You are on page 1of 10

ARTICLE IN PRESS

Building and Environment 44 (2009) 515– 524

Contents lists available at ScienceDirect

Building and Environment


journal homepage: www.elsevier.com/locate/buildenv

The effect of combining a relative-humidity-sensitive ventilation system with


the moisture-buffering capacity of materials on indoor climate and energy
efficiency of buildings
Monika Woloszyn a,b,c,, Targo Kalamees d, Marc Olivier Abadie e,f, Marijke Steeman g,
Angela Sasic Kalagasidis h
a
Université de Lyon, Lyon F-69003, France
b
Université Lyon1, Villeurbanne F-69622, France
c
INSA-Lyon, CETHIL UMR CNRS 5008, bat. Sadi Carnot, F-69621 Villeurbanne cedex, France
d
Chair of Building Physics and Architecture, Tallinn University of Technology, Ehiteja tee 5 19086, Estonia
e
Pontifical Catholic University of Parana – PUCPR/CCET-Thermal Systems Laboratory, Rua Imaculada Conceic- ão, 1155 Curitiba, PR 80215-901, Brazil
f
LEPTIAB-University of La Rochelle, Avenue M. Crépeau, 17000 La Rochelle, France
g
Department of Architecture and Urban Planning, UGENT-Ghent University, J. Plateaustraat 22, 9000 Ghent, Belgium
h
Department of Building Technology, Chalmers University of Technology, Sven Hultins gata 8, 412 96 Gothenburg, Sweden

a r t i c l e in fo abstract

Article history: Indoor moisture management, which means keeping the indoor relative humidity (RH) at correct levels,
Received 23 November 2007 is very important for whole building performance in terms of indoor air quality (IAQ), energy
Received in revised form performance and durability of the building. In this study, the effect of combining a relative-humidity-
20 April 2008
sensitive (RHS) ventilation system with indoor moisture buffering materials was investigated. Four
Accepted 22 April 2008
comprehensive heat–air–moisture (HAM) simulation tools were used to analyse the performance of
different moisture management strategies in terms of IAQ and of energy efficiency. Despite some
Keywords: differences in results, a good agreement was found and similar trends were detected from the results,
Whole building HAM simulation
using the four different simulation tools. The results from simulations demonstrate that RHS ventilation
Relative-humidity-sensitive (RHS)
reduces the spread between the minimum and maximum values of the RH in the indoor air and
ventilation system
Moisture-buffering generates energy savings. Energy savings are achieved while keeping the RH at target level, not allowing
Energy for possible risk of condensations. The disadvantage of this type of demand controlled-ventilation is
Indoor climate that other pollutants (such as CO2) may exceed target values. This study also confirmed that the use of
moisture-buffering materials is a very efficient way to reduce the amplitude of daily moisture
variations. It was possible, by the combined effect of ventilation and wood as buffering material, to keep
the indoor RH at a very stable level.
& 2008 Elsevier Ltd. All rights reserved.

1. Introduction with serious moisture problems for the building envelope and for
the indoor climate [6–10], due to the growth of micro-organisms
Indoor moisture management, which means keeping the [11,12] and house dust mites [13–15].
indoor relative humidity (RH) at correct levels, is very important Indoor air moisture is influenced by several factors, such as
for whole building performance in terms of indoor air quality moisture sources (human presence and activity, equipment), air
(IAQ), energy performance and durability of the building envel- change rate and airflow in rooms, the release or uptake of
ope. Indeed, indoor air humidity strongly affects indoor climate. moisture by hygroscopic surfaces of envelope and furniture,
The main risk factors related to low RH may be associated with moisture flow through building envelope, possible condensation
the dryness of the skin, mucous membranes, sensory irritation of as well as moisture content of the outdoor air. Adequate
the eyes and upper airways [1–3] as well as control of static ventilation is used in general in order to guarantee good IAQ
electricity [4,5]. The risk factors of having high RH are connected and to keep the indoor RH at a target level. The effect of
ventilation and resulting indoor humidity has a considerable
impact on the energy performance of the building, especially in
 Corresponding author at: INSA-Lyon, CETHIL, bat. Sadi Carnot, F-69621 modern, very well insulated dwellings, where the part of the heat
Villeurbanne cedex, France. Tel.: +33 472 436 269; fax: +33 472 438 811. loss due to air renewal can account for as much as half of the total
E-mail address: monika.woloszyn@insa-lyon.fr (M. Woloszyn). heat loss [16].

0360-1323/$ - see front matter & 2008 Elsevier Ltd. All rights reserved.
doi:10.1016/j.buildenv.2008.04.017
ARTICLE IN PRESS

