INSTRUCTION MANUAL

THE STATIC PLATE LOAD TESTER


www.hmp-online.com>information,video,animation
Calibration-
I N S T I T U T E
authorised by the
Federal Highway
Research Institute
click
HMP PDGpro
1
CONTENTS

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en

General Information
Safety instructions ...................................................................... 2
Information for Users ........................................................... 2
Symbols Used ..................................................................... 2
Legal terms of reference ...................................................... 2
Intended Use .............................................................................. 3

Plate Load Tester
Basics ......................................................................................... 4
Specification ........................................................................ 4
General structure / Components ......................................... 5
Measuring Instrument HMP PDGpro ....................................... 7
Operation ............................................................................. 7
Power Supply ....................................................................... 8
Charging of Rechargeable Batteries ................................... 8

Measuring
Prepare Measurements .............................................................. 9
Install Loading mechanism .................................................. 9
Installation of Measuring Frame (refer to Annex 1) ............. 9
Connect Devices .................................................................. 9
Measuring Procedure ............................................................... 10
Start Measurement ............................................................ 10
Error Menus ....................................................................... 12
Quit Measurement ............................................................. 12

Evaluation
Reading / Printing Measured Data ........................................... 13
Transfer the Stored Measured Data ........................................ 13
Delete Measuring Results ........................................................ 14

Options
AP 1300 Miniprinter .................................................................. 15
GPS Receiver ........................................................................... 18

Settings
Settings Measuring Instrument ................................................ 20
Display ............................................................................... 20
Device ................................................................................ 20
Printer ................................................................................. 20
Contact data ...................................................................... 20

Maintenance
Calibration ................................................................................ 21
Hotline ...................................................................................... 21

Annex 1
Plate Load Tester spare parts .................................................. 22

Annex 2
Operating Instructions Hydraulic System ................................ 23
Parts of Hydraulic System ................................................. 23
Using Hydraulic System .................................................... 23
Maintenance ...................................................................... 23

Annex 3
EC Declaration of Conformity

2
GENERAL INFORMATION

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Safety instructions

Information for Users

This instruction manual was prepared such that users can easily
become familiar with the HMP PDG Plate Load Tester, and make
use of the tester for intended applications.

Users should carefully read this instruction manual and the safety
instructions prior to using the Plate Load Tester.
Users also have to read carefully through the operating instructions
by company LUKAS for hand pump, hydraulic cylinder and quick
coupler before using the Plate Load Tester.

Follow the instructions of this instruction manual and the operating
instructions of company LUKAS without exception.


Symbols Used

Warnings and instructions are highlighted as described below:

Warning
This symbol is used in conjunction with related text to
draw user's attention to hazards and risks which may
cause failure of tester components or adversely affect
operating procedures, in case users do not take the
corresponding precautions.

Note
This symbol and the related text identify technical
requirements and provide additional information to be
taken into account by the operator to carry out the
following operations effectively and safely.



Legal terms of reference

The Plate Load Tester complies with the current state of the art and
all applicable safety regulations.

Construction and function of the Plate Load Tester meet the
requirements laid down in DIN 18134, issue 2012 Soil Testing
procedures and testing equipment Plate load test.

The Plate Load Tester meets the basic safety requirements laid
down in the EU Directives for Harmonisation referenced in the
EC Declaration of Conformity.

3
GENERAL INFORMATION

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Intended Use

The Plate Load Tester is exclusively intended for determining the
soil bearing capacity and the compaction quality of the soil referred
to DIN 18134, issue 2012 Soil Testing procedures and testing
equipment Plate load test.

Its intended use also includes:
l Compliance with the safety instructions and safety regulations
contained in this instruction manual and in the provided
operating instructions from company LUKAS for the hydraulic
components.
l Compliance with the maintenance and servicing instructions
contained in this instruction manual and in the provided
operating instructions from company LUKAS for the hydraulic
components.

