Vacuum circuit breaker

Evolis 17.5 kV
Catalogue

2003

Evolis 17.5 kV

General contents

Presentation
Enlarged products offer Versatility Performance Heavy duty and innovative Tailored to your requirements The commitment of a major manufacturer Simple to use and install 3 4 6 7 8 10 12

Circuit breaker
Contents Panorama Full version Fixed version and separated accessories Low voltage accessories Dimensions 15 16 18 24 29 36

Presentation

Enlarged products offer

PE55102

Busbar connection cover

Terminal block connector

Multi 9 circuit breaker

Sepam series 20-40

Lamp

Push button

Voltage presence indicator

Door handle Current transformer

Earthing switch operating mechanism

Extraction table

Surge arrester

Earthing switch

Heating resistance

Presentation

Evolis: versatility

Where to use Evolis?

PE55101

2 versions adapt to your fixed or withdrawable installation: b Full version withdrawable with cradle b Fixed version basic circuit breaker with kits delivered in separate

Evolis circuit breakers are used to protect and control public or industrial medium voltage electrical distribution networks. Evolis is indoor switchgear that is particularly suited to the production and renovation of HV/MV, MV/MV and MV/LV substations. It is suitable for the protection of all types of applications: cables, lines, motors, capacitors, transformers, bus sectioning of sources, etc.

200460

200461

Presentation

Evolis: performance

What does Evolis offer you?


PE55098

Electrical characteristics
b v v v b v v v 3 rated voltages: 7.2 kV index 7, 12 kV index 12, 17.5 kV index 17. 3 breaking capacities: 25 kA index P1, 31.5 kA index P2, 40 kA index P3.

b 3 rated currents: v 630, 1250, 2500.

Full version
200493

P3: 4 1.5 k A

0 kA

P2: 3
d Rate brea king curre nt

P1: 2

5 kA
25 1 0 6 250 0 A 2 12 500 30 A A 63 50 A 25 0 A 1 0 63 250 0 A A 0A A

1 250 63 250 0 A 0A A 1 250 63 250 0 A 2 50 0 1 A 63 250 0 A A 0A A

Ra

ted

cu

rre

nt

Rate

d vo

ltage

V 7.2 k V 12 k kV 17.5

1 2500 6 25 12 2500 30 A0 A A 5 63 0 0A A A 1 250 63 250 0 A 0A A

Fixed version
DE55180

P3: 4 1.5 k A

0 kA

P2: 3
db Rate reak ing c urren t

P1: 2

5 kA
25 00 1 63 250 A 2 0A A 12 500 63 50 A 2 0A A 12 500 63 50 A 0A A

25 1 0 63 250 0 A 2 0A A 12 500 63 50 A 0A A

Ra ted 2 cu 12 500 rre 63 50 nt 0A A A

Rate

ltag d vo

V 7.2 k V 12 k kV 17.5

1 250 63 250 0 A 0A A 12 250 0 5 6 30 0 A A 25 1 0 A 63 250 0 A 0A A

Presentation

Evolis: heavy duty and innovative

How does Evolis eliminate faults?

Electrical endurance
A magnetic field is applied along the axis of the vacuum interrupter contacts. This process maintains the arc in a diffuse mode even at high current values. It ensures optimum distribution of the energy over the contact surface thus avoiding localised hot spots. b The advantages of this technique: v a very compact vacuum interrupter, v low dissipation of arcing energy in the vacuum interrupter. Evolis is in conformity with highest electrical endurance class (IEC 62271-100: class E2).

200205

Mechanical endurance
200110

b This magnetic eld is generated by a patented external coil which surrounds the contact zone. This solution provides many advantages: v a simplied and therefore reliable vacuum interrupter, v heavy duty contacts which do not distort during repeated switching operations, v considerable reduction in control mechanism energy. b For the rst time, a low voltage device control mechanism has been integrated in a medium voltage circuit breaker. The Masterpact control mechanism used on Evolis provides the benets of a system that has proven itself for over 10 years on hundreds of thousands of installations. Evolis is in conformity with most demanding mechanical endurance class (IEC 62271-100: class M2).

PE55107

Protection chain
The Sepam series 20-40 protection unit combined with current sensors, provides a comprehensive measurement, protection and energy management chain. b A high performance and economical solution Sepam series 20-40, due to its modular nature, provides a cost-effective solution adapted to every requirement. b Easy to order and install v all components in the protection chain are referenced and deliverable very rapidly, v the functioning of the protection chain integrated in the Evolis circuit breaker has been fully tested and certied. b The power of a multifunctional digital unit Sepam series 20-40 is not simply a protection relay, it is a multi-functional unit notably providing: v circuit breaker diagnosis functions (number of switching operations, operating time, charging time, cumulative breaking current), v direct circuit breaker control whatever type of release, v remote operation of the equipment through the Modbus communication option. The Sepam series 20-40 is in compliance with the LPTC (Low Power Current Transducers) as defined by standard IEC 60044-8 (draft version).

Presentation

Evolis: tailored to your requirements

What does Evolis offer you?

