements are at times silent as to the specific requirements regarding codes and standards, and for this reason, the document contains all applicable industry standards and references for the specific requirement, as well as the International Building Code and Iraqi specifications for the requirement. The information contained in this document is provided in a format consistent with each SOR Section. For ease of reference, this document is also organized with the SOR specifications arranged by Construction Specification Institute (CSI) Master Format numbering sequence. Deviations from the International Buidling Code or other applicable referenced standard, specification or code must be submitted in writing to the Contracting Officers Representative (COR) at least 14 days in advance of planned implementation. The request for deviation must include a precise explanation for each requirement as to why the IBC or other specifications is not applicable, practical, or not achievable. This document and the specifications contained in it will be used by AFCEE Iraq Contracting Officer's Representatives and AFCEE Iraq Title II Quality Assurance to ensure contractual compliance and to evaluate construction methods, materials and workmanship for compliance with contractual requirments.

Page 2 of 40

REFERENCE DOCUMENTS
Following is a list of documents referred to in this guide specifications. For convenience, these documents have been posted on the VIAP-Iraq website under the AFCEE Interim Iraqi Construction Standards. For information contact AFCEE Iraq Quality Assurance Program Manager, Bill Johnson at wjohnson@viap.org. AFCEE Interim Iraqi Construction Standards - Civil Work Specifications. Developed in cooperation with the University of Technology - Baghdad. AFCEE Interim Iraqi Construction Standards - Electrical Services Specifications. Developed in cooperation with the University of Technology - Baghdad. General Technical Conditions and Specifications. Book -1 / 2; Specification of Materials; Workmanship of Civil Engineering Works; Second Edition. Al Fao General Engineering Company. Iraqi Building Code Requirements for Reinforced Concrete. Code 1/ 1987 Building Research Centre; Scientific Research Council. Iraqi Ministry of Housing and Construction - Technical Specification, Book 4: Mechanical Works_General. 1993. Iraqi Ministry of Housing and Construction - General and Technical Specifications of the Sanitary Works. Ministry of Higher Education and Scientific Research Architectural, Structural, Electrical, Mechanical, and Sanitary Specifications; University of Technology, Consulting Engineering Office.

ABBREVIATIONS
AFCEE Air Force Center for Environmental Excellence AIICS AFCEE Interim Iraqi Construction Standards CSI SOR Construction Specifications Insitute Master Format 2004 AFCEE Iraq Statement of Requirements

Page 3 of 40

CSI DIVISION NUMBERS AND TITLES

Page 4 of 40

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 02 42 00 02 41 16.13

Statement of Requirements (SOR) Section 2.00.01 2.00.02

Statement of Requirements Definition Completely remove all debris, rubble, and trash in each building. Completely remove all damaged floor tiles, ceiling tiles, window casements, doorframes, mechanical ductwork, straps, hangers, inserts, electrical boxes, and devices. Repair all walls, ceilings, overheads, and floors. Eliminate ceiling tile except where absolutely necessary Eliminate dropped ceilings except where absolutely necessary for chase development of enveloping equipment (Exception: Those areas where mandated by HVAC loads such as a DFAC). Repair all damage to exterior and interior walls. Seal all open cracks on interior and exterior walls. Repair all concrete awnings. Remove all loose materials and patch to match existing building surface. Repair any supporting structure as required. Clean and repair all tarred joints in the roofing slabs. Reseal all joints and make watertight. Test water tightness of roofing and wall openings. Where possible, eliminate parapets from building vertices. Consider steel trussed roofs vs. poured roofs where procurement and cost of steel permits. Enclose or fill in all existing openings in the walls, floors and ceilings with structurally stable material. All openings in the roof structure and exterior wall shall be made watertight. Remove and replace all damaged interior doors. Remove and replace all damaged exterior doors with insulated steel doors and frames. All necessary hardware, including locks, will be included for all doors. Ensure all doorframes are flush with the wall and seams are sealed. Paint all interior doors and frames. Install wooden doors and door frames at all interior door locations. Ensure all doorframes are flush with the wall and seams are sealed. Paint all interior doors and frames. Install wooden doors and door frames at all interior door locations. Paint all interior doors and frames. Install wooden doors and door frames at all interior door locations. Mechanical room doors shall not have glass but will have a grated vent. Main entrance door shall be steel and reinforced. All steel doors shall have steel frames. Paint all steel doors and frames with the same system as specified for metal above. All doors, frames, and hardware shall be commercial / institutional grade capable of withstanding heavy use.

Construction Specifications Institute # Description Removal and Salvage of Construction Material Demolition, Building Demolition

Code IBC IBC

Code #

Code Description

Iraqi Specification AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications

Iraqi Specification Number 2-1 2-1

Specification Description General, Destruction of Establishments General, Destruction of Establishments General, Destruction of Establishments General, Destruction of Establishments General, Destruction Establishments General, Destruction Establishments General, Destruction Establishments General, Destruction Establishments Movement Joints, Laitance removal of of of of

Section 3403 Additions, Alterations and Repairs Section 3303 Demolition

2.00.03 2.00.04 2.00.05

02 01 80 N/A 02 01 80

Maintenance of Facility Remediation Customer Requirement Maintenance of Facility Remediation

IBC N/A IBC

Section 3403 Additions, Alterations and Repairs N/A Customer Requirement Section 3403 Additions, Alterations and Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Alterations and Alterations and Alterations and Alterations and Alterations and

AFCEE IICS - Civil Work Specifications

2-1

AFCEE IICS - Civil Work Specifications

2-1

2.00.06 2.00.07 2.00.08 2.00.09 2.00.10

02 01 80 02 01 80 02 01 80 02 01 80 02 01 80

Maintenance of Facility Remediation Maintenance of Facility Remediation Maintenance of Facility Remediation Maintenance of Facility Remediation Maintenance of Facility Remediation

IBC IBC IBC IBC IBC

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications Iraq Building Code Requirements for Reinforced Concrete AFCEE IICS - Civil Work Specifications

2-1 2-1 2-1 2-1 4.5, 4.4.5 and 4.4.6

2.00.11

05 44 00

Cold Formed Metal Trusses

IBC

Section 2308 Conventional Light Frame Construction Section 3403 Additions, Alterations and Repairs Section 3403 Additions, Alterations and Repairs Section 1008 Doors, Gates, Turnstiles

2.00.12

02 01 80

Maintenance of Facility Remediation

IBC

AFCEE IICS - Civil Work Specifications

2-1

General, Destruction of Establishments General, Destruction of Establishments Doors and Windows

2.00.13 2.00.13.01

06 48 13 08 13 00

Interior Wood Door Metal Doors

IBC IBC

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications

2-1 Chapter 16.16

2.00.13.02

08 14 00

Wood Doors

IBC

Section 1008 Doors, Gates, Turnstiles

AFCEE IICS - Civil Work Specifications

Chapter 16.16

Doors and Windows

2.00.13.03

06 48 16

Wood Door Frames

IBC

Section 1008 Doors, Gates, Turnstiles

AFCEE IICS - Civil Work Specifications

Chapter 16.16

Doors and Windows

2.00.13.04 2.00.13.05 2.00.13.06 2.00.13.07 2.00.13.08 2.00.13.09 2.00.13.10

09 91 23 08 14 00 08 91 26 08 11 00 08 11 00 09 91 13 08 10 00

Interior Painting Wood Doors Door Louvers Metal Doors and Frames Metal Doors and Frames Exterior Painting Doors and Frames

IBC IBC IBC IBC IBC IBC IBC

Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles Section 805 Decorations and Trim Section 1008 Doors, Gates, Turnstiles

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications

Chapter 16.16 Chapter 16.16 Chapter 16.16 Chapter 16.16 Chapter 16.16

Doors and Windows Doors and Windows Doors and Windows Doors and Windows Doors and Windows

Chapter 16.16

Doors and Windows

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 5 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 32 31 00

Statement of Requirements (SOR) Section 2.1.

Statement of Requirements Definition Perimeter Wall: At each base the ECP shall meet Coalition Force Protection Standards for vehicle and personnel entrance. Provide new guard towers and security fencing as required. Contractor is to coordinate with the MITT team on site in order to meet the location requirements. Guard towers shall be spaced no more than 300 meters apart Electrical Work: Renovate the existing and/or install a new and complete building electrical power and lighting system to include all wiring. Panels Breakers Switches Outlets

Construction Specifications Institute # Description Fences and Gates

Code CFPS

Code #

Code Description

Iraqi Specification AFCEE IICS - Civil Work Specifications

Iraqi Specification Number 3-4

Specification Description General, Fencing the Site

Customer Customer Requirement requirement

2.2. 2.2.01

26 00 00 26 05 19

Electrical Low-Voltage Electrical Power Conductors and Cables Electrical Panel board Schedule Enclosed Switches and Circuit Breakers Wiring Devices Wiring Devices

NEC NEC

N/A N/A Article 300 & Conductors for General 310 Wiring and Wiring Methods Article 408 Switchboards and Panel boards Article 240 Over current Protection Article 404 Switches Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 342, Intermediate Metal 344, 358, Conduit/Rigid Metal Conduit; 353, 365 Electrical Metallic Tubing; Rigid Nonmatallic Conduit; High Density Polyethylene Conduit; Electrical Nonmetalic Tubing Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps Article 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 300 & Conductors for General 310 Wiring and Wiring Methods

AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Specifications AFCEE IICS - Electrical Specifications AFCEE IICS - Electrical Specifications AFCEE IICS - Electrical Specifications N/A Services Services Services Services

Section 3

Cables and Wires

2.2.01 01 2.2.01 02 2.2.01 03 2.2.01.04

26 06 20.16 26 28 16 26 27 26 26 27 26

NEC NEC NEC NEC

Section 2.4 Section 2.5 Section 4 Section 4.11

Distribution Board Miniature and Molded Case Circuit Breakers Installation, Sockets and Switches Socket Outlets

2.2.01 05

Junction boxes

26 27 26

Wiring Devices

NEC

2.2.01 06

Connectors

26 05 33

Raceway and Boxes for Electrical Systems Raceway and Boxes for Electrical Systems

NEC

N/A

2.2.01 07

Conduit

26 05 33

NEC

AFCEE IICS - Electrical Services Specifications

Section 3.1.5

Support and Fixing for Cable

2.2.01 08

Fixtures

26 51 13

Interior Lighting Fixtures

NEC

AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 5.1

Lighting Fixtures

2.2.01 09

2.2.01 10

Fluorescent lights shall be mounted on walls (near full wall height) vs. ceiling mounted. Steel conduit shall be exposed instead of embedded placement Install lights in each room and at least four (4) electrical outlets. Minimum of one (1) outlet per wall that is 2m long or longer, space receptacles at 2m maximum spacing. All outlets in bathrooms, kitchens, and other wet locations shall be waterproof type. Complete the interior and exterior electrical system with commercial/institutional grade wiring and fixtures using International Electric Code. This is to include tracing any existing electrical wires and/or providing new wiring. Installation of all switches. Lights with cover

26 51 13

Interior Lighting Fixtures

NEC

Section 5.1

Lighting Fixtures

26 06 20.26

Wiring Device Schedule

NEC

2.2.02

26 51 13

Interior Lighting Fixtures

NEC

N/A

2.2.03

26 05 19

Low-Voltage Electrical Power Conductors and Cables

NEC

AFCEE IICS - Electrical Services Specifications

Section 3

Cables and Wires

2.2.03 01 2.2.03 02

26 27 26 26 51 13

Wiring Devices Interior Lighting Fixtures

NEC NEC

Article 404 Switches AFCEE IICS - Electrical Services Specifications Article 410 luminaries (lighting fixtures), AFCEE IICS - Electrical Services Lamp holders and Lamps Specifications Article 422 Appliance N/A

Section 4 Section 5.1

Installation, Sockets and Switches Lighting Fixtures

2.2.03 03

Ceiling fans

N/A

N/A

NEC

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 6 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 23 81 16 26 06 20.26

Statement of Requirements (SOR) Section 2.2.03 04 2.2.03 05

Statement of Requirements Definition Air-conditioning with electric heaters. Electrical outlets

Construction Specifications Institute # Description Room Air-Conditioners Wiring Device Schedule

Code NEC NEC

Code #

Code Description

Iraqi Specification AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A AFCEE IICS - Electrical Services Specifications

Iraqi Specification Number Section 4.16 Section 4.11

Specification Description Electrical Installation (for air conditioning) Socket Outlets

2.2.03 06 2.2.03 07 2.2.03 08 2.2.04 2.2.05

Breakers Main panels The contractor shall provide main distribution panel for the generator. The completed system will be connected into the generated electrical power distribution system. The Contractor shall be responsible for trenching and laying underground cable at least 1 meter deep from the buildings to the main distribution panel, with a minimum of 90 cm depth. The building electrical lines shall be in metal conduit for exposed installation. Cable trays Each wire shall be numbered at the terminal points with a permanent numbering system. The contractor shall provide a communications site infrastructure for telephone as integral part of the infrastructure plan. The contractor shall provide computer systems as an integral part of the infrastructure plan. For facilities traditionally earmarked for computer systems. The contractor shall develop provisions for LAN network with consideration provided for Wireless Computer Networks. The contractor shall include the electrical outlets in hidden but accessible locations to power the duct-node computer networks like those found in hotels and office buildings. Perimeter & Exterior Lights

26 28 16 26 06 20.16 26 06 20.16 26 10 00 26 05 43

Enclosed Switches and Circuit Breakers Electrical Panel board Schedule Electrical Panel board Schedule Medium-Voltage Electrical Distribution Underground Ducts and Raceway for Electrical Systems Raceway and Boxes for Electrical System

NEC NEC NEC NEC NEC

Article 440 Air-Conditioning and Refrigerating Equipment Article 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) Article 240 Over current Protection Article 408 Switchboards and Panel boards Article 408 Switchboards and Panel boards Article 110 Requirements for Electrical Installation Article 300 Underground Installation section 300.50 Article 342/344

Section 2.5 Section 2.1.1 Section 2.1.1

Miniature and Molded Case Circuit Breakers Main L.V. Switchboard Main L.V. Switchboard

Section 3.1.11

Cables Laid Direct in the Ground Support and Fixing for Cable

2.2.06

26 05 33

NEC

Intermediate Metal AFCEE IICS - Electrical Services Conduit/Rigid Metal Conduit Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 3.1.5

2.2.06 01 2.2.06 02

26 05 36 26 05 19

Cable Trays for Electrical Systems Low-Voltage Electrical Power Conductors and Cables Voice Communications

NEC NEC

Article 392 Cable Trays Article 200 Use and Identification of Grounded Conductors Article 800 Communications Circuits

2.2.07

27 30 00

NEC

Section 3.12 & 3.13.1 Heavy Duty Cable Tray & Suspend Tray Section 3.1.10 & 3.7 Identification of Cables & Cable Core Identification Section 7.1.2 Telephone System

2.2.07 01

27 20 00

Data Communications

NEC

Article 800 Communications Circuits

2.2.07 02

27 20 00

Data Communications

NEC

Article 830 Communications Circuits

N/A

2.2.07 03

27 20 00

Data Communications

NEC

Article 800 Communications Circuits

N/A

2.2.1

26 50 00

Lighting

NEC

2.2.1 01

2.2.1 02

2.2.1 03

The contractor shall provide appropriate security lighting to all building entries, exit ways, building perimeters (1 per corner), and courtyard areas. Exterior lighting system shall provide sufficient lighting in all areas commonly used at night in accordance with ground illumination requirements of the NEC Utilize area lights mounted on building exteriors vs. polemounted lighting wherever feasible. Power Distribution The Contractor shall provide the electrical power distribution system in accordance with the International Building Code Electrical Standards. The Contractor shall provide for the connection of electrical system into the existing Iraqi National local sub-station, if possible. The contractor shall plan and install a complete electrical distribution system for the area. The electrical system shall be connected to all buildings requiring electrical service.

26 55 53

Security Lighting

NEC

26 56 00

Exterior Lighting

NEC

26 56 00

Exterior Lighting

NEC

2.2.2 2.2.2.01

26 10 00 N/A

Medium-Voltage Electrical Distribution N/A

NEC NEC

Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation

AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

Section 0

General Requirements

2.2.2.02

N/A

N/A

NEC

Section 1.1

Installation of Internal Electrical Services General Requirements

2.2.2.03 2.2.2.04

26 10 00 26 10 00

Medium-Voltage Electrical Distribution Medium-Voltage Electrical Distribution

NEC NEC

Section 0

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 7 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 26 12 00

Statement of Requirements (SOR) Section 2.2.2.05

Statement of Requirements Definition Install switching panels, transformer and ring gears for each location to facilitate proper electrical distribution to each of the buildings. Install electrical cable from the distribution panel to the main breakers in each building and tent. General The contractor shall provide connection of electrical system into the existing Iraqi National local sub-station, if possible. The power connection shall be installed in combination with and through an automatic transfer switch to the Electrical Power Generation Plant The Electrical Power Generation Plant shall be designed as the primary power generation system. Therefore, provide redundant power generation with the largest generator out of service. It is the intent to utilize the national power grid as a redundant electrical supply in addition to the Electrical Power Generation Plant. Criteria The contractor's plan shall provide continuous power through an underground or aerial electrical distribution system. The electrical system shall complete with all required transformers. (400V to11KV step-up and local step-down transformer) High voltage and low voltage cable

Construction Specifications Institute # Description Medium-Voltage Transformer

Code NEC

Code #

Code Description

Iraqi Specification AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Iraqi Specification Number Section 1.3

Specification Description Power Transformer

2.2.2.06

26 05 19

Low-Voltage Electrical Power Conductors and Cables Medium-Voltage Electrical Distribution Automatic Transfer Switch

NEC

Article 450 Transformer and Transformer Vaults (Including secondary ties) Article 300 & Conductors for General 310 Wiring and Wiring Methods Article 110 Requirements for Electrical Installation Article 700 Emergency System

Section 3

Cables and Wires

2.2.3 2.2.3.01

26 10 00 26 36 23

NEC NEC

Section 0

General Requirements

2.2.3.01 01

26 10 13

Primary Unit Substation

NEC

Article 490 Equipment Over 600Volts, Nominal

AFCEE IICS - Electrical Services Specifications

Section 10

Standby Diesel Generator Set

2.2.4 2.2.4.01

N/A 26 05 43

N/A Underground Ducts and Raceway for Electrical Systems Meduim Voltage Transformers

N/A NEC

N/A N/A Article 300 Wiring Methods

N/A AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 3.1.11

Cables Laid Direct in the Ground Power Transformer

2.2.4.01 01

26 12 00

NEC

2.2.4.01 02

26 05 13

Medium-Voltage Cables

NEC

Article 450 Transformer and Transformer Vaults (Including secondary ties) Article 300 & Conductors for General 310 Wiring and Wiring Methods Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 490 Equipment Over 600Volts, Nominal Article 300 & Conductors for General 310 Wiring and Wiring Methods Article 490 Equipment Over 600Volts, Nominal Article 490 Equipment Over 600Volts, Nominal Article 430 Motors, Motor Circuits and Controllers Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps

Section 1.3

Section 3

Cables and Wires

2.2.4.01 03

Manholes

26 05 43

Underground Ducts and Raceway for Electrical Systems Wiring Devices

NEC

2.2.4.01 04

Junction boxes

26 27 26

NEC

N/A

2.2.4.01 05 2.2.4.01 06

Connectors Conductors

N/A 26 05 13.16

N/A Medium-Voltage, Single- and MultiConductor Medium-Voltage Circuit Protection Devices Medium-Voltage Fuses Medium-Voltage Circuit Protection Devices Exterior Lighting

NEC NEC

N/A AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A AFCEE IICS - Electrical Services Specifications Section 3.13 High Tension Cable

2.2.4.01 07 2.2.4.01 08 2.2.4.01 09 2.2.5

Switches Fuses Overloads Street and Motor Pool Lighting System.