516 M. Woloszyn et al. / Building and Environment 44 (2009) 515–524

It is anticipated that the reduction of the amount of fresh cold simulation tools were used for two reasons: (1) to avoid any
air introduced into the building contributes to bringing down specific tool-related inaccuracy and (2) to compare capabilities
energy consumption. Evidently, the reduction of ventilation rates and possible differences of different tools for assessing indoor
must be carefully designed to prevent deterioration of IAQ, moisture management issues.
including RH and pollutant levels. Previously conducted studies
showed that humidity can be successfully used as a control
parameter for ventilation, enabling energy savings without 2. Methodology
compromising IAQ throughout the whole year (both in cold and
mild months). This is directly related to the reduction of mean 2.1. Studied configuration
ventilation rate, when the building is not used [17,18]. However,
for dwellings with very high moisture load, the RHS ventilation The simulation case is based on a real one-storey test building
may be used to improve IAQ, but lead to higher energy use [19]. (see Fig. 1) with two rooms (volume 49.4 m3, area 19.3 m2), which
Moreover, relevant use of the moisture-buffering capacity of are located at the outdoor testing site of the Fraunhofer-Institute
building materials contributes to stabilise the indoor climate in of building physics in Holzkirchen, Germany (altitude: 680 m NN;
terms of variations of RH. For example, Ref. [20] showed that in latitude: 47.881, north; longitude: 11.731, east).
the case of peak vapour production in the kitchen, about half of The walls of the rooms were built with 24 cm brick and
the produced vapour was absorbed by the materials. This externally insulated with 7 cm polystyrene. The internal surface in
moisture-buffering effect of materials was preventing surface the reference room was standard gypsum plaster with a latex
condensation. paint. The walls and the ceiling of the test room were first fully
All these interactions of indoor air humidity are complex, and coated with aluminium foil and then (in some cases) covered with
realistic predictions of different factors require the use of manufactured gypsum board (see Table 1). The roof was an 18 cm
advanced simulation tools. Simulation tools should be able to concrete slab, insulated with 20 cm polystyrene. A 25 cm concrete
take the whole building into account and calculate room air floor was insulated with 20 cm polystyrene and covered with PVC
humidity including exchange of moisture between indoor air and linoleum. Such material properties as density, porosity, specific
materials in contact with the indoor air. Several studies [20–24] heat capacity, thermal conductivity, moisture permeability, and
have shown that the moisture storage capacity of finishing moisture retention curve were measured in laboratory conditions
materials has a significant effect on indoor RH and models that and are described more in detail in Refs. [26,27].
do not include the sorption process do not adequately model The indoor air temperature was held at 20 1C, using a
indoor RH. Mendes et al. [25] showed that whole-building energy temperature controlling electric heater in the centre of the room.
simulation models that ignore moisture transfer in the building A ventilation system provided constant air change, determined by
envelope may overestimate conduction peak loads up to 210% and tracer gas measurements (n ¼ 0.63 h1 for the reference room and
underestimate the yearly integrated heat flux up to 59% that can n ¼ 0.66 h1 for the test room). To achieve a realistic assessment
lead to oversize heating, ventilation and air conditioning equip- of the course of RH with regard to the moisture-buffering effect,
ment (especially in dry climates) and underestimate energy 2.4 kg of water was introduced by an ultrasonic evaporator into
consumption (primarily in humid climates). each room per day, which corresponds to the equivalent amount
In this work, the possibilities of combining an RHS ventilation for a household of three persons [28].
system with moisture-buffering capacity of materials were To differentiate short- and long-term moisture-buffering of
investigated with whole building HAM simulation tools. At the surrounding surfaces, two moisture production cycles were
same time, four different simulation tools were tested to analyse chosen for each day: short but high moisture production in the
the performance of different indoor moisture management morning from 6 to 8 a.m. (0.4 kg/h) and larger but moderate
strategies in terms of IAQ and of energy efficiency. Different moisture production in the afternoon from 4 to 10 p.m. (0.2 kg/h).

Fig. 1. View and ground plan of test rooms: left-reference room with gypsum plaster and paint, and right-test room where different finishing materials were tested.

Table 1
Original finishing materials from experimental rooms

Room Step 1 (17/01–02/02) Step 2 (14/02–19/03) Step 3 (28/03–21/04)

Reference (ach ¼ 0.63 h1) Gypsum plaster+paint Gypsum plaster+paint Gypsum plaster+paint
Test (ach ¼ 0.66 h1) Aluminium foil Gypsum board on walls Gypsum board on walls+ceiling
ARTICLE IN PRESS

M. Woloszyn et al. / Building and Environment 44 (2009) 515–524 517

These peaks simulate taking showers, washing, cooking and the To study the influence of the ventilation system and properties
presence of human beings. The temperature of the wall surfaces, of finishing materials, simulations were performed with five
temperature layering in the middle of the rooms, and RH in the simulation runs (see Table 3):
rooms, as well as energy consumption of the heating system, were
measured. The temperature and humidity in the centre of the  Run A: Experimental data, with constant ventilation (validation
room were considered for comparison. For outdoor boundary of the simulation models),
conditions, recorded weather data from Holzkirchen (January to  Run B: Using original finishing materials (Table 1) and the
April 2005) were used. In constant indoor temperature, indoor RH original RHS ventilation system (Fig. 3),
depends on moisture production, air change rate, outdoor  Run C: Using original finishing materials (Table 1) and a
humidity by volume and on moisture flow exchanged between modified RHS ventilation system with modified maximum
indoor air and building envelope. Two first parameters are the (Q2) and minimum (Q1) airflow values (ventilation was
same in all steps. Outdoor humidity by volume was approximately modified independently by the participants of the study),
the same in steps 1 and 2. In step 3, the outdoor humidity by  Run D: Using the original RHS ventilation system (Fig. 3), but
volume was higher (see Fig. 2). Steps 1 and 2 presented cold and changing the moisture-buffering properties of materials
dry external conditions, and step 3 mild and humid ones. (materials were chosen independently by the participants of
The influence of different ventilation system strategies and the study), and
moisture-buffering capacity of the internal surface of finishing  Run E: Combining both—the ventilation and the materials—
materials of building envelope on indoor RH were investigated. In in order to reduce the energy consumption and to improve
some configurations, a constant airflow ventilation system was indoor RH.
replaced by a RHS exhaust, where the ventilation airflow was
controlled by the room RH level. Such a system adapts the airflow 2.2. Simulation tools
to changes in the indoor relative RH, as shown in Fig. 3 with
RH1 ¼ 25%, Q1 ¼ 10 m3/h, RH2 ¼ 60%, Q2 ¼ 40 m3/h. In some Four different commercially available simulation tools were
configurations, the moisture-buffering properties of the internal used by five different institutions (see Table 2). All are ‘whole-
surface of finishing materials of the building envelope were building’ simulation tools: multi-zone tools for building simula-
changed. tion of energy consumption, IAQ and thermal comfort in dynamic
conditions, under the influence of the outdoor climate and
variable loads. The different envelope parts (roof, walls and floor)
may separate the zones from each other and from the outdoors.
The geometry, material layers and their properties define the
envelope parts. The envelope may include a number of openings,
leaks, doors, and windows. Different heating, cooling, ventilation,
and lighting systems can be attached to rooms. Heat balances may
involve the heating/cooling devices, air handling units, elements
of the envelope, direct sun gains through windows, leaks and
thermal bridges, the internal thermal mass, occupants, lights,
equipment.
All four simulation tools include the main elements of
moisture balance, discussed for example in Refs. [20,26,29]:
vapour sources (occupants, equipment, etc.), airborne transport
(air handling units, leaks, inter-zone flow) and sorption by
materials in contact with the indoor air. The models of moisture
flow between the indoor air and materials depend on the
modelling of heat and moisture transfers in the elements of
building envelope. Two tools can represent coupled heat and mass
Fig. 2. Outdoor conditions for all three steps. transfers in the envelope (IDA-ICE and HAM-Tools) and two use
simplified models to represent the buffering effect of hygroscopic
materials (TRNSYS and Clim2000). In the following, the main
elements of moisture-buffering modelling are described, and
Air flow reference is made to the literature for further details of the
(m3/h) physical models used in the simulation tools.