Any other use or any use beyond this definition is not intended and
may cause injury to people and damage to property.
The manufacturer/supplier shall not be held liable for damages
resulting from other than the intended use. The risk shall be borne
solely by the user.

4
PLATE LOAD TESTER

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Basics

Specification

Loading mechanism
Hydraulic pump with 100 kN cylinder and 150 mm lift with high-
pressure hose of 2 m in length.
1 set of hydraulic cylinder extension pieces (plug-type connection)
1 pressure plate with magnetic holder and upper ball-and-socket
joint

Load plate
with adjustable bubble level
Diameter 300 mm
Thickness of plate 25 mm

Settlement measuring mechanism (measuring frame)
Support frame on three-point bearing, equipped with insertable and
turnable contact element (DIN 18134, Fig. 3a) and adjustable feet
Dimensions:
Length 2.320 mm
Width 570 mm
Height 420 mm
Weight 13.2 kg

Measuring of load
l Electrical load cell 50 kN, complete with thrust piece and adapter

Measuring of settlement
l Electronic dial gauge
25 mm measuring range, 0.01 mm resolution, local display unit,
IP 42

Automatic evaluation unit
l Measuring head
logging load and settlement data, interfering-immune digital
transmission to measuring instrument
l Measuring instrument
data logger for load and settlement data with automatic
processing and evaluation facilities as well as storage capability
for 200 tests
Comprising:
- Measuring instrument for data logging, storage and evaluation
with comfortable user interface
- LCD graphic display screen 65x65 mm
- Accumulator for 12 hours of autonomous operation,
rechargeable from mains or vehicle adapter
l Miniprinter to print data and pressure settling lines on the site
(optional)
l Aluminium case for measuring instruments
Dimensions: 460 x 340 x 210 mm
Weight: 8 kg
5
PLATE LOAD TESTER

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
General structure / Components




Picture 1 (refer to Annex 1)
Loading mechanism
1 Ball-and-socket joint with magnetic holder
2 Extension pieces
3 Hydraulic cylinder
4 Thrust piece
5 Load cell
6 Measuring tunnel
7 Load plate with bubble level
8 Hydraulic pump









Picture 2
Settlement measuring mechanism (measuring frame)
1 Extension arm with measuring finger
2 Traverse
3 Measuring frame
4 Measuring head
5 Dial gauge
6 Bubble level





Picture 3
Electronic dial gauge
1 Dial gauge
2 Dial gauge cable










I
I

I
Picture 1

Picture 3
Picture 2
I



6
PLATE LOAD TESTER

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en

Picture 4
Measuring case
1 Measuring instrument
2 Electrical load cell
3 Electronic dial gauge
4 GPS receiver (optional)
5 Measuring head
6 Printer (optional)







Picture 5
Measuring instrument
1 USB port
2 GPS port
3 Printer port
4 LCD graphic display
5 Measuring cable outlet
6 Function keys



Picture 5
Enter
Magdeburger Prfgertebau GmbH
Service: +49(0)391 2514666
www.hmp-online.com
HMP PDG
5
6
3
4
1
2
Picture 4
3
2
4
6
1
5
7
PLATE LOAD TESTER

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Measuring Instrument HMP PDGpro

Operation

The measuring instrument HMP PDGpro can be operated easily
and intuitively by means of the function keys.


Key functions

Switch on / off measuring instrument

Select forward / upward

Select backward / downward

Confirm selection / Start action


Overview menu functions

Measuring Taking measurement
Measured data Read/Print
USB
Delete
Back
Settings Display Date
Time
Language
Contrast
Illumination
Back
Device Meas. range
GPS
Unit
Graphics
Calibr. date
Back
Printer Print head
Date/time
Graphics
Contact data
Back
Back

By confirming the menu item Back you always come back to the
previous menu.



Enter
8
PLATE LOAD TESTER

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Power Supply

The measuring instrument HMP PDGpro is provided by 4 NiMH
rechargeable batteries, which are located within the battery
compartment on the backside. These rechargeable batteries can
be charged by means of the charger and the adapter cable of
measurement instrument ( Charging of Rechargeable Batteries).
In emergencies measuring instrument can also be provided by
4 AA batteries.