26 18 00 26 18 16 26 18 00 26 56 00

NEC NEC NEC NEC

Section 2.3 Section 2.3

Fused Switchgear and Isolators Fused Switchgear and Isolators Lighting Fixtures

Section 5.1

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 8 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 26 56 00

Statement of Requirements (SOR) Section 2.2.5.01

Statement of Requirements Definition The contractor shall conduct a complete site investigation and field check in order to fully research and document the existing electrical street and motor pool lighting system. The contractor shall map out all existing conditions. With this information, the contractor shall provide a complete plan illustrating all existing and proposed new work for the complete renovation of the installations street and motor pool lighting system. Construction shall not be started until the plan is approved. The contractor shall complete all work associated with the plan in order to provide a complete and comprehensive street and motor pool lighting system. Sanitary Work Renovate the existing and/or install a new and complete building sanitary sewer system to include all piping, fittings, hangers, straps, flanges, traps, vents, drains and fixtures. Piping

Construction Specifications Institute # Description Exterior Lighting

Code NEC

Code #

Code Description

Iraqi Specification

Iraqi Specification Number Section 5.1

Specification Description Lighting Fixtures

Article 410 Luminaries (lighting AFCEE IICS - Electrical Services fixtures), Lamp holders and Specifications Lamps

2.3. 2.3.00.1

22 13 16

Sanitary Waste and Vent Piping

IPC

Section 701 General

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

Chapter 9

Building Drainage and Sanitary Fittings Building Drainage and Sanitary Fittings Drainage and Vent Pipes

2.3.2

22 13 16

Sanitary Waste and Vent Piping

IPC

2.3.2.1

Waste lines from toilets will be a minimum of 100mm diameter and slope a minimum of 2%. Lateral lines from the building to the sewer mains will slope at a minimum of 2%. Fittings

23 13 16

Sanitary Waste and Vent Piping

IPC

2.3.2.2 2.3.3

24 13 16 22 05 16

Sanitary Waste and Vent Piping Expansion Fittings and Loops for Plumbing Hangers and Support for Plumbing Piping and Equipment Hangers and Support for Plumbing Piping and Equipment Backwater Valves

IPC IPC

2.3.4 2.3.5

Hangers Straps

22 05 29 23 05 29

IPC IPC

2.3.6

Valves

22 13 19.33

IPC

2.3.7 2.3.7.1 2.3.7.2 2.3.7.3 2.3.7.4

Drains Floor drains shall be provided in each room that contains a water source Floor drains shall be provided in the mechanical equipment and toilet rooms as required. Drains shall be located near urinals or toilet partitions in toilet rooms In mechanical rooms, floor drains will be installed in such away to ensure positive slope to the drains, floor drains shall be provided to avoid running drain piping long distances above or over the floor. Install p-traps at all applicable locations

22 13 19.13 23 13 19.13 24 13 19.13 25 13 19.13 26 13 19.13

Sanitary Drains Sanitary Drains Sanitary Drains Sanitary Drains Sanitary Drains

IPC IPC IPC IPC IPC

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Section 704 Drainage Piping Installation AL-FAO General Engineering Company General Technical Conditions and Specifications Section 704 Drainage Piping Installation AL-FAO GEC - General Technical Conditions and Specifications Section 702.4 Fittings Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Table 308.5 Hanger Spacing AL-FAO GEC - General Technical Conditions and Specifications Section 308 Piping Support Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Section 715 Backwater Valves Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Section 412 Floor and Trench Drains AL-FAO GEC - General Technical Conditions and Specifications Section 412 Floor and Trench Drains AL-FAO GEC - General Technical Conditions and Specifications Section 412 Floor and Trench Drains AL-FAO GEC - General Technical Conditions and Specifications Section 412 Floor and Trench Drains AL-FAO GEC - General Technical Conditions and Specifications Section 412 Floor and Trench Drains AL-FAO GEC - General Technical Conditions and Specifications Section 1002 Trap Requirements Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works -

Section 702 Materials

Chapter 9

Section 3.2.3.12

Section 3.2.3.12 Section 9.3

Drainage and Vent Pipes Sanitary Fittings

Section 3.2.4.3 Section 6.2

Piping Pipe Supports

Section 7.1

Valves and Strainers

Section 3.2.11.15 Section 3.2.11.15 Section 3.2.11.15 Section 3.2.11.15 Section 3.2.11.15

Floor Drains Floor Drains Floor Drains Floor Drains Floor Drains

2.3.7.5

N/A

N/A

IPC

Section 9.3

Sanitary Fittings

2.3.8

Faucets

22 42 39

Commercial Faucets Supplies, and Trim

IPC

Section 424 Faucets and other Fixture Fittings Chapter 9 Vents

Section 9.4

Sanitary Fittings

2.3.9

Vent system

07 72 23

Relief Vents

IPC

Section 6

Pipe Work, Fittings and Installation Plumbing Fixtures Main Supply Distribution

2.3.10 2.3.11

Plumbing Fixtures Domestic and cold water shall be provided in the facilities to serve the water heater usage and plumbing fixtures provided for the facility.

22 40 00 22 11 13

Plumbing Fixtures Facility Water Distribution Piping

IPC IPC

Chapter 4 Chapter 6

Fixtures, Faucets and Fixture Fittings Water Supply and Distribution

Section 3.2.11 Section 11.1

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 9 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 23 11 13

Statement of Requirements (SOR) Section 2.3.12

Statement of Requirements Definition Water service to each facility shall enter the building in a mechanical, storage, or similar type space. Isolation valves shall be installed at each facility and to separate latrine/shower area. All water piping shall be routed parallel to the building lines. Insulation shall be provided where required to control sweating of pipes. Domestic water shall be distributed by means of schedule 40 galvanized steel pipe or suitable high pressure PVC equivalent. Note: the contractor shall provide galvanized Schedule 40 plumbing for sinks, showers, and toilets. The hot water shall be generated by electric water heaters

Construction Specifications Institute # Description Facility Water Distribution Piping

Code IPC

Code # Chapter 6

Code Description Water Supply and Distribution Water Supply and Distribution Piping Insulation

Iraqi Specification Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications

Iraqi Specification Number Section 11.1

Specification Description Main Supply Distribution

2.3.13 2.3.14

24 11 13 22 07 19

Facility Water Distribution Piping 22 07 19 Plumbing Piping Insulation

IPC IPC

Chapter 6 Section 607.2.1

Section 3.2.4.2 Section 8

Piping Thermal Insulation

2.3.15

22 11 13

Facility Water Distribution Piping

IPC

Section 605 Materials, Joints and Connections

Section 3.3.2

Service and Distribution Pipes.

2.3.16

22 33 00

Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

2.3.17

2.3.18

The storage unit shall be typically located inside the mechanical room, storage room, janitor room or similar type space. Floor drain shall be provided in each room that contains a water source. Floor drains shall be provided in the mechanical equipment and toilet room as required. Install showers to include all piping, faucets, drains and concrete or tile work. Shower pan shall be lowered so all water on shower floor will run into the shower pan. Install Eastern style toilets and sinks (provision of concrete trough in barracks for the feet/hand wash/laundry). Include all piping and hardware to make the units functional. Provide foot wash stations in all places where there are showers Provide sanitary sprayer and hose assembly at each toilet.

23 33 00

Electric Domestic Water Heaters

IPC

Section 501.4 Location

24 13 19.13

Sanitary Drains

IPC

Section 412 Floor and Trench Drains

Iraq Ministry of Housing & Construction Section 11.2 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 11.6 and 11.7 General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Section 3.2.11.15 Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications Section 3.2.11.8

Cold and Hot Water Distribution Electric Storage Water Heater Floor Drains

2.3.19

22 41 23

Residential Shower Receptors and Basin

IPC

Section 417 Showers

Showers

2.3.20

22 42 13

Commercial Water Closets, Urinals and Bidets N/A

IPC

Section 420 Water Closets

Section 3.2.11.5

Eastern Water Closets

2.3.20.1

N/A

NA

N/A

N/A

N/A

N/A

2.3.21

N/A

N/A

IPC

Section 424.4 Hose Connected Outlets

N/A

N/A

2.3.22 2.3.22.1 2.3.22.2 2.3.22.3 2.3.23 2.3.24

Latrine and shower walls, from floor to ceiling, shall receive ceramic tile. Provide tile base on all walls. All the joints shall be grouted and sealed to prevent water migration into the walls. Shower units shall include a changing space and privacy enclosure. Latrine stalls shall receive a swinging door with barrel bolt closure. Hose connects with appropriate piping shall be provided in each latrine/shower facility. Water Supply & Distribution:

09 30 13 09 30 00 32 01 19.61 10 21 16 10 26 19.16 22 45 36

Ceramic Tiling Tiling Sealing of Joints in Rigid Paving Shower and Dressing Compartments Shower Doors Hand-held Emergency Drench Hoses

IBC IBC IPC IPC IBC IPC

Section Showers 1210.3 Section Walls 1210.2 Section 705 Joints Section 417 Showers Section Bathroom Accessories 2606.9 Section 424.4 Hose Connected Outlets

Chapter 11 Chapter 7 Chapter 11 Section 3.2.11.8 Section 3.2.11.8 N/A

Finishing of Walls and Ceilings Construction Works Finishing of Walls and Ceilings Showers Showers N/A

2.4.

22 11 00

Facility Water Distribution

IPC

Chapter 6

Water Supply and Distribution Water Supply and Distribution Water Supply and Distribution Manholes

Section 11

2.4.1

The CONTRACTOR shall repair and renovate the existing water supply and distribution system and provide a new water supply and distribution system where required. The main headers leaving the primary water pumping plant shall be at least two (2) pipe sizes oversized and have blind flanges located at tees near both ends of future expansion zones. Fabricate and install covers or access hatches at all manholes, and electric hand holes.

22 11 13

Facility Water Distribution Piping

IPC

Chapter 6

Section 1

Water Supply Main, Distribution, Service Pipes and Equipments General and Technical Specification of the Sanitary Work. Main Supply Distribution

2.4.1.2.1

N/A

N/A

IPC

Chapter 6

Section 11.1

2.4.1.2.2

33 39 13

Sanitary Utility Sewerage Manholes, Frames and Covers

IPC

Section 708.3.6

Section 3.1.23

Manholes

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 10 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 33 39 13

Statement of Requirements (SOR) Section 2.4.1.2.3

Statement of Requirements Definition Cisterns

Construction Specifications Institute # Description Sanitary Utility Sewerage Manholes, Frames and Covers Sanitary Utility Sewerage Manholes, Frames and Covers Sanitary Utility Sewerage Manholes, Frames and Covers Sanitary Utility Sewerage Manholes, Frames and Covers Water Utility Distribution Valves

Code IPC

Code # Section 606.5.3

Code Description Covers

Iraqi Specification Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

Iraqi Specification Number Section 11.3

Specification Description Cold Water Storage Tanks Manholes Manholes Manholes

2.4.1.2.4 2.4.1.2.5 2.4.1.2.6

Sanitary sewer and water system valve manhole covers shall be round cast iron. Recess and grout all concrete manhole caps. Add fill dirt to within 2 centimeters on the top of concrete manhole cap and grade to slope away from manhole. Add fill dirt to cover an area of 2 meters around all sides of manhole. Service connections to individual building connections requiring water service shall be 1.5 meters outside each building, and shall have an isolation valve in a separate service box with accessible actuator. Pipe Bedding

33 39 13 33 39 13 33 39 13

IPC IBC IBC

Section Manholes 708.3.6 Section Concrete Masonry 2105.2.2.1.2 Section Fill Material J107.4 Section 606 Installation of Building Water Distribution System Section 306 Trenching, Excavation and Backfill Section 306 Trenching, Excavation and Backfill

Section 3.1.23 Section 3.1.23 Section 3.1.23

2.4.1.2.7

33 12 16

IPC

Section 3.1.28

Valves and Fittings

2.4.1.3

31 23 23.13

Backfill

IPC

Section 10.3

Bedding and Laying of Pipes Bedding and Laying of Pipes

2.4.1.3.1

2.4.1.3.10

The CONTRACTOR will ensure that the following criteria are met when planning and installing the new, and renovating the existing underground water supply and distribution system: CONTRACTOR shall provide bedding material to level out any irregularities. Water supply mains sizes shall be calculated according to maximum daily future flows. Compaction shall attain 95 percent maximum density for cohesionless soils, and 90 percent maximum density for cohesive soils. This is based on a Standard Proctor, ASTM D698. Maximum size of aggregate should be not more than 8 millimeters per 100 millimeters (1 inch per foot) of pipe diameter, or 75 millimeters (3 inches) maximum. Selected aggregate shall consist of well-graded sand, gravel, crushed gravel, crushed stone. The Contractor shall ensure that the water supply and distribution system conform to International Plumbing Code. The Contractor shall provide a new water supply and distribution system as needed. The Contractor shall inspect all existing underground water piping for defects. The Contractor shall repair all damaged and defective underground water piping as necessary. After completion of a section of water supply pipe the Contractor shall provide a static pressure test of the system. Any leaks shall be repaired and the section shall be retested prior to backfilling the trench covering the pipe. The Contractor will plan the overall water supply and distribution system for the base population which will vary with each facility. The CONTRACTOR shall inspect all existing underground water piping and manholes for damage and defects. The CONTRACTOR shall repair all damaged and defective underground water piping as necessary. After completion of a water section, the CONTRACTOR shall provide a static pressure test of the system. Any leaks shall be repaired and the section shall be retested.

31 23 23.13

Backfill

IPC

Section 10.3

34 06 10

Schedules for Water Utilities

IPC

Section 604 Design of Building Water Distribution System Section J107.5 Section J107.4 Compaction

Section 11.1

Main Supply Distribution

2.4.1.3.2

32 23 23.23

Compaction

IBC

Section 3.1.8

Backfilling of Trenches

2.4.1.3.3

31 05 16

Aggregate for earthwork

IBC

Fill Material

Section 10.5

Backfilling of Trenches

2.4.1.3.4

01 41 00

Regulatory Requirements

IPC

2.4.1.3.5

22 11 00

Facility Water Distribution

IPC

2.4.1.3.6 2.4.1.3.7 2.4.1.3.8

33 01 30.16 33 01 30.71 01 43 26

TV Inspection of Sewer Pipelines Rehabilitation of Sewer Utilities Testing and Inspecting Agency Qualifications

IPC IPC IPC

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Chapter 6 Water Supply and Iraq Ministry of Housing & Construction General and Technical Specifications of Distribution the Sanitary Works Section 312 Tests and Inspections AL-FAO GEC - General Technical Conditions and Specifications Section 703.4 Existing Building Sewers and AL-FAO GEC - General Technical drains Conditions and Specifications Section 312 Tests and Inspections Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Chapter 6 Water Supply and Distribution Section 604 Design of Building Water Distribution System Chapter 6 Water Supply and Distribution Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

Section 1

Section 1

Section 3.1.5 Section 3.1.5 Section 2.3

General and Technical Specification of the Sanitary Work. General and Technical Specification of the Sanitary Work. Existing Service Existing Service Cold Water Systems

2.4.1.3.9

33 06 10

Schedules for Water Utilities

IPC

Section 2.1

General Requirements

2.4.2

23 11 13

Facility Water Distribution Piping

IPC

Section 2.1

General Requirements

2.4.3

01 43 26

Testing and Inspecting Agency Qualifications

IPC

Section 312 Tests and Inspections

Section 2.3

Cold Water Systems

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 11 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 22 11 13

Statement of Requirements (SOR) Section 2.4.4

Statement of Requirements Definition Piping Materials

Construction Specifications Institute # Description Facility Water Distribution Piping

Code IPC

Code #

Code Description

Iraqi Specification AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

Iraqi Specification Number Section 3.1.10

Specification Description Pipe work

2.4.4.1

2.5. 2.5.1

Domestic water shall be distributed by means of standard weight (schedule 40) galvanized steel pipe that is installed underground with a minimum of 80cm coverage of compacted soil. Waste Water Disposal: The Contractor shall plan and construct a gravity waste water collection and treatment system. All sewerage lift stations are to be fenced and accessible only to Contractor tasked with maintenance of the WWCS The Contractor shall ensure that the sanitary sewer system conforms to International Plumbing Code. The Contractor shall plan for a gravity sanitary sewer system. Where gravity flow is not practical, the system shall consist of a series of holding tanks. The holding tanks will not be placed at or in front of any entrance. The Contractor shall plan for a non-mechanical waste water treatment plant where practical, if gravity sewer to the Municipal facilities is not available. After completion of a section of sewer the Contractor shall provide a static pressure test of the system. Any leaks shall be repaired and the section shall be retested prior to backfilling of the trench. The Contractor will plan the overall sanitary sewer collection system for the base population with a requirement rate of 300 liters per person per day and the wastewater treatment plant at 200 liters per person per day. The Contractor shall complete all work in order to provide a complete and comprehensive sanitary sewer collection system. The Contractor is responsible for all planning and construction aspects for a complete sanitary sewer collection system. Pipe shall be installed from the holding tanks to the facility exterior to allow removal of product without entering the compound. Cleanouts will be provided at each building. Site Storm Water Management System The CONTRACTOR shall conduct a complete site investigation and field check in order to fully research and document the existing site storm water management and drainage system. The CONTRACTOR shall map out all existing conditions. With this information, CONTRACTOR shall plan an overall comprehensive site storm water management and drainage plan. The CONTRACTOR shall incorporate the existing storm water management system, if applicable, into the new plan in order to ensure that the entire installation is provided with the most efficient drainage system available and that redundant work is not performed. Grade all areas to provide a uniform sloping surface. Provide fill material as needed to raise grade elevations in built up areas. Fill low areas, unused ditches, and holes.

23 11 13

Facility Water Distribution Piping

IPC

Table 605.3, Piping Materials Table 605.4 and 605.5 Table 605.3, Piping Materials Table 605.4 and 605.5 Section 701.4 Sewage Treatment

Section 3.1.10

Pipe work

44 41 13

Packaged Water Treatment Plant

IPC

N/A

N/A

N/A

2.5.2

33 32 13

Packaged Sewage Lift Stations

IPC

Section 701.4 Sewage Treatment

N/A

N/A

N/A

2.5.3

01 41 00

Regulatory Requirements

IPC

Chapter 7

Sanitary Drainage

2.5.4

44 41 13

Packaged Water Treatment Plant

IPC

Section 712 Sumps and Ejectors

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works N/A

Section 9.1

Section 9.2

Building Soil, Waste, Vent and Rain Water Pipe work. Drainage Pump Stations

2.5.5

44 41 13

Packaged Water Treatment Plant

IPC

Section 701.4 Sewage Treatment

N/A

N/A

2.5.6

01 43 26

Testing and Inspecting Agency Qualifications Schedules for Sanitary Sewerage Utilities

IPC

Section 312 Tests and Inspections

AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

Section 3.1.21

Testing Gravity Sewers and Manholes General Notes

2.5.7

33 06 30

IPC

Section 710 Drainage System Sizing

Section 3.1.1

2.5.8

33 06 30

Schedules for Sanitary Sewerage Utilities

IPC

Chapter 7

Sanitary Drainage

2.5.9

33 06 30

Schedules for Sanitary Sewerage Utilities

IPC

Chapter 7

Sanitary Drainage

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

Section 9.1

Section 9.1

Building Soil, Waste, Vent and Rain Water Pipe work. Building Soil, Waste, Vent and Rain Water Pipe work. Pipe Cleanouts

2.5.12 2.6. 2.6.1

22 05 75

Facility Drainage Piping Cleanouts

IPC

Section 708 Cleanouts

Section 3.2.11.12

22 14 00

Facility Storm Drainage

IPC

Chapter 11 Storm Drainage

Section 9.1

Building Soil, Waste, Vent and Rain Water Pipe work. Building Soil, Waste, Vent and Rain Water Pipe work. Existing Service

2.6.2

22 14 00

Facility Storm Drainage

IBC

Section 1803 Excavation, Grading and Fill Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Chapter 11 Storm Drainage AL-FAO GEC - General Technical Conditions and Specifications

Section 9.1

2.6.3

22 14 00

Facility Storm Drainage

IPC

Section 3.1.5

2.6.4 2.6.5

31 22 00 31 23 23

Grading Fill

IBC IBC

Section 1803 Excavation, Grading and Fill AL-FAO GEC - General Technical Conditions and Specifications Section J107 Fill AL-FAO GEC - General Technical Conditions and Specifications

Section 3.1.3.3 Section 3.1.3.3

Clearing and Grading of Site Clearing and Grading of Site

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 12 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 31 22 00

Statement of Requirements (SOR) Section 2.6.6

Statement of Requirements Definition Areas around facilities shall be graded to slope away from buildings and facilities in order to provide storm water drainage. Provide storm water management basins or pond areas away from developed areas for storm water detention. Soil fill shall be compacted to 90% of the maximum density in unpaved areas and 95% maximum density in paved areas determined by the Standard Proctor Method, ASTM D 698. Minimum extent of grading shall be 300 meters from any facility. Plumbing The CONTRACTOR shall plan and construct domestic cold water systems and the succeeding plumbing work in accordance with International Plumbing Code. Hot water systems

Construction Specifications Institute # Description Grading

Code IBC

Code #

Code Description

Iraqi Specification

Iraqi Specification Number Section 3.2.1.4

Specification Description Scope of Work

Section 1803 Excavation, Grading and Fill AL-FAO GEC - General Technical Conditions and Specifications Chapter 11 Storm Drainage Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications

2.6.7

33 47 26

Storm Water Drainage Reservoir

IPC

Section 10.5

Backfilling of Trenches

2.6.8

32 23 23.23

Compaction

IBC

Section J107.5

Compaction

Section 3.1.8

Backfilling of Trenches

2.7. 2.7.1

01 41 00

Regulatory Requirements

IPC

Chapter 6

Water Supply and Distribution

AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works N/A

Section 3.2.1

Scope of Work

2.7.1.1

22 11 13

Facility Water Distribution Piping

IPC

Section 607 Hot Water Supply System

Section 11.2

Cold and Hot Water Distribution Cold and Hot Water Distribution N/A Piping Thermal Insulation

2.7.1.1.1

2.7.1.1.2 2.7.1.1.3 2.7.1.1.4

Hot water shall be provided for the facility to supply 49C (120F) hot water to fixtures and outlets requiring hot water. Hot water of a higher temperature shall be provided only where required for special use or process. Hot water piping shall be routed parallel to the building lines and concealed within finished rooms. All hot water piping shall be insulated.