Full version: a fully assembled and tested unit


b As standard, the circuit breaker is equiped with all the components required for ready to use withdrawable installation in metalclad cubicles. This unit is easy to integrate in a cubicle environment, all it needs is mechanical fixing in place. An installation guide explains the required operations in detail. b This version provides the guarantees of a highly reliable unit, whose components function in perfect harmony. Critical points such as inter-locking systems, dielectric withstand and temperature rise have been checked thoroughly during design. It is a system that is fully integrated and tested by the manufacturer, in conformity with IEC standards 60298 and 62271-100. The interface with optional earthing switch is already existing on the floor of the cradle.

Circuit breakers that combine simplicity of selection and richness of offer. 2 versions are proposed: b full version comprising the withdrawable circuit breaker and its cradle b fixed version and separately delivered kits. Universal accessories can be added to either version. E.g: release, contact, motor, connection, inter-locking systems, etc...

PE55101

Fixed version and high added value accessories:


b The circuit breaker is proposed in its most simple conguration. In this case it can be combined with additional functions, to satisfy various requirements.
PE40002

b This version offers maximum exibility to adapt to constraints in existing cubicles or to operating specications: v retrot: xed and withdrawable installation, v block-type cubicle or fenced substation: xed or removable installation, v compartmented cubicle: xed and withdrawable installation. b The panel builder chooses the components he needs for a customised solution tailor made to his know-how.

Build your own version...

PE40002

DE30114

DE30115

DE30113

Presentation

Evolis: the commitment of a major manufacturer

What guarantees does Evolis provide?

Conformity with standards


b Conformity with standards is a guarantee of suitability for the required function, the very basis of the contract between the supplier and the customer: v dependability, v operator safety. It allows specifications to be fully satisfied whilst complying with local contraints. During its design phase, Evolis was subjected to a series of tests which confirmed excellent performance levels, beyond the standards requirements. b v v v v v v Type testing: dielectric tests, temperature rise, breaking capacity, thermal withstand, mechanical endurance, electrical endurance.

200477

b Specic testing: v ageing, v transport and storage. N.B.:


IEC 60694: common specifications for high voltage switchgear and controlgear standards IEC 62271-100: high voltage alternating current circuit breakers IEC 60298: A.C metal-enclosed switchgear between 1 kV and 52 kV. Comment: for more information, consult the IEC organisation site: www.iec.ch.

Certification
b Certication of conformity provides guarantees that the product: v has been subjected to type testing according to the procedures of standard EN 45001 in accredited laboratories by independent organisations, v is in conformity with recognized international standards. b Evolis is under process of certication by external EN 45011 accredited organisations. N.B.:
EN 45001: general requirements for the competence of testing and calibration laboratories EN 45011: general requirements for bodies operating product certification systems.

10

Guaranteed quality
200465

Schneider Electric integrates a functional organisation in each of its units with the main mission of checking quality and overseeing compliance with standards. The quality system, for the design and manufacture of Evolis circuit breakers, is certified to be in conformity with the requirements of ISO 9001 and ISO 9002 quality assurance standards. b ISO 9001: quality system for design/production and installation b ISO 9002: quality system for production and installation b IQNET: international certication network.

Systematic control
PE55105

During manufacture, each circuit breaker is subjected to routine systematic testing, with the aim of checking both quality and conformity. b Control of vacuum interrupters Each vacuum interrupter, sealed and airtight, is checked for the quality of the vacuum obtained. This pressure measurement is based on the proven magnetron discharge method. Using this sophisticated procedure, measurement is very precise and does not require access to the inside of the bulb, thus not affecting the airtight seal. b Control of the circuit breaker A rigorous set of tests and measurements is carried out on each circuit breaker. The results obtained are reported on and signed off by the quality control department on the test certificate for each device, thereby guaranteeing product traceability.

PE55104

Respecting the environment


b Schneider Electric has given the goal of: v actively participating in environmental protection, from a circuit breaker's design right through to its end of life, v complying with the environmental requirements of both its customers and end users of its products. b For Evolis circuit breakers v development teams integrated the products end-of-life right from the design stage. The product is easy to dismantle, all the materials used are recyclable and nonpolluting, v plastic parts are marked to identify the material, v the circuit breakers are produced in factories which respect the environment. Our subsidiary at Aubenas, France has been awarded the ISO 14001 standard certification (environmental management system).
Comment: for more information, consult the ISO organisation site: www.ISO.CH

PE55103

11

Presentation

Evolis: simple to use and install

How Evolis makes your life easier?

Choice
Evolis circuit breakers offer a comprehensive and rational range: b 3 operating voltages (7.2 kV - 12 kV - 17.5 kV) b 3 breaking capacities (25 kA - 31.5 kA - 40 kA) b 3 current ratings (630 - 1250 - 2500 A) b 1 common range of accessories and auxiliaries b 2 versions: full and xed with accessories.

061032N

Ordering and delivery


b You can order: v the cradle before the circuit breaker, v accessories, at the last moment, that you will easily be able to install yourself. b Thanks to modular design and local customising, the delivery is faster.