Charging of Rechargeable Batteries

In case that nonrechargeable batteries are used in the
device, the charger must not be connected, because
otherwise the device could be damaged.

In case that the rechargeable batteries voltage of the measuring
instrument falls below the required minimum voltage, an information
appears on the display and the rechargeable batteries have to be
charged.

The rechargeable batteries should be charged only by means of
the supplied power pack charger and adapter cable of measuring
instrument. The power pack charger can be connected to a 100
240 V / 50 60 Hz mains supply or, by means of an adapter cable,
to a 12 24 V car battery. The adapter cables are included in the
scope of supply, and are housed in the carrying case. The power
pack charger is housed in the carrying case beneath the measuring
instrument.

Picture 6
1 Power pack charger
2 Cable of measuring instrument
3 Adapter cable of measuring instrument
4 Adapter cable for car battery

B Connect the adapter cable of measuring instrument to the cable
of measuring instrument and to the cable of power pack charger.
B Connect the power pack charger to the mains supply.
B After completion of the charging procedure disconnect the
charger from the electricity grid.

The supplied power pack charger is designed for two modes of
operation indicated by LEDs of different colour, refer to passage
Miniprinter AP 1300 / Charging of power pack on page 16.



Picture 6




9
MEASURING

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Prepare Measurements

Install Loading mechanism

B Prepare the test site in compliance with the requirements of
DIN 18 134, issue 2012.
B Place the load plate on the test site.
The opening of the measuring tunnel points into the direction
from which the measuring finger of the measuring frame is
inserted.
B Mount the load cell onto the pin of the load plate and the thrust
piece onto the load cell.
B Attach the hydraulic cylinder to the pin of the thrust piece.
B Mount the ball-and-socket joint with magnetic holder to the
loading vehicle.
Use the extension pieces to adjust height differences.


Installation of Measuring Frame
(refer to Annex 1)

B Mount the traverse (2) to the longitudinal beam of the measuring
frame (3) and align with height adjustment (star grips).
B Remove the extension arm (1) from the bracket, insert it into the
measuring frame and fix it by means of the 2 star grips.
B Insert the measuring finger into the measuring tunnel until the
relevant mark is reached, and align horizontally by using the
circular bubble.
B Place the dial gauge in the dial gauge bracket of the measuring
frame and make settings it as appropriate (set to zero).


Connect Devices

Position measuring head
B Mount the measuring head to the traverse (magnetic fixture).

Connect the load cell
B Connect the load cell cable to the measuring head outlet labeled
Force.

Connect the dial gauge (used for distance measuring)
B Connect the dial gauge cable to the dial gauge.
B Connect the dial gauge cable to the measuring head outlet
labeled Distance.

Connect measuring instrument
B Connect the cable of measuring instrument to the measuring
head.



10
MEASURING

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Measuring Procedure

For theoretical foundations of the measuring process please refer
to DIN 18134, issue 2012.

Start Measurement

B Press the key to switch on the measuring instrument.
On the LCD display appears the main menu (on the left) incl.
device type and serial number (xxxx), the individual menu
items and the stress state of the measuring device batteries.
Optionally appears a hint regarding the GPS device and/or
charge state of the printer rechargeable batteries.

Before starting the measurement the desired measuring
range has to be chosen within the measuring instrument
( page 20).

In case that the rechargeable batteries voltage of the
measuring instrument falls below the required minimum
voltage, the hint meas. dev. charge appears ( page 8).

If the note printer charge occurs on the display, the
printer has to be charged before using to avoid a deep
discharge of the power pack (Charging of power pack
page 15).