2.2.1. Moisture transfer through the envelope parts


Q2 2.2.1.1. Coupled heat and mass flow models. Detailed, one-dimen-
sional coupled heat and water vapour transfer models are im-
plemented in IDA-ICE and HAM-Tools. Both are based on similar
equations, and suppose that moisture transfer is governed by one
moisture transfer potential, the humidity by volume, v (kg/m3).
Q1 The governing equations for the moisture (1) and energy (2)
transfer are then:
 
qv q qv
RH1 RH2 Relative ¼ dv , (1)
qt qx qx
Humidity (%)
 
qT q qT qv
Fig. 3. Original RHS ventilation system test room (no moisture-buffering rc ¼ l þ hvap , (2)
materials) and reference room (painted plaster). qt qx qx qt
ARTICLE IN PRESS

518 M. Woloszyn et al. / Building and Environment 44 (2009) 515–524

Table 2
Simulation tools and users in this study

Simulation tool Detailed presentation of the tool Validation of the tool Institution, country

TRNSYS (version 16) [30,31] [32] UG (University of Ghent), Belgium


IDA-ICE [33–35] [36,37] TTU (Tallinn University of Technology), Estonia
Clim2000 [38,39] [20,40] CETHIL (Centre de Thermique de Lyon), France
HAM-Tools [41,42] [43,44] CTH (Chalmers University), Sweden
TRNSYS (version 15) [30,31] [32] PUCPR (Pontifical Catholic University of Parana), Brazil

70 70

60 60
Relative humidity (%)

Relative humidity (%)


50 50

40 40

30 30

20 20

10 10
0 0
27/1 0:00 27/1 12:00 28/1 0:00 28/1 12:00 29/1 0:00 27/01 00:00 27/01 12:00 28/01 00:00 28/01 12:00 29/01 00:00
UG PUCPR UG PUCPR
TTU CTH TTU CTH
CETHIL experimental measurements CETHIL experimental measurements

Fig. 4. Comparison of measured indoor RH with simulation results (left-test room, right-reference room).

where r is the density of the material (kg/m3), dv is the vapour Dalicieux [38] to represent ‘low absorption’ and ‘high absorption’
permeability (m2/s), l is the thermal conductivity [W/(m K)], c is finishing materials and furniture.
the specific heat capacity of the material [J/(kg K)] and hvap is the
latent heat of vaporisation (J/kg). In the current study, the liquid
2.2.2. Validation of simulation models: RH and energy demand with
flow and airflow through the envelope are neglected. This sim-
constant ventilation rate
plification does not influence the result, because infiltration air-
Even though in this study previously validated simulation tools
flow is included to the overall ventilation rate and condensation
were used, it was necessary to validate the simulation models. The
did not occur. The walls are discretised, using finite volume
validation was performed on a configuration very similar to the
method with several nodes per wall.
case study analysed in this paper. Validation against experimental
data is essential, because all simulation tools are different: they
2.2.1.2. Simplified moisture-buffering models. Both TRNSYS versions
have different simulation possibilities and limitations, material
and Clim2000 simulation tools only compute heat transfers in
properties are defined differently, etc. In this study, simulation
building envelope elements and use simplified models to assess
tools were tested against experimental data for both test and
moisture-buffering capacity of materials in contact with the in-
reference rooms (referred as run A in this study). Validation was
door air. Both tools use similar types of penetration depth models
done as the blind test (only input parameters were given [26]).
with two nodes (one for deep layer and one for surface layer) to
More detailed description of the experimental data and compar-
represent the average behaviour of room materials.
ison between simulated and measured data can be found in Refs.
Humidity levels in materials (in deep and surface layers) are
[26,27]. Fig. 4 shows an example of indoor air RH for two typical
then described using Eqs. (3) and (4):
days. Simulation tools are able to represent correctly experimental
dosurf data; the spread between the simulated and the measured values
Asurf ¼ bsurf ðoint  osurf Þ þ bdeep ðodeep  osurf Þ, (3)
dt is in general below 10% of RH. The spread between experimental
and simulated data is always lower than 5% for CTH and lower
dodeep than 10% for UG. For the three remaining results (TTU, CETHIL and
Adeep ¼ bdeep; ðosurf  odeep Þ. (4)
dt PUCPR) the spread is lower than 10% during 95% of the time,
In TRNSYS, moisture transfers are governed by differences in the meaning that the difference is higher than 10% only once a day
humidity ratio o (), and both transfer coefficients b and storage (during the highest moisture production). This difference is the
coefficients A are computed, using materials properties for vapour largest for the reference room simulated by CETHIL, for minimum
transfers and the quantity of materials in the room. and maximum values. This fact can be easily explained by the
In Clim2000, only Eq. (3) is used, the differences in the simplified model used to represent moisture sorption by painted
humidity ratio o () are simply replaced by differences in water plaster (envelope material directly in contact with the indoor air).
vapour density r (kg/m3) and rdeep is fixed to represent the mean Simplified model used in Clim2000 has only two sets of default
value of indoor air RH. Transfer coefficients b and storage parameters (see Section 2.2.2); which do not correspond to the
coefficients A were experimentally evaluated by Duforestel and materials used in the experiment. Certainly, they can be adjusted,
ARTICLE IN PRESS

