The term Power Quality relates to the amplitude, frequency and distortion of the electrical supply. Whilst the utility provides a supply, which has the amplitude and the frequency within controlled limits, it is the consumer and his equipment that distorts both the voltage and current waveforms.
Prior to the proliferation of modern power electronics, most loads were linear, drawing a sinusoidal current following the supply voltage. However, nowadays the most common loads are non-linear, utilizing power that is not sinusoidal. Non- linear equipment use converters to transform AC power to DC power. The type of converter, the semiconductor and load characteristics dictate the current drawn by the source. Since the current drawn is not sinusoidal, harmonics are generated.
Harmonic Distortion, caused by non-linear loads on the supply network, results in currents in the system that are of a higher magnitude than expected and contain harmonic frequency components. The economic effects of these harmonics are shorter equipment life, reduced energy efficiency, and a susceptibility to nuisance tripping.
There are several common problems associated with harmonics:-
Overheating of transformers, cables and motors
Nuisance tripping of circuit breakers
Over-stressing of PF correction capacitors
Reduced current carrying capacity of cables due to skin effect
Overloading of neutral conductors
Zero crossing noise
Voltage distortion
Problems caused when harmonic currents reach the supply legislation problems.
The Solution: AIM Active Harmonic Filter
A proven technology is now available to isolate harmonic current and protect the equipment on your power distribution system from damage due to harmonic voltage distortion.
By actively monitoring the non-linear current demanded by the load, the AIM Active Harmonic Filter (AHF) electronically generates an adaptive current waveform, which matches the shape of the non-linear portion of the load current. By injecting this matching current into the bus in real time, the AHF stops the destructive current at the point of connection.
By this mode of cancellation, the AIM AHF provides the industrys best attenuation of harmonic currents. The AHFs IGBT Converter Bridge reacts at micro-second speed to changes in the non-linear load current, allowing cancellation even as the high frequency harmonic components change.
The AHF is not affected by changes in the impedance in the system, nor will it react with other devices. The AHF will not adversely affect the resonant points in the system.
The AHF has no series components allowing an easy-to- install connection. If greater capacity is required, the AHF has built-in circuitry to allow for simple paralleling. Paralleled systems are available for single point field connections.
Unique Features
AIM (Adaptive Injection Mode) Harmonic Filter The AHFs electronic bridge draws leading reactive current from the power line, stores it in a DC capacitor bus, and delivers it back to the line as harmonic current, meeting the loads demand for non-linear current at the point of connection. The source delivers fundamental current.
Industrys Best Harmonic Cancellation Device Unlike a tuned filter, the AHF continuously measures the loads changing non-linear current and injects the required waveform to supply the loads harmonic current demand from the 2 nd to the 51 st harmonic.
Easy to Apply The AHF is a non-resonating, non-tuned device. It can be installed anywhere on the distribution system. A simple measurement to determine the magnitude of harmonic current is all that is needed. For new installations the equipment manufacturer or your AHF supplier can provide the required data. IGBT Bridge The AHFs Class-D Switching Mode Current Source Amplifier uses Insulated Gate Bipolar Transistors. These are high frequency switched power electronic devices that allow high resolution and micro-second response to match the loads non-linear current waveform.
The AHF is connected parallel to the bus through a soft start circuit. When energized the AHF draws leading reactive current and the converter uses this to charge the internal DC Bus.
The current transformers on two of the phases measure the load current. An electronic notch filter rejects the fundamental frequency component and passes the distortion current components (harmonic as well as non- harmonic, transient and sub-harmonic components). Electronically controlled linear attenuators reduce the harmonic current signals to limit the AHFs harmonic current output to the units rated RMS value.
The amplifier control logic uses this signal to modulate current waveform which matches the non-fundamental current demanded by the non-linear load.
Features
Adaptive Injection Mode (AIM) Continuously monitors the load harmonic current spectrum and cancels it.
Industrys Best Harmonic Cancellation Device Superior non-linear current cancellation from the 2 nd to 51 st harmonic. Greatly reduces notching caused by SCR switching, diode rectification and other load generated transients.
Parallel Connection With no series components the AHF can be easily installed without major re-work. Current measurement is made with current transformers. Energy consumption is low.
Electronic VAR Current In addition to harmonic cancellation current, the AHF electronically produces leading VAR current, aiding the improvement of system power factor without the negative effects of traditional power factor correction capacitors.
Current Limited The AHF unit is current limited and can work in any system without overload or damage, regardless of the magnitude of harmonic current demanded by the load.
Safety and Access The AHFs power sections are covered within the enclosure to LVD standards. Removable panels allow easy front access and clear view of major components.
G5/4 & IEEE 519-1992 The AHF units are easily paralleled and can be sized to guarantee compliance with G5/4 and IEEE 519-1992 harmonic standards under most load conditions.
