Floor Mounted
SAP- FTR129E
Ceiling Mounted
WARNING
This symbol refers to a hazard or unsafe practice which can result When installing...
in severe personal injury or death. ... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.
SPECIAL PRECAUTIONS
When connecting refrigerant tubing
• During installation, connect before the refrigerant system and • Keep all tubing runs as short as possible.
then the wiring one; proceed in the reverse orden when removing • Use the flare method for connecting tubing.
the units. • Apply refrigerant lubricant to the matching surfaces of the flare
and union tubes before connecting them; screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.
WARNING When wiring • Check carefully for leaks before starting the test run.
• Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked, to ensure the grounding. When servicing
• Highly dangerous electrical voltages are used in this system. • Turn the power OFF at the main power board before opening
Carefully refer to the wiring diagram and these instructions when the unit to check or repair electrical parts and wiring.
wiring. • Keep your fingers and clothing away from any moving parts.
Improper connections and inadequate grounding can cause • Clean up the site after the work, remembering to check that no
accidental injury and death. metal scraps or bits of wiring have been left inside the unit being
serviced.
• Ventilate the room during the installation or testng the refrigeration
system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.
2
Table of Contents
Page
1. SPECIFICATIONS 4
1-1 Unit specifications 4
1-2 Major Component specifications 6
1-3 Other Component specifications 8
2. DIMENSIONAL DATA 9
3. PERFORMANCE DATA 11
3-1 Air Throw Distance Chart 11
4. ELECTRICAL DATA 12
4-1 Electric Wiring Diagrams 12
5. FUNCTION 13
5-1 Room Temperature Control 13
5-2 Dry Operation (Dehumidification) 14
5-3 Freeze Prevention (Cooling and Dry) 15
6. TROUBLESHOOTING 16
6-1 Check before and after troubleshooting 16
6-2 Air conditioner does not operate 17
6-3 Some part of air conditioner does not operate 21
6-4 Air conditioner operates, but abnormalities are observed 23
6-5 If a sensor is defective 24
8. MAINTENANCE 27
8-1 Changing Address of Remote Control Unit in Indoor Unit 27
3
1. SPECIFICATIONS
1-1 Unit Specifications
SAP- FR99E
Performance
Capacity See catalogue with the requested matching
Air circulation High m³/h 400
Features
Controls/Temperature controls Microprocessor/ I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & Daily program, 1-hour OFF
Fan speed 3 and Auto /1(Hi)
Airflow direction Horizontal Manual
Vertical Manual
Air Filter Washable, Anti-Mold
Operation Sound High dB(A) 51
Refrigerant tubing connections Flare type
Refrigerant Narrow tube mm(in.) 6,35 (1/4)
tube diameter Wide tube mm(in.) 9,52 (3/8)
Refrigerant R407C
Refrigerant tube kit / Air clean filter Optional / Optional
4
SAP- FTR129E
Performance
Capacity See catalogue with the requested matching
Air circulation High m³/h 700
Features
Controls/Temperature controls Microprocessor/ I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & Daily program, 1-hour OFF
Fan speed 3 and Auto /1(Hi)
Airflow direction Horizontal Manual
Vertical Auto
Air Filter Washable, Anti-Mold
Operation Sound High dB(A) 55
Refrigerant tubing connections Flare type
Refrigerant Narrow tube mm(in.) 6,35 (1/4)
tube diameter Wide tube mm(in.) 12,7 (1/2)
Refrigerant R407C
Refrigerant tube kit / Air clean filter Optional / Optional
5
1-2 Major Component Specifications
SAP- FR99E
Controller PCB
Part No. XR99/129E
Controls Microprocessor
Control circuit fuse 250 V - 3,15 A
6
SAP- FTR129E
Controller PCB
Part No. XR99/129E
Controls Microprocessor
Control circuit fuse 250 V - 3,15 A
Flap Motor
Type Synchro motor
Model M2LJ24ZE31
Rating AC 208/230 V ; 50-60 Hz
No. of poles…rpm 8…2,5÷3
Nominal output W 2,5÷3
Coil resistance (Ambient temp. 25 °C ) κΩ 16,45±15%
7
1-3 Other Component Specifications SAP- FR99E
SAP- FTR129E
8
2. DIMENSIONAL DATA
SAP- FR99E
Unit: mm
9
SAP- FTR129E
Unit: mm
Unit: mm
10
3. PERFORMANCE DATA
3-1 Air Throw Distance Chart
SAP- FTR129E
11
4. ELECTRICAL DATA
4-1 Electric Wiring Diagrams
12
5. FUNCTION
5-1. Room Temperature Control
■ Cooling
● Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
● The room temperature (and other information) is transmitted every 5 minutes by the remote control unit to the
controller in the indoor unit.
More than
5 minutes 5 minutes 3 minutes Room temp.
● The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least
3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant
pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
● As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor
operation.
● Thermo. ON : When the room temperature is above T + 1°C (T°C is set temperature).
Compressor ➞ ON
● Thermo. OFF : When the room temperature is equal to or below set temperature T°C.
Compressor ➞ OFF
13
5-2. Dry Operation (Dehumidification)
● Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to
dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON
and OFF automatically as shown in the chart below according to the room temperature.
Room temp.