M. Woloszyn et al. / Building and Environment 44 (2009) 515–524 519

using experimental data of indoor RH. However, the results energy, RH, ventilation flow, as well as vapour flow between air
presented here are the direct results of the blind test, without any and construction for both test and reference rooms. Run A was
‘tuning’ of parameters according to monitored data. used for validation against the experimental data and as reference
Also, overall energy demand is simulated for both steps 1 for assessment of indoor moisture management performance. As
and 2; the difference between the experimental and simulated the computed indoor temperature was exactly equal to 20 1C for all
results is under 10% for CETHIL, TTU, PUCPR and UG, as simulation tools, the RH was used for comparative purposes.
represented in Fig. 5.
The comparison between simulated and measured data shows
3.1. Impact of indoor moisture management strategies on the indoor
satisfactory performance of simulation models. In the following,
climate
the tools are used to perform parametric studies.

Daily evolution of indoor RH for both ventilation systems in a


room with no hygroscopic surfaces (test room of step 1, Table 1) is
3. Results and discussion presented in Fig. 6. Clearly, the amplitude of RH variations is
smaller for RHS ventilation. Fig. 7 provides more details about the
The sets of results used in this study are presented in Table 3. statistical distribution of RH. It is noticeable that maximum values
Results included calculated hourly averaged temperatures, heating are very similar for both systems, (even slightly lower for RHS
system). However, the mean and average values, as well as the
1000 minimum values are higher for RHS system. Minimum values are
STEP 1 STEP 2
approximately 20% RH for the RHS system and go as low as 10% in
900
the case of constant ventilation. The target values of the indoor air
800 RH were between 40% and 50%, as proposed by EN 15251 [45] for
class A buildings.
energy demand (kWh)

700
As shown in Fig. 8, the impact of ventilation systems is much
600 smaller in the mild period. The spread of RH values is still smaller
500
and the minimum values are higher for RHS ventilation. However,
the differences are very small, approximately 2–3% of RH. Both
400 Figs. 8 and 9 illustrate the influence of moisture-buffering on the
300
indoor RH. When some hygroscopic surfaces are in contact with
the indoor air, the amplitude of RH variations is much lower; it
200 drops approximately from 50% to 20%. This was confirmed by run
100 D, presented in Fig. 10 where the participants proposed some
hygroscopic materials associated with RHS ventilation. In this
0 case, the amplitude was less than 20%; and 50% of values were
experiment UG TTU CETHIL CTH PUCPR
within an interval of 8%, considered very stable. TTU and CTH used
Fig. 5. Comparison of measured heating energy use with simulation results for the wood to reduce very efficiently RH variations. Indeed, the
reference room and two simulation steps (step 1–17 days, step 2–34 days). maximum spread was then 15% for TTU and 24% for CTH. PUCPR

Table 3
Studied configurations and sets of results

Run A (exp./sim.) Run B (sim.) Run C (sim.) Run D (sim.) Run E (sim.)

Ventilation Constant RHS Proposed by participant RHS Proposed by participant


Indoor materials Original Original Original Proposed by participant Proposed by participant

Step 1 (17/01–02/02) UG, TTU, CETHIL, CTH, PUCPR UG, TTU, CETHIL, CTH, PUCPR UG, TTU, PUCPR UG, TTU UG, TTU
Step 2 (14/02–19/03) UG, TTU, CETHIL, CTH, PUCPR UG, TTU, CETHIL, CTH, PUCPR UG, TTU, PUCPR UG, TTU, CTH UG, TTU
Step 3 (28/03–21/04) UG, TTU, CETHIL, CTH, PUCPR UG, TTU, CETHIL, CTH, PUCPR UG, TTU, PUCPR UG, TTU, CTH, PUCPR UG, TTU, PUCPR

70 70

60 60
Relative humidity (%)

Relative humidity (%)

50 50

40 40

30 30

20 20

10 10

0 0
27/1 0:00 27/1 12:00 28/1 0:00 28/1 12:00 29/1 0:00 27/1 0:00 27/1 12:00 28/1 0:00 28/1 12:00 29/1 0:00

UG PUCPR TTU CTH CETHIL UG PUCPR TTU CTH CETHIL

Fig. 6. Indoor RH in the test room computed by all participants: run A-constant ventilation rate (left) and run B-RHS ventilation (right).
ARTICLE IN PRESS

520 M. Woloszyn et al. / Building and Environment 44 (2009) 515–524

Ι min - max 25-75 percentile mean median Ι min - max 25-75 percentile mean median
90 90
80 80

Relative Humidity [%]


Relative Humidity [%]

70 70
60 60
50 50
40 40
30 30
20 20
10 target RH
10 target RH
0 0
UG TTU CETHIL CTH PUCPR UG TTU CETHIL CTH PUCPR

Fig. 7. Indoor RH in the test room during step 1 for both ventilation systems: run A-constant ventilation rate (left) and run B-RHS ventilation (right).