22 11 13

Facility Water Distribution Piping

IPC

Section 607 Hot Water Supply System

Section 11.2

22 11 13 22 11 13 22 07 19

Facility Water Distribution Piping Facility Water Distribution Piping Plumbing Piping Insulation

IPC IPC IPC

2.7.1.2

Sanitary waste system.

22 13 00

Facility Sanitary Sewerage

IPC

2.7.1.3 2.7.1.4

Drains Vent system

22 13 13 22 13 16

Sanitary Drains Sanitary Waste and Vent Piping

IPC IPC

2.7.1.5

Waste oil collection and storage.

44 42 49

Water Treatment Oil/Grease Interceptors Facility Fuel Storage Tanks

IPC

2.7.1.6 2.7.2 2.7.2.1

Fuel oil storage and distribution Sub-Contractors Qualifications The plumbing systems shall be executed by a plumbing specialist sub-contractor experienced in the plan and construction of these types of systems. All materials and equipment shall be standard product of a manufacturer regularly engaged in the manufacture of the product and shall duplicate items that have been in satisfactory use for at least two (2) years prior to bid opening. Plumbing Systems Requirements Compressed Air Systems: Compressed air shall be provided using a packaged aircooled electric motor driven compressor ASME rated receiver air cooler moisture separator to remove moisture and oil.

23 13 00

IMC

AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Chapter 7 Sanitary Drainage Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Section 412 Floor and Trench Drains AL-FAO GEC - General Technical Conditions and Specifications Chapter 9 Vents Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Section 1003 Interceptors and Separators Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Chapter 13 Fuel Oil Piping and Storage N/A

Water Supply and Distribution Water Supply and Distribution Section 607 Hot Water Supply System Chapter 6

Chapter 6

N/A Section 3.2.4.2

Section 8

Section 9.1

Section 3.2.11.15 Section 6

Building Soil, Waste, Vent and Rain Water Pipe work. Floor Drains Pipe Work, Fittings and Installation Manholes, Inspection Chambers and Gullies N/A

Section 10.6

N/A

01 43 23

Installer Qualifications

IPC

Section 106 Permits

2.7.3

01 43 13

Manufacturer Qualification

IPC

Section 303 Materials

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications

Section 2.1

General Requirements

Section 3.2.1.8

Scope of Work

2.7.4 2.7.4.00.1 2.7.4.01.01 2.7.4.01.02 2.7.4.01.03 2.7.4.01.04

22 61 00 43 12 00 N/A N/A N/A

Compressed-Air Systems for Laboratory and Healthcare Facilities Gas Compressors N/A N/A N/A

IMC IMC IMC IMC IMC

Section 1003 Pressure Vessels Section 1003 Pressure Vessels Section 1003 Pressure Vessels Section 1003 Pressure Vessels Section 1003 Pressure Vessels

N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

N/A N/A N/A N/A N/A

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 13 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 22 61 00

Statement of Requirements (SOR) Section 2.7.4.01.05

Statement of Requirements Definition Compressed air system shall be capable of operation up to 1380 KPa (200 psig) maximum for 862 KPa (125 psig) normal units. High-pressure system (above 1380 KPa) shall be provided to supply compressed air to equipment where required. Provide an engine driven air compressor where needed for operation during electrical power outages. The air distribution system shall be provided with necessary regulator valves to maintain desired pressure. Criteria The CONTRACTOR will plan the overall water supply and distribution system for the base population. Provide water pressure of 1.5 bars to the highest point in each building. Plumbing Fixtures

Construction Specifications Institute # Description Compressed-Air Systems for Laboratory and Healthcare Facilities Compressed-Air Systems for Laboratory and Healthcare Facilities Piston Gas Compressors Compressed-Air Systems for Laboratory and Healthcare Facilities N/A Facility Water Distribution Piping

Code IMC

Code #

Code Description N/A

Iraqi Specification

Iraqi Specification Number N/A N/A

Specification Description

Section 1003 Pressure Vessels

2.7.4.01.06

22 61 00

IMC

Section 1003 Pressure Vessels

N/A

N/A

N/A

2.7.4.01.07 2.7.4.01.08

43 12 16 22 61 00

IMC IMC

Section 1003 Pressure Vessels Section 1003 Pressure Vessels

N/A N/A

N/A N/A

N/A N/A

2.7.4.1 2.7.4.1.1

N/A 22 11 13

IPC IPC

Section 604 Design of Building Water Distribution System Section 604 Design of Building Water Distribution System Section 604 Design of Building Water Distribution System Section 402 Fixture Materials

2.7.4.1.2

22 11 13

Facility Water Distribution Piping

IPC

2.7.4.2

22 40 00

Plumbing Fixtures

IPC

2.7.4.2.1 2.7.4.2.1.1 2.7.4.2.1.2 2.7.4.3

Eastern Water Closet with flush tank assembly Enameled cast iron, recessed floor mounted. Install p-traps at all water closet locations. Lavatories

22 41 13 22 41 13 N/A 22 41 16

Residential Water Closets, Urinals and Bidets Residential Water Closets, Urinals and Bidets N/A Residential Lavatories and Sinks

IPC IPC IPC IPC

Section 420 Water Closets Section 402 Fixture Materials Section 1002 Trap Requirements Section 416 Lavatories

2.7.4.3.1

2.7.4.3.2

Enameled cast iron, wall or counter mounted. Brass fittings provided for water supplies. In addition to lavatories, a combination foot and hand washing station will be provided. This should be a concrete trough assembly covered with ceramic tile. Install p-traps at all sink locations.

22 41 16

Residential Lavatories and Sinks

IPC

Section 416 Lavatories

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

N/A

N/A

N/A

N/A

Section 9.3

Sanitary Fittings

Section 3.2.11 Section 3.2.11 Section 3.2.11 Section 9.3

Plumbing Fixtures Plumbing Fixtures Plumbing Fixtures Sanitary Fittings

Section 9.3

Sanitary Fittings

N/A

N/A

IPC

Section 1002 Trap Requirements

Section 9.3

Sanitary Fittings

2.7.4.4

Mop Sink

22 41 16

Residential Lavatories and Sinks

IPC

Section 427 Floor Sinks

Section 9.3

Sanitary Fittings

2.7.4.4.1

2.7.4.4.2

Floor mounted enameled cast iron with copper alloy rim guard. Provide hot and cold-water valves with manual mixing. Faucet handles shall be copper alloy. Install p-traps at all sink locations

22 41 16

Residential Lavatories and Sinks

IPC

Section 427 Floor Sinks

Section 9.3

Sanitary Fittings

N/A

N/A

IPC

Section 1002 Trap Requirements

Section 9.3

Sanitary Fittings

2.7.4.5 2.7.4.5.1

Shower Showerhead and faucet handles shall be copper alloy. Provide for manual mixing with hot and cold-water valves. Shower head riser pipe shall be schedule 40 galvanized steel. Emergency Shower

22 41 23 22 41 23

Residential Showers Receptors and Basin Residential Showers Receptors and Basin Residential Showers Receptors and Basin Emergency Showers

IPC IPC

Section 417 Showers Section 424 Faucets and other Fixture Fittings Section 605 Materials Joints and Connections Section 411 Emergency Showers and Eyewash Stations Section 411 Emergency Showers and Eyewash Stations

Section 3.2.11.8 Section 3.2.11.8

Showers Showers

2.7.4.5.2

22 41 23

IPC

2.7.4.6

22 45 13

IPC

2.7.4.6.1

Eye Wash Assembly

22 45 16

Eyewash Equipment

IPC

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

N/A

N/A

N/A

N/A

N/A

N/A

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 14 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 22 45 33

Statement of Requirements (SOR) Section 2.7.4.6.2

Statement of Requirements Definition Provide in Vehicle Maintenance Building and in other facilities where required. Service Sink

Construction Specifications Institute # Description Combination Emergency Fixtures

Code IPC

Code # N/A N/A

Code Description

Iraqi Specification -

Iraqi Specification Number N/A N/A

Specification Description

2.7.4.7

22 41 16

Residential Lavatories and Sinks

IPC

Section 418

2.7.4.7.1

2.7.4.7.2

Standard trap type, enameled cast iron. Service sinks provided in maintenance areas shall be metallic, and in battery rooms acid resistant. Install p-traps at all sink locations

22 41 16

Residential Lavatories and Sinks

IPC

Section 418

N/A

N/A

IPC

Section 1002

2.7.4.8

Grease Interceptor

44 42 49

Water Treatment Oil/Grease Interceptors Water Treatment Oil/Grease Interceptors Concrete Curing Sanitary Drains Sanitary Drains

IPC

Section 1003

2.7.4.8.1

Steel construction, manual cleaning type with removable checker-plate cover, complete with flow control valve. Concrete shall have 21 MPa (3045 psi) as a specified minimum compressive strength in 28 days. Floor or Shower Drain Cast iron construction with galvanized body, integral seepage pan, and adjustable perforated or slotted chromium plated bronze, nickel-bronze or nickel brass strainer consisting of a grate and threaded collar. Install p-traps at all drain locations

44 42 49

IPC

Section 1003

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Sinks Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Sinks Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Trap Requirements Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Interceptors and Separators Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Interceptors and Separators

Section 3.2.9

Service Sinks

Section 3.2.9

Service Sinks

Section 9.3

Sanitary Fittings

Section 10.6

Manholes, Inspection Chambers and Gullies

2.7.4.8.2 2.7.4.9 2.7.4.9.1

03 39 00 22 13 19.13 22 13 19.13

IBC IPC IPC

Minimum Specified Tables 1904.2.2(2) Compressive Strength Section 412 Floor and Trench Drains Section 412 Floor and Trench Drains

Iraq Building Code Requirements for Reinforced Concrete AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

2.1.6 (Table 2.1) Section 3.2.11.15 Section 3.2.11.15

Grade of Concrete Floor Drains Floor Drains

2.7.4.9.2

N/A

N/A

IPC

Section 1002 Trap Requirements

Section 9.3

Sanitary Fittings

2.7.4.10 2.7.4.11 2.7.4.11.1

Provide vent line between last p-trap inside building and locate away from all entrances for the building Trench Drain Cast iron construction with galvanized body, integral seepage pan, and adjustable perforated or slotted chromium plated bronze, nickel-bronze, or nickel brass strainer consisting of a grate and threaded collar. Hose Bibs

07 72 23 22 14 26.19 22 14 26.19

Relief Vents Facility Trench drains Facility Trench drains

IPC IPC IPC

Chapter 9

Vents

Section 3.2.3.13 Section 3.2.11.15 Section 3.2.11.15

Building Drainage Floor Drains Floor Drains

Section 412 Floor and Trench Drains Section 412 Floor and Trench Drains

2.7.4.12

N/A

N/A

IPC

Section Hose Connections 608.15.4.2 Section Hose Connections 608.15.4.2 Section 606.4 Valve Identification

N/A

N/A

2.7.4.12.1

Provide steel taps vs. hose bibs in latrines

N/A

N/A

IPC

N/A

N/A

2.7.4.12.2

Room hose bibs shall be provided as required

N/A

N/A

IPC

N/A

N/A

2.7.5 2.7.5.1

Plumbing Equipments Water heaters

22 33 00

Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

- Section 11.6 and 11.7 Electric water Storage Heaters Section 11.2 Cold and Hot Water Distribution Cold and Hot Water Distribution Cold and Hot Water Distribution N/A

2.7.5.1.1

The hot water shall be generated by electric water heater.

22 33 00

Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

2.7.5.1.2

The unit shall be located inside a mechanical room, storage room, toilet/janitor room or similar type locked space. The unit shall be of the commercially available tank type having low or medium watt density electric heating elements. Gas (natural or liquid propane) powered hot water generators shall be provided to satisfy large hot water requirements when economically justifiable and practical.

22 33 00

Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

Section 11.2

2.7.5.1.3

22 33 00

Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

Section 11.2

2.7.5.1.4

22 34 30

Residential Gas Domestic Water Heaters

IPC

Section 502 Installation

N/A

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 15 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 01 35 26

Statement of Requirements (SOR) Section 2.7.5.1.5

Statement of Requirements Definition All installed water heaters shall have a pressure relief valve installed. Booster Pumps

Construction Specifications Institute # Description Governmental Safety Requirements

Code IPC

Code #

Code Description

Iraqi Specification

Iraqi Specification Number

Specification Description Electric water Storage Heaters Cold Water Service Boosting Plant Cold Water Service Boosting Plant N/A

Section 504.4 Relief valve

2.7.5.2

22 11 23.13

Domestic Water Packaged Booster Pump

IPC

Section 606.5 Water Pressure Booster Systems Section 606.5.1 Water Pressure Booster Systems Required

2.7.5.2.1

2.7.6 2.7.6.1

In the event that the water distribution system is not sufficient to provide building pressure, then booster pumps with hydro-pneumatic tanks shall be installed. Special Plumbing System Contractor shall plan and construct compressor air storage and distribution. Waste-oil collection and storage

22 11 23.13

Domestic Water Packaged Booster Pump

IPC

Iraq Ministry of Housing & Construction - Section 11.6 and 11.7 General and Technical Specifications of the Sanitary Works Section 11.5 Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction Section 11.5 General and Technical Specifications of the Sanitary Works N/A

22 15 00

General Service Packaged Air Compressors and Receivers Water Treatment Oil/Grease Interceptors Facility Fuel Systems

IPC

2.7.6.2

44 42 49

IPC

2.7.6.3

2.7.6.4

Fuel-oil storage and distribution plumbing systems that are required for full performance of equipment and other operations in the Power Plant Sewage Treatment Facility

23 10 00

IPC

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Section 1003 Interceptors and Separators Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Chapter 13 Fuel Oil Piping and Storage N/A

Chapter 12 Special Piping and Storage System

Section 10.6

Manholes, Inspection Chambers and Gullies N/A

N/A

44 42 00

Water Treatment Equipment

IPC

Section 701.4 Sewage Treatment

2.7.7 2.7.7 2.7.7.1

2.7.7.1

2.7.7.2

Special Waste Testing and Commissioning Waste or hazardous drainage from battery repair/charging areas shall be treated prior to entering the sites general waste drainage system. After completing the work, the Contractor shall demonstrate that all plumbing systems operate to fully satisfy the function for which these systems have been designed. All drainage piping shall be acid resistant

IPC 44 41 13 Packaged Water Treatment Plant IPC Chapter 8 Indirect/Special Waste

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General -

Section 10.6

Manholes, Inspection Chambers and Gullies

Section 10.6

Manholes, Inspection Chambers and Gullies Cold Water Systems

01 43 26

Testing and Inspecting Agency Qualifications Facility Sanitary Sewers

IPC

Section 312 Tests and Inspections

Section 2.3

22 13 13

IPC

Section 702 Materials

N/A

N/A

2.7.7.2

2.7.7.3

The Contractor shall include tests for interlocks, safety cutouts and other protective devices to demonstrate safe operation Smaller battery rooms shall have waste treated using acid neutralizing tank. Fully flush and sanitize system prior to final acceptance.

01 45 23

Testing and Inspecting Services

IPC

Section 307 Structural Safety

Section 2.3

Cold water Systems

23 13 13.13

Double wall Steel, Underground Storage tanks Code Required Special Inspector Classifications Double wall Steel, Underground Storage tanks Testing and Inspecting Services

IPC

Chapter 8

Indirect/Special Waste

N/A

N/A

2.7.7.3

01 43 29

IPC

Section 312 Tests and Inspections

Section 2.2

Water Mains Test

2.7.7.4

Waste oil storage tanks shall be provided for collection of waste oil in the power plant Pressures test all lines for leaks.

23 13 13.13

IPC

Chapter 8

Indirect/Special Waste

N/A

N/A

2.7.7.4

01 45 23

IPC

Section 312 Tests and Inspections

Section 2.3

Cold water Systems

2.7.7.5

Waste oil storage tank shall be underground double-wall fiberglass or double-wall steel. MECHANICAL WORK: Heating Ventilating Air Conditioning:

23 13 13.23

Glass-Fiber Reinforced Plastic, Underground Fuel-Oil storage Tanks HEATING, VENTILATING, AND AIRCONDITIONING (HVAC) HVAC

IPC

Chapter 8

Indirect/Special Waste

N/A

N/A

2.8. 2.8.00.1

23 00 00 23 00 00

IMC IMC Chapter 4, 5, Ventilation, Exhaust 6, 11 Systems, Duct Systems, Refrigeration Chapter 4 Ventilation

4.2.14

Package Air Conditioner Unit Centrifugal Power Supply Fan Package Air Conditioner Unit

2.8.00.01.01

Ventilation fans,

23 34 00

HVAC Fans

IMC

4.2.64

2.8.00.01.02

Air-conditioning systems utilizing packaged terminal Air Handling Units,

23 81 13

Package Terminal Air-Conditioners

IMC

Section 312 Heating and Cooling Load Calculations

4.2.14

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 16 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 23 63 00

Statement of Requirements (SOR) Section 2.8.01.03

Statement of Requirements Definition Condensing Units,

Construction Specifications Institute # Description Refrigerant Condensers

Code IMC

Code #

Code Description

Iraqi Specification Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General

Iraqi Specification Number 4.2.18 g

Specification Description Condensers

Chapter 11 Refrigeration

2.8.01.04

Air-handling units,

23 30 00

HVAC Air Distribution

IMC

Chapter 6

Duct Systems

4.2.13 g

Evaporator and Condenser Fans Evaporator and Condenser coils Refrigerant pipe work

2.8.01.05

Coils,

23 82 16

Air Coils

IMC

Chapter 11 Refrigeration

4.2.13 f

2.8.01.06

Piping,

23 23 00

Refrigerant Piping

IMC

Chapter 11 Refrigeration

4.2.18 h

2.8.01.07

Exhaust fans,

23 34 00

HVAC Fans

IMC

Chapter 5

Exhaust System

4.2.63

Centrifugal Roof Exhauster Supply Air Diffuser

2.8.01.08

Grills,

23 37 13

Diffusers, Registers, and Grilles

IMC

Section 603.17 Chapter 6

Registers, grilles and diffusers Duct Systems

4.2.45

2.8.01.09

Registers,

23 37 13

Diffusers, Registers, and Grilles

IMC

4.2.43

Supply Air Registers

2.8.01.10

Ductwork,

23 32 00

Air Duct Accessories

IMC

Chapter 6

Duct Systems

4.2.40

Low Velocity Ductwork

2.8.01.11

Hangers,

23 32 00

Air Duct Accessories

IMC

Chapter 6

Duct Systems

4.2.47

Connections to Ductwork

2.8.01.12

Straps,

23 32 00

Air Duct Accessories

IMC

Chapter 6

Duct Systems

4.2.47

Connections to Ductwork

2.8.01.13

Fasteners,

23 32 00

Air Duct Accessories

IMC

Chapter 6

Duct Systems

4.2.47

Connections to Ductwork

2.8.02.01

The Contractor shall plan, supply, fabricate and install new ventilation system. The Contractor shall plan, supply, fabricate and install new heating systems. Ventilators and Heaters,

23 82 23

Unit Ventilators

IMC

Chapter 4

Ventilation

4.2.61

Fans-Propeller Type (Wall Mounted) Heaters

2.8.02.02

23 82 39

Unit Heaters

IMC

Section 920 Unit Heaters

4.2.14 i

2.8.03

23 82 00

Convection Heating and Cooling Units

IMC

Section 920 Heating and Cooling Load Calculations Section 920 Unit Heaters

4.2.14 i

Heaters

2.8.03.01

Heating systems,

23 83 00

Radiant Heating Units

IMC

4.2.14 i

Heaters

2.8.03.02

Baseboard heaters,

23 83 13

Radiant Heating Electric Cables

IMC

Section 920 Unit Heaters

4.2.14 i

Heaters

2.8.03.03

Resistance heaters in the A/C units may be substituted for electric baseboard heaters, ceiling fans,