Cooling operation
T+2 °C
*Dry A zone
Compressor : Continuous operation
FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation
Set temp. T °C
only while the compressor is ON.
T–1 °C
*Dry B zone
Compressor : Intermittent operation (ON for 3 minutes and OFF for 9 minutes)
FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
Room temp. 15 °C
Monitor zone
Both the indoor and outdoor units stop.
NOTE
● Intermittent ventilation occurs by switching the indoor fan speed between L ↔ LL.
● Dry operation does not occur when the room temperature is under 15°C, which is the monitor zone.
● When the compressor stops, the indoor fan stops as well.
14
5-3. Freeze Prevention (Cooling and Dry)
● This function prevents freezing of the indoor heat exchange coil.
● When the compressor has been running for 6 minutes or more and the temperature of the indoor heat exchange
coil falls below 2.4°C, the control circuit stops the compressor for at least 6 minutes. The compressor does not
start again until the temperature rises above 8°C or 6 minutes has elapsed.
Thermo. OFF
Room temp. Thermo. ON
T+1 ° C
Set temp. T ° C
More than
Indoor heat exch. 6 minutes 6 minutes
coil temp.
2.4 ° C
More than More than
6 minutes 6 minutes
15
6. TROUBLESHOOTING
6-1. Check before and after troubleshooting
WARNING
6-1-4. Check lead wires and connectors in indoor and outdoor units.
● Check that coating of lead wires is not damaged.
● Check that lead wires and connectors are firmly connected.
● Check that wiring is correct.
16
6-2. Air conditioner does not operate.
6-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
● There is a possibility of ground fault.
● Check insulation resistance.
WARNING
17
B. Circuit breaker trips in several minutes after turning the air conditioner on.
● There is a possibility of short circuit.
Circuit breaker
is tripped. Reset breaker.
• Check power supply.
NO
Power is being supplied to the
indoor unit. Wait for recovery
Power failure or contact power
company.
NO
18
C. Check remote control unit.
OK
• Check fuse on indoor PCB Ass'y If fuse has been blown, • Measure resistance of indoor and
for continuity. (F) outdoor fan motor winding.
(FM)
OK OK
Light is OFF OK
OK
19
6-2-3. Only outdoor unit does not run.
NO
OK
20
6-3. Some part of air conditioner does not operate.
6-3-1. Only indoor fan does not run.
OK
21
6-3-4. Only compressor does not run.
YES
YES
YES
Refrigerant gas shortage. Charge refrigerant gas (R22).
NO
22
6-4. Air conditioner operates, but abnormalities are observed.
6-4-1. Poor cooling.
• Wide and narrow tubes between NO Insulate both wide and narrow
indoor unit and outdoor unit are tubes separately and then
insulated. tape together.
YES
Temperature
difference
• Measure temperature of suction and is small. Possibility of Charge refrigerant
discharge air of air conditioner. gas shortage. gas.
Reduce cooling
• Review cooling load estimate, load or replace the air
if performance of air conditioner is conditioner with larger
normal. capacity.
23
6-5. If a sensor is defective.
6-5-1. Thermistor (TH1 or TH2) is defective.
• Operation lamp on front side of YES • Indoor coil thermistor (TH1 ) or room
indoor unit is flashing on and off. (*) air thermistor (TH2 ) is defective.
YES
24
7. CHECKING ELECTRICAL COMPONENTS
7-1. Measurement of Insulation power plug
(Local supply)
Resistance
● The insulation is in good condition if the resistance Ground
exceeds 2MΩ.
probe
Copper Insulation
7-1-3. Outdoor Unit tube or tester
metallic part
Fig. 2
Clamp an aluminum plate fin or copper tube with the
lead clip of the insulation resistance tester and
measure the resistance by placing a probe on each
terminal screw on the terminal plate. (Fig. 2) Probe
Note that the ground line terminal should be skipped
for the check.
Clip
7-1-4. Measurement of Insulation
Copper
Resistance for Electrical Parts tube or
metallic part
Disconnect the lead wires of the desired electric part
from terminal plate, capacitor, etc. Similarly disconnect Insulation
tester
the connector. Then measure the insulation resistance. Fig. 3
(Figs. 3 and 4) From fan motor,
compressor and
other parts
NOTE
Refer to Electric Wiring Diagram.
Metallic Probe
part
If the probe cannot enter the poles because the hole is
too narrow then use a probe with a thinner pin. Clip
Insulation
tester
Fig. 4
51
25
7-2. Checking Continuity of Fuse
Fuse
on PCB Ass'y
● Remove the PCB Ass’y from the electrical
component box. Then pull out the fuse from the PCB
Ass’y. (Fig. 5)
PCB Ass’y
● Check for continuity using a multimeter as shown in
Fig. 6.
Fig. 5
Compressor motor
capacitor
Fan motor
capacitor
Fig. 7
26
8. MAINTENANCE
8-1 Changing Address of Remote Control Unit in Indoor Unit
If you are installing more than 1 indoor unit (up to 2) in the same room, it is necessary for you to assign each unit
its own address, so each can be operated by its own separate remote control unit. You assign the addresses by
matching the remocon address on the PCB of each indoor unit with the switch positions of its remote control unit.
(1) Set the switch n.2 to "off" position on the address dip switch (S01)
(see detail on figure)
27