MCAC-UTSM-2008-11

Contents

Part 1 General Information .................................................................................................... 1 Part 2 Indoor Units ................................................................................................................. 7 Part 3 Outdoor Units........................................................................................................... 161 Part 4 Installation................................................................................................................ 199 Part 5 Control ...................................................................................................................... 208

The specifications, designs, and information in this book are subject to change without notice for product improvement.

Contents

MCAC-UTSM-2008-11

General Information

Part 1 General Information


1. Model Names of Indoor/Outdoor Units ....................... 2 2. External Appearance.................................................... 3
2.1 Indoor Units ................................................................................. 3 2.2 Outdoor Units .............................................................................. 4

3. Nomenclature ............................................................... 5 4. Features ........................................................................ 6

General Information

Model Names of Indoor/Outdoor Units

MCAC-UTSM-2008-11

1. Model Names of Indoor/Outdoor Units


Outdoor unit model Power supply (V-ph-Hz) Compressor type Compressor brand Matched indoor units model MCA-12HRN1 MOU-12HN1 220~240-1-50 ROTARY MIDEA-TOSHIBA MUB-12HRN1 MTA3-12HRN1 MCA-18HRN1 MTA3-18HRN1 MOUA-18HN1 220~240-1-50 ROTARY MIDEA-TOSHIBA MHB-18HRN1 MUB-18HRN1 MCC-24HRN1 MTA3-24HRN1 MOUA-24HN1 220~240-1-50 ROTARY MIDEA-TOSHIBA MHB-24HRN1 MUB-24HRN1 MCC-30HRN1 MTA3-30HRN1 MOU-30HN1 220~240-1-50 SCROLL SANYO MUB-30HRN1 MHB-30HRN1 MCC-30HRN1-R MTA3-30HRN1 MOU-30HN1-R 380~415-3-50 SCROLL SANYO MUB-30HRN1 MHB-30HRN1 MCC-36HRN1 MTA3-36HRN1 MOU-36HN1 220~240-1-50 SCROLL SANYO MUB-36HRN1 MHB-36HRN1 MCC-36HRN1-R MTA3-36HRN1 MOU-36HN1-R 380~415-3-50 SCROLL SANYO MUB-36HRN1 MHB-36HRN1 MCC-48HRN1-R MTA3-48HRN1-R MOUA-48HN1-R 380~415-3-50 SCROLL DAIKIN MHB-48HRN1 MUB-48HRN1-R MCC-60HRN1 MOUA-60HN1-R 380~415-3-50 SCROLL SANYO MTA-60HRN1-R MUB-60HRN1-R

General Information

MCAC-UTSM-2008-11

External Appearance

2. External Appearance
2.1 Indoor Units
Four-way cassette type (compact) Four-way cassette type

Duct type (18000~48000Btu/h)

Duct type (60000Btu/h)

High static pressure duct type (18000~36000Btu/h)

High static pressure duct type (48000Btu/h)

Ceiling & floor type

Ceiling & floor type

Duct type (12000Btu/h)

General Information

External Appearance

MCAC-UTSM-2008-11

2.2 Outdoor Units


12,000Btu/h 18,000Btu/h

24,000Btu/h

30,000~36,000Btu/h

48,000Btu/h

60,000Btu/h

General Information

MCAC-UTSM-2008-11

Nomenclature

3. Nomenclature
3.1 Indoor Unit M C C - 48 H R N1 - R

Power Supply R 380~415V, 3N, 50Hz -- 220~240V, 1N, 50Hz Refrigerant Type N1 R410A Control Mode W Wired Control Function Code C Cooling Only H Cooling & Heating Capacity (1000Btu/h) Product Series A Time A Designed C Time C Designed

R Remote Control

B Time B Designed

Indoor Unit Type T Duct H High Static Pressure Duct C Cassette U Ceiling & Floor Midea

3.2 Outdoor Unit

M O U A - 48 H N1 - R
Power Supply R 380V~415V, 3N, 50Hz -- 220~240V, 1N, 50Hz Refrigerant Type N1 R410A

Function Code C Cooling Only H Cooling & Heating Capacity (1000Btu/h) Product Series A Time A Designed B Time B Designed Universal Outdoor Unit O Outdoor unit U Universal Midea

General Information

Features

MCAC-UTSM-2008-11

4. Features
1. High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins.

2. Anti-rust, 500 hours salt spray test. 3. Low operation sound level: Well-known stable and quiet running fan motor. 4. Well-known compressor. 5. Compact design: Smaller dimension and larger stuffing capacity. 6. Universal outdoor unit design. 7. Optional air outlet grille: plastic type and wire type.

Wire type 8. Optional low temperature cooling module. 9. R410A environment friendly refrigerant.

Plastic type

Plastic type

General Information

MCAC-UTSM-2008-11

Indoor Units

Part 2 Indoor Units


Four-way Cassette Type (Compact) ................................ 8 Four-way Cassette Type ................................................ 21 Duct Type ........................................................................ 57 High Static Pressure Duct Type .................................... 94 Ceiling & Floor Type..................................................... 126

Indoor Units

Four-way Cassette Type (Compact)

MCAC-UTSM-2008-11

Four-way Cassette Type (Compact)


1. Features ..................................................................................................... 9 2. Specifications .......................................................................................... 10 3. Dimensions ...............................................................................................11 4. Service Space ...........................................................................................11 5. Wiring Diagram ........................................................................................ 12 6. Air Velocity and Temperature Distributions .......................................... 13 7. Capacity Tables ....................................................................................... 14 8. Electric Characteristics .......................................................................... 16 9. Sound Levels ........................................................................................... 16 10. Exploded View ....................................................................................... 17 11. Accessories ........................................................................................... 18 12. The Specification of Power................................................................... 18 13. Field Wiring ............................................................................................ 19

Indoor Units

MCAC-UTSM-2008-11

Features

1. Features
(1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment (2) Efficient cooling ---Equal, fast and widerange cooling

(3) The adoption of the most advanced 3-Dimensional Screw Fan ---Reduces the air resistance passing through ---Smoothes the air flow ---Makes air speed distribution to the heat exchange uniform

(4) Improvement for easy installation and maintenance ---Little space is required for installation into a shallow ceiling ---Because of the compactness and weight reduction of the main unit and panel, all models can be installed without a hoist

Indoor Units

Specifications

MCAC-UTSM-2008-11

2. Specifications
Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow (Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD)(body) Packing (WHD)(body) Indoor unit Dimension (WHD)(panel) Packing (WHD)(panel) Net/Gross weight(body) Net/Gross weight(panel) Refrigerant type Design pressure Refrigerant piping Liquid side/ Gas side MPa mm mm mm mm mm
2 2 2

MCA-12HRN1 220042002960 V-ph-Hz kW W kW W 220~240-1-50 3.2 1100 4 1050 YDK45-4F Welling W uF r/min 56.7/51.5/44.4 1.5uF/450V 930/845/680 2 mm mm 2113.37 1.4 Hydrophilic aluminium mm mm
3

MCA-18HRN1 220042001870 220~240-1-50 5.3 1900 6 1900 YDK45-4F Welling 56.7/51.5/44.4 2.5uF/450V 930/845/680 2 2113.37 1.4 Hydrophilic aluminium 7 Inner grooved copper tube 124721026.74 5 860/760/500 44/41/38 580254580 750340745 65030650 715115715 21/27 3/5 R410A 4.4/2.6 6.4/12.7 OD25 32.5 52.5 1-core shield wire 10.5 R11HG/E(standard) 17-30

Heating

7 Inner grooved copper tube 124721026.74 5

m /h dB(A) mm mm mm mm kg kg

680/600/400 41/38/35 580254580 750340745 65030650 715115715 21/28 3/5 R410A 4.4/2.6 6.4/12.7 OD25 32.5 52.5 1-core shield wire 10.5 R11HG/E(standard) 17-30

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring Controller Operation temperature

Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

10

Indoor Units

MCAC-UTSM-2008-11

Dimensions

3. Dimensions

4. Service Space

Indoor Units

11

Wiring Diagram

MCAC-UTSM-2008-11

5. Wiring Diagram

12

Indoor Units

MCAC-UTSM-2008-11

Air Velocity and Temperature Distributions

6. Air Velocity and Temperature Distributions


Airflow velocity

Temperature

Indoor Units

13

Capacity Tables

MCAC-UTSM-2008-11

7. Capacity Tables
7.1 Cooling Capacity MCA-12HRN1
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC SC Input TC SC Input TC SC Input 21C 3.30 2.44 0.91 3.39 2.54 0.97 3.46 2.56 0.99 3.52 2.99 1.03 Outdoor conditions (DB) 28C 35C 3.14 2.98 2.41 2.38 0.99 1.03 3.23 3.07 2.52 2.49 1.03 1.08 3.20 3.30 2.54 2.50 1.10 1.05 3.39 2.95 1.08 3.33 2.93 1.16 43C 2.85 2.39 1.07 2.88 2.42 1.13 2.98 2.44 1.16 3.07 2.86 1.20

24/17C DB/WB

27/19C DB/WB

32/23C DB/WB

MCA-18HRN1
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 5.46 4.04 1.58 5.62 4.21 1.67 5.72 4.24 1.71 5.83 4.96 1.79 Outdoor conditions (DB) 28C 5.19 4.00 1.71 5.35 4.18 1.79 5.46 4.20 1.81 5.62 4.89 1.86 35C 4.93 3.94 1.79 5.09 4.12 1.86 5.30 4.13 1.90 5.51 4.85 2.00 43C 4.72 3.96 1.84 4.77 4.01 1.96 4.93 4.04 2.00 5.09 4.73 2.07

14

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

7.2 Heating Capacity MCA-12HRN1


Heating Indoor Conditions (DB) 15C (kW) TC Input 20C TC Input 27C TC Input 24/18C DB/WB 5.20 1.13 5.04 1.24 4.72 1.31 Outdoor conditions 7/6C DB/WB 4.20 0.98 4.00 1.05 3.76 1.13 2/1C DB/WB 3.44 0.84 3.24 0.92 3.04 1.00 -5/-6C DB/WB 3.12 0.79 3.04 0.85 2.96 0.92

MCA-18HRN1
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC: Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 7.80 2.05 7.56 2.24 7.08 2.38 Outdoor conditions 7/6C DB/WB 6.30 1.77 6.00 1.90 5.64 2.05 2/1C DB/WB 5.16 1.52 4.86 1.67 4.56 1.81 -5/-6C DB/WB 4.68 1.43 4.56 1.54 4.44 1.67

Indoor Units

15

Electric Characteristics

MCAC-UTSM-2008-11

8. Electric Characteristics
Model MCA-12HRN1 Indoor Units Hz 50 Voltage 220-240V Min. 198V 198V Max. 254V 254V Power Supply MCA 0.33 0.33 MFA 25 25 Indoor Fan Motor kW 0.045 0.045 FLA 0.264 0.264

MCA-18HRN1 50 220-240V Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A)

9. Sound Levels
FOUR-WAY CASSETTE TYPE

1.0m

Microphone

Model MCA-12HRN1 MCA-18HRN1

Noise level dB(A) H 41 44 M 38 41 L 35 38

16

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10. Exploded View


MCA-12HRN1 MCA-18HRN1

10.5

No. 1 2 3 4 5 6 7 8 9 10 10.1 10.2 10.3 10.4 10.5

Part Name Drainage pan ass'y Centrifugal fan Installation bracket Evaporator fixing hanger Motor Motor base Base ass'y Board Sealed board ass'y E-part box ass'y Main controller ass'y Motor capacitor Wire joint, 7p Wire joint Transformer

Quantity 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1

No. 11 12 13 14 15 16 17 18 19 20 21 22 22.1 22.2

Part Name E-Part box cover Drain pump Holder Drain pump Right clapboard ass'y Partition board Evaporator fixing board ass'y Evaporator ass'y Evaporator temp. sensor ass'y Room temp. sensor ass'y Remote controller Remote controller holder Panel ass'y Swing motor Display board

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Indoor Units

17

Accessories

MCAC-UTSM-2008-11

11. Accessories
Name 1. Expansible hook Installation fittings 2. Installation hook 3. Installation paper board 4. Out-let pipe sheath 5. Out-let pipe clasp 6. Tightening band 7. Drain joint Shape Quantity 4 4 1 1 1 20 1

Drainpipe Fittings

8. Remote controller Remote controller & Its holder

9. Remote controller holder 10. Mounting screw(ST2.910-C-H) 11. Alkaline dry batteries (AM4) 12. Owner's manual

1 2 2 1 1

Others 13. Installation manual

12. The Specification of Power


Type Power Phase Frequency and Voltage Circuit Breaker/ Fuse (A) Indoor Unit Power Wiring (mm ) 2.5 Indoor/Outdoor Connecting Wiring Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal 52.5 1-core shield wire 10.5 52.5 1-core shield wire 10.5
2

MCA-12HRN1 1-phase 220-240V, 50Hz 40/25 32.5 2.5

MCA-18HRN1 1-phase 220-240V, 50Hz 40/25 32.5 2.5

18

Indoor Units

MCAC-UTSM-2008-11

Field Wiring

13. Field Wiring

MCA-12HRN1

Indoor Units

19

Field Wiring

MCAC-UTSM-2008-11

MCA-18HRN1

20

Indoor Units

MCAC-UTSM-2008-11

Four-way Cassette Type

Four-way Cassette Type


1. Features ................................................................................................... 22 2. Specifications .......................................................................................... 24 3. Dimensions .............................................................................................. 27 4. Service Space .......................................................................................... 28 5. Wiring Diagrams ...................................................................................... 29 6. Air Velocity and Temperature Distributions .......................................... 32 7. Capacity Tables ....................................................................................... 33 8. Electric Characteristics .......................................................................... 40 9. Sound Levels ........................................................................................... 40 10. Exploded View ....................................................................................... 41 11. Accessories ........................................................................................... 55 12. The Specification of Power................................................................... 55 13. Field Wiring ............................................................................................ 56

Indoor Units

21

Features

MCAC-UTSM-2008-11

1. Features
(1) Ultra thin machine body to easy installation and maintenance. 24K:230mm, 30-48K:300mm.

(2) Different color panels to choose: White, Gray, Blue, Black

(3) The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees.

(4) 4 speeds available, optional super high fan speed design, suitable for the large building over 3m high.

(5) Adding digital tube displaying on the display board. LED can display the Error Code to make the malfunction checking easier.

(6) Reserve spaces for air side-outlet, it is available to connect duct pipe hence Air supplying from the four sides to nearby small room.

22

Indoor Units

MCAC-UTSM-2008-11

Features

(7) Stylish design is harmonious with any interior decoration and creates and elegant environment.

(8) Built-in water pump with 750mm pumping head.

(9) Fresh air makes life more healthy and comfortable.

(10) 360air flow panel : 360air flow delivery ensures uniform airflow distribution. For 60K it is standard, the others are optional.

Indoor Units

23

Specifications

MCAC-UTSM-2008-11

2. Specifications
Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow (Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD)(body) Packing (WHD)(body) Indoor unit Dimension (WHD)(panel) Packing (WHD)(panel) Net/Gross weight(body) Net/Gross weight(panel) Refrigerant type Design pressure Refrigerant piping Liquid side/Gas side MPa mm mm mm mm mm
2 2 2

MCC-24HRN1 220042500390 V-ph-Hz kW W kW W 220~240-1-50 7.1 2474 7.6 2428 YDK80-6E Welling W uF r/min 120/110/100/90 3.5uF/450V 800/670/550/400 2 mm mm 2113.37 1.5 Hydrophilic aluminum mm mm
3

MCC-30HRN1 220042600250 220~240-1-50 9.0 3191 9.5 3369 YDK90-6E Welling 165/143/116/100 3.5uF/450V 840/770/640/550 2 2113.37 1.5 Hydrophilic aluminium 7 Inner grooved copper tube 199025226.74 12 1538/1296/1124 44/42.5/41 840300840 955317955 95055950 1035901035 35/42 6/9 R410A 4.4/2.6 12.7/19 OD32 34.0 32.5 1-core shield wire 10.5 R05/BGE(standard)

Heating

7 Inner grooved copper tube 199016826.74 8

m /h dB(A) mm mm mm mm kg kg

1220/1010/822 42/40.5/39 840230840 955247955 95055950 1035901035 29/36 6/9 R410A 4.4/2.6 9.5/15.9 OD32 34.0 32.5 1-core shield wire 10.5 R05/BGE(standard)

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

24

Indoor Units

MCAC-UTSM-2008-11

Specifications

Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow (Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD)(body) Packing (WHD)(body) Indoor unit Dimension (WHD)(panel) Packing (WHD)(panel) Net/Gross weight(body) Net/Gross weight(panel) Refrigerant type Design pressure Refrigerant piping Liquid side/Gas side MPa mm mm mm mm mm
2 2 2

MCC-30HRN1-R 220042600270 V-ph-Hz kW W kW W 380~415-3-50 9.0 3180 10.5 3381 YDK90-6E Welling W uF r/min 165/143/116/100 3.5uF/450V 840/770/640/550 2 mm mm 2113.37 1.5 Hydrophilic aluminum mm mm
3

MCC-36HRN1 220042700210 220~240-1-50 10.5 3763 12.0 4301 YDK90-6E Welling 165/143/116/100 3.5uF/450V 840/770/640/550 2 2113.37 1.5 Hydrophilic aluminum 7 Inner grooved copper tube 199025226.74 12 1538/1296/1124 44/42.5/41 840300840 955317955 95055950 1035901035 35/42 6/9 R410A 4.4/2.6 12.7/19 OD32 34.0 32.5 1-core shield wire 10.5 R05/BGE(standard)

Heating

7 Inner grooved copper tube 199025226.74 12

m /h dB(A) mm mm mm mm kg kg

1538/1296/1124 44/42.5/41 840300840 955317955 95055950 1035901035 35/42 6/9 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 R05/BGE(standard)

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Indoor Units

25

Specifications

MCAC-UTSM-2008-11

Model Code Power supply Capacity Cooling Input Capacity Heating Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow (Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD)(body) Packing (WHD)(body) Indoor unit Dimension (WHD)(panel) Packing (WHD)(panel) Net/Gross weight(body) Net/Gross weight(panel) Refrigerant type Design pressure Refrigerant piping Liquid side/Gas side MPa mm mm mm mm
2 2

MCC-36HRN1-R 220042700230 V-ph-Hz kW W kW W 380~415-3-50 10.5 3777 12.0 4301 YDK90-6E Welling W uF r/min 165/143/116/100 3.5uF/450V 840/770/640/550 2 mm mm 2113.37 1.5 Hydrophilic aluminum mm mm 7 Inner grooved copper tube 199025226.74 12 m /h dB(A) mm mm mm mm kg kg
3

MCC-48HRN1-R 220042800310 380~415-3-50 14 5147 15 5369 YDK90-6E Welling 165/143/116/100 3.5uF/450V 840/770/640/550 2 2113.37 1.5 Hydrophilic aluminum 7 Inner grooved copper tube 199025226.74 12 1538/1296/1124 44/42.5/41 840300840 955317955 95055950 1035901035 35/42 6/9 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 R05/BGE(standard) 17-30

MCC-60HRN1 220042900040 380-3-50 16 5904 19 6859 YDK90-6E-1 Welling 165/143/116/100 4uF/450V 840/770/640/550 3 2113.37 1.5 Hydrophilic aluminum 7 Inner grooved copper tube 208025240.11 12 1800/1480/1280 47/44/43 840300840 955317955 95055950 1035901035 32/39 6/9 R410A 4.4/2.6 12.7/19 OD32 52.5 32.5 R05/BGE(standard) 17-30

1538/1296/1124 44/42.5/41 840300840 955317955 95055950 1035901035 35/42 6/9 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 R05/BGE(standard)

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring

mm2

Controller Operation temperature

17-30

Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

26

Indoor Units

MCAC-UTSM-2008-11

Dimensions

3. Dimensions
3.1 MCC-24HRN1

3.2 MCC-30HRN1 MCC-60HRN1

MCC-30HRN1-R

MCC-36HRN1

MCC-36HRN1-R MCC-48HRN1-R

Indoor Units

27

Service Space

MCAC-UTSM-2008-11

4. Service Space
The indoor unit should be installed in a location that meets the following requirements: There is enough room for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room. The connecting pipe and drainpipe could be extracted out easily. There is no direct radiation from heaters.