23 83 33

Electric Radiant Heaters

IMC

Section 920 Unit Heaters

4.2.14 i

Heaters

2.8.03.04

23 34 00

HVAC Fans

IMC

Section 503.2 Exhaust System

4.2.61

Fans-Propeller Type (Wall Mounted) Package Air Conditioner Unit Centrifugal Roof Exhauster Heaters

2.8.03.05

Air conditioning,

23 81 16

Room Air-Conditioners

IMC

Section 312 Heating and Cooling Load Calculations Chapter 5 Exhaust System

4.2.14

2.8.03.06

Toilet exhaust systems,

23 34 00

HVAC Fans

IMC

4.2.63

2.8.03.07

Electric heaters,

23 82 39

Unit Heaters

IMC

Section 920 Unit Heaters

4.2.14 i

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 17 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 23 82 00

Statement of Requirements (SOR) Section 2.8.03.08

Statement of Requirements Definition Air conditioners/heat pumps in all enlisted quarters,

Construction Specifications Institute # Description Convection Heating and Cooling Units

Code IMC

Code #

Code Description

Iraqi Specification Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General

Iraqi Specification Number 4.2.14

Specification Description Package Air Conditioner Unit Package Air Conditioner Unit Package Air Conditioner Unit Package Air Conditioner Unit Fans-Propeller Type (Wall Mounted)

Section 312 Heating and Cooling Load Calculations Section 312 Heating and Cooling Load Calculations Section 312 Heating and Cooling Load Calculations Specific appliances, fireplaces and solid fuel burning equipment Chapter 4, 5 Ventilation and Exhaust Systems Chapter 9

2.8.04

Air Conditioners/heat pumps,

23 81 00

Decentralized Unitary HVAC Equipment

IMC

4.2.14

2.8.04.01

Air Conditioners shall be window mounted type, shall be manually operated and enclosed in a protective vandal proof steel cage and mounted out of high traffic areas. Heat pumps shall be of the window mounted type, manually operated and enclosed in a protective vandal proof steel cage and mounted out of high traffic areas. Exhaust and Ventilation:

23 81 16

Room Air-Conditioners

IMC

4.2.14

2.8.04.02

23 81 43

Air-Source Unitary Heat Pumps

IMC

4.2.14

2.8.1

23 30 00

HVAC Air Distribution

IMC

4.2.61

2.8.1.1 2.8.1.2 2.8.1.2.01

General: Criteria: FILTRATION:

N/A N/A 23 40 00

HVAC Air Cleaning Devices

IMC

2.8.1.2.01.01

Outside Air Intakes,

23 41 00

Particulate Air Filtration

IMC

2.8.1.2.01.02

Weatherproof louvers with a bird screen,

32 35 13

Screens and Louvers

IMC

2.8.1.2.01.03

Wall intakes,

23 37 00

Air Outlets and inlets

IMC

2.8.1.2.01.04

Roof hoods,

23 38 00

Ventilation Hoods

IMC

2.8.1.2.01.05

2.8.1.2.02

50mm thick permanent washable metal mesh type filters as first stage for filtration of dust. Medium efficiency (30 percent, as defined by ASHRAE 52 Dust Spot Efficiency Criteria) filters, the 50 mm (2 inch) thick disposable panel type, shall be the second. VENTILATION AND EXHAUST FANS:

23 43 13

Washable Electronic Air Cleaners

IMC

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Section 605 Air Filters Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Section 401.6 Outdoor opening protection Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Chapter 4 Ventilation Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Chapter 4 Ventilation Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Section 605 Air Filters Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General Section 503 Ventilations rate in rooms Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General

Section 605 Air Filters

4.2.60

Air Filters

4.2.60

Air Filters

4.2.62 e

Bird Screen

4.2.52 b

Fresh air (Roof intakes)

4.2.54

Kitchen Exhaust Hoods

4.2.60

Air Filters

23 34 00

HVAC Fans

IMC

4.2.64

Centrifugal Power Supply Fan Centrifugal Power Supply Fan

2.8.1.2.02.01

2.8.1.2.02.02

All fans used for ventilation and pressurization shall be selected for required performance and for minimum noise level. Unit mounted supply and exhaust fans shall be centrifugal forward curved, backward inclined, or airfoil fans with non-overloading characteristics of high efficiency and quiet running plan. Gravity dampers,

23 34 16

Centrifugal HVAC Fans

IMC

Chapter 4

Ventilation

4.2.64

23 33 13

Dampers

IMC

Section Ventilation [B]513.10.4 Section 506.3.2.4 Section 506.3.3 Chapter 5 Vibration isolation

2.8.1.2.02.03

Vibration isolators,

23 37 23

HVAC Gravity Ventilators

IMC

2.8.1.2.02.04 2.8.1.2.02.05

External lubricators, accessories and controls necessary for specified sequence of operation. Administrative Areas: 34 CMH/person (20 CFM/person) with air conditioning; 37 CMH/m2 (2 CFM/Ft2) of floor area.

23 37 23 23 37 23

HVAC Gravity Ventilators HVAC Gravity Ventilators

IMC IMC

Grease duct support Exhaust System

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General N/A Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General

4.2.61f

Dampers

4.2.64f

Vibration Isolation

N/A 4.2.63h

N/A Controls

2.8.1.2.03

23 34 16

Centrifugal HVAC Fans

IMC

[F]502.5.2

Ventilation rate in rooms

4.2.64 b

Centrifugal Power Supply Fan/Capacity

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 18 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 23 34 16

Statement of Requirements (SOR) Section 2.8.1.2.04

Statement of Requirements Definition Toilet and Wash Areas: Exhaust ventilation at 37 CMH/m2 (2 CFM/Ft2) of floor area. Or 85 CMH/Water Closet or Urinal. Kitchen Hood Exhaust and Make-up air: As required and as per Kitchen plan specialist and equipment supplier requirements. Minimum requirements include requirements. Minimum requirements include hoods with exhaust fans and fire extinguishers over each cooking area Electrical/Mechanical rooms: Mechanical ventilation sufficient to limit space temperature and to remove heat given out by operating equipment, 37 CMH/M2. Maintenance Shops: Maintenance Shops and similar spaces that use solvents and oils shall be provided with mechanical exhaust air systems. The systems shall consist of centrifugal fan, ductwork, exhaust grille, and interlock controls. These type spaces shall not return exhaust air to any split system unit or ventilation system. Centrifugal fan,

Construction Specifications Institute # Description Centrifugal HVAC Fans

Code IMC

Code # [F]502.5.2

Code Description Ventilation rate in rooms

Iraqi Specification

Iraqi Specification Number 4.2.64 b

Specification Description Centrifugal Power Supply Fan/Capacity Kitchen Exhaust Hoods

2.8.1.2.05

23 38 13

Commercial Kitchen Hoods

IMC

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Section 506 Commercial Kitchen Hood Iraq Ministry of Housing & Construction Ventilation system ducts and Technical Specification Book 4: exhaust equipment Mechanical Works_General

4.2.54

2.8.1.2.06

23 34 16

Centrifugal HVAC Fans

IMC

[F]502.5.2

Ventilation rate in rooms

2.8.1.2.07

23 34 16

Centrifugal HVAC Fans

IMC

503

Motors and Fans

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General

4.2.64 b

Centrifugal Power Supply Fan/Capacity Centrifugal Roof Exhauster

4.2.63

2.8.1.2.07.01

23 34 16

Centrifugal HVAC Fans

IMC

Chapter 4

Ventilation

2.8.1.2.07.02

Ductwork,

23 31 00

HVAC Ducts and Casings

IMC

Chapter 6

Duct Systems

2.8.1.2.07.03

Exhaust grille,

23 37 13

Diffusers, Registers, and Grilles

IMC

Section 603.17 Chapter 6

Registers, grilles and diffusers Duct Systems

2.8.1.2.07.04

Interlock controls,

23 33 00

Air Duct Accessories

IMC

2.8.1.2.08

2.8.1.2.08.01

Central Diesel Generator Facility: Per the calculations of the plan ENGINEER and approval of the COR. The facility shall be provided with mechanical exhaust air systems. The system shall consist of centrifugal fan, Ductwork,

23 35 00

Special Exhaust Systems

IMC

502.1.1

Exhaust Location

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General

4.2.64

Centrifugal Power Supply Fan Low Velocity Ductwork

4.2.40

4.2.52

Fresh and Exhaust Air Louvers Flexible Connections

4.2.41e

4.2.63

Centrifugal Roof Exhauster Low Velocity Ductwork

23 33 00

Air Duct Accessories

IMC

Chapter 6

Duct Systems

4.2.40

2.8.1.2.08.02

Exhaust grille,

23 33 00

Air Duct Accessories

IMC

Chapter 6

Duct Systems

4.2.52

Fresh and Exhaust Air Louvers Flexible Connections

2.8.1.2.08.03

Interlock,

23 33 00

Air Duct Accessories

IMC

Section 603.6.2 [F]502.5.2

Flexible Air Connectors

4.2.41e

2.8.1.2.09

2.8.1.3 2.8.1.3.01

Barracks: Air conditioning for officers and Senior NCO's only. Ceiling fans and adequate room ventilation for Junior NCO (jundis). Specific Requirements: Install ceiling fans in all rooms, with vibration mounts or hook-type suspension. To reduce sand and dirt migration, outside air intakes shall be located as high as possible within architectural constraints. The intakes shall be sized so that free air velocities are below 2.5 m/s (500 fpm). All fans used for ventilation and pressurization shall be selected for required performance and for minimum noise level. Unit mounted supply and exhaust fans shall be centrifugal forward curved, backward inclined, or airfoil fans with non-overloading characteristics of high efficiency and quiet running plan. Power Generation:

23 34 23

HVAC Power Ventilators

IMC

Ventilations rate in rooms

4.2.61

Fans-Propeller Type (Wall Mounted) Fans-Propeller Type (Wall Mounted) Air Filters

23 34 23

HVAC Power Ventilators

IMC

[F]502.5.2

Ventilations rate in rooms

4.2.61

2.8.1.3.02

23 41 00

Particulate Air Filtration

IMC

605.3

Airflow over the filter

4.2.60

2.8.1.3.03

23 34 16

Centrifugal HVAC Fans

IMC

[F]502.5.2

Ventilation rate in rooms

4.2.66

Utility Exhaust Fan

2.8.2

26 10 00

Medium-Voltage Electrical Distribution

NEC

Article 110 Requirements for Electrical Installation

N/A

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 19 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 21 20 00

Statement of Requirements (SOR) Section 3.2.

Statement of Requirements Definition Fire Prevention: A minimum of one (1), 8 kg or greater, fire extinguisher per 100 square meters shall be provided. All fire extinguishers shall be mounted to the wall or placed in existing cabinets. Fire extinguishers shall be of the ABC type. Install commercial grade, hard wired electric and battery powered smoke alarms in all rooms and hallways. Install emergency exit signs, in Arabic with international symbols, over primary fire exit routes. Install commercial grade, hard wired electric and battery powered smoke alarms in all rooms and hallways. Non-load bearing shall be reinforced with 15 cm x 15 cm 12 gauge wire mesh or larger. A broom type finish is expected unless otherwise requested. Expansion or control joints shall be placed in the concrete for a maximum slab size of approximately 3 m x 3 m. All block and brick walls, both solid and hollow core shall be placed with mortar on all surfaces in contact with adjacent block or brick. Placing the mortar after the block is positioned in place is unacceptable. Finished Flooring: All finished flooring shall be of terrazzo tile except for food preparation areas and bathroom floors. All food preparation and bathroom finished floors shall be of glazed ceramic tile finish. The project includes all structures, buildings and systems as required for the installation. Submit all manufacturers documentation, training manuals and training procedures, quality control, safety, security, and environmental protection procedures to the Contracting Officers Representative (COR). At time of negotiations, the Contractor and COR will determine number and type of copies of each submittal required. The Contractor will submit these items at a time determined by the COR and the submission will be documented on the Contractors schedule. All submittals shall include a cover letter to the COR on or before the date indicated in the Contractors schedule. Submit reports as required by the COR on all project related issues to the COR. Submit the following to COR and Title II for review and approval: Preventive Maintenance Plan: The Contractor shall prepare a Preventive Maintenance Plan and submit it to the COR for review and approval. This plan shall identify manufacturers information and recommendations for preventive maintenance on all new equipment installed under this contract. Training Manuals: The Contractor will be responsible for providing a minimum 3 hours of training on each (1) HVAC, (2) Electrical, (3) Generator, (4) Plumbing, and (5) Fire Alarm systems. The Contractor shall provide Training Manuals for the components of these systems in English and Arabic. COR Submittals:

Construction Specifications Institute # Description Fire Extinguishing Systems

Code IBC

Code #

Code Description

Iraqi Specification

Iraqi Specification Number 41.1

Specification Description Halon 1301 Cylinders

Section 906 Portable Fire Extinguishers

3.2.01

21 21 00

Carbon-Dioxide Fire-Extinguishing Systems Smoke Detection Sensors

IBC

Section 902 [F] [F]907.2.8.3

3.2.02

28 31 46

IBC

3.2.03

26 53 00

Exit Signs

IBC

Chapter 10

3.2.1

28 31 00

Fire Detection and Alarm

IBC

Chapter 9

3.3.02

03 22 00

Welded Wire Fabric Reinforcing

ASTM

A 185-1

3.3.03 3.3.04

03 25 36 07 95 00

Grooved Concrete Finish Expansion Control

IBC IBC

Section 804

Ministry of Higher Education and Scientific Research - Electrical Specifications Carbon Dioxide Ministry of Higher Education and Extinguishing Systems Scientific Research - Electrical Specifications Smoke Alarms Ministry of Higher Education and Scientific Research - Electrical Specifications Means of Egress Ministry of Higher Education and Scientific Research - Electrical Specifications Fire Protection Systems Ministry of Higher Education and Scientific Research - Electrical Specifications Specification for Steel Iraq Building Code Requirements for Welded Reinforcement, Plain Reinforced Concrete Concrete Interior Floor Finish AFCEE IICS - Civil Work Specifications

41.1

Halon 1301 Cylinders

41.6

Smoke Detectors

N/A

N/A

41

Fire Detection and Extinguishing System Shrinkage and Temperature Reinforcement Movement Joints

5.10.2,5.10.4

N/A 4.5.1

Section 1906 Formwork, Embedded Pipes Iraq Building Code Requirements for and Construction Joints Reinforced Concrete Section 2103,2104 Masonry Construction Material AFCEE IICS - Civil Work Specifications

3.3.05

04 20 00

Unit Masonry

IBC

Chapter 6

Mortar

3.4.00.01

09 66 13

Portland Cement Terrazzo Flooring

IBC

Section 804 Interior Floor Finish

AFCEE IICS - Civil Work Specifications

Chapter 12.12

Floors and surfaces

3.4.00.02 4.01. 5.00.00

04 21 16 N/A 01 33 00

Ceramic Glazed Clay Masonry N/A Submittal Procedures

IBC N/A IBC

Section 804 Interior Floor Finish N/A N/A

AFCEE IICS - Civil Work Specifications

Chapter 12.13

Floors and surfaces

Section 106 Construction Documents

AFCEE IICS - Civil Work Specifications

1-9

General, Performed designer and which was performed.

5.1.

01 78 23.19

Preventive Maintenance Instruction

IBC

Section 106 Construction Documents

AFCEE IICS - Civil Work Specifications

1-10

General, Sample of Material and Works

5.2.

01 79 00

Demonstration and Training

IBC

Section 106 Construction Documents

N/A

N/A

N/A

5.3.

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 20 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 01 45 33 01 45 33 01 45 33 01 45 33

Statement of Requirements (SOR) Section 5.3.01 5.3.02 5.3.03 5.3.04 6.00.00 6.01.

Statement of Requirements Definition Submit the following to the COR for review and approval: Construction Inspection Reports Testing and Inspection Reports Coordination Memoranda PLANNING STANDARDS: The Contractor must adhere to the International Building Code, International Electrical Code, International Mechanical Code, International Plumbing Code, International Fire Code and in any other standards specifically cited herein as applicable. The Contractor must provide copies of all specifications, calculations and manuals used. All calculations, standards and correspondence shall be in English The Contractor shall provide all site assessments and work plans with calculations and CADD drawings (where applicable). Provide as-built drawings, training manuals, warranties, preventive maintenance plans and operations and maintenance manuals, in English and Arabic. Provide 2 copies of legible operation and maintenance manuals for all new equipments, finishes, fixtures and hardware bound and cataloged in CSI format on A4 sized paper. Follow "single manufacturer" premise for generators, pumps, valves, compressors, electrical components, etc. where possible for utility plants and critical infrastructure elements (WTPs, WWTPs, Power Plants, etc.) The contractor shall develop provisions for Wireless Computer Networks; consider including electrical outlets in hidden but accessible locations to power the duct-node computer networks like those found in hotels and office buildings. Explore opportunities to make manhole covers inaccessible to vehicle traffic or protect with bollards. The Contractor shall provide catalog cuts, supplier data, test reports and other information required by the COR during construction. Submittals shall clearly show that the materials or equipments supplied meet or exceed the specifications and project requirements. Concrete Requirements: CONSTRUCTION DRAWINGS: Provide shop drawings or a detailed Scope of Work for approval before construction proceeds. As-built drawings must reflect full details of items built. All buildings will be planned, designed, renovated, or constructed according to requirements and specifications. Iraqi standards or any other acceptable standards shall be implemented. Eastern and Western-style fixtures will be required and installed where indicated on construction drawings. All concrete shall have a minimum 28 day compressive strength of 21 MPa (3000 psi). Reinforce slabs with 15 cm x 15 cm 12 gauge steel wire mesh or larger. A broom type finish is expected unless otherwise requested.

Construction Specifications Institute # Description Code-Required Procedures Code-Required Procedures Code-Required Procedures Code-Required Procedures Special Inspections and Special Inspections and Special Inspections and Special Inspections and

Code IBC IBC IBC IBC

Code # N/A

Code Description Customer Requirement N/A

Iraqi Specification

Iraqi Specification Number N/A 4-1 to 4-5 1-7 1-7 N/A

Specification Description

Section 1704 Special Inspection Section 1715 Material and Testing Standards Section 106 Construction Documents

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications

General, Planning the Site General, Planning the Site General, Planning the Site General, Standard Specifications

01 41 00

Regulatory Requirements

IBC

Section 106 Construction Documents

AFCEE IICS - Civil Work Specifications

1-7

6.02.

01 33 23

Shop Drawings, Product Data and Samples

IBC

SEC 106

Construction Documents

AFCEE IICS - Civil Work Specifications

1-9, 1-10

Planning, Sample of Materials and Work

6.03.

N/A

Customer Requirement

N/A

N/A

Customer Requirement

N/A

N/A

N/A

6.04.

27 21 33

Data Communication s Wireless Access Point

NES

N/A

N/A

N/A

6.06. 6.07.

N/A 01 33 00

Customer Requirement Submittal Procedures

N/A IBC

N/A

Customer Requirement

N/A AFCEE IICS - Civil Work Specifications

N/A 1-10

N/A General, Sample of Material and Works

7.1. 7.00.01

01 33 23

Shop Drawings, Product Data and Samples Customer Requirement

IBC

AFCEE IICS - Civil Work Specifications

1-10

General, Sample of Material and Works Standard Specifications

7.00.02

N/A

N/A

N/A

Customer Requirement

AFCEE IICS - Civil Work Specifications

1-7

7.1.01 7.1.02

03 31 00 03 22 00

Structural Concrete Welded Wire Fabric Reinforcing

IBC ASTM

7.1.03

03 25 36

Grooved Concrete Finish

IBC

Section 1905 Concrete Quality, Mixing and Placing A 185-1 Specification for Steel Welded Reinforcement, Plain Concrete Section 804 Interior Floor Finish

Iraq Building Code Requirements for Reinforced Concrete Iraq Building Code Requirements for Reinforced Concrete AFCEE IICS - Civil Work Specifications

2.1.6 (Table 2.1) 5.10.2,5.10.4

Grade of Concrete Shrinkage and Temperature Reinforcement

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 21 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

VIAP Iraq

Versar International Assistance Projects

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by SOR
Construction Specifications Institute (CSI) # 03 39 00

Statement of Requirements (SOR) Section 7.1.04

Statement of Requirements Definition The concrete shall be free from excessive voids or cracks when poured and be wetted sufficiently to avoid stress cracking due to excessive moisture loss. Provide test cylinders or cubes for every 20 cubic meter of concrete placed. Compact soils on foundation to 95% maximum density determined by the Standard Proctor Method, ASTM D 698 before concrete is poured. Place expansion or control joints in the concrete for a maximum slab size of 3 meters x 3 meters.