Ι min - max 25-75 percentile mean median Ι min - max 25-75 percentile mean median
90 90

80 80
Relative Humidity [%]
Relative Humidity [%]

70 70

60 60

50 50

40 40

30 30
target RH target RH
20 20
UG TTU CETHIL CTH PUCPR UG TTU CETHIL CTH PUCPR

Fig. 8. Indoor RH during step 3 for both ventilation systems (UG, TTU and CTH include hygroscopic materials and CETHIL and PUCPR do not): run A-constant ventilation
rate (left) and run B-RHS ventilation (right).

90 Ι min - max 25-75 percentile mean median


80 90
Relative humidity (%)

70 80
Relative Humidity [%]

60
70
50
60
40
30 50
20 40
10
30
0 target RH
16/04 16/04 17/04 17/04 18/04 20
00:00 12:00 00:00 12:00 00:00 UG TTU CTH PUCPR

UG PUCPR TTU CTH CETHIL Fig. 10. Indoor RH in step 3, run D: with RHS ventilation and hygroscopic materials
proposed by the participant.
Fig. 9. Indoor RH in step 3 with (UG, CTH) and without (TTU, CETHIL, PUCPR)
additional moisture-buffering materials for constant ventilation.

used an enlarged surface of gypsum board (which resulted in a applied. The suggestion was to increase this lower limit to
maximum spread of 25%), and UG used concrete to buffer decrease the ventilation rate in low RH regions. Finally, a
humidity variations (and obtained a maximum spread of 22%). more stable indoor RH was achieved for the following schemes
Additional simulations have been performed to improve the (see Fig. 11):
RHS ventilation by adapting it to the outdoor climate (run C).
Indeed, run B confirmed that the indoor RH in the test room  Step 1 (cold): If the indoor RH o40%, the airflow rate is set to
was often below 40% because of the dry outside air in winter. For 10 m3/h, if RH 450%, it is set to 40 m3/h; in between the flow is
steps 2 and 3 the indoor RH never dropped under 25%, linearly interpolated. In this case, the humidity outside was
and thus the lowest airflow rate (10 m3/h) was almost never quite low and no buffering occurred. Not much difference in
ARTICLE IN PRESS

M. Woloszyn et al. / Building and Environment 44 (2009) 515–524 521

indoor RH was noticed when applying another ventilation 3.2. Impact of indoor moisture management strategies on energy
scheme. demand
 Step 2 (cold): If the indoor RH o40%, the airflow rate is set to
10 m3/h, if RH 450%, it is set to 20 m3/h; in between the flow is Ventilation airflow rates for runs A and B for the test room are
linearly interpolated. In this case the maximum ventilation compared in Fig. 12. During step 1 (cold period), the average value
rate could be decreased because there is moisture-buffering of the airflow was approximately 63% of the constant ventilation
and the outdoor air is still quite dry. airflow rate. The differences are much less significant for the mild
 Step 3 (mild): If the indoor RH o40%, the airflow rate is set to period, where both mean ventilation rates are very similar. Very
10 m3/h, if RH 450%, it is set to 50 m3/h; in between the flow is good agreement between all tools on both average and amplitude
linearly interpolated. Here again the maximum airflow rate values can be seen in Fig. 12, left for step 1 with no hygroscopic
was increased, because of the higher indoor humidity caused materials. Only CTH obtained larger maximum spread; however,
by the higher humidity of the outdoor air. the maximum value represents only very few singular points
corresponding precisely to the instant when the ventilation starts,
due to a sudden peak in vapour production. The spread between
values computed by different tools is higher for step 3 (Fig. 12,
right). This is partly explained by the fact that hygroscopic
materials were differently represented in all tools.
Energy demand is presented in Fig. 13. Ventilation systems are
compared for both average values (representing energy demand)
and maximum values (representing heating power to be in-
stalled). During the cold season (low outdoor absolute humidity,
see Fig. 13 left), reduction in energy demand is clearly identified in
the case of RHS ventilation. The energy savings computed by all
tools are between 14% and 17% of energy demand. This is directly
correlated with the reduction of the average value of fresh air
flowing into the room. However, most of the simulations predict
higher peak power (rise of as much as 8%) in the case of RHS
ventilation. This is easily explained by the sudden rise of air
change when vapour release starts, which combined with the very
Fig. 11. Different RHS ventilation schemes adapted to the outdoor climate. cold outdoor leads to a higher heating power demand, in order to

Ι min - max 25-75 percentile mean median Ι min - max 25-75 percentile mean median
45 constant vent.
45
40 40
Ventilation flow [m3/h]

Ventilation flow [m3/h]

35 35
30 30
25 25
20 20
15 15
constant vent.
10 10
5 5
0 0
UG TTU CETHIL CTH PUCPR UG TTU CETHIL CTH PUCPR

Fig. 12. Computed ventilation airflow during step 1 (left) and during step 3 (right).