28

Indoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5. Wiring Diagrams
5.1 MCC-24HRN1 MCC-30HRN1 MCC-36HRN1

Indoor Units

29

Wiring Diagrams

MCAC-UTSM-2008-11

5.2 MCC-30HRN1-R MCC-36HRN1-R

MCC-48HRN1-R

30

Indoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.3 MCC-60HRN1

Indoor Units

31

Air Velocity and Temperature Distributions

MCAC-UTSM-2008-11

6. Air Velocity and Temperature Distributions


Airflow velocity

Temperature

32

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

7. Capacity Tables
MCC-24HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 7.31 5.41 2.05 7.53 5.64 2.18 7.67 5.67 2.23 7.81 6.64 2.33 Outdoor conditions (DB) 28C 6.96 5.36 2.23 7.17 5.59 2.33 7.31 5.63 2.35 7.53 6.55 2.42 35C 6.60 5.28 2.33 6.82 5.52 2.42 7.10 5.54 2.474 7.38 6.50 2.60 43C 6.32 5.31 2.40 6.39 5.37 2.55 6.60 5.41 2.60 6.82 6.34 2.70

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 9.88 2.62 9.58 2.87 8.97 3.04 Outdoor conditions 7/6C DB/WB 7.98 2.26 7.60 2.43 7.14 2.62 2/1C DB/WB 6.54 1.94 6.16 2.14 5.78 2.31 -5/-6C DB/WB 5.93 1.82 5.78 1.97 5.62 2.14

Indoor Units

33

Capacity Tables

MCAC-UTSM-2008-11

MCC-30HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 9.27 6.86 2.65 9.54 7.16 2.81 9.72 7.19 2.87 9.90 8.42 3.00 Outdoor conditions (DB) 28C 8.82 6.79 2.87 9.09 7.09 3.00 9.27 7.14 3.03 9.54 8.30 3.13 35C 8.37 6.70 3.00 8.64 7.00 3.13 9.00 7.02 3.191 9.36 8.24 3.35 43C 8.01 6.73 3.10 8.10 6.80 3.29 8.37 6.86 3.35 8.64 8.04 3.48

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 12.35 3.64 11.97 3.98 11.21 4.21 Outdoor conditions 7/6C DB/WB 9.98 3.13 9.50 3.37 8.93 3.64 2/1C DB/WB 8.17 2.70 7.70 2.96 7.22 3.20 -5/-6C DB/WB 7.41 2.53 7.22 2.73 7.03 2.96

34

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MCC-30HRN1-R Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 9.27 6.86 2.64 9.54 7.16 2.80 9.72 7.19 2.86 9.90 8.42 2.99 Outdoor conditions (DB) 28C 8.82 6.79 2.86 9.09 7.09 2.99 9.27 7.14 3.02 9.54 8.30 3.12 35C 8.37 6.70 2.99 8.64 7.00 3.12 9.00 7.02 3.180 9.36 8.24 3.34 43C 8.01 6.73 3.08 8.10 6.80 3.28 8.37 6.86 3.34 8.64 8.04 3.47

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 13.65 3.65 13.23 3.99 12.39 4.23 Outdoor conditions 7/6C DB/WB 11.03 3.14 10.50 3.38 9.87 3.65 2/1C DB/WB 9.03 2.70 8.51 2.98 7.98 3.21 -5/-6C DB/WB 8.19 2.54 7.98 2.74 7.77 2.98

Indoor Units

35

Capacity Tables

MCAC-UTSM-2008-11

MCC-36HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.12 11.13 8.35 3.31 11.34 8.39 3.39 11.55 9.82 3.54 Outdoor conditions (DB) 28C 10.29 7.92 3.39 10.61 8.27 3.54 10.82 8.33 3.57 11.13 9.68 3.69 35C 9.77 7.81 3.54 10.08 8.16 3.69 10.50 8.19 3.763 10.92 9.61 3.95 43C 9.35 7.85 3.65 9.45 7.94 3.88 9.77 8.01 3.95 10.08 9.37 4.10

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 15.60 4.65 15.12 5.08 14.16 5.38 Outdoor conditions 7/6C DB/WB 12.60 4.00 12.00 4.30 11.28 4.65 2/1C DB/WB 10.32 3.44 9.72 3.78 9.12 4.09 -5/-6C DB/WB 9.36 3.23 9.12 3.48 8.88 3.78

36

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MCC-36HRN1-R Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.13 11.13 8.35 3.32 11.34 8.39 3.40 11.55 9.82 3.55 Outdoor conditions (DB) 28C 10.29 7.92 3.40 10.61 8.27 3.55 10.82 8.33 3.59 11.13 9.68 3.70 35C 9.77 7.81 3.55 10.08 8.16 3.70 10.50 8.19 3.777 10.92 9.61 3.97 43C 9.35 7.85 3.66 9.45 7.94 3.89 9.77 8.01 3.97 10.08 9.37 4.12

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 15.60 4.65 15.12 5.08 14.16 5.38 Outdoor conditions 7/6C DB/WB 12.60 4.00 12.00 4.30 11.28 4.65 2/1C DB/WB 10.32 3.44 9.72 3.78 9.12 4.09 -5/-6C DB/WB 9.36 3.23 9.12 3.48 8.88 3.78

Indoor Units

37

Capacity Tables

MCAC-UTSM-2008-11

MCC-48HRN1-R Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 14.42 10.67 4.27 14.84 11.13 4.53 15.12 11.19 4.63 15.40 13.09 4.84 Outdoor conditions (DB) 28C 13.72 10.56 4.63 14.14 11.03 4.84 14.42 11.10 4.89 14.84 12.91 5.04 35C 13.02 10.42 4.84 13.44 10.89 5.04 14.00 10.92 5.147 14.56 12.81 5.40 43C 12.46 10.47 4.99 12.60 10.58 5.30 13.02 10.68 5.40 13.44 12.50 5.61

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 19.50 5.80 18.90 6.34 17.70 6.71 Outdoor conditions 7/6C DB/WB 15.75 4.99 15.00 5.37 14.10 5.80 2/1C DB/WB 12.90 4.30 12.15 4.72 11.40 5.10 -5/-6C DB/WB 11.70 4.03 11.40 4.35 11.10 4.72

38

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MCC-60HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC SC Input TC SC Input TC SC Input 21C 16.48 12.20 4.90 16.96 12.72 5.20 17.28 12.79 5.31 17.60 14.96 5.55 Outdoor conditions (DB) 28C 35C 15.68 14.88 12.07 11.90 5.31 5.55 16.16 15.36 12.60 12.44 5.55 5.79 16.00 16.48 12.69 12.48 5.904 5.61 16.96 16.64 14.76 14.64 5.79 6.20 43C 14.24 11.96 5.73 14.40 12.10 6.08 14.88 12.20 6.20 15.36 14.28 6.44

24/17C DB/WB

27/19C DB/WB

32/23C DB/WB

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input 20C TC Input 27C TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 24.70 7.41 23.94 8.09 22.42 8.57 Outdoor conditions 7/6C DB/WB 19.95 6.38 19.00 6.86 17.86 7.41 2/1C DB/WB 16.34 5.49 15.39 6.04 14.44 6.52 -5/-6C DB/WB 14.82 5.14 14.44 5.56 14.06 6.04

Indoor Units

39

Electric Characteristics

MCAC-UTSM-2008-11

8. Electric Characteristics
Model MCC-24HRN1 MCC-30HRN1 MCC-30HRN1-R MCC-36HRN1 MCC-36HRN1-R MCC-48HRN1-R Indoor Units Hz 50 50 50 50 50 50 Voltage 220-240V 220-240V 380-415V 220-240V 380-415V 380-415V 380 Min. 198V 198V 342V 198V 342V 342V 342V Max. 254V 254V 418V 254V 418V 418V 418V Power Supply MCA 0.7 0.955 0.955 0.955 0.955 0.955 0.955 MFA 25 25 15 25 15 15 25 Indoor Fan Motor kW 0.065 0.090 0.090 0.090 0.090 0.090 0.090 FLA 0.56 0.8 0.8 0.8 0.8 0.8 0.8

MCC-60HRN1 50 Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A)

9. Sound Levels
FOUR-WAY CASSETTE TYPE

1.0m

Microphone

Model MCC-24HRN1 MCC-30HRN1/MCC-30HRN1-R MCC-36HRN1/MCC-36HRN1-R MCC-48HRN1-R MCC-60HRN1

Noise level dB(A) H 42 44 44 44 47 M 40.5 42.5 42.5 42.5 44 L 39 41 41 41 43

40

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10. Exploded View


10.1 MCC-24HRN1

33

Indoor Units

41

Exploded View

MCAC-UTSM-2008-11

No. 1 2 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4 5 6 7 8 8.1 8.2 8.3 8.4 9 9.1 10 11

Part Name Electricity control box coping I Electricity control box coping II E-part box ass'y E-part box Transformer Room temp. sensor ass'y Motor capacitor Main controller Wire joint Wire joint, 3p Air guide ring ass'y Foam ass'y Fan ass'y Evaporator fixing board Evaporator ass'y Evaporator Evaporator output pipe ass'y Evaporator input pipe ass'y Sleeve Board ass'y Hook Foam ass'y Board ass'y

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1

No. 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 26.1 27 28 29 30 31 32 33

Part Name Motor Base Wire clamp Panel Wire clamp Double-ended wire clip Evaporator fixing hanger Water pump board Drain pump Installation bracket ass'y Board ass'y Water pipe clamp Fan clip Water cover ass'y Board ass'y Hook Water pipe Sealed board ass'y Pump rubber washer Remote controller Installation bracket Evaporator temp. sensor Water-level sensor assy

Quantity 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 2 1 1 3 1 1 1 1

42

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.2 MCC-30HRN1

Indoor Units

43

Exploded View

MCAC-UTSM-2008-11

No. 1 2 3 3.1 3.2 3.3 3.4 3.5 4 5 6 7 8 8.1 8.2 8.3 8.4 9 10 11 12

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Part Base pan seat

Name

Quantity 1 1 1 1 1 3 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1

Electric control box head cover I Electric control box head cover II Electric control box assembly of indoor unit Electric control box welded assembly Voltage transformer Indoor temp. sensor subassembly Capacitor Four sides air outlet indoor main control plate Air inducting coils subassembly Foam subassembly ,drip tray Fan assembly Evaporator fixing board Evaporator assembly Evaporator Evaporator output tube assembly Evaporator filter assembly Barrel Front barrier I subassembly Foam seat subassembly Front barrier II subassembly Asynchronous dynamo

Base pan welded assembly Plate, wire Tandem, wire Double-ended wire clip Evaporator fixing hook Water pump baffle plate Water drain pump subassembly Water pump installation subassembly Front barrier IV subassembly Fan fins Install lifting lug Water finder cover subassembly Front barrier III subassembly Water pumping connect pipe Exhalant tube seal plate subassembly Water pump's rubber pad Remote controller Bracket, remote controller Front panel bracket

Water pump pumping pipe grommet

44

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.3 MCC-30HRN1 -R

Indoor Units

45

Exploded View

MCAC-UTSM-2008-11

No. 1 2 3 3.1 3.2 3.3 3.4 3.5 4 5 6 7 8 8.1 8.2 8.3 8.4 9 10 11 12

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Part Base pan seat

Name

Quantity 1 1 1 1 1 3 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1

Electric control box head cover I Electric control box head cover II Electric control box assembly of indoor unit Electric control box welded assembly Voltage transformer Indoor temp. sensor subassembly Capacitor Four sides air outlet indoor main control plate Air inducting coils subassembly Foam subassembly ,drip tray Fan assembly Evaporator fixing board Evaporator assembly Evaporator Evaporator output tube assembly Evaporator filter assembly Barrel Front barrier I subassembly Foam seat subassembly Front barrier II subassembly Asynchronous dynamo

Base pan welded assembly Plate, wire Tandem, wire Double-ended wire clip Evaporator fixing hook Water pump baffle plate Water drain pump subassembly Water pump installation subassembly Front barrier IV subassembly Fan fins Install lifting lug Water finder cover subassembly Front barrier III subassembly Water pumping connect pipe Exhalant tube seal plate subassembly water pump's rubber pad Remote controller Bracket, remote controller Front panel bracket

Water pump pumping pipe grommet

46

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.4 MCC-36HRN1

Indoor Units

47

Exploded View

MCAC-UTSM-2008-11

No. 1 2 3 3.1 3.2 3.3 3.4 3.5 4 5 6 7 8 8.1 8.2 8.3 8.4 9 10 11 12

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Part Base pan seat

Name

Quantity 1 1 1 1 1 3 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1

Electric control box head cover I Electric control box head cover II Electric control box assembly of indoor unit Electric control box welded assembly Voltage transformer Indoor temp. sensor subassembly Capacitor Four sides air outlet indoor main control plate Air inducting coils subassembly Foam subassembly ,drip tray Fan assembly Evaporator fixing board Evaporator assembly Evaporator Evaporator output tube assembly Evaporator filter assembly Barrel Front barrier I subassembly Foam seat subassembly Front barrier II subassembly Asynchronous dynamo

Base pan welded assembly Plate, wire Tandem, wire Double-ended wire clip Evaporator fixing hook Water pump baffle plate Water drain pump subassembly Water pump installation subassembly Front barrier IV subassembly fan fins Install lifting lug Water finder cover subassembly Front barrier III subassembly Water pumping connect pipe Exhalant tube seal plate subassembly Water pump's rubber pad Remote controller Bracket, remote controller Front panel bracket

Water pump pumping pipe grommet

48

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.5 MCC-36HRN1-R

Indoor Units

49

Exploded View

MCAC-UTSM-2008-11

No. 1 2 3 3.1 3.2 3.3 3.4 3.5 4 5 6 7 8 8.1 8.2 8.3 8.4 9 10 11 12

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Part Base pan seat

Name

Quantity 1 1 1 1 1 3 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1

Electric control box head cover I Electric control box head cover II Electric control box assembly of indoor unit Electric control box welded assembly Voltage transformer Indoor temp. sensor subassembly Capacitor Four sides air outlet indoor main control plate Air inducting coils subassembly Foam subassembly ,drip tray Fan assembly Evaporator fixing board Evaporator assembly Evaporator Evaporator output tube assembly Evaporator filter assembly Barrel Front barrier I subassembly Foam seat subassembly Front barrier II subassembly Asynchronous dynamo

Base pan welded assembly Plate, wire Tandem, wire Wire clip Evaporator fixing hook Water pump baffle plate Water drain pump subassembly Water pump installation subassembly Front barrier IV subassembly Fan fins Install lifting lug Water finder cover subassembly Front barrier III subassembly Water pumping connect pipe Exhalant tube seal plate subassembly Water pump's rubber pad Remote controller Bracket, remote controller Front panel bracket

Water pump pumping pipe grommet

50

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.6 MCC-48HRN1-R

3/3.2/3.3/3.4/3.5/3.6/3.7

34

32

Indoor Units

51

Exploded View

MCAC-UTSM-2008-11

No. 1 2 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4 5 6 7 8 8.1 8.2 8.3 8.4 9 9.1 10 11 12

Part Name Electricity control box coping I Electricity control box coping II Electric control assy subassembly E-part box Transformer Indoor temp. sensor subassembly Motor capacitor Main controller subassembly Wire joint, 6p Wire joint, 6p Guide wind circle subassembly Foam subassembly ,drip tray Wind wheel assembly Fixing board, Evaporator Evaporator assembly Evaporator Gas output pipe, evaporator, assembly Eva filter, assemby assembly Sleeve Boarding subassembly I Installation hanger Foam subassembly, Base boarding subassembly II Asynchronism motor

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1

No. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 27.1 28 29 30 31 32 33 34

Part Name Chassis pillow Chassis Ass'y Plate, wire Panel Plate, wire Double-ended wire clip Fixing hanger, evaporator Water pump baffle Drain pump Water Pump installation subassembly Boarding subassembly Water pipe clamp Clip, wind wheel water finder cover subassembly Boarding subassembly Installation hanger Extended water pipe Sealing board for pipe tie-in subassembly Rubber washer, pump Remote controller Holder Evaporator temp. sensor Water-level sensor assy

Quantity 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1

52

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.7 MCC-60HRN1

Indoor Units

53

Exploded View

MCAC-UTSM-2008-11

No. 1 1.1 1.2 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Part

Name

Quantity 1 2 1 1 1 4 1 4 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1

No. 22 23 24 25 26 27 28 29 30 31 32 33 34 34.1 34.2 34.3 34.4 34.5 34.6 34.7 35 36

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1 1 1

Panel Swing motor Display control box ass'y Foam ass'y Fan ass'y Motor gasket Fan clip Motor gasket Water pipe clamp Drain pump Water Pump installation bracket ass'y Pump rubber washer Water level sensor ass'y Water pipe Foam ass'y Remote controller Installation bracket Board ass'y Base Board ass'y Water cover ass'y Water pipe Clapboard ass'y

Sealed board ass'y Board ass'y Wire clamp Gasket Temperature sensor Temp. sensor ass'y Wire joint ass'y Evaporator ass'y Evaporator joint board ass'y Evaporator Fixing board Motor Ring ass'y E-part box ass'y Motor capacitor Transformer Wire joint, 5p Main control board ass'y E-part box Wire joint,6p Room temp sensor ass'y Wire clamp E-Part box cover

54

Indoor Units

MCAC-UTSM-2008-11

Accessories

11. Accessories
Name 1. Expansible hook Installation Fittings 2. Installation hook 3. Installation paper board 4. Bolt M5 5. Connecting pipe group Tubing & Fittings 6. Binding tape 7.Soundproof/insulation sheath 8. Out-let pipe sheath 9. Out-let pipe clasp Drainpipe Fittings 10. Tightening band 11. Drain joint 12. Seal ring 13. Wall conduit Protect Pipe Fittings 14. Wall conduit cover Shape Quantity 4 4 1 4 1 6 2 1 1 20 1 1 1 1

15. Remote controller Remote controller & Its Frame 16. Frame 17. Mounting screw(ST2.910-C-H) 18. Alkaline dry batteries (AM4) 19. Owner's manual Others 20. Installation manual

1 1 2 2 1 1

12. The Specification of Power


Type Phase Power Frequency and Voltage Circuit Breaker/ Fuse (A) 2 Indoor Unit Power Wiring (mm ) Ground Wiring Outdoor Unit Power Wiring Indoor/Outdoor Connecting 2 Wiring (mm ) Strong Electric Signal Weak Electric Signal MCC-24HRN1 1-phase 220-240V, 50Hz 40/25 34.0 4.0 34.0 32.5 1-core shield wire 10.5 MCC-30HRN1 1-phase 220-240V, 50Hz 40/25 34.0 4.0 34.0 32.5 1-core shield wire 10.5 MCC-48HRN1-R 3-phase 380-415V, 50Hz 25/15 52.5 2.5 52.5 31.0 MCC-30HRN1-R 3-phase 380-415V, 50Hz 25/15 52.5 2.5 52.5 31.0

Type Phase Power Frequency and Voltage Circuit Breaker/ Fuse (A) 2 Indoor Unit Power Wiring (mm ) Ground Wiring Outdoor Unit Power Wiring Indoor/Outdoor Strong Electric 2 Connecting Wiring (mm ) Signal Weak Electric Signal Indoor Units

MCC-36HRN1 1-phase 220-240V, 50Hz 40/25 34.0 4.0 34.0 32.5 1-core shield wire 10.5

MCC-36HRN1-R 3-phase 380-415V, 50Hz 25/15 52.5 2.5 52.5 31.0

MCC-60HRN1 3-phase 380V, 50Hz 40/25 52.5 2.5 52.5 32.5

55

Field Wiring

MCAC-UTSM-2008-11

13. Field Wiring

56

Indoor Units

MCAC-UTSM-2008-11

Duct Type

Duct Type
1. Features ................................................................................................... 58 2. Specifications .......................................................................................... 59 3. Dimensions .............................................................................................. 63 4. Service Space .......................................................................................... 65 5. Wiring Diagrams ...................................................................................... 66 6. Air Velocity and Temperature Distributions .......................................... 70 7. Capacity Tables ....................................................................................... 71 8. Electric Characteristics .......................................................................... 80 9. Sound Levels ........................................................................................... 80 10. Exploded View ....................................................................................... 81 11. Accessories ........................................................................................... 88 12. The Specification of Power................................................................... 89 13. Field Wiring ............................................................................................ 90

Indoor Units

57

Features

MCAC-UTSM-2008-11

1. Features
(1) Economic and convenient installation ---Several diffusers branch off from an indoor unit, adjusting the room temperature, which makes many rooms to be air-conditioned with only one indoor unit. ---All models feature thin design making them applicable to ceiling pocket that tends to be shallow

(2) Optional accessories ---Including front clapboard, panel, canvas air passage, filter, etc..

Canvas air passage

Clapboard

Panel (3) A long-life and high-efficiency filter

(4) Way of air intake and inserting air filter ---Air intake can be positioned either at the back or below the unit. Similarly, the air filter also can be inserted either from the back or from the bottom of the unit.