Construction Specifications Institute # Description Concrete Curing

Code IBC

Code #

Code Description

Iraqi Specification

Iraqi Specification Number 2.3.3a, 3.2 to 3.4

Specification Description Exposure Conditions

Section 1905 Concrete Quality, Mixing and Iraq Building Code Requirements for Placing Reinforced Concrete Section 1903, Specification for tests and 1905.6.2.3 Materials J107.5 Compaction Iraq Building Code Requirements for Reinforced Concrete AFCEE IICS - Civil Work Specifications

7.1.05

03 39 00

Concrete Curing

IBC

2.2.5, 2.4.1

Proportioning of Concrete Chapter 2, Digging Lengthened trenches for general services. Compaction) Movement Joints

7.1.06

32 11 16

Sub base Course

IBC

6-2, 6-3

7.1.07

07 95 00

Expansion Control

IBC

1905.10.7

Construction Joints

Iraq Building Code Requirements for Reinforced Concrete

4.5.1

IBC,IEC, IPC, IMC, NES,NEC andASTM are all registered and copyrighted material.

Page 22 of 40
Versar 2006 VIAP 2006 This is a proprietary VIAP document. Any unauthorized use, distribution or copying of this document is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 01 33 00 Statement of Requirements (SOR) Section 5.00.00 Statement of Requirements Definition Construction Specifications Institute # Description Code Code # Code Description Iraqi Specification Iraqi Specification Number 1-9 Specification Description General, Performed designer and which was performed.

Submit all manufacturers documentation, training Submittal Procedures manuals and training procedures, quality control, safety, security, and environmental protection procedures to the Contracting Officers Representative (COR). At time of negotiations, the Contractor and COR will determine number and type of copies of each submittal required. The Contractor will submit these items at a time determined by the COR and the submission will be documented on the Contractors schedule. All submittals shall include a cover letter to the COR on or before the date indicated in the Contractors schedule. Submit reports as required by the COR on all project related issues to the COR. Submit the following to COR and Title II for review and approval: Submittal Procedures The Contractor shall provide catalog cuts, supplier data, test reports and other information required by the COR during construction. Submittals shall clearly show that the materials or equipments supplied meet or exceed the specifications and project requirements. The Contractor shall provide all site assessments and work Shop Drawings, Product Data and plans with calculations and CADD drawings (where Samples applicable). Provide as-built drawings, training manuals, warranties, preventive maintenance plans and operations and maintenance manuals, in English and Arabic. Provide 2 copies of legible operation and maintenance manuals for all new equipments, finishes, fixtures and hardware bound and cataloged in CSI format on A4 sized paper. CONSTRUCTION DRAWINGS: Provide shop drawings or a Shop Drawings, Product Data and Samples detailed Scope of Work for approval before construction proceeds. As-built drawings must reflect full details of items built. All installed water heaters shall have a pressure relief Governmental Safety Requirements valve installed. The Contractor shall ensure that the water supply and distribution system conform to International Plumbing Code. The Contractor shall ensure that the sanitary sewer system conforms to International Plumbing Code. Regulatory Requirements

IBC

Section 106 Construction Documents

AFCEE IICS - Civil Work Specifications

01 33 00

6.07.

IBC

AFCEE IICS - Civil Work Specifications

1-10

General, Sample of Material and Works

01 33 23

6.02.

IBC

SEC 106

Construction Documents

AFCEE IICS - Civil Work Specifications

1-9, 1-10

Planning, Sample of Materials and Work

01 33 23

7.00.01

IBC

AFCEE IICS - Civil Work Specifications

1-10

General, Sample of Material and Works Electric water Storage Heaters General and Technical Specification of the Sanitary Work. Building Soil, Waste, Vent and Rain Water Pipe work. Scope of Work

01 35 26

2.7.5.1.5

IPC

Section 504.4 Chapter 6

Relief valve

01 41 00

2.4.1.3.4

IPC

Water Supply and Distribution Sanitary Drainage

01 41 00

2.5.3

Regulatory Requirements

IPC

Chapter 7

01 41 00

2.7.1

01 41 00

6.01.

The CONTRACTOR shall plan and construct domestic cold Regulatory Requirements water systems and the succeeding plumbing work in accordance with International Plumbing Code. The Contractor must adhere to the International Building Regulatory Requirements Code, International Electrical Code, International Mechanical Code, International Plumbing Code, International Fire Code and in any other standards specifically cited herein as applicable. The Contractor must provide copies of all specifications, calculations and manuals used. All calculations, standards and correspondence shall be in English

IPC

Chapter 6

Water Supply and Distribution

Iraq Ministry of Housing & Construction - Section 11.6 and 11.7 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 1 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 9.1 General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Section 3.2.1 Conditions and Specifications AFCEE IICS - Civil Work Specifications 1-7

IBC

Section 106 Construction Documents

General, Standard Specifications

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 23 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 01 43 13 Statement of Requirements (SOR) Section 2.7.3 Statement of Requirements Definition Construction Specifications Institute # Description Manufacturer Qualification Code Code # Code Description Iraqi Specification Iraqi Specification Number Specification Description

01 43 23

2.7.2.1

01 43 26

2.4.1.3.8

01 43 26

2.4.3

All materials and equipment shall be standard product of a manufacturer regularly engaged in the manufacture of the product and shall duplicate items that have been in satisfactory use for at least two (2) years prior to bid opening. The plumbing systems shall be executed by a plumbing specialist sub-contractor experienced in the plan and construction of these types of systems. After completion of a section of water supply pipe the Contractor shall provide a static pressure test of the system. Any leaks shall be repaired and the section shall be retested prior to backfilling the trench covering the pipe. After completion of a water section, the CONTRACTOR shall provide a static pressure test of the system. Any leaks shall be repaired and the section shall be retested. After completion of a section of sewer the Contractor shall provide a static pressure test of the system. Any leaks shall be repaired and the section shall be retested prior to backfilling of the trench. After completing the work, the Contractor shall demonstrate that all plumbing systems operate to fully satisfy the function for which these systems have been designed. Fully flush and sanitize system prior to final acceptance.

IPC

Section 303 Materials

AL-FAO GEC - General Technical Conditions and Specifications

Section 3.2.1.8 Scope of Work

Installer Qualifications

IPC

Section 106 Permits

Testing and Inspecting Agency Qualifications

IPC

Section 312 Tests and Inspections

Iraq Ministry of Housing & Construction - Section 2.1 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 2.3 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 2.3 General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications

General Requirements

Cold Water Systems

Testing and Inspecting Agency Qualifications Testing and Inspecting Agency Qualifications Testing and Inspecting Agency Qualifications Code Required Special Inspector Classifications

IPC

Section 312 Tests and Inspections

Cold Water Systems

01 43 26

2.5.6

IPC

Section 312 Tests and Inspections

Section 3.1.21 Testing Gravity Sewers and Manholes Cold Water Systems

01 43 26

2.7.7.1

IPC

Section 312 Tests and Inspections

Iraq Ministry of Housing & Construction - Section 2.3 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 2.2 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 2.3 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 2.3 General and Technical Specifications of the Sanitary Works N/A N/A AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications 4-1 to 4-5 1-7 1-7 1-10

01 43 29

2.7.7.3

IPC

Section 312 Tests and Inspections

Water Mains Test

01 45 23

2.7.7.2

01 45 23

2.7.7.4

Testing and Inspecting Services The Contractor shall include tests for interlocks, safety cutouts and other protective devices to demonstrate safe operation Pressures test all lines for leaks. Testing and Inspecting Services

IPC

Section 307 Structural Safety

Cold water Systems

IPC

Section 312 Tests and Inspections

Cold water Systems

01 45 33 01 45 33 01 45 33 01 45 33 01 78 23.19

5.3.01 5.3.02 5.3.03 5.3.04 5.1.

01 79 00

5.2.

02 01 80

2.00.03

Submit the following to the COR for review and approval: Code-Required Special Inspections and Procedures Construction Inspection Reports Code-Required Special Inspections and Procedures Testing and Inspection Reports Code-Required Special Inspections and Procedures Coordination Memoranda Code-Required Special Inspections and Procedures Preventive Maintenance Plan: The Contractor shall Preventive Maintenance Instruction prepare a Preventive Maintenance Plan and submit it to the COR for review and approval. This plan shall identify manufacturers information and recommendations for preventive maintenance on all new equipment installed under this contract. Training Manuals: The Contractor will be responsible for Demonstration and Training providing a minimum 3 hours of training on each (1) HVAC, (2) Electrical, (3) Generator, (4) Plumbing, and (5) Fire Alarm systems. The Contractor shall provide Training Manuals for the components of these systems in English and Arabic. Repair all walls, ceilings, overheads, and floors. Maintenance of Facility Remediation

IBC IBC IBC IBC IBC

N/A

Customer Requirement

N/A General, Planning the Site General, Planning the Site General, Planning the Site General, Sample of Material and Works

Section 1704 Special Inspection Section 1715 Material and Testing Standards Section 106 Construction Documents Section 106 Construction Documents

IBC

Section 106 Construction Documents

N/A

N/A

N/A

IBC

Section 3403 Additions, Alterations and Repairs

AFCEE IICS - Civil Work Specifications

2-1

General, Destruction of Establishments

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 24 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 02 01 80 Statement of Requirements (SOR) Section 2.00.05 Statement of Requirements Definition Construction Specifications Institute # Description Maintenance of Facility Remediation Code Code # Code Description Iraqi Specification Iraqi Specification Number 2-1 Specification Description General, Destruction of Establishments of of of of

02 01 80 02 01 80 02 01 80 02 01 80 02 01 80

2.00.06 2.00.07 2.00.08 2.00.09 2.00.10

Eliminate dropped ceilings except where absolutely necessary for chase development of enveloping equipment (Exception: Those areas where mandated by HVAC loads such as a DFAC). Repair all damage to exterior and interior walls. Seal all open cracks on interior and exterior walls. Repair all concrete awnings. Remove all loose materials and patch to match existing building surface. Repair any supporting structure as required. Clean and repair all tarred joints in the roofing slabs. Reseal all joints and make watertight. Test water tightness of roofing and wall openings. Enclose or fill in all existing openings in the walls, floors and ceilings with structurally stable material. All openings in the roof structure and exterior wall shall be made watertight. Completely remove all damaged floor tiles, ceiling tiles, window casements, doorframes, mechanical ductwork, straps, hangers, inserts, electrical boxes, and devices. Completely remove all debris, rubble, and trash in each building. Non-load bearing shall be reinforced with 15 cm x 15 cm 12 gauge wire mesh or larger. Reinforce slabs with 15 cm x 15 cm 12 gauge steel wire mesh or larger. A broom type finish is expected unless otherwise requested. A broom type finish is expected unless otherwise requested. All concrete shall have a minimum 28 day compressive strength of 21 MPa (3000 psi). Concrete shall have 21 MPa (3045 psi) as a specified minimum compressive strength in 28 days. The concrete shall be free from excessive voids or cracks when poured and be wetted sufficiently to avoid stress cracking due to excessive moisture loss. Provide test cylinders or cubes for every 20 cubic meter of concrete placed. All block and brick walls, both solid and hollow core shall be placed with mortar on all surfaces in contact with adjacent block or brick. Placing the mortar after the block is positioned in place is unacceptable. All food preparation and bathroom finished floors shall be of glazed ceramic tile finish. Where possible, eliminate parapets from building vertices. Consider steel trussed roofs vs. poured roofs where procurement and cost of steel permits. Remove and replace all damaged interior doors.

IBC

Section 3403 Additions, Alterations and Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Section 3403 Additions, Repairs Alterations and Alterations and Alterations and Alterations and Alterations and

AFCEE IICS - Civil Work Specifications

Maintenance of Facility Remediation Maintenance of Facility Remediation Maintenance of Facility Remediation Maintenance of Facility Remediation Maintenance of Facility Remediation

IBC IBC IBC IBC IBC

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications Iraq Building Code Requirements for Reinforced Concrete AFCEE IICS - Civil Work Specifications

General, Destruction Establishments 2-1 General, Destruction Establishments 2-1 General, Destruction Establishments 2-1 General, Destruction Establishments 4.5, 4.4.5 and Movement Joints, 4.4.6 Laitance removal 2-1

2-1

02 01 80

2.00.12

Maintenance of Facility Remediation

IBC

Section 3403 Additions, Alterations and Repairs Section 3303 Demolition

General, Destruction of Establishments General, Destruction of Establishments

02 41 16.13

2.00.02

Demolition, Building Demolition

IBC

AFCEE IICS - Civil Work Specifications

2-1

02 42 00 03 22 00

2.00.01 3.3.02

Removal and Salvage of Construction Material Welded Wire Fabric Reinforcing

IBC ASTM

03 22 00

7.1.02

Welded Wire Fabric Reinforcing

ASTM

03 25 36 03 25 36 03 31 00 03 39 00 03 39 00

3.3.03 7.1.03 7.1.01 2.7.4.8.2 7.1.04

Grooved Concrete Finish Grooved Concrete Finish Structural Concrete Concrete Curing Concrete Curing

IBC IBC IBC IBC IBC

Section 3403 Additions, Alterations and Repairs A 185-1 Specification for Steel Welded Reinforcement, Plain Concrete A 185-1 Specification for Steel Welded Reinforcement, Plain Concrete Section 804 Interior Floor Finish Section 804 Interior Floor Finish Section 1905 Concrete Quality, Mixing and Placing Tables Minimum Specified 1904.2.2(2) Compressive Strength Section 1905 Concrete Quality, Mixing and Placing Section 1903, 1905.6.2.3 Section 2103,2104 Specification for tests and Materials Masonry Construction Material

AFCEE IICS - Civil Work Specifications Iraq Building Code Requirements for Reinforced Concrete Iraq Building Code Requirements for Reinforced Concrete AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications Iraq Building Code Requirements for Reinforced Concrete Iraq Building Code Requirements for Reinforced Concrete Iraq Building Code Requirements for Reinforced Concrete Iraq Building Code Requirements for Reinforced Concrete AFCEE IICS - Civil Work Specifications

General, Destruction of Establishments 5.10.2,5.10.4 Shrinkage and Temperature Reinforcement 5.10.2,5.10.4 Shrinkage and Temperature Reinforcement N/A

2-1

2.1.6 (Table Grade of Concrete 2.1) 2.1.6 (Table Grade of Concrete 2.1) 2.3.3a, 3.2 to Exposure Conditions 3.4 2.2.5, 2.4.1 Proportioning of Concrete Mortar

03 39 00

7.1.05

Concrete Curing

IBC

04 20 00

3.3.05

Unit Masonry

IBC

Chapter 6

04 21 16 05 44 00

3.4.00.02 2.00.11

Ceramic Glazed Clay Masonry Cold Formed Metal Trusses

IBC IBC

Section 804 Interior Floor Finish Section 2308 Conventional Light Frame Construction Section 3403 Additions, Alterations and Repairs

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications

Chapter 12.13 Floors and surfaces

06 48 13

2.00.13

Interior Wood Door

IBC

AFCEE IICS - Civil Work Specifications

2-1

General, Destruction of Establishments

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 25 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 06 48 16 Statement of Requirements (SOR) Section 2.00.13.03 Statement of Requirements Definition Construction Specifications Institute # Description Wood Door Frames Code Code # Code Description Iraqi Specification Iraqi Specification Number Specification Description

07 72 23

2.3.9

Ensure all doorframes are flush with the wall and seams are sealed. Paint all interior doors and frames. Install wooden doors and door frames at all interior door locations. Vent system

IBC

Section 1008 Doors, Gates, Turnstiles

AFCEE IICS - Civil Work Specifications

Chapter 16.16 Doors and Windows

Relief Vents

IPC

07 72 23 07 95 00

2.7.4.10 3.3.04

Provide vent line between last p-trap inside building and Relief Vents locate away from all entrances for the building Expansion or control joints shall be placed in the concrete Expansion Control for a maximum slab size of approximately 3 m x 3 m. Place expansion or control joints in the concrete for a maximum slab size of 3 meters x 3 meters. All doors, frames, and hardware shall be commercial / institutional grade capable of withstanding heavy use. Main entrance door shall be steel and reinforced. All steel doors shall have steel frames. Remove and replace all damaged exterior doors with insulated steel doors and frames. All necessary hardware, including locks, will be included for all doors. Ensure all doorframes are flush with the wall and seams are sealed. Paint all interior doors and frames. Install wooden doors and door frames at all interior door locations. Install wooden doors and door frames at all interior door locations. Mechanical room doors shall not have glass but will have a grated vent. Provide tile base on all walls. Latrine and shower walls, from floor to ceiling, shall receive ceramic tile. Finished Flooring: All finished flooring shall be of terrazzo tile except for food preparation areas and bathroom floors. Paint all steel doors and frames with the same system as specified for metal above. Paint all interior doors and frames. Expansion Control Doors and Frames Metal Doors and Frames Metal Doors and Frames Metal Doors

IPC IBC

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Chapter 9 Vents AL-FAO GEC - General Technical Conditions and Specifications Section 1906 Formwork, Embedded Pipes Iraq Building Code Requirements for and Construction Joints Reinforced Concrete 1905.10.7 Construction Joints Iraq Building Code Requirements for Reinforced Concrete AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications

Chapter 9

Vents

Section 6

Pipe Work, Fittings and Installation Building Drainage Movement Joints

Section 3.2.3.13 4.5.1

07 95 00 08 10 00 08 11 00 08 11 00 08 13 00

7.1.07 2.00.13.10 2.00.13.07 2.00.13.08 2.00.13.01

IBC IBC IBC IBC IBC

4.5.1

Movement Joints

Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles

Chapter 16.16 Doors and Windows Chapter 16.16 Doors and Windows Chapter 16.16 Doors and Windows Chapter 16.16 Doors and Windows

08 14 00

2.00.13.02

Wood Doors

IBC

Section 1008 Doors, Gates, Turnstiles

AFCEE IICS - Civil Work Specifications

Chapter 16.16 Doors and Windows

08 14 00 08 91 26 09 30 00 09 30 13 09 66 13

2.00.13.05 2.00.13.06 2.3.22.1 2.3.22 3.4.00.01

Wood Doors Door Louvers Tiling Ceramic Tiling Portland Cement Terrazzo Flooring

IBC IBC IBC IBC IBC

Section 1008 Doors, Gates, Turnstiles Section 1008 Doors, Gates, Turnstiles Section Walls 1210.2 Section Showers 1210.3 Section 804 Interior Floor Finish

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications

Chapter 16.16 Doors and Windows Chapter 16.16 Doors and Windows Chapter 7 Chapter 11 Construction Works

Finishing of Walls and Ceilings Chapter 12.12 Floors and surfaces

09 91 13 09 91 23 10 21 16 10 26 19.16 21 20 00

2.00.13.09 2.00.13.04 2.3.22.3 2.3.23 3.2.

Exterior Painting Interior Painting

IBC IBC IPC IBC IBC

Section 805 Decorations and Trim Section 1008 Doors, Gates, Turnstiles Section 417 Showers Section Bathroom Accessories 2606.9 Section 906 Portable Fire Extinguishers

AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications Chapter 16.16 Doors and Windows Showers Showers Halon 1301 Cylinders

Shower units shall include a changing space and privacy Shower and Dressing Compartments enclosure. Latrine stalls shall receive a swinging door with barrel bolt Shower Doors closure. Fire Prevention: A minimum of one (1), 8 kg or greater, Fire Extinguishing Systems fire extinguisher per 100 square meters shall be provided. All fire extinguishers shall be mounted to the wall or placed in existing cabinets. Fire extinguishers shall be of the ABC type. Water heaters Carbon-Dioxide Fire-Extinguishing Systems Electric Domestic Water Heaters

21 21 00

3.2.01

IBC

Section 902 Carbon Dioxide [F] Extinguishing Systems Chapter 5 Water Heaters

22 33 00

2.7.5.1

IPC

AL-FAO GEC - General Technical Section Conditions and Specifications 3.2.11.8 AL-FAO GEC - General Technical Section Conditions and Specifications 3.2.11.8 41.1 Ministry of Higher Education and Scientific Research - Electrical Specifications Ministry of Higher Education and 41.1 Scientific Research - Electrical Specifications Iraq Ministry of Housing & Construction - Section 11.6 and 11.7 General and Technical Specifications of the Sanitary Works

Halon 1301 Cylinders

Electric water Storage Heaters

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 26 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 22 33 00 Statement of Requirements (SOR) Section 2.7.5.1.1 Statement of Requirements Definition Construction Specifications Institute # Description Code Code # Code Description Iraqi Specification Iraqi Specification Number - Section 11.2 Specification Description Cold and Hot Water Distribution Cold and Hot Water Distribution Cold and Hot Water Distribution Sanitary Fittings

The hot water shall be generated by electric water heater. Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

22 33 00

2.7.5.1.2

22 33 00

2.7.5.1.3

22 05 16

2.3.3

The unit shall be located inside a mechanical room, storage room, toilet/janitor room or similar type locked space. The unit shall be of the commercially available tank type having low or medium watt density electric heating elements. Fittings

Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

Electric Domestic Water Heaters

IPC

Chapter 5

Water Heaters

Expansion Fittings and Loops for Plumbing Hangers and Support for Plumbing Piping and Equipment Facility Drainage Piping Cleanouts 22 07 19 Plumbing Piping Insulation

IPC

Section 702.4

Fittings

22 05 29 22 05 75 22 07 19

2.3.4 2.5.12 2.3.14

Hangers Cleanouts will be provided at each building. Insulation shall be provided where required to control sweating of pipes. All hot water piping shall be insulated.