Installation
Evolis is easy to incorporate in cubicles. b Optimisation of volumes: one single height and depth throughout the range. b Electrical auxiliaries are interchangeable throughout the range. b Adjustable device height in the cubicle. b Variable phase to phase connection points.

Operation
Increased safety
Evolis has been designed and industrialised to provide maximum safety for operators whilst guaranteeing the simplicity and rapidity of operations. b Protective metal shutters. b Safety interlocking systems to avoid operator errors when racking in or out. b Racking in/out possible only with the door closed. b Safety interlockings to avoid operators errors on earthing switch.
PE40002

Reduced maintenance
b Common stock of replacement parts with the Masterpact circuit breaker. b Diagnosis of the circuit breaker's functional chain using Sepam series 20-40.

Evolis circuit breaker

12

From pre-engineering to switchboard manufacturing, a toolkit exists for panel builders to highlight their know-how and optimise their work around Evolis.

Tools to complement your know-how

Design guide
This document provides you with all the technical recommendations you require for your calculations when designing cubicles and incorporating equipment in conformity with IEC standard 60 298. E.g.: b dening the switchgear, b dielectric strength, b busbar calculation, b temperature rise calculation, b denition of IP protection index.
200467E

Installation guide
200475

This document provides you with all the information and recommendations you need to incorporate the circuit breaker and its accessories in a cubicle. E.g.: b dimensions and space requirements, b mechanical interface, b power circuit connection, b auxiliary connection, b layout diagrams.

200469

CAD library
For easier and more reliable integration of Evolis in a cubicle environment, an extensive library of dimensional drawings and electrical layout diagrams is available in AUTOCAD and ACROBAT READER formats (DWG/DXF/PDF).

MT25000

Internet site
Missing a certificate? Lost a technical manual? Connect up to our web site where you can download all of our technical documentation (http://www.mvproduct.merlin-gerin.com) . Become a club member and discover the information for designing and choosing the right product and integrating it into your switchboard.

13

Circuit breaker

Contents

This chapter provides useful information in selecting the performance levels of your Evolis circuit breaker. It also describes all the functions associated with each version.

Panorama Optional LV accessories Description of withdrawable full version Full version Performance tables Power circuit Racking in Low voltage plug and socket Fixed version and separated accessories Performance tables Connecting the power circuit Power circuit Racking in and support frame Low voltage accessories Opening circuit Remote control Indication Low voltage plug, socket and terminal blocks Locking/Interlocking Dimensions Full version Fixed version

16 16 17 18 18 20 21 22 24 24 26 27 28 29 29 31 33 34 35 36 36 37

15

Panorama

Optional LV accessories

PE55109

Circuit breaker open position padlocking Low voltage plug

Circuit breaker open position key locking

Push button disabling

Bloc of 4 O/C position contacts

Shunt closing release

Shunt opening release or undervoltage release

Ready to close contact

Low energy release

Operation counter

Motor mechanism

16

Panorama

Description of withdrawable full version

PE55110

MV connectors

Shutters

Bushings

Fingers

Clusters

Arms

Racking base

Circuit breaker

A
1 contact for circuit breaker in cranked position.

B Bloc of 4 contacts for circuit breaker racked in/out positions.

Please note: using A and B you can signal C.B. OK to be operated: PAF, and C.B. in test position.

Racking truck

17

Full version

Performance tables 7P1 630 to 17P3 2500

Common characteristics according to IEC 62271-100


rated frequency short-time withstand current rated peak withstand current rated short circuit making current operating sequence fr Ik for tk = 3 s Ip (Hz) (kA) rms peak (kA) peak (kA) 50 & 60 Ik = Isc Ip = 2.5 & 2.6 Ik = 2.5 & 2.6 Isc O - 3 mn - CO - 3 mn - CO O - 0.3 s - CO - 3 mn - CO O - 0.3 s - CO - 15 s - CO < 50 < 60 < 65 M2 10000 E2 100 50 30 class C1

operating times

mechanical endurance electrical endurance

opening breaking closing class number of operations class number of operations

ms ms ms

25 kA 31.5 kA 40 kA

capacitive current breaking

Electrical characteristics according to IEC 62271-100


circuit breaker rated voltage rated insulation voltage rated insulation voltage rated short-circuit breaking current rated normal current (-25 +40C) climatic version Installation and connections phase distance: between poles (mm) dimensions C.B. and cradle (mm) width (W) depth (D) height (H) mass C.B. and cradle (kg)
145 & 185 592 & 702 1140 965 165 & 174 145 & 185 592 & 702 1140 965 165 & 174 240 882 1140 965 272 185 702 1140 965 174 185 702 1140 965 174 240 882 1140 965 272 240 882 1140 965 272 240 882 1140 965 272 240 882 1140 965 272 145 & 185 592 & 702 1140 965 165 & 174

7P1 630 Ur (kV) rms Ud (kV) rms Up (kV) peak Isc (kA) rms Ir (A) rms -25 +40C 7.2 20 60 25 630 b