B Press the key to acknowledge the Measuring mode at the
basic menu.
A note for logging GPS Data and/or the last calibration date
optionally appear on the LCD display (dependent on the
settings of the measuring instrument).
B .Acknowledge optionally the note for logging GPS data. It is not
required to acknowledge the last calibration date.
The menu shown on the left is displayed on the screen:
Number of the current measuring series and the current
measuring range (xxx xxx)
Number of the current measuring point
Compression #.#### MN/m
Settlement #.## mm
These values result from weight of testing equipment.
Measuring is not possible in case of full memory. A
corresponding note appears.

To continue measuring stored series may be removed
(e.g. by transferring to the USB-Stick or the PC or
printing) and subsequently deleted to provide the device
with new storage capacity.

It is recommended to transfer the test series and
measurement results stored in the measuring instrument
regularly onto the provided USB-Stick or to the PC
( page 13/13) and to delete afterwards the data in the
measuring instrument ( Seite 14).
In this way the transference time will be shortened and
multiple data transfer avoided.


Enter
meas. point: 01
measurement XXX XXX
reset data
MN/m
mm
0.0049
0.52
meas. dev.
measuring
measured data
settings
HMP PDGpro XXXX
printer
GPS ready
11
MEASURING

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Value 1
B Acknowledge reset data by pressing the key to tare the
displayed values.
The values 0.0000 MN/m for compression and 0.00 mm for
settlement appear on the display. By that offset values, if any,
are cleared.

B Acknowledge reset gauge by pressing the key after
approaching the required preload, according to DIN 18134,
issue 2012, to set the displayed value for the settlement to zero.
The start value for the pressing and the zero value for the
settlement appear on the LCD display. These values are
stored as first measured values.
The local display on the dial gauge remains unaffected by this
zero setting.

Please refer to DIN 18 134, issue 2012 for the required
number of measurements and set values to perform.
Set values according to DIN 18 134, issue 2012 are stored
on the measuring device as orientation for the examiner,
for load plates with diameter of 300 mm.
If the measuring range 300 is selected, the specific set
values are displayed on the screen.

Perform Measurement
B Approach the set point with the hydraulic pump.
(Operating Instructions Hydraulic System refer to Annex 2,
page 23.)
The measured value for compression and settlement appears
on the display.
The number of the current measuring series and the current
measuring range, the number of the current measuring point
and also the nominal value for the pressing (setpoint) are
displayed.
B Accept the value after the required waiting time by pressing the
key.
The Values by pressing key are frozen in the display.
B By means of the selection keys it can be switched
between the mode save, the mode delete and the mode
quit?.

B Press the key to acknowledge Store or Delete of the
current (frozen) measuring value.
The current measured values are displayed on the screen.

Follow the procedure described above for any further set values.


Enter
Enter
Enter
Enter
Enter
meas. point: 01
measurement XXX XXX
reset gauge
MN/m
mm
0.0100
0.00
meas. point: 02
setpoint: 0,08
Wert halten
MN/m
mm
0.0831
1.16
measurement XXX XXX
12
MEASURING

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Error Menus

The measuring instrument provides instructions to monitor the
measuring procedure which pop up as an error report before
measurement or during the measurement.

The following error reports might appear before the measurement:

Error report Error cause
Force error no connection between load cell and
measuring head
Gauge error no connection between dial gauge and
measuring head or dial gauge is not
switched on
no
Communication
no connection between measuring
instrument and measuring head

B Check/establish the connections.
B Restart the measuring process by pressing the key, as soon
as the connections are correct.


The following error reports might appear during the measurement:

Error report Error cause
Compression too
small
The value for compression falls below the
required minimum value for compression
according to DIN 18134, issue 2012.

B Press the key.
B Continue measurement.


Quit Measurement

All required measurements completed, the measuring procedure
can be terminated.

B Quit measuring by pressing the key after storing of last
measuring value.
The menu shown on the left is displayed on the screen.
B In order to return to the last measuring value and to continue the
measurement choose no and confirm.
B In order to quit the measurement choose yes and confirm.