IPC IPC IPC

Table 308.5 Hanger Spacing Section 708 Cleanouts Section 607.2.1 Piping Insulation

22 07 19

2.7.1.1.4

Plumbing Piping Insulation

IPC

Section 607 Hot Water Supply System

22 11 00

2.4.

Water Supply & Distribution:

Facility Water Distribution

IPC

Chapter 6

Water Supply and Distribution Water Supply and Distribution Water Supply and Distribution

22 11 00

2.4.1.3.5

The Contractor shall provide a new water supply and distribution system as needed.

Facility Water Distribution

IPC

Chapter 6

22 11 13

2.3.11

22 11 13

2.3.15

Domestic and cold water shall be provided in the facilities Facility Water Distribution Piping to serve the water heater usage and plumbing fixtures provided for the facility. Domestic water shall be distributed by means of schedule Facility Water Distribution Piping 40 galvanized steel pipe or suitable high pressure PVC equivalent. Note: the contractor shall provide galvanized Schedule 40 plumbing for sinks, showers, and toilets. The CONTRACTOR shall repair and renovate the existing water supply and distribution system and provide a new water supply and distribution system where required. Piping Materials Facility Water Distribution Piping

IPC

Chapter 6

IPC

Section 605 Materials, Joints and Connections

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications

- Section 11.2

- Section 11.2

- Section 9.3

Section 3.2.4.3 Piping Section 3.2.11.12 Section 8 Pipe Cleanouts Thermal Insulation

Section 8

Thermal Insulation

Section 11

Section 1

- Section 11.1

Water Supply Main, Distribution, Service Pipes and Equipments General and Technical Specification of the Sanitary Work. Main Supply Distribution

Section 3.3.2 Service and Distribution Pipes.

22 11 13

2.4.1

IPC

Chapter 6

Water Supply and Distribution

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications

Section 1

General and Technical Specification of the Sanitary Work.

22 11 13

2.4.4

Facility Water Distribution Piping

IPC

22 11 13

2.7.1.1

Hot water systems

Facility Water Distribution Piping

IPC

Table 605.3, Piping Materials Table 605.4 and 605.5 Section 607 Hot Water Supply System

Section 3.1.10 Pipe work

22 11 13

2.7.1.1.1

22 11 13 22 11 13 22 11 13

2.7.1.1.2 2.7.1.1.3 2.7.4.1.1

Hot water shall be provided for the facility to supply 49C (120F) hot water to fixtures and outlets requiring hot water. Hot water of a higher temperature shall be provided only where required for special use or process. Hot water piping shall be routed parallel to the building lines and concealed within finished rooms. The CONTRACTOR will plan the overall water supply and distribution system for the base population.

Facility Water Distribution Piping

IPC

Section 607 Hot Water Supply System

Facility Water Distribution Piping Facility Water Distribution Piping Facility Water Distribution Piping

IPC IPC IPC

Water Supply and Distribution Chapter 6 Water Supply and Distribution Section 604 Design of Building Water Distribution System

Chapter 6

Iraq Ministry of Housing & Construction - Section 11.2 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 11.2 General and Technical Specifications of the Sanitary Works N/A N/A

Cold and Hot Water Distribution Cold and Hot Water Distribution N/A

AL-FAO GEC - General Technical Section 3.2.4.2 Piping Conditions and Specifications N/A N/A Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 27 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 22 11 13 Statement of Requirements (SOR) Section 2.7.4.1.2 Statement of Requirements Definition Construction Specifications Institute # Description Code Code # Code Description Iraqi Specification Iraqi Specification Number N/A N/A Specification Description

Provide water pressure of 1.5 bars to the highest point in Facility Water Distribution Piping each building. Booster Pumps Domestic Water Packaged Booster Pump Domestic Water Packaged Booster Pump Facility Sanitary Sewerage

IPC

Section 604 Design of Building Water Distribution System Section 606.5 Section 606.5.1 Chapter 7 Water Pressure Booster Systems Water Pressure Booster Systems Required Sanitary Drainage

22 11 23.13

2.7.5.2

IPC

22 11 23.13

2.7.5.2.1

22 13 00

2.7.1.2

In the event that the water distribution system is not sufficient to provide building pressure, then booster pumps with hydro-pneumatic tanks shall be installed. Sanitary waste system.

IPC

IPC

22 13 13 22 13 13

2.7.1.3 2.7.7.2

Drains All drainage piping shall be acid resistant

Sanitary Drains Facility Sanitary Sewers

IPC IPC

Section 412 Floor and Trench Drains Section 702 Materials

22 13 16

2.3.00.1

22 13 16

2.3.2

Renovate the existing and/or install a new and complete Sanitary Waste and Vent Piping building sanitary sewer system to include all piping, fittings, hangers, straps, flanges, traps, vents, drains and fixtures. Piping Sanitary Waste and Vent Piping

IPC

Section 701 General

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

- Section 11.5

Cold Water Service Boosting Plant Cold Water Service Boosting Plant Building Soil, Waste, Vent and Rain Water Pipe work. Floor Drains N/A

- Section 11.5

- Section 9.1

Section 3.2.11.15 N/A

Chapter 9

Building Drainage and Sanitary Fittings Building Drainage and Sanitary Fittings Pipe Work, Fittings and Installation Floor Drains Floor Drains Floor Drains

IPC

Section 702 Materials

22 13 16

2.7.1.4

Vent system

Sanitary Waste and Vent Piping

IPC

Chapter 9

Vents

22 13 19.13 22 13 19.13 22 13 19.13

2.3.7 2.7.4.9 2.7.4.9.1

Drains Floor or Shower Drain Cast iron construction with galvanized body, integral seepage pan, and adjustable perforated or slotted chromium plated bronze, nickel-bronze or nickel brass strainer consisting of a grate and threaded collar. Valves

Sanitary Drains Sanitary Drains Sanitary Drains

IPC IPC IPC

Section 412 Floor and Trench Drains Section 412 Floor and Trench Drains Section 412 Floor and Trench Drains

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

Chapter 9

Section 6

Section 3.2.11.15 Section 3.2.11.15 Section 3.2.11.15

22 13 19.33

2.3.6

Backwater Valves

IPC

Section 715 Backwater Valves

22 14 00

2.6.1

22 14 00

2.6.2

22 14 00

2.6.3

22 14 26.19 22 14 26.19

2.7.4.11 2.7.4.11.1

The CONTRACTOR shall conduct a complete site investigation and field check in order to fully research and document the existing site storm water management and drainage system. The CONTRACTOR shall map out all existing conditions. With this information, CONTRACTOR shall plan an overall comprehensive site storm water management and drainage plan. The CONTRACTOR shall incorporate the existing storm water management system, if applicable, into the new plan in order to ensure that the entire installation is provided with the most efficient drainage system available and that redundant work is not performed. Trench Drain Cast iron construction with galvanized body, integral seepage pan, and adjustable perforated or slotted chromium plated bronze, nickel-bronze, or nickel brass strainer consisting of a grate and threaded collar.

Facility Storm Drainage

IPC

Chapter 11 Storm Drainage

Iraq Ministry of Housing & Construction - Section 7.1 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 9.1 General and Technical Specifications of the Sanitary Works

Valves and Strainers

Building Soil, Waste, Vent and Rain Water Pipe work. Building Soil, Waste, Vent and Rain Water Pipe work.

Facility Storm Drainage

IBC

Section 1803 Excavation, Grading and Fill Iraq Ministry of Housing & Construction - Section 9.1 General and Technical Specifications of the Sanitary Works Chapter 11 Storm Drainage AL-FAO GEC - General Technical Conditions and Specifications

Facility Storm Drainage

IPC

Section 3.1.5 Existing Service

Facility Trench drains Facility Trench drains

IPC IPC

Section 412 Floor and Trench Drains Section 412 Floor and Trench Drains

AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

Section 3.2.11.15 Section 3.2.11.15

Floor Drains Floor Drains

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 28 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 22 15 00 Statement of Requirements (SOR) Section 2.7.6.1 Statement of Requirements Definition Construction Specifications Institute # Description General Service Packaged Air Compressors and Receivers Code Code # Code Description Iraqi Specification Iraqi Specification Number N/A Specification Description

Contractor shall plan and construct compressor air storage and distribution.

IPC

Chapter 12 Special Piping and Storage System Chapter 5 Water Heaters

22 33 00

2.3.16

The hot water shall be generated by electric water heaters Electric Domestic Water Heaters

IPC

22 34 30

2.7.5.1.4

Gas (natural or liquid propane) powered hot water Residential Gas Domestic Water Heaters generators shall be provided to satisfy large hot water requirements when economically justifiable and practical. Plumbing Fixtures Plumbing Fixtures Plumbing Fixtures Plumbing Fixtures

IPC

Section 502 Installation

N/A Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 11.2 General and Technical Specifications of the Sanitary Works N/A Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

Cold and Hot Water Distribution N/A

22 40 00 22 40 00

2.3.10 2.7.4.2

IPC IPC

Fixtures, Faucets and Fixture Fittings Section 402 Fixture Materials

Chapter 4

Section 3.2.11 Plumbing Fixtures - Section 9.3 Sanitary Fittings

22 41 13 22 41 13 22 41 16

2.7.4.2.1 2.7.4.2.1.1 2.7.4.3

Eastern Water Closet with flush tank assembly Enameled cast iron, recessed floor mounted. Lavatories

Residential Water Closets, Urinals and Bidets Residential Water Closets, Urinals and Bidets Residential Lavatories and Sinks

IPC IPC IPC

Section 420 Water Closets Section 402 Fixture Materials Section 416 Lavatories

Section 3.2.11 Plumbing Fixtures Section 3.2.11 Plumbing Fixtures - Section 9.3 Sanitary Fittings

22 41 16

2.7.4.3.1

22 41 16

2.7.4.4

Enameled cast iron, wall or counter mounted. Brass fittings provided for water supplies. In addition to lavatories, a combination foot and hand washing station will be provided. This should be a concrete trough assembly covered with ceramic tile. Mop Sink

Residential Lavatories and Sinks

IPC

Section 416 Lavatories

- Section 9.3

Sanitary Fittings

Residential Lavatories and Sinks

IPC

Section 427 Floor Sinks

- Section 9.3

Sanitary Fittings

22 41 16

2.7.4.4.1

22 41 16

2.7.4.7

Floor mounted enameled cast iron with copper alloy rim guard. Provide hot and cold-water valves with manual mixing. Faucet handles shall be copper alloy. Service Sink

Residential Lavatories and Sinks

IPC

Section 427 Floor Sinks

- Section 9.3

Sanitary Fittings

Residential Lavatories and Sinks

IPC

Section 418 Sinks

- Section 3.2.9 Service Sinks

22 41 16

2.7.4.7.1

22 41 23 22 41 23

2.7.4.5 2.7.4.5.1

Residential Showers Receptors and Basin Showerhead and faucet handles shall be copper alloy. Residential Showers Receptors and Provide for manual mixing with hot and cold-water valves. Basin Shower head riser pipe shall be schedule 40 galvanized steel. Install showers to include all piping, faucets, drains and concrete or tile work. Shower pan shall be lowered so all water on shower floor will run into the shower pan. Install Eastern style toilets and sinks (provision of concrete trough in barracks for the feet/hand wash/laundry). Include all piping and hardware to make the units functional. Faucets Residential Showers Receptors and Basin Residential Shower Receptors and Basin

Standard trap type, enameled cast iron. Service sinks provided in maintenance areas shall be metallic, and in battery rooms acid resistant. Shower

Residential Lavatories and Sinks

IPC

Section 418 Sinks

- Section 3.2.9 Service Sinks

IPC IPC

Section 417 Showers Section 424 Faucets and other Fixture Fittings Section 605 Materials Joints and Connections Section 417 Showers

Section 3.2.11.8 Section 3.2.11.8 N/A

Showers Showers

22 41 23

2.7.4.5.2

IPC

22 41 23

2.3.19

IPC

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

N/A

Section 3.2.11.8 Section 3.2.11.5

Showers

22 42 13

2.3.20

Commercial Water Closets, Urinals and Bidets Commercial Faucets Supplies, and Trim

IPC

Section 420 Water Closets

Eastern Water Closets

22 42 39

2.3.8

IPC

Section 424 Faucets and other Fixture Fittings

Iraq Ministry of Housing & Construction - Section 9.4 General and Technical Specifications of the Sanitary Works

Sanitary Fittings

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 29 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 22 45 13 Statement of Requirements (SOR) Section 2.7.4.6 Statement of Requirements Definition Construction Specifications Institute # Description Emergency Showers Code Code # Code Description Iraqi Specification Iraqi Specification Number N/A N/A Specification Description

Emergency Shower

IPC

Section 411 Emergency Showers and Eyewash Stations Section 411 Emergency Showers and Eyewash Stations N/A N/A

22 45 16

2.7.4.6.1

Eye Wash Assembly

Eyewash Equipment

IPC

22 45 33

2.7.4.6.2

Provide in Vehicle Maintenance Building and in other facilities where required.

Combination Emergency Fixtures

IPC

22 45 36

2.3.24

Hose connects with appropriate piping shall be provided in Hand-held Emergency Drench Hoses each latrine/shower facility. Compressed-Air Systems for Laboratory and Healthcare Facilities Compressed air system shall be capable of operation up to Compressed-Air Systems for Laboratory 1380 KPa (200 psig) maximum for 862 KPa (125 psig) and Healthcare Facilities normal units. High-pressure system (above 1380 KPa) shall be provided Compressed-Air Systems for Laboratory to supply compressed air to equipment where required. and Healthcare Facilities The air distribution system shall be provided with necessary regulator valves to maintain desired pressure. MECHANICAL WORK: Heating Ventilating Air Conditioning: Compressed-Air Systems for Laboratory and Healthcare Facilities HEATING, VENTILATING, AND AIRCONDITIONING (HVAC) HVAC Compressed Air Systems:

IPC

Section 424.4

Hose Connected Outlets

22 61 00 22 61 00

2.7.4.00.1 2.7.4.01.05

IMC IMC

Section 1003 Pressure Vessels Section 1003 Pressure Vessels

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works N/A N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A N/A

N/A N/A

22 61 00

2.7.4.01.06

IMC

Section 1003 Pressure Vessels

N/A

N/A

N/A

22 61 00

2.7.4.01.08

IMC

Section 1003 Pressure Vessels

N/A

N/A

N/A

23 00 00 23 00 00

2.8. 2.8.00.1

IMC IMC Chapter 4, 5, Ventilation, Exhaust 6, 11 Systems, Duct Systems, Refrigeration Section 308 Piping Support Iraq Ministry of Housing & Construction 4.2.14 Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction - Section 6.2 General and Technical Specifications of the Sanitary Works Chapter 13 Fuel Oil Piping and Storage N/A N/A Package Air Conditioner Unit Pipe Supports

23 05 29

2.3.5

Straps

Hangers and Support for Plumbing Piping and Equipment

IPC

23 10 00

2.7.6.3

23 11 13

2.3.12

23 11 13

2.4.2

Facility Fuel Systems Fuel-oil storage and distribution plumbing systems that are required for full performance of equipment and other operations in the Power Plant Water service to each facility shall enter the building in a Facility Water Distribution Piping mechanical, storage, or similar type space. Isolation valves shall be installed at each facility and to separate latrine/shower area. The CONTRACTOR shall inspect all existing underground Facility Water Distribution Piping water piping and manholes for damage and defects. The CONTRACTOR shall repair all damaged and defective underground water piping as necessary. Domestic water shall be distributed by means of standard Facility Water Distribution Piping weight (schedule 40) galvanized steel pipe that is installed underground with a minimum of 80cm coverage of compacted soil. Fuel oil storage and distribution Facility Fuel Storage Tanks Smaller battery rooms shall have waste treated using acid Double wall Steel, Underground Storage neutralizing tank. tanks Waste oil storage tanks shall be provided for collection of Double wall Steel, Underground Storage waste oil in the power plant tanks

IPC

N/A

IPC

Chapter 6

Water Supply and Distribution Water Supply and Distribution

Iraq Ministry of Housing & Construction - Section 11.1 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 2.1 General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications

Main Supply Distribution

IPC

Chapter 6

General Requirements

23 11 13

2.4.4.1

IPC

Table 605.3, Piping Materials Table 605.4 and 605.5

Section 3.1.10 Pipe work

23 13 00 23 13 13.13

2.7.1.6 2.7.7.3

IMC IPC

Chapter 13 Fuel Oil Piping and Storage N/A Chapter 8 Indirect/Special Waste Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works

N/A N/A

N/A N/A

23 13 13.13

2.7.7.4

IPC

Chapter 8

Indirect/Special Waste

N/A

N/A

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 30 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 23 13 13.23 Statement of Requirements (SOR) Section 2.7.7.5 Statement of Requirements Definition Construction Specifications Institute # Description Glass-Fiber Reinforced Plastic, Underground Fuel-Oil storage Tanks Sanitary Waste and Vent Piping Code Code # Code Description Iraqi Specification Iraqi Specification Number N/A Specification Description

Waste oil storage tank shall be underground double-wall fiberglass or double-wall steel. Waste lines from toilets will be a minimum of 100mm diameter and slope a minimum of 2%. Floor drains shall be provided in each room that contains a water source Piping,

IPC

Chapter 8

23 13 16

2.3.2.1

IPC

Section 704

23 13 19.13 23 23 00

2.3.7.1 2.8.01.06

Sanitary Drains Refrigerant Piping

IPC IMC

Section 412 Chapter 11

23 30 00

2.8.01.04

Air-handling units,

HVAC Air Distribution

IMC

Chapter 6

23 30 00

2.8.1

Exhaust and Ventilation:

HVAC Air Distribution

IMC

Chapter 4, 5

23 31 00

2.8.1.2.07.02

Ductwork,

HVAC Ducts and Casings

IMC

Chapter 6

23 32 00

2.8.01.10

Ductwork,

Air Duct Accessories

IMC

Chapter 6

23 32 00

2.8.01.11

Hangers,

Air Duct Accessories

IMC

Chapter 6

23 32 00

2.8.01.12

Straps,

Air Duct Accessories

IMC

Chapter 6

23 32 00

2.8.01.13

Fasteners,

Air Duct Accessories

IMC

Chapter 6

23 33 00

2.3.17

23 33 00

2.8.1.2.07.04

The storage unit shall be typically located inside the mechanical room, storage room, janitor room or similar type space. Interlock controls,

Electric Domestic Water Heaters

IPC

Section 501.4 Chapter 6

Air Duct Accessories

IMC

23 33 00

2.8.1.2.08.01

Ductwork,

Air Duct Accessories

IMC

Chapter 6

23 33 00

2.8.1.2.08.02

Exhaust grille,

Air Duct Accessories

IMC

Chapter 6

23 33 00

2.8.1.2.08.03

Interlock,

Air Duct Accessories

IMC

Section 603.6.2 Section [B]513.10.4 Chapter 4

23 33 13

2.8.1.2.02.02

Gravity dampers,

Dampers

IMC

23 34 00

2.8.00.01.01

Ventilation fans,

HVAC Fans

IMC

23 34 00

2.8.01.07

Exhaust fans,

HVAC Fans

IMC

Chapter 5

N/A Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Section Drainage Piping Installation AL-FAO General Engineering Company 3.2.3.12 General Technical Conditions and Specifications Section Floor and Trench Drains AL-FAO GEC - General Technical 3.2.11.15 Conditions and Specifications Refrigeration Iraq Ministry of Housing & Construction 4.2.18 h Technical Specification Book 4: Mechanical Works General Duct Systems Iraq Ministry of Housing & Construction 4.2.13 g Technical Specification Book 4: Mechanical Works General Ventilation and Exhaust Iraq Ministry of Housing & Construction 4.2.61 Systems Technical Specification Book 4: Mechanical Works General Duct Systems Iraq Ministry of Housing & Construction 4.2.40 Technical Specification Book 4: Mechanical Works General 4.2.40 Duct Systems Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Duct Systems Iraq Ministry of Housing & Construction 4.2.47 Technical Specification Book 4: Mechanical Works General 4.2.47 Duct Systems Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General 4.2.47 Duct Systems Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Location Iraq Ministry of Housing & Construction - Section 11.6 and 11.7 General and Technical Specifications of the Sanitary Works Duct Systems Iraq Ministry of Housing & Construction 4.2.41e Technical Specification Book 4: Mechanical Works General Duct Systems Iraq Ministry of Housing & Construction 4.2.40 Technical Specification Book 4: Mechanical Works General Duct Systems Iraq Ministry of Housing & Construction 4.2.52 Technical Specification Book 4: Mechanical Works General Flexible Air Connectors Iraq Ministry of Housing & Construction 4.2.41e Technical Specification Book 4: Mechanical Works General 4.2.61f Ventilation Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Ventilation Iraq Ministry of Housing & Construction 4.2.64 Technical Specification Book 4: Mechanical Works General Exhaust System Iraq Ministry of Housing & Construction 4.2.63 Technical Specification Book 4: Mechanical Works General Indirect/Special Waste