7P1 1250 7.2 20 60 25 1250 b

7P1 2500 7.2 20 60 25 2500 b

7P2 630 7.2 20 60 31.5 630 b

7P2 1250 7.2 20 60 31.5 1250 b

7P2 2500 7.2 20 60 31.5 2500 b

7P3 630 7.2 20 60 40 630 b

7P3 1250 7.2 20 60 40 1250 b

7P3 2500 7.2 20 60 40 2500 b

12P1 630 12 28 75 25 630 b

18

Full version

200206

200207

12P1 1250 12 28 75 25 1250 b

12P1 2500 12 28 75 25 2500 b

12P2 630 12 28 75 31.5 630 b

12P2 1250 12 28 75 31.5 1250 b

12P2 2500 12 28 75 31.5 2500 b

12P3 630 12 28 75 40 630 b

12P3 1250 12 28 75 40 1250 b

12P3 2500 12 28 75 40 2500 b

17P1 630 17.5 38 95 25 630 b

17P1 1250 17.5 38 95 25 1250 b

17P1 2500 17.5 38 95 25 2500 b

17P2 630 17.5 38 95 31.5 630 b

200208

17P2 1250 17.5 38 95 31.5 1250 b

17P2 2500 17.5 38 95 31.5 2500 b

17P3 630 17.5 38 95 40 630 b

17P3 1250 17.5 38 95 40 1250 b

17P3 2500 17.5 38 95 40 2500 b

145 & 185 240 592 & 702 882 1140 965 1140 965

185

185

240

240

240

240

185

185

240

185

185

240

240

240

240

702 1140 965 174

702 1140 965 174

882 1140 965 272

882 1140 965 272

882 1140 965 272

882 1140 965 272

702 1140 965 174

702 1140 965 174

882 1140 965 272

702 1140 965 174

702 1140 965 174

882 1140 965 272

882 1140 965 272

882 1140 965 272

882 1140 965 272

165 & 174 272

19

Full version

Power circuit

Composition
b The power circuit comprises: v mobile contacts made up of disconnecting clusters and arms mounted on the circuit breaker, v xed ngers located on the cradle and insulated by bushings and metal shutters. b This unit gives perfect control of dielectric, short time withstand current and temperature rise considerations. All of these characteristics have been validated by testing.
DE30118

Power circuit

200159

Connection
b Customer connection is easily achieved outside the cradle: v on vertical copper terminals integrated in the bushing, v through a set of connectors, also used on the basic circuit breaker unit. Connection variants described on page 26 are possible.
Comments: The dielectric withstand values shown in the performance tables are guaranteed excluding these connectors. The panel builder should check the overall cubicle connection configuration.

3 sets of connectors

201252

b For Ur = 17.5 kV CBs with 185 mm phase-to-phase distance, the eld deectors are used to increase the dielectric withstand from 75 kV to 95 kV.

Field deflectors

20

Full version

Racking in

Composition
The racking in function is provided by: b The racking truck supporting the circuit breaker (mobile part). b The cradle including the bushings (xed part). b The LV plug.
DE30119

Operating procedure
b v v v The circuit breaker moves through 3 stable states: service: circuit breaker racked in and locked in place; low voltage plug connected, test: circuit breaker racked out and locked in place; low voltage connected, extracted: the circuit breaker can be unlocked and extracted from the cubicle.

3 stable states for manual operation


DE30124 DE30125 DE30126

200146

Service position

Test position

Extracted position

Comments: Arrows indicate the lock-in-positions for the circuit breaker and the low voltage connector. Propulsive system

Functions
b A propulsive system combined with a screw-shaft makes racking in and racking out easier. The racking mechanism can be operated with the door closed. Interlocking prevents the user from inserting the lever until the racking base selector has been positioned to the racking in/racking out position. b Interlocking between circuit breaker position and cradle makes operation safer: racking in or out only when the circuit breaker is open. b Interlocking is also provided between the low voltage connector and the circuit breaker. Racking in is only possible when the low voltage connector is connected. The oor of the cradle includes all necessary xing holes to position properly the operating mechanism and the power circuit of the earthing switch. This allows reliable operations of the earthing switch and guarantees the interlocking between circuit breaker and earthing switch. b Earthing is automatically achieved throughout the whole racking in operation. b Protective shutters placed on the cradle prevent access to the racking ngers when the device is extracted (protection index: IP2X). b For maintenance operations, it is possible to: v padlock the shutters in the closed position, v unlock the shutters mechanism to access the racking ngers. b A full proof protection enables cradle and circuit breaker to be matched up. This system is mounted on the racking base. Part of it has to be assembled by the panel builder on the cubicle floor.
DE30121

Shutters
MT66049 DE30122

Locked C.B. position contact


DE30136

Racked in/ racked out contacts

Earthing device

Accessories
b A set of auxiliary contacts: v 4 racked in/racked out circuit breaker position contacts, v 1 contact indicating that the circuit breaker is locked in place in the cradle. b The earthing for the base is provided by a copper brush. b A key locking system (Ronis or Profalux) for the racked out position on the circuit breaker will provide increased safety when working downstream of the circuit breaker. This system is combined with an earthing switch (refer to page 43). b Circuit breaker compartment door interlocking. b The device allows circuit breaker operation only when the door is closed for full version with truck.
Cubicle door interlocking mechanism

21

Full version

Low voltage plug and socket

Main functions
This plug and socket system provides an auxiliary supply connection with a high level of electrical safety.