58

Indoor Units

MCAC-UTSM-2008-11

Specifications

2. Specifications
Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor external static pressure (Hi) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) Net/Gross weight Refrigerant type Design pressure Refrigerant Liquid side/ Gas side piping Drainage water pipe diameter Connection wiring Controller Power wiring Strong electric signal wiring Weak electric signal wiring MPa mm mm mm mm mm
2 2 2

MTA3-12HRN1 220086100470 V-ph-Hz kW W kW W 220~240-1-50 3.2 1100 4 1050 RPS20D Welling W uF r/min 34.5/30.5/27.3 1uF/450V 940/840/760 2 2113.37 1.5 Hydrophilic aluminium 7Inner grooved copper tube 71835026.74 4 m /h Pa dB(A) mm mm kg
3

MTA3-18HRN1 220086002290 220~240-1-50 5.3 1900 6 1900 YSK55-4D Welling 117/110/101 3uF/450V 900/800/690 2 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 80025444 2 1160/1100/1050 40 45/41/38 1000298800 1205370940 36/43 R410A 4.4/2.6 6.4/12.7 OD32 32.5 52.5 1-core shield wire 10.5 R11HG/E(standard)

Heating

mm mm

mm mm

580/490/420 10 41/38/35 870210385 1044277439 14/18 R410A 4.4/2.6 6.4/12.7 OD19 32.0 52.0 1-core shield wire 10.5 R11HG/E(standard)

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Indoor Units

59

Specifications

MCAC-UTSM-2008-11

Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor external static pressure (Hi) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) Net/Gross weight Refrigerant type Design pressure Refrigerant Liquid side/ Gas side piping Drainage water pipe diameter Power wiring Strong electric signal wiring Weak electric signal wiring MPa mm mm mm mm mm
2 2

MTA3-24HRN1 220086002450 V-ph-Hz kW W kW W 220~240-1-50 7.1 2510 7.6 2500 YSK74-4C Welling W uF r/min 170/150/133 6.5uF/450V 1100/1020/900 3 mm mm 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 80025466 3 m /h Pa dB(A) mm mm kg
3

MTA3-30HRN1 220086003740 220~240-1-50 9 3270 9.5 3232 YSK59-4A(2) Welling 104/87/78(2) 4uF/450V 840/695/610 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 115025466 5 2070/1950/1860 70 49/47/44 1350298800 1555370940 48/57 R410A 4.4/2.6 12.7/19 OD32 34.0 31.0 3-core cable wire 1-core shield wire 10.5 R11HG/E(standard)

Heating

mm mm

1460/1400/1350 40 49/45/42 1000298800 1205370940 38/45 R410A 4.4/2.6 9.5/15.9 OD32 32.5 31.0 1-core shield wire 10.5 R11HG/E(standard)

Connection wiring

Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

60

Indoor Units

MCAC-UTSM-2008-11

Specifications

Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor external static pressure (Hi) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) Net/Gross weight Refrigerant type Design pressure Refrigerant Liquid side/ Gas side piping Drainage water pipe diameter Power wiring Strong electric signal wiring Weak electric signal wiring MPa mm mm mm mm mm
2 2

MTA3-30HRN1 220086003745 V-ph-Hz kW W kW W 380-3-50 9 3250 10.5 3250 YSK59-4A(2) Welling W uF r/min 104/87/78(2) 2.5uF/450V 840/695/610 3 mm mm 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 115025466 5 m /h Pa dB(A) mm mm kg
3

MTA3-36HRN1 220086002560 220~240-1-50 10.5 3750 12 3720 YSK59-4A(2) Welling 104/87/78(2) 4uF/450V 840/695/610 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 115025466 5 2070/1950/1860 70 49/47/44 1350298800 1555370940 48/57 R410A 4.4/2.6 12.7/19 OD32 34.0 31.0 3-core cable wire 1-core shield wire 10.5 R11HG/E(standard)

Heating

mm mm

2070/1950/1860 70 49/47/44 1350298800 1555370940 48/57 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 3-core cable wire R11HG/E(standard)

Connection wiring

Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Indoor Units

61

Specifications

MCAC-UTSM-2008-11

Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits W uF r/min V-ph-Hz kW W kW W

MTA3-36HRN1 220086002565 380-3-50 10.5 3700 12 3350 YSK59-4A(2) Welling 104/87/78(2) 2.5uF/450V 840/695/610 3 mm mm 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 115025466 5 m /h Pa dB(A) mm mm kg
3

MTA3-48HRN1-R 220086002655 380~415-3-50 14 4700 15 4900 YSK59-4A(2) Welling 104/87/78(2) 4uF/450V 840/695/610 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 115025466 5 2400/2300/2200 70 51/47/44 1350298800 1555370940 48/57 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 3-core cable wire R11HG/E(standard)

MTA-60HRN1-R 220086003860 380~415-3-50 16 6000 19 5564 YSK160-4 YONGAN 324/264/223/186 10uF/450V 870/770/700/630 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 114625466 6 2800/2700/2600 100 52/48/46 1350320800 1555420930 62/72 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 3-core cable wire R11HG/E(standard)

Heating

mm mm

Indoor air flow(Hi/Mi/Lo) Indoor external static pressure (Hi) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) Net/Gross weight Refrigerant type Design pressure Refrigerant Liquid side/ Gas piping side Drainage water pipe diameter Power wiring Strong electric signal wiring Weak electric signal wiring

2070/1950/1860 70 49/47/44 1350298800 1555370940 48/57 R410A

MPa mm mm mm mm mm
2 2

4.4/2.6 12.7/19 OD32 52.5 31.0 3-core cable wire R11HG/E(standard)

Connection wiring

Controller

Operation temperature 17-30 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

62

Indoor Units

MCAC-UTSM-2008-11

Dimensions

3. Dimensions
3.1 MTA3-12HRN1
380

Air Outlet

220 175

210

102

87

55

25

715 870
Refrigerant pipe

Drain port

63
? 25 Refrigerant pipe Liquid Side 9.53

Gas Side 19.0


915 870

148
100 >250mm

? 100
268 380
Fresh air inlet

>500mm

3.2 MTA3-18HRN1

MTA3-24HRN1

Indoor Units

210

>500mm

63

Dimensions

MCAC-UTSM-2008-11

3.3 MTA3-30HRN1

MTA3-36HRN1

MTA3-48HRN1-R

3.4 MTA-60HRN1-R

64

Indoor Units

MCAC-UTSM-2008-11

Service Space

4. Service Space
Ensure enough space required for installation and maintenance.

Indoor Units

65

Wiring Diagrams

MCAC-UTSM-2008-11

5. Wiring Diagrams
5.1 MTA3-12HRN1

66

Indoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.2 MTA3-18HRN1

Indoor Units

67

Wiring Diagrams

MCAC-UTSM-2008-11

5.3 MTA3-24HRN1

MTA3-30HRN1

MTA3-36HRN1 (1 phase)

68

Indoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.4 MTA3-30HRN1

MTA3-36HRN1

MTA3-48HRN1-R MTA-60HRN1-R (3 phase)

Indoor Units

69

Air Velocity and Temperature Distributions

MCAC-UTSM-2008-11

6. Air Velocity and Temperature Distributions


Discharge angle 60
Airflow velocity

Temperature

70

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

7. Capacity Tables
MTA3-12HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 3.30 2.44 0.91 3.39 2.54 0.97 3.46 2.56 0.99 3.52 2.99 1.03 Outdoor conditions (DB) 28C 3.14 2.41 0.99 3.23 2.52 1.03 3.30 2.54 1.05 3.39 2.95 1.08 35C 2.98 2.38 1.03 3.07 2.49 1.08 3.20 2.50 1.10 3.33 2.93 1.16 43C 2.85 2.39 1.07 2.88 2.42 1.13 2.98 2.44 1.16 3.07 2.86 1.20

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 5.20 1.13 5.04 1.24 4.72 1.31 Outdoor conditions 7/6C DB/WB 4.20 0.98 4.00 1.05 3.76 1.13 2/1C DB/WB 3.44 0.84 3.24 0.92 3.04 1.00 -5/-6C DB/WB 3.12 0.79 3.04 0.85 2.96 0.92

Indoor Units

71

Capacity Tables

MCAC-UTSM-2008-11

MTA3-18HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 5.46 4.04 1.58 5.62 4.21 1.67 5.72 4.24 1.71 5.83 4.96 1.79 Outdoor conditions (DB) 28C 5.19 4.00 1.71 5.35 4.18 1.79 5.46 4.20 1.81 5.62 4.89 1.86 35C 4.93 3.94 1.79 5.09 4.12 1.86 5.30 4.13 1.90 5.51 4.85 2.00 43C 4.72 3.96 1.84 4.77 4.01 1.96 4.93 4.04 2.00 5.09 4.73 2.07

Heating
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 7.80 2.05 7.56 2.24 7.08 2.38 Outdoor conditions 7/6C DB/WB 6.30 1.77 6.00 1.90 5.64 2.05 2/1C DB/WB 5.16 1.52 4.86 1.67 4.56 1.81 -5/-6C DB/WB 4.68 1.43 4.56 1.54 4.44 1.67

72

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MTA3-24HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 7.31 5.41 2.08 7.53 5.64 2.21 7.67 5.67 2.26 7.81 6.64 2.36 Outdoor conditions (DB) 28C 6.96 5.36 2.26 7.17 5.59 2.36 7.31 5.63 2.38 7.53 6.55 2.46 35C 6.60 5.28 2.36 6.82 5.52 2.46 7.10 5.54 2.51 7.38 6.50 2.64 43C 6.32 5.31 2.43 6.39 5.37 2.59 6.60 5.41 2.64 6.82 6.34 2.74

Heating
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 9.88 2.70 9.58 2.95 8.97 3.13 Outdoor conditions 7/6C DB/WB 7.98 2.33 7.60 2.50 7.14 2.70 2/1C DB/WB 6.54 2.00 6.16 2.20 5.78 2.38 -5/-6C DB/WB 5.93 1.88 5.78 2.03 5.62 2.20

Indoor Units

73

Capacity Tables

MCAC-UTSM-2008-11

MTA3-30HRN1 (1 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 9.27 6.86 2.71 9.54 7.16 2.88 9.72 7.19 2.94 9.90 8.42 3.07 Outdoor conditions (DB) 28C 8.82 6.79 2.94 9.09 7.09 3.07 9.27 7.14 3.11 9.54 8.30 3.20 35C 8.37 6.70 3.07 8.64 7.00 3.20 9.00 7.02 3.27 9.36 8.24 3.43 43C 8.01 6.73 3.17 8.10 6.80 3.37 8.37 6.86 3.43 8.64 8.04 3.56

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 12.35 3.49 11.97 3.81 11.21 4.04 Outdoor conditions 7/6C DB/WB 9.98 3.01 9.50 3.23 8.93 3.49 2/1C DB/WB 8.17 2.59 7.70 2.84 7.22 3.07 -5/-6C DB/WB 7.41 2.42 7.22 2.62 7.03 2.84

74

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MTA3-30HRN1 (3 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC SC Input TC SC Input TC SC Input 21C 9.27 6.86 2.70 9.54 7.16 2.86 9.72 7.19 2.93 9.90 8.42 3.06 Outdoor conditions (DB) 28C 35C 8.82 8.37 6.79 6.70 2.93 3.06 9.09 8.64 7.09 7.00 3.06 3.19 9.00 9.27 7.14 7.02 3.25 3.09 9.54 9.36 8.30 8.24 3.19 3.41 43C 8.01 6.73 3.15 8.10 6.80 3.35 8.37 6.86 3.41 8.64 8.04 3.54

24/17C DB/WB

27/19C DB/WB

32/23C DB/WB

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input 24/18C DB/WB 13.65 3.51 13.23 3.84 12.39 4.06 Outdoor conditions 7/6C DB/WB 11.03 3.02 10.5 3.25 9.87 3.51 2/1C DB/WB 9.03 2.60 8.51 2.86 7.98 3.09 -5/-6C DB/WB 8.19 2.44 7.98 2.63 7.77 2.86

20C

27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW

Indoor Units

75

Capacity Tables

MCAC-UTSM-2008-11

MTA3-36HRN1 (1 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.11 11.13 8.35 3.30 11.34 8.39 3.38 11.55 9.82 3.53 Outdoor conditions (DB) 28C 10.29 7.92 3.38 10.61 8.27 3.53 10.82 8.33 3.56 11.13 9.68 3.68 35C 9.77 7.81 3.53 10.08 8.16 3.68 10.50 8.19 3.75 10.92 9.61 3.94 43C 9.35 7.85 3.64 9.45 7.94 3.86 9.77 8.01 3.94 10.08 9.37 4.09

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 15.60 4.02 15.12 4.39 14.16 4.65 Outdoor conditions 7/6C DB/WB 12.60 3.46 12.00 3.72 11.28 4.02 2/1C DB/WB 10.32 2.98 9.72 3.27 9.12 3.53 -5/-6C DB/WB 9.36 2.79 9.12 3.01 8.88 3.27

76

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MTA3-36HRN1 (3 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.07 11.13 8.35 3.26 11.34 8.39 3.33 11.55 9.82 3.48 Outdoor conditions (DB) 28C 10.29 7.92 3.33 10.61 8.27 3.48 10.82 8.33 3.52 11.13 9.68 3.63 35C 9.77 7.81 3.48 10.08 8.16 3.63 10.50 8.19 3.70 10.92 9.61 3.89 43C 9.35 7.85 3.59 9.45 7.94 3.81 9.77 8.01 3.89 10.08 9.37 4.03

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 15.60 3.62 15.12 3.95 14.16 4.19 Outdoor conditions 7/6C DB/WB 12.60 3.12 12.00 3.35 11.28 3.62 2/1C DB/WB 10.32 2.68 9.72 2.95 9.12 3.18 -5/-6C DB/WB 9.36 2.51 9.12 2.71 8.88 2.95

Indoor Units

77

Capacity Tables

MCAC-UTSM-2008-11

MTA3-48HRN1-R Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 14.42 10.67 3.90 14.84 11.13 4.14 15.12 11.19 4.23 15.40 13.09 4.42 Outdoor conditions (DB) 28C 13.72 10.56 4.23 14.14 11.03 4.42 14.42 11.10 4.47 14.84 12.91 4.61 35C 13.02 10.42 4.42 13.44 10.89 4.61 14.00 10.92 4.70 14.56 12.81 4.94 43C 12.46 10.47 4.56 12.60 10.58 4.84 13.02 10.68 4.94 13.44 12.50 5.12

Heating
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 19.50 5.29 18.90 5.78 17.70 6.13 Outdoor conditions 7/6C DB/WB 15.75 4.56 15.00 4.90 14.10 5.29 2/1C DB/WB 12.90 3.92 12.15 4.31 11.40 4.66 -5/-6C DB/WB 11.70 3.68 11.40 3.97 11.10 4.31

78

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MTA-60HRN1-R Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 16.48 12.20 4.98 16.96 12.72 5.28 17.28 12.79 5.40 17.60 14.96 5.64 Outdoor conditions (DB) 28C 15.68 12.07 5.40 16.16 12.60 5.64 16.48 12.69 5.70 16.96 14.76 5.88 35C 14.88 11.90 5.64 15.36 12.44 5.88 16.00 12.48 6.00 16.64 14.64 6.30 43C 14.24 11.96 5.82 14.40 12.10 6.18 14.88 12.20 6.30 15.36 14.28 6.54

Heating
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 24.70 6.01 23.94 6.57 22.42 6.96 Outdoor conditions 7/6C DB/WB 19.95 5.17 19.00 5.564 17.86 6.01 2/1C DB/WB 16.34 4.45 15.39 4.90 14.44 5.29 -5/-6C DB/WB 14.82 4.17 14.44 4.51 14.06 4.90

Indoor Units

79

Electric Characteristics

MCAC-UTSM-2008-11

8. Electric Characteristics
Model MTA3-12HRN1 MTA3-18HRN1 MTA3-24HRN1 MTA3-30HRN1 MTA3-30HRN1 MTA3-36HRN1 MTA3-36HRN1 MTA3-48HRN1-R Indoor Units Hz 50 50 50 50 50 50 50 50 Voltage 220-240V 220-240V 220-240V 220-240V 380V 220-240V 380V 380-415V Min. 198V 198V 198V 198V 342V 198V 342V 342V 342V Max. 254V 254V 254V 254V 418V 254V 418V 418V 418V Power Supply MCA 0.2 0.675 1 1.25 1.25 1.25 1.25 1.25 1.9 MFA 10 25 25 25 15 25 15 15 15 Indoor Fan Motor kW 0.02 0.055 0.074 0.059 0.059 0.059 0.059 0.059 0.16 FLA 0.157 0.54 0.785 0.4752 0.4752 0.4752 0.4752 0.4752 1.47

MTA-60HRN1-R 50 380-415V Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A)

9. Sound Levels
Concealed Duct Type
Discharge Suction

Duct

Duct

1.4m

Microphone

Model MTA3-12HRN1 MTA3-18HRN1 MTA3-24HRN1 MTA3-30HRN1 (1 phase) MTA3-30HRN1 (3 phase) MTA3-36HRN1 (1 phase) MTA3-36HRN1 (3 phase) MTA3-48HRN1-R MTA-60HRN1-R

Noise level dB(A) H


41

M 38 41 45 47 47 47 47 47 48

L
35

45 49 49 49 49 49 51 52

38 42 44 44 44 44 44 46

80

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10. Exploded View


10.1 MTA3-12HRN1

No. 1 2 3 4 5 6 6.1 6.2 6.3 7 8 9 10 11 12

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27

Part Motor

Name

Quantity 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1

Evaporator ass'y Input pipe ass'y Output pipe ass'y Capacitor box Motor capacitor E-part box ass'y Main controller ass'y Wire joint,5p Transformer E-part box cover Drainage pan cover Display board ass'y Remote controller Display box Motor cover

Fixing board Fixing board Motor base Volute tongue Base Return air fixing box board Drainage pan Filter Return air fixing box board Fan Bearing Remote controller holder Room temp sensor ass'y Temperature sensor

Indoor Units

81

Exploded View

MCAC-UTSM-2008-11

10.2 MTA3-18HRN1

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Part Name Base ass'y Board Motor clamp Motor clamp Fan motor Motor capacitor Motor bracket Fan ass'y E-Part box cover Wire joint,7p Transformer E-part box weldment Main controller ass'y Pipe clamp board Sealed board ass'y Left clapboard ass'y Display board ass'y Remote controller Installation box Input pipe ass'y

Quantity 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1

No. 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39

Part Name Evaporator ass'y Output pipe ass'y Evaporator lining board Evaporator left clapboard ass'y Evaporator right clapboard ass'y Drainage pan ass'y Middle beam weldment Right cover ass'y Rear cover ass'y Bearing base Bearing Bearing supporting board Rear beam Connecting shaft Coupling E-part box ass'y Remote controller holder Room temp. sensor ass'y Evaporator pipe temp. sensor

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

82

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.3 MTA3-24HRN1

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Part Name Base ass'y Board Motor clamp Motor clamp Fan motor Capacitor Motor bracket Fan ass'y E-Part box cover Wire joint, 7p Transformer E-part box weldment Main controller ass'y Pipe clamp board Sealed board ass'y Left clapboard ass'y Display board ass'y Remote controller Installation box Remote controller holder

Quantity 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1

No. 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39

Part Name Input pipe ass'y Evaporator ass'y Output pipe ass'y Evaporator lining board Evaporator left clapboard ass'y Evaporator right clapboard ass'y Drainage pan ass'y Middle beam Right cover ass'y Rear cover ass'y Bearing base Bearing Bearing supporting board Rear beam Connecting shaft Coupling E-part box ass'y Room temp. sensor ass'y Evaporator pipe temp. sensor

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Indoor Units

83

Exploded View

MCAC-UTSM-2008-11

10.4 MTA3-30HRN1

MTA3-36HRN1(1 phase)

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Part

Name

Quantity 1 4 2 2 2 2 4 2 2 1 1 1 1 1 1 1 1 1

No. 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Base ass'y Fan ass'y Motor Board Motor clamp Motor bracket Capacitor box Motor clamp Motor capacitor Left clapboard ass'y Wire joint, 7p E-part box Transformer Main controller ass'y E-Part box cover Pipe clamp board Sealed board ass'y Display board ass'y

Remote controller Display box Input pipe ass'y Output pipe ass'y Evaporator ass'y Evaporator left clapboard ass'y Evaporator lining board Drainage pan ass'y Evaporator right clapboard ass'y Right cover ass'y Middle beam Rear cover ass'y Rear beam E-part box ass'y Remote controller holder Room temp sensor ass'y Temperature sensor

84

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.5 MTA3-30HRN1

MTA3-36HRN1(3 phase)

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Part

Name

Quantity 1 4 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1

No. 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Base ass'y Fan ass'y Motor Board Motor clamp Motor bracket Capacitor box Motor clamp Motor capacitor Left clapboard ass'y Wire joint, 9p E-part box Transformer Main controller ass'y E-Part box cover Pipe clamp board Sealed board ass'y Display board ass'y

Remote controller Display box Input pipe ass'y Output pipe ass'y Evaporator ass'y Evaporator left clapboard ass'y Evaporator lining board Drainage pan ass'y Evaporator right clapboard ass'y Right cover ass'y Middle beam Rear cover ass'y Rear beam E-part box ass'y Remote controller holder Room temp sensor ass'y Temperature sensor

Indoor Units

85

Exploded View

MCAC-UTSM-2008-11

10.6 MTA3-48HRN1-R

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Part Name Base ass'y Fan ass'y Motor Board Motor clamp Motor bracket Capacitor box Motor clamp Motor capacitor Left clapboard ass'y Wire joint, 9p E-part box weldment Transformer Main controller ass'y E-Part box cover Pipe clamp board Sealed board ass'y Display board ass'y