Drainage and Vent Pipes

Floor Drains Refrigerant pipe work

Evaporator and Condenser Fans Fans-Propeller Type (Wall Mounted) Low Velocity Ductwork

Low Velocity Ductwork

Connections to Ductwork Connections to Ductwork Connections to Ductwork Electric Storage Water Heater Flexible Connections

Low Velocity Ductwork

Fresh and Exhaust Air Louvers Flexible Connections

Dampers

Centrifugal Power Supply Fan Centrifugal Roof Exhauster

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 31 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 23 34 00 Statement of Requirements (SOR) Section 2.8.03.04 Statement of Requirements Definition Construction Specifications Institute # Description HVAC Fans Code Code # Code Description Iraqi Specification Iraqi Specification Number 4.2.61 Specification Description Fans-Propeller Type (Wall Mounted) Centrifugal Roof Exhauster Centrifugal Power Supply Fan Centrifugal Power Supply Fan

ceiling fans,

IMC

Section 503.2 Chapter 5

Exhaust System

23 34 00

2.8.03.06

Toilet exhaust systems,

HVAC Fans

IMC

Exhaust System

23 34 00

2.8.1.2.02

VENTILATION AND EXHAUST FANS:

HVAC Fans

IMC

Section 503 Ventilations rate in rooms

23 34 16

2.8.1.2.02.01

23 34 16

2.8.1.2.03

23 34 16

2.8.1.2.04

23 34 16

2.8.1.2.06

23 34 16

2.8.1.2.07

All fans used for ventilation and pressurization shall be selected for required performance and for minimum noise level. Unit mounted supply and exhaust fans shall be centrifugal forward curved, backward inclined, or airfoil fans with non-overloading characteristics of high efficiency and quiet running plan. Administrative Areas: 34 CMH/person (20 CFM/person) with air conditioning; 37 CMH/m2 (2 CFM/Ft2) of floor area. Toilet and Wash Areas: Exhaust ventilation at 37 CMH/m2 (2 CFM/Ft2) of floor area. Or 85 CMH/Water Closet or Urinal. Electrical/Mechanical rooms: Mechanical ventilation sufficient to limit space temperature and to remove heat given out by operating equipment, 37 CMH/M2. Maintenance Shops: Maintenance Shops and similar spaces that use solvents and oils shall be provided with mechanical exhaust air systems. The systems shall consist of centrifugal fan, ductwork, exhaust grille, and interlock controls. These type spaces shall not return exhaust air to any split system unit or ventilation system. Centrifugal fan,

Centrifugal HVAC Fans

IMC

Chapter 4

Ventilation

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General

4.2.63

4.2.64

4.2.64

Centrifugal HVAC Fans

IMC

[F]502.5.2 Ventilation rate in rooms

Centrifugal HVAC Fans

IMC

[F]502.5.2 Ventilation rate in rooms

Centrifugal HVAC Fans

IMC

[F]502.5.2 Ventilation rate in rooms

Centrifugal HVAC Fans

IMC

503

Motors and Fans

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General

4.2.64 b

Centrifugal Power Supply Fan/Capacity Centrifugal Power Supply Fan/Capacity Centrifugal Power Supply Fan/Capacity Centrifugal Roof Exhauster

4.2.64 b

4.2.64 b

4.2.63

23 34 16

2.8.1.2.07.01

Centrifugal HVAC Fans

IMC

Chapter 4

Ventilation

23 34 16

2.8.1.3.03

23 34 23

2.8.1.2.09

23 34 23

2.8.1.3.01

Centrifugal HVAC Fans All fans used for ventilation and pressurization shall be selected for required performance and for minimum noise level. Unit mounted supply and exhaust fans shall be centrifugal forward curved, backward inclined, or airfoil fans with non-overloading characteristics of high efficiency and quiet running plan. HVAC Power Ventilators Barracks: Air conditioning for officers and Senior NCO's only. Ceiling fans and adequate room ventilation for Junior NCO (jundis). Install ceiling fans in all rooms, with vibration mounts or HVAC Power Ventilators hook-type suspension. Central Diesel Generator Facility: Per the calculations of the plan ENGINEER and approval of the COR. The facility shall be provided with mechanical exhaust air systems. The system shall consist of centrifugal fan, Wall intakes, Special Exhaust Systems

IMC

[F]502.5.2 Ventilation rate in rooms

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General

4.2.64

Centrifugal Power Supply Fan Utility Exhaust Fan

4.2.66

IMC

[F]502.5.2 Ventilations rate in rooms

IMC

[F]502.5.2 Ventilations rate in rooms

23 35 00

2.8.1.2.08

IMC

502.1.1

Exhaust Location

Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works_General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General

4.2.61

Fans-Propeller Type (Wall Mounted) Fans-Propeller Type (Wall Mounted) Centrifugal Roof Exhauster Fresh air (Roof intakes)

4.2.61

4.2.63

23 37 00

2.8.1.2.01.03

Air Outlets and inlets

IMC

Chapter 4

Ventilation

4.2.52 b

23 37 13

2.8.01.08

Grills,

Diffusers, Registers, and Grilles

IMC

Section 603.17

Registers, grilles and diffusers

4.2.45

Supply Air Diffuser

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 32 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 23 81 43 Statement of Requirements (SOR) Section 2.8.04.02 Statement of Requirements Definition Construction Specifications Institute # Description Air-Source Unitary Heat Pumps Code Code # Code Description Iraqi Specification Iraqi Specification Number Specification Description Package Air Conditioner Unit Heaters

23 82 00

2.8.03

Heat pumps shall be of the window mounted type, manually operated and enclosed in a protective vandal proof steel cage and mounted out of high traffic areas. Ventilators and Heaters,

IMC

Convection Heating and Cooling Units

IMC

Specific appliances, fireplaces and solid fuel burning equipment Section 920 Heating and Cooling Load Calculations Section 312

Chapter 9

23 82 00

2.8.03.08

Air conditioners/heat pumps in all enlisted quarters,

Convection Heating and Cooling Units

IMC

23 82 16

2.8.01.05

Coils,

Air Coils

IMC

Chapter 11

23 82 23

2.8.02.01

The Contractor shall plan, supply, fabricate and install new Unit Ventilators ventilation system. The Contractor shall plan, supply, fabricate and install new Unit Heaters heating systems. Electric heaters, Unit Heaters

IMC

Chapter 4

23 82 39

2.8.02.02

IMC

Section 920

23 82 39

2.8.03.07

IMC

Section 920

23 83 00

2.8.03.01

Heating systems,

Radiant Heating Units

IMC

Section 920

23 83 13

2.8.03.02

Baseboard heaters,

Radiant Heating Electric Cables

IMC

Section 920

23 83 33

2.8.03.03

Resistance heaters in the A/C units may be substituted for Electric Radiant Heaters electric baseboard heaters, All water piping shall be routed parallel to the building lines. Lateral lines from the building to the sewer mains will slope at a minimum of 2%. Floor drains shall be provided in the mechanical equipment and toilet rooms as required. Floor drain shall be provided in each room that contains a water source. Floor drains shall be provided in the mechanical equipment and toilet room as required. Drains shall be located near urinals or toilet partitions in toilet rooms Electrical Work: High voltage and low voltage cable Facility Water Distribution Piping Sanitary Waste and Vent Piping Sanitary Drains Sanitary Drains

IMC

Section 920

24 11 13 24 13 16 24 13 19.13 24 13 19.13

2.3.13 2.3.2.2 2.3.7.2 2.3.18

IPC IPC IPC IPC

Chapter 6 Section 704 Section 412 Section 412

Iraq Ministry of Housing & Construction 4.2.14 Technical Specification Book 4: Mechanical Works General Iraq Ministry of Housing & Construction 4.2.14 i Technical Specification Book 4: Mechanical Works General Heating and Cooling Load Iraq Ministry of Housing & Construction 4.2.14 Calculations Technical Specification Book 4: Mechanical Works General Refrigeration Iraq Ministry of Housing & Construction 4.2.13 f Technical Specification Book 4: Mechanical Works General Ventilation Iraq Ministry of Housing & Construction 4.2.61 Technical Specification Book 4: Mechanical Works General Unit Heaters Iraq Ministry of Housing & Construction 4.2.14 i Technical Specification Book 4: Mechanical Works General 4.2.14 i Unit Heaters Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Unit Heaters Iraq Ministry of Housing & Construction 4.2.14 i Technical Specification Book 4: Mechanical Works General Unit Heaters Iraq Ministry of Housing & Construction 4.2.14 i Technical Specification Book 4: Mechanical Works General Unit Heaters Iraq Ministry of Housing & Construction 4.2.14 i Technical Specification Book 4: Mechanical Works General Section 3.2.4.2 Water Supply and AL-FAO GEC - General Technical Distribution Conditions and Specifications Drainage Piping Installation AL-FAO GEC - General Technical Section Conditions and Specifications 3.2.3.12 Floor and Trench Drains AL-FAO GEC - General Technical Section Conditions and Specifications 3.2.11.15 Floor and Trench Drains AL-FAO GEC - General Technical Section Conditions and Specifications 3.2.11.15 AL-FAO GEC - General Technical Conditions and Specifications Section 3.2.11.15 Section 3

Package Air Conditioner Unit Evaporator and Condenser coils Fans-Propeller Type (Wall Mounted) Heaters

Heaters

Heaters

Heaters

Heaters

Piping Drainage and Vent Pipes Floor Drains Floor Drains

25 13 19.13 26 00 00 26 05 13

2.3.7.3 2.2. 2.2.4.01 02

Sanitary Drains Electrical Medium-Voltage Cables

IPC NEC NEC

Section 412 Floor and Trench Drains

Floor Drains

N/A N/A Article 300 & Conductors for General AFCEE IICS - Electrical Services 310 Wiring and Wiring Methods Specifications Article 300 & Conductors for General AFCEE IICS - Electrical Services 310 Wiring and Wiring Methods Specifications Article 300 & Conductors for General AFCEE IICS - Electrical Services 310 Wiring and Wiring Methods Specifications Article 300 & Conductors for General AFCEE IICS - Electrical Services 310 Wiring and Wiring Methods Specifications

Cables and Wires

26 05 13.16

2.2.4.01 06

Conductors

Medium-Voltage, Single- and MultiConductor Low-Voltage Electrical Power Conductors and Cables Low-Voltage Electrical Power Conductors and Cables

NEC

Section 3.13

High Tension Cable

26 05 19

2.2.01

26 05 19

2.2.03

Renovate the existing and/or install a new and complete building electrical power and lighting system to include all wiring. Complete the interior and exterior electrical system with commercial/institutional grade wiring and fixtures using International Electric Code. This is to include tracing any existing electrical wires and/or providing new wiring.

NEC

Section 3

Cables and Wires

NEC

Section 3

Cables and Wires

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 33 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 26 05 19 Statement of Requirements (SOR) Section 2.2.06 02 Statement of Requirements Definition Construction Specifications Institute # Description Code Code # Code Description Iraqi Specification Iraqi Specification Number Specification Description

Each wire shall be numbered at the terminal points with a Low-Voltage Electrical Power permanent numbering system. Conductors and Cables Install electrical cable from the distribution panel to the main breakers in each building and tent. Connectors Low-Voltage Electrical Power Conductors and Cables Raceway and Boxes for Electrical Systems Raceway and Boxes for Electrical Systems

NEC

Article 200 Use and Identification of Grounded Conductors

AFCEE IICS - Electrical Services Specifications

26 05 19

2.2.2.06

NEC

Article 300 & Conductors for General AFCEE IICS - Electrical Services 310 Wiring and Wiring Methods Specifications N/A Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 342, Intermediate Metal AFCEE IICS - Electrical Services 344, 358, Conduit/Rigid Metal Specifications 353, 365 Conduit; Electrical Metallic Tubing; Rigid Nonmatallic Conduit; High Density Polyethylene Conduit; Electrical Nonmetalic Tubing Article 342/344 Intermediate Metal AFCEE IICS - Electrical Services Conduit/Rigid Metal Conduit Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 3.1.10 Identification of Cables & 3.7 & Cable Core Identification Section 3 Cables and Wires

26 05 33

2.2.01 06

NEC

26 05 33

2.2.01 07

Conduit

NEC

Section 3.1.5 Support and Fixing for Cable

26 05 33

2.2.06

The building electrical lines shall be in metal conduit for exposed installation. Cable trays The Contractor shall be responsible for trenching and laying underground cable at least 1 meter deep from the buildings to the main distribution panel, with a minimum of 90 cm depth. The contractor's plan shall provide continuous power through an underground or aerial electrical distribution system. Manholes

Raceway and Boxes for Electrical System Cable Trays for Electrical Systems Underground Ducts and Raceway for Electrical Systems Underground Ducts and Raceway for Electrical Systems Underground Ducts and Raceway for Electrical Systems Electrical Panel board Schedule Electrical Panel board Schedule Electrical Panel board Schedule Wiring Device Schedule

NEC

Section 3.1.5 Support and Fixing for Cable Section 3.12 & Heavy Duty Cable Tray 3.13.1 & Suspend Tray Section 3.1.11 Cables Laid Direct in the Ground Section 3.1.11 Cables Laid Direct in the Ground

26 05 36 26 05 43

2.2.06 01 2.2.05

NEC NEC

Article 392 Cable Trays Article 300 Underground Installation section 300.50 Article 300 Wiring Methods

26 05 43

2.2.4.01

NEC

26 05 43

2.2.4.01 03

NEC

26 06 20.16 26 06 20.16 26 06 20.16 26 06 20.26

2.2.01 01 2.2.03 07 2.2.03 08 2.2.01 10

Panels Main panels The contractor shall provide main distribution panel for the generator. Install lights in each room and at least four (4) electrical outlets. Minimum of one (1) outlet per wall that is 2m long or longer, space receptacles at 2m maximum spacing. Electrical outlets

NEC NEC NEC NEC

Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 408 Switchboards and Panel boards Article 408 Switchboards and Panel boards Article 408 Switchboards and Panel boards Article 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) Article 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation Article 110 Requirements for Electrical Installation

AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 2.4

Distribution Board

Section 2.1.1 Main L.V. Switchboard Section 2.1.1 Main L.V. Switchboard

26 06 20.26

2.2.03 05

Wiring Device Schedule

NEC

AFCEE IICS - Electrical Services Specifications N/A N/A AFCEE IICS - Electrical Services Specifications N/A AFCEE IICS - Electrical Services Specifications

Section 4.11

Socket Outlets

26 10 00 26 10 00 26 10 00 26 10 00 26 10 00

2.2.04 2.2.2 2.2.2.03 2.2.2.04 2.2.3

The completed system will be connected into the generated electrical power distribution system. Power Distribution The contractor shall plan and install a complete electrical distribution system for the area. The electrical system shall be connected to all buildings requiring electrical service. General

Medium-Voltage Electrical Distribution Medium-Voltage Electrical Distribution Medium-Voltage Electrical Distribution Medium-Voltage Electrical Distribution Medium-Voltage Electrical Distribution

NEC NEC NEC NEC NEC

Section 0

General Requirements

Section 0

General Requirements

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 34 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 26 10 00 26 10 13 Statement of Requirements (SOR) Section 2.8.2 2.2.3.01 01 Statement of Requirements Definition Construction Specifications Institute # Description Medium-Voltage Electrical Distribution Primary Unit Substation Code Code # Code Description Iraqi Specification Iraqi Specification Number Specification Description

Power Generation: The Electrical Power Generation Plant shall be designed as the primary power generation system. Therefore, provide redundant power generation with the largest generator out of service. It is the intent to utilize the national power grid as a redundant electrical supply in addition to the Electrical Power Generation Plant. Install switching panels, transformer and ring gears for each location to facilitate proper electrical distribution to each of the buildings. The electrical system shall complete with all required transformers. (400V to11KV step-up and local step-down transformer) In mechanical rooms, floor drains will be installed in such away to ensure positive slope to the drains, floor drains shall be provided to avoid running drain piping long distances above or over the floor. Switches Overloads Fuses Switches Outlets

NEC NEC

Article 110 Requirements for Electrical N/A Installation Article 490 Equipment Over 600Volts, AFCEE IICS - Electrical Services Nominal Specifications

Section 10

Standby Diesel Generator Set

26 12 00

2.2.2.05

Medium-Voltage Transformer

NEC

26 12 00

2.2.4.01 01

Meduim Voltage Transformers

NEC

26 13 19.13

2.3.7.4

Sanitary Drains

IPC

Article 450 Transformer and Transformer Vaults (Including secondary ties) Article 450 Transformer and Transformer Vaults (Including secondary ties) Section 412 Floor and Trench Drains

AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AL-FAO GEC - General Technical Conditions and Specifications AFCEE IICS - Electrical Services Specifications N/A AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 1.3

Power Transformer

Section 1.3

Power Transformer

Section 3.2.11.15 Section 2.3

Floor Drains

26 18 00 26 18 00 26 18 16 26 27 26 26 27 26

2.2.4.01 07 2.2.4.01 09 2.2.4.01 08 2.2.01 03 2.2.01.04

Medium-Voltage Circuit Protection Devices Medium-Voltage Circuit Protection Devices Medium-Voltage Fuses Wiring Devices Wiring Devices

NEC NEC NEC NEC NEC

Article 490 Equipment Over 600Volts, Nominal Article 430 Motors, Motor Circuits and Controllers Article 490 Equipment Over 600Volts, Nominal Article 404 Switches Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 404 Switches Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 240 Over current Protection Article 240 Over current Protection Article 700 Emergency System

Fused Switchgear and Isolators Fused Switchgear and Isolators Installation, Sockets and Switches Socket Outlets

Section 2.3 Section 4 Section 4.11

26 27 26

2.2.01 05

Junction boxes

Wiring Devices

NEC

26 27 26 26 27 26

2.2.03 01 2.2.4.01 04

Installation of all switches. Junction boxes

Wiring Devices Wiring Devices

NEC NEC

AFCEE IICS - Electrical Services Specifications N/A

Section 4

Installation, Sockets and Switches

26 28 16 26 28 16 26 36 23

2.2.01 02 2.2.03 06 2.2.3.01

Breakers Breakers

Enclosed Switches and Circuit Breakers Enclosed Switches and Circuit Breakers

NEC NEC NEC

26 50 00

2.2.1

The contractor shall provide connection of electrical Automatic Transfer Switch system into the existing Iraqi National local sub-station, if possible. The power connection shall be installed in combination with and through an automatic transfer switch to the Electrical Power Generation Plant Perimeter & Exterior Lights Lighting

AFCEE IICS - Electrical Services Specifications AFCEE IICS - Electrical Services Specifications N/A

Section 2.5 Section 2.5

Miniature and Molded Case Circuit Breakers Miniature and Molded Case Circuit Breakers

NEC

26 51 13

2.2.01 08

Fixtures

Interior Lighting Fixtures

NEC

AFCEE IICS - Electrical Services Article 410 Luminaries (lighting fixtures), Lamp holders and Specifications Lamps AFCEE IICS - Electrical Services Article 410 Luminaries (lighting fixtures), Lamp holders and Specifications Lamps

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 35 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 26 51 13 Statement of Requirements (SOR) Section 2.2.01 09 Statement of Requirements Definition Construction Specifications Institute # Description Code Code # Code Description Iraqi Specification Iraqi Specification Number Section 5.1 Specification Description Lighting Fixtures

26 51 13

2.2.02

Fluorescent lights shall be mounted on walls (near full wall Interior Lighting Fixtures height) vs. ceiling mounted. Steel conduit shall be exposed instead of embedded placement All outlets in bathrooms, kitchens, and other wet locations Interior Lighting Fixtures shall be waterproof type. Lights with cover Interior Lighting Fixtures

NEC

NEC

26 51 13

2.2.03 02

NEC

26 53 00

3.2.03

Install emergency exit signs, in Arabic with international symbols, over primary fire exit routes. The contractor shall provide appropriate security lighting to all building entries, exit ways, building perimeters (1 per corner), and courtyard areas. Exterior lighting system shall provide sufficient lighting in all areas commonly used at night in accordance with ground illumination requirements of the NEC Utilize area lights mounted on building exteriors vs. polemounted lighting wherever feasible. Street and Motor Pool Lighting System.