Interlocking function
It is possible to connect and disconnect the plug only if the breaker is in racked out position. It is not possible during the racking in operation.

Two versions of plug and socket


DE30127

An 18 pin version
This version allows you to connect: b For remote control v 1 electric motor, v 1 shunt closing release, v 1 shunt opening release, v 1 contact ready to close. b For auxiliary contacts v 2 changeover contacts, v 1 normally-open contact, v 1 normally-closed contact.

Plug and socket 18 pin version

A 42 pin version
This version allows you to connect: b For remote control v 1 electric motor, v 1 shunt closing release, v 2 shunt opening releases or 1 shunt opening release + 1 undervoltage release, v 1 contact ready to close, v 1 low energy release, v 1 fault-trip indication contact, v 1 SDE contact remote reset. b For auxiliary contacts v 2 changeover contacts, v 5 normally-open contacts, v 4 normally-closed contacts.
Plug and socket 42 pin version
DE30128

22

23

Fixed version

Performance tables 7P1 630 to 17P3 2500

Common characteristics according to IEC 62271-100


rated frequency short-time withstand current rated peak withstand current rated short circuit making current operating sequence fr Ik for tk = 3 s Ip (Hz) (kA) rms peak (kA) peak (kA) 50 & 60 Ik = Isc Ip = 2.5 & 2.6 Ik = 2.5 & 2.6 Isc O - 3 mn - CO - 3 mn - CO O - 0.3 s - CO - 3 mn - CO O - 0.3 s - CO - 15 s - CO < 50 < 60 < 65 M2 10000 E2 100 50 30 class C1

operating times

mechanical endurance electrical endurance

opening breaking closing class number of operations class number of operations

ms ms ms

25 kA 31.5 kA 40 kA

capacitive current breaking

Electrical characteristics according to IEC 62271-100


circuit breaker rated voltage rated insulation voltage rated insulation voltage rated normal current (-25 +40C) climatic version Installation and connections phase distance between poles: without MV connections (mm) dimensions C.B. (mm) width (W) depth (D) height (H) mass C.B. (kg)
145 & 185 145 & 185 240 470 429 535 51 / 55 470 & 550 660 429 535 51 / 55 429 535 79 185 550 429 535 55 185 550 429 535 55 240 660 429 535 79 240 660 429 535 79 240 660 429 535 79 240 660 429 535 79 145 & 185 470 & 550 429 535 51 / 55 145 & 185 470 & 550 429 535 51 / 55 240 660 429 535 79

7P1 630 Ur (kV) rms 7.2 Ud (kV) rms 20 Up (kV) peak 60 Ir (A) rms -25 +40C 630 b

7P1 1250 7.2 20 60 25 1250 b

7P1 2500 7.2 20 60 25 2500 b

7P2 630 7.2 20 60 31.5 630 b

7P2 1250 7.2 20 60 31.5 1250 b

7P2 2500 7.2 20 60 31.5 2500 b

7P3 630 7.2 20 60 40 630 b

7P3 1250 7.2 20 60 40 1250 b

7P3 2500 7.2 20 60 40 2500 b

12P1 630 12 28 75 25 630 b

12P1 1250 12 28 75 25 1250 b

12P1 2500 12 28 75 25 2500 b

rated short-circuit breaking current Isc (kA) rms 25

24

Fixed version

200209

200210

12P2 630 12 28 75 31.5 630 b

12P2 1250 12 28 75 31.5 1250 b

12P2 2500 12 28 75 31.5 2500 b

12P3 630 12 28 75 40 630 b

12P3 1250 12 28 75 40 1250 b

12P3 2500 12 28 75 40 2500 b

17P1 630 17.5 38 95 25 630 b

17P1 1250 17.5 38 95 25 1250 b

17P1 2500 17.5 38 95 25 2500 b

17P2 630 17.5 38 95 31.5 630 b

17P2 1250 17.5 38 95 31.5 1250 b

17P2 2500 17.5 38 95 31.5 2500 b

200211

17P3 630 17.5 38 95 40 630 b

17P3 1250 17.5 38 95 40 1250 b

17P3 2500 17.5 38 95 40 2500 b

185 550 429 535 55

185 550 429 535 55

240 660 429 535 79

240 660 429 535 79

240 660 429 535 79

240 660 429 535 79

185 550 429 535 55

185 550 429 535 55

240 660 429 535 79

185 550 429 535 55

185 550 429 535 55

240 660 429 535 79

240 660 429 535 79

240 660 429 535 79

240 660 429 535 79

25

Fixed version and separated accessories

Connecting the power circuit

Composition
DE30129

b The basic circuit breaker unit is equipped with drilled copper connection terminals, located at the top and bottom of the breaking poles. b Connectors are mounted on these terminals using the associated bolt work. They enable several connection variants. The same connectors can be also mounted on the bushing connection terminals (see page 20).