Displaying results
After acknowledgement of quit measuring, measuring series will be
finished.
The time of the start and the end of the measurement, the
Values of E
V1,
E
V2
and the ratio E
V2
/E
V1
are displayed on the
screen.

After completing one measurement series it is possible to print out
the current measurement row (only devices with printer) and also to
display the curve data (pressure settling lines) and the measured
data.
Enter
Enter
Enter
quit measurement?
no
measurement XXX XXX
measurement xxx
23.04.2012 08:47
23.04.2012 08:59
Ev1= 94.98MN/m
EV2=241.99MN/m
EV1/EV2= 2.55
print
measurement 1
print
13
EVALUATION

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Reading / Printing Measured Data

The in the measuring instrument stored test series and -results can
be displayed via menu item Read/Print on the LCD-screen (all
types of measuring instrument) and they can be printed out (only
devices with printer).

Prior to using the AP1300 miniprinter read the instruction
manual furnished with the printer and follow the
instructions given for putting into operation and for
handling.

B Choose and confirm the desired test series.
The values of the chosen test series are displayed on the
LCD-screen.

By pressing the keys, the following functions can be used
(depending on the device settings):

l Print: Printing the current test series
l Curve data: Displaying the settlement curves
l Measurements: Displaying the values for the individual
measuring points
l Evaluation: Displaying the test series number, the time of
the start and the end of the measurement, the
values for E
V1
and E
V2
and also the ratio
E
V2
/E
V1

l Back: Return to the previous menu



Transfer the Stored Measured Data

The in the measuring instrument stored test series and results can
be transferred via menu item USB to the supplied USB stick or to
PC.


Data transfer measuring instrument USB stick

B Connect the USB stick to the measuring instrument.
B Choose transfer mode Device USB stick and confirm by
pressing .
On the LCD display appears the inquiry USB stick
connected?
B Confirm this inquiry by pressing the key.
The data are being copied to the USB stick.
After completion of data transfer the measuring instrument
switches off automatically.

To transfer the data from the USB stick to the PC see Protocol
software for the Plate Load Tester HMP PDGpro.

Enter
Enter
meas. dev.
read/print
USB
delete
back
HMP PDGpro XXXX
printer
No. date time Ev2
2 23.04./09:40 241
3 ./10:24 234
4 ./11:34 228
5 25.04./08:52 225
6 ./12:54 236
7 ./14:07 235
8 ./14:45 240
9 26.04./13:21 237
10 26.04./14:27 232
page forward
page back
back
23.04
23.04
25.04
25.04
25.04
1 08.04./09:29 233
meas. dev.
read/print
delete
back
USB
HMP PDGpro XXXX
printer
meas. dev.
device->USBstick
device->PC
back
HMP PDGpro XXXX
printer
14
EVALUATION

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Data transfer measuring instrument PC

B Connect measuring instrument and PC via the supplied USB
cable.

B Choose transfer mode Device PC and confirm by
pressing .
On the LCD display appears the inquiry PC connected?

B Confirm the inquiry by pressing the key.
The measuring instrument works now just like removable
media.

B After completion of data transfer to PC remove the removable
media and switch off the measuring instrument.

To transfer data from measuring instrument to PC see Protocol
software for the Plate Load Tester HMP PDGpro.



Delete Measuring Results

The test series and results stored in measuring instrument can be
deleted via menu item Delete.

B Confirm menu item Delete by pressing key.
On the LCD screen is displayed the choice
Delete all measurements resp. not delete.

B Confirm Delete all measurements by pressing the key.
All measurements will be deleted.

Stored series cannot be deleted individually.



Enter
Enter
Enter
Enter
maes. dev.
device->USBStick
back
device->PC
HMP PDGpro XXXX
printer
read/print
USB
back
delete
HMP PDGpro XXXX
meas. dev.
printer
15
OPTIONS

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
AP 1300 Miniprinter

Included in the HMP PDGpro scope of supply is an AP 1300
miniprinter (optional).