Exit Signs

IBC

Article 410 Luminaries (lighting fixtures), Lamp holders and Lamps Article 314 Outlet, Device, Pull and Junction Boxes: Conduit Bodies: Fittings and Manholes Article 410 luminaries (lighting fixtures), Lamp holders and Lamps Chapter 10 Means of Egress

AFCEE IICS - Electrical Services Specifications N/A

AFCEE IICS - Electrical Services Specifications

Section 5.1

Lighting Fixtures

26 55 53

2.2.1 01

Security Lighting

NEC

Article 410

26 56 00

2.2.1 02

Exterior Lighting

NEC

Article 410

26 56 00

2.2.1 03

Exterior Lighting

NEC

Article 410

26 56 00

2.2.5

Exterior Lighting

NEC

Article 410

26 56 00

2.2.5.01

The contractor shall conduct a complete site investigation Exterior Lighting and field check in order to fully research and document the existing electrical street and motor pool lighting system. The contractor shall map out all existing conditions. With this information, the contractor shall provide a complete plan illustrating all existing and proposed new work for the complete renovation of the installations street and motor pool lighting system. Construction shall not be started until the plan is approved. The contractor shall complete all work associated with the plan in order to provide a complete and comprehensive street and motor pool lighting system. Data Communications The contractor shall provide computer systems as an integral part of the infrastructure plan. For facilities traditionally earmarked for computer systems. The contractor shall develop provisions for LAN network Data Communications with consideration provided for Wireless Computer Networks. The contractor shall include the electrical outlets in hidden Data Communications but accessible locations to power the duct-node computer networks like those found in hotels and office buildings. Data Communication s Wireless Access The contractor shall develop provisions for Wireless Computer Networks; consider including electrical outlets Point in hidden but accessible locations to power the duct-node computer networks like those found in hotels and office buildings. Voice Communications The contractor shall provide a communications site infrastructure for telephone as integral part of the infrastructure plan.

NEC

Article 410

Ministry of Higher Education and Scientific Research - Electrical Specifications Luminaries (lighting AFCEE IICS - Electrical Services fixtures), Lamp holders and Specifications Lamps Luminaries (lighting AFCEE IICS - Electrical Services fixtures), Lamp holders and Specifications Lamps AFCEE IICS - Electrical Services Luminaries (lighting fixtures), Lamp holders and Specifications Lamps AFCEE IICS - Electrical Services Luminaries (lighting fixtures), Lamp holders and Specifications Lamps Luminaries (lighting AFCEE IICS - Electrical Services fixtures), Lamp holders and Specifications Lamps

N/A

N/A

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

Section 5.1

Lighting Fixtures

27 20 00

2.2.07 01

NEC

Article 800 Communications Circuits

N/A

27 20 00

2.2.07 02

NEC

Article 830 Communications Circuits

N/A

27 20 00

2.2.07 03

NEC

Article 800 Communications Circuits

N/A

27 21 33

6.04.

NES

N/A

N/A

N/A

27 30 00

2.2.07

NEC

Article 800 Communications Circuits

AFCEE IICS - Electrical Services Specifications

Section 7.1.2 Telephone System

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 36 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 28 31 00 Statement of Requirements (SOR) Section 3.2.1 Statement of Requirements Definition Construction Specifications Institute # Description Fire Detection and Alarm Code Code # Code Description Iraqi Specification Iraqi Specification Number Specification Description Fire Detection and Extinguishing System Smoke Detectors

Install commercial grade, hard wired electric and battery powered smoke alarms in all rooms and hallways. Install commercial grade, hard wired electric and battery powered smoke alarms in all rooms and hallways.

IBC

Chapter 9

Fire Protection Systems

28 31 46

3.2.02

Smoke Detection Sensors

IBC

[F]907.2.8.3 Smoke Alarms

31 05 16

2.4.1.3.3

31 22 00 31 22 00

2.6.4 2.6.6

Aggregate for earthwork Maximum size of aggregate should be not more than 8 millimeters per 100 millimeters (1 inch per foot) of pipe diameter, or 75 millimeters (3 inches) maximum. Selected aggregate shall consist of well-graded sand, gravel, crushed gravel, crushed stone. Grade all areas to provide a uniform sloping surface. Grading Areas around facilities shall be graded to slope away from Grading buildings and facilities in order to provide storm water drainage. Provide fill material as needed to raise grade elevations in Fill built up areas. Fill low areas, unused ditches, and holes. Pipe Bedding Backfill

IBC

Section J107.4

Fill Material

41 Ministry of Higher Education and Scientific Research - Electrical Specifications 41.6 Ministry of Higher Education and Scientific Research - Electrical Specifications Iraq Ministry of Housing & Construction - Section 10.5 General and Technical Specifications of the Sanitary Works

Backfilling of Trenches

IBC IBC

Section 1803 Excavation, Grading and Fill AL-FAO GEC - General Technical Conditions and Specifications Section 1803 Excavation, Grading and Fill AL-FAO GEC - General Technical Conditions and Specifications Section J107 Fill AL-FAO GEC - General Technical Conditions and Specifications

Section 3.1.3.3 Clearing and Grading of Site Section 3.2.1.4 Scope of Work

31 23 23

2.6.5

IBC

Section 3.1.3.3 Clearing and Grading of Site Bedding and Laying of Pipes Bedding and Laying of Pipes

31 23 23.13

2.4.1.3

IPC

Section 306 Trenching, Excavation and Backfill Section 306 Trenching, Excavation and Backfill

31 23 23.13

2.4.1.3.1

32 01 19.61 32 11 16

2.3.22.2 7.1.06

Backfill The CONTRACTOR will ensure that the following criteria are met when planning and installing the new, and renovating the existing underground water supply and distribution system: CONTRACTOR shall provide bedding material to level out any irregularities. All the joints shall be grouted and sealed to prevent water Sealing of Joints in Rigid Paving migration into the walls. Compact soils on foundation to 95% maximum density Sub base Course determined by the Standard Proctor Method, ASTM D 698 before concrete is poured. Compaction shall attain 95 percent maximum density for cohesionless soils, and 90 percent maximum density for cohesive soils. This is based on a Standard Proctor, ASTM D698. Soil fill shall be compacted to 90% of the maximum density in unpaved areas and 95% maximum density in paved areas determined by the Standard Proctor Method, ASTM D 698. Minimum extent of grading shall be 300 meters from any facility. Perimeter Wall: At each base the ECP shall meet Coalition Force Protection Standards for vehicle and personnel entrance. Provide new guard towers and security fencing as required. Contractor is to coordinate with the MITT team on site in order to meet the location requirements. Guard towers shall be spaced no more than 300 meters apart Weatherproof louvers with a bird screen, Compaction

IPC

Iraq Ministry of Housing & Construction - Section 10.3 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 10.3 General and Technical Specifications of the Sanitary Works AFCEE IICS - Civil Work Specifications AFCEE IICS - Civil Work Specifications Chapter 11

IPC IBC

Section 705 Joints J107.5 Compaction

32 23 23.23

2.4.1.3.2

IBC

Section J107.5 Section J107.5

Compaction

AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

Finishing of Walls and Ceilings 6-2, 6-3 Chapter 2, Digging Lengthened trenches for general services. Compaction) Section 3.1.8 Backfilling of Trenches

32 23 23.23

2.6.8

Compaction

IBC

Compaction

Section 3.1.8 Backfilling of Trenches

32 31 00

2.1.

Fences and Gates

CFPS

Customer Customer Requirement requirement

AFCEE IICS - Civil Work Specifications

3-4

General, Fencing the Site

32 35 13

2.8.1.2.01.02

Screens and Louvers

IMC

33 01 30.16 33 01 30.71

2.4.1.3.6 2.4.1.3.7

The Contractor shall inspect all existing underground water piping for defects. The Contractor shall repair all damaged and defective underground water piping as necessary.

TV Inspection of Sewer Pipelines Rehabilitation of Sewer Utilities

IPC IPC

Outdoor opening protection Iraq Ministry of Housing & Construction Technical Specification Book 4: Mechanical Works General Section 312 Tests and Inspections AL-FAO GEC - General Technical Conditions and Specifications Section Existing Building Sewers AL-FAO GEC - General Technical 703.4 and drains Conditions and Specifications

Section 401.6

4.2.62 e

Bird Screen

Section 3.1.5 Existing Service Section 3.1.5 Existing Service

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 37 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 33 06 10 Statement of Requirements (SOR) Section 2.4.1.3.9 Statement of Requirements Definition Construction Specifications Institute # Description Schedules for Water Utilities Code Code # Code Description Iraqi Specification Iraqi Specification Number Specification Description

33 06 30

2.5.7

33 06 30

2.5.8

33 06 30

2.5.9

33 12 16

2.4.1.2.7

33 32 13

2.5.2

The Contractor will plan the overall water supply and distribution system for the base population which will vary with each facility. The Contractor will plan the overall sanitary sewer collection system for the base population with a requirement rate of 300 liters per person per day and the wastewater treatment plant at 200 liters per person per day. The Contractor shall complete all work in order to provide a complete and comprehensive sanitary sewer collection system. The Contractor is responsible for all planning and construction aspects for a complete sanitary sewer collection system. Pipe shall be installed from the holding tanks to the facility exterior to allow removal of product without entering the compound. Service connections to individual building connections requiring water service shall be 1.5 meters outside each building, and shall have an isolation valve in a separate service box with accessible actuator. All sewerage lift stations are to be fenced and accessible only to Contractor tasked with maintenance of the WWCS Fabricate and install covers or access hatches at all manholes, and electric hand holes. Cisterns

IPC

Section 604 Design of Building Water Distribution System Section 710 Drainage System Sizing

Schedules for Sanitary Sewerage Utilities

IPC

Iraq Ministry of Housing & Construction - Section 2.1 General Requirements General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Section 3.1.1 General Notes Conditions and Specifications

Schedules for Sanitary Sewerage Utilities Schedules for Sanitary Sewerage Utilities

IPC

Chapter 7

Sanitary Drainage

IPC

Chapter 7

Sanitary Drainage

Iraq Ministry of Housing & Construction - Section 9.1 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 9.1 General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications N/A

Building Soil, Waste, Vent and Rain Water Pipe work. Building Soil, Waste, Vent and Rain Water Pipe work.

Water Utility Distribution Valves

IPC

Section 606 Installation of Building Water Distribution System Section 701.4 Section 708.3.6 Section 606.5.3 Sewage Treatment

Section 3.1.28 Valves and Fittings

Packaged Sewage Lift Stations

IPC

N/A

N/A

33 39 13 33 39 13

2.4.1.2.2 2.4.1.2.3

Sanitary Utility Sewerage Manholes, Frames and Covers Sanitary Utility Sewerage Manholes, Frames and Covers

IPC IPC

Manholes Covers

33 39 13 33 39 13 33 39 13

2.4.1.2.4 2.4.1.2.5 2.4.1.2.6

Sanitary sewer and water system valve manhole covers shall be round cast iron. Recess and grout all concrete manhole caps.

33 47 26

2.6.7

Sanitary Utility Sewerage Manholes, Frames and Covers Sanitary Utility Sewerage Manholes, Frames and Covers Add fill dirt to within 2 centimeters on the top of concrete Sanitary Utility Sewerage Manholes, manhole cap and grade to slope away from manhole. Add Frames and Covers fill dirt to cover an area of 2 meters around all sides of manhole. Provide storm water management basins or pond areas Storm Water Drainage Reservoir away from developed areas for storm water detention.

IPC IBC IBC

Section Manholes 708.3.6 Section Concrete Masonry 2105.2.2.1.2 Section Fill Material J107.4 Chapter 11 Storm Drainage

AL-FAO GEC - General Technical Conditions and Specifications Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications AL-FAO GEC - General Technical Conditions and Specifications

Section 3.1.23 Manholes - Section 11.3 Cold Water Storage Tanks

Section 3.1.23 Manholes Section 3.1.23 Manholes Section 3.1.23 Manholes

IPC

34 06 10

2.4.1.3.10

Water supply mains sizes shall be calculated according to Schedules for Water Utilities maximum daily future flows. Compressed air shall be provided using a packaged aircooled electric motor driven compressor Provide an engine driven air compressor where needed for operation during electrical power outages. Waste or hazardous drainage from battery repair/charging areas shall be treated prior to entering the sites general waste drainage system. The Contractor shall plan and construct a gravity waste water collection and treatment system. The Contractor shall plan for a gravity sanitary sewer system. Where gravity flow is not practical, the system shall consist of a series of holding tanks. The holding tanks will not be placed at or in front of any entrance. Gas Compressors Piston Gas Compressors Packaged Water Treatment Plant

IPC

Section 604 Design of Building Water Distribution System Section 1003 Pressure Vessels Section 1003 Pressure Vessels Chapter 8 Indirect/Special Waste

43 12 00 43 12 16 44 41 13

2.7.4.01.01 2.7.4.01.07 2.7.7.1

IMC IMC IPC

Iraq Ministry of Housing & Construction - Section 10.5 General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction - Section 11.1 General and Technical Specifications of the Sanitary Works N/A N/A N/A N/A

Backfilling of Trenches

Main Supply Distribution

N/A N/A Manholes, Inspection Chambers and Gullies N/A Drainage Pump Stations

44 41 13 44 41 13

2.5.1 2.5.4

Packaged Water Treatment Plant Packaged Water Treatment Plant

IPC IPC

Section Sewage Treatment 701.4 Section 712 Sumps and Ejectors

Iraq Ministry of Housing & Construction - Section 10.6 General and Technical Specifications of the Sanitary Works N/A N/A Iraq Ministry of Housing & Construction - Section 9.2 General and Technical Specifications of the Sanitary Works

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 38 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # 44 41 13 Statement of Requirements (SOR) Section 2.5.5 Statement of Requirements Definition Construction Specifications Institute # Description Code Code # Code Description Iraqi Specification Iraqi Specification Number N/A N/A Specification Description

44 42 49

2.7.1.5

Packaged Water Treatment Plant The Contractor shall plan for a non-mechanical waste water treatment plant where practical, if gravity sewer to the Municipal facilities is not available. Waste oil collection and storage. Water Treatment Oil/Grease Interceptors Grease Interceptor Water Treatment Oil/Grease Interceptors Water Treatment Oil/Grease Interceptors Water Treatment Equipment

IPC

Section 701.4

Sewage Treatment

N/A

IPC

44 42 49

2.7.4.8

IPC

44 42 49

2.7.4.8.1

Steel construction, manual cleaning type with removable checker-plate cover, complete with flow control valve. Sewage Treatment Facility

IPC

Section 1003 Interceptors and Separators Iraq Ministry of Housing & Construction - Section 10.6 General and Technical Specifications of the Sanitary Works Section 1003 Interceptors and Separators Iraq Ministry of Housing & Construction - Section 10.6 General and Technical Specifications of the Sanitary Works Section 1003 Interceptors and Separators

Manholes, Inspection Chambers and Gullies Manholes, Inspection Chambers and Gullies

44 42 00

2.7.6.4

IPC

44 42 49

2.7.6.2

Waste-oil collection and storage

Water Treatment Oil/Grease Interceptors Customer Requirement N/A N/A

IPC

N/A N/A N/A

2.00.04 2.2.03 03 2.2.2.01

N/A

2.2.2.02

N/A N/A N/A

2.2.4 2.2.4.01 05 2.3.7.5

Eliminate ceiling tile except where absolutely necessary Ceiling fans The Contractor shall provide the electrical power distribution system in accordance with the International Building Code Electrical Standards. The Contractor shall provide for the connection of electrical system into the existing Iraqi National local substation, if possible. Criteria Connectors Install p-traps at all applicable locations

N/A NEC NEC

Iraq Ministry of Housing & Construction - Section 10.6 General and Technical Specifications of the Sanitary Works Section 1003 Interceptors and Separators Iraq Ministry of Housing & Construction - Section 10.6 General and Technical Specifications of the Sanitary Works N/A Customer Requirement Article 422 Appliance N/A Article 110 Requirements for Electrical AFCEE IICS - Electrical Services Section 0 Installation Specifications Section 701.4 Sewage Treatment Article 110 Requirements for Electrical AFCEE IICS - Electrical Services Installation Specifications N/A N/A Article 490 Equipment Over 600Volts, Nominal Section 1002 Trap Requirements N/A N/A Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works N/A N/A N/A - Section 9.3 Section 1.1

Manholes, Inspection Chambers and Gullies Manholes, Inspection Chambers and Gullies

General Requirements

N/A

NEC

Installation of Internal Electrical Services

N/A N/A N/A

N/A NEC IPC

Sanitary Fittings

N/A

2.3.20.1

Provide foot wash stations in all places where there are showers

N/A

NA

N/A

N/A

N/A

N/A

N/A

2.3.21

Provide sanitary sprayer and hose assembly at each toilet. N/A

IPC

Section 424.4 Chapter 6

Hose Connected Outlets

N/A

N/A

N/A

2.4.1.2.1

N/A N/A N/A N/A N/A N/A

2.7.4.01.02 2.7.4.01.03 2.7.4.01.04 2.7.4.1 2.7.4.2.1.2 2.7.4.3.2

The main headers leaving the primary water pumping plant shall be at least two (2) pipe sizes oversized and have blind flanges located at tees near both the ends of future expansion zones. ASME rated receiver air cooler moisture separator to remove moisture and oil. Criteria Install p-traps at all water closet locations. Install p-traps at all sink locations.

N/A

IPC

Water Supply and Distribution

- Section 11.1

Main Supply Distribution

N/A N/A N/A N/A N/A N/A

IMC IMC IMC IPC IPC IPC

Section 1003 Pressure Vessels Section 1003 Pressure Vessels Section 1003 Pressure Vessels Section 604 Design of Building Water Distribution System Section 1002 Trap Requirements Section 1002 Trap Requirements

N/A N/A N/A

N/A N/A N/A

AL-FAO GEC - General Technical Section 3.2.11 Plumbing Fixtures Conditions and Specifications Iraq Ministry of Housing & Construction - Section 9.3 Sanitary Fittings General and Technical Specifications of the Sanitary Works

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 39 of 40

Versar 2006 and VIAP 2006 . This is a proprietary VIAP document. Any unauthorized use, distribution or copying is prohibited.

AFCEE Iraq Construction Guide Specifications


Requirements Sorted by CSI
Construction Specifications Institute (CSI) # N/A Statement of Requirements (SOR) Section 2.7.4.4.2 Statement of Requirements Definition Construction Specifications Institute # Description N/A Code Code # Code Description Iraqi Specification Iraqi Specification Number - Section 9.3 Specification Description Sanitary Fittings

Install p-traps at all sink locations

IPC

Section 1002 Trap Requirements

N/A

2.7.4.7.2

Install p-traps at all sink locations

N/A

IPC

Section 1002 Trap Requirements

N/A

2.7.4.9.2

Install p-traps at all drain locations

N/A

IPC

Section 1002 Trap Requirements

N/A

2.7.4.12

Hose Bibs

N/A

IPC

Section Hose Connections 608.15.4.2 Section Hose Connections 608.15.4.2 Section 606.4 N/A N/A Valve Identification

N/A

2.7.4.12.1

Provide steel taps vs. hose bibs in latrines

N/A

IPC

N/A

2.7.4.12.2

Room hose bibs shall be provided as required

N/A

IPC

N/A N/A

4.01. 6.03.

N/A N/A

6.06. 7.00.02

The project includes all structures, buildings and systems as required for the installation. Follow "single manufacturer" premise for generators, pumps, valves, compressors, electrical components, etc. where possible for utility plants and critical infrastructure elements (WTPs, WWTPs, Power Plants, etc.) Explore opportunities to make manhole covers inaccessible to vehicle traffic or protect with bollards. All buildings will be planned, designed, renovated, or constructed according to requirements and specifications. Iraqi standards or any other acceptable standards shall be implemented. Eastern and Western-style fixtures will be required and installed where indicated on construction drawings.

N/A Customer Requirement

N/A N/A

N/A Customer Requirement

Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works Iraq Ministry of Housing & Construction General and Technical Specifications of the Sanitary Works N/A

- Section 9.3

Sanitary Fittings

- Section 9.3

Sanitary Fittings

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Customer Requirement Customer Requirement

N/A N/A

N/A N/A

Customer Requirement Customer Requirement

N/A AFCEE IICS - Civil Work Specifications

N/A 1-7

N/A Standard Specifications

IBC, IEC,IPC,IMC,NES, NEC and ASTM are all registered and copyrighted material.

Page 40 of 40