Fixed connectors
horizontal connectors (H)
P000020D P000021D

vertical connectors (V)


P000022D

mixed connectors

A horizontal connector becomes a vertical connector by a 90 rotation.


Terminal

Variable distance connectors


horizontal spreading connectors (H)
P000024D P000023D

vertical spreading connectors (V)

DE30130

The spreading connector enables the connecting distance to be increased by 0 to 25 mm.

Combined solution
Example
3 sets of connectors
P000025D

Comments: The dielectric withstand values shown in the performance tables do not take into account these connectors. These connectors may be fitted with either bare copper, tin plated copper or tin plated aluminium conductors without any particular protection. The dimensions and shapes of these conductors should be determined by the panel builder according to the required dielectric and temperature rise characteristics of the full connection system; typical examples are given in the installation guide.

26

Fixed version and separated accessories

Power circuit

Composition
The panel builder produces the power circuit himself. He has the possibility of integrating one of these two highly technical units. b Clusters and ngers. b Arms, clusters, ngers inside bushings.
DE30131

Cluster and finger


b The tulip type cluster has a shape which provides maximum contact surface whilst optimising heat dissipation. Moreover, in the case of short-circuit, it offers good compensation characteristics for electrodynamic forces.
Cluster and finger

b The nger is a component designed specically for the cluster, regarding its shape, tolerances and materials. Contact between the nger and the cluster is guaranteed by type testing: 1000 racking in-out operations.

DE30132

Arm, cluster, finger and bushing


b The choice of a cylindrical shape for the arm optimises the dielectric withstand and eliminates the need for additional insulation. b The cylindrical shape of the bushing provides excellent dielectric withstand. b It includes a connection terminal that can be tted with the connectors described on page 20.
Comment: Performances of the overall unit shall be controlled by the panel builder and are limited to 12 kV. Conditions of installation for both units described above are given in the installation guide. For withdrawable circuit breaker 17.5 kV, 185 mm phase-to-phase distance, field deflectors must be added on bushings.

Arm, cluster, finger and bushing

DE30133

Field deflector
b For Ur = 17.5 kV CBs with 185 mm phase-to-phase distance, the eld deectors are used to increase the dielectric withstand from 75 kV to 95 kV.

Arm, cluster, finger, bushing, busbar and field deflectors

27

Fixed version and separated accessories

Racking in and support frame

External tripping device


This circuit breaker opening kit allows the panel builders to install a mechanical tripping by any external action. Example: b To trip the circuit breaker before extracting it from the MV compartment. b To maintain the circuit breaker in open position during racked in and racked out operations.
Note: b This option is included if using of a standard screw shaft racking truck. b See installation guide for design and assembling.
DE30134

DE55182

Support frame
The support frame allows: b A xing support to be produced for the circuit breaker. Fixing to the ground is achieved using a roller kit. A drawing enables the interface to be produced between the rolling channel and the circuit breaker. b The rolling function is provided using the integrated rollers.
Note: please consult the installation guide.

Support frame

28

200158

Low voltage accessories

Opening circuit

Composition
The basic circuit breaker equipment includes a shunt trip release unit (MX).
200202

b v v v v

It may also include the following options: a second MX release, or an undervoltage release (MN), or an undervoltage release with time delay (MN + time delay unit), and a low energy release (MITOP).

Opening mechanism circuit diagram

200476EN

opening order

opening order

delayed opening order time delay unit

Circuit breaker equipped with an opening release

MX

MN

MN

200213

Shunt opening release (MX)


This enables the instant opening of the circuit breaker when energised. The permanent energising of the MX locks the circuit breaker in the open position. Characteristics supply
MX shunt opening release

V AC 50/60 Hz V DC

threshold consumption (VA or W)

24 48 100-130 200-250 24-30 48-60 100-130 200-250 0.7 to 1.1 Un (DC) 0.85 to 1.1 Un (AC) pick-up: 200 hold: 4.5

29

Low voltage accessories

Opening circuit

Undervoltage release (MN)


An undervoltage release operates to open the circuit breaker when the voltage at the terminals of the release decreases below 35% of its rated voltage, even in case of slow and gradual decrease. It doesnt operate the circuit breaker when the voltage at its terminals exceeds 70% of its rated apply voltage. The closing of the circuit breaker is possible when the values of the voltage at the terminals of the release are equal to, or higher than 85% of its rated voltage. Its closing is impossible when the voltage of the terminals is lower than 35% of its rated supply voltage. Characteristics supply
200213

MN undervoltage release

V AC 50/60 Hz V DC threshold opening closing consumption (VA or W)

24 48 100-130 200-250 24-30 48-60 100-130 200-250 0.35 to 0.7 Un 0.85 Un pick-up: 200 hold: 4.5