Power supply
The printer can be operated independent of a power supply unit,
and is powered by a 1.8 Ah NiMH power pack housed in the
printer. Thus, the printer can be carried from job to job.


Safety

l The NiMH power pack is provided with an internal fuse
unit. However, a short-circuit may occur when the NiMH
power pack gets into contact with metallic items.
l The power pack must not be opened; otherwise it may
leak out or a short-circuit may occur.
l Before you remove or replace the power pack,
disconnect it from the external power pack charger.

The power pack has to be charged only by means of the supplied
power pack charger. The power pack charger can be connected to
a 100 240 V / 50 60 Hz mains supply or, by means of an
adapter cable, to a 12 24 V car battery. The adapter cable is
included in the scope of supply, and is housed in the carrying case.
The AP1300 printer is shipped with a connected and fully loaded
power pack.

l When the printer is used for the first time after a lengthy
period or has been standing idle for a lengthy period,
recharge the power pack prior to use.
l In the event of malfunction the printer may only be
opened by authorised personnel.


Charging of power pack

l For charging the power pack it is only allowed to use the
supplied power pack charger.
l Use the power pack charger only indoors. Disconnect the
device from the mains if it is not used. Do not operate the
device in case of damage to the housing or the mains
plug.
l Only charge nickel/metal hydride power packs; its use for
charging other batteries may involve an explosion
hazard.
l Do not open the power pack charger.
16
OPTIONS

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
B Connect the power pack charger to the Power Supply
connection of the printer.
B Connect the power pack charger to the mains supply.
B Disconnect the power pack charger from the mains supply when
charging of power pack has been finished.

The supplied power pack charger is designed for two modes of
operation indicated by LEDs of different colour.
l Red LED (flashing):
Indicates the proper contact of the power pack during the test
phase (about 10 s);
Indicates that the power pack has not been properly
connected to the correct pole;
Indicates a defect power pack or an incorrect number of cells;
l Red LED (steady):
Indicates the charging process of the power pack.
l Green LED (steady):
Power pack is charged.

When the power pack has to charge again, the power
pack charger has to disconnect from the mains supply at
first. New charging can start when the two LED (red and
green) have been go out (after 10-15 seconds).


Front panel of printer

1 Paper feed Single-line paper feed:
Press the key for a short interval, and
release.
Multi-line paper feed:
Hold down this key until the desired length
of paper is reached.

2 LED Signals READY
LED off:
The printer is in the power-saving mode.
Power pack is discharged.
Charging of power pack has been finished.
Green LED (steady):
Printer is active.
Green flashing LED:
Paper out.
Green orange flashing LED:
Power pack is charged (trickle charging).
Orange flashing LED:
Power pack is charged (fast charging).
Red green flashing LED:
Power pack voltage is too low.

3 Paper compartment opener

The miniprinter AP 1300 switches on and off
automatically. It isnt necessary to switch it on or off
manual.
17
OPTIONS

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Insert paper roll
B Push the paper compartment opener to the front until the printer
lid opens (1).
B Unwind a few centimetres of the new roll and load the paper roll
into the compartment such that the paper will unwind from below
(2).
B Close the printer lid (3).
B Press the paper feed key to check the correct paper movement.
B Rapidly tear off excessive paper using the cutting edge.

The AP1300 miniprinter is provided with sensors to detect lacking
paper or opened paper compartment. A sensor activated, the
printer switches to the storage mode; all data transmitted to the
printer are preserved. Printing is continued immediately as soon as
the defect has been removed.

It is recommendable to use original paper role for thermo
printer only.



Malfunction

Printer fails to start printing:
l Connection correct? Check connections.
l Has the printer automatically switched on and is the LED on?
l Is the power pack discharged? Charge the printer before use.


18
OPTIONS

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
GPS Receiver

The Plate Load Tester HMP PDGpro is optionally equipped with an
external highly sensitive GPS receiver to determine the measuring
position.

The coordinates are captured fast and exactly, because of newest
technology, are transferred to the measuring instrument
HMP PDGpro, are associated to the corresponding test and saved
in the device.