Quantity 1 4 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1

No. 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Part Name Remote controller Installation box Input pipe ass'y Output pipe ass'y Evaporator ass'y Evaporator left clapboard ass'y Evaporator lining board Drainage pan ass'y Evaporator right clapboard ass'y Right cover ass'y Middle beam Rear cover ass'y Rear beam E-part box ass'y Remote controller holder Room temp. sensor ass'y Evaporator pipe temp. sensor

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

86

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.7 MTA-60HRN1-R

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19.1 19.2 19.3

Part Name Base ass'y Fan ass'y Volute shell Connecting shaft Bearing supporting board Bearing Fixing board Coupling Board Motor below cover Motor up cover Motor below cover Motor up cover Rear board ass'y E-Part box cover Display board ass'y Display box Control box cover Remote controller E-part box ass'y Wire joint, 9p Transformer Main controller ass'y

Quantity 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 19.4 20 21 22 23 23.1 23.2 23.3 23.4 24 25 26 27 28 29 30 31 32 33 34 35

Part Name E-Part box weldment Cover board ass'y Left clapboard ass'y Partition board Evaporator ass'y Output pipe ass'y Input pipe ass'y Evaporator Evaporator pipe temp. sensor Water pipe Middle beam Drainage pan ass'y Beam cover Evaporator lining board Right cover ass'y Board Capacitor Capacitor box Motor Room temp. sensor Remote controller holder

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Indoor Units

87

Accessories

MCAC-UTSM-2008-11

11. Accessories
11.1 MTA3-12HRN1
Name Owners manual Installation manual Insulation pipe Remote controller Big washer Constriction bandage Water outlet joint (for cool/heat type only) Gasket (for cool/heat type only) Copper nut Drain hose 7# Alkaline battery Remote signal receiver subassembly Q'ty 1 1 2 1 8 10 1 1 2 1 1 1 (This manual) Heat insulation Remote control the air-conditioner. Overhang indoor unit Binding insulation pipe Outdoor unit drainage Outdoor unit drainage Connecting pipe Indoor unit drainage Outline Usage

11.2 MTA3-18HRN1
Name

MTA3-24HRN1
Q'ty 1 1 2 1 1

MTA3-30HRN1
Outline (This manual)

MTA3-36HRN1

MTA3-48HRN1-R
Usage

Installation manual Remote controller subassembly Pipe insulation material Accessory drain pipe Adhesive tape for seal

Remote control the air-conditioner. Heat insulation To connect drain pipe To connect drain pipe

11.3 MTA-60HRN1-R
Name Owner's manual Installation manual Pipe insulating material Drain elbow Seal Signal receiver display board Q'ty 1 1 2 1 1 1 (This manual) Heat insulation To connect drain pipe To connect drain pipe Receive signal Outline Usage

88

Indoor Units

MCAC-UTSM-2008-11

The Specification of Power

12. The Specification of Power


Type Phase Power Frequency and Voltage Circuit Breaker/ Fuse (A) 2 Indoor Unit Power Wiring (mm ) Ground Wiring Indoor/Outdoor Connecting 2 Wiring (mm ) Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal MTA3-12HRN1 1-phase 220-240V, 50Hz 20/10 32.0 2.0 32.0 52.0 1-core shield wire 10.5 52.5 1-core shield wire 10.5 MTA3-18HRN1 1-phase 220-240V, 50Hz 40/25 32.5 2.5 MTA3-24HRN1 1-phase 220-240V, 50Hz 40/25 32.5 2.5 32.5 31.0 1-core shield wire 10.5

Type Phase Frequency and Voltage Circuit Breaker/ Fuse (A) 2 Indoor Unit Power Wiring (mm ) Ground Wiring Outdoor Unit Power Wiring Indoor/Outdoor Connecting 2 Strong Electric Signal Wiring (mm ) Weak Electric Signal Power Type Phase Power Frequency and Voltage Circuit Breaker/ Fuse (A) 2 Indoor Unit Power Wiring (mm ) Ground Wiring Outdoor Unit Power Wiring Indoor/Outdoor Connecting 2 Strong Electric Signal Wiring (mm ) Weak Electric Signal

MTA3-30HRN1 MTA3-36HRN1 1-phase 220-240V, 50Hz 40/25 34.0 4.0 31.0 32.5 1-core shield wire 10.5 MTA3-48HRN1-R 3-phase 380-415V, 50Hz 20/15 52.5 2.5 52.5 31.0 3-core cable wire

MTA3-30HRN1 MTA3-36HRN1 3-phase 380-415V, 50Hz 20/15 52.5 2.5 52.5 31.0 3-core cable wire

MTA-60HRN1-R 3-phase 380-415V, 50Hz 20/15 52.5 2.5 52.5 31.0 3-core cable wire

Indoor Units

89

Field Wiring

MCAC-UTSM-2008-11

13. Field Wiring


MTA3-12HRN1

MTA3-18HRN1

90

Indoor Units

MCAC-UTSM-2008-11

Field Wiring

MTA3-24HRN1

MTA3-30HRN1

MTA3-36HRN1 (1 Phase)

Indoor Units

91

Field Wiring

MCAC-UTSM-2008-11

MTA3-30HRN1

MTA3-36HRN1 (3 Phase)

MTA3-48HRN1-R

92

Indoor Units

MCAC-UTSM-2008-11

Field Wiring

MTA-60HRN1-R

Indoor Units

93

High Static Pressure Duct Type

MCAC-UTSM-2008-11

High Static Pressure Duct Type


1. Features ................................................................................................... 95 2. Specifications .......................................................................................... 96 3. Dimensions .............................................................................................. 99 4. Service Space ........................................................................................ 101 5. Wiring Diagrams .................................................................................... 102 6. Air Velocity and Temperature Distributions ........................................ 105 7. Capacity Tables ..................................................................................... 106 8. Electric Characteristics ........................................................................ 113 9. Sound Levels ......................................................................................... 113 10. Exploded View ..................................................................................... 114 11. Accessories ......................................................................................... 121 12. The Specification of Power................................................................. 122 13. Field Wiring .......................................................................................... 123

94

Indoor Units

MCAC-UTSM-2008-11

Features

1. Features
1.1 Two air intake methods: from below or rear, to satisfy your fitments needs.

1.2 High-static pressure. Blowing pressure of indoor unit can reach 150Pa. The air conditioner delivers cold wind to every indoor corner even the ceiling is super-high. 1.3 Indoor unit can be installed in various ways to give you a creative space. 1.4 Optional accessories ---Including front clapboard, panel, canvas air passage, filter, etc..

Canvas air passage

Clapboard

Panel 1.5 A long-life and high-efficiency filter

Indoor Units

95

Specifications

MCAC-UTSM-2008-11

2. Specifications
Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor external static pressure (Hi) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) mm mm W uF r/min V-ph-Hz kW W kW W MHB-18HRN1 220070200150 220~240-1-50 5.3 1900 6 1900 YSK74-4C Welling 170/150/133 6.5uF/450V 1100/1020/900 2 mm mm 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 80025444 2 m /h Pa dB(A) mm mm kg
3

MHB-24HRN1 220070300320 220~240-1-50 7.1 2510 7.6 2500 YSK120-4C Welling 230/208/190 6.5uF/450V 1315/1230/1130 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 80025466 3 1589/1469/1364 70 49/45/42 1000298800 1205370940 41/43 R410A 4.4/2.6 9.5/15.9 OD32 32.5 31.0 1-core shield wire 10.5 R11HG/E(standard)

Heating

1502/1337/1225 70 45/41/38 1000298800 1205370940 36/41 R410A

Net/Gross weight Refrigerant type Design pressure Refrigerant Liquid side/Gas side piping Drainage water pipe diameter Power wiring Strong electric signal wiring Weak electric signal wiring

MPa mm mm mm mm mm
2 2

4.4/2.6 6.4/12.7 OD32 32.5 52.5 1-core shield wire 10.5 R11HG/E(standard)

Connection wiring

Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

96

Indoor Units

MCAC-UTSM-2008-11

Specifications

Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor external static pressure (Hi) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) mm mm W uF r/min V-ph-Hz kW W kW W

MHB-30HRN1

MHB-30HRN1

220070400200
220~240-1-50 9 3270 9.5 3380 YSK80-4X(2) YONGAN 162/138/120 5uF/450V 1250/1125/920 3 mm mm 25.422 1.7 Hydrophilic aluminum 9.53 Inner grooved copper tube 115025466 5 m /h Pa dB(A) mm mm kg
3

220070400190
380~415-3-50 9 3250 9.5 3350 YSK80-4X(2) YONGAN 162/138/120 5uF/450V 1250/1125/920 3 25.422 1.7 Hydrophilic aluminum 9.53 Inner grooved copper tube 115025466 5 2279/2203/2000 100 49/47/44 1350298800 1555370940 50/55 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 R11HG/E(standard)

Heating

2279/2203/2000 100 49/47/44 1350298800 1555370940 50/55 R410A

Net/Gross weight Refrigerant type Design pressure Refrigerant Liquid side/Gas side piping Drainage water pipe diameter Power wiring Strong electric signal wiring Weak electric signal wiring

MPa mm mm mm mm mm
2 2

4.4/2.6 12.7/19 OD32 34.0 31.0 1-core shield wire 10.5 R11HG/E(standard)

Connection wiring

Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Indoor Units

97

Specifications

MCAC-UTSM-2008-11

Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil length height width Number of circuits W uF r/min V-ph-Hz kW W kW W

MHB-36HRN1 220070500370 220~240-1-50 10.5 3750 12 3720 YSK80-4X(2) YONGAN 162/138/120 5uF/450V 1250/1125/920 3 mm mm 25.422 1.7 Hydrophilic aluminum 9.53 Inner grooved copper tube 115025466 5 m /h Pa dB(A) mm mm kg
3

MHB-36HRN1 220070500350 380-3-50 10.5 3700 12 3550 YSK80-4X(2) YONGAN 162/138/120 5uF/450V 1250/1125/920 3 25.422 1.7 Hydrophilic aluminum 9.53 Inner grooved copper tube 115025466 5 2279/2203/2000 100 49/47/44 1350298800 1555370940 51/55 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 R11HG/E(standard)

MHB-48HRN1 220070700230 380-3-50 14 4700 15 4900 YSK350-4 YONGAN 620/480/370/310 10uF/450V 1020/850/725/660 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 114625466 6 3348/2296/1927 150 52/48/46 1350320800 1555420930 58/65 R410A 4.4/2.6 12.7/19 OD32 52.5 31.0 R11HG/E(standard)

Heating

mm mm

Indoor air flow(Hi/Mi/Lo) Indoor external static pressure (Hi) Indoor noise level (sound pressure) Dimension (WHD) Packing Indoor unit (WHD) Net/Gross weight Refrigerant type Design pressure Refrigerant Liquid side/Gas piping side Drainage water pipe diameter Power wiring Strong electric signal wiring Weak electric signal wiring

2279/2203/2000 100 49/47/44 1350298800 1555370940 51/55 R410A

MPa mm mm mm mm mm
2 2

4.4/2.6 12.7/19 OD32 34.0 31.0 1-core shield wire 10.5 R11HG/E(standard)

Connection wiring

Controller

Operation temperature 17-30 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

98

Indoor Units

MCAC-UTSM-2008-11

Dimensions

3. Dimensions
3.1. MHB-18HRN1 MHB-24HRN1

3.2 MHB-30HRN1

MHB-36HRN1

Indoor Units

99

Dimensions

MCAC-UTSM-2008-11

3.3. MHB-48HRN1

100

Indoor Units

MCAC-UTSM-2008-11

Service Space

4. Service Space

Note: Above figure means minimum value. Please keep these value at least.

Indoor Units

101

Wiring Diagrams

MCAC-UTSM-2008-11

5. Wiring Diagrams
5.1 MHB-18HRN1

102

Indoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.2 MHB-24HRN1

MHB-30HRN1

MHB-36HRN1 (1 phase)

Indoor Units

103

Wiring Diagrams

MCAC-UTSM-2008-11

5.3 MHB-30HRN1

MHB-36HRN1

MHB-48HRN1 (3 phase)

104

Indoor Units

MCAC-UTSM-2008-11

Air Velocity and Temperature Distributions

6. Air Velocity and Temperature Distributions


Discharge angle 60
Airflow velocity

Temperature

Indoor Units

105

Capacity Tables

MCAC-UTSM-2008-11

7. Capacity Tables
MHB-18HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 5.46 4.04 1.58 5.62 4.21 1.67 5.72 4.24 1.71 5.83 4.96 1.79 Outdoor conditions (DB) 28C 5.19 4.00 1.71 5.35 4.18 1.79 5.46 4.20 1.81 5.62 4.89 1.86 35C 4.93 3.94 1.79 5.09 4.12 1.86 5.30 4.13 1.90 5.51 4.85 2.00 43C 4.72 3.96 1.84 4.77 4.01 1.96 4.93 4.04 2.00 5.09 4.73 2.07

Heating
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 7.80 2.05 7.56 2.24 7.08 2.38 Outdoor conditions 7/6C DB/WB 6.30 1.77 6.00 1.90 5.64 2.05 2/1C DB/WB 5.16 1.52 4.86 1.67 4.56 1.81 -5/-6C DB/WB 4.68 1.43 4.56 1.54 4.44 1.67

106

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MHB-24HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 7.31 5.41 2.08 7.53 5.64 2.21 7.67 5.67 2.26 7.81 6.64 2.36 Outdoor conditions (DB) 28C 6.96 5.36 2.26 7.17 5.59 2.36 7.31 5.63 2.38 7.53 6.55 2.46 35C 6.60 5.28 2.36 6.82 5.52 2.46 7.10 5.54 2.51 7.38 6.50 2.64 43C 6.32 5.31 2.43 6.39 5.37 2.59 6.60 5.41 2.64 6.82 6.34 2.74

Heating
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 9.88 2.70 9.58 2.95 8.97 3.13 Outdoor conditions 7/6C DB/WB 7.98 2.33 7.60 2.50 7.14 2.70 2/1C DB/WB 6.54 2.00 6.16 2.20 5.78 2.38 -5/-6C DB/WB 5.93 1.88 5.78 2.03 5.62 2.20

Indoor Units

107

Capacity Tables

MCAC-UTSM-2008-11

MHB-30HRN1 (1 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 9.27 6.86 2.71 9.54 7.16 2.88 9.72 7.19 2.94 9.90 8.42 3.07 Outdoor conditions (DB) 28C 8.82 6.79 2.94 9.09 7.09 3.07 9.27 7.14 3.11 9.54 8.30 3.20 35C 8.37 6.70 3.07 8.64 7.00 3.20 9.00 7.02 3.27 9.36 8.24 3.43 43C 8.01 6.73 3.17 8.10 6.80 3.37 8.37 6.86 3.43 8.64 8.04 3.56

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 12.35 3.65 11.97 3.99 11.21 4.23 Outdoor conditions 7/6C DB/WB 9.98 3.14 9.50 3.38 8.93 3.65 2/1C DB/WB 8.17 2.70 7.70 2.97 7.22 3.21 -5/-6C DB/WB 7.41 2.54 7.22 2.74 7.03 2.97

108

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MHB-30HRN1 (3 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 9.27 6.86 2.70 9.54 7.16 2.86 9.72 7.19 2.93 9.90 8.42 3.06 Outdoor conditions (DB) 28C 8.82 6.79 2.93 9.09 7.09 3.06 9.27 7.14 3.09 9.54 8.30 3.19 35C 8.37 6.70 3.06 8.64 7.00 3.19 9.00 7.02 3.25 9.36 8.24 3.41 43C 8.01 6.73 3.15 8.10 6.80 3.35 8.37 6.86 3.41 8.64 8.04 3.54

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 12.35 3.62 11.97 3.95 11.21 4.19 Outdoor conditions 7/6C DB/WB 9.98 3.12 9.50 3.35 8.93 3.62 2/1C DB/WB 8.17 2.68 7.70 2.95 7.22 3.18 -5/-6C DB/WB 7.41 2.51 7.22 2.71 7.03 2.95

Indoor Units

109

Capacity Tables

MCAC-UTSM-2008-11

MHB-36HRN1 (1 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.11 11.13 8.35 3.30 11.34 8.39 3.38 11.55 9.82 3.53 Outdoor conditions (DB) 28C 10.29 7.92 3.38 10.61 8.27 3.53 10.82 8.33 3.56 11.13 9.68 3.68 35C 9.77 7.81 3.53 10.08 8.16 3.68 10.50 8.19 3.75 10.92 9.61 3.94 43C 9.35 7.85 3.64 9.45 7.94 3.86 9.77 8.01 3.94 10.08 9.37 4.09

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 15.60 4.02 15.12 4.39 14.16 4.65 Outdoor conditions 7/6C DB/WB 12.60 3.46 12.00 3.72 11.28 4.02 2/1C DB/WB 10.32 2.98 9.72 3.27 9.12 3.53 -5/-6C DB/WB 9.36 2.79 9.12 3.01 8.88 3.27

110

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MHB-36HRN1 (3 phase) Cooling


Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.07 11.13 8.35 3.26 11.34 8.39 3.33 11.55 9.82 3.48 Outdoor conditions (DB) 28C 10.29 7.92 3.33 10.61 8.27 3.48 10.82 8.33 3.52 11.13 9.68 3.63 35C 9.77 7.81 3.48 10.08 8.16 3.63 10.50 8.19 3.70 10.92 9.61 3.89 43C 9.35 7.85 3.59 9.45 7.94 3.81 9.77 8.01 3.89 10.08 9.37 4.03

Heating
Heating Indoor Conditions (DB) 15C 20C 27C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 15.60 3.83 15.12 4.19 14.16 4.44 Outdoor conditions 7/6C DB/WB 12.60 3.30 12.00 3.55 11.28 3.83 2/1C DB/WB 10.32 2.84 9.72 3.12 9.12 3.37 -5/-6C DB/WB 9.36 2.66 9.12 2.88 8.88 3.12

Indoor Units

111

Capacity Tables

MCAC-UTSM-2008-11

MHB-48HRN1 Cooling
Cooling Indoor Conditions 21/15C DB/WB (kW) TC SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 14.42 10.67 3.90 14.84 11.13 4.14 15.12 11.19 4.23 15.40 13.09 4.42 Outdoor conditions (DB) 28C 13.72 10.56 4.23 14.14 11.03 4.42 14.42 11.10 4.47 14.84 12.91 4.61 35C 13.02 10.42 4.42 13.44 10.89 4.61 14.00 10.92 4.70 14.56 12.81 4.94 43C 12.46 10.47 4.56 12.60 10.58 4.84 13.02 10.68 4.94 13.44 12.50 5.12

Heating
Heating Indoor Conditions (DB) 15C 20C 27C Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW (kW) TC Input TC Input TC Input 24/18C DB/WB 19.50 5.29 18.90 5.78 17.70 6.13 Outdoor conditions 7/6C DB/WB 15.75 4.56 15.00 4.90 14.10 5.29 2/1C DB/WB 12.90 3.92 12.15 4.31 11.40 4.66 -5/-6C DB/WB 11.70 3.68 11.40 3.97 11.10 4.31

112

Indoor Units

MCAC-UTSM-2008-11

Electric Characteristics

8. Electric Characteristics
Model MHB-18HRN1 MHB-24HRN1 MHB-30HRN1 MHB-30HRN1 MHB-36HRN1 MHB-36HRN1 Indoor Units Hz 50 50 50 50 50 50 Voltage 220-240V 220-240V 220-240V 380-415V 220-240V 380V Min. 198V 198V 198V 342V 198V 342V 342V Max. 254V 254V 254V 418V 254V 418V 418V Power Supply MCA 1.57 1.3 0.9125 0.9125 0.9125 0.9125 2.82 MFA 25 25 25 15 25 15 15 Indoor Fan Motor kW 0.074 0.12 0.08 0.08 0.08 0.08 0.35 FLA 0.785 1.01 0.73(2) 0.73(2) 0.73(2) 0.73(2) 2.25

MHB-48HRN1 50 380V Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A) IFM: Indoor Fan Motor

9. Sound Levels
Concealed Duct Type
Discharge Suction

Duct

Duct

1.4m

Microphone

Model MHB-18HRN1 MHB-24HRN1 MHB-30HRN1(1 phase) MHB-30HRN1(3 phase) MHB-36HRN1(1 phase) MHB-36HRN1(3 phase) MHB-48HRN1

Noise level dB(A) H 45 49 49 49 49 49 52 M 41 45 47 47 47 47 48 L 38 42 44 44 44 44 46

Indoor Units

113

Exploded View

MCAC-UTSM-2008-11

10. Exploded View


10.1 MHB-18HRN1

No. 1 2 3 4 5 6 7 8 9.1 9.2 9.3 9.4 9.5 9.6 10 11 12 13 14 15

Part Name Drainage pan ass'y Evaporator ass'y Pipe clamp board Sealed board ass'y Evaporator left clapboard ass'y Left clapboard ass'y Evaporator temp. sensor E-Part box cover Wire joint,2p Wire joint,7p Capacitor E-part box ass'y Transformer Main controller ass'y Room temp. sensor ass'y Motor bracket Fan motor Sucker Fan ass'y Motor left clamp