Av. Const Max Const Av. RHS Max RHS


Av. Const Max Const Av. RHS Max RHS
1400 1400
1200 1200
Power demand [W]

Power demand [W]

1000 1000
800 800
600 600
400 400
200 200
0 0
UG TTU CETHIL CTH PUCPR UG TTU CETHIL CTH PUCPR

Fig. 13. Power demand for runs A and B (no hygroscopic materials) during step 1 (left) and during step 3 (right).
ARTICLE IN PRESS

522 M. Woloszyn et al. / Building and Environment 44 (2009) 515–524

maintain constant temperature. In reality, the situation might be  when CO2 is between the minimum and the maximum, the
somewhat different, because most vapour sources are associated airflow rate is linearly interpolated.
with heat release (physical activity, cooking, shower, etc.).
For mild periods, the difference in energy use by both According to new standard EN 15251 [45], 1200 ppm was used
ventilation systems is much lower (between 1% and 7%). It as the maximum permissible indoor air CO2 content (outdoor CO2
confirms values from Fig. 12, right, where the average airflow concentration was 400 ppm) for third indoor climate category.
values for RHS ventilation are very similar to the constant A slightly higher limit for maximum ventilation was set to
ventilation rate. increase the capacity of the ventilation system.
The diurnal CO2 and humidity production patterns used in the
3.3. RH versus CO2 sensitive ventilations simulation tool are shown in Fig. 14. CO2 production was
calculated based on metabolic activity rate of 0.8 met during
the night and 1.2 met during peaks in the morning and the
IDA-ICE was used to include the effect of indoor CO2 on both
afternoon.
IAQ estimations and on controlling the ventilation rate. Indeed,
The main results, presented in Table 4, were:
reducing energy used for ventilation of buildings should be made
without compromising the IAQ. Indoor CO2 levels can be used as
an indicator of the presence of human body odour and also are  In the case of constant ventilation, the lowest CO2 level but
often employed as an indicator to control the performance of a also the highest energy consumption and RH deviation were
ventilation system. In runs C and E, the ventilation systems with observed.
the airflow controlled by carbon dioxide (CO2) adapt the airflow to  There was similar energy consumption in the case of CO2- and
changes in the indoor CO2 RH-controlled ventilation systems, especially during cold
period (steps 1 and 2).
 Hygroscopic indoor surface materials (wood fibreboard com-
 when CO2o600 ppm, the flow is set to the minimum value of pared to gypsum board) damped the fluctuations of indoor RH
3
Qmin ¼ 10 m /h,
in all cases, irrespective of ventilation system.
 when CO241500 ppm, the flow is set to the maximum value of  During cold period, in the case of RH controlled ventilation, the
Qmax ¼ 40 m3/h, and
longest period when the CO2 was higher than 1200 ppm
occurred.
 During warm period (step 3), both RH and CO2 controlled
ventilations, were keeping the CO2 levels under the limit.
 During warm period (step 3), with RHS ventilation and wood
fibreboard, the best stability of HR values was achieved (65% of
the time RH values were within the target interval).

4. Conclusions

This study confirmed that RHS ventilation is a good way of


reducing building energy demand in residential buildings. This
fact is directly related to the reduction of the mean ventilation
rate when the building is not used. Presented results demon-
strate that RHS ventilation reduces the spread between the
minimum and the maximum values of RH. In the tested case, it
was found that the use of a RHS system could reduce the mean
Fig. 14. Diurnal CO2 and humidity production pattern. ventilation rate of 30–40% in the cold period and generate 12–17%

Table 4
Percentage of time when the indoor climate parameters were out of the target RH (40–50%) and over acceptable CO2 limit value (1200 ppm) and associated average power
demand

Run A Run B Run C Run D Run E


Ventilation flow Constant RH controlled CO2 controlled RH controlled CO2 controlled
Indoor surfaces Aluminium foil Gypsum board Gypsum board Wood fibreboard Wood fibreboard

Step 1 (17.01–2.02)
CO2 41200 ppm 0 33 0 33 0
RH out of [40–50%] 84 79 80 79 80
Average power demand (W) 674 571 589 571 589

Step 2 (14.02–19.03)
CO2 41200 ppm 0 35 0 45 0
RH out of [40–50%] 83 65 67 57 72
Average power demand (W) 650 562 570 550 558

Step 3 (28.03–21.04)
CO2 41200 ppm 0 1 0 0 0
RH out of [40–50%] 62 49 79 35 69
Average power demand (W) 392 388 351 390 348
ARTICLE IN PRESS