Basis for the determination of the measuring position with
the GPS receiver is a measuring location, where this
device has free reception.


Operation GPS Receiver

1 Power on/off
2 LED
3 Port measuring instrument

The operation state is indicated by LED (2):
LED off:
- GPS receiver is switched off.
- Batteries empty.
Green LED steady:
- GPS receiver is switched on.
- Position not yet determined or no reception.
Green LED flashing:
- GPS active (position is determined).
Green LED unsteady:
- Batteries too low (not possible to determine the position).

In case the batteries of the GPS receiver are too low, the
request GPS Batt. change is displayed.


Power supply / Changing Batteries

The GPS receiver is powered by 2 pieces of LR03 batteries.

The scope of delivery includes 2 spare batteries and a screwdriver
suitable for battery changing.

In case that the batteries of the GPS receiver are empty or too low,
the batteries have to be replaced as follows:
B Loosen the screw of the battery box cover on the back side of
the device.
B Remove the battery box cover.
B Replace old batteries by new ones (pay attention to the polarity).
B Insert the battery box cover.
B Tighten the screw of the battery box cover.
HMP GPS
Service:
+49(0)391 2514666
www.hmp-online.com
on
off
on
off
active
1
3
2
meas. dev.
measuring
measured data
settings
HMP PDGpro XXXX
printer
GPS Batt. change
19
OPTIONS

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Use GPS Receiver

Should the GPS receiver be used, is to be proceeded as follows:
B Switch on the GPS receiver.
Initialization and determination of the position
(lasts at least 1 minute).
B Wait, until the position is determined and the LED flashes green.
B Press the key to switch on the measuring instrument.
At the bottom of the display the GPS status appears.
B If the GPS status is not displayed, the GPS function can be
activated in the menu settings under menu item device ().
B Conduct the measurement corresponding to instruction manual.

After acknowledgement the Measuring mode the coordinates are
submitted from the GPS receiver to the measuring instrument and
associated to the series of measurement. The coordinates are
automatically saved when storing the measuring results.

For saving batteries energy turn off the GPS receiver
during disuse or after transmission of the coordinates to
the measuring instrument.

When printing out the measuring results via thermal printer, the
position coordinates are automatically added.
The measuring results and corresponding coordinates can be
printed out immediately at the site or can be transferred to the PC
for subsequent processing.

If the GPS receiver is not being used, prior to measurement the
GPS function of the measuring instrument has to be deactivated.

If in the measuring instrument the GPS function is
activated and the GPS receiver is not connected or not
ready, the note No GPS-Position appears. Now the
measuring process can be aborted or continued without
the acquisition of GPS-data.



HMP PDGpro XXXX
meas. range 300
unit MN/m
graphics
calibr. date x
back

GPS
20
SETTINGS

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Settings Measuring Instrument

Display

Under the menu item Display the following settings can be carried
out.

l Date set date
l Time set time
l Language choose language
l Contrast set contrast display
l Illumination set backlight display
l Back Return to previous menu


Device

Under the menu item Device the following settings can be carried
out for device configuration:

l Meas. range (300/600/ set measuring range
762/force) ( of loadplate or force)
l GPS ( / x) activate / deactivate GPS
l Unit (MN/m / MPa) set unit
l Graphics () show curve
l Calibr. date ( / x) show / do not show calibration
date on startup screen
l Back return to previous menu


Printer

Under the menu item Printer the following settings can be carried
out for printer configuration:

l Print head () print out protocol head active.
l Date / Time ( / x) print out date / time
l Graphics ( / x) print out curve
l Contact data ( / x) print out company data (optional)
l Back return to previous menu


Contact data

In particular, these are the company details of the device owner,
which can optionally be printed out in the protocol head.
The company details are not programmed by default. This requires
a file with the desired data, which could be provided on request
and would have to be installed on the measuring instrument.
date
time
language
contrast
Illumination
back
HMP PDGpro XXXX
HMP PDGpro XXXX
meas. range 300
GPS
unit MN/m
graphics
calibr. date x
back
x

HMP PDGpro XXXX


print head
date/time
graphics
back

contact data x
21
MAINTENANCE

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Calibration

In terms of DIN 18 134 re-calibration is required at least
annually.

