1TVS013113P0300 REV1 - 1/11
Installation
Remove cover by releasing 4 off screws with a screwdriver. Wiring to overload: Connect leads provided from terminal 14 to terminal 95 and terminal A2 to terminal 96 Check operating coil voltage and frequency Remove appropriate top/bottom conduit knockouts. Mount base on a vertical surface using 4 off fixing points. To ensure environmental protection cover screws internally with supplied caps. See Figure 1. For on-site control circuit conversions see overleaf. Connect cables and ensure that all terminals are tight. When installed, set the hand/auto rest selector and adjust the current calibration to the desired value. (See AL overload settings) Replace cover and re-tighten cover screws.
Overload Selection
Order references Overload in deltaloop 0.58 FLC (A) min. max. 1.7 2.4 2.2 2.8 3.5 4.5 6.0 7.5 10.0 13.0 3.1 4.0 5.0 6.5 8.5 11.0 14.0 19.0 Approximate motor rating 400V/3PH AC3 KW hp 1.5 2.0 1.8 2.2 3.0 4.0 5.5 7.5 11.0 15.0 2.5 3.0 4.0 5.5 7.5 10.0 15.0 20.0 35 80 20
10
Terminal capacity
Supply terminals All ratings Main 6mm2 Overload < 7.5kW 11kW 15kW Main 4mm 4mm2 6mm2
2
Summary
A range of star-delta motor starters with ingress protection to IP65. Plastic enclosure.
Council of European Communities Directives: The products in this publication conform to relevant EEC Directives and EN Standards. Installation and use of such products must be carried out by competent, properly trained personnel, complying with any instructions supplied by the manufacturer. Liability for improper incorporation, assembly, use, processing, storing or handling of goods remains the sole responsibility of the individual, or company carrying out such work. This publication is for information only. Whilst every care has been taken in the preparation of this leaflet, no liability is accepted for any consequence of its use. No licence to use any patent should be assumed. All dimensions are approximate only and subject to change without notice, as are other technical features resulting from continual development and improvement.
Connection Data
Type SD40015P99 (400Vcoil)
E L1 L2 L3
Conversion Chart
Type SD23015P99 (230V coil)
E L1 L2 L3 N
A1
A2 L2 L3 13
01
02
A1 L1 L2
A2 L3 13
A1 L1 L2
A2 L3 13
A1
A2 L2 L3 13
01
02
A1 L1 L2
L1 L2 L3
L1
L1 L2 L3 N
L1
Star
01
Delta
Main
Star
01
Delta
Main
T1
T2
T3
14
VE5-1
02
T1
T2
T3
14
T1
T2
T3
14
T1
T2
T3
14
VE5-1
02
T1
T2
T3
14
T1
T2
T3
14
96
95
96
95
Overload
T1
2
Overload
T3
6
T2
4
T1
2
T2
4
T3
6
U2
V2 W2
U2
V2 W2
M 3
U1
~
U1
M 3
V1 W1
V1 W1
5 6 7 8 9 10 12 14 16 18 20 25 30 35
2.9 3.5 4.0 4.6 5.2 5.8 7.0 8.1 9.3 10.4 11.6 14.5 17.4 20.3
Note : Overload relay is fitted in the delta loop. It is therefore necessary to use the conversion chart to obtain correct overload setting for a particular motor full load current.
Circuit
Star-Delta (main contactor in Delta loop)
Supply L1 L2 L3 N
230v
Control
Supply L2 L3 N
230v
Control
400v
Control
400v
Control
Star
Delta
Main
Star
Delta
Main
Overload
Overload
Pressure switch
W2 V2 U2
W1
W2 V2 U2
W1
M 3~
V1 U1
M 3~
V1 U1
Overload Stop/Reset 96 95 8
Start 7 16 02 D 01 A2 A1
Overload Stop/Reset
Start 8 7 02 16 D 01 A2 A1
96
95
Link
15
18 02 S 01 A2
15
A1
18
02 S
01 A2
A1
A2
T
TES5 Electronic Timer
A1 14 S M 13
A2
T
TES5 Electronic Timer
A1 14 S M 13 13 A2
14
13 A2
A1
14
A1
For further information please contact your ABB Technical Helpline 02476 368500