M. Woloszyn et al. / Building and Environment 44 (2009) 515–524 523

of energy savings. However, during the mild period, the savings In: Proceedings of the 8th international congress on indoor air quality, vol. 2.
are much lower (only about 2%), mainly because of much higher Edinburgh, UK, 1999. p. 107–12.
[9] Bornehag CG, Blomquist G, Gyntelberg F, Järvholm B, Malmberg P, Nordvall L,
external moisture content. It should be stressed that the energy et al. Dampness in buildings and health. Nordic interdisciplinary review of the
savings are realised while keeping the peak RH values at the scientific evidence on associations between exposure to ‘‘dampness’’ in
same level, therefore, without raising the risk of condensation. buildings and health effects (NORDDAMP). Indoor Air 2001;11(2):72–86.
[10] Bornehag CG, Sundell J, Bonini S, Custovic A, Malmberg P, Skerfving S,
This is a significant advantage of this type of demand controlled et al. Dampness in buildings as a risk factor for health effects, EUROEXPO:
ventilation. a multidisciplinary review of the literature (1998–2000) on dampness
However, reducing energy used for ventilation of buildings and mite exposure in buildings and health effects. Indoor Air 2004;14(4):
243–57.
should be made without compromising the IAQ. For example, in
[11] Adan OCG. On the fungal defacement of interior finishes. Doctoral thesis,
cold climates outdoor air is very dry; therefore, the indoor air is Eindhoven University of Technology; 1994. p. 224.
also dry, but even then the ventilation rate cannot be too low. [12] Rowan NJ, Johnstone CM, McLean RC, Anderson JG, Clarke JA. Prediction of
Moisture production depends directly on the human activity. toxigenic fungal growth in buildings by using a novel modelling system.
Applied and Environmental Microbiology 1999(65):4814–21.
Moreover, indoor CO2 levels can be used as an indicator of the [13] Hart BJ. Life cycle and reproduction of house-dust mites: environmental
presence of human body odour. Then, the compromise could be a factors influencing mite populations. Allergy 1998;5(48):13–7.
combination of CO2 controlled and RH controlled ventilation [14] Korsgaard J. House-dust mites and absolute indoor humidity. Allergy
1983;38(2):85–92.
systems. Of course all other pollutants (e.g. VOCs or CO) should be [15] Arlian LG, Neal JS, Vyszenski-Moher DL. Reducing relative humidity to control
kept within correct limits. Therefore, the lower and upper limits of the house dust mite Dermatophagoides farinae. Journal of Allergy and Clinical
ventilation rate must be carefully chosen. Immunology 1999;104(4 Pt. 1):852–6.
[16] Jokisalu J, Kurnitski J. Simulation of energy consumption in typical Finnish
This study also confirmed that the use of moisture-buffering detached house. Helsinki University of Technology, HVAC Laboratory, report
materials is a very efficient way to reduce the amplitude of daily B74, 2002.
moisture variations. It was even possible, by the combined effect [17] Afshari A, Bergsøe NC. Humidity as a control parameter for ventilation. Indoor
and Built Environment 2003;12:215–6.
of ventilation and wood as buffering material (see Fig. 10) to keep
[18] Savin, JL, Berthin S, Jardinier M. Assessment of improvement brought by
the indoor RH at a very stable level, between 43% and 59%. humidity sensitive and hybrid ventilation/HR-Vent project. In: Proceedings of
The deviation of results between different simulation tools, 26th AIVC conference on ventilation in relation to the energy performance of
remaining within a reasonable range, gives some more confidence buildings. Brussels, Belgium, 2005. p. 157–67.
[19] Woloszyn M, Shen J, Mordelet A, Brau J. Numerical simulations of energy
in the tools. Also all codes, with rather different HAM models, performance of a ventilation system controlled by relative humidity. In:
proved their performance in HAM modelling of whole buildings. Proceedings of 26th AIVC conference on ventilation in relation to the energy
performance of buildings. Brussels, Belgium, 2005. p. 295–300.
[20] Plathner P, Woloszyn M. Interzonal air and moisture transport in a test
house. Experiment and modelling. Buildings and Environment 2002;37(2):
Acknowledgements 189–99.
[21] Isetti C, Laurenti L, Ponticello A. Predicting vapour content of the indoor air
and latent loads for air-conditioned environments: effect of the moisture
This study was done within the cooperative project Annex 41 storage capacity of the walls. Energy and Buildings 1988;12:141–7.
‘Whole Building Heat, Air and Moisture Response’ of the [22] Plathner P, Ross D. The effect of sorption on airborne moisture movement in
dwellings. International Journal of Ventilation 2003;1(3):201–8.
International Energy Agency’s (IEA) Energy Conservation in [23] El Diasty R, Fazio P, Budaiwi I. Modelling of indoor air humidity: the
Buildings and Community Systems (ECBCS) program [46]. More dynamic behaviour within an enclosure. Energy and Buildings 1992;19(1):
details about whole building hygrothermal modelling in the IEA 61–73.
[24] Koronthalyova O. The coupled effect of hygroscopic materials and ventilation
Annex 41 can be found in Ref. [26]. All participants of the IEA regime on indoor humidity. IEA Annex 41 report A41-T1-Sl-06-1; 2006.
Annex 41 are acknowledged for their useful discussions and [25] Mendes N, Winkelmann FC, Lamberts R, Philippi PC. Moisture effects on
remarks. conduction loads. Energy and Buildings 2003;35(7):631–44.
[26] Woloszyn M, Rode C. Annex 41, Subtask 1: Modelling principles and common
The authors gratefully acknowledge the support from Ing.
exercises. Draft final report for the energy conservation in buildings and
Kristin Lengsfeld from the Fraunhofer Institute for Building community systems executive committee of the International Energy Agency,
Physics (IBP) in Holzkirchen, Germany, who provided the experi- 2008.
[27] Holm A, Lengsfeld K. Moisture-buffering effect—experimental investigations
mental data needed for validation.
and validation. In: Proceedings buildings X conference, thermal performance
The authors want to thank for financial support of this study: of the exterior envelopes of whole buildings. Clearwater Bach, FL; 2007.
Brazilian Research Council (CNPq) of the Secretary for Science and [28] Hartmann, et al. Feuchteschäden und Schimmelpilzbefall in Wohnungen.
Technology of Brazil, Tallinn University of Technology (B605, Bundesbaublatt Jg 2001;53(3):38–42.
[29] Hens H. Modelling: hygric aspects. Chapter. In: Condensation and energy:
V352) and ADEME, France (Grant no. 03 04 C 0147). source book. IEA-Annex 14. Leuven, Belgium: Acco; 1991.
[30] Klein SA, Beckman WA, Mitchell JW, Duffie JA, Duffie NA, Freeman TL, et al.
References TRNSYS 16 – A TRaNsient system simulation program, user manual. Madison:
Solar Energy Laboratory, University of Wisconsin-Madison; 2004.
[31] Crawley DB, Hand JW, Kummert M, Griffith BT. Contrasting the capabilities of
[1] Wolkoff P, Kjærgaard SK. The dichotomy of relative humidity on indoor air building energy performance simulation programs. Version 1.0, 2005.
quality. Environmental International 2007;33:850–7. [32] Voit P, Lechner Th, Schuler M. Common EC validation procedure for
[2] Fanger PO. Air humidity, comfort and health. Lyndby, Denmark: Technical dynamic simulation programs – application with TRNSYS, TRANSSOLAR
University of Denmark; 1971. GmbH. In: Conference of international simulation societies 94. Zürich,
[3] Wyon DP, Fang L, Mayer HW, Sundell J, Weirsoe CG, Sederberg-Olsen N, et al. 1994.
Limiting criteria for human exposure to low humidity indoors. In: Proceed- [33] Sahlin P, Eriksson L, Grozman P, Johnsson H, Shapovalov A, Vuolle M. Whole
ings of the 9th international congress on indoor air quality, vol. IV, July 2–6, building simulation with symbolic DAE equations and general purpose
2002. Monterey, USA. p. 400–5. solvers. Building and Environment 2004;39(8):949–58.
[4] Brundrett GW. A review of the factors influencing electrostatic shocks in the [34] Sahlin P. Modelling and simulation methods for modular continuous systems
offices. Journal of Electrostatics 1977;2(4):295–315. in buildings. Doctoral dissertation. Stockholm, Sweden: KTH; 1996.
[5] Paasi J, Nurmi S, Vuorinen R, Strengell S, Maijala P. Perfomance of ESD [35] Kurnitski J, Vuolle M. Simultaneous calculation of heat, moisture, and
protective materials at low relative humidity. Journal of Electrostatics air transport in a modular simulation environment. In: Proceedings
2001;51–52(1–4):429–34. of the Estonian academy of sciences engineering, vol. 6/1, March 2000.
[6] Fang L, Clausen G, Fanger PO. The impact of temperature and humidity on p. 25–47.
perception of indoor air quality. Indoor Air 1998;8:80–90. [36] Achermann M. Validation of IDA ICE. Version 2.11.06 with IEA task 12 –
[7] Fang L, Clausen G, Fanger PO. Impact of temperature and humidity on the envelope BESTEST. Hochschule Technik+Architektur Luzern. HLK Engineering,
perception of indoor air quality during immediate and longer whole-body 2000.
exposures. Indoor Air 1998;8:276–84. [37] Kropf S, Zweifel G. Validation of the building simulation program IDA
[8] Fang L, Wargocki P, Witterseh T, Clausen G, Fanger PO. Field study on the ICE according to CEN 13791 thermal performance of buildings – calcula-
impact of temperature, humidity and ventilation on perceived air quality. tion of internal temperatures of a room in summer without mechanical
ARTICLE IN PRESS