200214

Time delay unit for MN


To eliminate spurious tripping of the circuit breaker during momentary voltage drops MN's action is time-delayed. This function is achieved by adding an external time delay to the MN release circuit (delay is ajustable). This unit is placed outside of the circuit breaker and can be inhibited by an emergency stop button to obtain instant opening.
Time delay unit for MN

Characteristics supply

V AC 50/60 Hz V DC threshold opening closing consumption (VA or W) time delay

48-60 48-60 0.35 to 0.7 Un 0.85 Un pick-up: 200 hold: 4.5 0.5 s - 0.9 s - 1.5 s - 3 s

100-130 200-250 100-130 200-250

Low energy release (MITOP)


200268

This specific coil actuates the opening mechanism of the poles to trip the circuit breaker. It is characterized by a low energy consumption. Characteristics supply threshold response time of the circuit breaker at Un

direct current 0.6 A < I < 3 A 11 ms

Any tripping caused by the Mitop release is indicated momentarily by an SDE type changeover contact. This Release Unit also includes a coil enabling the remote rearming of the SDE contact.
Comment: To use the MITOP release requires the adjustment of a time delay to be set by the protection relay in order to ensure a circuit breaker operating time of 45-50 ms. MITOP low energy release

30

Low voltage accessories

Remote control

Function
b The remote control enables remote opening and closing of the circuit breaker. b In the case of continuous opening and closing orders, the remote control unit blocks the device in the open position as standard: the anti-pumping function. This function gives absolute priority to the opening order, but and also it stops closing order and thus avoids the device being locked in an indefinite opening-closing cycle: v the opening and closing coils may be fed power on a constant basis to achieve an electrical type locking: there is no self-breaking contact inside the device, v the interlocking between the opening and closing orders, whatever their causes, is achieved as standard within the device's control mechanism. Remote control circuit diagram
200485EN 200203

Circuit breaker equipped with remote control


charged springs opening order closing order ready to close open closed

MCH PF MX CH XF OF OF OF

Composition
b The remote control comprises: v electrical motor and associated mechanism (MCH) equipped with a spring-loaded limit switch (CH), v two shunt trip releases: - a closing release (XF), - an opening release (MX). b It can be added with: v a ready to close contact PF, v a second block of 4 contacts for indication of the O/C position of the device.

31

Low voltage accessories

Remote control

Electric motor (MCH)


The MCH unit arms and rearms the energy storage springs as soon as the circuit breaker is closed. This enables instant reclosing of the device after opening. The arming lever is only used as back up control in the absence of an auxiliary voltage. The MCH is equipped as standard with a CH limit switch. This contact indicates the armed position of the mechanism (spring charged). Characteristics supply
200215

V AC 50/60 Hz V DC

threshold consumption (VA or W) motor overcurrent charging time switching rate CH contact

48-60 100-130 200-240 24-30 48-60 100-125 200-250 0.85 to 1.1 Un 180 2 to 3 In during 0.1 s 6 s. max. 3 cycles per minute max. 10 A at 240 V

Shunt release (XF and MX)


Closing release (XF)
This enables the remote closing of the circuit breaker when the control mechanism is charged.
200213

Opening release (MX)


This enables the opening of the circuit breaker when energised. Characteristics XF/MX supply V AC 50/60 Hz V DC threshold consumption (VA or W)

Shunt release XF/MX

24 48 24-30 48-60 0.85 to 1.1 Un (DC/AC) pick-up: 200 hold: 4.5

100-130 200-250 100-130 200-250 pick-up: 200 hold: 4.5

32

Low voltage accessories

Indication

Open/closed position contacts (OF)


These contacts indicate the open or closed position of the circuit breaker. b Rotary type change over contacts directly driven by the circuit breaker mechanism. b The indicator contacts are proposed: v in standard use for a relaying application, v in low level use for control of plcs or electronic circuits. This version is compatible with the Sepam series 20-40 unit. Characteristics delivered as standard maximum quantity breaking capacity (A) cos : 0.3 AC12/DC12
200217

Rotary type O/C position contacts

standard V AC

V DC

240-380 480 690 24-48 125 250 24-48 240 380 24-48 125 250

low level V AC

V DC

4 8 min. load: 100 mA/24 V 10/6* 10/6* 6 10/6* 10/6* 3 min. load: 2 mA/15V DC 6 6 3 6 6 3

* standard contacts: 10 A; optional contacts: 6 A (temperature derating)

200218

Ready to close contact (PF)


b The ready to close position of the circuit breaker is indicated by a mechanical indicator and a changeover contact PF. b This information simultaneously indicates that: v the circuit breaker is open, v the stored energy springs are charged, v there is no permanent closing order, v there is no permanent opening order which could be caused by: - safety opening order (2nd MX or MN) - device locked in the open position with a key lock. Characteristics delivered as standard maximum quantity breaking capacity (A) cos : 0.3 AC12/DC12

Ready to close contacts

standard V AC

V DC

240-380 480 690 24-48 125 250 24-48 240 380 24-48 125 250

low-level V AC

V DC

0 1 min. load: 100 mA/24 V 5 5 3 3 0.3 0.15 min. load: 2 mA/15V DC 3 3 3 3 0.3 0.15

200216

Operation counter (CDM)


The operation counter is visible on the front face. It displays the number of operating cycles that the device performs.
Operation counter

33

Low voltage accessories

Low voltage plug, socket and terminal blocks

The fixed circuit breaker delivered with the mounted low voltage plug & socket or with the low voltage terminal blocks. The withdrawable circuit breaker( full version) is always supplied with the low voltage plug & socket.
DE30152

Low voltage terminal blocks


b Main functions This block allow you to connect and supply the low voltage auxiliaries.

