Umm mAlQ Quwain S ndary Secon yTech hnicalScho ool

FM200 2 UtilityBuildi ingCalcu ulations


ember,2012 2 Date:Nove

Rev.0

Calculations

Umm Al-Quwain Secondary Technical School FM-200 Fire extinguishing systems: 1. FM-200 system (1) for M.V. Switchgear room: Room Length = 26 m Room width = 6.5 m Room area = 169 m Total Room volume = 169 x 5.25 = 887.25 m For using FM-200 with density of 0.6 kg/m based on 7 % concentration, taking 10% as a safety factor Total Amount of agent for the room = 887.25 x 0.6 x 1.1 = 585.6 kg For discharging at maximum time of 10 seconds: Total Agent flow rate = 585.6 / 10 = 58.56 kg/sec No of cylinders: Three cylinders, filled with 200 kg agent each. For DC Battery Room: Room Length = 4 m Room width = 2.5 m Room area = 10 m Room volume = 10 x 5.25 = 52.5 m Amount of agent for DC Battery Room = 52.5 x 0.6 x 1.1 = 34.65 kg For discharging at maximum time of 10 seconds: Agent flow rate for DC Battery room = 34.65 / 10 = 3.46556 kg/sec No of nozzles: one nozzle with 25mm diameter. For M.V. Switchgear room: Room Length = 26 m Room width = 6.5 m Room area = 159 m Room volume = 159 x 5.25 = 834.75 m Amount of agent for M.V Switchgear Room = 834.75 x 0.6 x 1.1 = 551 kg For discharging at maximum time of 10 seconds: Agent flow rate for the room = 551 / 10 = 55.1 kg/sec

November 2012, Rev.0 1 of 7

Calculations

No of nozzles: Four nozzles with 50 mm diameter each.

November 2012, Rev.0 2 of 7

Calculations

2. FM-200 system (2) for Transformers room: Room Length = 26 m Room width = 10 m Room area = 260 m Room volume = 260 x 5.25 = 1365 m For using FM-200 with density of 0.6 kg/m based on 7 % concentration, taking 10% as a safety factor Amount of agent for the room = 1365 x 0.6 x 1.1 = 900 kg For discharging at maximum time of 10 seconds: Agent flow rate for the room = 900 / 10 = 90 kg/sec No of cylinders: Four cylinders, filled with 230 kg agent each No of nozzles: Seven nozzles with 50mm diameter each.

November 2012, Rev.0 3 of 7

Calculations

November 2012, Rev.0 4 of 7

Calculations

3. FM-200 system (3) for L.V Room: Room Length = 26 m Room width = 14 m Room area = 364 m Room volume = 364 x 5.25 = 1911 m For using FM-200 with density of 0.6 kg/m based on 7 % concentration, taking 10% as a safety factor Amount of agent for the room = 1911 x 0.6 x 1.1 = 1261 kg For discharging at maximum time of 10 seconds: Agent flow rate for the room = 1261 / 10 = 126.1 kg/sec No of cylinders: Four cylinders, filled with 300 kg agent each No of nozzles: Ten nozzles with 50mm diameter each.

November 2012, Rev.0 5 of 7

Calculations

November 2012, Rev.0 6 of 7

Calculations

4. FM-200 system (3) for IT & BMS Room: Room Length = 4 m Room width = 3 m Room area = 12 m Room volume = 12 x 5.55 = 66.6 m For using FM-200 with density of 0.6 kg/m based on 7 % concentration, taking 10% as a safety factor Amount of agent for the room = 66.6 x 0.6 x 1.1 = 43.96 kg For discharging at maximum time of 10 seconds: Agent flow rate for the room = 43.96 / 10 = 4.4 kg/sec No of cylinders: one cylinder, filled with 50 kg agent each No of nozzles: one nozzle with 25 mm diameter.

November 2012, Rev.0 7 of 7