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1

No. 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Part Name Motor right clamp Board of board Display box Display board ass'y Control box cover Rear cover ass'y Remote controller holder Remote controller Water pipe Middle beam Rear beam Connecting shaft Bearing Fixing board Bearing base Bearing supporting board Base ass'y Right cover ass'y Evaporator lining board Evaporator right clapboard ass'y Coupling

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

114

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.2 MHB-24HRN1

No. 1 2 3 4 5 6 7 8 9.1 9.2 9.3 9.4 9.5 9.6 10 11 12 13 14 15

Part Name Drainage pan ass'y Evaporator ass'y Pipe clamp board Sealed board ass'y Evaporator left clapboard ass'y Left clapboard ass'y Evaporator temp. sensor E-Part box cover Wire joint, 2p Wire joint, 7p Capacitor E-part box ass'y Transformer Main controller ass'y Room temp. sensor ass'y Motor bracket Motor Sucker Fan ass'y Motor clamp

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1

No. 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Part Name Motor clamp Board Display box Display board ass'y Control box cover Rear cover ass'y Remote controller holder Remote controller Water pipe Middle beam Rear beam Connecting shaft Bearing Fixing board Bearing base Bearing supporting board Base ass'y Right cover ass'y Evaporator lining board Evaporator right clapboard ass'y Coupling

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Indoor Units

115

Exploded View

MCAC-UTSM-2008-11

10.3 MHB-30HRN1 (1 phase)

No. 1 2 3 4 5 6 7 8 9 10 10.1 10.2 10.3 11 12 12.1 12.2 12.3 12.4

Part

Name

Quantity 1 1 2 2 2 2 2 4 1 1 1 1 1 1 1 1 1 1 1

No. 12.5 12.6 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

Part

Name

Quantity 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Base ass'y Evaporator lining board Board Motor clamp Motor clamp Motor Motor bracket Fan ass'y Middle beam Evaporator ass'y Evaporator ass'y Output pipe ass'y Input pipe ass'y Left clapboard ass'y E-part box ass'y E-part box Transformer Main controller ass'y E-Part box cover

Motor capacitor Wire joint, 7p Pipe clamp board Sealed board ass'y Evaporator left clapboard ass'y Display box Display board ass'y Control box cover Remote controller Water pipe Drainage pan ass'y Rear cover ass'y Rear beam Evaporator right clapboard ass'y Right cover ass'y Remote controller holder Room temp sensor ass'y Temp. sensor ass'y

116

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.4 MHB-30HRN1 (3 phase)

No. 1 2 3 4 5 6 7 8 9 10 10.1 10.2 10.3 11 12 12.1 12.2 12.3 12.4

Part

Name

Quantity 1 1 2 2 2 2 2 4 1 1 1 1 1 1 1 1 1 1 1

No. 12.5 12.6 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

Part

Name

Quantity 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Base ass'y Evaporator lining board Board Motor clamp Motor clamp Motor Motor bracket Fan ass'y Middle beam Evaporator ass'y Evaporator ass'y Output pipe ass'y Input pipe ass'y Left clapboard ass'y E-part box ass'y E-part box Transformer Main controller ass'y E-Part box cover

Motor capacitor Wire joint, 9p Pipe clamp board Sealed board ass'y Evaporator left clapboard ass'y Display box Display board ass'y Control box cover Remote controller Water pipe Drainage pan ass'y Rear cover ass'y Rear beam Evaporator right clapboard ass'y Right cover ass'y Remote controller holder Room temp sensor ass'y Temp. sensor ass'y

Indoor Units

117

Exploded View

MCAC-UTSM-2008-11

10.5 MHB-36HRN1 (1 phase)

No. 1 2 3 4 5 6 7 8 9 10 10.1 10.2 10.3 11 12 12.1 12.2 12.3 12.4

Part

Name

Quantity 1 1 2 2 2 2 2 4 1 1 1 1 1 1 1 1 1 1 1

No. 12.5 12.6 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

Part

Name

Quantity 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Base ass'y Evaporator lining board Board Motor clamp Motor clamp Motor Motor bracket Fan ass'y Middle beam Evaporator ass'y Evaporator ass'y Output pipe ass'y Input pipe ass'y Left clapboard ass'y E-part box ass'y E-part box Transformer Main controller ass'y E-Part box cover

Motor capacitor Wire joint, 7p Pipe clamp board Sealed board ass'y Evaporator left clapboard ass'y Display box Display board ass'y Control box cover Remote controller Water pipe Drainage pan ass'y Rear cover ass'y Rear beam Evaporator right clapboard ass'y Right cover ass'y Remote controller holder Room temp sensor ass'y Temp. sensor ass'y

118

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.6 MHB-36HRN1 (3 phase)

No. 1 2 3 4 5 6 7 8 9 10 10.1 10.2 10.3 11 12 12.1 12.2 12.3 12.4

Part

Name

Quantity 1 1 2 2 2 2 2 4 1 1 1 1 1 1 1 1 1 1 1

No. 12.5 12.6 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

Part

Name

Quantity 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Base ass'y Evaporator lining board Board Motor clamp Motor clamp Motor Motor bracket Fan ass'y Middle beam Evaporator ass'y Evaporator ass'y Output pipe ass'y Input pipe ass'y Left clapboard ass'y E-part box ass'y E-part box Transformer Main controller ass'y E-Part box cover

Motor capacitor Wire joint, 9p Pipe clamp board Sealed board ass'y Evaporator left clapboard ass'y Display box Display board ass'y Control box cover Remote controller Water pipe Drainage pan ass'y Rear cover ass'y Rear beam Evaporator right clapboard ass'y Right cover ass'y Remote controller holder Room temp sensor ass'y Temp. sensor ass'y

Indoor Units

119

Exploded View

MCAC-UTSM-2008-11

10.7 MHB-48HRN1

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 13.1 13.2 13.3 14 15 16 17 18 120

Part Name Base ass'y Rear board ass'y Fan ass'y Bearing supporting board Bearing Fixing board Connecting shaft Coupling Motor up cover Motor below cover Right cover ass'y Middle beam Evaporator lining board Evaporator ass'y Evaporator Input pipe ass'y Output pipe ass'y Beam cover Drainage pan ass'y Water pipe Remote controller Control box cover

Quantity 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 19 20 21 22 23 24 25 25.1 25.2 25.3 25.4 26 27 28 29 30 31 32 33 34 35

Part Name Display board ass'y Display box Partition board Cover board ass'y Left clapboard ass'y E-Part box cover E-part box ass'y Wire joint, 9p E-Part box Transformer Main controller ass'y Board Motor below cover Motor up cover Motor Board Capacitor box Capacitor Remote controller holder Room temp. sensor ass'y Evaporator temp. sensor

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Indoor Units

MCAC-UTSM-2008-11

Accessories

11. Accessories
11.1 MHB-18HRN1
Name Installation manual Remote controller subassembly Pipe insulation material Accessory drain pipe Adhesive tape for seal

MHB-24HRN1
Q'ty 1 1 2 1 1

MHB-30HRN1

MHB-36HRN1
Outline (This manual) Remote control the air-conditioner Heat insulation To connect drain pipe To connect drain pipe Usage

11.2 MHB-48HRN1
Name Owner's manual Installation manual Pipe insulating material Drain elbow Seal Signal receiver display board Q'ty 1 1 2 1 1 1 (This manual) Heat insulation To connect drain pipe To connect drain pipe Receive signal Outline Usage

Indoor Units

121

The Specification of Power

MCAC-UTSM-2008-11

12. The Specification of Power


Type Power Phase Frequency and Voltage Circuit Breaker/ Fuse (A) Indoor Unit Power Wiring (mm ) Ground Wiring Indoor/Outdoor Connecting 2 Wiring (mm ) Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal Type Power Phase Frequency and Voltage Circuit Breaker/ Fuse (A) Indoor Unit Power Wiring (mm ) Ground Wiring Indoor/Outdoor Connecting 2 Wiring (mm ) Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal
2 2

MHB-18HRN1 1-phase 220-240V, 50Hz 40/25 32.5 2.5 52.5 1-core shield wire 10.5 MHB-30HRN1 MHB-36HRN1 1-phase 220-240V, 50Hz 40/25 34.0 4.0 34.0 31.0 1-core shield wire 10.5

MHB-24HRN1 1-phase 220-240V, 50Hz 40/25 32.5 2.5 32.5 31.0 1-core shield wire 10.5 MHB-30HRN1 MHB-36HRN1 3-phase 380-415V, 50Hz 20/15 52.5 2.5 52.5 31.0 3-core cable wire

Type Power Phase Frequency and Voltage Circuit Breaker/ Fuse (A) Indoor Unit Power Wiring (mm ) Ground Wiring Indoor/Outdoor Connecting 2 Wiring (mm ) Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal
2

MHB-48HRN1 3-phase 380-415V, 50Hz 20/15 52.5 2.5 52.5 31.0 3-core cable wire

122

Indoor Units

MCAC-UTSM-2008-11

Field Wiring

13. Field Wiring


MHB-18HRN1

MHB-24HRN1

Indoor Units

123

Field Wiring

MCAC-UTSM-2008-11

MHB-30HRN1

MHB-36HRN1 (1 phase)

MHB-30HRN1

MHB-36HRN1 (3 phase)

124

Indoor Units

MCAC-UTSM-2008-11

Field Wiring

MHB-48HRN1

Indoor Units

125

Ceiling & Floor Type

MCAC-UTSM-2008-11

Ceiling & Floor Type


1. Features ................................................................................................. 127 2. Specifications ........................................................................................ 128 3. Dimensions ............................................................................................ 132 4. Service Space ........................................................................................ 133 5. Wiring Diagrams .................................................................................... 134 6. Air Velocity and Temperature Distributions ........................................ 138 7. Capacity Tables ..................................................................................... 140 8. Electric Characteristics ........................................................................ 149 9. Sound Levels ......................................................................................... 149 10. Exploded View ..................................................................................... 150 11. Accessories ......................................................................................... 157 12. The Specification of Power................................................................. 157 13. Field Wiring .......................................................................................... 158

126

Indoor Units

MCAC-UTSM-2008-11

Features

1. Features
1.1. New design, more modern and elegant appearance.

1.2. Convenient installation --The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting 1.3. Two direction auto swing (vertical & horizontal) and wide angle air flow --Air flow directional control minimizes the air resistance and produces wilder air flow to vertical direction. --The range of horizontal air discharge is widened which secures wider air flow distribution to provide more comfortable air circulation no matter where the unit is set up

1.4. Three level fan speed, more humanism design, meets different air-supply requirement. 1.5. Water proof by utilizing the absorbing plastic film on water collector. 1.6. Easy operation. Auto-restart function, remote control and optional wire control method. 1.7. Low noise level plus compact size --Shape of the blades has been improved to prevent noise caused by turbulence.

Indoor Units

127

Specifications

MCAC-UTSM-2008-11

2. Specifications
Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil lengthheightwidth Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) m /h dB(A) mm mm kg
3

MUB-12HRN1 220042101900 V-ph-Hz kW W kW W 220~240-1-50 3.2 1022 4 1220 YSK25-6L Welling W uF r/min 33.4/31.1/29.5 1.2uF/450V 756/666/592 2 mm mm 25.422 1.7 Hydrophilic aluminum mm mm 9.53 Inner grooved copper tube 80425444 3 600/480/400 43/41/38 990660203 1089744296 25/33 R410A MPa Liquid side/Gas side mm mm mm mm mm
2

MUB-18HRN1 220042101920 220~240-1-50 5.3 1726 6 1863 YSK55-4L Welling 125/105/85 2.5uF/450V 1310/1190/1040 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 80425466 3 800/600/500 43/41/38 990660203 1089744296 27/33 R410A 4.4/2.6 6.4/12.7 OD25 32.5 52.5 1-core shield wire 10.5 R05/BGE(standard)

Heating

Net/Gross weight Refrigerant type Design pressure Refrigerant piping

4.4/2.6 6.4/12.7 OD25 32.5 52.5 1-core shield wire 10.5 R05/BGE(standard)

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

128

Indoor Units

MCAC-UTSM-2008-11 Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil lengthheightwidth Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) m /h dB(A) mm mm kg
3

Specifications MUB-24HRN1 220042101940 V-ph-Hz kW W kW W 220~240-1-50 7.1 2423 7.6 2413 YSK55-4L Welling W uF r/min 125/105/85 2.5uF/450V 1310/1190/1040 3 mm mm 25.422 1.7 Hydrophilic aluminium mm mm 9.53 Inner grooved copper tube 80425466 3 1200/900/700 45/43/40 990660203 1089744296 27/33 R410A MPa 4.4/2.6 9.5/15.9 OD25
2

MUB-30HRN1 220044300050 220~240-1-50 9 3180 9.5 3345 YSK80-4A Welling 143/122/110 3.5uF/450V 1310/1210/1115 3 25.422 1.7 Hydrophilic aluminum 9.53 Inner grooved copper tube 109425466 5 1400/1200/1000 45/43/40 1280660203 1379744296 35/40 R410A 4.4/2.6 12.7/19 OD25 32.5 32.5 1-core shield wire 10.5 R05/BGE(standard)

Heating

Net/Gross weight Refrigerant type Design pressure Refrigerant piping Liquid side/Gas side

mm mm mm mm mm

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring Controller

32.5 32.5 1-core shield wire 10.5 R05/BGE(standard)

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Indoor Units

129

Specifications

MCAC-UTSM-2008-11

Model Code Power supply Cooling Capacity Input Capacity Input Model Brand Indoor fan motor Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil lengthheightwidth Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) m /h dB(A) mm mm kg
3

MUB-30HRN1 220042102000 V-ph-Hz kW W kW W 380-3-50 9 3169 9.5 3428 YSK80-4A Welling W uF r/min 143/122/110 3.5uF/450V 1310/1210/1115 3 mm mm 25.422 1.7 Hydrophilic aluminum mm mm 9.53 Inner grooved copper tube 109425466 5 1400/1200/1000 45/43/40 1280660203 1379744296 35/40 R410A MPa Liquid side/Gas side mm mm mm mm mm
2

MUB-36HRN1 220044400160 220~240-1-50 10.5 3737 12 4286 YSK80-4A Welling 143/122/110 3.5uF/450V 1310/1210/1115 3 25.422 1.7 Hydrophilic aluminum 9.53 Inner grooved copper tube 109425466 5 1400/1200/1000 45/43/40 1280660203 1379744296 35/40 R410A 4.4/2.6 12.7/19 OD25 32.5 32.5 1-core shield wire 10.5 R05/BGE(standard)

Heating

Net/Gross weight Refrigerant type Design pressure Refrigerant piping

4.4/2.6 12.7/19 OD25 52.5 32.5 R05/BGE(standard)

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring Controller

Operation temperature 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

130

Indoor Units

MCAC-UTSM-2008-11

Specifications

Model Code Power supply Cooling Capacity Input Capacity Input Model Indoor fan motor Brand Input Capacitor Speed(Hi/Mi/Lo) Number of rows Tube pitch(a)row pitch(b) Fin spacing Indoor coil Fin type (code) Tube outside dia.and type Coil lengthheightwidth Number of circuits Indoor air flow(Hi/Mi/Lo) Indoor noise level (sound pressure) Dimension (WHD) Indoor unit Packing (WHD) m /h dB(A) mm mm kg
3

MUB-36HRN1 220042102020 V-ph-Hz kW W kW W 380-3-50 10.5 3763 12 4286 YSK80-4A Welling W uF r/min 143/122/110 3.5uF/450V 1310/1210/1115 3 mm mm 25.422 1.7 Hydrophilic aluminum mm 9.53 Inner grooved copper tube 109425466 5 1400/1200/1000 45/43/40 1280660203 1379744296 35/40 R410A MPa mm mm mm mm
2

MUB-48HRN1-R 220042102040 380~415-3-50 14 5128 15 5376 YSK59-4D(2) Welling 89.5/81.5/77.5 2.5uF/450V 1170/1070/995 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 136025466 5 2000/1800/1600 47/45/42 1670680240 1764760329 52/59 R410A 4.4/2.6 12.7/19 OD25 52.5 32.5

MUB-60HRN1-R 220042102060 380~415-3-50 16 5882 19 6835 YSK59-4D(2) Welling 89.5/81.5/77.5 2.5uF/450V 1170/1070/995 3 25.422 1.7 Hydrophilic aluminium 9.53 Inner grooved copper tube 136025466 5 2000/1800/1600 47/45/42 1670680240 1764760329 52/59 R410A 4.4/2.6 12.7/19 OD25 52.5 32.5

Heating

mm

Net/Gross weight Refrigerant type Design pressure Refrigerant piping Liquid side/Gas side

4.4/2.6 12.7/19 OD25 52.5 32.5

Drainage water pipe diameter Power wiring Connection wiring Strong electric signal wiring Weak electric signal wiring Controller

mm

R05/BGE(standard)

R05/BGE(standard)

R05/BGE(standard)

Operation temperature 17-30 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.

Indoor Units

131

Dimensions

MCAC-UTSM-2008-11

3. Dimensions
a. Wall mounting installation

b. Ceiling installation

Capacity (Btu/h) 12000-24000 30000-36000

A 990 1280

B 660 660

C 203 203

D 505 795

E 506 506 450

F 907 1195 1542

G 200 200 200

48000-60000 1670 680 240 1070 Note: The dimension of 12000Btu/h, 18000Btu/h and 24000Btu/h are the same. The dimension of 30000Btu/h and 36000Btu/h are the same. The dimension of 48000Btu/h and 60000Btu/h are the same.

132

Indoor Units

MCAC-UTSM-2008-11

Service Space

4. Service Space

Indoor Units

133

Wiring Diagrams

MCAC-UTSM-2008-11

5. Wiring Diagrams
5.1 MUB-12HRN1 MUB-18HRN1

134

Indoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.2 MUB-24HRN1

MUB-30HRN1(1 phase)

MUB-36HRN1(1 phase)

Indoor Units

135

Wiring Diagrams

MCAC-UTSM-2008-11

5.3 MUB-30HRN1(3 phase)

MUB-36HRN1(3 phase)

136

Indoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.3 MUB-48HRN1-R MUB-60HRN1-R

Indoor Units

137

Air Velocity and Temperature Distributions

MCAC-UTSM-2008-11

6. Air Velocity and Temperature Distributions


Discharge angle 60 (CEILING)
Airflow velocity

Temperature

138

Indoor Units

MCAC-UTSM-2008-11

Air Velocity and Temperature Distributions

Discharge angle 60(FLOOR)


Temperature

Airflow velocity

Indoor Units

139

Capacity Tables

MCAC-UTSM-2008-11

7. Capacity Tables
MUB-12HRN1 Cooling
Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 3.30 2.44 0.85 3.39 2.54 0.90 3.46 2.56 0.92 3.52 2.99 0.96 Outdoor conditions (DB) 28C 3.14 2.41 0.92 3.23 2.52 0.96 3.30 2.54 0.97 3.39 2.95 1.00 35C 2.98 2.38 0.96 3.07 2.49 1.00 3.20 2.50 1.022 3.33 2.93 1.07 43C 2.85 2.39 0.99 2.88 2.42 1.05 2.98 2.44 1.07 3.07 2.86 1.11

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input 24/18C DB/WB 5.20 1.32 5.04 1.44 4.72 1.53 Outdoor conditions 7/6C DB/WB 4.20 1.13 4.00 1.22 3.76 1.32 2/1C DB/WB 3.44 0.98 3.24 1.07 3.04 1.16 -5/-6C DB/WB 3.12 0.92 3.04 0.99 2.96 1.07

20C

27C

Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW

140

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MUB-18HRN1 Cooling
Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 5.46 4.04 1.43 5.62 4.21 1.52 5.72 4.24 1.55 5.83 4.96 1.62 Outdoor conditions (DB) 28C 5.19 4.00 1.55 5.35 4.18 1.62 5.46 4.20 1.64 5.62 4.89 1.69 35C 4.93 3.94 1.62 5.09 4.12 1.69 5.30 4.13 1.726 5.51 4.85 1.81 43C 4.72 3.96 1.67 4.77 4.01 1.78 4.93 4.04 1.81 5.09 4.73 1.88

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 7.80 2.01 7.56 2.20 7.08 2.33 Outdoor conditions 7/6C DB/WB 6.30 1.73 6.00 1.86 5.64 2.01 2/1C DB/WB 5.16 1.49 4.86 1.64 4.56 1.77 -5/-6C DB/WB 4.68 1.40 4.56 1.51 4.44 1.64