Low voltage terminal blocks

Low voltage plug and socket


b Main functions This plug and socket system provides an auxiliary supply connection with a high level of electrical safety. b Interlocking function It is possible to connect and disconnect the plug only if the breaker is in racked out position. It is not possible during the racking in operation.

Two versions of plug and socket


DE30127

An 18 pin version
This version allows you to connect: b For remote control v 1 electric motor, v 1 shunt closing release, v 1 shunt opening release, v 1 contact ready to close. b For auxiliary contacts v 2 changeover contacts, v 1 normally-open contact, v 1 normally-closed contact.

Plug and socket 18 pin version

A 42 pin version
This version allows you to connect: b For remote control v 1 electric motor, v 1 shunt closing release, v 2 shunt opening releases or 1 shunt opening release + 1 undervoltage release, v 1 contact ready to close, v 1 low energy release, v 1 fault-trip indication contact, v 1 SDE contact remote reset. b For auxiliary contacts v 2 changeover contacts, v 5 normally-open contacts, v 4 normally-closed contacts.
Plug and socket 42 pin version
DE30128

34

Low voltage accessories

Locking/Interlocking

200219

DE30135

Push button disabling


Push button disabling

This transparent screen prevents access to the circuit breaker opening and closing push buttons. The device enables independent locking of the opening or closing button, it is often associated with an electrical motor (MCH). b Locking is achieved either by: v 2 screws, v 3 padlocks, not supplied, v sealing.

200200

200270

Padlocking the circuit breaker in open position

Padlocking
200201

200269

Sealing

Locking of the circuit breaker in the open position


b The circuit breaker is locked in the open position by blocking the opening push button in the pushed-in position: v using padlocks: 1 to 3 padlocks not supplied, v using key locks: 1 or 2 different key locks supplied. b The key locks are of Profalux or Ronis type captive keys, that become free once locked, and are offered according to the following options, either: v 1 single key lock, v 1 single key lock mounted on the device + 1 identical one delivered, separately for interlocking with another device, v 2 different key locks for double locking. b Profalux and Ronis key locks are inter-compatible.

Key locking the circuit breaker in open position

DE30136

Cubicle door interlocking mechanism

RONIS

Cubicle door interlocking mechanism


b The device allows C.B. operation only when the door is closed for full version with truck.

35

Dimensions

Full version

Phase distance between poles 145 mm


circuit breakers 7P1-630 7P1-1250 12P1-630 12P1-1250
DE30137 DE30140 DE30141 DE30140

Phase distance between poles 185 mm


circuit breakers 7P1-630 7P1-1250 7P2-630 7P2-1250 12P1-630 12P1-1250 12P2-630 12P2-1250 17P1-630 17P1-1250 17P2-630 17P2-1250
DE30138 DE30139

Phase distance between poles 240 mm


circuit breakers 7P1-2500 7P2-2500 7P3-630 7P3-1250 7P3-2500 12P1-2500 12P2-2500 12P3-630 12P3-1250 12P3-2500 17P1-2500 17P2-2500 17P3-630 17P3-1250 17P3-2500

36

Dimensions

Fixed version

Phase distance between poles 145 mm


circuit breakers 7P1-630 7P1-1250 12P1-630 12P1-1250
200108

535

470

Phase distance between poles 185 mm


circuit breakers 7P1-630 7P1-1250 7P2-630 7P2-1250 12P1-630 12P1-1250 12P2-630 12P2-1250 17P1-630 17P1-1250 17P2-630 17P2-1250
200113

535

550

Phase distance between poles 240 mm


circuit breakers 7P1-2500 7P2-2500 7P3-630 7P3-1250 7P3-2500 12P1-2500 12P2-2500 12P3-630 12P3-1250 12P3-2500 17P1-2500 17P2-2500 17P3-630 17P3-1250 17P3-2500
200116

240

240

90
200109

535

660

200109

185

185

90

200109

145

145 90

37

Personal notes

38

Personal notes

39

Personal notes

40

Schneider Electric Industries SAS


Electrical Distribution Communication MV Department F-38050 Grenoble Cedex 9 Tel.: +33 (0)4 76 57 60 60 http://www.schneiderelectric.com As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

RCS Nanterre B 954 503 439 ART.86213

Publishing: Schneider Electric Production: Headlines, Graphme Printing: Pozzo 09/2003

AMTED300015EN

This document has been printed on ecological paper

/4 2003 Schneider Electric - All rights reserved