Pictured 100Amp Model contains:
MCS / Isolation Device Fast Acting/High Interrupting Fuses High Frequency / EMI/EMC Filter Soft Start Contactor Circuit IGBT Switching-Mode Power Stage DC Bus Capacitors AC Capacitor Reactive Current section
Product Offering Summary
3-Wire models range between 25 and 300 amps (4-wire to 100 amps) with inputs of 208V through 600 VAC, 50Hz or 60Hz. CT requirements are specified per application. Split core CTs are available upon request. AHFs can be paralleled with one set of CTs. All units are available as chassis or enclosed. Consult AIM for special enclosure requirements. All models include a control / display panel.
Chassis models include a control / display panel, 1m of ribbon cable, 2 CTs and 200k AIC Fuses. A moulded case disconnect switch is included with all enclosed models. A power quality analyser (PQA) with communications is available at extra cost as an addition.
Typical Connection Diagram
AIM AHF Field Results 100Amp Attenuation From the 2nd to 51st Harmonic Typical results of the AHF during operation in parallel with SCR Bridge Rectifier non-linear load seen from Delta side of a Delta-Wye transformer.
SOURCE CURRENT WITHOUT AHF SOURCE CURRENT WITH AHF
SOURCE VOLTAGE WITHOUT AHF SOURCE VOLTAGE WITH AHF
Type Model Harmonic Cancellation Phase Current Harmonic Cancellation Neutral Current Reactive Current Corrective KVARs Losses @ rated output Dimensions H x W x D Approx Weight (Arms) (Arms) (Arms) (KVARs) (kw) (mm) (Kg) 3W Chassis 3A025F5ECHXF 25 - 14 9.3 0.6 788 x 407 x 312 50 3W Wall Mount 3A025F5EE3MF 25 - 14 9.3 0.6 788 x 407 x 338 59 4W Chassis 4A025F5ECHXF 25 75 14 9.3 0.6 788 x 407 x 312 50 4W Wall Mount 4A025F5EE3MF 25 75 14 9.3 0.6 788 x 407 x 338 59 3W Chassis 3A050F5ECHXF 50 - 27 19 1.1 1220 x 407 x 312 79 3W Wall Mount 3A050F5EE3MF 50 - 27 19 1.1 1220 x 407 x 338 86 4W Chassis 4A050F5ECHXF 50 150 27 19 1.1 1220 x 407 x 312 79 4W Wall Mount 4A050F5EE3MF 50 150 27 19 1.1 1220 x 407 x 338 86 3W Chassis 3A100F5ACHXF 100 - 54 37 2.2 1897 x 500 x 381 170 3W Floor Mount 3A100F5AE2MF 100 - 54 37 2.2 2109 x 610 x 508 272 4W Chassis 4A100F5ACHXF 100 300 54 37 2.2 1897 x 500 x 381 180 4W Floor Mount 4A100F5AE2MF 100 300 54 37 2.2 2107x610 x 508 282 3W Chassis 3A150F5ACHXF 150 - 81 56 3.3 1897 x 699x381 190 3W Floor Mount 3A150F5AE2MF 150 - 81 56 3.3 2109 x 813 x 508 318 3W Chassis 3A200F5ACHXF 200 - 104 72 4.4 1897 x 1106 x 381 204 3W Floor Mount 3A200F5AE2MF 200 - 104 72 4.4 2109 x 1220 x 508 397 3W Chassis 3A300F5ACHXF 300 - 162 112 6.6 1897 x 1106 x 381 250 3W Floor Mount 3A300F5AE2MF 300 - 162 112 6.6 2109 x 1220 x 508 443 * Other voltages 208V-600V available
General Specification
Input Voltage Nominal +6%, -14% steady state (+/- 10% at 208 VAC) Nominal +11%, -19% 20 minutes (+/- 15% at 208 VAC) Transient IEEE 587, class B Input Frequency Nominal +/- 5% Interrupting Capacity 200kA, fused Initialisation Time 6 sec maximum Peak Harmonic Current 3x nominal rms maximum rating Reactive Current Injected 85% electronically generated Control & Indication Panel Switch On / Off / Reset Indicators Power Applied Operate At Max. Capacity Fault Temp. Warning Remote Indicator (relay output) Operate Fault Power Applied Temperature 0 to 40C operating, - 30 to 50C storage Humidity to 95%, non-condensing Altitude to 1500 meters MFBF 10.8 years
Contacts
AIM Europe Balvaddi House 12 Ferry Row Fairlie Ayrshire KA29 0AJ Scotland United Kingdom Tel: +44 (0) 1475 568 423 Fax: +44 (0) 1475 568 808 email: powerquality@aimeurope.com www.aimeurope.com APT AIM Energy, Inc (Corporate Office) Port Ludlow WA 98365, USA Tel: +1 360 437 7779