20C

27C

Indoor Units

141

Capacity Tables

MCAC-UTSM-2008-11

MUB-24HRN1 Cooling
Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 7.31 5.41 2.01 7.53 5.64 2.13 7.67 5.67 2.18 7.81 6.64 2.28 Outdoor conditions (DB) 28C 6.96 5.36 2.18 7.17 5.59 2.28 7.31 5.63 2.30 7.53 6.55 2.37 35C 6.60 5.28 2.28 6.82 5.52 2.37 7.10 5.54 2.423 7.38 6.50 2.54 43C 6.32 5.31 2.35 6.39 5.37 2.50 6.60 5.41 2.54 6.82 6.34 2.64

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 9.88 2.61 9.58 2.85 8.97 3.02 Outdoor conditions 7/6C DB/WB 7.98 2.24 7.60 2.41 7.14 2.61 2/1C DB/WB 6.54 1.93 6.16 2.12 5.78 2.29 -5/-6C DB/WB 5.93 1.81 5.78 1.95 5.62 2.12

20C

27C

142

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MUB-30HRN1 (1 phase) Cooling


Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 9.27 6.86 2.64 9.54 7.16 2.80 9.72 7.19 2.86 9.90 8.42 2.99 Outdoor conditions (DB) 28C 8.82 6.79 2.86 9.09 7.09 2.99 9.27 7.14 3.02 9.54 8.30 3.12 35C 8.37 6.70 2.99 8.64 7.00 3.12 9.00 7.02 3.180 9.36 8.24 3.34 43C 8.01 6.73 3.08 8.10 6.80 3.28 8.37 6.86 3.34 8.64 8.04 3.47

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input 24/18C DB/WB 12.35 3.61 11.97 3.95 11.21 4.18 Outdoor conditions 7/6C DB/WB 9.98 3.11 9.50 3.35 8.93 3.61 2/1C DB/WB 8.17 2.68 7.70 2.94 7.22 3.18 -5/-6C DB/WB 7.41 2.51 7.22 2.71 7.03 2.94

20C

27C

Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW

Indoor Units

143

Capacity Tables

MCAC-UTSM-2008-11

MUB-30HRN1 (3 phase) Cooling


Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 9.27 6.86 2.63 9.54 7.16 2.79 9.72 7.19 2.85 9.90 8.42 2.98 Outdoor conditions (DB) 28C 8.82 6.79 2.85 9.09 7.09 2.98 9.27 7.14 3.01 9.54 8.30 3.11 35C 8.37 6.70 2.98 8.64 7.00 3.11 9.00 7.02 3.169 9.36 8.24 3.33 43C 8.01 6.73 3.07 8.10 6.80 3.26 8.37 6.86 3.33 8.64 8.04 3.45

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input 24/18C DB/WB 12.35 3.70 11.97 4.05 11.21 4.29 Outdoor conditions 7/6C DB/WB 9.98 3.19 9.50 3.43 8.93 3.70 2/1C DB/WB 8.17 2.74 7.70 3.02 7.22 3.26 -5/-6C DB/WB 7.41 2.57 7.22 2.78 7.03 3.02

20C

27C

Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW

144

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MUB-36HRN1 (1 phase) Cooling


Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.10 11.13 8.35 3.29 11.34 8.39 3.36 11.55 9.82 3.51 Outdoor conditions (DB) 28C 10.29 7.92 3.36 10.61 8.27 3.51 10.82 8.33 3.55 11.13 9.68 3.66 35C 9.77 7.81 3.51 10.08 8.16 3.66 10.50 8.19 3.737 10.92 9.61 3.92 43C 9.35 7.85 3.62 9.45 7.94 3.85 9.77 8.01 3.92 10.08 9.37 4.07

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input 24/18C DB/WB 15.60 4.63 15.12 5.06 14.16 5.36 Outdoor conditions 7/6C DB/WB 12.60 3.99 12.00 4.29 11.28 4.63 2/1C DB/WB 10.32 3.43 9.72 3.77 9.12 4.07 -5/-6C DB/WB 9.36 3.21 9.12 3.47 8.88 3.77

20C

27C

Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW

Indoor Units

145

Capacity Tables

MCAC-UTSM-2008-11

MUB-36HRN1 (3 phase) Cooling


Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 10.82 8.00 3.12 11.13 8.35 3.31 11.34 8.39 3.39 11.55 9.82 3.54 Outdoor conditions (DB) 28C 10.29 7.92 3.39 10.61 8.27 3.54 10.82 8.33 3.57 11.13 9.68 3.69 35C 9.77 7.81 3.54 10.08 8.16 3.69 10.50 8.19 3.763 10.92 9.61 3.95 43C 9.35 7.85 3.65 9.45 7.94 3.88 9.77 8.01 3.95 10.08 9.37 4.10

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input 24/18C DB/WB 15.60 4.63 15.12 5.06 14.16 5.36 Outdoor conditions 7/6C DB/WB 12.60 3.99 12.00 4.29 11.28 4.63 2/1C DB/WB 10.32 3.43 9.72 3.77 9.12 4.07 -5/-6C DB/WB 9.36 3.21 9.12 3.47 8.88 3.77

20C

27C

Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW

146

Indoor Units

MCAC-UTSM-2008-11

Capacity Tables

MUB-48HRN1-R Cooling
Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 14.42 10.67 4.26 14.84 11.13 4.51 15.12 11.19 4.62 15.40 13.09 4.82 Outdoor conditions (DB) 28C 13.72 10.56 4.62 14.14 11.03 4.82 14.42 11.10 4.87 14.84 12.91 5.03 35C 13.02 10.42 4.82 13.44 10.89 5.03 14.00 10.92 5.128 14.56 12.81 5.38 43C 12.46 10.47 4.97 12.60 10.58 5.28 13.02 10.68 5.38 13.44 12.50 5.59

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW 24/18C DB/WB 19.50 5.81 18.90 6.34 17.70 6.72 Outdoor conditions 7/6C DB/WB 15.75 5.00 15.00 5.38 14.10 5.81 2/1C DB/WB 12.90 4.30 12.15 4.73 11.40 5.11 -5/-6C DB/WB 11.70 4.03 11.40 4.35 11.10 4.73

20C

27C

Indoor Units

147

Capacity Tables

MCAC-UTSM-2008-11

MUB-60HRN1-R Cooling
Cooling Indoor Conditions (kW) TC 21/15C DB/WB SC Input TC 24/17C DB/WB SC Input TC 27/19C DB/WB SC Input TC 32/23C DB/WB SC Input 21C 16.48 12.20 4.88 16.96 12.72 5.18 17.28 12.79 5.29 17.60 14.96 5.53 Outdoor conditions (DB) 28C 15.68 12.07 5.29 16.16 12.60 5.53 16.48 12.69 5.59 16.96 14.76 5.76 35C 14.88 11.90 5.53 15.36 12.44 5.76 16.00 12.48 5.882 16.64 14.64 6.18 43C 14.24 11.96 5.71 14.40 12.10 6.06 14.88 12.20 6.18 15.36 14.28 6.41

Heating
Heating Indoor Conditions (DB) 15C (kW) TC Input TC Input TC Input 24/18C DB/WB 24.70 7.38 23.94 8.07 22.42 8.54 Outdoor conditions 7/6C DB/WB 19.95 6.36 19.00 6.84 17.86 7.38 2/1C DB/WB 16.34 5.47 15.39 6.01 14.44 6.49 -5/-6C DB/WB 14.82 5.13 14.44 5.54 14.06 6.01

20C

27C

Remark: TC : Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power ; kW

148

Indoor Units

MCAC-UTSM-2008-11

Electric Characteristics

8. Electric Characteristics
Model MUB-12HRN1 MUB-18HRN1 MUB-24HRN1 MUB-30HRN1 MUB-30HRN1 MUB-36HRN1 MUB-36HRN1 MUB-48HRN1-R Indoor Units Hz 50 50 50 50 50 50 50 50 Voltage 220-240V 220-240V 220-240V 220-240V 380V 220-240V 380V 380-415V Min. 198V 198V 198V 198V 342V 198V 342V 342V 342V Max. 254V 254V 254V 254V 418V 254V 418V 418V 418V Power Supply MCA 0.2 0.71 0.71 0.79 0.79 0.79 0.79 1.25 1.25 MFA 16 16 25 25 20 25 20 20 20 Indoor Fan Motor kW 0.025 0.055 0.055 0.08 0.08 0.08 0.08 0.059 0.059 FLA 0.145 0.57 0.57 0.63 0.63 0.63 0.63 0.39(2) 0.39(2)

MUB-60HRN1-R 50 380-415V Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A)

9. Sound Levels

Ceiling
Model MUB-12HRN1 MUB-18HRN1 MUB-24HRN1 MUB-30HRN1 (1 phase) MUB-30HRN1 (3 phase) MUB-36HRN1 (1 phase) MUB-36HRN1 (3 phase) MUB-48HRN1-R MUB-60HRN1-R Noise level H 43 43 45 45 45 45 45 47 47 M 41 41 43 43 43 43 43 45 45

Floor

L 38 38 40 40 40 40 40 42 42

Indoor Units

149

Exploded View

MCAC-UTSM-2008-11

10. Exploded View


10.1 MUB-12HRN1

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 15.2 15.3 15.4 15.5 16 17 18 19 150

Part Filter

Name

Quantity 2 2 1 2 1 2 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 Indoor Units

Evaporator ass'y Installation board Foam ass'y Foam ass'y Evaporator Left support Foam ass'y Support board Evaporator right clapboard Evaporator left clapboard Cover Display panel box Display board ass'y Manual button Air outlet ass'y Foam Drainage pan holder Drainage pan ass'y Plastic cover Motor Panel ass'y Remote controller Installation bracket Room temp sensor ass'y Temp.sensor ass'y

Grille clamp Grille Grille clamp Grille strengthening rib Volute shell Grille lock Plastic fan Motor clamp Motor clamp Volute shell Board Middle beam E-part box cover E-part box ass'y Main controller ass'y Motor capacitor Wire joint Wire joint Transformer Left cover Installation board Base ass'y Rear cover

MCAC-UTSM-2008-11

Exploded View

10.2 MUB-18HRN1

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 15.2 15.3 15.4 15.5 16 17 18 19

Part Name Filter Grille clamp Grille Grille hang Grille strengthening rib Volute shell Grille lock Plastic fan Motor clamp Motor clamp Volute shell Board Middle beam E-part box cover E-part box ass'y Main controller ass'y Motor capacitor Wire joint Wire joint Transformer Left cover Installation board Base ass'y Rear cover

Quantity 2 2 1 2 1 2 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43

Part Name Evaporator ass'y Installation board Foam ass'y Foam ass'y Evaporator Left support Foam ass'y Support board Evaporator right clapboard Evaporator left clapboard Cover Display panel box Display board ass'y Manual button Air outlet frame mount ass'y Foam Drainage pan holder Drainage pan ass'y Plastic cover Motor Panel ass'y Remote controller Installation bracket Room temp. sensor ass'y Evaporator temp. sensor ass'y

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1

Indoor Units

151

Exploded View

MCAC-UTSM-2008-11

10.3 MUB-24HRN1

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 15.2 15.3 15.4 15.5 16 17 18 19

Part Name Filter Grille clamp Grille Grille hang Grille strengthening rib Volute shell Grille lock Plastic fan Motor clamp Motor clamp Volute shell Board Middle beam E-part box cover E-part box ass'y Main controller ass'y Motor capacitor Wire joint Wire joint Transformer Left cover Installation board Base ass'y Rear cover

Quantity 2 2 1 2 1 2 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43

Part Name Evaporator ass'y Installation board Foam ass'y Foam ass'y Evaporator Left support Foam ass'y Support board Evaporator right clapboard Evaporator left clapboard Cover Display panel box Display board ass'y Manual button Air outlet frame mount ass'y Foam Drainage pan holder Drainage pan ass'y Plastic cover Motor Panel ass'y Remote controller Installation bracket Room temp. sensor ass'y Evaporator temp. sensor ass'y

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1

152

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.4 MUB-30HRN1

MUB-36HRN1(1 phase)

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 15.2 15.3 15.4 15.5 16 17 18 19

Part Filter

Name

Quantity 3 2 1 2 1 3 2 3 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Evaporator ass'y Installation board Foam ass'y Foam ass'y Evaporator Left support Foam ass'y Support board Evaporator right clapboard Evaporator left clapboard Cover Display panel box Display board ass'y Manual button Air outlet ass'y Foam Drainage pan holder Drainage pan ass'y Plastic cover Motor Panel ass'y Remote controller Installation bracket Room temp sensor ass'y Temp.sensor ass'y

Grille clamp Grille Grille clamp Grille strengthening rib Volute shell Grille lock Plastic fan Motor clamp Motor clamp Volute shell Board Middle beam E-part box cover E-part box ass'y Main controller ass'y Motor capacitor Wire joint Wire joint Transformer Left cover Installation board Base ass'y Rear cover

Indoor Units

153

Exploded View

MCAC-UTSM-2008-11

10.5 MUB-30HRN1

MUB-36HRN1(3 phase)

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 15.2 15.3 15.4 15.5 16 17 18 19

Part Filter

Name

Quantity 3 2 1 2 1 3 2 3 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Evaporator ass'y Installation board Foam ass'y Foam ass'y Evaporator Left support Foam ass'y Support board Evaporator right clapboard Evaporator left clapboard Cover Display panel box Display board ass'y Manual button Air outlet ass'y Foam Drainage pan holder Drainage pan ass'y Plastic cover Motor Panel ass'y Remote controller Installation bracket Room temp sensor ass'y Temp.sensor ass'y

Grille clamp Grille Grille clamp Grille strengthening rib Volute shell Grille lock Plastic fan Motor clamp Motor clamp Volute shell Board Middle beam E-part box cover E-part box ass'y Main controller ass'y Motor capacitor Wire joint Wire joint Transformer Left cover Installation board Base ass'y Rear cover

154

Indoor Units

MCAC-UTSM-2008-11

Exploded View

10.6 MUB-48HRN1-R

31.1

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 16 17 18 19 20

Part Name Grille ass'y Motor clamp Motor clamp Filter bracket Installation board Installation board Filter bracket Right sealed board left sealed board Pipe clamp board Cover Left cover Display board ass'y Display installation box Air outlet ass'y Display board ass'y Base ass'y Plastic fan Volute shell Motor Motor bracket

Quantity 2 2 2 2 1 1 2 1 1 1 1 1 1 1 1 1 1 4 4 2 2

No. 21 22 23 24 24.1 24.2 24.3 24.4 24.5 25 26 27 28 29 30 31 31.1 32 33 34

Part Name Volute shell Middle beam E-part box cover E-part box ass'y Main controller ass'y Motor capacitor Wire joint Wire joint Transformer Foam Top cover ass'y Drainage pan ass'y Plastic cover Foam Filter Evaporator ass'y Temp. sensor ass'y Remote controller Installation bracket Room temp. sensor ass'y

Quantity 4 1 1 1 1 2 1 1 1 2 1 1 1 2 4 1 1 1 1 1

Indoor Units

155

Exploded View

MCAC-UTSM-2008-11

10.7 MUB-60HRN1-R

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 16 17 18 19 20

Part Name Grille ass'y Motor clamp Motor clamp Filter bracket Installation board Installation board Filter bracket Right sealed board Left sealed board Pipe clamp board Cover Left cover Display board ass'y Display installation box Air outlet frame ass'y Display board ass'y Base ass'y Plastic fan Volute shell Motor Motor bracket

Quantity 2 2 2 2 1 1 2 1 1 1 1 1 1 1 1 1 1 4 4 2 2

No. 21 22 23 24 24.1 24.2 24.3 24.4 24.5 25 26 27 28 29 30 31 31.1 32 33 34

Part Name Volute shell Middle beam E-part box cover E-part box ass'y Main controller ass'y Motor capacitor Wire joint Wire joint Transformer Foam Top cover ass'y Drainage pan ass'y Plastic cover Foam Filter Evaporator ass'y Temp. sensor ass'y Remote controller Installation bracket Room temp. sensor ass'y

Quantity 4 1 1 1 1 2 1 1 1 2 1 1 1 2 4 1 1 1 1 1

156

Indoor Units

MCAC-UTSM-2008-11

Accessories

11. Accessories
Name Installation fittings 1.Hook 2.Hanging arm Shape Quantity 2 2

3. Remote controller

Remote controller & Its Holder

4. Remote controller holder 5. Mounting screw(ST2.910-C-H) 6. Alkaline dry batteries (AM4) 7. Owner's manual

1 2 2 1 1 1

Others

8. Installation manual 9. Remote controller manual

12. The Specification of Power


Type Power Phase Frequency and Voltage
2

12000-18000Btu/h 1-phase 220-240V, 50Hz 20/16 32.5 2.5 52.5 1-core shield wire 2 10.5 mm

24000-36000Btu/ h 1-phase 220-240V, 50Hz 40/25 32.5 2.5 32.5 32.5 1-core shield wire 2 10.5 mm

30000-60000Btu/ h 3-phase 380-415V, 50Hz 40/20 52.5 2.5 52.5 32.5

Circuit Breaker/ Fuse (A) Indoor Unit Power Wiring (mm ) Ground Wiring Indoor/Outdoor 2 Connecting Wiring (mm ) Outdoor Unit Power Wiring Strong Electric Signal Weak Electric Signal

Indoor Units

157

Field Wiring

MCAC-UTSM-2008-11

13. Field Wiring


MUB-12HRN1

MUB-18HRN1

158

Indoor Units

MCAC-UTSM-2008-11

Field Wiring

MUB-24HRN1

MUB-30HRN1

MUB-36HRN11 phase

Indoor Units

159

Field Wiring

MCAC-UTSM-2008-11

MUB-30HRN1

MUB-36HRN13 phase

MUB-48HRN1-R

MUB-60HRN1-R

160

Indoor Units

MCAC-UTSM-2008-11

Outdoor Units

Part 3 Outdoor Units


1. Specifications ........................................................... 162 2. Dimensions ............................................................... 167 3. Service Space ........................................................... 172 4. Piping Diagrams ....................................................... 173 5. Wiring Diagrams ....................................................... 176 6. Electric Characteristics ........................................... 182 7. Operation Limits ....................................................... 182 8. Sound Levels ............................................................ 183 9. Exploded View .......................................................... 184 10. Troubleshooting ..................................................... 191

Outdoor Units

161

Specifications

MCAC-UTSM-2008-11

1. Specifications
Model Code Power supply Max. input consumption Max. input current Starting current Model Type Brand Supplier Capacity Compressor Input Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Outdoor fan motor Brand Input Capacitor Speed Number of rows Tube pitch(a) row pitch(b) Fin spacing Outdoor coil Fin type Tube outside dia.and type Coil length height width Number of circuits Outdoor air flow Outdoor noise level (sound pressure) Dimension(WHD) Outdoor unit Packing (WHD) Net/Gross weight Refrigerant Design pressure Liquid side/ Gas side Refrigerant piping Ambient temp. Max. pipe length Max. difference in level Type Charged volume g MPa mm m m mm mm m /h dB(A) mm mm kg
3

MOU-12HN1 220075100110 V-ph-Hz W A A 220~240-1-50 1500 7.0 26 PA140X2C-4FT ROTARY MIDEA-TOSHIBA MIDEA-TOSHIBA Btu/h W A A F ml 11567 1150 5.3 29.9 Internal 35F/440-450V ESTEL OIL VG74, 480 YDK24-6F AC motor Welling W F r/min mm mm 58 2.5uF/450V 800 2 2113.37 1.5 Hydrophilic aluminium 7 Inner grooved copper tube 75550426.74 2 2100 43 838(780)547250 910575335 37/39 R410A 1120 4.4/2.6 6.4/12.7 15 8 cooling:18~43; heating:-7~24

MOUA-18HN1 220075200490 220~240-1-50 2400 10.9 53 PA225X2CS-4KU1 ROTARY MIDEA-TOSHIBA MIDEA-TOSHIBA 18697 1855 8.7 36.8 Internal 50F/440V-450V ESTER OIL VG74, 750 YDK48-6H(A) AC motor Welling 110 3F/450V 890 2 2219.05 1.4 Hydrophilic aluminium 7.94 Inner grooved copper tube 64552838.1 5 2439 48 824(762)593282 891657359 41/44 R410A 1450 4.4/2.6 6.4/12.7 25 15 cooling: 18~43; heating:-7~24

162

Outdoor Units

MCAC-UTSM-2008-11

Specifications

Model Code Power supply Max. input consumption Max. input current Starting current Model Type Brand Supplier Capacity Compressor Input Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Outdoor fan motor Brand Input Capacitor Speed Number of rows Tube pitch(a) row pitch(b) Fin spacing Outdoor coil Fin type Tube outside dia.and type Coil length height width Number of circuits Outdoor air flow Outdoor noise level (sound pressure) Dimension(WHD) Outdoor unit Packing Type Charged volume Liquid side/ Gas side Refrigerant piping Ambient temp. Max. pipe length Max. difference in level g MPa mm m m (WHD) Net/Gross weight Refrigerant Design pressure mm mm m /h dB(A) mm mm kg
3

