AUTOMATIC MAINS FAILURE UNIT

KO

AMF 4.0

Therefore, the user can monitor these values as analog values on the front panel without the need to use separate gauges. The system also monitors the mains values continuously, also in sleep mode, it detects all alarm conditions and the last 10 alarm status can be displayed on the unit display. All configuration parameters are adjustable from the control unit menu. The user can choose to download pre-stored gauge data from the menu for well known brands and this allows easy tuning of the control unit for any generator application.

FEATURES DESCRIPTION
AMF 4.0 series genset control units are designed and manufactured according to CE regulations and offers automatic engine starting, stopping, metering and generator protection and transfer switch operations. The system provides full AMF (Auto mains Failure) functions. It can be operated in Automatic, Test and Manual modes. The control unit has 5 digital displays (each display has 3 digit 7segment LED display), which allows all the measured engine and alternator values to be monitored simultaneously. This makes the classical analog type panel meters redundant, hence saving cost and introducing very accurate reading of all engine and alternator data. The following digital data can be monitored from the front panel of the unit: Three phase mains and generator voltage sensing (true rms) Three phase generator current (true rms A, KA) Mains and generator frequency (Hz) DC battery voltage (DC volts) Oil pressure (bar) Engine temperature (Celsius or Fahrenheit) Engine working hour time (Hour) Oil pressure and temperature sensors can either be of analog type or switch type. By means of analog sensors, engine control and monitoring can be made more accurately. The engine oil pressure and coolant temperature values are also displayed in analog bar-graph displays as well as digital displays.
EN-KO Electronic Control Systems
10006 Sok. No:64 A.O.S.B Cigli-zmir/TURKIYE Tel: +90 (232) 3767806 (Pbx) Fax: +90 (232) 3767792 E-Mail: info@enkoelektronik.com Web: www.enkoelektronik.com

AMF 4.0 E.003.R0 Specifications are subject to change without notice.

Automatic and Manual start/stop sequence for diesel engines Automatic control of mains (MCB) and generator (GCB) circuit breakers Mains monitoring, automatic start, stop and transfer switch functions True RMS voltage and current measurements for mains and generator Failure monitoring and control Pre-glow heater control Manuel, automatic and test modes Five 3-digit, 7 segment LED digital measurement displays Recording of the last 10 failure alarms Operating hours and service hours timing functions Analog engine temperature and oil pressure measurement and display Adjustable operating modes and timings via extensive parameter menu Special calibration menu for all analog measurement inputs Remote Start control input High reliability concept design (MTBF > 50.000 hours) CE compliant design and production

AMF 4.0 AUTOMATIC MAINS FAILURE


PROTECTION FUNCTIONS
Engine start/stop failure Over/Under engine speed failure Over/Under alternator voltage failure Over/Under frequency protection Over current (overload) failure High engine temperature failure Charge alternator failure warning Low oil pressure failure Periodic service time warning Auxiliary input failure INPUTS / OUTPUTS 3 phase mains voltage measurement inputs 3 phase generator voltage measurement inputs 3 phase generator current measurement inputs 12 / 24 Vdc battery supply input Engine oil pressure analog input Engine coolant temperature analog input Engine oil pressure and temperature switch input Charge alternator input Cranking relay output Pre-glow heater relay output Fuel solenoid relay output Generator circuit breaker (GCB) relay output Mains circuit breaker (MCB) relay output Alarm relay output 2 programmable auxiliary relay output 2 programmable auxiliary relay input
Mounting Installation Measurement Accuracy Charge Excitation Current Housing Protection Class Weight Dimensions (WxHxD) Panel Cut Out Voltage Measurement Frequency Measurement Current Measurement Connection Relay Outputs Power Supply Operating Temperature Relative Humidity

SPECIFICATIONS
9-35VDC 140 mA (relays in off position) -10C / +70C 10% - 95% non-condensing Cranking, fuel solenoid, alarm, preheat and auxiliary relays; contact rating max. 12V/24VDC 5 A, Mains and Generator contactor relays contact rating max. 250VAC/10 A 20 - 300VAC 1.0 Hz 99.0 Hz .../5 A current inputs (current transformer should be used) Screw type terminal sockets Phase voltages : 2% Frequency : 0.1Hz 80mA @ 12VDC 160mA@ 24VDC High temperature proof PPO GF %20 IP 52 (Front side) 600 gr. (aprox.) 192x144x62 mm 186x138 mm Front panel mounted with rear metal screw fixings Max. allowable mounting panel thickness 3mm

EN-KO Electronic Control Systems


10006 Sok. No:64 A.O.S.B Cigli-zmir/TURKIYE Tel: +90 (232) 3767806 (Pbx) Fax: +90 (232) 3767792 E-Mail: info@enkoelektronik.com Web: www.enkoelektronik.com

AMF 4.0 AUTOMATIC MAINS FAILURE


CONNECTION DIAGRAM

AMF 4.0 CONNECTION DIAGRAM


LOAD MAINS R S T N R S T N GENERATOR U V W N

11

22 23 24 25 14
Generator Contactor Relay Mains Contactor Relay Power Supply

12

26 27 28 29 13

30 31

Generator Current Inputs

32 33 34 35

AMF 4.0
15 7 8
Configurable output 1 (Default Horn)

2 1

3
Emergency Stop

9
Configurable output 2

10
Configurable output 3

20
Oil Pressure sender

21
Temperature Sender

16
Configurable Input 1 (Default Oil Pressure Switch)

17
Configurable Input 2 (Default Temperature Switch)

18

19

Com 2

PreheatingRalay

Battery

Crank

Fuel Selenoid

Crank Relay

Charge

D+WL

NEGATIVE TERMINAL OF BATTERY SHOULD BE GROUNDED

MOUNTING AND INSTALLATIONS

Dimensions in mm

EN-KO Electronic Control Systems


10006 Sok. No:64 A.O.S.B Cigli-zmir/TURKIYE Tel: +90 (232) 3767806 (Pbx) Fax: +90 (232) 3767792 E-Mail: info@enkoelektronik.com Web: www.enkoelektronik.com

Configurable Input 3

Configurable Input 4