524 M. Woloszyn et al. / Building and Environment 44 (2009) 515–524

cooling – general criteria and validation procedures. Hochschule Techni- [43] Sasic Kalagasidis A. The whole model validation for HAM-Tools. Case
k+Architektur Luzern. HLK Engineering, 2001. study: hygrothermal conditions in the cold attic under different ventila-
[38] Duforestel T, Dalicieux P. A model of hygroscopic buffer to simulate the indoor tion regimes. In: Proceedings of the 9th International Conference on
air humidity behaviour in transient conditions. In: Proceedings of European Performance of the Exterior Envelopes of Whole Buildings. Clearwater Beach,
conference on energy performance and indoor climate in buildings, vol. 3. FL, 2004.
Lyon, France, 1994. p. 791–7. [44] Hagentoft C-E, Sasic Kalagasidis A, Adl-Zarrabi B, Roels S, Carmeliet J, Hens H,
[39] Woloszyn M, Rusaouen G, Covalet D. Whole building simulation tools: et al. Assessment method of numerical prediction models for combined heat,
Clim2000. IEA Annex 41 report A41-T1-F-04-3. Zurich, Switzerland, 13–15 air and moisture transfer in building components. Benchmarks for one-
May 2004. 15pp. dimensional cases. Journal of Thermal Envelope and Building Science 2004;
[40] Lomas KJ, et al. Empirical validation of building energy simulation programs. 27:327–52. (4, April).
Energy and Buildings 1997;26:253–75. [45] EN 15251:2007. Indoor environmental input parameters for design and
[41] Sasic Kalagasidis A. HAM-Tools. An integrated simulation tool for heat, air and assessment of energy performance of buildings addressing indoor air quality,
moisture transfer analyses in building physics. Doctoral thesis. Chalmers thermal environment, lighting and acoustics. CEN, European Committee for
University of Technology, Gothenburg, Sweden, 2004. Standardization.
[42] Sasic Kalagasidis A, Weitzmann P, Nielsen TR, Peuhkuri R, Hagentoft C-E, Rode [46] Hens H. Annex 41—whole building heat, air and moisture response. In:
C. The international building physics toolbox in Simulink. Energy and Proceedings of 26th AIVC conference on ventilation in relation to the energy
Buildings 2007;39(6):665–74. performance of buildings. Brussels, Belgium, 2005.

You might also like