HMP Magdeburger Prfgertebau GmbH has calibrated
instrumentation used to conduct force and distance calibrations. In
addition, necessary repairs may be carried out.


Hotline

HMP Magdeburger Prfgertebau GmbH
Blstringer Strae 6
D-39126 Magdeburg

Tel.: (03 91) 2 51 46 66
(03 91) 2 51 46 67
Fax: (03 91) 2 51 46 68
E-Mail: info@hmp-online.de
22
ANNEX 1

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Plate Load Tester spare parts


H
M
P
B

l
s
t
r
i
n
g
e
r


S
t
r
.

6
3
9
1
2
6



M
a
g
d
e
b
u
r
g
N
a
m
e
B
e
n
e
n
n
u
n
g
D
a
t
u
m
D
a
t
u
m
B
e
a
r
b
.
G
e
p
r
.
B
u
c
h
-
s
t
a
b
e
Z
e
i
c
h
n
u
n
g
s
n
u
m
m
e
r
z
u
l

s
s
.

A
b
w
.

f

r

M
a
s
s
e
o
h
n
e

T
o
l
e
r
a
n
z
a
n
g
a
b
e
H
a
l
b
z
e
u
g

/

W
e
r
k
s
t
o
f
f
2
0
0
4

n
d
e
r
u
n
g
M
a
s
s
t
a
b
H
i
e
t
s
c
h
o
l
d
P
l
a
t
t
e
n
d
r
u
c
k
g
e
r
a
e
t
P
D
G

1
0
0
0
2
5
.
0
8
.
3
6
4
5
2
1
N
r
.
B
e
z
e
i
c
h
n
u
n
g
1
A
u
s
l
e
g
e
r

m
i
t

M
e
s
s
f
i
n
g
e
r
6
H
a
n
d
p
u
m
p
e
5
D
r
u
c
k
z
y
l
i
n
d
e
r
4
L
a
s
t
p
l
a
t
t
e
3
M
e
s
s
g
e
s
t
e
l
l
T
r
a
v
e
r
s
e
7
7
M
e
s
s
k
o
f
f
e
r
23
ANNEX 2

Service +49(0)391 2514666 07/2013 Instruction Manual HMP PDGpro en
Operating Instructions Hydraulic System

Parts of Hydraulic System

Hydraulic system comprises of parts by LUKAS Company:
l Hand pump ZPH 1A/1 PN 500
l Hydraulic cylinder LZM 10/160 PN 500
l Hydraulic hose DN6PN700-2000RT
l Quick coupler
The delivery includes operating instructions by LUKAS Company for
hand pump, hydraulic cylinder and quick coupler.

Hydraulic system was installed complete and vented
before delivery.


Using Hydraulic System

Before using the hydraulic system users have to read the
operating instructions by LUKAS Company.
Users must observe all safety instructions and warnings, to
avoid bodily injuries and damages of the system.

The pump lever must be locked for transport.

Advancing cylinder
B Close the drain valve on the pump by turning the hand wheel
clockwise (to the right) to advance the cylinder.
B Unlock the pump lever and move it up and down to load
pressure.

Also read the operating instructions of hand pump and
hydraulic cylinder by LUKAS Company to get more
information about advancing and retracting cylinder.

Retracting cylinder
B Open the drain valve on the pump by turning the hand wheel
against clockwise (to the left) to release pressure or retract the
cylinder. Turn the hand wheel slowly to have control over the
load.

Release the pressure always slowly to have control over
the load.


Maintenance

Information and tips with regard to
l maintenance
l adding oil to the pump, oil recommendations
l venting the cylinder
l troubleshooting
read in operating instructions by LUKAS Company.