MOUA-24HN1 220075300570 V-ph-Hz W A A 220~240-1-50 3300 15 62 PA290X3CS-4MU1 ROTARY MIDEA-TOSHIBA MIDEA-TOSHIBA Btu/h W A A F ml 24600 2430 11.4 61 Internal 50F/440V-450V ESTER OIL VG74, 950 YDK53-6Q AC motor Welling W F r/min mm mm 152.5 3F/450V 840 2 2219.05 1.4 Hydrophilic aluminium 7.94 Inner grooved copper tube 82061638.1 6 3200 55 932(852)660340 968695425 56/61 R410A 2050 4.4/2.6 9.5/15.9 25 15 cooling: 18~43; heating:-7~24

MOU-30HN1 220075400010 220~240-1-50 4620 21 97 C-SBN301H5D SCROLL SANYO SANYO 31902 3750 18.1 112 Internal 60uF/450V FV68S, 1700 YDK250-6D AC motor Welling 304 10uF5% 450V 740 1.6 2219.05 1.6 Hydrophilic aluminium 7.94 Inner grooved copper tube 72790238.1 7 5000 57 1075(990)966354 11201100435 94/104 R410A 3100 4.4/2.6 12.7/19 30 20 cooling: 18~43; heating:-7~24

Outdoor Units

163

Specifications

MCAC-UTSM-2008-11

Model Code Power supply Max. input consumption Max. input current Starting current Model Type Brand Supplier Capacity Compressor Input Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Outdoor fan motor Brand Input Capacitor Speed Number of rows Tube pitch(a) row pitch(b) Fin spacing Outdoor coil Fin type Tube outside dia.and type Coil length height width Number of circuits Outdoor air flow Outdoor noise level (sound pressure) Dimension(WHD) Outdoor unit Packing Type Charged volume Liquid side/ Gas side Refrigerant piping Ambient temp. Max. pipe length Max. difference in level g MPa mm m m (WHD) Net/Gross weight Refrigerant Design pressure mm mm m /h dB(A) mm mm kg
3

MOU-30HN1-R 220075400020 V-ph-Hz W A A 380~415-3-50 4620 7.1 61 C-SBN303H8D SCROLL SANYO SANYO(Dalian) Btu/h W A A F ml 33438 3650 6.58 48 Internal / FV68S, 1700 YDK250-6D AC motor Welling W F r/min mm mm 304 10uF5% 450V 740 1.6 2219.05 1.6 Hydrophilic aluminium 7.94 Inner grooved copper tube 72790238.1 7 5000 57 1075(990)966354 11201100435 99/104 R410A 3100 4.4/2.6 12.7/19 30 20 cooling: 18~43; heating:-7~24

MOU-36HN1 220075500670 220~240-1-50 4620 21 97 C-SBN301H5D SCROLL SANYO SANYO 31902 3750 18.1 112 Internal 60uF/450V FV68S 1700 YDK250-6D AC motor Welling 304 10uF5% 450V 740 1.6 2219.05 1.6 Hydrophilic aluminium 7.94 Inner grooved copper tube 72790238.1 7 5000 57 1075(990)966354 11201100435 99/104 R410A 3100 4.4/2.6 12.7/19 30 20 cooling: 18~43; heating:-7~24

164

Outdoor Units

MCAC-UTSM-2008-11

Specifications

Model Code Power supply Max. input consumption Max. input current Starting current Model Type Brand Supplier Capacity Compressor Input Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Outdoor fan motor Brand Input Capacitor Speed Number of rows Tube pitch(a) row pitch(b) Fin spacing Outdoor coil Fin type Tube outside dia.and type Coil length height width Number of circuits Outdoor air flow Outdoor noise level (sound pressure) Dimension(WHD) Outdoor unit Packing Type Charged volume Liquid side/ Gas side Refrigerant piping Ambient temp. Max. pipe length Max. difference in level g MPa mm m m (WHD) Net/Gross weight Refrigerant Design pressure mm mm m /h dB(A) mm mm kg
3

MOU-36HN1-R 220075500680 V-ph-Hz W A A 380~415-3-50 4620 8 61 C-SBN303H8D SCROLL SANYO SANYO(Dalian) Btu/h W A A F ml 33438 3650 6.58 48 Internal / FV68S, 1700 YDK250-6D AC motor Welling W F r/min mm mm 304 10uF5% 450V 740 1.6 2219.05 1.6 Hydrophilic aluminium 7.94 Inner grooved copper tube 72790238.1 7 5000 57 1075(990)966354 11201100435 99/104 R410A 3100 4.4/2.6 12.7/19 30 20 cooling: 18~43; heating:-7~24

MOUA-48HN1-R 220075700040 380~415-3-50 5870 10.7 42 JT160G-P8Y1 SCROLL DAIKIN DAIKIN 50941.16 4880 8.3 63 Internal / DAPHNE FVC68D, 1500 YDK65-6-1+YDK65-6F-1 AC motor Welling 171+171 4F/450V 825 2 2219.05 1.6 Hydrophilic aluminium 7.94 Inner grooved copper tube 845110038.1 8 6800 59 986(900)1167340 10321307443 93/99 R410A 3150 4.4/2.6 12.7/19 30 20 cooling: 18~43; heating:-7~24

Outdoor Units

165

Specifications

MCAC-UTSM-2008-11

Model Code Power supply Max. input consumption Max. input current Starting current Model Type Brand Supplier Capacity Compressor Input Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Outdoor fan motor Brand Input Capacitor Speed Number of rows Tube pitch(a) row pitch(b) Fin spacing Outdoor coil Fin type Tube outside dia.and type Coil length height width Number of circuits Outdoor air flow Outdoor noise level (sound pressure) Dimension(WHD) Outdoor unit Packing Type Charged volume Liquid side/ Gas side Refrigerant piping Ambient temp. Max. pipe length Max. difference in level g MPa mm m m (WHD) Net/Gross weight Refrigerant Design pressure m /h dB(A) mm mm kg
3

MOUA-60HN1-R 220075800650 V-ph-Hz W A A 380~415-3-50 7500 12.8 52 C-SBN453H8D SCROLL SANYO Dalian SANYO Compressor Co., Ltd. Btu/h W A A F ml 55956.8 5750 9.77 67 Internal / FV68S, 1700 YDK65-6-1+YDK65-6F-1 AC motor Welling W F r/min mm mm mm mm 171+171 4F/450V 825 2 2219.05 1.6 Hydrophilic aluminium 7.94 Inner grooved copper tube 845110038.1 8 6850 59.3 986(900)1167340 10321307443 93/99 R410A 3200 4.4/2.6 12.7/19 30 20 cooling: 18~43; heating:-7~24

166

Outdoor Units

MCAC-UTSM-2008-11

Dimensions

2. Dimensions
2.1 MOU-12HN1

Outdoor Units

167

Dimensions

MCAC-UTSM-2008-11

2.2 MOUA-18HN1

168

Outdoor Units

MCAC-UTSM-2008-11

Dimensions

2.3 MOUA-24HN1

Outdoor Units

169

Dimensions

MCAC-UTSM-2008-11

2.4 MOU-30HN1

MOU-30HN1-R MOU-36HN1

MOU-36HN1-R

170

Outdoor Units

MCAC-UTSM-2008-11

Dimensions

2.5 MOUA-48HN1-R

MOUA-60HN1-R

Outdoor Units

171

Service Space

MCAC-UTSM-2008-11

3. Service Space
(Wall or obstacle) Air inlet
>30cm

Obstacle
>60cm

>30cm

Air inlet

Fix with bolt Maintain channel


>60cm

>200cm

Air outlet
Necessary width

Deep foundation

600mm is necessary between 2 outdoor units

172

Outdoor Units

MCAC-UTSM-2008-11

Piping Diagrams

4. Piping Diagrams
4.1 MOU-12HN1
Outdoor unit
condenser temp. sensor

Indoor units
Check valve T3

T2 evaporator temp. sensor stop valve T1

4-way valve filter Throttle capiliary


room temp. sensor

stop valve

compressor

4.2 MOUA-18HN1
Outdoor unit
condenser temp. sensor

Indoor units
filter T3

T2 evaporator temp. sensor stop valve T1

4-way valve Throttle capiliary


room temp. sensor

stop valve

compressor

Outdoor Units

173

Piping Diagrams

MCAC-UTSM-2008-11

4.3 MOUA-24HN1
Outdoor unit
condenser temp. sensor

Indoor units
filter T3

T2 evaporator temp. sensor stop valve T1

4-way valve Throttle capiliary


room temp. sensor

stop valve

compressor

4.4 MOU-30HN1

MOU-36HN1
Outdoor unit

MOU-30HN1-R MOU-36HN1-R
Indoor units
condenser temp. sensor

Check valve T3 4-way valve T4 Throttle capiliary


ambient temp. sensor

T2 evaporator temp. sensor stop valve T1

filter

room temp. sensor

Muffle stop valve

High pressure switch T5


Discharge temp. sensor

compressor

low-pressure accumulator

Remark: For MOU-30HN1, MOU-36HN1, the T4 ambient temp. sensor is not included.

174

Outdoor Units

MCAC-UTSM-2008-11

Piping Diagrams

4.5 MOUA-48HN1-R
Outdoor unit
condenser temp. sensor

Indoor units

T3
4-way valve High pressure switch

filter

T2 evaporator temp. sensor


stop valve Throttle capiliary

T4
ambient temp. sensor

room temp. sensor

T1

stop valve
Discharge temp.sensor

Low pressure switch

compressor

low pressure receiver

4.6 MOUA-60HN1-R
Outdoor unit
condenser temp. sensor

Indoor units
filter T3

T2 evaporator temp. sensor stop valve T1

4-way valve high pressure switch

T4
ambient temp. sensor

Throttle capiliary

room temp. sensor

muffle discharge temp.sensor

low pressure switch

stop valve

compressor

low pressure receiver

Outdoor Units

175

Wiring Diagrams

MCAC-UTSM-2008-11

5. Wiring Diagrams
5.1 MOU-12HN1

176

Outdoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.2 MOUA-18HN1

Outdoor Units

177

Wiring Diagrams

MCAC-UTSM-2008-11

5.3 MOUA-24HN1

178

Outdoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5.4 MOU-30HN1

MOU-36HN1

Outdoor Units

179

Wiring Diagrams

MCAC-UTSM-2008-11

5.5 MOU-30HN1-R MOU-36HN1-R

180

Outdoor Units

MCAC-UTSM-2008-11

Wiring Diagrams

5. 6 MOUA-48HN1-R

MOUA-60HN1-R

Outdoor Units

181

Electric Characteristics

MCAC-UTSM-2008-11

6. Electric Characteristics
Model MOU-12HN1 MOUA-18HN1 MOUA-24HN1 MOU-30HN1 MOU-30HN1-R MOU-36HN1 MOU-36HN1-R MOUA-48HN1-R Outdoor Unit Hz 50 50 50 50 50 50 50 50 Voltage 220~240V 220~240V 220~240V 220~240V 380~415V 220~240V 380~415V 380~415V 380~415V Min. 198V 198V 198V 198V 342V 198V 342V 342V 342V Max. 254V 254V 254V 254V 418V 254V 418V 418V 418V Compressor MSC 29.9 36.8 61 112 48 112 48 63 67 RLA 5.3 8.7 11.4 18.1 6.58 18.1 6.58 8.3 9.77 KW 0.024 0.048 0.053 0.25 0.25 0.25 0.25 0.065+0.065 0.065+0.065 OFM FLA 0.275 0.48 0.715 1.38 1.38 1.38 1.38 0.78+0.78 0.78+0.78

MOUA-60HN1-R 50 Remark: MSC: Max. Starting Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. FLA: Full Load Amps. (A) KW: Rated Motor Output (kW)

7. Operation Limits
Operation mode Cooling operation Heating operation Outdoor temperature( ) 18~43 -7~24 Room temperature( ) 17~30 17~30

Cooling
45
Outdoor temperature( DB)
25 20
Outdoor temperature( WB)

Heating

40 35
STD

15 10 5 0 -5 -10 10 15 20 25 30 35
Indoor temperature( DB) STD

30 25 20 15 10 15 20 25 30 35
Indoor temperature( WB)

182

Outdoor Units

MCAC-UTSM-2008-11

Sound Levels

8. Sound Levels
For 12000~36000Btu/h
Outdoor Unit

For 4800060000Btu/h

Microphone

1.0m

Note: H= 0.5 height of outdoor unit

Note: The point A is in the middle of the whole outdoor panel.


Noise level dB(A) 43 48 55 57 57 57 57 59 59.3

Model MOU-12HN1 MOUA-18HN1 MOUA-24HN1 MOU-30HN1 MOU-30HN1-R MOU-36HN1 MOU-36HN1-R MOUA-48HN1-R MOUA-60HN1-R

Outdoor Units

183

Exploded View

MCAC-UTSM-2008-11

9. Exploded View
9.1 MOU-12HN1

No. 1 2 3 4 5 5.1 5.2 5.3 5.4 6 6.1 6.2 7 8 9

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 10 10.1 10.2 11 12 13 14 15 16 17 18 19 20 21 22

Part

Name

Quantity 1 1 1 1 1 1 1 6 1 1 1 1 1 1 1

Fan motor Motor bracket ass'y Rear net Condenser ass'y E-part box ass'y Wire joint,2p Wire joint,5p Compressor capacitor Motor capacitor 4-way valve ass'y 4-way valve Low pressure valve Big handle Suction pipe Valve plate

High pressure valve ass'y High pressure valve Filter ass'y Base ass'y Grille Front panel Compressor Net Clamp Right clapboard Partition board ass'y Left supporter Motor bracket Top cover Axial flow fan Temp.sensor ass'y

184

Outdoor Units

MCAC-UTSM-2008-11

Exploded View

9.2 MOUA-18HN1

5.1/ 5.2

No. 1 2 3 4 5 5.1 5.2 6 7 7.1 7.2 7.3 8 9 10 11

Part Name Motor Motor bracket ass'y Rear net Condenser ass'y High pressure valve ass'y High pressure valve Capillary Temp. sensor ass'y 4-way valve ass'y Low pressure valve 4-way valve Solenoid Right cover ass'y Drainage pan Base ass'y Compressor

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 12 13 14 15 16 17 18 18.1 18.2 18.3 18.4 18.5 19 20 21 23

Part Name Grille Front panel ass'y Valve plate Partition board ass'y Left supporter Big handle E-part box ass'y Compressor capacitor Motor capacitor Wire joint,2p Wire joint Electric installation board Rear Supporter Top cover Axial flow fan R410A

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Outdoor Units

185

Exploded View

MCAC-UTSM-2008-11

9.3 MOUA-24HN1

No. 1 2 3 4 5 6 6.1 6.2 7 7.1 7.2 7.3 7.4 8 9 10 11 12

Part Name Motor Motor bracket ass'y Rear net Condenser ass'y Condenser temp. sensor ass'y High pressure valve ass'y High pressure valve Capillary 4-way valve ass'y Solenoid 4-way valve Accumulator cylinder Low pressure valve Right cover ass'y Compressor Base ass'y Valve plate Grille

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 13 14 15 16 16.1 16.2 16.3 16.4 16.5 16.6 17 18 19 20 21 22 24

Part Name Front panel ass'y Partition board ass'y Drainage cover E-part box ass'y Compressor capacitor Wire joint Wire joint,2p Wire joint Contactor Motor capacitor Left supporter Big handle Handle Rear Supporter Top cover Axial flow fan R410A

Quantity 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1

186

Outdoor Units

MCAC-UTSM-2008-11

Exploded View

9.4 MOU-30HN1

MOU-36HN1

No. 1 2 3 4 5 6 7 8 8.1 8.2 8.3 9 10 11 11.1 11.2 11.3 12 12.1 12.2 13 14 15 16 16.1 16.2 16.3

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30.1 30.2 30.3 30.4 30.5 30.6 30.7 30.8 30.9 30.10 31 32

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1

Top cover ass'y Rear Supporter Motor bracket ass'y Fixing ring Accumulator cylinder Motor Suction pipe Condenser ass'y Condenser ass'y Input pipe ass'y Fluted pipe ass'y Rear right clapboard ass'y Front right clapboard ass'y 4-way valve ass'y Low pressure valve 4-way valve Solenoid High pressure valve ass'y High pressure valve One way valve Valve plate Base ass'y Compressor Discharge pipe ass'y Muffler Pipe joint Pressure controller

Copper nut Copper nut Sphere pad Sphere pad Temp. sensor ass'y Discharge temp sensor Compressor electric heater Front panel Front net ass'y Axial flow fan Partition board ass'y Rear net Left holder E-part box ass'y Wire joint Wire joint Electric installation board AC contactor Compressor capacitor Compressor capacitor Resistance ass'y Capacitor Wire joint Compressor relay Drainage cover Big handle

Outdoor Units

187

Exploded View

MCAC-UTSM-2008-11

9.5 MOU-30HN1-R MOU-36HN1-R

No. 1 2 3 4 5 6 7 8 8.1 8.2 8.3 9 10 11 11.1 11.2 11.3 12 12.1 12.2 13 14 15 16 16.1 16.2 16.3

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 31.1 31.2 31.3 31.4 31.5 31.6 31.7 31.8 31.9 32 33

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1

Top cover ass'y Rear Supporter Motor bracket ass'y Fixing ring Accumulator cylinder Motor Suction pipe Condenser ass'y Condenser ass'y Input pipe ass'y Fluted pipe ass'y Rear right clapboard ass'y Front right clapboard ass'y 4-way valve ass'y Low pressure valve 4-way valve Solenoid High pressure valve ass'y High pressure valve One way valve Valve plate Base ass'y Compressor Discharge pipe ass'y Muffler Pipe joint Pressure controller

Temp sensor Copper nut Copper nut Sphere pad Sphere pad Temp.sensor ass'y Discharge temp sensor Compressor electric heater Front panel Front net ass'y Axial flow fan Partition board ass'y Rear net Left holder E-part box ass'y Electric installation board E-Part box Main control board ass'y Wire joint Transformer Capacitor AC contactor Wire joint,4p Wire joint, 5p Drainage cover Big handle

188

Outdoor Units

MCAC-UTSM-2008-11

Exploded View

9.6 MOUA-48HN1-R

No. 1 2 3 3.1 3.2 4 5 6 7 8 8.1 8.2 8.3 9 10 10.1 10.2 11 11.1 12 12.1 13 14 15

Part

Name

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2

No. 16 17 18 19 20 20.1 20.2 20.3 20.4 20.5 20.6 20.7 20.8 20.9 21 22 23 24 25 26 27 28 29

Part

Name

Quantity 1 2 1 1 1 1 3 1 1 1 1 1 1 2 1 1 1 2 1 1 1 1 1

Rear supporter Motor bracket ass'y Condenser ass'y Input pipe ass'y Output pipe ass'y Top cover Partition board ass'y Big handle ass'y Rear-right panel Low pressure valve ass'y 4-way valve Solenoid Low pressure valve Valve plate High pressure valve ass'y Strainer High pressure valve Discharge pipe ass'y Pressure controller Suction pipe ass'y Pressure controller Compressor Separator Handle

Front-right panel ass'y Front net ass'y Front panel Rear-left supporting board E-part box ass'y E-Part box Wire joint Wire joint, 5p AC contactor Main control board ass'y Wire joint,4p Transformer Electric installation board Motor capacitor Base Motor Motor Axial flow fan Discharge temp sensor Temp sensor ass'y Room temp sensor ass'y Compressor electric heater Compressor wire joint ass'y

Outdoor Units

189

Exploded View

MCAC-UTSM-2008-11

9.7 MOUA-60HN1-R

No. 1 2 3 3.1 3.2 4 5 6 7 8 8.1 8.2 8.3 9 10 10.1 10.2 11 11.1 12 12.1 13 14 15 190

Part Name Rear supporter Motor bracket ass'y Condenser ass'y Input pipe ass'y Output pipe ass'y Top cover Partition board ass'y Big handle ass'y Rear-right panel Low pressure valve ass'y 4-way valve Solenoid Low pressure valve Valve plate High pressure valve ass'y Strainer High pressure valve Discharge pipe ass'y Pressure controller Suction pipe ass'y Pressure controller Compressor Separator Handle

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2

No. 16 17 18 19 20 20.1 20.2 20.3 20.4 20.5 20.6 20.7 20.8 20.9 21 22 23 24 25 26 27 28 29

Part Name Front-right panel ass'y Front net ass'y Front panel Rear-left supporting board E-part box ass'y E-Part box Wire joint Wire joint, 5p AC contactor Main control board ass'y Wire joint,4p Transformer Electric installation board Motor capacitor Base Motor Motor Axial flow fan Discharge temp sensor Temp sensor ass'y Room temp sensor ass'y Compressor electric heater Compressor wire joint ass'y

Quantity 1 2 1 1 1 1 3 1 1 1 1 1 1 2 1 1 1 2 1 1 1 1 1

Outdoor Units

MCAC-UTSM-2008-11

Troubleshooting

10. Troubleshooting
10.1. Self-diagnosis Indoor units LED indication
(1) For the Four-way cassette

During malfunction protection, digital pipe displays as follow:


No 1 2 3 4 5 6 7 Displaying contents E2 E3 E4 E5 E6 E7 E8 Malfunction or protection Indoor temperature sensor is abnormal Evaporator temperature sensor is abnormal Condenser temperature sensor is abnormal Temperature sensor error of water pump Outdoor unit malfunction EEPROM malfunction Full-water malfunction

(2) For the other types indoor unit


No. 1 2 3 4 5 6 7 8 9 10 11 Type Normal Normal Normal Normal Protection Protection Error Error Error Error Error Contents Standing-by System Off System startup LED Flashing Operation lamp flashes at 0.5Hz All lamps are off Operation lamp on Operation lamp flashes at 5Hz, Forced cooling Timer lamp on Lamps of operation, timer, Over current protection of the compressor defrosting (only fan) flashing occurs 4 times in 1h simultaneously at 5Hz. Outdoor protection (lack of phase, phase All lamps flashing at 5Hz sequence and temperature protection) Room temperature sensor checking Timer lamp flashing at 5Hz channel is abnormal Evaporator sensor checking channel is Operation lamp flashing at 5Hz abnormal Condenser sensor checking channel is Defrosting lamp flashing at 5Hz abnormal Operation lamp and timer lamp Communication of EEPROM malfunction flashing at 5Hz Water level alarm/pump sensor Alarm lamp flashes at 5Hz malfunction Remark Nothing wrong with the unit when LED indicate these contents. Whole unit is shut down. It cannot recover unless power is cut off

Recover automatically after errors are eliminated (For T3 malfunction of 5HP, cant recover automatically)

(3) LEDs for the indication of outdoor trouble (3 phase type, 14, 16kW)
Type Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Outdoor Units Contents Phase sequence Lack of phase(A,B) Lack of phase(C) Protection of Low pressure Overload of current Communication malfunction Open-circuit and short-circuit trouble of T3 Open-circuit and short-circuit trouble of T4(High discharge temperature protection) High temperature protection of condenser LED1 Flash Flash Off Flash Off Flash Off Off Flash LED2 Off Off Off Flash Off Off Flash Flash Flash LED3 Off Off Off Off Flash Flash Flash Off Flash 191

Troubleshooting

MCAC-UTSM-2008-11

10.2 Solving steps for typical malfunction


(1) For the new four-way cassette E2: Indoor temperature sensor is abnormal
E2

No Whether the resistance of the room temp. sensor is 10K Yes Replace temp. sensor

Replace the PCB

E3: Evaporator temperature sensor is abnormal


E3

No Whether the resistance of the evaporator temp. sensor is 10K Yes Replace evaporator temp. sensor

Replace the PCB

E4: Condenser temperature sensor is abnormal


E4

Whether the resistance of the condenser temp. sensor is 10K

No Replace condenser temp. sensor

Yes

Replace the PCB

192

Outdoor Units

MCAC-UTSM-2008-11

Troubleshooting

E5: Temperature sensor error of water pump


E5

No Whether the resistance of the temp. sensor is 10K Replace temp. sensor

Yes

Replace the PCB

E6: Outdoor unit malfunction


E6

Whether the outdoor unit is power on Yes

No

Check when the power is on

Measure whether the voltage of the communication lines red and black end between the indoor and outdoor unit is +5V

No

Replace the outdoor unit board

Yes

Check the indoor unit main board CN5 or replace the main control board

Yes

Replace the PCB

Outdoor Units

193

Troubleshooting

MCAC-UTSM-2008-11

E7: EEPROM malfunction


E7

EEPROM chip is broken

Yes

Replace EEPROM

No Yes Replace 9177 chip

Check whether the main control chip 9177 is broken

No

Check PCB board or replace the main control board

E8: Full-water malfunction


E8

Check whether the water-level switch is inserted well Yes

No

Insert the water-level switch well

Check whether the water-level switch is broken

Yes Replace the water-level switch

No No Check whether the water pump is normal Replace the water pump

Yes

Check PCB board or replace the main control board

194

Outdoor Units

MCAC-UTSM-2008-11

Troubleshooting

(2) For the outdoor unit a. Phase sequence error:


Phase sequence error

Change the order of two of the wires to power supply.

Switch on the unit again.

If the problem can not be solved, the outdoor PCB is defective

b. Overload of current
Overload of current

Check the current, normally Is the current in rated range? No Yes The outdoor PCB is defective Possible reason 1. Outdoor fan is defective 2. 3. 4. 5. The compressor is defective Refrigerant is over charged Air enter the refrigerant system Heat exchanger is too dirty

c. Lack of phase

Lack of phase

Check the power supply, is it 3 phase, 380-415V?

Yes Check the connection between power supply and terminal, is the voltage in outdoor terminal is 3 phase, 380-415V?

Yes

Outdoor PCB is defective

Outdoor Units

195

Troubleshooting

MCAC-UTSM-2008-11

d. Protection of pressure or temp.


Protection of pressure or temp.

Yes Is it k1 or K2 open ?

Is temp. protective switch K1 open

Is pressure protective switch K2 open

Yes

Yes

Possible reason 1. The wires is loose to K1 2. 3. 4. 5. 6. 7. Air or other gas in the refrigerant. Heat exchanger is dirty Outdoor fan or fan blade is defective Outdoor unit is bad ventilation Refrigerant is leakage K1 switch is defective

Possible reason 1. The wires is loose to K2 2. 3. 4. 5. 6. 7. Air or other gas in the refrigerant. Heat exchanger is dirty Outdoor fan or fan blade is defective Outdoor unit is bad ventilation Refrigerant is two much K2 switch is defective

e. Open-circuit and short-circuit trouble of T3


Is connection to connector of temp. sensor good? No Yes Repair connector

Check the resistance of the temp. sensor according to Annex 1

Is it the resistance is normal?

Yes

No

Indoor PCB is defective.

Replace the sensor

196

Outdoor Units

MCAC-UTSM-2008-11

Troubleshooting

f. Open-circuit and short-circuit trouble of T4


Is connection to connector of temp. sensor good?

Yes

No

Check the resistance of the temp. sensor according to Annex 1

Repair connector

Is it the resistance is normal? No

Yes Indoor PCB is defective.

Replace the sensor

g. High temperature protection of condenser


High temperature protection of condenser

Check the resistance of the temp. sensor according to Annex 1, is it normal?

Yes

No

Possible reason 1. Air or other gas in the refrigerant. 2. 3. 4. 5. 6. Heat exchanger is dirty Outdoor fan or fan blade is defective Outdoor unit is bad ventilation Refrigerant is leakage Outdoor PCB is defective

Replace the sensor

Outdoor Units

197

Troubleshooting

MCAC-UTSM-2008-11

Appendix Indoor Temp. and Pipe Temp. Sensor Resistance Value Table ( --K)

-20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

K Ohm 115.266 108.146 101.517 96.3423 89.5865 84.2190 79.3110 74.5360 70.1698 66.0898 62.2756 58.7079 56.3694 52.2438 49.3161 46.5725 44.0000 41.5878 39.8239 37.1988 35.2024 33.3269 31.5635 29.9058 28.3459 26.8778 25.4954 24.1932 22.5662 21.8094 20.7184 19.6891 18.7177 17.8005 16.9341 16.1156 15.3418 14.6181 13.9180 13.2631

20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

K Ohm 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355 6.40021 6.13059 5.87359 5.62961 5.39689 5.17519 4.96392 4.76253 4.57050 4.38736 4.21263 4.04589 3.88673 3.73476 3.58962 3.45097 3.31847 3.19183 3.07075 2.95896 2.84421 2.73823 2.63682 2.53973 2.44677

60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99

K Ohm 2.35774 2.27249 2.19073 2.11241 2.03732 1.96532 1.89627 1.83003 1.76647 1.70547 1.64691 1.59068 1.53668 1.48481 1.43498 1.38703 1.34105 1.29078 1.25423 1.21330 1.17393 1.13604 1.09958 1.06448 1.03069 0.99815 0.96681 0.93662 0.90753 0.87950 0.85248 0.82643 0.80132 0.77709 0.75373 0.73119 0.70944 0.68844 0.66818 0.64862

100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139

K Ohm 0.62973 0.61148 0.59386 0.57683 0.56038 0.54448 0.52912 0.51426 0.49989 0.48600 0.47256 0.45957 0.44699 0.43482 0.42304 0.41164 0.40060 0.38991 0.37956 0.36954 0.35982 0.35042 0.3413 0.33246 0.32390 0.31559 0.30754 0.29974 0.29216 0.28482 0.27770 0.27078 0.26408 0.25757 0.25125 0.24512 0.23916 0.23338 0.22776 0.22231

198

Outdoor Units

MCAC-UTSM-2008-11

Installation

Part 4 Installation
1. Precaution on Installation....................................... 200 2. Vacuum Dry and Leakage Checking ...................... 201 3. Additional Charge ................................................... 202 4. Water Drainage ........................................................ 203 5. Insulation Work ....................................................... 205 6. Wiring ....................................................................... 206 7. Test Operation ......................................................... 207

Installation

199

Precaution on Installation

MCAC-UTSM-2008-11

1. Precaution on Installation
1.1. Measure the necessary length of the connecting pipe, and make it by the following way. a. Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them. CAUTIONS: Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds With hands before fasten the flare nuts. Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge 6.4 9.5 12.7 15.9 19.1 Tightening torque 1516N.m (153163 kgf.cm) 2526N.m (255265kgf.cm) 3536N.m (357367kgf.cm) 4547N.m (459480 kgf.cm) 6567N.m (663684kgf.cm) Flare dimension A Min (mm) Max 8.3 12.0 15.4 18.6 22.9 8.7 12.4 15.8 19.1 23.3 Flare shape

b.

c.

The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection. Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.

1.2. Locate The Pipe a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover. b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation. c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing. 1.3. Connect the pipes. 1.4. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow. 1.5. Be sure of no leakage by checking it with leak detector or soap water. 1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage.

200

Installation

MCAC-UTSM-2008-11

Vacuum Dry and Leakage Checking

2. Vacuum Dry and Leakage Checking


2.1. Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100. Use vacuum pum p to m ake the pressure in the pipe near vacuum state, the boiling point of water falls relatively. When it falls under outdoor temperature, the moisture in the pipe will be vaporized.

2.2. Vacuum dry procedure There are two methods of vacuum dry due to different construction environment: common vacuum dry, special vacuum dry. . Common vacuum dry procedure Vacuum dry (for the first time)---connect the all-purpose detector to the inlet of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the vacuum pump should be below -755mmHg) If the pump cant achieve below -755mmHg after pumping 2 hours, moisture or leakage point will still exist in the pipe. At this time, it should be pumped 1 hour more. If the pump cant achieve -755mmHg after pumping 3 hours, please check if there are some leakage points. Vacuum placement test: place 1 hour when it achieves -755mmHg, pass if the vacuum watch shows no rising. If it rises, it shows theres moisture or leakage point. Vacuuming from liquid pipe and gas pipe at the same time. Sketch map of common vacuum dry procedure.

Installation

201

Additional Charge

MCAC-UTSM-2008-11

Special vacuum dry procedure This vacuum dry method is used in the following conditions: Theres moisture when flushing the refrigerant pipe. Rainwater may enter into the pipe. Vacuum dry for the first time 2h pumping . Vacuum destroy for the se cond time Fill nitrogen to 0.5Kgf/cm2 Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method cant dry thoroughly. So, please pay more attention to prevent water entering and forming condensation water. . Vacuum dry for the second time 1h pum ping Determinant: Pass if achieving below -755mmHg. If -755mmHg cant be achieved in 2h, repeat procedure and . . Vac uum plac ing test 1h . Sketch m ap of special vacuum dry procedure

3. Additional Charge
Caution Refrigerant cannot be charged until field wiring has been completed. Refrigerant may only be charged after performing the leak test and the vacuum pumping. When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer. Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged. Refrigerant containers shall be opened slowly. Always use protective gloves and protect your eyes when charging refrigerant. The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit
R(g) L(m) D(mm) 6.4 9.5 30g/m(L-5) 12.7 60g/m(L-5)

Less than 5m (One-way) Added Refrigerant When 11g/m(L-5) Over 5m(One-way) Remark: R(g): Additional refrigerant to be charged L(m): The length of the refrigerant pipe(one-way) D(mm): Liquid side piping diameter

202

Installation

MCAC-UTSM-2008-11

Water Drainage

4. Water Drainage
4.1. Gradient and Supporting 4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble. 4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop stand.
Diameter Hard PVC pipe 25~40mm Distance between the prop stands 1.5~2m

4.1.3. Precautions The diam eter of drainpipe should meet the drainage requirem ent at least. The drainpipe should be heat-insulated to prevent atomization. Drainpipe should be installed before installing indoor unit. After powering on, there is som e water in water-receiver plate. Please check if the drain pump can operate correctly. All connection should be firm . W ipe color on PVC pipe to note connection. Climbing, horizontal and bending conditions are prohibited. The dimension of drainpipe cant less than the connecting dimension of indoor drainpipe. Heat-insulation should be done well to prevent condensation. Indoor units with different drainage type cant share one convergent drainpipe. 4.2 Drainpipe Trap 4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap. 4.2.2. Every indoor unit needs one drainpipe trap. 4.2.3. A plug should be designed to do cleaning.

50cm 50cm

Plug

4.3 Upwards drainage(drain pump) For Four-way cassette(compact)

Installation

203

Water Drainage

MCAC-UTSM-2008-11

For Four-way cassette

4.4 Convergent drainage 4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.

4.4.3. Selecting the diameter Number of connecting indoor units Calculate drainage volumeSelect the diameter Calculate allowed volume =Total cooling capacity of indoor units(HP)2 (l/ hr) Allowed volume(lean 1/100) (l/ hr) I.D. (mm) Hard PVC 14 25 Hard PVC 1488 30 Hard PVC 88334 40 Hard PVC 175334 50 Hard PVC 334 80

Thick 3.0 3.5 4.0 4.5 6.0

4.5 Drainage test Drainage without drain pump After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly.

204

Installation

MCAC-UTSM-2008-11

Insulation Work

5. Insulation Work
5.1 Insulation material and thickness 5.1.1. Insulation material Insulation material should adopt the material which is able to endure the pipes temperature: no less than 70 in the high -pressure side, no less than 120 in the low-pressure side(For the cooling type machine, no requirements at the low-pressure side.) Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120 ) Cooling only type----Polyethylene foam (withstand above 100 )

5.1.2. Thickness choice for insulation material Insulation material thickness is as follows: Pipe diameter (mm) 6.425.4 28.638.1 Inner diameter2032 Adiabatic material thickness 10mm 15mm 6mm

Refrigerant pipe Drainage pipe 5.2 Refrigerant pipe insulation

5.2.1. Work Procedure Before laying the pipes, the non -jointing parts and non-connection parts should be heat insulated. W hen the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated 5.2.2. Insulation for non-jointing parts and non-connection parts wrong Gas pipe and liquid pipe should not be put together to insulate Insulate the gas pipe (cooling only) right Insulate the gas pipe and liquid pipe

Installation

205

Wiring

MCAC-UTSM-2008-11

For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes. 5.2.3. Insulate for the jointing area, expanding area and the flange area Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes Make sure theres no clearance in the joining part of the accessorial insulation material and local preparative insulation material.

5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part. 5.4 Note 5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test 5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. 5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes tie-in ,expand nut ) of the indoor unit

6. Wiring
Please refer to the Wiring Diagram.

206

Installation

MCAC-UTSM-2008-11

Test operation

7. Test operation
(1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points before the test operation. The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed. The refrigerant pipe system is leakage-checked. The drainage is unimpeded. The ground wiring is connected correctly. The length of the tubing and the added stow capacity of the refrigerant have been recorded. The power voltage fits the rated voltage of the air conditioner. There is no obstacle at the outlet and inlet of the outdoor and indoor units. The gas-side and liquid-side stop values are both opened. The air conditioner is pre-heated by turning on the power. (3) According to the user's requirement, install the remote controller when the remote controller's signal can reach the indoor unit smoothly. (4) Test operation Set the air conditioner under the mode of "COOLING" with the remote controller, and check the following points. Indoor unit Whether the switch on the remote controller works well. Whether the buttons on the remote controller works well. Whether the air flow louver moves normally. Whether the room temperature is adjusted well. Whether the indicator lights normally. Whether the temporary buttons works well. Whether the drainage is normal. Whether there is vibration or abnormal noise during operation. Outdoor unit Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. Whether any of the refrigerant is leaked.

Installation

207

Control

MCAC-UTSM-2008-11

Part 5 Control
1. Remote Controller ................................................. 209

208

Control

MCAC-UTSM-2008-11

Remote Controller

1. Remote Controller
1.1 R11-HG/E
Mode select button
Each time you push the button, a mode is selected in a sequence that goes from AUTO, COOL, DRY, HEAT (cooling only type without), FAN ONLY and back to AUTO.

I/O Button
Push the button to start operation, push the button again to stop operation.

Fan button
This button is used for selecting fan speed. Each time you push the button, a fan speed is selected in a sequence that goes from AUTO, LOW, MED(Some models without, HIGH, and back to AUTO.

Temperature Button

After Sliding the cover, the button and function are as follows:
Auto louver button
Push this button to swing louver. Push the button again to stop.

Timer button
Push ON-TIME timer button to set the ON timer. Push OFF-TIME timer button to set the OFF timer.

Confirmation button
Push this button to confirm ON and OFF timer settings. This button is used for setting the current time and OFF time. Adjust forwards Adjust backwords

FAN

Clock button
Push this button to set time. Push this button to cancel ON timer and OFF timer.

Lock button
When you push the LOCK button, all current settings are locked in and the remote controller does not accept any operation except that of the LOCK button. Use the lock mode when you want to prevent setting from being changed accidentally or play fully. Push the LOCK button again when you want to cancel the LOCK mode.

RESET button
When you push the RESET button, all current settings are cancelled and get into the condition of beginning. In the clock, the colon in "0:00" will flash, the mode displays "AUTO", fan speed displays "AUTO", the temperature displays "24".

Control

209

Remote Controller

MCAC-UTSM-2008-11

1.2 R05/BGE
The below is R05/BGE wireless remote controller, for Four-way cassette type and the Ceiling& floor type.

Mo de s etting Ad jus t

2 Fan s peed se ttin g

3
MOD E FAN S P EED

Adj us t

ON/OFF Horiz swin g

Ai r dire cti on setting Tim e settin g Time ON Ti me OFF Confirm b utton Economic operation

7
SWIN G

9
AIR DIRE CTI ON C LOC K

Vert. swing Reset Loc k


Co ol/heat

8 12 13

SW IN G

OK

TIME ON

10

EC O

TI ME OF F

11

14

15

16

1.3 General Function for wireless remote controller: MODEL AND SPECIFICATION
Model Rated voltage Min voltage for sending signal of CPU Effective receiving distance Operation condition R05/BGE 3.0V (2 pieces of LR03 7# batteries) 2.4V 8m~11m -5~60

210

Control

MCAC-UTSM-2008-11

Remote Controller

BUTTONS AND FUNCTION


MODE: Once pressing, running mode will be selected in the following sequence: AUTO COOL DRY HEAT FAN

NOTE: No heating mode for cool only type unit. FAN SPEED: Fan speed will be selected in following sequence once pressing this button: AUTO LOW Adjust Adjust MED HIGH

: Decrease the set temp. Keeping pressing will decrease the temp with 1 per 0.5s. : Increase the set temp. Keeping pressing will increase the temp with 1 per 0.5s.

ON/OFF: For turning on or turning off the air conditioner. AIR DIRECTION: Activate swing function of air deflector. Once pressing, air deflector will turn 6. For normal operation and better cooling and heating effect, deflector will not turn to the degree which is the state of deflector when the unit is turned off.( Only available when remote controller is used with corresponding unit.) HORIZ SWING: Activate or turn off horizontal swing function. (Only available when remote controller is used with corresponding unit, i.e. Ceiling & floor type) VERT SWING: Activate or turn off vertical swing function. (Only available when remote controller is used with corresponding unit.) CLOCK: Display the current time. (12:00 is displayed when resetting or electrifying for the first time.) Press CLOCK for 5s, icon indicating hour will flash with 0.5s. Press it again; icon indicating minute will flash with 0.5s. and are used to adjust the figure. Setting or modification is effective only by pressing OK button to make confirmation. TIME ON: For time ON setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjusting the figure to 0.00 will cancel time ON setting. TIME OFF: For time OFF setting. Once pressing this button, the time will increase by 0.5 hour. When the set time exceeds 10 hours, pressing the button will increase the time by 1 hour. Adjust the figure to 0.00 will cancel time ON setting. RESET (inner located): Press this button with a needle of 1mm to cancel the current setting and reset remote controller. LOCK (inner located): Press this button with a needle of 1mm to lock or unlock the current setting. OK: Used to confirm the time setting and modification. COOL/HEAT (inner located): Press this button with a needle of 1mm to shift mode between COOL only and COOL&HEAT. During setting, background light will be lightened. Factory default mode is COOL &HEAT. ECO: Activate or turn off economic operation mode. It is suggested to turn on this function when sleeping. (Only available when remote controller is used with corresponding unit.)

Control